This document provides a 3-sentence summary of a turbine control program mode worksheet:
The worksheet documents settings for turbine control parameters including startup configuration, speed control, speed setpoints, analog and contact inputs, function keys, relays, readouts, and communication for a turbine with serial number and application defined at the top. Various control modes, thresholds, and other parameters are configured through the settings on the worksheet to control aspects like startup rate, idle speed, overspeed trip, analog functions, and relay behavior. Refer to another document for details on individual settings listed on the worksheet.
This document provides a 3-sentence summary of a turbine control program mode worksheet:
The worksheet documents settings for turbine control parameters including startup configuration, speed control, speed setpoints, analog and contact inputs, function keys, relays, readouts, and communication for a turbine with serial number and application defined at the top. Various control modes, thresholds, and other parameters are configured through the settings on the worksheet to control aspects like startup rate, idle speed, overspeed trip, analog functions, and relay behavior. Refer to another document for details on individual settings listed on the worksheet.
This document provides a 3-sentence summary of a turbine control program mode worksheet:
The worksheet documents settings for turbine control parameters including startup configuration, speed control, speed setpoints, analog and contact inputs, function keys, relays, readouts, and communication for a turbine with serial number and application defined at the top. Various control modes, thresholds, and other parameters are configured through the settings on the worksheet to control aspects like startup rate, idle speed, overspeed trip, analog functions, and relay behavior. Refer to another document for details on individual settings listed on the worksheet.
This document provides a 3-sentence summary of a turbine control program mode worksheet:
The worksheet documents settings for turbine control parameters including startup configuration, speed control, speed setpoints, analog and contact inputs, function keys, relays, readouts, and communication for a turbine with serial number and application defined at the top. Various control modes, thresholds, and other parameters are configured through the settings on the worksheet to control aspects like startup rate, idle speed, overspeed trip, analog functions, and relay behavior. Refer to another document for details on individual settings listed on the worksheet.
Application :TURBINE #1 Date : 26 MARET 2020 Rev. 1
For details on individual settings, refer to Chapter 4.
TURBINE START Rated Spd Setpt 3000 rpm
Manual Start NO Use Freq Arm/Disarm ? NO Automatic Start YES Use Local/Remote NO Rate to Min (rpm/Sec) 5 rpm/sec Valve Lmtr Rate (%/Sec) 1 %/sec DRIVER CONFIGURATION Use Idle/Rated? YES Act #1 is 4–20 mA? YES Idle Setpt (rpm) 600 rpm Invert Driver Outputs ? NO Rated Setpt (rpm) 2880 rpm Use Act 1 Flt Shutdown NO Idle/Rtd Rate (rpm/sec) 10 rpm/sec Act #1 Dither 0,001 % Ext Trips in Trip Relay YES Use Actuator #2? NO Reset Clears Trip Output YES ANALOG INPUTS SPEED CONTROL Analog Input # 1 Function Not Used Teeth Seen by MPU 60 Input 1 4 mA Value 0 Units Gear Ratio 1 : 1 Input 1 20 mA Value 100 Units Failed Speed Level(rpm) 250 rpm Analog Input # 2 Function Not Used Use Speed Input #2? YES Input 2 4 mA Value 0 Units Failed Speed Level(rpm) 250 rpm Input 2 20 mA Value 100 Units Off-Line Prop Gain 5,975 % Analog Input # 3 Function Not Used Off-Line Int Gain 0,549 rps Input 3 4 mA Value 0 Units Off-Line Deriv Ratio 5,0 % Input 3 20 mA Value 100 Units On-Line Prop Gain 5,303 % Analog Input # 4 Function Not Used On-Line Int Gain 0,500 rps Input 4 4 mA Value 0 Units On-Line Deriv Ratio 5,0 % Input 4 20 mA Value 100 Units Analog Input # 5 Function Not Used SPEED SETPOINT VALUES Input 5 4 mA Value 0 Units Overspeed Test Lmt (rpm) 3290 rpm Input 5 20 mA Value 100 Units Overspeed Trip (rpm) 3240 rpm Analog Input # 6 Function KW/Unit Load Input Max Governor Speed (rpm) 3180 rpm Input 6 4 mA Value 0 Units Min Governor Speed (rpm) 2880 rpm Input 6 20 mA Value 10000 Units Setpt Slow Rate(rpm/sec) 5 rpm/sec Use Remote Speed Setpt ? NO Use Critical Speeds? YES CONTACT INPUTS Critical Speed Rate 30 rpm/sec Contact Input 1 Function Idle/ rate Critical Speed 1 Max 2200 rpm Contact Input 2 Function External Run Critical Speed 1 Min 1500 rpm Contact Input 3 Function Over Speed Test Use Critical Band 2 ? NO Contact Input 4 Function Generator Breaker Contact Input 5 Function Utility Breaker OPERATING PARAMETERS Contact Input 6 Function Start Permissive Generator Application? YES Contact Input 7 Function Not Used Use Gen Brkr Open Trip ? YES Contact Input 8 Function Not Used Use Tie Brkr Open Trip ? YES Contact Input 9 Function Not Used Use KW Droop? YES Contact Input 10 Fctn Not Used KW Max Load 7000 KW Contact Input 11 Fctn Not Used Droop (%) 6% Contact Input 12 Fctn Not Used FUNCTION KEYS RELAYS F3 Key Performs Not Used Use Relay #1? YES Blink when not Active? NO Relay # 1 is Level Switch? YES F4 Key Performs Not Used Relay 1 Is Level Sw For Actual Speed Blink when not Active? NO Relay 1 ON Level 500 Units Relay 1 OFF Level 450 Units AUXILIARY CONTROL Use Relay # 2? YES Use Auxiliary Control ? NO Relay # 2 is Level Switch? YES Relay 2 Is Level Sw For Valve Limiter CASCADE CONTROL Relay 2 On Level 30 Units Use Cascade Control? NO Relay 2 Off Level 25 Units Use Relay # 3? NO READOUTS Use Relay # 4? NO Analog Readout 1 Is Not Used Use Relay # 5? YES Readout 1 4 mA Value 0 Units Relay # 5 is Level Switch? NO Readout 1 20 mA Value 100 Units Relay 5 Energizes On Control Status OK Analog Readout 2 Is Speed Set Point Use Relay # 6? YES Readout 2 4 mA Value 0 Units Relay # 6 is Level Switch? NO Readout 2 20 mA Value 4000 Units Relay 6 Energizes On Over Speed test Analog Readout 3 Is Actuator Demand Enable read Out Readout 3 4 mA Value 0 Units COMMUNICATION Readout 3 20 mA Value 100 Units Use Communication? NO Analog Readout 4 Is Not Used Readout 4 4 mA Value 0 Units Readout 4 20 mA Value 100 Units Analog Readout 5 Is Not Used Readout 5 4 mA Value 0 Units Readout 5 20 mA Value 100 Units Analog Readout 6 Is Actual Speed Readout 6 4 mA Value 0 Units Readout 6 20 mA Value 100 Units