PRS

250-700-1800
.....
AC TO DC STANDBY POWER SYSTEM
250W TO 21,6KW
.....
THE COMPLETE RANGE
OF SMALL TO MEDIUM SIZE
POWER RACK SYSTEMS (PRS)

Eltek is one of the world´s leading The range of rectifier modules provides
producers of Power Supply cost effective power solutions for all needs
in the range from 250W to 21,6kW.
Systems for the Telecommunicat-
ions industry. The product design MODULAR DESIGN
and technical solutions are based The modular design provides flexible
on more than twenty five years distribution solutions and system features
according to customer requirements, and
experience in system development
facilitates system expansion.
and manufacturing. Using the
latest technology, Eltek achieves Modern manufacturing and servicing facilities
the highest quality standards for in Europe and Asia ensure prompt delivery of
quality products.
standby power systems.
COMPACT SOLUTIONS
The benefits are: The innovative design of the Power Rack
.........
System provides an optimum and compact
Modular design solution according to the need for output
.........
power (W), autonomy (Ah) and
Complete power range distribution. All systems and modules are
.........
convection cooled.
250 W to 21,6 kW
.........
EASY INSTALLATION
Total flexibility
......... All components have full front access ideal
for ease of installation and maintenance.
High power density
......... The rectifier modules are «Hot Plug In»
optimising the service time and mini-
High reliability and quality
......... mising the mean time to repair.
High efficiency
.........
Easy installation
.........
Eltek offers a complete power range from
Easy maintenance 250W to 21,6kW.
.........
World-wide sales and support 250 700 700/1800
.........
Series
1800
21,6kW

Series
700
21,0kW

Series
250

250 3000 8000 10000

1,5 kW 5,0 kW
ALARM MONITORING AND
SYSTEM CONTROL
The Power Rack System is either
controlled by the Alarm module AL 1000
or the more sophisticated AL 175 NT
giving detailed failure reports and system
battery tests.

The AL 175 NT advanced control and


monitoring unit provides battery
surveillance and protection optimizing the
battery life-time. The unit allows total
system remote control.
Feasabilities AL1000 AL175NT
The AL 1000 alarm monitoring and
control unit provides complete monitoring Alarm Monitoring 3xLED’s and 2xLED’s and
of the system with all necessary alarms. 3-char. display 32-char. display
Operation 3 key pads and 3 key pads
For high power requirements (>21.6kW), Remote control PC/Modem(RS232)
we refer to our 5000 series. Communication speed - 9600 baud
Current and Voltage Output Monitoring display display
Voltage level adjustment
Temperature compensated charging
Boost charging
Battery test
Low Voltage Disconnection
Storage of alarm messages -
Potentional free output relays 2 6
Test Operation of Relays -
Modem Call-Back -

Basic Alarms:
Mains Alarm
High/low battery voltage alarm
Module failure
Load fuse alarm
Battery fuse alarm
Common alarm
Battery test failure
Symmetry alarm -
Temperature alarm -
PRODUCT RANGE
SERIES 250

Wall mounted Wall mounted Wall mounted Floor mounted


PRSV 250 - 1.5kW PRSV 250 - 1.5kW PRSV 250 - 3.0kW PRSB 250 - 3.0kW
external batteries 42Ah at 48V DC external batteries 200Ah at 48Vdc
System Configuration
# Rectifier modules up to 6 SMPS 250 up to 6 SMPS 250 up to 12 SMPS 250 up to 12 SMPS 250
Battery capacity none 2 shelves none 2 shelves/drawers
Load circuit breakers, 2-50 A up to 27 ways up to 9 ways up to 27 ways
Load / Battery fuses up to 6 x 160A 1 batt. CB up to 6 x 160A blade fuses
Low voltage disconnect Battery and/or load disconnect
Mains CB’s optional
Mains input configurations 230V AC single phase
Electrical data - Mains input
Input voltage, module 230 VAC +/- 20% single phase
Line frequency 40 - 400Hz
Input current <2.17A RMS 230VAC per rectifier module at full load
Power factor > 0.6
Efficiency > 90%
Protection (rectifier module) none
Electrical data - DC output
Output voltage 24V / 48V DC: 23 - 29VDC / 45 - 58VDC adjustable
Output voltage regulation +/- 0.5% from 0 - 100% load
Dynamic response +/- 1.0% < 10ms response time
Output current (per module) 5A at 48V DC and 10A at 24V DC per rectifier module
Active current share Current share by common voltage referance
Hold-up time >10 ms at 54V/ 27 DC and full load
Ripple <100mV pp
Psophometric noise <2mV RMS (according to CCITT recommendations)
Protection Automatic module disconnect at high output voltage. Output fuse: 24V-25A, 48V-10 A fast
Automatic temp. de-rating none
General data
EMC -emission and immunity Emission: EN 50081-1 and Immunity: EN 50082 - 2
Safety IEC 950, EN 60950
Isolation Voltage Input/Earth: 1.5kVAC, Input/Output: 3.0kVAC, Ouput/Earth: 500VDC
Dimensions (HxWxD) mm 780x600x300mm 920x600x300mm 920x600x300mm 1450x600x600mm
Weight 28 kg 35 kg 35 kg 95 kg
Enclosure IP 20
Operating temperature -10 to +40oC
Storage temperature -25 to +85oC
LED indications (each module) Power On [green] and Module Error [red]
Approvals CE marked
SERIES 700

