CATALOG

2019
Our Trademarks

by Aktif

Where we are?
Load Banks................................................................................................................................................................................................................................................................................4
Areas of Use.............................................................................................................................................................................................................................................................................4
Electrical Specifications...................................................................................................................................................................................................................................................4
Physical Properties..............................................................................................................................................................................................................................................................5
Load Bank Control Types...............................................................................................................................................................................................................................................6
Load Banks Coding.............................................................................................................................................................................................................................................................7

3
Load Banks are used performance tests of generators, UPS,
voltage regulators, power transformers, alternators and
test laboratories and also ensure to operate the generators
safely (dummy load) Aktif manufactures all type of load
banks with the required;

• Characteristics (R, L, C)
• Electrical characteristics (AC, DC, V, A, kW)
• Stage precision
• Control (manual, HMI-controlled or automatic)
• Measuring methods
• Installation (indoor or outdoor)
• Rack mounted, portable, stationary and trailer mounted
alternatives

2 MW 400 V 50 Hz Load Bank


Areas of Use
Load Banks are used in many industrial areas and applications.
As energy needs become more and more important day by
day, testing, protecting and maintaining the resources that
provide this energy temporarily or continuously is becoming
more and more important. Major areas of use of Load Banks
are listed below.

• Testing whether the products such as power transformer,


generator, alternator, UPS, regulator provide the design
values and reporting the electrical values read or
recorded during the test.
• Testing the generators, UPS or regulators after
maintenance or repair on site or workshop.
• No-load operation of generators is not requested. In this case,
automatically providing artificial load when the load supplied
by a generator falls below a certain level (ideally 30%)
• Automatic damping of the regenerative power which is
created when facilities where high-power motors are
Outdoor Type Load Bank (IP23 during test)
driven by regenerative drives are supplied by generators.
• Load dispatch test at power plants
• Testing of alternators used by military or civil air, road or
marine vehicles
• Controlled discharge and capacity testing of batteries
• Electrical and heat simulation and performance tests of
data centers with load banks
• Invertor performance tests

Electrical Specifications

Load Banks can be manufactured for AC (50/60/400 Hz) or


DC and AG or OG operating voltages.

Load banks based on load characteristics;

• Resistive (kW-cosø: 1)
• Inductive (kVAr)
• Resistive + Inductive + Capacitive (kVA-cosØ : requested)

Outdoor Type Load Bank (IP54 During Storage) Special designs can be made for different frequency and
cosø values.

AC Load Banks are designed in kW, kVAr or kVA and DC


Load Banks are designed in Current (A).
www.aktif.net 4
Load Banks
Load stage precisions can be 1 kW or 1 kVAr for AC or 1 A for
DC standard. Lower precision can be provided if requested.
The resistor material for resistive loads is stainless steel wire
which has low temperature coefficient. This ensures that
voltage and power levels are within tolerances even in case
of continuous operation.

Inductive loads are manufactured with aluminum or


copperconductor, low losses and iron core.

Resistive load resistors provide a large cooling surface for


forced cooling and are resistant to short-term overheating
and cooling.

The insulation level of load banks are 3 kV/1 minute for


the power circuit and 2 kV/1 minute for the control circuit.
Ceramic insulation materials resistant to electric and heat
are used for insulators.

Any flammable materials, including the cables, are not used


in the load compartment. All serial and/or parallel power
connections are made with busbar inside the terminal board.
Automatic load banks which work dummy load principle for 200 kW 400 V AC Automatic Dummy Load
generators are manufactured without fans and with natural
cooling up to 50 kW.

Single-phase or three-phase fans used on load banks cooled


with forced air are designed based on the power and volume
of resistors and the flow (m3/h) and pressure (pa) of the fan.
Fan and control supply can be supplied with external
source from the network or internal from the load bank
supply system with a selector switch. This feature provides
convenience for tests on site that is far away from network.

