Professional Documents
Culture Documents
Polarization Cell Replacement (PCR) : Technical Literature
Polarization Cell Replacement (PCR) : Technical Literature
Polarization Cell Replacement (PCR) : Technical Literature
Dairyland Electrical Industries • P.O. Box 187 Stoughton, WI 53589 • 608-877-9900 • www.dairyland.com • marketing@dairyland.com
Document ID: 200008 PCR Technical Literature Published Date: 2019.08.16
PRODUCT OVERVIEW The steady-state AC impedance of the PCR at 60 Hz is 9.8
milliohms for the standard 45 ampere rating and 4.9 milliohms
AC Fault Current Ratings for the optional 80 ampere rating. At 50 Hz, the comparable
Some applications may have conditions where an over- impedances are 11.9 milliohms for the standard 45 ampere
voltage device such as the PCR is subject to fault current. For rating and 5.8 m
illiohms for the optional 80 ampere rating. Under
this reason, the PCR was designed to have AC fault current an AC fault or lightning current condition, these impedances
carrying capability. The PCR will limit the voltage between its momentarily become virtually zero. For more information on
connection points to less than 10 volts AC under the maximum steady-state current view our web article: Measuring Steady-
fault current ratings listed below. State AC Current
Four different fault current ratings are offered at 60Hz and DC Blocking Voltage Rating
50Hz with the following current-time relationship: The standard, and most commonly specified, PCR model has
an asymmetrical voltage blocking rating of -3.0 volts to +1.0
volt. Either model can also be furnished with a symmetrical
AC Fault Current Ratings voltage blocking rating of +/- 2.0 volts. Optional ratings of
(Amps AC-RMS Symmetrical) -4V+1V and -6V/+1V are available only with the associated AC
60 Hz Cycles 3.7kA 5kA 10kA 15kA fault current ratings of 3.7kA and 5kA.
1 6500 8800 20000 35000
3 5000 6800 15000 27000 The reasons for symmetrical and asymmetrical choices are
best described with an example. If the PCR is used to provide
10 4200 5700 12000 21000 over-voltage protection for an insulated joint and both sides
30 3700 5000 10000 15000 of the joint are cathodically protected, the DC voltage across
50 Hz Cycles 3.7kA 5kA 10kA 15kA the joint will be the difference in voltage between the two
1 6500 8800 19000 33000 cathodic protection systems, normally near zero volts. For
this application it is desirable to select the symmetrical +/- 2.0
3 5000 6800 14000 25000 volt blocking rating. In the event that the cathodic protection
10 4200 5700 11000 20000 system is OFF on one side of the joint, the device can block
30 3700 5000 9000 14000 2.0 VDC in either direction.
Note: Select a PCR fault current rating that encompasses the fault current If one side of the insulated joint is cathodically protected and
available. For more information on sizing for available fault current, view our the other side is grounded, then it is preferable to select the
web article: Determining AC Fault Current. asymmetrical version which blocks from -3.0 volts to +1.0 volt
since one side has been shifted to a more negative voltage.
Steady-State AC Current Ratings Whenever one side is referenced to ground, the asymmetrical
This rating represents the maximum steady-state AC current version is suggested because the CP voltage is situated in the
that is allowed to flow through the device while still blocking center of the threshold voltage range.
the flow of DC current. Two ratings are available for the PCR.
Lightning Surge Current Rating
The table represents maximum values. As the DC voltage All models have the same lightning surge current rating which
approaches the maximum blocking voltage rating selected, is shown in the following table.
the allowable steady-state AC current is reduced as shown in
Figures 1 and 2. Lightning Surge Current Rating
All PCR Models
Steady-State Current Ratings Peak Amperes: 100,000
(Amps AC-RMS Symmetrical)
Note: 8x20 microsecond waveform
50/60 Hz Ratings
Ambient Temp Standard 45A Rating Optional 80A Rating
20°C 50A 90A
Keep the Conductors Short!
65°C 40A 70A The PCR is designed to keep the voltage between the device
terminals to a limited value. During lightning conditions,
There are a number of applications where a PCR may be a more important factor than the PCR voltage clamping
required to block DC while simultaneously carrying steady-state capability is the voltage developed in the conductors or
AC current. For example, when a pipeline is in the same corridor bus used to attach the device. Use low inductance bus
as an electrical transmission line, steady-state AC voltage is bars or conductors ideally less than 6 inches (150 mm)
often induced on the pipeline. The PCR can mitigate this voltage long for best results. More information on conductor length
by providing a low AC impedance path for AC current to flow to is available at www.dairyland.com.
ground while simultaneously preventing the flow of DC current.
