Professional Documents
Culture Documents
Fire Test Protocol For Water Mist Systems
Fire Test Protocol For Water Mist Systems
Fire Test Protocol For Water Mist Systems
This document is binding only if its application has been agreed on a case-by-case basis.
Otherwise, any consideration of this document is non-binding. An agreement for applica-
tion of this document is entirely optional. On a case-by-case basis, third parties may also
accept, at their discretion, other requirements that do not comply with this document.
Content
1 General ..................................................................................................................... 4
1.1 Scope .................................................................................................................... 4
1.2 Validity .................................................................................................................. 4
2 Normative References ............................................................................................ 4
3 General Preconditions............................................................................................ 5
4 False ceilings and false floors fuel package ........................................................ 5
4.1 General ................................................................................................................. 5
4.2 Housing ................................................................................................................. 7
4.3 Cable Trays ........................................................................................................... 8
4.4 Cables ................................................................................................................... 8
4.5 Conditioning of the fuel load ................................................................................. 8
4.6 Ignition source....................................................................................................... 9
5 Reference sprinkler system requirements ........................................................... 9
6 Fire Tests ................................................................................................................. 9
6.1 General ................................................................................................................. 9
6.2 Reference sprinkler tests ...................................................................................... 9
6.3 Water mist system tests ...................................................................................... 10
6.4 Test arrangement................................................................................................ 10
6.5 Fire tests ............................................................................................................. 10
6.6 Test assembly requirements ............................................................................... 11
6.7 Instrumentation requirements ............................................................................. 12
6.8 Evaluation of test results ..................................................................................... 12
7 Test Report ............................................................................................................ 13
8 Films and photographs ........................................................................................ 14
3
Part 3: Protection of False Ceilings and False Floor of OH Group 1 VdS 3883-3en : 2020-06 (01)
1 General
1.1 Scope
This test method is intended for evaluating the fire performance of water mist systems
equivalent to the fire performance of a sprinkler system according to VdS CEA 4001.
The test protocol is applicable to ceiling mounted automatic water mist sprinklers to be
used in unlimited volumes with a minimum hydraulic demand area of 72 m² and a mini-
mum duration in accordance with VdS 3188. The test protocol is applicable for hori-
zontal, solid, flat ceilings.
It is not possible to apply these tests to other applications than the ones specified or to
greater room heights.
In case of a positive result of the tests false ceilings and false floors the water mist
system to be approved can be approved for the protection of the following risks:
The following limitations apply to the protection of false floors and ceilings:
1.2 Validity
These guidelines are valid from 1st July 2020.
Note: This is a translation of the German guidelines. If there are any discrepancies, the
German version shall be binding.
2 Normative References
These guidelines contain dated and undated references to other regulations (in alphabetical
order). The normative references are cited in the respective clauses, the titles are listed be-
low. For dated references, subsequent amendments to or revisions of any of these regulati-
ons apply to these guidelines only when published by revision or amendment of these gui-
delines. For undated references the latest edition of the regulation referred to applies.
VdS CEA 4001 Guidelines for sprinkler systems – planning and installation
4
VdS 3883-3en : 2020-06 (01) Part 3: Protection of False Ceilings and False Floor of OH Group 1
VdS 2344 Procedure for the testing, approval, certification and conformity assess-
ment of products and systems for fire protection and security technologies
VdS 3188 Guidelines for water mist systems – planning and installation
3 General Preconditions
The water mist system, operating without manual intervention, shall successfully
complete all described performance fire tests for their specific applications.
The water flow shall be shut-off 10 min after the activation of the first sprinkler/water mist
sprinkler. Any remaining fire shall be manually extinguished and the fire damages shall
be recorded.
All fire tests shall be conducted using the manufacturer instructions in regard to water
mist sprinkler placement, spray flux, and spray duration.
The fire test protocol is only applicable to ceiling mounted water mist sprinklers.
The water mist sprinklers shall be located in accordance with the manufacturer’s instruc-
tions.
The water supply shall be capable of supplying a flow rate and pressure according to the
specific requirements, which are based on the actual layout of the pipework installation.