Physical Properties

Load Banks can manufactured IP20 protection level for


indoor use, IP20 for outdoor use under shelter or IP23 for
outdoor use on open area.
210 A 24 V DC Load Bank 50 A 24 V DC Load Bank
Load banks are manufactured portable and case-type up to
100 kW. Load banks up to 1000 kW are manufactured with
wheels, on request. Over than 500 kW load banks are usally
stationary. Load banks can be installed on a trailer and
transported by a vehicle on demand.

There are two types of load banks according to cooling


direction.

• horizontal air flow


• vertical air flow

6,6 kW 230 V 19’’ Data Center Load Bank

5 www.aktif.net
Load Banks
Load Bank Control Types
“N0” Control Model
“N0” control model is used if the customer wants to control the
load bank themselves.Load bank includes loads, fans, sensors
and an empty control panel. The power cables of the loads,
the supply of the fans and the contacts of the sensors are
drawn into the terminals in the empty control panel.
“N1” Control Model
It is the simplest and cheapest control model. Each load
phase is directly switched with miniature circuit breaker or
cam switches. A wattmeter is used for measurement.
“N2” Control Model
Loads are protected with miniature circuit breakers or
compact circuit breakers and switched with contactors. Load
contactors are controlled with buttons and their indicators
on the control panel.
The network analyzer on the control panel is used for
N1 – Control Model measurement. This analyzer allows reading of kW, kVAr,
kVA, A, V, f, cosø ... etc. Optionally, an analyzer with PC
communication (RS212, RS458 or USB port) is used to monitor
the measured values on the PC.
The following safety precautions are taken in the load bank;
• Overcurrent (with miniature circuit breakers or compact
circuit breakers)
• Overtemperature (with thermal contactors)
• Overvoltage and low voltage if requested
• Fan blowing error (with airflow sensor if the fan cannot
blow)
Loads can be switched on only when there is no safety issue.
“N3” Control Model
Loads are protected with miniature circuit breakers or
compact circuit breakers and switched with contactors. Load
contactors are controlled through the interface of touchscreen
“TFT LCD HMI Panel”. HMI runs with a microprocessor-based
electronic control board or in integration with the PLC and
with a communicating network analyzer.
Operator can manually switch on all loads individually or all
in one go via the HMI interface and can automatically control
N2 – Control Model with many control options and scenario. In addition, kW,
kVAr, kVA, A, V, f, cosø, etc. are monitored on the HMI screen.
These values can also be stored on the HMI’s memory card.
The following safety precautions are taken in the load bank
• Overcurrent (with miniature circuit breakers or compact
circuit breakers)
• Overtemperature (with thermal contactors)
• Overvoltage and low voltage if requested
• Fan blowing error (with airflow sensor if the fan cannot
blow)
Loads can be switched on only when there is no safety issue.
In addition, all errors are monitored on HMI screen.

N3 – Control Model

www.aktif.net 6
Load Banks

“N4” Control Model


Loads are protected with miniature circuit breakers or
compact circuit breakers and switched with contactors. Load
contactors are controlled through the computer software.
Operator can manually switch on all loads individually or all
in one go via the computer software and can automatically
control with many control options and scenario. In addition,
kW, kVAr, kVA, A, V, f, cosø, etc. are monitored on computer
software. These values can also be stored as an excel file in
the computer and memory card.
The following safety precautions are taken in the load bank
• Overcurrent (with miniature circuit breakers or compact
circuit breakers)
• Overtemperature (with thermal contactors)
2x250 A 28 V DC Load Bank for Automatic Control Alternator Test
• Overvoltage and low voltage if requested
• Fan blowing error (with airflow sensor if the fan cannot
blow)
For Indoor (IP 20) Use
Loads can be switched on only when there is no safety issue.
In addition, all errors are monitored on computer software. Power
Load Step
Enclosure Dimension
Resolution
“N5” Control Model KVA
kW kW - kVAr a [mm] b [mm] c [mm]
Loads are protected with miniature circuit breakers or (Cosfi 0,8)