Dairyland Electrical Industries • P.O. Box 187 Stoughton, WI 53589 • 608-877-9900 • www.dairyland.com • marketing@dairyland.com
Document ID: 200008 PCR Technical Literature Published Date: 2019.08.16
Ordering Instructions The EAC version of the PCR, available by ordering a PCR model
with an “-EAC” suffix, is certified to the EAC requirements of
AC Fault Current
Choose: 3.7kA
Blocking Threshold Submersible the Customs Union (Russia, Kazakhstan, etc) for use in Zone
Blocking Threshold Options: Optional: Add “-CS2” for
5kA Add “-S” for -2/+2 NEMA 6P Version Class 2, Group IIC hazardous locations by NANIO-CCVE to:
10kA
15kA
Add “-4/1” for -4/+1*
Add “-6/1” for -6/+1* GOST R IEC 60079-15-2010, GOST R IEC 60079-0-2011.
Certifications Enclosure
Underwriters Laboratories (UL) has listed the PCR as meeting The PCR enclosure is made of a light gray fiberglass-reinforced
the criteria for “an effective grounding path” as defined in polyester material suitable for outdoor non-submersible
Section 250.2 and 250.4(A)(5) of the U.S. National Electrical applications and is rated NEMA 4X (comparable to IP 66).
Code (NFPA 70), thereby enabling its use as an AC grounding Optionally, the PCR can be supplied as a submersible device
device. The PCR is also C-UL listed in Canada as meeting the with the same dimensions rated NEMA 6P (comparable to
criteria for “an effective grounding path” as defined in C22.1- IP68). The optional submersible version of the PCR must
12, Section 10-500. not be installed such that it may be submerged in freezing
conditions.
The PCR is also listed by UL as meeting:
Terminals
•
The requirements of a DC isolating/AC coupling device Two-hole spade terminals are standard, but compact
suitable for the isolation of objectionable DC current from connectors and 4 hole NEMA terminals are available. Compact
cathodically protected systems to ground as defined in NFPA connectors are recommended where necessary to insulate the
70 Article 250.6(E) and C22.1-12 Section 10-806. connections to the PCR after installation (for example, with
a user furnished heat-shrink sleeve). Add “CC” to the end of
• An over-voltage protective device, having been tested to the any model number only if compact connectors are required, or
applicable requirements of ANSI C62.11. “4H” for 4 hole terminals.
Listings specific to hazardous locations are summarized as PCR terminals have preinstalled 1/2” stainless hardware (bolts,
follows: nuts, washers). See Accessories for various attachment options.
Dairyland Electrical Industries • P.O. Box 187 Stoughton, WI 53589 • 608-877-9900 • www.dairyland.com • marketing@dairyland.com
Document ID: 200008 PCR Technical Literature Published Date: 2019.08.16
Number of Operations
Virtually unlimited under maximum ratings, provided the
operations are not immediately repetitive.
Energy Requirements
None. The devices are totally passive.
Ambient Temperature
-45º C to +65º C
MOUNTING OPTIONS
Mounting Accessories
Numerous mounting accessories are available from Dairyland
to aid in the proper installation of the PCR. Detailed accessory
information, including complete installation instructions are
available on the Dairyland website here: Dairyland Accessories.
Dairyland Electrical Industries • P.O. Box 187 Stoughton, WI 53589 • 608-877-9900 • www.dairyland.com • marketing@dairyland.com
Document ID: 200008 PCR Technical Literature Published Date: 2019.08.16
KEY
KEY
Allowable Steady-State Operating Region
Allowable Steady-State Operating Region
Operation in this region only allowed for
Operation in this region only allowed for
transient conditions (AC faults and/or lightning)