The test scenario is based on a typical false ceiling comprising the appropriate fire load in
terms of cabling.
a) housing
b) cable trays
c) cables as fire load
d) heptan pan as ignition source
Figure 4-1 shows an example of the test assembly in accordance with the requirements
specified in this clause.
5
Part 3: Protection of False Ceilings and False Floor of OH Group 1 VdS 3883-3en : 2020-06 (01)
T7/8 T1/2/3
300mm
tray 2
800mm
300mm
tray 1
heptane pan
T4/5/6
200mm
6
VdS 3883-3en : 2020-06 (01) Part 3: Protection of False Ceilings and False Floor of OH Group 1
T2/5
ignition source:
Sp 1 T8 heptane pan
200mm*200mm*20mm
length = T1/4 T9
3 x water 3,0m
mist
sprinkler
distance
T3/6 T7
300 mm
The test assembly comprises the following elements. All tests are carried out with identi-
cal test assemblies which shall fulfil the requirements specified here.
4.2 Housing
A false ceiling/false floor is simulated by a standardised housing. The housing shall be
constructed as follows:
Dimensions:
height: 800 mm
width: 400 mm
length: 3-fold distance of water mist sprinklers to be approved
Materials:
7
Part 3: Protection of False Ceilings and False Floor of OH Group 1 VdS 3883-3en : 2020-06 (01)
floor plate: non-combustible material, proportion of holes 15%, optionally via the
entire length of the test assembly a gap of 15 cm width
Tray 1:
width: 200 mm
material: non-combustible, appropriate for the heat impact to be expected
Tray 2:
width: 300 mm
material: non-combustible, appropriate for the heat impact to be expected
4.4 Cables
The fire loads to be provided shall have normal humidity before the test as is achieved by
indoor storage at (20 ± 5)°C.
Preferred cabling:
Tray 1
NYY 3x1.5; number 15, fire load per cable approx. 0.75 kWh/m
Tray 2
NYY 3x1.5; number 30, fire load per cable approx. 0.75 kWh/m
Tray 1
HHJ 5x2.5 (PE/PP); number 7, fire load per cable approx. 0.80 kWh/m
MMJ 5x2.5 (PVC); number 8, fire load per cable approx. 0.72 kWh/m
Tray 2
MMJ 5x2.5 (PVC); number 15, fire load per cable approx. 0.72 kWh/m
HHJ 5x2.5 (PE/PP); number 15, fire load per cable approx. 0.80 kWh/m
8
VdS 3883-3en : 2020-06 (01) Part 3: Protection of False Ceilings and False Floor of OH Group 1
The water supply shall be capable of supplying a flow rate and pressure according to the
specific requirements, which are based on the actual layout of the pipework installation.
6 Fire Tests
6.1 General
The tests with the water mist system shall be conducted at maximum spacing and
minimum discharge condition. The system shall be installed in accordance with the
manufacturer's design and installation manual, reflecting the maximum allowed time
delay of water pressure build up of the system.
1
This value includes a safety factor of 15 %.
9
Part 3: Protection of False Ceilings and False Floor of OH Group 1 VdS 3883-3en : 2020-06 (01)
sprinkler, the flowing water pressure shall be maintained at a system operating pressure
of at least 0.56 bar.
The water flow shall be shut-off 10 min after the activation of the first sprinkler. Any re-
maining fire shall be manually extinguished and the fire damages shall be recorded.
The water flow shall be shut off 10 min after the activation of the first sprinkler/water mist
sprinkler. Any remaining fire shall be manually extinguished and the fire damages shall
be recorded.
In all tests, the water mist sprinklers of the water mist system to be approved shall be in-
stalled with maximum distance between each other (as specified by the applicant before-
hand). The layout of the water mist sprinklers is analogous to that of the sprinklers.
Note: If VdS considers the ventilation insufficient, O2 measuring points may have to be
installed in the test facility.
The tests shall be designated as specified in Table 6-1 for traceability reasons.
10
VdS 3883-3en : 2020-06 (01) Part 3: Protection of False Ceilings and False Floor of OH Group 1
The test facility should be of adequate size with natural or minimal ventilation so as to not
interfere with the fire testing within the enclosure or about the mock-up or test fuel
package.