compact circuit breakers and switched with contactors. Load 101 - 200 51 - 100 1-1 1350 900 1900
contactors are controlled through the interface of touchscreen 201 - 300 101 - 150 1-1 1500 900 1900
“TFT LCD HMI Panel”. HMI runs with a microprocessor-based
301 - 400 151 - 200 1-1 2000 1200 1790
electronic control board or in integration with the PLC and
with a communicating network analyzer. 401 - 500 201 - 250 1-1 2000 1300 1950
501 - 600 251 - 300 1-1 2150 1300 1950
No-load operation of generators is not requested. In this
case, Load Bank automatically provides artificial load by 601 - 800 301 - 400 1-1 2400 1400 2110
microprocessor-based electronic control board or PLC when 801 - 1000 401 - 500 1-1 2400 1600 2500
the load supplied by a generator falls below a certain level 1001 - 1250 501 - 625 1-1 2550 1600 2500
(ideally 30%).
1251 - 1500 626 - 750 1-1 2700 1600 2500
The following safety precautions are taken in the load bank 1751 - 2000 876 - 1000 1-1 2720 1900 3050
• Overcurrent (with miniature circuit breakers or compact 2001 - 2500 1001 - 1250 1-1 2870 1900 3050
circuit breakers) 2501 - 3000 1251 - 1500 1-1 3150 1900 3050
• Overtemperature (with thermal contactors)
• Overvoltage and low voltage if requested
b
• Fan blowing error (with airflow sensor if the fan cannot a
blow)
Loads can be switched on only when there is no safety issue.
In addition, all errors are monitored on HMI screen.

7 www.aktif.net
Load Banks
For Outdoor (IP23/IP54) Use
Load Step Enclosure Trailer
Power
Resolution Dimension Type
KVA c b
kW kW - kVAr a [mm] b [mm] kW kVA
(Cosfi 0,8) [mm]

101 - 200 51 - 100 1-1 1550 1050 1790 Tr-1 Tr-1 a


201 - 300 101 - 150 1-1 1700 1050 1790 Tr-1 Tr-2
301 - 400 151 - 200 1-1 2200 1350 1790 Tr-2 Tr-2
401 - 500 201 - 250 1-1 2200 1450 1950 Tr-2 Tr-2
501 - 600 251 - 300 1-1 2350 1450 1950 Tr-2 Tr-2
601 - 800 301 - 400 1-1 2600 1550 2110 Tr-2 Tr-3 c
801 - 1000 401 - 500 1-1 2600 1750 2500 Tr-2 Tr-3
1001 - 1250 501 - 625 1-1 2750 1750 2500 Tr-2 Tr-3
1251 - 1500 626 - 750 1-1 2900 1750 2500 Tr-2 Tr-5
1751 - 2000 876 - 1000 1-1 2920 2050 3050 Tr-4 Tr-5
2001 - 2500 1001 - 1250 1-1 3070 2050 3050 Tr-4 Tr-5
2501 - 3000 1251 - 1500 1-1 3350 2050 3050 Tr-4 Tr-5

Trailer Specifications
Max. Gross
Dimensions
Weight
Type Class Axles Type Axles Number Drawbar Type
a b c
[kg]
[mm] [mm] [mm]

Tr-1 2000 1500 700 1500 O2 Torsion 1 Constant


Tr-2 3500 2000 700 3500 O2 Torsion 2 Constant
Tr-3 3500 2000 750 5600 O3 Torsion 2 Adjustable
Tr-4 4000 2500 750 5600 O3 Torsion 2 Adjustable
Tr-5 7000 2500 1200 15000 O3 Air Suspended 2 Swivel

a
TR-1 b .

c
.

a
TR-2 b
.

c
.

a b
TR-3
.

c .

a b
TR-4
.

c .

a b
TR-5
.

c .

