Professional Documents
Culture Documents
Le160978 C WW SW DC 3220
Le160978 C WW SW DC 3220
Le160978 C WW SW DC 3220
CONTENTS
2 Load Calculations 4
3 Design of Purlin 8
DESIGNED CHECKED
TITLE: SLUDGE STORAGE YARD - DESIGN CALCULATION
PKR KSR/MK
SCOPE OF DESIGN REPORT
This document contains design of Sludge Storage Area. The structure consist of a
shed with GRP roof sheeting supported on purlins. The truss is supported on RCC
columns with isolated footings.
Design Method : STAAD model has been prepared for the Structure & Truss.
Footing have been designed using standard excel sheets.
DESIGN CONSTANTS
Grade of Concrete = 25 N/mm2
Grade of Steel = 500 N/mm2
Clear Cover to Reinforcement
Roof Beams : 30 mm
Other Beams : 40 mm
Foundations : 50 mm
Column : 40 mm
Seismic Zone III
Zone Factor 0.16
Importance Factor (As Per Table 6 of IS:1893 (Part 1)-2002 1.0
Page 3
L&T Construction
Water & Effluent Treatment
DESIGNED CHECKED
TITLE: SLUDGE STORAGE YARD - DESIGN CALCULATION
PKR KSR/MK
LOAD CALCULATIONS
Page 4
L&T Construction
Water & Effluent Treatment
DESIGNED CHECKED
SLUDGE STORAGE YARD - DESIGN
TITLE: CALCULATION PKR KSR/MK
DEAD LOAD
Self Weight of Sheeting with Fixtures = 0.15 kN/m2
Self Weight of Sheeting with Fixtures per m run = 0.15x1.245 0.187 kN/m
Self Weight of Purlin (ISMC 100) = 0.096 kN/m
Page 5
L&T Construction
Water & Effluent Treatment
DESIGNED CHECKED
SLUDGE STORAGE YARD - DESIGN
TITLE: CALCULATION PKR KSR/MK
-1.670 -1.670
0.689 0.689
DESIGNED CHECKED
SLUDGE STORAGE YARD - DESIGN
TITLE: CALCULATION PKR KSR/MK
Page 7
L&T Construction
Water & Effluent Treatment
DESIGNED CHECKED
TITLE: SLUDGE STORAGE YARD - DESIGN CALCULATION
PKR KSR/MK
DESIGN OF PURLIN
Page 8
L&T Construction
Water & Effluent Treatment
DESIGNED CHECKED
TITLE: SLUDGE STORAGE YARD - DESIGN CALCULATION
PKR KSR/MK
Design of Purlin
Spacing Between truss = 3.17 m
Spacing of Purlin = 1.25 m
Roof Angle (Degree) (θ) = 18.00
Roof Angle (Radian) (θ) = 0.314
DEAD LOAD
Self Weight = ISMC 75 68.00 N/m
Sheeting self weight with fixtures = ((68+(0.1x68))/1000) 0.075 kN/m
Load on Purlin = 15.00 Kg/m2
0.15 kN/m2
0.15x3.167 0.48 kN/m
Total dead load on Purlin = 0.475+0.075 0.55 kN/m
LIVE LOAD
Live load on roof truss = 0.75 kN/m2
Reduced Load on Purlin as per IS 875 0.75-0.02x(18-10) 0.59 kN/m2
Live load on Purlin = 0.59x1.245 0.73 kN/m
WIND LOAD
Basic Wind Speed (Vb) = 47 m/sec
k1 = 1.00
k2 = 0.98
k3 = 1.00
Design Wind Speed (Vz) = 47x1x0.98x1 46.06 m/sec