The size of the test facility should not impact firefighting capabilities of any test fires (i. e.
depletion of oxygen due to an inadequately sized test laboratory).
There shall be a minimum 1 m from ceiling rim to test facility wall, sufficient ventilation or
space, sufficient ventilation to guarantee sufficient O2 concentration over the entire test
period.
If the above mentioned conditions are not met during the tests, the water mist system
shall only be installed in rooms with a maximum size equal to the limits of the facility they
are tested in.
For all fire tests, the ceiling, floor, and walls should be as dry as possible, with only ambi-
ent moisture content allowed. The relative humidity in the test enclosure should not signif-
icantly differ from that of the ambient relative humidity.
The test enclosures shall be at an ambient temperature of 20°C ± 10°C prior to the start
of the test. The enclosure or hall shall be at as uniform an ambient temperature as
reasonably possible. Localized hot or cold spots are not permitted. All non-fire induced
drafts shall be eliminated.
The minimum operating nozzle pressure (as specified by the manufacturer) shall be used
for all tests, unless otherwise noted. System operating pressures shall be repeatable to
within ± 5 %. If the system pressures cannot be controlled within the specified tolerance,
fire tests should be conducted at the minimum and maximum pressure by using external
means to control the system pressure.
The maximum nozzle ceiling height and spacing (as specified by the manufacturer) shall
be used for all tests. This includes utilizing the maximum ceiling spacing of the nozzles
from the walls.
The fire tests should be conducted in a large open test hall of sufficient area, and with a
minimum ceiling height of 5.0 m, to avoid impacting the results of the tests.
Maximum allowed time delay of water pressure build-up of the system shall be specified
by manufacturer and shall be used for all tests.
11
Part 3: Protection of False Ceilings and False Floor of OH Group 1 VdS 3883-3en : 2020-06 (01)
Thermocouples
For measuring the temperature, exposed 0.5 mm thermocouples of type K shall be posi-
tioned 75 mm below the ceiling surface.
Figure 4-1 and Figure 4-2 show the positions of the individual thermocouples.
The applicant is entitled to install further thermocouples in the test assembly (e. g. at
each water mist sprinkler). However, any additional thermocouples shall also have the
a. m. characteristics.
Pressure transducer
Time measurement
t [mm:ss] time measurement over the entire test period, in which the following times are
recorded:
All measured variables shall be recorded over the entire test period. The tests shall also
be recorded per video. Any damage of the test assembly shall be photographed and
specified in the test report after each test.
12
VdS 3883-3en : 2020-06 (01) Part 3: Protection of False Ceilings and False Floor of OH Group 1
1. Determination of loss:
length of burnt cables on both cable trays (50 %)
area of charred surfaces at the sidewall of the cable trays (50 %)
The percentages given in the brackets describe the extent to which the criterion goes into
the pass/fail evaluation.
This evaluation refers to the temperatures reached after operation of the first sprinkler/
first water mist sprinkler. The temperature curves measured during the test are averaged
over a period of 30 s (maximum interval between measurements 1 s), and from the
averaged curves the peak temperatures shall be determined.
The average gas temperature at the ceiling is the average of the three peak
temperatures.
The total averaged damage of the water mist test series is less than or equal to the
total averaged damage of the sprinkler test (Spr.1).
The total averaged ceiling gas temperature of the water mist test series is less than
or equal to the total averaged ceiling gas temperature of the sprinkler test (Spr.1).
In case of a negative result of a water mist test, the test series may be repeated only with
modified parameters of the system to be approved (e. g. higher design density, smaller
water mist sprinkler distances). In this case the entire test series of sprinkler and fine
water spray tests shall be repeated.
7 Test Report
The results of the tests shall be documented in a test report.
The test report shall be submitted to VdS as electronic document (pdf) and on paper duly
and legally binding signed by the originator. The test report acc. to EN ISO/IEC 17025
shall include at least the following:
13
Part 3: Protection of False Ceilings and False Floor of OH Group 1 VdS 3883-3en : 2020-06 (01)
Moreover, the data acquired by measurement with unique identification of the measuring
points shall be delivered to VdS in an appropriate form (e. g. ASCII or MS Excel) as soon
as the tests are complete.
14