www.aktif.net 8
Load Banks Coding
L B 1 - 22 - 3333 4 5 6 - 777 88 9
L B Load Banks
1 Characteristics of Load
R : Resistive
L : Inductive
C : Resistive + Inductive or Resistive + Inductive + Capacative
22 Enclosure Type
00 : Special Dimension
01 : Standard Dimension (From 01 to 13)
C1 : 10 feet Container (Standard or High Cube)
C2 : 20 feet Container (Standard or High Cube)
C4 : 40 feet Container (Standard or High Cube)
R1 : Rack Mounted (Datacenter)
3333 Power in kW or kVA for AC systems, Current in A for DC
systems
0100 - 100 kW
1750 - 1750 kVA
0500 - 500 A
10M5 - 10500 kVA
4 Place of use
D : Indoor
H : Outdoor
5 Type of use
N : Normal, If there is a single entry
S : Selective, If there is more than one entry
(For example a single 200 A input at the load bank or 2x100 A
input if desired)
6 Control Type
0 : Without Control (Load Stages in Terminal Blocks)
1 : Controlled by manual circuit breakers or pako switches
2 : Manual button control (by contactors)
3 : Automatic HMI controlled (by PLC and Contactors)
4 : Automatic HMI and remote computer controlled
5 : Automatic ”Dummy load“ control
777 Voltage information in “Volt” for AC and DC systems
048 - 48 V
400 - 400 V
6K3 - 6,3 kV
88 Network information (1 Phase AC, 3 Phase AC or DC)
A1 : AC 1 Phase
A3 : AC 3 Phase
DC : DC
9 Air flow direction
H : Horizontal air flow
V : Vertical air flow
Examples:
1- LBR-03-0500HN3-400A3H
Description: 500 kW 3x400 VAC, horizontal airflow designed with enclosure number 3, single input, resistive, with automatic HMI
control, external type load bank
2- LBR-00-0250DS2-024DCV
Description: 2x125 A 24 VDC, vertical airflow designed with special sizes, two inputs, resistive, manual button control, internal
type load bank

B www.aktif.net
Switchgears and Substations
Metal Enclosed Switchgears
Metal Clad Switchgears
Mobile Substations White…
E-House / Compact Substations Color of the beginning…
White, color of the purity, honesty and clarity…
Power Resistors
Grounding Resistors Color of the stability and continuity, trust and quality…
Load Banks Since 2010, we decided to apply white color which symbolizes
Filter Resistors all of these values to all of our products.
Motor Control & Braking Resistors
Power Quality & Power Factor Correction
LV Capacitor & Filter Banks
MV Capacitor & Filter Banks
Capacitors & Harmonic Filter Reactors
Thyristor Switches
Medical Power & Control Panels
Operating Room Control Panels
Isolated Power Panel
Isolation Transformers
Automatic Transfer Relays
Smart Grid
Energy Management Systems
Metering & Submetering
Power Analyzers & Quality Recorders
Protection Devices
Traction Substation
Traction Rectifiers
DC Switchgears
DC Disconnectors
Traction Transformers
Renewable Energy & DC Conversion
High Power Rectifiers
Solar Inverters
Energy Storage Systems
EV Charging Stations
AGES - Grounding Transformers 20190201/Eng.

Group of Companies

Bayraktar Blv. Şehit sk. No: 5 Aktif Plaza Akşemsettin Mh. Çatalca sk. No:113 Pirahmetler mh. D-100 Yanyol cd.
34775 Ümraniye İstanbul / Turkey 06930 Sincan Ankara / Turkey No:78/A Erenler 54200 - Sakarya / Turkey
Tel : +90 (216) 314 93 20 Tel : +90 (312) 269 46 02 Tel : +90 (264) 276 64 50
Fax : +90 (216) 314 93 60 Fax : +90 (312) 269 45 01 Fax : +90 (264) 276 64 52
www.aktif.net - info@aktif.net www.aktif.net - info@aktif.net www.aktif.net - info@aktif.net

You might also like