Design Wind Pressure(Pz) = (0.6x46.06x46.06/1000) 1.27 kN/m2
Page 9
L&T Construction
Water & Effluent Treatment
DESIGNED CHECKED
TITLE: SLUDGE STORAGE YARD - DESIGN CALCULATION
PKR KSR/MK
- 1.26 - 1.26
0.5 0.5
LOAD COMBINATION
DESIGNED CHECKED
TITLE: SLUDGE STORAGE YARD - DESIGN CALCULATION
PKR KSR/MK
λx = 3167/29.6 106.993
λy = 1583.5/12.1 130.868
DESIGNED CHECKED
TITLE: SLUDGE STORAGE YARD - DESIGN CALCULATION
PKR KSR/MK
SAFE
DL + LL + WL
σ(bcx cal)=
((0.525x10^6)/20300)+((0.563x10^6)/20300)+((-1.987x10^6)/20300) -44.31
σ(bcy cal)=
((0.043x10^6)/4700)+((0.046x10^6)/4700) 18.79
(25.845/165)+(27.724/165)+(-97.877/126.43) -0.45
(9.067/165)+(9.727/165) 0.11
Interaction = -0.34
SAFE
CHECK FOR DEFLECTION
Max allowable deflection = (3.167x1000)/250 13 mm
Page 12
L&T Construction
Water & Effluent Treatment
DESIGNED CHECKED
TITLE: SLUDGE STORAGE YARD - DESIGN CALCULATION
PKR KSR/MK
DL + LL = ((1.087x10^6)x(3.167x1000)x(3.167x1000))/(10x2x10^5x760000) 7.18 mm
OK
DL + WL = ((-1.462x10^6)x(3.167x1000)x(3.167x1000))/(10x2x10^5x760000)-9.65 mm
OK
DL + LL + WL = ((-0.899x10^6)x(3.167x1000)x(3.167x1000))/(10x2x10^5x760000)-5.94 mm
OK
Page 13
L&T Construction
Water & Effluent Treatment
DESIGNED CHECKED
TITLE: SLUDGE STORAGE YARD - DESIGN CALCULATION
PKR KSR/MK
DESIGN OF BASE PLATE
Page 14
L&T Construction
Water & Effluent Treatment
DESIGNED CHECKED
TITLE: SLUDGE STORAGE YARD - DESIGN CALCULATION
PKR KSR/MK
350 mm
250 mm
Bearing Pressure
Case (I) Loading
Base Pressure W = (35.851x1000/(350x250)) 0.41 N/mm2
Permissible Bearing Pressure = 0.45x25 11.3 N/mm2
Page 15
L&T Construction
Water & Effluent Treatment
DESIGNED CHECKED
TITLE: SLUDGE STORAGE YARD - DESIGN CALCULATION
PKR KSR/MK
c= 88 mm
Minimum thickness of the plate, (4.13.2.2), t = 88xSQRT(3x0.41/250) 6.17 mm
Thickness Provided = 12 mm
Check for Edge Distance
Minimum edge distance = (Table 29) 1.25x18 22.5 mm
Edge Distance Provided = 88 mm
Provided > Minimum edge distance OK
Page 16
L&T Construction
Water & Effluent Treatment
SIZING, GROUPING & DESIGN OF
COLUMN FOOTINGS
Page 17
L&T Construction
Water & Effluent Treatment
REACTION FORCES FROM STAAD FOR BASIC LOAD CASES
Page 18
L&T Construction
Water & Effluent Treatment
REACTION FORCES FROM STAAD FOR BASIC LOAD CASES
REACTION FORCES FROM STAAD FOR BASIC LOAD CASES
Page 20
L&T Construction
Water & Effluent Treatment
JHUNJHUNU WATER SUPPLY AND SEWERAGE DOCUMENT NO. DATE
PROJECT: WORKS LE160978-C-WW-SW-DC-3220 31-Jan-18
TITLE: SLUDGE STORAGE YARD - DESIGN CALCULATION
DESIGNED CHECKED