Wall mounted Floor mounted Floor mounted Floor mounted Floor mounted
PRSV 700 - 7kW PRS/B 700 - 7kW PRS/B 700 - 14kW PRS 700 - 21kW PRS/B 700 - 7kW
external batteries 200Ah at 48V DC 100Ah at 48V DC external batteries 400Ah at 48V DC
System Configuration
# Rectifier modules up to 7 x SMPS 700/1000 up to 7 x SMPS 700/1000 up to 14 x SMPS 700/1000 up to 21 x SMPS 700/1000 up to 7 x SMPS 700/1000
Battery capacity none 2 shelves/drawers 1 shelf/drawer none 4 shelves/drawers
Load circuit breakers, 2-50 A up to 27 ways up to 54 ways up to 54 ways up to 27 ways
Load / Battery fuses up to 6 x 160A or 2 x 250A blade fuses (1 PR), 4x160 and 6x400/630A (2 PR)
Low voltage disconnect Battery and/ or load disconnect
Mains CB’s optional
Mains input configurations 230 VAC single phase, 230 VAC three phase or 400 VAC three phase
Electrical data - Mains input
Input voltage, module 230 VAC +20%/-35% nominal, 275 - 300VAC < 10min., 300 - 345VAC <400ms
Line frequency 50Hz +/- 10% nominal
Input current <4.8A rms at 230Vac and full load
Power factor > 0.995 (Power Factor Correction: THD < 9% at 230V AC and full load - typically <7%)
Efficiency > 91%
Protection (rectifier module) Line fuse F8.0A(H)-5x20mm HRC, replaceable from bottom of rectifier module. Mains low int. shut down w/aut. reset
Electrical data - DC output
Output voltage 24V / 48V / 60V DC: 10 - 30VDC / 40 - 58VDC / 45 - 75VDC adjustable
Output voltage regulation +/- 0.5% from 100 - 0%
Dynamic response +/- 1.0% <10ms response time
Output current (per module) 26.5/36.8A at 27.2V DC (30/40A at 22V DC), 15/18A at 54.5V DC (18/22A at 43VDC), 12A at 67.5 V DC (14.5A at 55.5 V DC)
Active current share +/- 5% (overall 10%)
Hold-up time > 10ms at 54V DC and full load
Ripple <100mVpp
Psophometric noise <2mVrms (acc. to CCITT), typically <0.3mVrms
Protection High output voltage shut down
Automatic temp. de-rating Decrease of output current at high temperatures
General data
EMC -emission and immunity Emission: EN 50081-1 and Immunity: EN 50082-2
Safety IEC 950, EN 60950
Isolation Voltage Input/Earth: 1.5kVAC, Input/Output: 3.0kVAC, Output/Earth: 1.0kVDC
Dimensions (HxWxD) mm 780x600x300 1450x600x600 1800x600x600 2200x600x600 2000x600x600
Weight 30 kg 95 kg 100 kg 130 kg 115 kg
Enclosure IP 20
Operating temperature -10 to +35oC full power, automatic power derating above this temperature
Storage temperature -25 to +85oC
LED indications (each module) Power On [green], Module Error [red] and Current Limit Mode [yellow]
Approvals CE
SERIES 1800

Norway:
Eltek Energy AS
P.O. Box 1500,
N-3007 Drammen
Tel.: 0047 32203200.
Fax: 0047 32203210.
E-mail: eltek@eltek.no
www.eltek.no

