505 Program Mode Worksheets


Governor Serial Number ______________________

Application :TURBINE #1 Date : 26 MARET 2020 Rev. 1

For details on individual settings, refer to Chapter 4.

TURBINE START Rated Spd Setpt 3000 rpm


Manual Start NO Use Freq Arm/Disarm ? NO
Automatic Start YES Use Local/Remote NO
Rate to Min (rpm/Sec) 5 rpm/sec
Valve Lmtr Rate (%/Sec) 1 %/sec DRIVER CONFIGURATION
Use Idle/Rated? YES Act #1 is 4–20 mA? YES
Idle Setpt (rpm) 600 rpm Invert Driver Outputs ? NO
Rated Setpt (rpm) 2880 rpm Use Act 1 Flt Shutdown NO
Idle/Rtd Rate (rpm/sec) 10 rpm/sec Act #1 Dither 0,001 %
Ext Trips in Trip Relay YES Use Actuator #2? NO
Reset Clears Trip Output YES
ANALOG INPUTS
SPEED CONTROL Analog Input # 1 Function Not Used
Teeth Seen by MPU 60 Input 1 4 mA Value 0 Units
Gear Ratio 1 : 1 Input 1 20 mA Value 100 Units
Failed Speed Level(rpm) 250 rpm Analog Input # 2 Function Not Used
Use Speed Input #2? YES Input 2 4 mA Value 0 Units
Failed Speed Level(rpm) 250 rpm Input 2 20 mA Value 100 Units
Off-Line Prop Gain 5,975 % Analog Input # 3 Function Not Used
Off-Line Int Gain 0,549 rps Input 3 4 mA Value 0 Units
Off-Line Deriv Ratio 5,0 % Input 3 20 mA Value 100 Units
On-Line Prop Gain 5,303 % Analog Input # 4 Function Not Used
On-Line Int Gain 0,500 rps Input 4 4 mA Value 0 Units
On-Line Deriv Ratio 5,0 % Input 4 20 mA Value 100 Units
Analog Input # 5 Function Not Used
SPEED SETPOINT VALUES Input 5 4 mA Value 0 Units
Overspeed Test Lmt (rpm) 3290 rpm Input 5 20 mA Value 100 Units
Overspeed Trip (rpm) 3240 rpm Analog Input # 6 Function KW/Unit Load Input
Max Governor Speed (rpm) 3180 rpm Input 6 4 mA Value 0 Units
Min Governor Speed (rpm) 2880 rpm Input 6 20 mA Value 10000 Units
Setpt Slow Rate(rpm/sec) 5 rpm/sec
Use Remote Speed Setpt ? NO
Use Critical Speeds? YES CONTACT INPUTS
Critical Speed Rate 30 rpm/sec Contact Input 1 Function Idle/ rate
Critical Speed 1 Max 2200 rpm Contact Input 2 Function External Run
Critical Speed 1 Min 1500 rpm Contact Input 3 Function Over Speed Test
Use Critical Band 2 ? NO Contact Input 4 Function Generator Breaker
Contact Input 5 Function Utility Breaker
OPERATING PARAMETERS Contact Input 6 Function Start Permissive
Generator Application? YES Contact Input 7 Function Not Used
Use Gen Brkr Open Trip ? YES Contact Input 8 Function Not Used
Use Tie Brkr Open Trip ? YES Contact Input 9 Function Not Used
Use KW Droop? YES Contact Input 10 Fctn Not Used
KW Max Load 7000 KW Contact Input 11 Fctn Not Used
Droop (%) 6% Contact Input 12 Fctn Not Used
FUNCTION KEYS RELAYS
F3 Key Performs Not Used Use Relay #1? YES
Blink when not Active? NO Relay # 1 is Level Switch? YES
F4 Key Performs Not Used Relay 1 Is Level Sw For Actual Speed
Blink when not Active? NO Relay 1 ON Level 500 Units
Relay 1 OFF Level 450 Units
AUXILIARY CONTROL Use Relay # 2? YES
Use Auxiliary Control ? NO Relay # 2 is Level Switch? YES
Relay 2 Is Level Sw For Valve Limiter
CASCADE CONTROL Relay 2 On Level 30 Units
Use Cascade Control? NO Relay 2 Off Level 25 Units
Use Relay # 3? NO
READOUTS Use Relay # 4? NO
Analog Readout 1 Is Not Used Use Relay # 5? YES
Readout 1 4 mA Value 0 Units Relay # 5 is Level Switch? NO
Readout 1 20 mA Value 100 Units Relay 5 Energizes On Control Status OK
Analog Readout 2 Is Speed Set Point Use Relay # 6? YES
Readout 2 4 mA Value 0 Units Relay # 6 is Level Switch? NO
Readout 2 20 mA Value 4000 Units Relay 6 Energizes On Over Speed test
Analog Readout 3 Is Actuator Demand Enable
read Out
Readout 3 4 mA Value 0 Units COMMUNICATION
Readout 3 20 mA Value 100 Units Use Communication? NO
Analog Readout 4 Is Not Used
Readout 4 4 mA Value 0 Units
Readout 4 20 mA Value 100 Units
Analog Readout 5 Is Not Used
Readout 5 4 mA Value 0 Units
Readout 5 20 mA Value 100 Units
Analog Readout 6 Is Actual Speed
Readout 6 4 mA Value 0 Units
Readout 6 20 mA Value 100 Units