PKR KSR/MK
SIZING OF FOOTINGS & CHECK FOR BEARING PRESSURE
Increase for EQ / Wind = 25%
Pump House
STAAD OUTPUT GROUP MAX PR MIN PR Permissible SIZE
NODE LOAD CASE FY MX MZ kN / sqm kN / sqm m
449 DL+LL 85.931 ‐2.519 ‐6.079 F2 49.43 24.70 79.40 1.7 x 1.5
DL+LL+EQXP 77.983 ‐2.51 13.408 F2 56.13 11.15 99.25 1.7 x 1.5
DL+LL+EQZP 103.446 ‐18.951 ‐6.158 F2 82.87 6.37 99.25 1.7 x 1.5
DL+LL+EQXN 93.879 ‐2.529 ‐25.566 F2 79.85 1.14 99.25 1.7 x 1.5
DL+LL+EQZN 68.416 13.913 ‐6.000 F2 59.64 ‐0.62 99.25 1.7 x 1.5
Page 21
L&T Construction
Water & Effluent Treatment
JHUNJHUNU WATER SUPPLY AND SEWERAGE DOCUMENT NO. DATE
PROJECT: WORKS LE160978-C-WW-SW-DC-3220 31-Jan-18
TITLE: SLUDGE STORAGE YARD - DESIGN CALCULATION
DESIGNED CHECKED
PKR KSR/MK
SIZING OF FOOTINGS & CHECK FOR BEARING PRESSURE
Increase for EQ / Wind = 25%
Pump House
STAAD OUTPUT GROUP MAX PR MIN PR Permissible SIZE
NODE LOAD CASE FY MX MZ kN / sqm kN / sqm m
469 DL+LL 85.941 2.519 6.086 F2 49.45 24.70 79.40 1.7 x 1.5
DL+LL+EQXP 94.376 2.551 25.948 F2 80.63 0.80 99.25 1.7 x 1.5
DL+LL+EQZP 68.492 ‐13.89 6.217 F2 59.94 ‐0.84 99.25 1.7 x 1.5
DL+LL+EQXN 77.506 2.487 ‐13.776 F2 56.40 10.47 99.25 1.7 x 1.5
DL+LL+EQZN 103.390 18.926 5.955 F2 82.53 6.67 99.25 1.7 x 1.5
Page 22
L&T Construction
Water & Effluent Treatment
DESIGN OF FOOTINGS F1
DESIGN FORCES
Page 23
L&T Construction
Water & Effluent Treatment
Page 24
L&T Construction
Water & Effluent Treatment
Shear Stress=
(59.8x1000/(((235x0.77x1000)+((1.5x1000-0.77x1000)x(235+235)/2)))) 0.17 N/mm2
Permissible Shear Stress= 0.31 N/mm2
OK
CHECK FOR TWO WAY SHEAR
235-(235x0.5-100)x0/(0.5x(1.5x1000-300-200)) 235.0 mm
Ks= 1.00
OK
Page 25
L&T Construction
Water & Effluent Treatment
DESIGN OF FOOTINGS F2
DESIGN FORCES
Page 26
L&T Construction
Water & Effluent Treatment
Page 27
L&T Construction
Water & Effluent Treatment
Shear Stress=
(64.7x1000/(((235x0.94x1000)+((1.7x1000-0.94x1000)x(235+235)/2)))) 0.16 N/mm2
Permissible Shear Stress= 0.32 N/mm2
OK
CHECK FOR TWO WAY SHEAR
235-(235x0.5-100)x0/(0.5x(1.5x1000-300-200)) 235.0 mm
Ks= 1.00
OK
Page 28
L&T Construction
Water & Effluent Treatment
DESIGN OF FOOTINGS F3
DESIGN FORCES
Page 29
L&T Construction
Water & Effluent Treatment
Page 30
L&T Construction
Water & Effluent Treatment
Shear Stress=
(79.5x1000/(((235x0.97x1000)+((2x1000-0.97x1000)x(235+235)/2)))) 0.17 N/mm2
Permissible Shear Stress= 0.32 N/mm2
OK
CHECK FOR TWO WAY SHEAR
235-(235x0.5-100)x0/(0.5x(1.7x1000-300-200)) 235.0 mm
Ks= 1.00
OK
Page 31