Professional Documents
Culture Documents
Summary of SAES-J-902
Summary of SAES-J-902
Summary of SAES-J-902
Summary of SAES-J-902
SIGNAL SEGREGATION
Level – 1 - High to Medium Susceptibility Level – 2 - Low Susceptibility
Analog signals of less than 50 V and discrete instrument signals of less Switching signals greater than 30 V, analog signals greater than
than 30 V. 50 V, and 120-240 AC feeders less than 20 amps.
Multi-pair/triad cable shall not be used to route more than one signal level. In addition, junction boxes shall be segregated based on
signal level
Cables with the same noise susceptibility level may be grouped in trays and conduit
SIGNAL SEPARATION
Unit: millimetres (inches)
Minimum This also applies to the distance between
trays and power equipment of less than
Tray Spacing
100 kVA.
When minimum space in the tables above cannot be maintained, parallel runs shall not exceed 5 ft in the overall run.
Near sources of strong electromagnetic fields, a minimum spacing of 1,500 mm (≈59 in) shall be maintained between the cables and the devices. If a steel
conduit is used, the distance may be reduced to 750 mm (29.5 in).
When routing Instrumentation cables (level 1 & level 2) near power cables carrying higher loads than the limits specified in level 3, the separation distances shall
be 1,000 mm (39.4 in) as a minimum. If the routing is to be done through a steel conduit, or crossed at 90 degrees, the minimum separation distance shall not be
less than 500 mm (19.7 in).
Wire Tagging Shall comply with SAES-P-104, Wiring Methods and Materials
Homerun cables shall be tagged with the assigned “IC” cable number.
The cable tagging philosophy for cables routed from junction boxes to field instruments shall be defined
by the Proponent Representative.
Cable Tagging
Cable-tags for outdoor applications shall be 316 SS with permanently marked alphanumeric characters,
i.e., raised or stamped characters and for indoor applications high quality plastic cable tags secured using
cable ties.
GROUNDING
All exposed non-current-carrying metallic parts must be reliably connected to the equipment grounding circuits with a minimum copper wire size
of 14 AWG. Two copper conductors, 25 mm² minimum, shall be connected from the safety ground bus to a single tie point on the safety
ground grid in a closed loop configuration. Instrument grounding should comply with SAES-P-111.