Unitech AS
P.O. Box 43,
Floor mounted Floor mounted Floor mounted Floor mounted 1361 Billingstad
Tel.: 0047 66980400.
PRS/B1800-7.2kW PRS/B1800-7.2kW PRS1800-14.4kW PRS1800 - 21.6kW Fax: 0047 66981440.
200Ah at 48V DC 400Ah at 48V DC external batteries external batteries
Great Britain:
System Configuration Eltek (UK) Ltd.
2 Maxted Road
# Rectifier modules up to 4 SMPS 1800 up to 4 SMPS 1800 up to 8 SMPS 1800 up to 12 SMPS1800 Hemel Hempstead,
Battery capacity 2 shelves/drawers 4 shelves/drawers none none Herts HP2 7DX
Tel.: 0044 1442219355.
Load circuit breakers, 2-50 A up to 27 ways up to 54 ways Fax: 0044 1442247194.
Load / Battery fuses up to 6 x 160A or 2 x 250A blade fuses up to 4 x 160A and 6 x 400A / 600A fuses
Poland:
Low voltage disconnect Battery and/or load disconnect Eltek Polska Sp. Z.o.o.
Mains CB’s optional Ul. Szczawiowa 53B,
70-010 Szczecin
Mains input configurations 230 VAC single phase, 230 VAC three phase or 400 VAC three phase Tel.: 0048 91825797.
Fax: 0048 91825786.
Electrical data - Mains input
Input voltage, module 230 VAC: 150 - 275VAC nominal, 275-300VAC <10min., 300 - 345VAC <400ms France:
Eltek Energy France
Line frequency 50Hz +/- 10 % nominal Place Francois Mitterand,
Input current <13.0A rms at 230Vac and full load 01 Tour Crédit Lyonnais,
59777 Euralille
Power factor > 0.995 (Power Factor Correction, acc. EN 61000-3-2) Tel.: 0033 320125210.
Efficiency > 91% Fax: 0033 320125225.

Protection (rectifier module) 16A fuse in phase and neutral line. Mains low internal shut down w/aut. reset Germany:
Gertek GmbH
Electrical data - DC output P.O.Box 1135,
Output voltage 48V DC: 43 - 58VDC adjustable Friedrich Luber Strasse 31
90592 Schwarzenbruck
Output voltage regulation +/- 0.5% from 100 - 0% Tel.: 0049 9128916486.
Dynamic response +/- 1.0% <10ms response time Fax: 0049 9128916487.

Output current (per module) 33A at 54V DC (41.5A at 43V DC) India:
Active current share +/- 5% (overall 10%) Eltek SGS Pvt. Ltd.
899 Udyog Vihar, Phasa 1
Hold-up time > 10ms at 54V DC and full load Gurgaon 122016 (Haryana) 1
Tel.: 0091 124346996.
Ripple <100mVpp Fax: 0091 124346997.
Psophometric noise <2mVrms (acc. to CCITT)
Hong Kong:
Protection High ouput voltage shut down Eltek Energy Ltd.
Automatic temp. de-rating Decrease of output current at high temperatures Rm. 812 Eight Commercial Tower
8 Sun Yip Street, Chaiwan
General data Tel.: 0085 228982689.
EMC -emission and immunity Emission: EN 50081-1 and Immunity: EN 50082-2 Fax: 0085 228983189.

Safety IEC 950, EN 60950 Singapore:


Eltek Power Supplies PTA.
Isolation Voltage Input/Earth: 1.5kVAC, Input/Output: 3.0kVAC, Output/Earth: 1.0kVDC 194 Pandan Loop #07-19
Dimensions (HxWxD) mm 1450x600x600 2000x600x600 2000x600x600 2200x600x600 Pantech Industrial Complex,
Singapore 128383
Weight 100 kg 120 kg 130 kg 150 kg Tel.: 0065 7732326.
Enclosure IP 20 Fax: 0065 7753607.

Operating temperature -10 to +40oC full power, automatic power derating above this temperature United Arab Emirates:
Storage temperature -25 to +85oC Eltek Middle East
P.O.Box 33090,
LED indications (each module) Mains OK[yellow], Power On[green], Current Lim.[red], Current>2A[green], OVS[red] Dubai
Tel.: 0097 14481637.
Approvals CE marking Fax: 0097 14485802.
Specifications are subject to change without notice. Art. nr. 364060.023
Utg. 3-4000-02/99
S&J/ Stens