transient conditions (AC faults and/or lightning) 100
100
80
80
70
IAC-RMS Amps
IAC-RMS Amps
60
60
45
40 40
Asymmetrical Asymmetrical
Version Version
20 20
Symmetrical Symmetrical
Version Version
0 0 -0.5 -1 -1.5 -2 -2.5 -3.0 -3.5
-0.5 -1 -1.5 -2 -2.5 -3.0 -3.5
VDC Volts VDC Volts
(Allowable AC Current vs. DC Voltage) (Allowable AC Current vs. DC Voltage)
FIGURE 1: PCR Operating Characteristics @ 43°C FIGURE 2: PCR Operating Characteristics @ 43°C
(Standard 45A @ 50/60 Hz) (Standard 80A @ 50/60 Hz)
10000
1000
@ 65˚ C
DC Leakage in milliamperes
100
@ 20˚ C
10
0 .1
0 .0 1
0 0 .5 1 1 .5 2 2 .5 3 3 .5 4 4 .5
DC Volts
FIGURE 3: DC Voltage vs. DC Leakage Current
(Standard Asymmetrical PCR with -3V / +1V Blocking Voltage)
Dairyland Electrical Industries • P.O. Box 187 Stoughton, WI 53589 • 608-877-9900 • www.dairyland.com • marketing@dairyland.com
Document ID: 200008 PCR Technical Literature Published Date: 2019.08.16
1.75
44.5
1.00
25.4
4.98
126.6
1.13 7.32
28.6 185.9
9.50
241.3 8.75
222.3
15.54
394.8
1/2" HARDWARE
2X .56
2.35 1.00 14.3
59.8 25.4
1.75 ALTERNATE TERMINAL
44.5 SPECIFIED BY ADDING "-CC"
TO ANY PCR MODEL NUMBER
1.75
2X .44 44.5
3.00 .38
11.1 1.04
76.2 9.7 .83
26.4
21.0 ANSI Y14.5M 1994 APPLIES
DAIRYLAND DESCRIPTION
ELECTRICAL
INDUSTRIES, INC. PCR 3.7KA THRU 10KA OUTLINE DRAWING
UNLESS NOTED 63 P.O. BOX 187 DOCUMENT # REV DATE DRAWN DWG SIZE DATE APPROVAL
STOUGHTON,
UNITS: INCHES
3-PLACE: .005 WI 53589 100060 A 2014-06-20 B
2-PLACE: .015 608-877-9900
1-PLACE / FRAC:
ANGULAR: 1
.03 DAIRYLAND.COM SCALE 1:3 DRAWN: JPW SHEET: 1 OF 1 DWG APPROVAL:
1.75
44.5
1.00
25.4
5.43
137.9
2.69
3.00 16.88
68.3
76.2 428.8
17.5
445
11.50
292.1 10.75
273.1
2X .56
14.3
2.35 1.00
59.7 25.4
1.75 ALTERNATE TERMINAL
SPECIFIED BY ADDING "-CC"
44.5 TO ANY PCR MODEL NUMBER
5.0 1.75
2X .44
127 44.5
11.1 .38 1.04 ANSI Y14.5M 1994 APPLIES
DAIRYLAND DESCRIPTION
ELECTRICAL
9.7 .59 26.4 INDUSTRIES, INC. PCR-15KA OUTLINE DRAWING
UNLESS NOTED 63 P.O. BOX 187 DOCUMENT # REV DATE DRAWN DWG SIZE DATE APPROVAL
15.1 UNITS: INCHES STOUGHTON,
100085 A 2015-08-18 B
3-PLACE: .005 WI 53589
2-PLACE: .015 608-877-9900
1-PLACE / FRAC:
ANGULAR: 1
.03 DAIRYLAND.COM SCALE 3:10 DRAWN: JPW SHEET: 1 OF 1 DWG APPROVAL:
15.46
392.6
9.32
236.6
.44
11.1
7.32
185.8
2.49 3.00
63.3 76.2
.25
6.4
12.63 1.13
.38 320.8 28.6
9.7
ALTERNATE TERMINAL
1.00
25.4
7.51
190.8
1.75
44.5 1.00
25.4
1.04
26.4 14.88
378.0
.56
14.3 ALTERNATE TERMINAL
SPECIFIED BY ADDING "-CC" TO ANY PCR MODEL NUMBER
1.75
44.5
ANSI Y14.5M 1994 APPLIES
DAIRYLAND DESCRIPTION
ELECTRICAL
INDUSTRIES, INC. PCR 3.7KA THRU 10KA-80A OUTLINE DRAWING
P.O. BOX 187 DOCUMENT # REV DATE DRAWN DWG SIZE DATE APPROVAL
APPLIES TO MODELS: UNLESS NOTED 63
STOUGHTON,
PCR-3.7KA/80A, PCR-5KA/80A and PCR-10KA/80A
UNITS: INCHES
3-PLACE: .005 WI 53589 100081 A 2015-05-29 B 2015-06-02
2-PLACE: .015 608-877-9900
1-PLACE / FRAC:
ANGULAR: 1
.03 DAIRYLAND.COM SCALE 1:3 DRAWN: JPW SHEET: 1 OF 1 DWG APPROVAL: TC
1.75
44.5
1.00
25.4
6.98
177.3
9.31
1.13 3.07
236.5
28.6 77.9
3.00 2.69
68.3 16.88
76.2
428.8
17.4
442
11.50
292.1 10.75
273.1
1/2" HARDWARE
14.63
371.6
2X .56
14.3
2.22 1.00
56.5 25.4
1.75 ALTERNATE TERMINAL
SPECIFIED BY ADDING "-CC"
44.5 TO ANY PCR MODEL NUMBER
1.75
2X .44 5.0
44.5
11.1 127 .38 1.04 ANSI Y14.5M 1994 APPLIES
DAIRYLAND DESCRIPTION
9.7 26.4 ELECTRICAL
INDUSTRIES, INC. PCR-15KA/80A OUTLINE DRAWING
.59
UNLESS NOTED 63 P.O. BOX 187 DOCUMENT # REV DATE DRAWN DWG SIZE DATE APPROVAL
15.1 UNITS: INCHES
3-PLACE: .005
STOUGHTON,
WI 53589 100087 A 2015-08-17 B
2-PLACE: .015 608-877-9900
1-PLACE / FRAC:
ANGULAR: 1
.03 DAIRYLAND.COM SCALE 3:10 DRAWN: JPW SHEET: 1 OF 1 DWG APPROVAL: