Professional Documents
Culture Documents
Simatic st70 Chap03 English 2017
Simatic st70 Chap03 English 2017
© Siemens AG 2017
Siemens ST 70 · 2017
© Siemens AG 2017
■ Overview
• Compact controllers for the low to mid-performance ranges
• Large-scale integration, space-saving, powerful
• With exceptional real-time performance and powerful
communication options:
- Controller with integrated PROFINET IO interface for
communication between SIMATIC controllers, HMI,
3 programming device or other automation components
• All CPUs can be used in stand-alone mode, in networks and
within distributed structures
• Extremely simple installation, programming and operation
• Integrated web server with standard and user-specific web
pages
• Data logging functionality for archiving of data at runtime from
the user program
• Powerful, integrated technology functions such as counting,
measuring, closed-loop control, and motion control
• Integrated digital and analog inputs/outputs
• Flexible expansion facilities
- Signal boards for direct use in a controller
- Signal modules for expansion of controllers with input/output
channels; including an Energy Meter module for recording
and preparing energy data
- Accessories, e.g. power supply, switch module or SIMATIC
Memory Card
■ Technical specifications
General technical specifications SIMATIC S7-1200 General technical specifications SIPLUS S7-1200
Degree of protection IP20 acc. to IEC 529 Ambient temperature range -40/-25/-20 ... +55/+60/+70 °C
Ambient temperature Conformal coating Coating of the printed circuit boards
• Operation (95% humidity) and the electronic components
- Horizontal installation -20 ... +60 °C Technical specifications The technical specifications of the
3
- Vertical installation -20 ... +50 °C standard product apply except for
• Transportation and storage -40 ... +70 °C the ambient conditions.
- With 95% humidity 25 ... 55 °C Ambient conditions
Insulation Extended range of environmental
• 5/24 V DC circuits 500 V AC test voltage conditions
• 115/230 V AC circuits to ground 1500 V AC test voltage • with reference to ambient tempera- Tmin ... Tmax at
• 115/230 V AC circuits to 1500 V AC test voltage ture, air pressure and altitude 1080 hPa ... 795 hPa
115/230 V AC circuits (-1000 m ... +2000 m) //
Tmin ... (Tmax - 10K) at
• 230 V AC circuits to 1500 V AC test voltage
795 hPa ... 658 hPa
5/24 V DC circuits
(+2000 m ... +3500 m) //
• 115 V AC circuits to 1500 V AC test voltage Tmin ... (Tmax - 20K) at
5/24 V DC circuits 658 hPa ... 540 hPa
Electromagnetic compatibility Requirements of the EMC directive (+3500 m ... +5000 m)
• Noise immunity acc. to EN 50082-2 Test acc. to: • At cold restart, min. 0° C
IEC 801-2, IEC 801-3, IEC 801-4, Relative humidity
EN 50141, EN 50204, IEC 801-5,
• with condensation, max. 100%; RH incl. bedewing/frost
VDE 0160
(no commissioning in bedewed state)
• Emitted interference acc. to Test according to
EN 50081-1 and EN 50081-2 EN 55011, Class A, Resistance
Group 1 • to biologically active substances/ Yes; Class 3B2 mold and fungal
compliance with EN 60721-3-3 spores (except fauna); the supplied
Mechanical strength
plug covers must remain in place on
• Vibrations, test acc. to / tested with IEC 68, Part 2-6: the unused interfaces during opera-
10 ... 57 Hz; tion.
constant amplitude
• to chemically active substances/ Yes; Class 3C4 (RH < 75%) incl. salt
0.3 mm;
compliance with EN 60721-3-3 spray in accordance with EN 60068-
58 ... 150 Hz;
2-52 (severity 3); the supplied plug
constant acceleration 1 g (mounted
covers must remain in place on the
on DIN rail) or
unused interfaces during operation.
2 g (mounted in switchboard);
mode of vibration: • to mechanically active substances, Yes; Class 3S4 incl. sand, dust; the
frequency sweeps with a sweep rate compliance with EN 60721-3-3 supplied plug covers must remain in
of 1 octave/minute; place on unused interfaces during
duration of vibration: operation.
10 frequency sweeps per axis in
each direction of the three mutually
perpendicular axes
• Shocks, test acc. to / tested with IEC 68, Part 2-27/half-sine:
magnitude of shock 15 g (peak
value), duration 11 ms,
6 shocks in each of the three mutually
perpendicular axes
■ Overview
• Controller for intro to S7
• Expandable by:
- 1 signal board (SB), battery board (BB) or communication
board (CB)
- Max. 3 communication modules (CM)
■ Technical specifications
Article number 6ES7211-1BE40-0XB0 6ES7211-1AE40-0XB0 6ES7211-1HE40-0XB0
CPU 1211C, AC/DC/RELAY, CPU 1211C, DC/DC/DC, CPU 1211C, DC/DC/RELAY,
6DI/4DO/2AI 6DI/4DO/2AI 6DI/4DO/2AI
General information
Product type designation CPU 1211C AC/DC/Relay CPU 1211C DC/DC/DC CPU 1211C DC/DC/Relay
Engineering with
• Programming package STEP 7 V14 or higher STEP 7 V14 or higher STEP 7 V14 or higher
Supply voltage
Rated value (DC)
• 24 V DC Yes Yes
Rated value (AC)
• 120 V AC Yes
• 230 V AC Yes
Encoder supply
24 V encoder supply
• 24 V 20.4 to 28.8V L+ minus 4 V DC min. L+ minus 4 V DC min.
Power loss
Power loss, typ. 10 W 8W 8W
Memory
Work memory
• integrated 50 kbyte 50 kbyte 50 kbyte
Load memory
• integrated 1 Mbyte 1 Mbyte 1 Mbyte
• Plug-in (SIMATIC Memory Card), with SIMATIC memory card with SIMATIC memory card with SIMATIC memory card
max.
Backup
• without battery Yes Yes Yes
CPU processing times
for bit operations, typ. 0.085 µs; / instruction 0.085 µs; / instruction 0.085 µs; / instruction
for word operations, typ. 1.7 µs; / instruction 1.7 µs; / instruction 1.7 µs; / instruction
for floating point arithmetic, typ. 2.3 µs; / instruction 2.3 µs; / instruction 2.3 µs; / instruction
Data areas and their retentivity
Flag
• Number, max. 4 kbyte; Size of bit memory address 4 kbyte; Size of bit memory address 4 kbyte; Size of bit memory address
area area area
Process image
• Inputs, adjustable 1 kbyte 1 kbyte 1 kbyte
• Outputs, adjustable 1 kbyte 1 kbyte 1 kbyte
Time of day
Clock
• Hardware clock (real-time) Yes Yes Yes
3 - LAD
- FBD
Yes
Yes
Yes
Yes
Yes
Yes
- SCL Yes Yes Yes
Dimensions
Width 90 mm 90 mm 90 mm
Height 100 mm 100 mm 100 mm
Depth 75 mm 75 mm 75 mm
Weights
Weight, approx. 420 g 370 g 380 g
3
SIM 1274 simulator module Windows 7 Professional SP1
(optional) (64-bit),
Windows 7 Enterprise SP1 (64-bit),
8 input switches, 6ES7274-1XF30-0XA0 Windows 7 Ultimate SP1 (64-bit),
for CPU 1211C / CPU 1212C Windows 8.1 Professional (64-bit),
Analog input simulator Windows 8.1 Enterprise (64-bit),
SIM 1274 simulator module Windows 10 Professional
(optional) Version 1607,
Windows 10 Enterprise
2 potentiometers 6ES7274-1XA30-0XA0 Version 1607,
Windows 10 Enterprise 2016 LTSB,
SIMATIC Memory Card (optional) Windows 10 Enterprise 2015 LTSB,
4 MB 6ES7954-8LC02-0AA0 Windows Server 2008 R2 StdE
(full installation),
12 MB 6ES7954-8LE02-0AA0 Windows Server 2012 StdE
(full installation),
24 MB 6ES7954-8LF02-0AA0 Windows Server 2016 Standard
256 MB 6ES7954-8LL02-0AA0 (full installation);
2 GB 6ES7954-8LP02-0AA0 STEP 7 Basic V14 SP1 in addition:
Windows 7 Home Premium SP1
32 GB 6ES7954-8LT03-0AA0 (64-bit),
Windows 8.1 (64-bit),
Terminal block (spare part) Windows 10 Home Version 1607
For CPU 1211C AC/DC/relay Type of delivery:
• For DI, with 14 screws, tin-coated, 6ES7292-1AP40-0XA0 German, English, Chinese, Italian,
coded; 4 units French, Spanish
• For DO, with 8 screws, tin-coated, 6ES7292-1AH40-0XA0 STEP 7 Professional V14 SP1, 6ES7822-1AA04-0YA5
coded; 4 units floating license
• For AI, with 3 screws, gold-plated; 6ES7292-1BC30-0XA0
4 units STEP 7 Professional V14 SP1, 6ES7822-1AE04-0YA5
floating license, software download
For CPU 1211C DC/DC/DC incl. license key 1)
• For DI, with 14 screws, tin-coated; 6ES7292-1AP30-0XA0 Email address required for delivery
4 units
• For DO, with 8 screws, tin-coated; 6ES7292-1AH30-0XA0 STEP 7 Basic V14 SP1, 6ES7822-0AA04-0YA5
4 units floating license
• For AI, with 3 screws, gold-plated; 6ES7292-1BC30-0XA0 STEP 7 Basic V14 SP1, 6ES7822-0AE04-0YA5
4 units floating license,
software download incl. license
For CPU 1211C DC/DC/relay key1)
• For DI, with 14 screws, tin-coated; 6ES7292-1AP30-0XA0
4 units Email address required for delivery
• For DO, with 8 screws, tin-coated, 6ES7292-1AH40-0XA0
coded; 4 units
• For AI, with 3 screws, gold-plated; 6ES7292-1BC30-0XA0
4 units
RJ45 cable grip
4 units per pack
Single port 6ES7290-3AA30-0XA0
Front flap set (spare part)
For CPU 1211C/1212C 6ES7291-1AA30-0XA0
1)
For up-to-date information and download availability, see:
http://www.siemens.com/tia-online-software-delivery
■ Overview
• Controller for intro to S7 with basic expansion options
• Expandable by:
- 1 signal board (SB), battery board (BB) or communication
board (CB)
- 2 signal modules (SM)
- Max. 3 communication modules (CM)
3
■ Technical specifications
Article number 6ES7212-1BE40-0XB0 6ES7212-1AE40-0XB0 6ES7212-1HE40-0XB0
CPU 1212C, AC/DC/RELAY, CPU 1212C ,DC/DC/DC, CPU 1212C, DC/DC/RELAY,
8DI/6DO/2AI 8DI/6DO/2AI 8DI/6DO/2AI
General information
Product type designation CPU 1212C AC/DC/Relay CPU 1212C DC/DC/DC CPU 1212C DC/DC/Relay
Engineering with
• Programming package STEP 7 V14 or higher STEP 7 V14 or higher STEP 7 V14 or higher
Supply voltage
Rated value (DC)
• 24 V DC Yes Yes
Rated value (AC)
• 120 V AC Yes
• 230 V AC Yes
Encoder supply
24 V encoder supply
• 24 V 20.4 to 28.8V L+ minus 4 V DC min. L+ minus 4 V DC min.
Power loss
Power loss, typ. 11 W 9W 9W
Memory
Work memory
• integrated 75 kbyte 75 kbyte 75 kbyte
Load memory
• integrated 2 Mbyte 2 Mbyte 2 Mbyte
• Plug-in (SIMATIC Memory Card), with SIMATIC memory card with SIMATIC memory card with SIMATIC memory card
max.
Backup
• without battery Yes Yes Yes
CPU processing times
for bit operations, typ. 0.085 µs; / instruction 0.085 µs; / instruction 0.085 µs; / instruction
for word operations, typ. 1.7 µs; / instruction 1.7 µs; / instruction 1.7 µs; / instruction
for floating point arithmetic, typ. 2.3 µs; / instruction 2.3 µs; / instruction 2.3 µs; / instruction
Data areas and their retentivity
Flag
• Number, max. 4 kbyte; Size of bit memory address 4 kbyte; Size of bit memory address 4 kbyte; Size of bit memory address
area area area
Process image
• Inputs, adjustable 1 kbyte 1 kbyte 1 kbyte
• Outputs, adjustable 1 kbyte 1 kbyte 1 kbyte
3 • min.
• max.
-20 °C
60 °C; Number of simultaneously
-20 °C
60 °C; Number of simultaneously
-20 °C
60 °C; Number of simultaneously
activated inputs or outputs 4 or 3 activated inputs or outputs 4 or 3 activated inputs or outputs 4 or 3
(no adjacent points) at 60 °C horizontal (no adjacent points) at 60 °C horizontal (no adjacent points) at 60 °C horizontal
or 50 °C vertical, 8 or 6 at 55 °C or 50 °C vertical, 8 or 6 at 55 °C or 50 °C vertical, 8 or 6 at 55 °C
horizontal or 45 °C vertical horizontal or 45 °C vertical horizontal or 45 °C vertical
Pollutant concentrations
- SO2 at RH < 60% without S02: < 0.5 ppm; H2S: < 0.1 ppm; S02: < 0.5 ppm; H2S: < 0.1 ppm; S02: < 0.5 ppm; H2S: < 0.1 ppm;
condensation RH < 60% condensation-free RH < 60% condensation-free RH < 60% condensation-free
Configuration
Programming
Programming language
- LAD Yes Yes Yes
- FBD Yes Yes Yes
- SCL Yes Yes Yes
Dimensions
Width 90 mm 90 mm 90 mm
Height 100 mm 100 mm 100 mm
Depth 75 mm 75 mm 75 mm
Weights
Weight, approx. 425 g 370 g 385 g
3
• For AI, with 3 screws, gold-plated; 6ES7292-1BC30-0XA0
1 input for resistance temperature 4 units
sensors Pt 100, Pt 200, Pt 500,
Pt 1000, resolution 15 bits + sign For CPU 1212C DC/DC/relay
SB 1232 signal board 6ES7232-4HA30-0XB0 • For DI, with 14 screws, tin-coated; 6ES7292-1AP30-0XA0
4 units
1 analog output, ±10 V with 12 bits • For DO, with 8 screws, tin-coated, 6ES7292-1AH40-0XA0
or 0 to 20 mA with 11 bits coded; 4 units
CB 1241 RS 485 6ES7241-1CH30-1XB0 • For AI, with 3 screws, gold-plated; 6ES7292-1BC30-0XA0
communication board 4 units
For point-to-point connection, RJ45 cable grip
with 1 RS 485 interface 4 units per pack
BB1297 battery board 6ES7297-0AX30-0XA0 Single port 6ES7290-3AA30-0XA0
For long-term backup of real-time
Front flap set (spare part)
clock, can be plugged into the
signal board slot; For CPU 1211C/1212C 6ES7291-1AA30-0XA0
battery (CR1025) is not included
STEP 7 Professional / Basic
Digital input simulator V14 SP1
SIM 1274 simulator module
(optional) Target system:
SIMATIC S7-1200, S7-1500,
8 input switches, 6ES7274-1XF30-0XA0 S7-300, S7-400, WinAC
for CPU 1211C / CPU 1212C
Requirement:
Analog input simulator Windows 7 Professional SP1
SIM 1274 simulator module (64-bit),
(optional) Windows 7 Enterprise SP1 (64-bit),
Windows 7 Ultimate SP1 (64-bit),
2 potentiometers 6ES7274-1XA30-0XA0 Windows 8.1 Professional (64-bit),
SIMATIC Memory Card (optional) Windows 8.1 Enterprise (64-bit),
Windows 10 Professional
4 MB 6ES7954-8LC02-0AA0 Version 1607,
Windows 10 Enterprise
12 MB 6ES7954-8LE02-0AA0 Version 1607,
24 MB 6ES7954-8LF02-0AA0 Windows 10 Enterprise 2016 LTSB,
Windows 10 Enterprise 2015 LTSB,
256 MB 6ES7954-8LL02-0AA0 Windows Server 2008 R2 StdE
(full installation),
2 GB 6ES7954-8LP02-0AA0
Windows Server 2012 StdE
32 GB 6ES7954-8LT03-0AA0 (full installation),
Windows Server 2016 Standard
Extension cable for 6ES7290-6AA30-0XA0 (full installation);
two-tier configuration
STEP 7 Basic V14 SP1 in addition:
For connecting digital/analog Windows 7 Home Premium SP1
signal modules; (64-bit),
length 2 m Windows 8.1 (64-bit),
Windows 10 Home Version 1607
Starter box CPU 1212C 6ES7212-1BD34-4YB0
AC/DC/relay Type of delivery:
German, English, Chinese, Italian,
Complete offer SIMATIC S7-1200, French, Spanish
starter box, comprising:
CPU 1212C AC/DC/relay, simulator, STEP 7 Professional V14 SP1, 6ES7822-1AA04-0YA5
STEP 7 BASIC CD, manual CD, info floating license
material, in Systainer STEP 7 Professional V14 SP1, 6ES7822-1AE04-0YA5
Terminal block (spare part) floating license, software download
incl. license key 1)
For CPU 1212C AC/DC/relay
Email address required for delivery
• For DI, with 14 screws, tin-coated, 6ES7292-1AP40-0XA0
coded; 4 units STEP 7 Basic V14 SP1, 6ES7822-0AA04-0YA5
• For DO, with 8 screws, tin-coated, 6ES7292-1AH40-0XA0 floating license
coded; 4 units STEP 7 Basic V14 SP1, 6ES7822-0AE04-0YA5
• For AI, with 3 screws, gold-plated; 6ES7292-1BC30-0XA0 floating license, software download
4 units incl. license key1)
Email address required for delivery
1) For up-to-date information and download availability, see:
http://www.siemens.com/tia-online-software-delivery
■ Overview
• Controller for intro to S7 with flexible expansion options
• Expandable by:
- 1 signal board (SB), battery board (BB) or communication
board (CB)
- 8 signal modules (SM)
- Max. 3 communication modules (CM)
3
■ Technical specifications
Article number 6ES7214-1BG40-0XB0 6ES7214-1AG40-0XB0 6ES7214-1HG40-0XB0
CPU 1214C, AC/DC/RELAY, CPU 1214C, DC/DC/DC, CPU 1214C, DC/DC/RELAY,
14DI/10DO/2AI 14DI/10DO/2AI 14DI/10DO/2AI
General information
Product type designation CPU 1214C AC/DC/Relay CPU 1214C DC/DC/DC CPU 1214C DC/DC/Relay
Engineering with
• Programming package STEP 7 V14 or higher STEP 7 V14 or higher STEP 7 V14 or higher
Supply voltage
Rated value (DC)
• 24 V DC Yes Yes
Rated value (AC)
• 120 V AC Yes
• 230 V AC Yes
Encoder supply
24 V encoder supply
• 24 V 20.4 to 28.8V L+ minus 4 V DC min. L+ minus 4 V DC min.
Power loss
Power loss, typ. 14 W 12 W 12 W
Memory
Work memory
• integrated 100 kbyte 100 kbyte 100 kbyte
Load memory
• integrated 4 Mbyte 4 Mbyte 4 Mbyte
• Plug-in (SIMATIC Memory Card), with SIMATIC memory card with SIMATIC memory card with SIMATIC memory card
max.
Backup
• without battery Yes Yes Yes
CPU processing times
for bit operations, typ. 0.085 µs; / instruction 0.085 µs; / instruction 0.085 µs; / instruction
for word operations, typ. 1.7 µs; / instruction 1.7 µs; / instruction 1.7 µs; / instruction
for floating point arithmetic, typ. 2.3 µs; / instruction 2.3 µs; / instruction 2.3 µs; / instruction
Data areas and their retentivity
Flag
• Number, max. 8 kbyte; Size of bit memory address 8 kbyte; Size of bit memory address 8 kbyte; Size of bit memory address
area area area
Process image
• Inputs, adjustable 1 kbyte 1 kbyte 1 kbyte
• Outputs, adjustable 1 kbyte 1 kbyte 1 kbyte
Time of day
Clock
• Hardware clock (real-time) Yes Yes Yes
3 - LAD
- FBD
Yes
Yes
Yes
Yes
Yes
Yes
- SCL Yes Yes Yes
Dimensions
Width 110 mm 110 mm 110 mm
Height 100 mm 100 mm 100 mm
Depth 75 mm 75 mm 75 mm
Weights
Weight, approx. 455 g 415 g 435 g
3
SIM 1274 simulator module
(optional) STEP 7 Professional / Basic
V14 SP1
14 input switches, 6ES7274-1XH30-0XA0
for CPU 1214C/1215C Target system:
SIMATIC S7-1200, S7-1500,
Analog input simulator S7-300, S7-400, WinAC
SIM 1274 simulator module
(optional) Requirement:
Windows 7 Professional SP1
2 potentiometers 6ES7274-1XA30-0XA0 (64-bit),
Windows 7 Enterprise SP1 (64-bit),
SIMATIC Memory Card (optional) Windows 7 Ultimate SP1 (64-bit),
4 MB 6ES7954-8LC02-0AA0 Windows 8.1 Professional (64-bit),
Windows 8.1 Enterprise (64-bit),
12 MB 6ES7954-8LE02-0AA0 Windows 10 Professional
24 MB 6ES7954-8LF02-0AA0 Version 1607,
Windows 10 Enterprise
256 MB 6ES7954-8LL02-0AA0 Version 1607,
Windows 10 Enterprise 2016 LTSB,
2 GB 6ES7954-8LP02-0AA0 Windows 10 Enterprise 2015 LTSB,
32 GB 6ES7954-8LT03-0AA0 Windows Server 2008 R2 StdE
(full installation),
Extension cable for 6ES7290-6AA30-0XA0 Windows Server 2012 StdE
two-tier configuration (full installation),
Windows Server 2016 Standard
For connecting digital/analog (full installation);
signal modules;
length 2 m STEP 7 Basic V14 SP1 in addition:
Windows 7 Home Premium SP1
Terminal block (spare part) (64-bit),
For CPU 1214C AC/DC/relay Windows 8.1 (64-bit),
Windows 10 Home Version 1607
• For DI, with 20 screws, tin-coated, 6ES7292-1AV40-0XA0
coded; 4 units Type of delivery:
• For DO, with 12 screws, 6ES7292-1AM40-0XA0 German, English, Chinese, Italian,
tin-coated, coded; 4 units French, Spanish
• For AI, with 3 screws, gold-plated; 6ES7292-1BC30-0XA0 STEP 7 Professional V14 SP1, 6ES7822-1AA04-0YA5
4 units floating license
For CPU 1214C DC/DC/DC STEP 7 Professional V14 SP1, 6ES7822-1AE04-0YA5
• For DI, with 20 screws, tin-coated; 6ES7292-1AV30-0XA0 floating license, software download
4 units incl. license key 1)
• For DO, with 12 screws, 6ES7292-1AM30-0XA0 Email address required for delivery
tin-coated; 4 units
STEP 7 Basic V14 SP1, 6ES7822-0AA04-0YA5
• For AI, with 3 screws, gold-plated; 6ES7292-1BC30-0XA0 floating license
4 units
STEP 7 Basic V14 SP1, 6ES7822-0AE04-0YA5
For CPU 1214C DC/DC/relay floating license, software download
• For DI, with 20 screws, tin-coated; 6ES7292-1AV30-0XA0 incl. license key1)
4 units
Email address required for delivery
• For DO, with 12 screws, 6ES7292-1AM40-0XA0
tin-coated, coded; 4 units
• For AI, with 3 screws, gold-plated; 6ES7292-1BC30-0XA0
4 units
1) For up-to-date information and download availability, see:
http://www.siemens.com/tia-online-software-delivery
■ Overview
• Powerful controller with enhanced networking option
• Expandable by:
- 1 signal board (SB), battery board (BB) or communication
board (CB)
- 8 signal modules (SM)
- Max. 3 communication modules (CM)
3
■ Technical specifications
Article number 6ES7215-1BG40-0XB0 6ES7215-1AG40-0XB0 6ES7215-1HG40-0XB0
CPU 1215C, AC/DC/RLY, CPU 1215C, DC/DC/DC, CPU 1215C, DC/DC/RLY,
14DI/10DO/2AI/2AO 14DI/10DO/2AI/2AO 14DI/10DO/2AI/2AO
General information
Product type designation CPU 1215C AC/DC/Relay CPU 1215C DC/DC/DC CPU 1215C DC/DC/Relay
Engineering with
• Programming package STEP 7 V14 or higher STEP 7 V14 or higher STEP 7 V14 or higher
Supply voltage
Rated value (DC)
• 24 V DC Yes Yes
Rated value (AC)
• 120 V AC Yes
• 230 V AC Yes
Encoder supply
24 V encoder supply
• 24 V 20.4 to 28.8V L+ minus 4 V DC min. L+ minus 4 V DC min.
Power loss
Power loss, typ. 14 W 12 W 12 W
Memory
Work memory
• integrated 125 kbyte 125 kbyte 125 kbyte
Load memory
• integrated 4 Mbyte 4 Mbyte 4 Mbyte
• Plug-in (SIMATIC Memory Card), with SIMATIC memory card with SIMATIC memory card with SIMATIC memory card
max.
Backup
• without battery Yes Yes Yes
CPU processing times
for bit operations, typ. 0.085 µs; / instruction 0.085 µs; / instruction 0.085 µs; / instruction
for word operations, typ. 1.7 µs; / instruction 1.7 µs; / instruction 1.7 µs; / instruction
for floating point arithmetic, typ. 2.3 µs; / instruction 2.3 µs; / instruction 2.3 µs; / instruction
Data areas and their retentivity
Flag
• Number, max. 8 kbyte; Size of bit memory address 8 kbyte; Size of bit memory address 8 kbyte; Size of bit memory address
area area area
Process image
• Inputs, adjustable 1 kbyte 1 kbyte 1 kbyte
• Outputs, adjustable 1 kbyte 1 kbyte 1 kbyte
Time of day
Clock
• Hardware clock (real-time) Yes Yes Yes
3 - LAD
- FBD
Yes
Yes
Yes
Yes
Yes
Yes
- SCL Yes Yes Yes
Dimensions
Width 130 mm 130 mm 130 mm
Height 100 mm 100 mm 100 mm
Depth 75 mm 75 mm 75 mm
Weights
Weight, approx. 550 g 500 g 585 g
3
SIM 1274 simulator module
(optional) STEP 7 Professional / Basic
V14 SP1
2 potentiometers 6ES7274-1XA30-0XA0
Target system:
SIMATIC Memory Card (optional) SIMATIC S7-1200, S7-1500,
4 MB 6ES7954-8LC02-0AA0 S7-300, S7-400, WinAC
Requirement:
12 MB 6ES7954-8LE02-0AA0 Windows 7 Professional SP1
24 MB 6ES7954-8LF02-0AA0 (64-bit),
Windows 7 Enterprise SP1 (64-bit),
256 MB 6ES7954-8LL02-0AA0 Windows 7 Ultimate SP1 (64-bit),
2 GB 6ES7954-8LP02-0AA0 Windows 8.1 Professional (64-bit),
Windows 8.1 Enterprise (64-bit),
32 GB 6ES7954-8LT03-0AA0 Windows 10 Professional
Version 1607,
Extension cable for 6ES7290-6AA30-0XA0 Windows 10 Enterprise
two-tier configuration Version 1607,
For connecting digital/analog Windows 10 Enterprise 2016 LTSB,
signal modules; Windows 10 Enterprise 2015 LTSB,
length 2 m Windows Server 2008 R2 StdE
(full installation),
Terminal block (spare part) Windows Server 2012 StdE
(full installation),
For CPU 1215C AC/DC/relay Windows Server 2016 Standard
• For DI, with 20 screws, tin-coated, 6ES7292-1AV40-0XA0 (full installation);
coded; 4 units
STEP 7 Basic V14 SP1 in addition:
• For DO, with 12 screws, 6ES7292-1AM40-0XA0 Windows 7 Home Premium SP1
tin-coated, coded; 4 units (64-bit),
• For analog units, with 6 screws, 6ES7292-1BF30-0XB0 Windows 8.1 (64-bit),
gold-plated; 4 units Windows 10 Home Version 1607
For CPU 1215C DC/DC/DC Type of delivery:
• For DI, with 20 screws, tin-coated; 6ES7292-1AV30-0XA0 German, English, Chinese, Italian,
4 units French, Spanish
• For DO, with 12 screws, 6ES7292-1AM30-0XA0 STEP 7 Professional V14 SP1, 6ES7822-1AA04-0YA5
tin-coated; 4 units floating license
• For analog units, with 6 screws, 6ES7292-1BF30-0XB0
gold-plated; 4 units STEP 7 Professional V14 SP1, 6ES7822-1AE04-0YA5
floating license, software download
For CPU 1215C DC/DC/relay incl. license key 1)
• For DI, with 20 screws, tin-coated; 6ES7292-1AV30-0XA0 Email address required for delivery
4 units
STEP 7 Basic V14 SP1, 6ES7822-0AA04-0YA5
• For DO, with 12 screws, 6ES7292-1AM40-0XA0
floating license
tin-coated, coded; 4 units
• For analog units, with 6 screws, 6ES7292-1BF30-0XB0 STEP 7 Basic V14 SP1, 6ES7822-0AE04-0YA5
gold-plated; 4 units floating license, software download
incl. license key1)
Email address required for delivery
1)
For up-to-date information and download availability, see:
http://www.siemens.com/tia-online-software-delivery
■ Overview
• Powerful controller for extremely fast signal processing
• Expandable by:
- 1 signal board (SB), battery board (BB) or communication
board (CB)
- 8 signal modules (SM)
- Max. 3 communication modules (CM)
3
■ Technical specifications
Article number 6ES7217-1AG40-0XB0 Article number 6ES7217-1AG40-0XB0
CPU 1217C, DC/DC/DC, CPU 1217C, DC/DC/DC,
14DI/10DQ/2AI/2AQ 14DI/10DQ/2AI/2AQ
General information Time of day
Product type designation CPU 1217C DC/DC/DC Clock
Engineering with • Hardware clock (real-time) Yes
• Programming package STEP 7 V14 or higher Digital inputs
Supply voltage Number of digital inputs 14; Integrated
Rated value (DC) • of which inputs usable for 6; HSC (High Speed Counting)
• 24 V DC Yes technological functions
Encoder supply Digital outputs
24 V encoder supply Number of digital outputs 10
• 24 V L+ minus 4 V DC min. • of which high-speed outputs 4; 100 kHz Pulse Train Output
Power loss Analog inputs
Power loss, typ. 12 W Number of analog inputs 2
Memory Input ranges
Work memory • Voltage Yes
• integrated 150 kbyte Analog outputs
Load memory Number of analog outputs 2
• integrated 4 Mbyte Output ranges, current
• Plug-in (SIMATIC Memory Card), with SIMATIC memory card • 0 to 20 mA Yes
max. 1. Interface
Backup Interface type PROFINET
• without battery Yes Physics Ethernet
CPU processing times Functionality
for bit operations, typ. 0.085 µs; / instruction • PROFINET IO Controller Yes
for word operations, typ. 1.7 µs; / instruction • PROFINET IO Device Yes
for floating point arithmetic, typ. 2.3 µs; / Operation • SIMATIC communication Yes
Data areas and their retentivity • Open IE communication Yes
Flag • Web server Yes
• Number, max. 8 kbyte; Size of bit memory address • Media redundancy Yes; as MRP client
area
Process image
• Inputs, adjustable 1 kbyte
• Outputs, adjustable 1 kbyte
■ Overview
• The clever compact solution
• With 10 integrated I/Os
• Expandable with:
- 1 signal board (SB) or communication board (CB);
not possible with: 6AG1211-1AE31-2XB0,
6AG1211-1BE31-2XB0, 6AG1211-1HE31-2XB0
- Max. 3 communication modules (CM)
3
Note:
SIPLUS extreme products are based on SIMATIC standard
products. The contents listed here were taken from the respec-
tive standard products. SIPLUS extreme-specific information
was added.
■ Technical specifications
Article number 6AG1211-1AE31-4XB0 6AG1211-1AE31-2XB0
Based on 6ES7211-1AE31-0XB0 6ES7211-1AE31-0XB0
SIPLUS S7-1200 CPU1211 DC/DC/DC SIPLUS S7-1200 CPU1211 DC/DC/DC
Ambient conditions
Ambient temperature during
operation
• min. -20 °C; = Tmin; Startup @ 0 °C -40 °C; = Tmin; Startup @ -25 °C
• max. 60 °C; = Tmax 70 °C; = Tmax; > +60 °C Number of simultaneously
controllable inputs and outputs max. 50%;
no signal board can be used
Extended ambient conditions
• relative to ambient temperature- Tmin ... Tmax at 1080 hPa ... 795 hPa Tmin ... Tmax at 1080 hPa ... 795 hPa
atmospheric pressure-installation (-1000 m ... +2000 m) // (-1000 m ... +2000 m) //
altitude Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa
(+2000 m ... +3500 m) // (+2000 m ... +3500 m) //
Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa
(+3500 m ... +5000 m) (+3500 m ... +5000 m)
• At cold restart, min. 0 °C -25 °C
Relative humidity
- With condensation, tested in 100%; RH incl. condensation/frost (no commissioning 100%; RH incl. condensation/frost (no commissioning
accordance with IEC 60068-2-38, under condensation conditions) under condensation conditions)
max.
Resistance
- against biologically active Yes; Class 3B2 mold, fungus and dry rot spores (with the Yes; Class 3B2 mold, fungus and dry rot spores (with the
substances / conformity with exception of fauna). The supplied connector covers must exception of fauna). The supplied connector covers must
EN 60721-3-3 remain on the unused interfaces during operation! remain on the unused interfaces during operation!
- against chemically active Yes; Class 3C4 (RH < 75%) incl. salt spray according to Yes; Class 3C4 (RH < 75%) incl. salt spray according to
substances / conformity with EN 60068-2-52 (degree of severity 3). The supplied EN 60068-2-52 (degree of severity 3). The supplied
EN 60721-3-3 connector covers must remain on the unused interfaces connector covers must remain on the unused interfaces
during operation! during operation!
- against mechanically active Yes; Class 3S4 incl. sand, dust. The supplied connector Yes; Class 3S4 incl. sand, dust. The supplied connector
substances / conformity with covers must remain on the unused interfaces during covers must remain on the unused interfaces during
EN 60721-3-3 operation! operation!
3 • min.
• max.
-20 °C; = Tmin; Startup @ 0 °C
60 °C; = Tmax
-40 °C; = Tmin; Startup @ -25 °C
70 °C; = Tmax; > +60 °C Number of simultaneously
controllable inputs and outputs max. 50%;
no signal board can be used
Extended ambient conditions
• relative to ambient temperature- Tmin ... Tmax at 1080 hPa ... 795 hPa Tmin ... Tmax at 1080 hPa ... 795 hPa
atmospheric pressure-installation (-1000 m ... +2000 m) // (-1000 m ... +2000 m) //
altitude Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa
(+2000 m ... +3500 m) // (+2000 m ... +3500 m) //
Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa
(+3500 m ... +5000 m) (+3500 m ... +5000 m)
• At cold restart, min. 0 °C -25 °C
Relative humidity
- With condensation, tested in 100%; RH incl. condensation/frost (no commissioning 100%; RH incl. condensation/frost (no commissioning
accordance with IEC 60068-2-38, under condensation conditions) under condensation conditions)
max.
Resistance
- against biologically active Yes; Class 3B2 mold, fungus and dry rot spores (with the Yes; Class 3B2 mold, fungus and dry rot spores (with the
substances / conformity with exception of fauna). The supplied connector covers must exception of fauna). The supplied connector covers must
EN 60721-3-3 remain on the unused interfaces during operation! remain on the unused interfaces during operation!
- against chemically active Yes; Class 3C4 (RH < 75%) incl. salt spray according to Yes; Class 3C4 (RH < 75%) incl. salt spray according to
substances / conformity with EN 60068-2-52 (degree of severity 3). The supplied EN 60068-2-52 (degree of severity 3). The supplied
EN 60721-3-3 connector covers must remain on the unused interfaces connector covers must remain on the unused interfaces
during operation! during operation!
3
IEC type 1 current sinking; -25 ... +55 °C
2 transistor outputs 24 V DC,
0.5 A, 5 W; 1 analog output, ±10 V with 12 bits 6AG1232-4HA30-5XB0
can be used as HSC at up to or 0 ... 20 mA with 11 bits
30 kHz Ambient temperature range
• Suitable for areas with extreme 6AG1223-0BD30-4XB0 0 ... +55 °C
medial exposure
(conformal coating) 1 analog output, ±10 V with 12 bits 6AG1232-4HA30-4XB0
or 0 ... 20 mA with 11 bits
• Ambient temperature 6AG1223-0BD30-5XB0
-25 ... +55 °C SIPLUS CB 1241 RS 485
communication board
2 inputs, 5 V DC, 200 kHz 6AG1223-3AD30-5XB0
2 outputs 5 V DC, 0.1 A, 200 kHz (Extended temperature range and
exposure to media; cannot be used
2 inputs, 24 V DC, 200 kHz 6AG1223-3BD30-5XB0 with 6AG1211-1....-2XB0)
2 outputs 24 V DC, 0.1 A, 200 kHz
For point-to-point connection, 6AG1241-1CH30-5XB1
with 1 RS 485 interface
Additional accessories See SIMATIC S7-1200
CPU 1211C, page 3/6
■ Overview
• The superior compact solution
• With 14 integral input/outputs
• Expandable by:
- 1 signal board (SB) or communication board (CB);
not possible with: 6AG1212-1AE31-2XB0,
6AG1212-1BE31-2XB0, 6AG1212-1HE31-2XB0
- 2 signal modules (SM)
- Max. 3 communication modules (CM)
3
Note:
SIPLUS extreme products are based on SIMATIC standard
products. The contents listed here were taken from the respec-
tive standard products. SIPLUS extreme-specific information
was added.
■ Technical specifications
Article number 6AG1212-1AE40-4XB0 6AG1212-1AE40-2XB0
Based on 6ES7212-1AE40-0XB0 6ES7212-1AE40-0XB0
SIPLUS S7-1200 CPU 1212C DC/DC/DC SIPLUS S7-1200 CPU 1212C DC/DC/DC
Ambient conditions
Ambient temperature during
operation
• min. -20 °C; = Tmin; Startup @ 0 °C -40 °C; = Tmin; Startup @ -25 °C
• max. 60 °C; Number of simultaneously activated inputs or 70 °C; = Tmax; Tmax > +55 °C number of simultaneously
outputs 4 or 3 (no adjacent points) at 60 °C horizontal or switched-on digital inputs 4, digital outputs 3, analog
50 °C vertical, 8 or 6 at 55 °C horizontal or 45 °C vertical inputs 2 (no adjacent points) with horizontal mounting
position; Tmax > +60 °C number of simultaneously
switched-on digital inputs 3, digital outputs 2, analog
inputs 0 (no adjacent points) with horizontal mounting
position
Extended ambient conditions
• relative to ambient temperature- Tmin ... Tmax at 1080 hPa ... 795 hPa Tmin ... Tmax at 1080 hPa ... 795 hPa
atmospheric pressure-installation (-1000 m ... +2000 m) // (-1000 m ... +2000 m) //
altitude Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa
(+2000 m ... +3500 m) // (+2000 m ... +3500 m) //
Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa
(+3500 m ... +5000 m) (+3500 m ... +5000 m)
Relative humidity
- With condensation, tested in 100%; RH incl. condensation/frost (no commissioning 100%; RH incl. condensation/frost (no commissioning
accordance with IEC 60068-2-38, under condensation conditions) under condensation conditions)
max.
Resistance
- against biologically active Yes; Class 3B2 mold, fungus and dry rot spores (with the Yes; Class 3B2 mold, fungus and dry rot spores (with the
substances / conformity with exception of fauna). The supplied connector covers must exception of fauna). The supplied connector covers must
EN 60721-3-3 remain on the unused interfaces during operation! remain on the unused interfaces during operation!
- against chemically active Yes; Class 3C4 (RH < 75%) incl. salt spray according to Yes; Class 3C4 (RH < 75%) incl. salt spray according to
substances / conformity with EN 60068-2-52 (degree of severity 3). The supplied EN 60068-2-52 (degree of severity 3). The supplied
EN 60721-3-3 connector covers must remain on the unused interfaces connector covers must remain on the unused interfaces
during operation! during operation!
- against mechanically active Yes; Class 3S4 incl. sand, dust. The supplied connector Yes; Class 3S4 incl. sand, dust. The supplied connector
substances / conformity with covers must remain on the unused interfaces during covers must remain on the unused interfaces during
EN 60721-3-3 operation! operation!
3 • min.
• max.
-20 °C; = Tmin; Startup @ 0 °C
60 °C; Number of simultaneously activated inputs or
-40 °C; = Tmin; Startup @ -25 °C
70 °C; = Tmax; Tmax > +55 °C number of simultaneously
outputs 4 or 3 (no adjacent points) at 60 °C horizontal or switched-on digital inputs 4, digital outputs 3, analog
50 °C vertical, 8 or 6 at 55 °C horizontal or 45 °C vertical inputs 2 (no adjacent points) with horizontal mounting
position; Tmax > +60 °C number of simultaneously
switched-on digital inputs 3, digital outputs 2, analog
inputs 0 (no adjacent points) with horizontal mounting
position
Extended ambient conditions
• relative to ambient temperature- Tmin ... Tmax at 1 080 hPa ... 795 hPa Tmin ... Tmax at 1 080 hPa ... 795 hPa
atmospheric pressure-installation (-1 000 m ... +2 000 m) // (-1 000 m ... +2 000 m) //
altitude Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa
(+2 000 m ... +3 500 m) // (+2 000 m ... +3 500 m) //
Tmin ... (Tmax - 20 K) at 658 hPa ... 540 hPa Tmin ... (Tmax - 20 K) at 658 hPa ... 540 hPa
(+3 500 m ... +5 000 m); from 2 000 m max. 132 V AC (+3 500 m ... +5 000 m); from 2 000 m max. 132 V AC
Relative humidity
- With condensation, tested in 100%; RH incl. condensation/frost (no commissioning 100%; RH incl. condensation/frost (no commissioning
accordance with IEC 60068-2-38, under condensation conditions) under condensation conditions)
max.
Resistance
- against biologically active Yes; Class 3B2 mold, fungus and dry rot spores (with the Yes; Class 3B2 mold, fungus and dry rot spores (with the
substances / conformity with exception of fauna). The supplied connector covers must exception of fauna). The supplied connector covers must
EN 60721-3-3 remain on the unused interfaces during operation! remain on the unused interfaces during operation!
- against chemically active Yes; Class 3C4 (RH < 75%) incl. salt spray according to Yes; Class 3C4 (RH < 75%) incl. salt spray according to
substances / conformity with EN 60068-2-52 (degree of severity 3). The supplied EN 60068-2-52 (degree of severity 3). The supplied
EN 60721-3-3 connector covers must remain on the unused interfaces connector covers must remain on the unused interfaces
during operation! during operation!
- against mechanically active Yes; Class 3S4 incl. sand, dust. The supplied connector Yes; Class 3S4 incl. sand, dust. The supplied connector
substances / conformity with covers must remain on the unused interfaces during covers must remain on the unused interfaces during
EN 60721-3-3 operation! operation!
3
IEC type 1 current sinking; -25 ... +55 °C
2 transistor outputs 24 V DC,
0.5 A, 5 W; can be used as HSC at 1 analog output, ±10 V with 12 bits 6AG1232-4HA30-5XB0
up to 30 kHz or 0 ... 20 mA with 11 bits
• Suitable for areas with extreme 6AG1223-0BD30-4XB0 Ambient temperature range
medial exposure 0 ... +55 °C
(conformal coating)
1 analog output, ±10 V with 12 bits 6AG1232-4HA30-4XB0
• Ambient temperature 6AG1223-0BD30-5XB0 or 0 ... 20 mA with 11 bits
-25 ... +55 °C
SIPLUS CB 1241 RS 485
2 inputs, 5 V DC, 200 kHz 6AG1223-3AD30-5XB0 communication board
2 outputs 5 V DC, 0.1 A, 200 kHz
(Extended temperature range and
2 inputs, 24 V DC, 200 kHz 6AG1223-3BD30-5XB0 exposure to media; cannot be used
2 outputs 24 V DC, 0.1 A, 200 kHz with 6AG1212-1....-2XB0)
For point-to-point connection, 6AG1241-1CH30-5XB1
with 1 RS 485 interface
Additional accessories See SIMATIC S7-1200
CPU 1212C, page 3/10
■ Overview
• The compact high-performance CPU
• With 24 integrated I/Os
• Expandable with:
- 1 signal board (SB) or communication board (CB);
not possible with: 6AG1214-1AG40-2XB0,
6AG1214-1BG40-2XB0, 6AG1214-1HG40-2XB0
- 8 signal modules (SM)
- Max. 3 communication modules (CM)
3
Note:
SIPLUS extreme products are based on SIMATIC standard
products. The contents listed here were taken from the respec-
tive standard products. SIPLUS extreme-specific information
was added.
■ Technical specifications
Article number 6AG1214-1AG40-4XB0 6AG1214-1AG40-5XB0 6AG1214-1AG40-2XB0
Based on 6ES7214-1AG40-0XB0 6ES7214-1AG40-0XB0 6ES7214-1AG40-0XB0
SIPLUS S7-1200 CPU 1214C SIPLUS S7-1200 CPU 1214C SIPLUS S7-1200 CPU 1214C
DC/DC/DC DC/DC/DC DC/DC/DC
Ambient conditions
Ambient temperature during
operation
• min. -20 °C; = Tmin; Startup @ 0 °C -40 °C; = Tmin; Startup @ -25 °C -40 °C; = Tmin; Startup @ -25 °C
• max. 60 °C; Number of simultaneously 60 °C; = Tmax; Tmax > +55 °C number 70 °C; = Tmax; Tmax > +55 °C number
activated inputs or outputs 7 or 5 of simultaneously switched-on digital of simultaneously switched-on digital
(no adjacent points) at 60 °C horizontal inputs 7, digital outputs 5, analog inputs 7, digital outputs 5, analog
or 50 °C vertical, 14 or 10 at 55 °C inputs 2 (no adjacent points) with inputs 2 (no adjacent points) with
horizontal or 45 °C vertical horizontal mounting position horizontal mounting position;
Tmax > +60 °C number of simultane-
ously switched-on digital inputs 7,
digital outputs 5, analog inputs 1
(no adjacent points) with horizontal
mounting position
Extended ambient conditions
• relative to ambient temperature- Tmin ... Tmax at Tmin ... Tmax at Tmin ... Tmax at
atmospheric pressure-installation 1080 hPa ... 795 hPa 1080 hPa ... 795 hPa 1080 hPa ... 795 hPa
altitude (-1000 m ... +2000 m) // (-1000 m ... +2000 m) // (-1000 m ... +2000 m) //
Tmin ... (Tmax - 10K) at Tmin ... (Tmax - 10K) at Tmin ... (Tmax - 10K) at
795 hPa ... 658 hPa 795 hPa ... 658 hPa 795 hPa ... 658 hPa
(+2000 m ... +3500 m) // (+2000 m ... +3500 m) // (+2000 m ... +3500 m) //
Tmin ... (Tmax - 20K) at Tmin ... (Tmax - 20K) at Tmin ... (Tmax - 20K) at
658 hPa ... 540 hPa 658 hPa ... 540 hPa 658 hPa ... 540 hPa
(+3500 m ... +5000 m) (+3500 m ... +5000 m) (+3500 m ... +5000 m)
Relative humidity
- With condensation, tested in 100%; RH incl. condensation/frost 100%; RH incl. condensation/frost 100%; RH incl. condensation/frost
accordance with IEC 60068-2-38, (no commissioning under conden- (no commissioning under conden- (no commissioning under conden-
max. sation conditions) sation conditions) sation conditions)
Resistance
- against biologically active Yes; Class 3B2 mold, fungus and dry Yes; Class 3B2 mold, fungus and dry Yes; Class 3B2 mold, fungus and dry
substances / conformity with rot spores (with the exception of rot spores (with the exception of rot spores (with the exception of
EN 60721-3-3 fauna). The supplied connector covers fauna). The supplied connector covers fauna). The supplied connector covers
must remain on the unused interfaces must remain on the unused interfaces must remain on the unused interfaces
during operation! during operation! during operation!
- against chemically active Yes; Class 3C4 (RH < 75%) incl. salt Yes; Class 3C4 (RH < 75%) incl. salt Yes; Class 3C4 (RH < 75%) incl. salt
substances / conformity with spray according to EN 60068-2-52 spray according to EN 60068-2-52 spray according to EN 60068-2-52
EN 60721-3-3 (degree of severity 3). The supplied (degree of severity 3). The supplied (degree of severity 3). The supplied
connector covers must remain on the connector covers must remain on the connector covers must remain on the
unused interfaces during operation! unused interfaces during operation! unused interfaces during operation!
- against mechanically active Yes; Class 3S4 incl. sand, dust. The Yes; Class 3S4 incl. sand, dust. The Yes; Class 3S4 incl. sand, dust. The
substances / conformity with supplied connector covers must supplied connector covers must supplied connector covers must
EN 60721-3-3 remain on the unused interfaces remain on the unused interfaces remain on the unused interfaces
during operation! during operation! during operation!
3 operation
• min. -20 °C; = Tmin; Startup @ 0 °C -40 °C; = Tmin; Startup @ -25 °C -40 °C; = Tmin; Startup @ -25 °C
• max. 60 °C; = Tmax 60 °C; = Tmax; Tmax > +55 °C number 70 °C; = Tmax; Tmax > +55 °C number
of simultaneously switched-on digital of simultaneously switched-on digital
inputs 7, digital outputs 5, analog inputs 7, digital outputs 5, analog
inputs 2 (no adjacent points) with inputs 2 (no adjacent points) with
horizontal mounting position horizontal mounting position;
Tmax > +60 °C number of simultane-
ously switched-on digital inputs 7,
digital outputs 5, analog inputs 1
(no adjacent points) with horizontal
mounting position
Extended ambient conditions
• relative to ambient temperature- Tmin ... Tmax at Tmin ... Tmax at Tmin ... Tmax at
atmospheric pressure-installation 1 080 hPa ... 795 hPa 1 080 hPa ... 795 hPa 1 080 hPa ... 795 hPa
altitude (-1 000 m ... +2 000 m) // (-1 000 m ... +2 000 m) // (-1 000 m ... +2 000 m) //
Tmin ... (Tmax - 10 K) at Tmin ... (Tmax - 10 K) at Tmin ... (Tmax - 10 K) at
795 hPa ... 658 hPa 795 hPa ... 658 hPa 795 hPa ... 658 hPa
(+2 000 m ... +3 500 m) // (+2 000 m ... +3 500 m) // (+2 000 m ... +3 500 m) //
Tmin ... (Tmax - 20 K) at Tmin ... (Tmax - 20 K) at Tmin ... (Tmax - 20 K) at
658 hPa ... 540 hPa 658 hPa ... 540 hPa 658 hPa ... 540 hPa
(+3 500 m ... +5 000 m); (+3 500 m ... +5 000 m); (+3 500 m ... +5 000 m);
from 2 000 m max. 132 V AC from 2 000 m max. 132 V AC from 2 000 m max. 132 V AC
Relative humidity
- With condensation, tested in 100%; RH incl. condensation/frost 100%; RH incl. condensation/frost 100%; RH incl. condensation/frost
accordance with IEC 60068-2-38, (no commissioning under conden- (no commissioning under conden- (no commissioning under conden-
max. sation conditions) sation conditions) sation conditions)
Resistance
- against biologically active Yes; Class 3B2 mold, fungus and dry Yes; Class 3B2 mold, fungus and dry Yes; Class 3B2 mold, fungus and dry
substances / conformity with rot spores (with the exception of rot spores (with the exception of rot spores (with the exception of
EN 60721-3-3 fauna). The supplied connector covers fauna). The supplied connector covers fauna). The supplied connector covers
must remain on the unused interfaces must remain on the unused interfaces must remain on the unused interfaces
during operation! during operation! during operation!
- against chemically active Yes; Class 3C4 (RH < 75%) incl. salt Yes; Class 3C4 (RH < 75%) incl. salt Yes; Class 3C4 (RH < 75%) incl. salt
substances / conformity with spray according to EN 60068-2-52 spray according to EN 60068-2-52 spray according to EN 60068-2-52
EN 60721-3-3 (degree of severity 3). The supplied (degree of severity 3). The supplied (degree of severity 3). The supplied
connector covers must remain on the connector covers must remain on the connector covers must remain on the
unused interfaces during operation! unused interfaces during operation! unused interfaces during operation!
- against mechanically active Yes; Class 3S4 incl. sand, dust. The Yes; Class 3S4 incl. sand, dust. The Yes; Class 3S4 incl. sand, dust. The
substances / conformity with supplied connector covers must supplied connector covers must supplied connector covers must
EN 60721-3-3 remain on the unused interfaces remain on the unused interfaces remain on the unused interfaces
during operation! during operation! during operation!
3
IEC type 1 current sinking; -25 ... +55 °C
2 transistor outputs 24 V DC,
0.5 A, 5 W; can be used as HSC at 1 analog output, ±10 V with 12 bits 6AG1232-4HA30-5XB0
up to 30 kHz or 0 ... 20 mA with 11 bits
• Suitable for areas with extreme 6AG1223-0BD30-4XB0 Ambient temperature range
medial exposure 0 ... +55 °C
(conformal coating)
1 analog output, ±10 V with 12 bits 6AG1232-4HA30-4XB0
• Ambient temperature 6AG1223-0BD30-5XB0 or 0 ... 20 mA with 11 bits
-25 ... +55 °C
SIPLUS CB 1241 RS 485
2 inputs, 5 V DC, 200 kHz 6AG1223-3AD30-5XB0 communication board
2 outputs 5 V DC, 0.1 A, 200 kHz
(Extended temperature range and
2 inputs, 24 V DC, 200 kHz 6AG1223-3BD30-5XB0 exposure to media; cannot be used
2 outputs 24 V DC, 0.1 A, 200 kHz with 6AG1214-1....-2XB0)
For point-to-point connection, 6AG1241-1CH30-5XB1
with 1 RS 485 interface
Additional accessories See SIMATIC S7-1200
CPU 1214C, page 3/14
■ Overview
• The compact high-performance CPU
• With 24 integrated I/Os
• Expandable with:
- 1 signal board (SB) or communication board (CB);
not possible with: 6AG1215-1AG40-2XB0,
6AG1215-1BG40-2XB0, 6AG1215-1HG40-2XB0
3 - 8 signal modules (SM)
- Max. 3 communication modules (CM)
Note:
SIPLUS extreme products are based on SIMATIC standard
products. The contents listed here were taken from the respec-
tive standard products. SIPLUS extreme-specific information
was added.
■ Technical specifications
Article number 6AG1215-1AG40-4XB0 6AG1215-1AG40-5XB0 6AG1215-1AG40-2XB0
Based on 6ES7215-1AG40-0XB0 6ES7215-1AG40-0XB0 6ES7215-1AG40-0XB0
SIPLUS S7-1200 CPU 1215C SIPLUS S7-1200 CPU 1215C SIPLUS S7-1200 CPU 1215C
DC/DC/DC DC/DC/DC DC/DC/DC
Ambient conditions
Ambient temperature during
operation
• min. -20 °C; = Tmin; Startup @ 0 °C -40 °C; = Tmin; Startup @ -25 °C -40 °C; = Tmin; Startup @ -25 °C
• max. 60 °C; Number of simultaneously 60 °C; = Tmax; Tmax > +55 °C number 70 °C; = Tmax; Tmax > +55 °C number
activated inputs or outputs 7 or 5 of simultaneously switched-on digital of simultaneously switched-on digital
(no adjacent points) at 60 °C horizontal inputs 7, digital outputs 5, analog inputs 7, digital outputs 5, analog
or 50 °C vertical, 14 or 10 at 55 °C inputs 2, analog outputs 2 (no adjacent inputs 2, analog outputs 2 (no adjacent
horizontal or 45 °C vertical points) with horizontal mounting points) with horizontal mounting
position position; Tmax > +60 °C number of
simultaneously switched-on digital
inputs 7, digital outputs 5, analog
inputs 1, analog outputs 1 (no adjacent
points) with horizontal mounting
position
Extended ambient conditions
• relative to ambient temperature- Tmin ... Tmax at Tmin ... Tmax at Tmin ... Tmax at
atmospheric pressure-installation 1080 hPa ... 795 hPa 1080 hPa ... 795 hPa 1080 hPa ... 795 hPa
altitude (-1000 m ... +2000 m) // (-1000 m ... +2000 m) // (-1000 m ... +2000 m) //
Tmin ... (Tmax - 10K) at Tmin ... (Tmax - 10K) at Tmin ... (Tmax - 10K) at
795 hPa ... 658 hPa 795 hPa ... 658 hPa 795 hPa ... 658 hPa
(+2000 m ... +3500 m) // (+2000 m ... +3500 m) // (+2000 m ... +3500 m) //
Tmin ... (Tmax - 20K) at Tmin ... (Tmax - 20K) at Tmin ... (Tmax - 20K) at
658 hPa ... 540 hPa 658 hPa ... 540 hPa 658 hPa ... 540 hPa
(+3500 m ... +5000 m) (+3500 m ... +5000 m) (+3500 m ... +5000 m)
Relative humidity
- With condensation, tested in 100%; RH incl. condensation/frost 100%; RH incl. condensation/frost 100%; RH incl. condensation/frost
accordance with IEC 60068-2-38, (no commissioning under conden- (no commissioning under conden- (no commissioning under conden-
max. sation conditions) sation conditions) sation conditions)
Resistance
- against biologically active Yes; Class 3B2 mold, fungus and dry Yes; Class 3B2 mold, fungus and dry Yes; Class 3B2 mold, fungus and dry
substances / conformity with rot spores (with the exception of rot spores (with the exception of rot spores (with the exception of
EN 60721-3-3 fauna). The supplied connector covers fauna). The supplied connector covers fauna). The supplied connector covers
must remain on the unused interfaces must remain on the unused interfaces must remain on the unused interfaces
during operation! during operation! during operation!
- against chemically active Yes; Class 3C4 (RH < 75%) incl. salt Yes; Class 3C4 (RH < 75%) incl. salt Yes; Class 3C4 (RH < 75%) incl. salt
substances / conformity with spray according to EN 60068-2-52 spray according to EN 60068-2-52 spray according to EN 60068-2-52
EN 60721-3-3 (degree of severity 3). The supplied (degree of severity 3). The supplied (degree of severity 3). The supplied
connector covers must remain on the connector covers must remain on the connector covers must remain on the
unused interfaces during operation! unused interfaces during operation! unused interfaces during operation!
- against mechanically active Yes; Class 3S4 incl. sand, dust. The Yes; Class 3S4 incl. sand, dust. The Yes; Class 3S4 incl. sand, dust. The
substances / conformity with supplied connector covers must supplied connector covers must supplied connector covers must
EN 60721-3-3 remain on the unused interfaces remain on the unused interfaces remain on the unused interfaces
during operation! during operation! during operation!
3 operation
• min. -20 °C; = Tmin; Startup @ 0 °C -40 °C; = Tmin; Startup @ -25 °C -40 °C; = Tmin; Startup @ -25 °C
• max. 60 °C; Number of simultaneously 60 °C; = Tmax; Tmax > +55 °C number 70 °C; = Tmax; Tmax > +55 °C number
activated inputs or outputs 7 or 5 of simultaneously switched-on digital of simultaneously switched-on digital
(no adjacent points) at 60 °C horizontal inputs 7, digital outputs 5, analog inputs 7, digital outputs 5, analog
or 50 °C vertical, 14 or 10 at 55 °C inputs 2, analog outputs 2 (no adjacent inputs 2, analog outputs 2 (no adjacent
horizontal or 45 °C vertical points) with horizontal mounting points) with horizontal mounting
position position; Tmax > +60 °C number of
simultaneously switched-on digital
inputs 7, digital outputs 5, analog
inputs 1, analog outputs 1 (no adjacent
points) with horizontal mounting
position
Extended ambient conditions
• relative to ambient temperature- Tmin ... Tmax at Tmin ... Tmax at Tmin ... Tmax at
atmospheric pressure-installation 1 080 hPa ... 795 hPa 1080 hPa ... 795 hPa 1 080 hPa ... 795 hPa
altitude (-1 000 m ... +2 000 m) // (-1000 m ... +2000 m) // (-1 000 m ... +2 000 m) //
Tmin ... (Tmax - 10 K) at Tmin ... (Tmax - 10K) at Tmin ... (Tmax - 10 K) at
795 hPa ... 658 hPa 795 hPa ... 658 hPa 795 hPa ... 658 hPa
(+2 000 m ... +3 500 m) // (+2000 m ... +3500 m) // (+2 000 m ... +3 500 m) //
Tmin ... (Tmax - 20 K) at Tmin ... (Tmax - 20K) at Tmin ... (Tmax - 20 K) at
658 hPa ... 540 hPa 658 hPa ... 540 hPa 658 hPa ... 540 hPa
(+3 500 m ... +5 000 m); (+3500 m ... +5000 m) (+3 500 m ... +5 000 m);
from 2 000 m max. 132 V AC from 2 000 m max. 132 V AC
Relative humidity
- With condensation, tested in 100%; RH incl. condensation/frost 100%; RH incl. condensation/frost 100%; RH incl. condensation/frost
accordance with IEC 60068-2-38, (no commissioning under conden- (no commissioning under conden- (no commissioning under conden-
max. sation conditions) sation conditions) sation conditions)
Resistance
- against biologically active Yes; Class 3B2 mold, fungus and dry Yes; Class 3B2 mold, fungus and dry Yes; Class 3B2 mold, fungus and dry
substances / conformity with rot spores (with the exception of rot spores (with the exception of rot spores (with the exception of
EN 60721-3-3 fauna). The supplied connector covers fauna). The supplied connector covers fauna). The supplied connector covers
must remain on the unused interfaces must remain on the unused interfaces must remain on the unused interfaces
during operation! during operation! during operation!
- against chemically active Yes; Class 3C4 (RH < 75%) incl. salt Yes; Class 3C4 (RH < 75%) incl. salt Yes; Class 3C4 (RH < 75%) incl. salt
substances / conformity with spray according to EN 60068-2-52 spray according to EN 60068-2-52 spray according to EN 60068-2-52
EN 60721-3-3 (degree of severity 3). The supplied (degree of severity 3). The supplied (degree of severity 3). The supplied
connector covers must remain on the connector covers must remain on the connector covers must remain on the
unused interfaces during operation! unused interfaces during operation! unused interfaces during operation!
- against mechanically active Yes; Class 3S4 incl. sand, dust. The Yes; Class 3S4 incl. sand, dust. The Yes; Class 3S4 incl. sand, dust. The
substances / conformity with supplied connector covers must supplied connector covers must supplied connector covers must
EN 60721-3-3 remain on the unused interfaces remain on the unused interfaces remain on the unused interfaces
during operation! during operation! during operation!
3
IEC type 1 current sinking; -25 ... +55 °C
2 transistor outputs 24 V DC,
0.5 A, 5 W; 1 analog output, ±10 V with 12 bits 6AG1232-4HA30-5XB0
can be used as HSC at up to or 0 ... 20 mA with 11 bits
30 kHz Ambient temperature range
• Suitable for areas with extreme 6AG1223-0BD30-4XB0 0 ... +55 °C
medial exposure
(conformal coating) 1 analog output, ±10 V with 12 bits 6AG1232-4HA30-4XB0
or 0 ... 20 mA with 11 bits
• Ambient temperature 6AG1223-0BD30-5XB0
-25 ... +55 °C SIPLUS CB 1241 RS 485
communication board
2 inputs, 5 V DC, 200 kHz 6AG1223-3AD30-5XB0
2 outputs 5 V DC, 0.1 A, 200 kHz (Extended temperature range and
exposure to media; cannot be used
2 inputs, 24 V DC, 200 kHz 6AG1223-3BD30-5XB0 with 6AG1215-1....-2XB0)
2 outputs 24 V DC, 0.1 A, 200 kHz
For point-to-point connection, 6AG1241-1CH30-5XB1
with 1 RS 485 interface
Additional accessories See SIMATIC S7-1200
CPU 1215C. page 3/18
■ Overview
• Standard controller with integrated safety functions:
- Standardized and convenient diagnostic functions for
standard and safety
- Uniform symbols, data consistency, ...
• Modular system with scalable range of CPUs and expandable
I/O quantity structure:
- One engineering for standard and fail-safe automation
- Use of the standard I/O modules together with the fail-safe 3
I/O modules in the central system
- Integrated standard PROFINET functionalities for PROFINET
controllers and PROFINET iDevice services
- Connection of distributed standard I/O via field bus such as
PROFINET or PROFIBUS
- F-library certified by the German Technical Inspectorate
(TÜV) for all common safety functions
- Free programming of the safety logic using FBD and LAD
- Standard-compliant printout of the F-program
The fail-safe SIMATIC S7-1200 Controllers are based on the • One integrated engineering for both standard and safety from
S7-1200 standard CPUs and offer additional safety-related S7-1200 to S7-300/400/1500 and WinAC RTX F:
functions. - STEP 7 Safety Basic for easy engineering of the
CPU 1200 FC
They can be used for safety-oriented tasks according to - STEP 7 Safety Advanced for the entire fail-safe SIMATIC S7
IEC 61508 up to SIL 3 and ISO 13849-1 up to PL e. portfolio
Safety-related programs are created in the TIA Portal. The • Integrated system diagnosis of the CPUs, for standard and
STEP 7 Safety engineering tool offers commands, operations safety:
and blocks for safety-related programs in the LAD and FBD - Consistent plain text display of system diagnostic
languages. To this end, there is a library with pre-configured, information in the TIA Portal, HMI and web server
TÜV-approved blocks for safety-related functions. - Messages are updated even if the CPU is in STOP state
- System diagnostics integrated in the CPU firmware.
Configuration by user not required
- The diagnostics is automatically updated on configuration
changes.
• 2 fail-safe compact controllers with graded performances in
the versions DC/DC/DC and DC/DC/relay
Characteristics CPU 1212 FC CPU 1214 FC CPU 1215 FC
Variants DC/DC/DC, DC/DC/relay DC/DC/DC, DC/DC/relay DC/DC/DC, DC/DC/relay
Main memory, integrated 100 KB 125 KB 150 KB
Load memory, integrated 2 MB 4 MB 4 MB
Memory card SIMATIC Memory Card (optional) SIMATIC Memory Card (optional) SIMATIC Memory Card (optional)
Standard digital inputs/outputs, 8/6 14/10 14/10
integrated
Standard analog inputs, integrated 2 2 2
Standard analog outputs, integrated - - 2
Process image 1024 bytes for inputs, 1024 bytes for inputs, 1024 bytes for inputs,
1024 bytes for outputs 1024 bytes for outputs 1024 bytes for outputs
Expansion by signal board Max. 1 Max. 1 Max. 1
Expansion by signal modules Max. 2 Max. 8 Max. 8
Expansion by communication modules Max. 3 Max. 3 Max. 3
■ Technical specifications
Article number 6ES7212-1AF40- 6ES7212-1HF40- 6ES7214-1AF40- 6ES7214-1HF40- 6ES7215-1AF40- 6ES7215-1HF40-
0XB0 0XB0 0XB0 0XB0 0XB0 0XB0
CPU 1212FC , CPU 1212FC, CPU 1214 FC, CPU 1214 FC, CPU 1215 FC, CPU 1215 FC,
DC/DC/DC, DC/DC/RELAY, DC/DC/DC, DC/DC/RELAY, DC/DC/DC, 14DI/ DC/DC/RLY,14DI/
8DI/6DO/2AI 8DI/6DO/2AI 14DI/10DO/2AI 14DI/10DO/2AI 10DO/2AI/2AO 10DO/2AI/2AO
General information
3
Interface type PROFINET PROFINET PROFINET PROFINET PROFINET PROFINET
Physics Ethernet Ethernet Ethernet Ethernet Ethernet Ethernet
Functionality
• PROFINET IO Controller Yes Yes Yes Yes Yes Yes
• PROFINET IO Device Yes Yes Yes Yes Yes Yes
• SIMATIC communication Yes Yes Yes Yes Yes Yes
• Open IE communication Yes Yes Yes Yes Yes Yes
• Web server Yes Yes Yes Yes Yes Yes
• Media redundancy Yes; as MRP client Yes; as MRP client Yes; as MRP client Yes; as MRP client
Communication functions
S7 communication
• supported Yes Yes Yes Yes Yes Yes
Open IE communication
• TCP/IP Yes Yes Yes Yes Yes Yes
• ISO-on-TCP (RFC1006) Yes Yes Yes Yes Yes Yes
• UDP Yes Yes Yes Yes Yes Yes
Web server
• supported Yes Yes Yes Yes Yes Yes
Number of connections
• overall 16; dynamically 16; dynamically 16; dynamically 16; dynamically
Integrated Functions
Number of counters 4 4 6 6 6 6
Counting frequency (counter) max. 100 kHz 100 kHz 100 kHz 100 kHz 100 kHz 100 kHz
Frequency meter Yes Yes Yes Yes Yes Yes
controlled positioning Yes Yes Yes Yes Yes Yes
Number of position-controlled 8 8 8 8 8 8
positioning axes, max.
Number of positioning axes Up to 4 with Up to 4 with Up to 4 with Up to 4 with Up to 4 with Up to 4 with
via pulse-direction interface SB 1222 SB 1222 SB 1222 SB 1222 SB 1222 SB 1222
PID controller Yes Yes Yes Yes Yes Yes
Number of alarm inputs 4 4 4 4 4
Number of pulse outputs 4 4
Limit frequency (pulse) 100 kHz
Ambient conditions
Ambient temperature during
operation
• min. -20 °C -20 °C -20 °C -20 °C -20 °C -20 °C
• max. 60 °C; Number of 60 °C; Number of 60 °C; Number of 60 °C; Number of 60 °C; Number of 60 °C; Number of
simultaneously simultaneously simultaneously simultaneously simultaneously simultaneously
activated inputs or activated inputs or activated inputs or activated inputs or activated inputs or activated inputs or
outputs 7 or 5 (no outputs 7 or 5 (no outputs 7 or 5 (no outputs 7 or 5 (no outputs 7 or 5 (no outputs 7 or 5 (no
adjacent points) at adjacent points) at adjacent points) at adjacent points) at adjacent points) at adjacent points) at
60 °C horizontal or 60 °C horizontal or 60 °C horizontal or 60 °C horizontal or 60 °C horizontal or 60 °C horizontal or
50 °C vertical, 50 °C vertical, 50 °C vertical, 50 °C vertical, 50 °C vertical, 50 °C vertical,
14 or 10 at 55 °C 14 or 10 at 55 °C 14 or 10 at 55 °C 14 or 10 at 55 °C 14 or 10 at 55 °C 14 or 10 at 55 °C
horizontal or 45 °C horizontal or 45 °C horizontal or 45 °C horizontal or 45 °C horizontal or 45 °C horizontal or 45 °C
vertical vertical vertical vertical vertical vertical
Pollutant concentrations
- SO2 at RH < 60% without S02: < 0.5 ppm; S02: < 0.5 ppm; S02: < 0.5 ppm; S02: < 0.5 ppm; S02: < 0.5 ppm; S02: < 0.5 ppm;
condensation H2S: < 0.1 ppm; H2S: < 0.1 ppm; H2S: < 0.1 ppm; H2S: < 0.1 ppm; H2S: < 0.1 ppm; H2S: < 0.1 ppm;
RH < 60% RH < 60% RH < 60% RH < 60% RH < 60% RH < 60%
condensation-free condensation-free condensation-free condensation-free condensation-free condensation-free
3
Programming
Programming language
- LAD Yes; incl. failsafe Yes; incl. failsafe Yes; incl. failsafe Yes; incl. failsafe Yes; incl. failsafe Yes; incl. failsafe
- FBD Yes; incl. failsafe Yes; incl. failsafe Yes; incl. failsafe Yes; incl. failsafe Yes; incl. failsafe Yes; incl. failsafe
- SCL Yes Yes Yes Yes Yes Yes
Dimensions
Width 90 mm 90 mm 110 mm 110 mm 130 mm 130 mm
Height 100 mm 100 mm 100 mm 100 mm 100 mm 100 mm
Depth 75 mm 75 mm 75 mm 75 mm 75 mm 75 mm
Weights
Weight, approx. 370 g 385 g 435 g 435 g 585 g 585 g
3
per operation; • For AI, with 3 screws, gold-plated; 6ES7292-1BC30-0XA0
14 digital inputs, 4 units
10 digital outputs, For CPU 1215FC, DC/DC/DC
2 analog inputs;
• For DI, with 20 screws, tin-coated; 6ES7292-1AV30-0XA0
2 analog outputs;
4 units
expandable by up to
3 communication modules, • For DO, with 12 screws, 6ES7292-1AM30-0XA0
8 signal modules, and 1 signal tin-coated; 4 units
board/communication board; • For AI, with 6 screws, gold-plated; 6ES7292-1BF30-0XA0
digital inputs can be used as HSC 4 units
at 100 kHz,
24 V DC digital outputs can be For CPU 1215FC, DC/DC/relay
used as pulse outputs (PTO) or • For DI, with 20 screws, tin-coated; 6ES7292-1AV30-0XA0
pulse-width modulated outputs 4 units
(PWM) at 100 kHz • For DO, with 12 screws, 6ES7292-1AM40-0XA0
tin-coated, coded; 4 units
Fail-safe compact CPU, 6ES7215-1HF40-0XB0
DC/DC/relay; • For AI, with 6 screws, gold-plated; 6ES7292-1BF30-0XA0
integrated program/data memory 4 units
150 KB, load memory 4 MB; Front flap set (spare part)
power supply 24 V DC;
Boolean execution times 0.085 s For CPU 1214 FC 6ES7291-1AB30-0XA0
per operation; For CPU 1215 FC 6ES7291-1AC30-0XA0
14 digital inputs,
10 digital outputs (relays), RJ45 cable grip
2 analog inputs;
2 analog outputs; 4 items per pack
expandable by up to Single port 6ES7290-3AA30-0XA0
3 communication modules,
8 signal modules, and 1 signal Dual port 6ES7290-3AB30-0XA0
board/communication board;
digital inputs can be used as HSC STEP 7 Safety Advanced V14 SP1
at 100 kHz Task:
Accessories Engineering tool for configuring and
programming fail-safe user
SIMATIC S7-1200 Fail-Safe 6ES7212-1HF41-4YB0 programs for SIMATIC S7-1200 FC,
Starter Kit S7-1500F, S7-1500F Software
Controller, S7-300F, S7-400F,
Consisting of: WinAC RTX F, ET 200SP F Controller
CPU 1212FC DC/DC relay, F digital and the fail-safe ET 200SP,
input SM 1226 16 x 24 V DC, ET 200S, ET 200M, ET 200iSP,
F digital output SM 1226 ET 200pro and ET 200eco I/O
4 x 24 V DC, input simulator, Requirement:
STEP 7 Basic and STEP 7 Safety STEP 7 Professional V14 SP1
Basic on CD, manual on CD, info
material; in Systainer Floating license for 1 user, 6ES7833-1FA14-0YA5
software and documentation on
Simulator (optional) 6ES7274-1XH30-0XA0 DVD, license key on USB flash drive
14 incoming circuit breakers Floating license for 1 user, 6ES7833-1FA14-0YH5
SIMATIC Memory Card (optional) software, documentation and
license key for download1);
4 MB 6ES7954-8LC02-0AA0 email address required for delivery
12 MB 6ES7954-8LE02-0AA0 STEP 7 Safety Basic V14 SP1
24 MB 6ES7954-8LF02-0AA0 Task:
Engineering tool for configuring
256 MB 6ES7954-8LL02-0AA0 fail-safe user programs for
2 GB 6ES7954-8LP02-0AA0 SIMATIC S7-1200 FC
Requirement:
32 GB 6ES7954-8LT03-0AA0 STEP 7 Basic V14 SP1 and higher
Extension cable for 6ES7290-6AA30-0XA0 Floating license for 1 user; 6ES7833-1FB14-0YA5
two-tier configuration software and documentation on
For connecting digital/analog signal DVD, license key on USB flash drive
modules; length 2 m Floating license for 1 user, 6ES7833-1FB14-0YH5
Terminal block (spare part) software, documentation and
license key for download1);
For CPU 1214FC, DC/DC/DC email address required for delivery
• For DI, with 20 screws, tin-coated; 6ES7292-1AV30-0XA0
4 units
• For DO, with 12 screws, 6ES7292-1AM30-0XA0
tin-coated; 4 units
• For AI, with 3 screws, gold-plated; 6ES7292-1BC30-0XA0
4 units
1) For up-to-date information and download availability, see:
http://www.siemens.com/tia-online-software-delivery
■ Overview
Characteristics SIPLUS CPU 1214 FC
Variants DC/DC/DC, DC/DC/relay
Main memory, integrated 125 KB
Load memory, integrated 4 MB
Memory card SIMATIC memory card (optional)
3 Standard digital inputs/outputs,
integrated
14/10
■ Technical specifications
Article number 6AG1214-1AF40-5XB0 6AG1214-1HF40-5XB0
Based on 6ES7214-1AF40-0XB0 6ES7214-1HF40-0XB0
SIPLUS S7-1200 CPU 1214FC DC/DC/DC SIPLUS S7-1200 CPU 1214FC DC/DC/RLY
Ambient conditions
Ambient temperature during
operation
• min.
• max.
-25 °C; = Tmin
55 °C; = Tmax
-25 °C; = Tmin
55 °C; = Tmax
3
Extended ambient conditions
• relative to ambient temperature- Tmin ... Tmax at 1080 hPa ... 795 hPa Tmin ... Tmax at 1080 hPa ... 795 hPa
atmospheric pressure-installation (-1000 m ... +2000 m) (-1000 m ... +2000 m)
altitude
Relative humidity
- With condensation, tested in 100%; RH incl. condensation/frost (no commissioning 100%; RH incl. condensation/frost (no commissioning
accordance with IEC 60068-2-38, under condensation conditions) under condensation conditions)
max.
Pollutant concentrations
- SO2 at RH < 60% without S02: < 0.5 ppm; H2S: < 0.1 ppm; S02: < 0.5 ppm; H2S: < 0.1 ppm;
condensation RH < 60% condensation-free RH < 60% condensation-free
Resistance
- against biologically active Yes; Class 3B2 mold, fungus and dry rot spores (with the Yes; Class 3B2 mold, fungus and dry rot spores (with the
substances / conformity with exception of fauna). The supplied connector covers must exception of fauna). The supplied connector covers must
EN 60721-3-3 remain on the unused interfaces during operation! remain on the unused interfaces during operation!
- against chemically active Yes; Class 3C4 (RH < 75%) incl. salt spray according to Yes; Class 3C4 (RH < 75%) incl. salt spray according to
substances / conformity with EN 60068-2-52 (degree of severity 3). The supplied EN 60068-2-52 (degree of severity 3). The supplied
EN 60721-3-3 connector covers must remain on the unused interfaces connector covers must remain on the unused interfaces
during operation! during operation!
- against mechanically active Yes; Class 3S4 incl. sand, dust. The supplied connector Yes; Class 3S4 incl. sand, dust. The supplied connector
substances / conformity with covers must remain on the unused interfaces during covers must remain on the unused interfaces during
EN 60721-3-3 operation! operation!
■ Overview
• Digital inputs as supplement to the integral I/O of the CPUs
• For flexible adaptation of the controller to the relevant task
• For subsequent expansion of the system with additional inputs
■ Technical specifications
Article number 6ES7221-1BF32-0XB0 6ES7221-1BH32-0XB0
DIGITAL INPUT SM 1221, 8DI, 24V DC DIGITAL INPUT SM 1221, 16DI, 24V DC
General information
Product type designation SM 1221 DI 8x24 VDC SM 1221 DI 16x24 VDC
Supply voltage
Rated value (DC)
• 24 V DC Yes Yes
Input current
from backplane bus 5 V DC, max. 105 mA 130 mA
Digital inputs
• from load voltage L+ (without load), 4 mA; per channel 4 mA; per channel
max.
Output voltage
Power supply to the transmitters
• present Yes Yes
Power loss
Power loss, typ. 1.5 W 2.5 W
Digital inputs
Number of digital inputs 8 16
• in groups of 2 4
Input characteristic curve in Yes Yes
accordance with IEC 61131, type 1
Number of simultaneously
controllable inputs
all mounting positions
- up to 40 °C, max. 8 16
horizontal installation
- up to 40 °C, max. 8 16
- up to 50 °C, max. 8 16
vertical installation
- up to 40 °C, max. 8 16
3
• for signal "0" 5 V DC at 1 mA 5 V DC at 1 mA
• for signal "1" 15 V DC at 2.5 mA 15 V DC at 2.5 mA
Input current
• for signal "0", max. (permissible 1 mA 1 mA
quiescent current)
• for signal "1", min. 2.5 mA 2.5 mA
• for signal "1", typ. 4 mA 4 mA
Input delay
(for rated value of input voltage)
for standard inputs
- parameterizable Yes; 0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and Yes; 0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and
12.8 ms, selectable in groups of four 12.8 ms, selectable in groups of four
for interrupt inputs
- parameterizable Yes Yes
Cable length
• shielded, max. 500 m 500 m
• unshielded, max. 300 m 300 m
Interrupts/diagnostics/
status information
Alarms
• Diagnostic alarm Yes Yes
Diagnostics indication LED
• for status of the inputs Yes Yes
Potential separation
Potential separation digital inputs
• between the channels, in groups of 2 4
Degree and class of protection
Degree of protection acc. to
EN 60529
• IP20 Yes Yes
Standards, approvals, certificates
CE mark Yes Yes
CSA approval Yes Yes
cULus Yes Yes
FM approval Yes Yes
RCM (formerly C-TICK) Yes Yes
Marine approval
• Marine approval Yes
Ambient conditions
Free fall
• Fall height, max. 0.3 m; five times, in product package 0.3 m; five times, in product package
Ambient temperature during
operation
• permissible temperature range -20 °C to +60 °C horizontal mounting, -20 °C to 50 °C
vertical mounting, 95% humidity, non-condensing
• min. -20 °C -20 °C
• max. 60 °C 60 °C
Connection method
required front connector Yes Yes
Mechanics/material
Enclosure material (front)
• Plastic Yes Yes
Dimensions
Width 45 mm 45 mm
Height 100 mm 100 mm
Depth 75 mm 75 mm
Weights
Weight, approx. 170 g 210 g
■ Overview
• Digital inputs as a supplement to the integral I/O of
SIMATIC S7-1200 CPUs
• Can be plugged directly into the CPU
■ Technical specifications
Article number 6ES7221-3AD30-0XB0 6ES7221-3BD30-0XB0
SIGNAL BOARD SB 1221, 4 DI 5VDC 200KHZ SIGNAL BOARD SB 1221, 4 DI 24VDC 200KHZ
General information
Product type designation SB 1221 4xDI 5VDC 200kHz SB 1221 4xDI 24VDC 200kHz
Input current
from backplane bus 5 V DC, typ. 40 mA 40 mA
Power loss
Power loss, typ. 1W 1W
Digital inputs
Number of digital inputs 4; Current-sourcing 4; Current-sourcing
• in groups of 4 4
Input voltage
• Type of input voltage DC DC
• Rated value (DC) 5V 24 V
• for signal "0" (L+ minus 1.0 V DC) ... L+ (2.2 ... 0 mA) (L+ minus 5.0 V DC) ... L+ (1.4 ... 0 mA)
• for signal "1" 0 V ... (L+ minus 2.0 V DC (20 ... 5.1 mA)) 0 V ... (L+ minus 10 V DC (10 ... 2.9 mA))
Input current
• for signal "0", max. (permissible 2.2 mA 1.4 mA
quiescent current)
• for signal "1", min. 5.1 mA 2.9 mA
• for signal "1", typ. 7 mA
Input delay
(for rated value of input voltage)
for standard inputs
- parameterizable Yes; 0.1 / 0.2 / 0.4 / 0.8 / 1.6 / 3.2 / 6.4 / 10.0 / 12.8 / 20.0 s; Yes; 0.1 / 0.2 / 0.4 / 0.8 / 1.6 / 3.2 / 6.4 / 10.0 / 12.8 / 20.0 s;
0.05 / 0.1 / 0.2 / 0.4 / 0.8 / 1.6 / 3.2 / 6.4 / 10.0 / 12.8 / 0.05 / 0.1 / 0.2 / 0.4 / 0.8 / 1.6 / 3.2 / 6.4 / 10.0 / 12.8 /
20.0 ms 20.0 ms
for interrupt inputs
- parameterizable Yes Yes
for counter/technological functions
- parameterizable Yes Yes
Cable length
• shielded, max. 50 m; shielded, twisted pair 50 m; shielded, twisted pair
Diagnostics indication LED
• for status of the inputs Yes Yes
Degree and class of protection
Degree of protection acc. to
EN 60529
• IP20 Yes Yes
3
Ambient temperature during
operation
• permissible temperature range -20 °C to +60 °C horizontal mounting, -20 °C to +60 °C horizontal mounting,
-20 °C to 50 °C vertical mounting -20 °C to 50 °C vertical mounting with 2 simultaneously
activated, non-adjacent inputs;
otherwise up to 55 °C with horizontal mounting or
45 °C with vertical mounting
• min. -20 °C -20 °C
• max. 60 °C 60 °C
Mechanics/material
Enclosure material (front)
• Plastic Yes Yes
Dimensions
Width 38 mm 38 mm
Height 62 mm 62 mm
Depth 21 mm 21 mm
Weights
Weight, approx. 35 g 35 g
■ Overview
• Digital outputs as supplement to the integral I/O of the CPUs
• For flexible adaptation of the controller to the relevant task
• For subsequent expansion of the system with additional
outputs
■ Technical specifications
Article number 6ES7222-1BF32- 6ES7222-1BH32- 6ES7222-1HF32- 6ES7222-1HH32- 6ES7222-1XF32-0XB0
0XB0 0XB0 0XB0 0XB0
DIGITAL OUTPUT DIGITAL OUTPUT DIGITAL OUTPUT DIGITAL OUTPUT DIGITAL OUTPUT
SM1222, 8 DO, SM1222, 16 DO, SM 1222, 8 DO, SM1222, 16 DO, SM 1222, 8 DO,
24V DC 24V DC RELAY RELAY CHANGEOVER
General information
Product type designation SM 1222 DQ 8x24VDC SM 1222 DQ SM 1222 DQ 8xRelay SM 1222 DQ 16xRelay SM 1222 DQ 8x relay
16x24VDC changeover contact
Input current
from backplane bus 5 V DC, max. 120 mA 140 mA 120 mA 135 mA 140 mA
Digital outputs
• from load voltage L+, max. 11 mA/relay coil 11 mA/relay coil 16.7 mA/relay coil
Power loss
Power loss, typ. 1.5 W 2.5 W 4.5 W 8.5 W 5W
Digital outputs
Number of digital outputs 8 16 8 16 8
• in groups of 1 1 2 1 1
Short-circuit protection No; to be provided No; to be provided No; to be provided No; to be provided No; to be provided
externally externally externally externally externally
Limitation of inductive shutdown typ. (L+) -48 V typ. (L+) -48 V
voltage to
Switching capacity of the outputs
• with resistive load, max. 0.5 A 0.5 A 2A 2A 2A
• on lamp load, max. 5W 5W 30 W with DC, 30 W with DC, 30 W with DC,
200 W with AC 200 W with AC 200 W with AC
Output voltage
• Rated value (DC) 24 V 24 V 5 V DC to 30 V DC 5 V DC to 30 V DC 5 V DC to 30 V DC
• Rated value (AC) 5 V AC to 250 V AC 5 V AC to 250 V AC 5 V AC to 250 V AC
• for signal "0", max. 0.1 V; 0.1 V;
with 10 kOhm load with 10 kOhm load
• for signal "1", min. 20 V DC 20 V DC
Output current
• for signal "1" rated value 0.5 A 0.5 A
• for signal "1" permissible range, 2A 2A 2A
max.
• for signal "0" residual current, max. 10 µA 10 µA
Output delay with resistive load
• "0" to "1", max. 50 µs 50 µs 10 ms 10 ms 10 ms
• "1" to "0", max. 200 µs 200 µs 10 ms 10 ms 10 ms
Total current of the outputs
(per group)
horizontal installation
- up to 50 °C, max. 4 A; Current per mass 8 A; Current per mass 10 A; Current per 10 A; Current per 2 A; Current per mass
mass mass
3
• Number of relay outputs 8 16 8
• Rated supply voltage of relay coil L+ 24 V 24 V 24 V
(DC)
• Number of operating cycles, max. mechanically mechanically mechanically
10 million, at rated 10 million, at rated 10 million, at rated
load voltage 100 000 load voltage 100 000 load voltage 100 000
Switching capacity of contacts
- with inductive load, max. 0.5 A 0.5 A 2A 2A 2A
- on lamp load, max. 5W 5W 30 W with DC, 30 W with DC, 30 W with DC,
200 W with AC 200 W with AC 200 W with AC
- with resistive load, max. 0.5 A 0.5 A 2A 2A 2A
Cable length
• shielded, max. 500 m 500 m 500 m 500 m 500 m
• unshielded, max. 150 m 150 m 150 m 150 m 150 m
Interrupts/diagnostics/
status information
Alarms
• Diagnostic alarm Yes Yes Yes Yes Yes
Diagnostics indication LED
• for status of the outputs Yes Yes Yes Yes Yes
Potential separation
Potential separation digital outputs
• between the channels Relays Relays Relays
• between the channels, in groups of 1 1 2 4 1
• between the channels and 500 V AC 500 V AC 1500 V AC for 1 minute 1500 V AC for 1 minute 1500 V AC for 1 minute
backplane bus
Permissible potential difference
between different circuits 750 V AC for 1 minute 750 V AC for 1 minute 750 V AC for 1 minute
Degree and class of protection
Degree of protection acc. to
EN 60529
• IP20 Yes Yes Yes Yes Yes
Standards, approvals, certificates
CE mark Yes Yes Yes Yes Yes
CSA approval Yes Yes Yes Yes Yes
cULus Yes Yes Yes Yes Yes
FM approval Yes Yes Yes Yes Yes
RCM (formerly C-TICK) Yes Yes Yes Yes Yes
Marine approval
• Marine approval Yes Yes Yes Yes Yes
Ambient conditions
Free fall
• Fall height, max. 0.3 m; five times, in 0.3 m; five times, in 0.3 m; five times, in 0.3 m; five times, in 0.3 m; five times, in
product package product package product package product package product package
Ambient temperature during
operation
• permissible temperature range -20 °C to +60 °C -20 °C to +60 °C -20 °C to +60 °C -20 °C to +60 °C -20 °C to +60 °C
horizontal mounting, horizontal mounting, horizontal mounting, horizontal mounting, horizontal mounting,
-20 °C to 50 °C vertical -20 °C to 50 °C vertical -20 °C to 50 °C vertical -20 °C to 50 °C vertical -20 °C to 50 °C vertical
mounting, mounting, mounting, mounting, mounting,
95% humidity, 95% humidity, 95% humidity, 95% humidity, 95% humidity,
non-condensing non-condensing non-condensing non-condensing non-condensing
• min. -20 °C -20 °C -20 °C -20 °C -20 °C
• max. 60 °C 60 °C 60 °C 60 °C; Number of 60 °C; Number of
simultaneously simultaneously
activated outputs: activated outputs:
8 (no adjacent points) 4 (no adjacent points)
at 60 °C horizontal or at 60 °C horizontal or
50 °C vertical, 50 °C vertical,
16 at 55 °C horizontal 8 at 55 °C horizontal or
or 45 °C vertical 45 °C vertical
3
required front connector Yes Yes Yes Yes Yes
Mechanics/material
Enclosure material (front)
• Plastic Yes Yes Yes Yes Yes
Dimensions
Width 45 mm 45 mm 45 mm 45 mm 70 mm
Height 100 mm 100 mm 100 mm 100 mm 100 mm
Depth 75 mm 75 mm 75 mm 75 mm 75 mm
Weights
Weight, approx. 180 g 220 g 190 g 260 g 310 g
■ Overview
• Digital outputs as a supplement to the integral I/O of
SIMATIC S7-1200 CPUs
• Can be plugged directly into the CPU
■ Technical specifications
Article number 6ES7222-1AD30-0XB0 6ES7222-1BD30-0XB0
SIGNAL BOARD SB1222, 4 DQ 5VDC 200KHZ SIGNAL BOARD SB1222, 4 DQ 24VDC 200KHZ
General information
Product type designation SB 1222 4xDQ 5VDC 200kHz SB 1222 4xDQ 24VDC 200kHz
Input current
from backplane bus 5 V DC, typ. 35 mA 35 mA
Power loss
Power loss, typ. 0.5 W 0.5 W
Digital outputs
Number of digital outputs 4; MOSFET, solid-state (current-sinking/current-sourcing) 4; MOSFET, solid-state (current-sinking/current-sourcing)
• in groups of 4 4
Short-circuit protection No No
Switching capacity of the outputs
• with resistive load, max. 0.1 A 0.1 A
Load resistance range
• upper limit 7 11
Output voltage
• Rated value (DC) 5V 24 V
• for signal "0", max. 0.2 V 1 V; with 10 kOhm load
• for signal "1", min. L+ minus 0.7 V DC L+ (-1.5 V)
• for signal "1", max. 6V
Output current
• for signal "1" rated value 0.1 A 0.1 A
• for signal "1" permissible range, 0.1 A
max.
Cable length
• shielded, max. 50 m 50 m
Diagnostics indication LED
• for status of the outputs Yes Yes
Degree and class of protection
Degree of protection acc. to
EN 60529
• IP20 Yes Yes
3
Ambient temperature during
operation
• permissible temperature range -20 °C to +60 °C horizontal mounting, -20 °C to +60 °C horizontal mounting,
-20 °C to 50 °C vertical mounting with 2 simultaneously -20 °C to 50 °C vertical mounting
activated, non-adjacent inputs;
otherwise up to 55 °C with horizontal mounting or
45 °C with vertical mounting
• min. -20 °C -20 °C
• max. 60 °C 60 °C
Mechanics/material
Enclosure material (front)
• Plastic Yes Yes
Dimensions
Width 38 mm 38 mm
Height 62 mm 62 mm
Depth 21 mm 21 mm
Weights
Weight, approx. 35 g 35 g
■ Overview
• Digital inputs and outputs as supplement to the integral I/O of
the CPUs
• For flexible adaptation of the controller to the relevant task
• For subsequent expansion of the system with additional inputs
and outputs
■ Technical specifications
Article number 6ES7223-1BH32- 6ES7223-1BL32- 6ES7223-1PH32- 6ES7223-1PL32- 6ES7223-1QH32-
0XB0 0XB0 0XB0 0XB0 0XB0
DIGITAL I/O SM 1223, DIGITAL I/O SM 1223, DIGITAL I/O SM 1223, DIGITAL I/O SM 1223, DIGITAL I/O SM 1223,
8 DI / 8 DO 16DI/16DO 8DI/8DO 16DI/16DO 8DI AC/ 8DO RLY
General information
Product type designation SM 1223 DI 8x24 VDC, SM 1223 DI 16x24 SM 1223 DI 8x24 VDC, SM 1223 DI 16x24 120/230 V AC SM223
DQ 8x24 VDC VDC, DQ 16x24 VDC DQ 8xRelay VDC, DQ 16xRelay DIx8/DQx8 RLY
Supply voltage
Rated value (DC)
• 24 V DC Yes Yes Yes Yes Yes
Input current
from backplane bus 5 V DC, max. 145 mA 185 mA 145 mA 180 mA 120 mA
Digital inputs
• from load voltage L+ (without load), 4 mA; per channel 4 mA; per channel 4 mA/input 11 mA/ 4 mA/input 11 mA/
max. relay relay
Output voltage
Power supply to the transmitters
• present Yes Yes Yes Yes Yes
Power loss
Power loss, typ. 2.5 W 4.5 W 5.5 W 10 W 7.5 W
Digital inputs
Number of digital inputs 8 16 8 16 8
• in groups of 2 2 2 2 4
Input characteristic curve in Yes Yes Yes Yes Yes
accordance with IEC 61131, type 1
Number of simultaneously
controllable inputs
all mounting positions
- up to 40 °C, max. 8 16 8 16 8
horizontal installation
- up to 40 °C, max. 8 16 8 16 8
- up to 50 °C, max. 8 16 8 16 8
vertical installation
- up to 40 °C, max. 8 16 8 16 8
Input voltage
• Type of input voltage DC DC DC DC AC
• Rated value (DC) 24 V 24 V 24 V 24 V
• Rated value (AC) 120/230V AC
• for signal "0" 5 V DC at 1 mA 5 V DC at 1 mA 5 V DC at 1 mA 5 V DC at 1 mA 20 V AC at 1 mA
• for signal "1" 15 V DC at 2.5 mA 15 V DC at 2.5 mA 15 V DC at 2.5 mA 15 V DC at 2.5 mA 79 V AC at 2.5 mA
Input current
• for signal "0", max. (permissible 1 mA 1 mA 1 mA 1 mA 1 mA
quiescent current)
• for signal "1", min. 2.5 mA 2.5 mA 2.5 mA 2.5 mA 2.5 mA
• for signal "1", typ. 4 mA 4 mA 4 mA 4 mA 9 mA
3
for standard inputs
- parameterizable Yes; 0.2 ms, 0.4 ms, Yes; 0.2 ms, 0.4 ms, Yes; 0.2 ms, 0.4 ms, Yes; 0.2 ms, 0.4 ms, Yes; 0.2 ms, 0.4 ms,
0.8 ms, 1.6 ms, 3.2 ms, 0.8 ms, 1.6 ms, 3.2 ms, 0.8 ms, 1.6 ms, 3.2 ms, 0.8 ms, 1.6 ms, 3.2 ms, 0.8 ms, 1.6 ms, 3.2 ms,
6.4 ms and 12.8 ms, 6.4 ms and 12.8 ms, 6.4 ms and 12.8 ms, 6.4 ms and 12.8 ms, 6.4 ms and 12.8 ms,
selectable in groups of selectable in groups of selectable in groups of selectable in groups of selectable in groups of
four four four four four
for interrupt inputs
- parameterizable Yes Yes Yes Yes Yes
Cable length
• shielded, max. 500 m 500 m 500 m 500 m 500 m
• unshielded, max. 300 m 300 m 300 m 300 m 300 m
Digital outputs
Number of digital outputs 8 16 8 16 8
• in groups of 1 1 2 4 4
Short-circuit protection No; to be provided No; to be provided No; to be provided No; to be provided No; to be provided
externally externally externally externally externally
Limitation of inductive shutdown L+ (-48 V) L+ (-48 V)
voltage to
Switching capacity of the outputs
• with resistive load, max. 0.5 A 0.5 A 2A 2A 2A
• on lamp load, max. 5W 5W 30 W with DC, 30 W with DC, 30 W with DC,
200 W with AC 200 W with AC 200 W with AC
Output voltage
• Rated value (DC) 24 V 24 V 5 V DC to 30 V DC 5 V DC to 30 V DC 5 V DC to 30 V DC
• Rated value (AC) 5 V AC to 250 V AC 5 V AC to 250 V AC 5 V AC to 250 V AC
• for signal "0", max. 0.1 V; 0.1 V;
with 10 kOhm load with 10 kOhm load
• for signal "1", min. 20 V DC 20 V DC
Output current
• for signal "1" rated value 0.5 A 0.5 A
• for signal "1" permissible range, 0.5 A 0.5 A 2A 2A 2A
max.
• for signal "0" residual current, max. 10 µA 10 µA
Output delay with resistive load
• "0" to "1", max. 50 µs 50 µs 10 ms 10 ms 10 ms
• "1" to "0", max. 200 µs 200 µs 10 ms 10 ms 10 ms
Total current of the outputs (per
group)
horizontal installation
- up to 50 °C, max. 4 A; Current per mass 8 A; Current per mass 10 A; Current per 8 A; Current per mass 8 A; Current per mass
mass
Relay outputs
• Number of relay outputs 8 16 8
• Rated supply voltage of relay coil L+ 24 V 24 V 24 V
(DC)
• Number of operating cycles, max. mechanically mechanically mechanically
10 million, at rated 10 million, at rated 10 million, at rated
load voltage 100 000 load voltage 100 000 load voltage 100 000
Switching capacity of contacts
- with inductive load, max. 0.5 A 2A 2A 2A
- on lamp load, max. 5W 30 W with DC, 30 W with DC, 30 W with DC,
200 W with AC 200 W with AC 200 W with AC
- with resistive load, max. 0.5 A 2A 2A 2A
Cable length
• shielded, max. 500 m 500 m 500 m 500 m 500 m
• unshielded, max. 150 m 150 m 150 m 150 m 150 m
3
Alarms
• Diagnostic alarm Yes Yes Yes Yes Yes
Diagnostics indication LED
• for status of the inputs Yes Yes Yes Yes Yes
• for status of the outputs Yes Yes Yes Yes Yes
Potential separation
Potential separation digital inputs
• between the channels, in groups of 2 2 2 2 2
Potential separation digital outputs
• between the channels Relays Relays Relays
• between the channels, in groups of 1 1 2 4 2
• between the channels and 500 V AC 500 V AC 1500 V AC for 1 minute 1500 V AC for 1 minute 1500 V AC for 1 minute
backplane bus
Permissible potential difference
between different circuits 750 V AC for 1 minute 750 V AC for 1 minute 750 V AC for 1 minute
Degree and class of protection
Degree of protection acc. to
EN 60529
• IP20 Yes Yes Yes Yes Yes
Standards, approvals, certificates
CE mark Yes Yes Yes Yes Yes
CSA approval Yes Yes Yes Yes Yes
cULus Yes Yes Yes Yes Yes
FM approval Yes Yes Yes Yes Yes
RCM (formerly C-TICK) Yes Yes Yes Yes Yes
Marine approval
• Marine approval Yes Yes Yes Yes
Ambient conditions
Free fall
• Fall height, max. 0.3 m; five times, in 0.3 m; five times, in 0.3 m; five times, in 0.3 m; five times, in 0.3 m; five times, in
product package product package product package product package product package
Ambient temperature during
operation
• permissible temperature range -20 °C to +60 °C -20 °C to +60 °C -20 °C to +60 °C -20 °C to +60 °C -20 °C to +60 °C
horizontal mounting, horizontal mounting, horizontal mounting, horizontal mounting, horizontal mounting,
-20 °C to 50 °C vertical -20 °C to 50 °C vertical -20 °C to 50 °C vertical -20 °C to 50 °C vertical -20 °C to 50 °C vertical
mounting, mounting, mounting, mounting, mounting,
95% humidity, 95% humidity, 95% humidity, 95% humidity, 95% humidity,
non-condensing non-condensing non-condensing non-condensing non-condensing
• min. -20 °C -20 °C -20 °C -20 °C -20 °C
• max. 60 °C 60 °C 60 °C 60 °C; Number of 60 °C; Number of
simultaneously simultaneously
activated outputs: activated outputs:
8 (no adjacent points) 4 (no adjacent points)
at 60 °C horizontal or at 60 °C horizontal or
50 °C vertical, 50 °C vertical,
16 at 55 °C horizontal 8 at 55 °C horizontal or
or 45 °C vertical 45 °C vertical
Connection method
required front connector Yes Yes Yes Yes Yes
Mechanics/material
Enclosure material (front)
• Plastic Yes Yes Yes Yes Yes
Dimensions
Width 45 mm 70 mm 45 mm 70 mm 45 mm
Height 100 mm 100 mm 100 mm 100 mm 100 mm
Depth 75 mm 75 mm 75 mm 75 mm 75 mm
Weights
Weight, approx. 210 g 310 g 230 g 350 g 230 g
■ Overview
• Digital inputs and outputs as supplement to the integral I/O of
the SIMATIC S7-1200 CPUs
• Can be plugged direct into the CPU
■ Technical specifications
Article number 6ES7223-0BD30-0XB0 6ES7223-3AD30-0XB0 6ES7223-3BD30-0XB0
SIGNAL BOARD SB1223, 2 DI/2 DO SIGNAL BOARD SB 1223, 2DI/2DQ 5V SIGNAL BOARD SB 1223, 2DI/2DQ
200KHZ 24V 200KHZ
General information
Product type designation SB 1223 DI2x24 VDC, DQ 2x24 VDC SB 1223 2xDI / 2xDQ 5VDC 200kHz SB 1223 2xDI / 2xDQ 24VDC 200kHz
Input current
from backplane bus 5 V DC, typ. 50 mA 35 mA 35 mA
Output voltage
Power supply to the transmitters
• Supply current, max. 4 mA; per channel
Power loss
Power loss, typ. 1W 0.5 W 0.5 W
Digital inputs
Number of digital inputs 2; Current-sinking 2; Current-sourcing 2; Current-sourcing
• in groups of 1 2 2
Input characteristic curve in Yes
accordance with IEC 61131, type 1
Number of simultaneously
controllable inputs
all mounting positions
- up to 40 °C, max. 2 2
Input voltage
• Type of input voltage DC DC DC
• Rated value (DC) 24 V 5V 24 V
• for signal "0" 0 to 5 V (L+ minus 1.0 V DC) ... L+ (L+ minus 5.0 V DC) ... L+
• for signal "1" +15 to +30V 0 V ... (L+ minus 2.0 V DC) 0 V ... (L+ minus 10 V DC)
Input current
• for signal "0", max. (permissible 1 mA 2.2 mA 1.4 mA
quiescent current)
• for signal "1", min. 5.1 mA 2.9 mA
• for signal "1", typ. 0.5 A 7 mA
■ Overview
• Digital inputs as supplement to the integral I/O of the CPUs
• For flexible adaptation of the controller to the corresponding
task
• For subsequent expansion of the system with additional inputs
• From +60 °C to +70 °C, max. 50% of the inputs can be
3
controlled simultaneously
Note:
SIPLUS extreme products are based on SIMATIC standard
products. The contents listed here were taken from the respec-
tive standard products. SIPLUS extreme-specific information
was added.
■ Technical specifications
Article number 6AG1221-1BF32-2XB0 6AG1221-1BF32-4XB0 6AG1221-1BH32-2XB0 6AG1221-1BH32-4XB0
Based on 6ES7221-1BF32-0XB0 6ES7221-1BF32-0XB0 6ES7221-1BH32-0XB0 6ES7221-1BH32-0XB0
SIPLUS S7-1200 SM 1221 SIPLUS S7-1200 SM 1221 SIPLUS S7-1200 SM 1221 SIPLUS S7-1200 SM 1221
8DI 8DI 16DI 16DI
Ambient conditions
Free fall
• Fall height, max. 0.3 m; five times, in product 0.3 m; five times, in product 0.3 m; five times, in product 0.3 m; five times, in product
package package package package
Ambient temperature during
operation
• min. -40 °C; = Tmin; -20 °C; = Tmin; -40 °C; = Tmin; -20 °C; = Tmin;
Startup @ -25 °C Startup @ 0 °C Startup @ -25 °C Startup @ 0 °C
• max. 70 °C; = Tmax; 60 °C; = Tmax 70 °C; = Tmax; 60 °C; = Tmax
Tmax > +60 °C number of Tmax > +60 °C number of
simultaneously activated simultaneously activated
inputs 4 (no adjacent points) inputs 8 (no adjacent points)
for horizontal mounting for horizontal mounting
position position
Extended ambient conditions
• relative to ambient temperature- Tmin ... Tmax at Tmin ... Tmax at Tmin ... Tmax at Tmin ... Tmax at
atmospheric pressure-installation 1080 hPa ... 795 hPa 1080 hPa ... 795 hPa 1080 hPa ... 795 hPa 1080 hPa ... 795 hPa
altitude (-1000 m ... +2000 m) // (-1000 m ... +2000 m) // (-1000 m ... +2000 m) // (-1000 m ... +2000 m) //
Tmin ... (Tmax - 10K) at Tmin ... (Tmax - 10K) at Tmin ... (Tmax - 10K) at Tmin ... (Tmax - 10K) at
795 hPa ... 658 hPa 795 hPa ... 658 hPa 795 hPa ... 658 hPa 795 hPa ... 658 hPa
(+2000 m ... +3500 m) // (+2000 m ... +3500 m) // (+2000 m ... +3500 m) // (+2000 m ... +3500 m) //
Tmin ... (Tmax - 20K) at Tmin ... (Tmax - 20K) at Tmin ... (Tmax - 20K) at Tmin ... (Tmax - 20K) at
658 hPa ... 540 hPa 658 hPa ... 540 hPa 658 hPa ... 540 hPa 658 hPa ... 540 hPa
(+3500 m ... +5000 m) (+3500 m ... +5000 m) (+3500 m ... +5000 m) (+3500 m ... +5000 m)
Relative humidity
- With condensation, tested in 100%; RH incl. conden- 100%; RH incl. conden- 100%; RH incl. conden- 100%; RH incl. conden-
accordance with IEC 60068-2-38, sation/frost (no commis- sation/frost (no commis- sation/frost (no commis- sation/frost (no commis-
max. sioning under condensation sioning under condensation sioning under condensation sioning under condensation
conditions) conditions) conditions) conditions)
Resistance
- against biologically active Yes; Class 3B2 mold, fungus Yes; Class 3B2 mold, fungus Yes; Class 3B2 mold, fungus Yes; Class 3B2 mold, fungus
substances / conformity with and dry rot spores (with the and dry rot spores (with the and dry rot spores (with the and dry rot spores (with the
EN 60721-3-3 exception of fauna). The exception of fauna). The exception of fauna). The exception of fauna). The
supplied connector covers supplied connector covers supplied connector covers supplied connector covers
must remain on the unused must remain on the unused must remain on the unused must remain on the unused
interfaces during operation! interfaces during operation! interfaces during operation! interfaces during operation!
- against chemically active Yes; Class 3C4 (RH < 75%) Yes; Class 3C4 (RH < 75%) Yes; Class 3C4 (RH < 75%) Yes; Class 3C4 (RH < 75%)
substances / conformity with incl. salt spray according to incl. salt spray according to incl. salt spray according to incl. salt spray according to
EN 60721-3-3 EN 60068-2-52 (degree of EN 60068-2-52 (degree of EN 60068-2-52 (degree of EN 60068-2-52 (degree of
severity 3). The supplied severity 3). The supplied severity 3). The supplied severity 3). The supplied
connector covers must connector covers must connector covers must connector covers must
remain on the unused inter- remain on the unused inter- remain on the unused inter- remain on the unused inter-
faces during operation! faces during operation! faces during operation! faces during operation!
- against mechanically active Yes; Class 3S4 incl. sand, Yes; Class 3S4 incl. sand, Yes; Class 3S4 incl. sand, Yes; Class 3S4 incl. sand,
substances / conformity with dust. The supplied dust. The supplied dust. The supplied dust. The supplied
EN 60721-3-3 connector covers must connector covers must connector covers must connector covers must
remain on the unused inter- remain on the unused inter- remain on the unused inter- remain on the unused inter-
faces during operation! faces during operation! faces during operation! faces during operation!
■ Overview
• Digital inputs as a supplement to the integral I/O of
SIMATIC S7-1200 CPUs
• Can be plugged directly into the CPU
Note:
SIPLUS extreme products are based on SIMATIC standard
products. The contents listed here were adopted from the re-
spective standard products. SIPLUS extreme specific informa- 3
tion was added.
■ Technical specifications
Article number 6AG1221-3AD30-5XB0 6AG1221-3BD30-5XB0
Based on 6ES7221-3AD30-0XB0 6ES7221-3BD30-0XB0
SIPLUS S7-1200 SB 1221 4DI 5VDC SIPLUS S7-1200 SB 1221 4DI 24VDC
Ambient conditions
Ambient temperature during
operation
• min. -40 °C; = Tmin; Startup @ -25 °C -40 °C; = Tmin; Startup @ -25 °C
• max. 60 °C; = Tmax; Tmax > 55 °C number of simultaneously 60 °C; = Tmax; Tmax > 55 °C number of simultaneously
activated inputs 2 (no adjacent points) for horizontal activated inputs 2 (no adjacent points) for horizontal
mounting position mounting position
Extended ambient conditions
• relative to ambient temperature- Tmin ... Tmax at 1080 hPa ... 795 hPa Tmin ... Tmax at 1080 hPa ... 795 hPa
atmospheric pressure-installation (-1000 m ... +2000 m) // (-1000 m ... +2000 m) //
altitude Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa
(+2000 m ... +3500 m) // (+2000 m ... +3500 m) //
Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa
(+3500 m ... +5000 m) (+3500 m ... +5000 m)
Relative humidity
- With condensation, tested in 100%; RH incl. condensation / frost (no commissioning in 100%; RH incl. condensation / frost (no commissioning in
accordance with IEC 60068-2-38, bedewed state), horizontal installation bedewed state), horizontal installation
max.
Resistance
- against biologically active Yes; Class 3B2 mold, fungus and dry rot spores (with the Yes; Class 3B2 mold, fungus and dry rot spores (with the
substances / conformity with exception of fauna). The supplied connector covers must exception of fauna). The supplied connector covers must
EN 60721-3-3 remain on the unused interfaces during operation! remain on the unused interfaces during operation!
- against chemically active Yes; Class 3C4 (RH < 75%) incl. salt spray according to Yes; Class 3C4 (RH < 75%) incl. salt spray according to
substances / conformity with EN 60068-2-52 (degree of severity 3). The supplied EN 60068-2-52 (degree of severity 3). The supplied
EN 60721-3-3 connector covers must remain on the unused interfaces connector covers must remain on the unused interfaces
during operation! during operation!
- against mechanically active Yes; Class 3S4 incl. sand, dust. The supplied connector Yes; Class 3S4 incl. sand, dust. The supplied connector
substances / conformity with covers must remain on the unused interfaces during covers must remain on the unused interfaces during
EN 60721-3-3 operation! operation!
■ Overview
• Digital outputs as a supplement to the integral I/O of the CPUs
• For flexible adaptation of the controller to the corresponding
task
• For subsequent expansion of the system with additional
outputs
3
• From +60 °C to +70 °C, max. 50% of the inputs can be
controlled simultaneously
Note:
SIPLUS extreme products are based on SIMATIC standard
products. The contents listed here were taken from the respec-
tive standard products. SIPLUS extreme-specific information
was added.
■ Technical specifications
Article number 6AG1222-1BF32-2XB0 6AG1222-1BF32-4XB0 6AG1222-1BH32-2XB0 6AG1222-1BH32-4XB0
Based on 6ES7222-1BF32-0XB0 6ES7222-1BF32-0XB0 6ES7222-1BH32-0XB0 6ES7222-1BH32-0XB0
SIPLUS S7-1200 SM 1222 SIPLUS S7-1200 SM 1222 SIPLUS S7-1200 SM 1222 SIPLUS S7-1200 SM 1222
8DQ 8DQ 16DQ 16DQ
Ambient conditions
Free fall
• Fall height, max. 0.3 m; five times, in product 0.3 m; five times, in product 0.3 m; five times, in product 0.3 m; five times, in product
package package package package
Ambient temperature during
operation
• min. -40 °C; = Tmin; -20 °C; = Tmin; -40 °C; = Tmin; -20 °C; = Tmin;
Startup @ -25 °C Startup @ 0 °C Startup @ -25 °C Startup @ 0 °C
• max. 70 °C; = Tmax; 60 °C; = Tmax 70 °C; = Tmax; 60 °C; = Tmax
Tmax > +60 °C number of Tmax > +60 °C number of
simultaneously activated simultaneously activated
outputs 4 (no adjacent outputs 8 (no adjacent
points) for horizontal points) for horizontal
mounting position mounting position
Extended ambient conditions
• relative to ambient temperature- Tmin ... Tmax at Tmin ... Tmax at Tmin ... Tmax at Tmin ... Tmax at
atmospheric pressure-installation 1080 hPa ... 795 hPa 1080 hPa ... 795 hPa 1080 hPa ... 795 hPa 1080 hPa ... 795 hPa
altitude (-1000 m ... +2000 m) // (-1000 m ... +2000 m) // (-1000 m ... +2000 m) // (-1000 m ... +2000 m) //
Tmin ... (Tmax - 10K) at Tmin ... (Tmax - 10K) at Tmin ... (Tmax - 10K) at Tmin ... (Tmax - 10K) at
795 hPa ... 658 hPa 795 hPa ... 658 hPa 795 hPa ... 658 hPa 795 hPa ... 658 hPa
(+2000 m ... +3500 m) // (+2000 m ... +3500 m) // (+2000 m ... +3500 m) // (+2000 m ... +3500 m) //
Tmin ... (Tmax - 20K) at Tmin ... (Tmax - 20K) at Tmin ... (Tmax - 20K) at Tmin ... (Tmax - 20K) at
658 hPa ... 540 hPa 658 hPa ... 540 hPa 658 hPa ... 540 hPa 658 hPa ... 540 hPa
(+3500 m ... +5000 m) (+3500 m ... +5000 m) (+3500 m ... +5000 m) (+3500 m ... +5000 m)
Relative humidity
- With condensation, tested in 100%; RH incl. conden- 100%; RH incl. conden- 100%; RH incl. conden- 100%; RH incl. conden-
accordance with IEC 60068-2-38, sation/frost (no commis- sation/frost (no commis- sation/frost (no commis- sation/frost (no commis-
max. sioning under condensation sioning under condensation sioning under condensation sioning under condensation
conditions) conditions) conditions) conditions)
Resistance
- against biologically active Yes; Class 3B2 mold, fungus Yes; Class 3B2 mold, fungus Yes; Class 3B2 mold, fungus Yes; Class 3B2 mold, fungus
substances / conformity with and dry rot spores (with the and dry rot spores (with the and dry rot spores (with the and dry rot spores (with the
EN 60721-3-3 exception of fauna). The exception of fauna). The exception of fauna). The exception of fauna). The
supplied connector covers supplied connector covers supplied connector covers supplied connector covers
must remain on the unused must remain on the unused must remain on the unused must remain on the unused
interfaces during operation! interfaces during operation! interfaces during operation! interfaces during operation!
- against chemically active Yes; Class 3C4 (RH < 75%) Yes; Class 3C4 (RH < 75%) Yes; Class 3C4 (RH < 75%) Yes; Class 3C4 (RH < 75%)
substances / conformity with incl. salt spray according to incl. salt spray according to incl. salt spray according to incl. salt spray according to
EN 60721-3-3 EN 60068-2-52 (degree of EN 60068-2-52 (degree of EN 60068-2-52 (degree of EN 60068-2-52 (degree of
severity 3). The supplied severity 3). The supplied severity 3). The supplied severity 3). The supplied
connector covers must connector covers must connector covers must connector covers must
remain on the unused inter- remain on the unused inter- remain on the unused inter- remain on the unused inter-
faces during operation! faces during operation! faces during operation! faces during operation!
- against mechanically active Yes; Class 3S4 incl. sand, Yes; Class 3S4 incl. sand, Yes; Class 3S4 incl. sand, Yes; Class 3S4 incl. sand,
substances / conformity with dust. The supplied dust. The supplied dust. The supplied dust. The supplied
EN 60721-3-3 connector covers must connector covers must connector covers must connector covers must
remain on the unused inter- remain on the unused inter- remain on the unused inter- remain on the unused inter-
faces during operation! faces during operation! faces during operation! faces during operation!
■ Overview
• Digital outputs as a supplement to the integral I/O of the CPUs
• For flexible adaptation of the controller to the respective task
• For subsequent expansion of the system with additional
outputs
• Can be plugged directly into the CPU
• From +60 °C to +70 °C, max. 50% of the inputs can be
controlled simultaneously 3
Note:
SIPLUS extreme products are based on SIMATIC standard
products. The contents listed here were taken from the respec-
tive standard products. SIPLUS extreme specific information
was added.
■ Technical specifications
Article number 6AG1222-1AD30-5XB0 6AG1222-1BD30-5XB0
Based on 6ES7222-1AD30-0XB0 6ES7222-1BD30-0XB0
SIPLUS S7-1200 SB 1222 4DQ 5VDC SIPLUS S7-1200 SB 1222 4DQ 24VDC
Ambient temperature during
operation
• min. -40 °C; = Tmin; Startup @ -25 °C -40 °C; = Tmin; Startup @ -25 °C
• max. 60 °C; = Tmax; Tmax > 55 °C number of simultaneously 60 °C; = Tmax; Tmax > 55 °C number of simultaneously
activated outputs 2 (no adjacent points) for horizontal activated outputs 2 (no adjacent points) for horizontal
mounting position mounting position
Extended ambient conditions
• relative to ambient temperature- Tmin ... Tmax at 1080 hPa ... 795 hPa Tmin ... Tmax at 1080 hPa ... 795 hPa
atmospheric pressure-installation (-1000 m ... +2000 m) // (-1000 m ... +2000 m) //
altitude Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa
(+2000 m ... +3500 m) // (+2000 m ... +3500 m) //
Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa
(+3500 m ... +5000 m) (+3500 m ... +5000 m)
Relative humidity
- With condensation, tested in 100%; RH incl. condensation / frost (no commissioning in 100%; RH incl. condensation / frost (no commissioning in
accordance with IEC 60068-2-38, bedewed state), horizontal installation bedewed state), horizontal installation
max.
Resistance
- against biologically active Yes; Class 3B2 mold, fungus and dry rot spores (with the Yes; Class 3B2 mold, fungus and dry rot spores (with the
substances / conformity with exception of fauna). The supplied connector covers must exception of fauna). The supplied connector covers must
EN 60721-3-3 remain on the unused interfaces during operation! remain on the unused interfaces during operation!
- against chemically active Yes; Class 3C4 (RH < 75%) incl. salt spray according to Yes; Class 3C4 (RH < 75%) incl. salt spray according to
substances / conformity with EN 60068-2-52 (degree of severity 3). The supplied EN 60068-2-52 (degree of severity 3). The supplied
EN 60721-3-3 connector covers must remain on the unused interfaces connector covers must remain on the unused interfaces
during operation! during operation!
- against mechanically active Yes; Class 3S4 incl. sand, dust. The supplied connector Yes; Class 3S4 incl. sand, dust. The supplied connector
substances / conformity with covers must remain on the unused interfaces during covers must remain on the unused interfaces during
EN 60721-3-3 operation! operation!
SIPLUS SB 1222 digital output Accessories See SIMATIC S7-1200 digital output
signal board module SB 1222, page 3/57
(Extended temperature range and
exposure to media)
4 outputs, 5 V DC, 0.1 A, 200 kHz 6AG1222-1AD30-5XB0
4 outputs, 24 V DC, 0.1 A, 200 kHz 6AG1222-1BD30-5XB0
■ Overview
• Digital inputs and outputs as supplement to the integral I/O of
the CPUs
• For flexible adaptation of the controller to the corresponding
task
• For subsequent expansion of the system with additional inputs
and outputs
3 • From +60 °C to +70 °C, max. 50% of the inputs can be
controlled simultaneously
Note:
SIPLUS extreme products are based on SIMATIC standard
products. The contents listed here were taken from the respec-
tive standard products. SIPLUS extreme-specific information
was added.
■ Technical specifications
Article number 6AG1223-1BH32-2XB0 6AG1223-1BH32-4XB0 6AG1223-1PH32-2XB0 6AG1223-1PH32-4XB0
Based on 6ES7223-1BH32-0XB0 6ES7223-1BH32-0XB0 6ES7223-1PH32-0XB0 6ES7223-1PH32-0XB0
SIPLUS S7-1200 SM 1223 SIPLUS S7-1200 SM 1223 SIPLUS S7-1200 SM 1223 SIPLUS S7-1200 SM 1223
8DI/8DQ 8DI/8DQ 8DI/8DQ RLY 8DI/8DQ RLY
Ambient conditions
Free fall
• Fall height, max. 0.3 m; five times, in product 0.3 m; five times, in product 0.3 m; five times, in product 0.3 m; five times, in product
package package package package
Ambient temperature during
operation
• min. -40 °C; = Tmin; -20 °C; = Tmin; -40 °C; = Tmin; -20 °C; = Tmin;
Startup @ -25 °C Startup @ 0 °C Startup @ -25 °C Startup @ 0 °C
• max. 70 °C; = Tmax; 60 °C; = Tmax 70 °C; = Tmax; 60 °C; = Tmax
Tmax > +60 °C number of Tmax > +60 °C number of
simultaneously activated simultaneously activated
outputs 4, inputs 4 outputs 4, inputs 4
(no adjacent points) for (no adjacent points) for
horizontal mounting position horizontal mounting position
Extended ambient conditions
• relative to ambient temperature- Tmin ... Tmax at Tmin ... Tmax at Tmin ... Tmax at Tmin ... Tmax at
atmospheric pressure-installation 1080 hPa ... 795 hPa 1080 hPa ... 795 hPa 1080 hPa ... 795 hPa 1080 hPa ... 795 hPa
altitude (-1000 m ... +2000 m) // (-1000 m ... +2000 m) // (-1000 m ... +2000 m) // (-1000 m ... +2000 m) //
Tmin ... (Tmax - 10K) at Tmin ... (Tmax - 10K) at Tmin ... (Tmax - 10K) at Tmin ... (Tmax - 10K) at
795 hPa ... 658 hPa 795 hPa ... 658 hPa 795 hPa ... 658 hPa 795 hPa ... 658 hPa
(+2000 m ... +3500 m) // (+2000 m ... +3500 m) // (+2000 m ... +3500 m) // (+2000 m ... +3500 m) //
Tmin ... (Tmax - 20K) at Tmin ... (Tmax - 20K) at Tmin ... (Tmax - 20K) at Tmin ... (Tmax - 20K) at
658 hPa ... 540 hPa 658 hPa ... 540 hPa 658 hPa ... 540 hPa 658 hPa ... 540 hPa
(+3500 m ... +5000 m) (+3500 m ... +5000 m) (+3500 m ... +5000 m) (+3500 m ... +5000 m)
• At cold restart, min. -25 °C
Relative humidity
- With condensation, tested in 100%; RH incl. conden- 100%; RH incl. conden- 100%; RH incl. conden- 100%; RH incl. conden-
accordance with IEC 60068-2-38, sation/frost (no commis- sation/frost (no commis- sation/frost (no commis- sation/frost (no commis-
max. sioning under condensation sioning under condensation sioning under condensation sioning under condensation
conditions) conditions) conditions) conditions)
Resistance
- against biologically active Yes; Class 3B2 mold, fungus Yes; Class 3B2 mold, fungus Yes; Class 3B2 mold, fungus Yes; Class 3B2 mold, fungus
substances / conformity with and dry rot spores (with the and dry rot spores (with the and dry rot spores (with the and dry rot spores (with the
EN 60721-3-3 exception of fauna). The exception of fauna). The exception of fauna). The exception of fauna). The
supplied connector covers supplied connector covers supplied connector covers supplied connector covers
must remain on the unused must remain on the unused must remain on the unused must remain on the unused
interfaces during operation! interfaces during operation! interfaces during operation! interfaces during operation!
- against chemically active Yes; Class 3C4 (RH < 75%) Yes; Class 3C4 (RH < 75%) Yes; Class 3C4 (RH < 75%) Yes; Class 3C4 (RH < 75%)
substances / conformity with incl. salt spray according to incl. salt spray according to incl. salt spray according to incl. salt spray according to
EN 60721-3-3 EN 60068-2-52 (degree of EN 60068-2-52 (degree of EN 60068-2-52 (degree of EN 60068-2-52 (degree of
severity 3). The supplied severity 3). The supplied severity 3). The supplied severity 3). The supplied
connector covers must connector covers must connector covers must connector covers must
remain on the unused inter- remain on the unused inter- remain on the unused inter- remain on the unused inter-
faces during operation! faces during operation! faces during operation! faces during operation!
- against mechanically active Yes; Class 3S4 incl. sand, Yes; Class 3S4 incl. sand, Yes; Class 3S4 incl. sand, Yes; Class 3S4 incl. sand,
substances / conformity with dust. The supplied dust. The supplied dust. The supplied dust. The supplied
EN 60721-3-3 connector covers must connector covers must connector covers must connector covers must
remain on the unused inter- remain on the unused inter- remain on the unused inter- remain on the unused inter-
faces during operation! faces during operation! faces during operation! faces during operation!
3 8 transistor outputs,
24 V DC, 0.5 A, 5 W
• Suitable for areas with 6AG1223-1BH32-4XB0
(conformal coating)
• -25 ... +70 °C,
from +60 … +70 °C number of
6AG1223-1PH32-2XB0
■ Overview
• Digital inputs and outputs as supplement to the integral I/O of
the SIPLUS S7-1200-CPUs
• Can be plugged directly into the CPU
(cannot be used for +70 °C version)
Note:
SIPLUS extreme products are based on SIMATIC standard prod-
ucts. The contents listed here were taken from the respective 3
standard products. SIPLUS extreme-specific information was
added.
■ Technical specifications
Article number 6AG1223-0BD30-4XB0 6AG1223-0BD30-5XB0 6AG1223-3AD30-5XB0 6AG1223-3BD30-5XB0
Based on 6ES7223-0BD30-0XB0 6ES7223-0BD30-0XB0 6ES7223-3AD30-0XB0 6ES7223-3BD30-0XB0
SIPLUS S7-1200 SB 1223 SIPLUS S7-1200 SB 1223 SIPLUS S7-1200 SB 1223 SIPLUS S7-1200 SB 1223
2DI/2DQ 24VDC 2DI/2DQ 24VDC 2DI/2DQ 5VDC 2DI/2DQ, 24VDC
Ambient conditions
Free fall
• Fall height, max. 0.3 m; five times, in product
package
Ambient temperature during
operation
• min. 0 °C; = Tmin -40 °C; = Tmin; -40 °C; = Tmin; -40 °C; = Tmin;
Startup @ -25 °C Startup @ -25 °C Startup @ -25 °C
• max. 55 °C; = Tmax 60 °C; = Tmax 60 °C; = Tmax 60 °C; = Tmax
Extended ambient conditions
• relative to ambient temperature- Tmin ... Tmax at Tmin ... Tmax at Tmin ... Tmax at Tmin ... Tmax at
atmospheric pressure-installation 1080 hPa ... 795 hPa 1080 hPa ... 795 hPa 1080 hPa ... 795 hPa 1080 hPa ... 795 hPa
altitude (-1000 m ... +2000 m) // (-1000 m ... +2000 m) // (-1000 m ... +2000 m) // (-1000 m ... +2000 m) //
Tmin ... (Tmax - 10K) at Tmin ... (Tmax - 10K) at Tmin ... (Tmax - 10K) at Tmin ... (Tmax - 10K) at
795 hPa ... 658 hPa 795 hPa ... 658 hPa 795 hPa ... 658 hPa 795 hPa ... 658 hPa
(+2000 m ... +3500 m) // (+2000 m ... +3500 m) // (+2000 m ... +3500 m) // (+2000 m ... +3500 m) //
Tmin ... (Tmax - 20K) at Tmin ... (Tmax - 20K) at Tmin ... (Tmax - 20K) at Tmin ... (Tmax - 20K) at
658 hPa ... 540 hPa 658 hPa ... 540 hPa 658 hPa ... 540 hPa 658 hPa ... 540 hPa
(+3500 m ... +5000 m) (+3500 m ... +5000 m) (+3500 m ... +5000 m) (+3500 m ... +5000 m)
Relative humidity
- With condensation, tested in 100%; Relative humidity, incl. 100%; RH incl. condensation 100%; RH incl. condensation 100%; RH incl. condensation
accordance with IEC 60068-2-38, condensation / frost / frost (no commissioning in / frost (no commissioning in / frost (no commissioning in
max. permitted (no commis- bedewed state), horizontal bedewed state), horizontal bedewed state), horizontal
sioning under condensation installation installation installation
conditions)
Resistance
- against biologically active Yes; Class 3B2 mold, fungus Yes; Class 3B2 mold, fungus Yes; Class 3B2 mold, fungus Yes; Class 3B2 mold, fungus
substances / conformity with and dry rot spores (with the and dry rot spores (with the and dry rot spores (with the and dry rot spores (with the
EN 60721-3-3 exception of fauna). The exception of fauna). The exception of fauna). The exception of fauna). The
supplied connector covers supplied connector covers supplied connector covers supplied connector covers
must remain on the unused must remain on the unused must remain on the unused must remain on the unused
interfaces during operation! interfaces during operation! interfaces during operation! interfaces during operation!
- against chemically active Yes; Class 3C4 incl. salt Yes; Class 3C4 (RH < 75%) Yes; Class 3C4 (RH < 75%) Yes; Class 3C4 (RH < 75%)
substances / conformity with spray according to incl. salt spray according to incl. salt spray according to incl. salt spray according to
EN 60721-3-3 EN 60068-2-52 (degree of EN 60068-2-52 (degree of EN 60068-2-52 (degree of EN 60068-2-52 (degree of
severity 3). The supplied severity 3). The supplied severity 3). The supplied severity 3). The supplied
connector covers must connector covers must connector covers must connector covers must
remain on the unused inter- remain on the unused inter- remain on the unused inter- remain on the unused inter-
faces during operation! faces during operation! faces during operation! faces during operation!
- against mechanically active Yes; Class 3S4 incl. sand, Yes; Class 3S4 incl. sand, Yes; Class 3S4 incl. sand, Yes; Class 3S4 incl. sand,
substances / conformity with dust. The supplied dust. The supplied dust. The supplied dust. The supplied
EN 60721-3-3 connector covers must connector covers must connector covers must connector covers must
remain on the unused inter- remain on the unused inter- remain on the unused inter- remain on the unused inter-
faces during operation! faces during operation! faces during operation! faces during operation!
3 2 transistor outputs
24 V DC, 0.5 A, 5 W;
can be used as HSC at up to
30 kHz
• Suitable for areas with extreme 6AG1223-0BD30-4XB0
medial exposure
(conformal coating)
• Ambient temperature 6AG1223-0BD30-5XB0
-25 ... +55 °C
2 inputs, 5 V DC, 200 kHz 6AG1223-3AD30-5XB0
2 outputs 5 V DC, 0.1 A, 200 kHz
2 inputs, 24 V DC, 200 kHz 6AG1223-3BD30-5XB0
2 outputs 24 V DC, 0.1 A, 200 kHz
■ Overview
• Analog inputs for SIMATIC S7-1200
• With extremely short conversion times
• For connecting analog sensors without additional amplifiers
• For solving even more complex automation tasks
■ Technical specifications
Article number 6ES7231-4HD32-0XB0 6ES7231-4HF32-0XB0 6ES7231-5ND32-0XB0
ANALOG INPUT SM 1231, 4AI ANALOG INPUT SM 1231, 8AI ANALOG INPUT SM 1231, 4AI 16BIT
General information
Product type designation SM 1231 AI 4x13 bit SM 1231 AI 8 x 13 bit SM 1231 AI 4 x 16 bit
Supply voltage
Rated value (DC)
• 24 V DC Yes Yes Yes
Input current
Current consumption, typ. 45 mA 45 mA 65 mA
from backplane bus 5 V DC, typ. 80 mA 90 mA 80 mA
Power loss
Power loss, typ. 1.5 W 1.5 W 1.8 W
Analog inputs
Number of analog inputs 4; Current or voltage differential inputs 8; Current or voltage differential inputs 4; Current or voltage differential inputs
permissible input voltage for current ±35 V ±35 V ±15 V
input (destruction limit), max.
permissible input voltage for voltage 35 V 35 V ±35 V
input (destruction limit), max.
permissible input current for voltage 40 mA 40 mA 40 mA;
input (destruction limit), max. limited by input resistance 1 MOhm
permissible input current for current 40 mA 40 mA 40 mA
input (destruction limit), max.
Cycle time (all channels) max. 625 µs 625 µs 100 µs
Input ranges
• Voltage Yes; ±10V, ±5V, ±2.5V Yes; ±10V, ±5V, ±2.5V Yes; ±10V, ±5V, ±2.5V or ±1.25V
• Current Yes; 4 to 20 mA, 0 to 20 mA Yes; 4 to 20 mA, 0 to 20 mA Yes; 4 to 20 mA, 0 to 20 mA
• Thermocouple No No No
• Resistance thermometer No No No
• Resistance No Yes No
Input ranges (rated values),
voltages
• -1.25 V to +1.25 V Yes
• -10 V to +10 V Yes Yes Yes
• -2.5 V to +2.5 V Yes Yes Yes
• -5 V to +5 V Yes Yes Yes
Input ranges (rated values), currents
• 0 to 20 mA Yes Yes Yes
• 4 mA to 20 mA Yes Yes Yes
Thermocouple (TC)
Temperature compensation
- parameterizable No
3
Ambient temperature during
operation
• permissible temperature range -20 °C to +60 °C horizontal mounting, -20 °C to +60 °C horizontal mounting, -20 °C to +60 °C horizontal mounting,
-20 °C to 50 °C vertical mounting, -20 °C to 50 °C vertical mounting, -20 °C to 50 °C vertical mounting,
95% humidity, non-condensing 95% humidity, non-condensing 95% humidity, non-condensing
• min. -20 °C -20 °C -20 °C
• max. 60 °C 60 °C 60 °C
Pollutant concentrations
- SO2 at RH < 60% without S02: < 0.5 ppm; H2S: < 0.1 ppm; S02: < 0.5 ppm; H2S: < 0.1 ppm; S02: < 0.5 ppm; H2S: < 0.1 ppm;
condensation RH < 60% condensation-free RH < 60% condensation-free RH < 60% condensation-free
Connection method
required front connector Yes Yes Yes
Mechanics/material
Enclosure material (front)
• Plastic Yes Yes Yes
Dimensions
Width 45 mm 45 mm 45 mm
Height 100 mm 100 mm 100 mm
Depth 75 mm 75 mm 75 mm
Weights
Weight, approx. 180 g 180 g 180 g
■ Overview
• Analog input module for the SIMATIC S7-1200
• With extremely short conversion times
• For the connection of analog sensors without additional
amplifiers
• For the solution of more complex automation tasks as well
3
• Can be plugged directly into the CPU
■ Technical specifications
Article number 6ES7231-4HA30-0XB0 Article number 6ES7231-4HA30-0XB0
SIGNAL BOARD SB 1231, 1 AI SIGNAL BOARD SB 1231, 1 AI
General information Analog value generation for the
Product type designation SB1231 AI 1x12 BIT inputs
Supply voltage Measurement principle integrating
Rated value (DC) Integration and conversion time/
resolution per channel
• 24 V DC Yes
• Resolution with overrange 11 bit; + sign
Input current (bit including sign), max.
from backplane bus 5 V DC, typ. 55 mA • Integration time, parameterizable Yes
Power loss • Interference voltage suppression for 40 dB, DC to 60 Hz
Power loss, typ. 0.4 W interference frequency f1 in Hz
Analog inputs Smoothing of measured values
Number of analog inputs 1; Current or voltage differential • parameterizable Yes
inputs • Step: None Yes
permissible input voltage for current ±35 V • Step: low Yes
input (destruction limit), max.
• Step: Medium Yes
permissible input voltage for voltage 35 V
input (destruction limit), max. • Step: High Yes
permissible input current for voltage 40 mA Errors/accuracies
input (destruction limit), max. Temperature error (relative to input 25 °C ±0.3%, to 55 °C ±0.6% total
permissible input current for current 40 mA range), (+/-) measurement range
input (destruction limit), max. Interrupts/diagnostics/
Cycle time (all channels) max. 156.25 µs; 400 Hz suppression status information
Input ranges Alarms Yes
• Voltage Yes; ±10V, ±5V, ±2.5V Diagnostic functions Yes
• Current Yes; 0 to 20 mA Alarms
• Thermocouple No • Diagnostic alarm Yes
• Resistance thermometer No Diagnostic messages
• Resistance No • Wire-break No
Input ranges (rated values), Diagnostics indication LED
voltages • for status of the inputs Yes
• -10 V to +10 V Yes • for maintenance Yes
• -2.5 V to +2.5 V Yes Degree and class of protection
• -5 V to +5 V Yes Degree of protection acc. to
Input ranges (rated values), currents EN 60529
• 0 to 20 mA Yes • IP20 Yes
Analog outputs Standards, approvals, certificates
Number of analog outputs 0 CE mark Yes
CSA approval Yes
FM approval Yes
RCM (formerly C-TICK) Yes
3
Ambient temperature during
operation For signal board
• permissible temperature range -20 °C to +60 °C horizontal With 6 screws, gold-plated; 4 pcs. 6ES7292-1BF30-0XA0
mounting, -20 °C to 50 °C vertical
mounting, 95% humidity,
non-condensing
• min. -20 °C
• max. 60 °C
Pollutant concentrations
- SO2 at RH < 60% without S02: < 0.5 ppm; H2S: < 0.1 ppm;
condensation RH < 60% condensation-free
Connection method
required front connector Yes
Mechanics/material
Enclosure material (front)
• Plastic Yes
Dimensions
Width 38 mm
Height 62 mm
Depth 21 mm
Weights
Weight, approx. 35 g
■ Overview
• Analog outputs for SIMATIC S7-1200
• With extremely short conversion times
• For connecting analog actuators without additional amplifiers
• For solving even more complex automation tasks
■ Technical specifications
Article number 6ES7232-4HB32-0XB0 6ES7232-4HD32-0XB0
ANALOG OUTPUT SM 1232, 2AO ANALOG OUTPUT SM 1232, 4AO
General information
Product type designation SM 1232 AQ 2x14 bit SM 1232 AQ 4 x 14bit
Supply voltage
Rated value (DC)
• 24 V DC Yes Yes
Input current
Current consumption, typ. 45 mA 45 mA
from backplane bus 5 V DC, typ. 80 mA 80 mA
Power loss
Power loss, typ. 1.5 W 1.5 W
Analog outputs
Number of analog outputs 2; Current or voltage 4; Current or voltage
Output ranges, voltage
• -10 V to +10 V Yes Yes
Output ranges, current
• 0 to 20 mA Yes Yes
Load impedance (in rated range of
output)
• with voltage outputs, min. 1 000 1 000
• with current outputs, max. 600 600
Analog value generation for the
outputs
Integration and conversion time/
resolution per channel
• Resolution (incl. overrange) Voltage: 14 bits; Current : 13 bits Voltage: 14 bits; Current : 13 bits
Errors/accuracies
Temperature error (relative to output 25 °C ±0.3%, to 55 °C ±0.6% total measurement range 25 °C ±0.3%, to 55 °C ±0.6% total measurement range
range), (+/-)
Basic error limit
(operational limit at 25 °C)
• Voltage, relative to output range, 0.3% 0.3%
(+/-)
• Current, relative to output range, 0.3% 0.3%
(+/-)
Interference voltage suppression for
f = n x (f1 +/- 1%), f1 = interference
frequency
• Common mode voltage, max. 12 V 12 V
■ Overview
• Analog output for the SIMATIC S7-1200
• Can be plugged direct into the CPU
■ Technical specifications
Article number 6ES7232-4HA30-0XB0 Article number 6ES7232-4HA30-0XB0
SIGNAL BOARD SB 1232, 1 AO SIGNAL BOARD SB 1232, 1 AO
General information Errors/accuracies
Product type designation SB 1232 1x AO Temperature error 25 °C ±0.5%, to 55 °C ±1%
Input current (relative to output range), (+/-)
from backplane bus 5 V DC, typ. 15 mA Interrupts/diagnostics/
status information
Output voltage
Alarms Yes
Power supply to the transmitters
Diagnostic functions Yes
• Supply current, max. 25 mA
Diagnostics indication LED
Power loss
• for status of the outputs Yes
Power loss, typ. 1.5 W
Degree and class of protection
Analog inputs
Degree of protection acc. to
Number of analog inputs 0 EN 60529
Analog outputs • IP20 Yes
Number of analog outputs 1 Standards, approvals, certificates
Cycle time (all channels) max. Voltage: 300 S (R), 750 S (1 uF) CE mark Yes
Current: 600 ms (1 mH);
2 ms (10 mH) CSA approval Yes
Output ranges, voltage FM approval Yes
• -10 V to +10 V Yes RCM (formerly C-TICK) Yes
Output ranges, current
• 0 to 20 mA Yes
Load impedance
(in rated range of output)
• with voltage outputs, min. 1 000
• with current outputs, max. 600
Cable length
• shielded, max. 10 m; shielded, twisted pair
3
Ambient temperature during
operation For signal board
• permissible temperature range 0 °C to 55 °C horizontal installation, With 6 screws, gold-plated; 4 pcs. 6ES7292-1BF30-0XA0
0 °C to 45 °C vertical installation
• min. 0 °C
• max. 55 °C
Pollutant concentrations
- SO2 at RH < 60% without S02: < 0.5 ppm; H2S: < 0.1 ppm;
condensation RH < 60% condensation-free
Mechanics/material
Enclosure material (front)
• Plastic Yes
Dimensions
Width 38 mm
Height 62 mm
Depth 21 mm
Weights
Weight, approx. 40 g
■ Overview
• Analog inputs and outputs for the SIMATIC S7-1200
• With extremely short conversion times
• For connecting analog actuators and sensors without
additional amplifiers
• For solving even more complex automation tasks
■ Technical specifications
Article number 6ES7234-4HE32-0XB0 Article number 6ES7234-4HE32-0XB0
ANALOG I/O SM 1234, 4AI/2AO ANALOG I/O SM 1234, 4AI/2AO
General information Analog outputs
Product type designation SM 1234 A I4x13 bit AQ 2x14 bit Number of analog outputs 2; Current or voltage
Supply voltage Output ranges, voltage
Rated value (DC) • -10 V to +10 V Yes
• 24 V DC Yes Output ranges, current
Input current • 0 to 20 mA Yes
Current consumption, typ. 60 mA • 4 mA to 20 mA Yes
from backplane bus 5 V DC, typ. 80 mA Load impedance
Power loss (in rated range of output)
Power loss, typ. 2W • with voltage outputs, min. 1 000
Analog inputs • with current outputs, max. 600
Number of analog inputs 4; Current or voltage differential Analog value generation for the
inputs inputs
permissible input voltage for current ±35 V Measurement principle Differential
input (destruction limit), max. Integration and conversion time/
permissible input voltage for voltage 35 V resolution per channel
input (destruction limit), max. • Resolution with overrange 12 bit; + sign
permissible input current for voltage 40 mA (bit including sign), max.
input (destruction limit), max. • Integration time, parameterizable Yes
permissible input current for current 40 mA • Interference voltage suppression for 40 dB, DC to 60 V for interference
input (destruction limit), max. interference frequency f1 in Hz frequency 50 / 60 Hz
Cycle time (all channels) max. 625 µs Smoothing of measured values
Input ranges • parameterizable Yes
• Voltage Yes; ±10V, ±5V, ±2.5V • Step: None Yes
• Current Yes; 4 to 20 mA, 0 to 20 mA • Step: low Yes
Input ranges (rated values), • Step: Medium Yes
voltages • Step: High Yes
• -10 V to +10 V Yes Analog value generation for the
• -2.5 V to +2.5 V Yes outputs
• -5 V to +5 V Yes Integration and conversion time/
Input ranges (rated values), currents resolution per channel
• 0 to 20 mA Yes • Resolution (incl. overrange) Voltage: 14 bits; Current : 13 bits
• 4 mA to 20 mA Yes
3
FM approval Yes
range), (+/-) measurement range
RCM (formerly C-TICK) Yes
Basic error limit (operational limit at
25 °C) Marine approval
• Voltage, relative to input range, (+/-) 0.1% • Marine approval Yes
• Current, relative to input range, (+/-) 0.1% Ambient conditions
• Voltage, relative to output range, (+/-) 0.3% Free fall
• Current, relative to output range, (+/-) 0.3% • Fall height, max. 0.3 m; five times, in product package
Interference voltage suppression for Ambient temperature during
f = n x (f1 +/- 1%), f1 = interference operation
frequency • permissible temperature range -20 °C to +60 °C horizontal
• Common mode voltage, max. 12 V mounting, -20 °C to 50 °C vertical
mounting, 95% humidity, non-
Interrupts/diagnostics/ condensing
status information
• min. -20 °C
Alarms Yes
• max. 60 °C
Diagnostic functions Yes
Pollutant concentrations
Alarms
- SO2 at RH < 60% without conden- S02: < 0.5 ppm; H2S: < 0.1 ppm; RH
• Diagnostic alarm Yes sation < 60% condensation-free
Diagnostic messages Connection method
• Monitoring the supply voltage Yes required front connector Yes
• Wire-break Yes Mechanics/material
• Short-circuit Yes Enclosure material (front)
Diagnostics indication LED • Plastic Yes
• for status of the inputs Yes Dimensions
• for status of the outputs Yes Width 45 mm
• for maintenance Yes Height 100 mm
Potential separation analog outputs Depth 75 mm
• between the channels and the No Weights
power supply of the electronics
Weight, approx. 220 g
Degree and class of protection
Degree of protection acc. to
EN 60529
• IP20 Yes
■ Overview
• For the convenient recording of temperatures with great
accuracy
• 7 common thermocouple types can be used
• Also for the measurement of analog signals with a low level
(±80 mV)
• Can easily be retrofitted to existing plant
3
■ Technical specifications
Article number 6ES7231-5QD32-0XB0 6ES7231-5QF32-0XB0
S7-1200, ANALOG INPUT SM 1231 TC, 4 AI S7-1200, ANALOG INPUT SM 1231 TC, 8 AI
General information
Product type designation SM 1231 TC 4x16 bit SM 1231 TC 8x16bit
Supply voltage
Rated value (DC)
• 24 V DC Yes Yes
Input current
Current consumption, typ. 40 mA 40 mA
from backplane bus 5 V DC, typ. 80 mA 80 mA
Power loss
Power loss, typ. 1.5 W 1.5 W
Analog inputs
Number of analog inputs 4; Thermocouples 8; Thermocouples
permissible input voltage for current ±35 V ±35 V
input (destruction limit), max.
permissible input voltage for voltage +-35 V +-35 V
input (destruction limit), max.
Technical unit for temperature Degrees Celsius/degrees Fahrenheit Degrees Celsius/degrees Fahrenheit
measurement adjustable
Input ranges
• Voltage Yes Yes
• Current No No
• Thermocouple Yes; J, K, T, E, R, S, N, C, TXK/XK(L); Yes; J, K, T, E, R & S, B, N, C, TXK/XK(L);
voltage range: +/-80 mV voltage range: ±80 mV
• Resistance thermometer No No
• Resistance No No
Input ranges (rated values),
voltages
• -80 mV to +80 mV Yes Yes
Input ranges (rated values),
thermocouples
• Type B Yes Yes
• Type C Yes Yes
• Type E Yes Yes
• Type J Yes Yes
• Type K Yes Yes
• Type N Yes Yes
• Type R Yes Yes
• Type S Yes Yes
• Type T Yes Yes
• Type TXK/TXK(L) to GOST Yes Yes
Thermocouple (TC)
Temperature compensation
- parameterizable No No
3
Enclosure material (front)
• Plastic Yes Yes
Dimensions
Width 45 mm 45 mm
Height 100 mm 100 mm
Depth 75 mm 75 mm
Weights
Weight, approx. 180 g 220 g
■ Overview
• For the convenient recording of temperatures with great
accuracy
• 1 input with 16-bit resolution
• Common thermocouple types can be used
• Also for the measurement of analog signals with a low level
(±80 mV)
3 • Can easily be retrofitted to existing plant
• Can be plugged directly into the CPU
■ Technical specifications
Article number 6ES7231-5QA30-0XB0 Article number 6ES7231-5QA30-0XB0
SIGNAL BOARD SB 1231 TC, 1 AI SIGNAL BOARD SB 1231 TC, 1 AI
General information Analog value generation for the
Product type designation SB1231 AI 1xTC inputs
Supply voltage Measurement principle integrating
Rated value (DC) Integration and conversion time/
resolution per channel
• 24 V DC Yes
• Resolution with overrange 15 bit; + sign
Input current (bit including sign), max.
Current consumption, typ. 5 mA • Integration time, parameterizable No
from backplane bus 5 V DC, typ. 20 mA • Interference voltage suppression for 85 dB at 10 / 50 / 60 / 400 Hz
Power loss interference frequency f1 in Hz
Power loss, typ. 0.5 W Smoothing of measured values
Analog inputs • parameterizable Yes
Number of analog inputs 1; Thermocouples Errors/accuracies
permissible input voltage for current ±35 V Temperature error (relative to input 25 °C ±0.1%, to 55 °C ±0.2% total
input (destruction limit), max. range), (+/-) measurement range
permissible input voltage for voltage +-35 V Repeat accuracy in steady state at 0.5%
input (destruction limit), max. 25 °C (relative to output range), (+/-)
Technical unit for temperature Degrees Celsius/degrees Fahrenheit Interference voltage suppression for
measurement adjustable f = n x (f1 +/- 1%), f1 = interference
frequency
Input ranges
• Common mode interference, min. 120 dB
• Voltage Yes
Interrupts/diagnostics/
• Current No status information
• Thermocouple Yes; J, K; voltage range ±80 mV Alarms Yes
• Resistance thermometer No Diagnostic functions Yes; Can be read out
• Resistance No Alarms
Input ranges (rated values), • Diagnostic alarm Yes
voltages
Diagnostic messages
• -80 mV to +80 mV Yes
• Wire-break Yes
Input ranges (rated values),
thermocouples Diagnostics indication LED
• Type J Yes • for status of the inputs Yes
• Type K Yes • for maintenance Yes
Thermocouple (TC) Degree and class of protection
Temperature compensation Degree of protection acc. to
EN 60529
- parameterizable No
• IP20 Yes
Analog outputs
Standards, approvals, certificates
Number of analog outputs 0
CE mark Yes
CSA approval Yes
FM approval Yes
RCM (formerly C-TICK) Yes
3
Ambient temperature during Terminal block (spare part)
operation
For signal board
• permissible temperature range -20 °C to +60 °C horizontal
mounting, -20 °C to 50 °C vertical With 6 screws, gold-plated; 4 pcs. 6ES7292-1BF30-0XA0
mounting, 95% humidity,
non-condensing
• min. -20 °C
• max. 60 °C
Pollutant concentrations
- SO2 at RH < 60% without S02: < 0.5 ppm; H2S: < 0.1 ppm;
condensation RH < 60% condensation-free
Connection method
required front connector Yes
Mechanics/material
Enclosure material (front)
• Plastic Yes
Dimensions
Width 38 mm
Height 62 mm
Depth 21 mm
Weights
Weight, approx. 35 g
■ Overview
• For the convenient recording of temperatures with great
accuracy
• 4 inputs
• Most popular resistance temperature detectors can be used
• Can easily be retrofitted to existing installation
3 ■ Technical specifications
Article number 6ES7231-5PD32-0XB0 6ES7231-5PF32-0XB0
S7-1200, ANALOG INPUT SM 1231 RTD, 4 AI S7-1200, ANALOG INPUT SM 1231 RTD, 8 AI
General information
Product type designation SM 1231 RTD 4x16bit SM 1231 RTD 8x16bit
Supply voltage
Rated value (DC)
• 24 V DC Yes Yes
Input current
Current consumption, typ. 40 mA 40 mA
from backplane bus 5 V DC, typ. 80 mA 80 mA
Power loss
Power loss, typ. 1.5 W 1.5 W
Analog inputs
Number of analog inputs 4; Resistance thermometer 8; Resistance thermometer
permissible input voltage for current ±35 V ±35 V
input (destruction limit), max.
Technical unit for temperature Degrees Celsius/degrees Fahrenheit Degrees Celsius/degrees Fahrenheit
measurement adjustable
Input ranges
• Voltage No No
• Current No No
• Thermocouple No No
• Resistance thermometer Yes; Resistance-type transmitter: Pt10, Pt50, Pt100, Pt200, Yes; Resistance-type transmitter: Pt10, Pt50, Pt100, Pt200,
Pt500, Pt1000, Ni100, Ni120, Ni200, Ni500, Ni1000, Cu10, Pt500, Pt1000, Ni100, Ni120, Ni200, Ni500, Ni1000, Cu10,
Cu50, Cu100, LG-Ni1000 Cu50, Cu100, LG-Ni1000
• Resistance Yes; 150 , 300 , 600 Yes; 150 , 300 , 600
Input ranges (rated values),
resistance thermometer
• Cu 10 Yes Yes
• Ni 100 Yes Yes
• Ni 1000 Yes Yes
• LG-Ni 1000 Yes Yes
• Ni 120 Yes Yes
• Ni 200 Yes Yes
• Ni 500 Yes Yes
• Pt 100 Yes Yes
• Pt 1000 Yes Yes
• Pt 200 Yes Yes
• Pt 500 Yes Yes
Input ranges (rated values),
resistors
• 0 to 150 ohms Yes Yes
• 0 to 300 ohms Yes Yes
• 0 to 600 ohms Yes Yes
Thermocouple (TC)
Temperature compensation
- parameterizable No No
■ Overview
• For the convenient recording of temperatures with great
accuracy
• 1 input with 16-bit resolution
• Common resistance-type temperature detectors can be used
• Can easily be retrofitted to existing plant
3
• Can be plugged directly into the CPU
■ Technical specifications
Article number 6ES7231-5PA30-0XB0 Article number 6ES7231-5PA30-0XB0
SIGNAL BOARD SB 1231 RTD SIGNAL BOARD SB 1231 RTD
General information Analog value generation for the
Product type designation SB1231 AI 1xRTD inputs
Supply voltage Measurement principle integrating
Rated value (DC) Integration and conversion time/
resolution per channel
• 24 V DC Yes
• Resolution with overrange 15 bit; + sign
Input current (bit including sign), max.
Current consumption, typ. 5 mA • Integration time, parameterizable No
from backplane bus 5 V DC, typ. 20 mA • Interference voltage suppression for 85 dB at 10 / 50 / 60 / 400 Hz
Power loss interference frequency f1 in Hz
Power loss, typ. 0.5 W Errors/accuracies
Analog inputs Temperature error (relative to input 25 °C ±0.1%, to 55 °C ±0.2% total
range), (+/-) measurement range
Number of analog inputs 1; Resistance thermometer
Repeat accuracy in steady state at 0.05%
permissible input voltage for current ±35 V 25 °C (relative to output range), (+/-)
input (destruction limit), max.
Interference voltage suppression for
Technical unit for temperature Degrees Celsius/degrees Fahrenheit f = n x (f1 +/- 1%), f1 = interference
measurement adjustable frequency
Input ranges • Common mode interference, min. 120 dB
• Voltage Yes Interrupts/diagnostics/
• Current No status information
• Thermocouple No Alarms Yes
• Resistance thermometer Yes; Platinum (Pt) Diagnostic functions Yes; Can be read out
• Resistance Yes; 150 , 300 , 600 Alarms
Input ranges (rated values), • Diagnostic alarm Yes
resistance thermometer Diagnostic messages
• Pt 100 Yes • Wire-break Yes
• Pt 1000 Yes Diagnostics indication LED
• Pt 200 Yes • for status of the inputs Yes
• Pt 500 Yes • for maintenance Yes
Input ranges (rated values), Degree and class of protection
resistors
Degree of protection acc. to
• 0 to 150 ohms Yes EN 60529
• 0 to 300 ohms Yes • IP20 Yes
• 0 to 600 ohms Yes Standards, approvals, certificates
Thermocouple (TC) CE mark Yes
Temperature compensation CSA approval Yes
- parameterizable No FM approval Yes
Analog outputs RCM (formerly C-TICK) Yes
Number of analog outputs 0
3
Ambient temperature during Terminal block (spare part)
operation
For signal board
• permissible temperature range -20 °C to +60 °C horizontal
mounting, -20 °C to 50 °C vertical With 6 screws, gold-plated; 4 pcs. 6ES7292-1BF30-0XA0
mounting, 95% humidity,
non-condensing
• min. -20 °C
• max. 60 °C
Pollutant concentrations
- SO2 at RH < 60% without S02: < 0.5 ppm; H2S: < 0.1 ppm;
condensation RH < 60% condensation-free
Connection method
required front connector Yes
Mechanics/material
Enclosure material (front)
• Plastic Yes
Dimensions
Width 38 mm
Height 62 mm
Depth 21 mm
Weights
Weight, approx. 35 g
■ Overview
• Energy management based on SIMATIC S7-1200
• Data acquisition of electrical characteristics in 1 and 3-phase
networks up to 480 V AC
• Direct connection of voltage inputs
• Current measurement performed by 1 A and 5 A current
transformers
• Can be used in TN and TT networks 3
• Data backup of measurement data in the event of a power
failure
■ Technical specifications
Article number 6ES7238-5XA32-0XB0 Article number 6ES7238-5XA32-0XB0
SM 1238 Energy Meter 480V AC SM 1238 Energy Meter 480V AC
General information Power loss
Product type designation SM 1238 AI Energy Meter 480 VAC Power loss, typ. 0.6 W
Product function Address area
• Voltage measurement Yes Address space per module
• Voltage measurement with voltage Yes • Address space per module, max. 124 byte; 112 byte input / 12 byte
transformers output
• Current measurement Yes Analog inputs
• Phase current measurement without No Cycle time (all channels), typ. 50 ms; Time for consistent update of
current transformers all measured and calculated values
• Phase current measurement with Yes (cyclic und acyclic data)
current transformers Interrupts/diagnostics/
• Energy measurement Yes status information
• Frequency measurement Yes Alarms
• Power measurement Yes • Diagnostic alarm Yes
• Active power measurement Yes • Limit value alarm Yes
• Reactive power measurement Yes • Hardware interrupt No
• I&M data Yes; I&M 0 Diagnostics indication LED
• Isochronous mode No • Monitoring of the supply voltage Yes
(PWR-LED)
Engineering with
• Channel status display Yes; Green LED
• STEP 7 TIA Portal configurable/ V13 SP1
integrated as of version • for channel diagnostics Yes; red Fn LED
Operating mode • for module diagnostics Yes; green/red DIAG LED
• cyclic measurement Yes Integrated Functions
• acyclic measurement Yes Measuring functions
• Acyclic measured value access Yes • Measuring procedure for voltage TRMS
measurement
• Fixed measured value sets Yes
• Measuring procedure for current TRMS
• Freely definable measured value Yes measurement
sets
• Type of measured value acquisition seamless
CiR – Configuration in RUN
• Curve shape of voltage Sinusoidal or distorted
Reparameterization possible in RUN Yes
• Buffering of measured variables Yes
Calibration possible in RUN Yes
• Parameter length 74 byte
Installation type/mounting
• Bandwidth of measured value 2 kHz;
Mounting position Horizontal, vertical acquisition Harmonics: 39 / 50 Hz, 32 / 60 Hz
Supply voltage Operating mode for measured value
Design of the power supply Supply via voltage measurement acquisition
channel L1 - automatic detection of line No; Parameterizable
Type of supply voltage AC 100 - 277 V frequency
permissible range, lower limit (AC) 90 V Measuring range
permissible range, upper limit (AC) 293 V - Frequency measurement, min. 45 Hz
Line frequency - Frequency measurement, max. 65 Hz
• permissible range, lower limit 47 Hz
• permissible range, upper limit 63 Hz
phase and neutral conductor, min. - Measured variable active power 0.5
- Measurable line voltage between 293 V - Measured variable reactive power 1
phase and neutral conductor,
max. - Measured variable power factor 0.5
- Measurable line voltage between 155 V - Measured variable active energy 0.5
the line conductors, min. - Measured variable reactive energy 1
- Measurable line voltage between 508 V - Measured variable neutral current 0.5; calculated
the line conductors, max.
- Measured variable phase angle ±1 °; not covered by IEC 61557-12
- Measurement category for voltage CAT II; CAT III in case of guaranteed
measurement in accordance with protection level of 1.5 kV - Measured variable frequency 0.05
IEC 61010-2-030 Potential separation
- Internal resistance line conductor 3.4 M Potential separation channels
and neutral conductor
• between the channels and Yes; 3 700V AC (type test) CAT III
- Power consumption per phase 20 mW backplane bus
- Impulse voltage resistance 1 kV Isolation
1,2/50µs
Isolation tested with 2 300V AC for 1 min. (type test)
Measuring inputs for current
Ambient conditions
- measurable relative current (AC), 1%; Relative to the secondary rated
Ambient temperature during
min. current 5 A
operation
- measurable relative current (AC), 100%; Relative to the secondary
• horizontal installation, min. -20 °C
max. rated current 5 A
• horizontal installation, max. 60 °C
- Continuous current with AC, 5A
maximum permissible • vertical installation, min. -20 °C
- Apparent power consumption per 0.6 V·A • vertical installation, max. 50 °C
phase for measuring range 5 A Dimensions
- Rated value short-time withstand 100 A Width 45 mm
current restricted to 1 s
Height 100 mm
- Input resistance measuring range 25 m; At the terminal
0 to 5 A Depth 75 mm
- Zero point suppression Parameterizable: 2 - 250 mA, Weights
default 50 mA Weight (without packaging) 165 g
- Surge strength 10 A; for 1 minute Data for selecting a current
transformer
• Burden power current transformer As a function of cable length and
x/1A, min. cross section, see device manual
• Burden power current transformer As a function of cable length and
x/5A, min. cross section, see device manual
■ Overview
• Analog inputs for SIPLUS S7-1200
• With extremely short conversion times
• For connecting analog actuators and sensors without
additional amplifiers
• Even solves more complex automation tasks
• From +60 °C to +70 °C, max. 50% of the inputs can be
controlled simultaneously 3
Note:
SIPLUS extreme products are based on SIMATIC standard
products. The contents listed here were taken from the respec-
tive standard products. SIPLUS extreme-specific information
was added.
■ Technical specifications
Article number 6AG1231-4HD32-4XB0 Article number 6AG1231-4HD32-4XB0
Based on 6ES7231-4HD32-0XB0 Based on 6ES7231-4HD32-0XB0
SIPLUS S7-1200 SM 1231 4AI 13Bit SIPLUS S7-1200 SM 1231 4AI 13Bit
Ambient conditions Relative humidity
Free fall - With condensation, tested in 100%; RH incl. condensation/frost
• Fall height, max. 0.3 m; five times, in product package accordance with IEC 60068-2-38, (no commissioning under conden-
max. sation conditions)
Ambient temperature during
operation Resistance
• min. -20 °C; = Tmin; Startup @ 0 °C - against biologically active Yes; Class 3B2 mold, fungus and dry
substances / conformity with rot spores (with the exception of
• max. 60 °C; = Tmax EN 60721-3-3 fauna). The supplied connector
Extended ambient conditions covers must remain on the unused
interfaces during operation!
• relative to ambient temperature- Tmin ... Tmax at
atmospheric pressure-installation 1080 hPa ... 795 hPa - against chemically active Yes; Class 3C4 (RH < 75%) incl. salt
altitude (-1000 m ... +2000 m) // substances / conformity with spray according to EN 60068-2-52
Tmin ... (Tmax - 10K) at EN 60721-3-3 (degree of severity 3). The supplied
795 hPa ... 658 hPa connector covers must remain on the
(+2000 m ... +3500 m) // unused interfaces during operation!
Tmin ... (Tmax - 20K) at - against mechanically active Yes; Class 3S4 incl. sand, dust. The
658 hPa ... 540 hPa substances / conformity with supplied connector covers must
(+3500 m ... +5000 m) EN 60721-3-3 remain on the unused interfaces
during operation!
■ Overview
• Analog outputs for SIPLUS S7-1200
• With extremely short conversion times
• For connecting analog actuators without additional amplifiers
• Even solves more complex automation tasks
• From +60 °C to +70 °C, max. 50% of the outputs can be
3 controlled simultaneously
Note:
SIPLUS extreme products are based on SIMATIC standard
products. The contents listed here were taken from the respec-
tive standard products. SIPLUS extreme-specific information
was added.
■ Technical specifications
Article number 6AG1232-4HB32-4XB0 Article number 6AG1232-4HB32-4XB0
Based on 6ES7232-4HB32-0XB0 Based on 6ES7232-4HB32-0XB0
SIPLUS S7-1200 SM 1232 2AQ 13Bit SIPLUS S7-1200 SM 1232 2AQ 13Bit
Ambient conditions Relative humidity
Free fall - With condensation, tested in 100%; RH incl. condensation/frost
• Fall height, max. 0.3 m; five times, in product package accordance with IEC 60068-2-38, (no commissioning under conden-
max. sation conditions)
Ambient temperature during
operation Resistance
• min. -20 °C; = Tmin; Startup @ 0 °C - against biologically active Yes; Class 3B2 mold, fungus and dry
substances / conformity with rot spores (with the exception of
• max. 60 °C; = Tmax EN 60721-3-3 fauna). The supplied connector
Extended ambient conditions covers must remain on the unused
interfaces during operation!
• relative to ambient temperature- Tmin ... Tmax at
atmospheric pressure-installation 1080 hPa ... 795 hPa - against chemically active Yes; Class 3C4 (RH < 75%) incl. salt
altitude (-1000 m ... +2000 m) // substances / conformity with spray according to EN 60068-2-52
Tmin ... (Tmax - 10K) at EN 60721-3-3 (degree of severity 3). The supplied
795 hPa ... 658 hPa connector covers must remain on the
(+2000 m ... +3500 m) // unused interfaces during operation!
Tmin ... (Tmax - 20K) at - against mechanically active Yes; Class 3S4 incl. sand, dust. The
658 hPa ... 540 hPa substances / conformity with supplied connector covers must
(+3500 m ... +5000 m) EN 60721-3-3 remain on the unused interfaces
during operation!
■ Overview
• Analog output for SIPLUS S7-1200
• Can be plugged directly into the CPU
(cannot be used for +70 °C version)
Note:
SIPLUS extreme products are based on SIMATIC standard
products. The contents listed here were taken from the respec-
tive standard products. SIPLUS extreme-specific information 3
was added.
■ Technical specifications
Article number 6AG1232-4HA30-4XB0 6AG1232-4HA30-5XB0
Based on 6ES7232-4HA30-0XB0 6ES7232-4HA30-0XB0
SIPLUS S7-1200 SB 1232 1AQ SIPLUS S7-1200 SB 1232 1AQ
Ambient conditions
Free fall
• Fall height, max. 0.3 m; five times, in product package 0.3 m; five times, in product package
Ambient temperature during
operation
• min. 0 °C; = Tmin -40 °C; = Tmin; Startup @ -25 °C
• max. 55 °C; = Tmax 55 °C; = Tmax
Extended ambient conditions
• relative to ambient temperature- Tmin ... Tmax at 1080 hPa ... 795 hPa Tmin ... Tmax at 1080 hPa ... 795 hPa
atmospheric pressure-installation (-1000 m ... +2000 m) // (-1000 m ... +2000 m) //
altitude Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa
(+2000 m ... +3500 m) // (+2000 m ... +3500 m) //
Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa
(+3500 m ... +5000 m) (+3500 m ... +5000 m)
Relative humidity
- With condensation, tested in 100%; RH incl. condensation/frost (no commissioning 100%; RH incl. condensation/frost (no commissioning
accordance with IEC 60068-2-38, under condensation conditions) under condensation conditions)
max.
Resistance
- against biologically active Yes; Class 3B2 mold, fungus and dry rot spores (with the Yes; Class 3B2 mold, fungus and dry rot spores (with the
substances / conformity with exception of fauna). The supplied connector covers must exception of fauna). The supplied connector covers must
EN 60721-3-3 remain on the unused interfaces during operation! remain on the unused interfaces during operation!
- against chemically active Yes; Class 3C4 (RH < 75%) incl. salt spray according to Yes; Class 3C4 (RH < 75%) incl. salt spray according to
substances / conformity with EN 60068-2-52 (degree of severity 3). The supplied EN 60068-2-52 (degree of severity 3). The supplied
EN 60721-3-3 connector covers must remain on the unused interfaces connector covers must remain on the unused interfaces
during operation! during operation!
- against mechanically active Yes; Class 3S4 incl. sand, dust. The supplied connector Yes; Class 3S4 incl. sand, dust. The supplied connector
substances / conformity with covers must remain on the unused interfaces during covers must remain on the unused interfaces during
EN 60721-3-3 operation! operation!
■ Overview
• Analog inputs and outputs for SIPLUS S7-1200
• With extremely short conversion times
• For connecting analog actuators and sensors without
additional amplifiers
• Even solves more complex automation tasks
• From +60 °C to +70 °C, max. 50% of the inputs and outputs
can be controlled simultaneously 3
Note:
SIPLUS extreme products are based on SIMATIC standard
products. The contents listed here were taken from the respec-
tive standard products. SIPLUS extreme-specific information
was added.
■ Technical specifications
Article number 6AG1234-4HE32-2XB0 6AG1234-4HE32-4XB0
Based on 6ES7234-4HE32-0XB0 6ES7234-4HE32-0XB0
SIPLUS S7-1200 SM 1234 4AI/2AQ 13Bit SIPLUS S7-1200 SM 1234 4AI/2AQ 13Bit
Ambient conditions
Free fall
• Fall height, max. 0.3 m; five times, in product package 0.3 m; five times, in product package
Ambient temperature during
operation
• min. -40 °C; = Tmin; Startup @ -25 °C -20 °C; = Tmin; Startup @ 0 °C
• max. 70 °C; = Tmax; Tmax > +60 °C number of simultaneously 60 °C; = Tmax
used outputs 1, inputs 2 (no adjacent points) for horizontal
mounting position
Extended ambient conditions
• relative to ambient temperature- Tmin ... Tmax at 1080 hPa ... 795 hPa Tmin ... Tmax at 1080 hPa ... 795 hPa
atmospheric pressure-installation (-1000 m ... +2000 m) // (-1000 m ... +2000 m) //
altitude Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa
(+2000 m ... +3500 m) // (+2000 m ... +3500 m) //
Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa
(+3500 m ... +5000 m) (+3500 m ... +5000 m)
Relative humidity
- With condensation, tested in 100%; RH incl. condensation/frost (no commissioning 100%; RH incl. condensation/frost (no commissioning
accordance with IEC 60068-2-38, under condensation conditions) under condensation conditions)
max.
Resistance
- against biologically active Yes; Class 3B2 mold, fungus and dry rot spores (with the Yes; Class 3B2 mold, fungus and dry rot spores (with the
substances / conformity with exception of fauna). The supplied connector covers must exception of fauna). The supplied connector covers must
EN 60721-3-3 remain on the unused interfaces during operation! remain on the unused interfaces during operation!
- against chemically active Yes; Class 3C4 (RH < 75%) incl. salt spray according to Yes; Class 3C4 (RH < 75%) incl. salt spray according to
substances / conformity with EN 60068-2-52 (degree of severity 3). The supplied EN 60068-2-52 (degree of severity 3). The supplied
EN 60721-3-3 connector covers must remain on the unused interfaces connector covers must remain on the unused interfaces
during operation! during operation!
- against mechanically active Yes; Class 3S4 incl. sand, dust. The supplied connector Yes; Class 3S4 incl. sand, dust. The supplied connector
substances / conformity with covers must remain on the unused interfaces during covers must remain on the unused interfaces during
EN 60721-3-3 operation! operation!
■ Overview
• For the convenient recording of temperatures with great Note:
accuracy
SIPLUS extreme products are based on SIMATIC standard
• 7 common thermocouple types can be used products. The contents listed here were taken from the respec-
• Also for the measurement of analog signals with a low level tive standard products. SIPLUS extreme specific information
(±80 mV) was added.
• Can easily be retrofitted to existing plant
3
■ Technical specifications
Article number 6AG1231-5QF32-4XB0 6AG1231-5QD32-4XB0
Based on 6ES7231-5QF32-0XB0 6ES7231-5QD32-0XB0
SIPLUS S7-1200 SM 1231 8AI TC 16Bit SIPLUS S7-1200 SM 1231 4AI TC 16Bit
Ambient conditions
Free fall
• Fall height, max. 0.3 m; five times, in product package 0.3 m; five times, in product package
Ambient temperature during
operation
• min. -20 °C; = Tmin; Startup @ 0 °C -20 °C; = Tmin; Startup @ 0 °C
• max. 60 °C; = Tmax 60 °C; = Tmax
Extended ambient conditions
• relative to ambient temperature- Tmin ... Tmax at 1080 hPa ... 795 hPa Tmin ... Tmax at 1080 hPa ... 795 hPa
atmospheric pressure-installation (-1000 m ... +2000 m) // (-1000 m ... +2000 m) //
altitude Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa
(+2000 m ... +3500 m) // (+2000 m ... +3500 m) //
Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa
(+3500 m ... +5000 m) (+3500 m ... +5000 m)
Relative humidity
- With condensation, tested in 100%; RH incl. condensation/frost (no commissioning 100%; RH incl. condensation/frost (no commissioning
accordance with IEC 60068-2-38, under condensation conditions) under condensation conditions)
max.
Resistance
- against biologically active Yes; Class 3B2 mold, fungus and dry rot spores (with the Yes; Class 3B2 mold, fungus and dry rot spores (with the
substances / conformity with exception of fauna). The supplied connector covers must exception of fauna). The supplied connector covers must
EN 60721-3-3 remain on the unused interfaces during operation! remain on the unused interfaces during operation!
- against chemically active Yes; Class 3C4 (RH < 75%) incl. salt spray according to Yes; Class 3C4 (RH < 75%) incl. salt spray according to
substances / conformity with EN 60068-2-52 (degree of severity 3). The supplied EN 60068-2-52 (degree of severity 3). The supplied
EN 60721-3-3 connector covers must remain on the unused interfaces connector covers must remain on the unused interfaces
during operation! during operation!
- against mechanically active Yes; Class 3S4 incl. sand, dust. The supplied connector Yes; Class 3S4 incl. sand, dust. The supplied connector
substances / conformity with covers must remain on the unused interfaces during covers must remain on the unused interfaces during
EN 60721-3-3 operation! operation!
■ Overview
• For the convenient recording of temperatures with great Note:
accuracy
SIPLUS extreme products are based on SIMATIC standard
• 4 inputs products. The contents listed here were taken from the respec-
• Most popular resistance temperature detectors can be used tive standard products. SIPLUS extreme specific information
• Can easily be retrofitted to existing plant was added.
3 ■ Technical specifications
Article number 6AG1231-5PD32-4XB0 6AG1231-5PD32-2XB0 6AG1231-5PF32-4XB0 6AG1231-5PF32-2XB0
Based on 6ES7231-5PD32-0XB0 6ES7231-5PD32-0XB0 6ES7231-5PF32-0XB0 6ES7231-5PF32-0XB0
SIPLUS S7-1200 SM 1231 SIPLUS S7-1200 SM 1231 SIPLUS S7-1200 SM 1231 SIPLUS S7-1200 SM 1231
4AI RTD 16Bit 4AI RTD 16Bit 8AI RTD 16Bit 8AI RTD 16Bit
Ambient conditions
Free fall
• Fall height, max. 0.3 m; five times, in product 0.3 m; five times, in product 0.3 m; five times, in product 0.3 m; five times, in product
package package package package
Ambient temperature during
operation
• min. -20 °C; = Tmin; -40 °C; = Tmin; -20 °C; = Tmin; -40 °C; = Tmin;
Startup @ 0 °C Startup @ -25 °C Startup @ 0 °C Startup @ -25 °C
• max. 60 °C; = Tmax 70 °C; = Tmax 60 °C; = Tmax 70 °C; = Tmax
Extended ambient conditions
• relative to ambient temperature- Tmin ... Tmax at Tmin ... Tmax at Tmin ... Tmax at Tmin ... Tmax at
atmospheric pressure-installation 1080 hPa ... 795 hPa 1080 hPa ... 795 hPa 1080 hPa ... 795 hPa 1080 hPa ... 795 hPa
altitude (-1000 m ... +2000 m) // (-1000 m ... +2000 m) // (-1000 m ... +2000 m) // (-1000 m ... +2000 m) //
Tmin ... (Tmax - 10K) at Tmin ... (Tmax - 10K) at Tmin ... (Tmax - 10K) at Tmin ... (Tmax - 10K) at
795 hPa ... 658 hPa 795 hPa ... 658 hPa 795 hPa ... 658 hPa 795 hPa ... 658 hPa
(+2000 m ... +3500 m) // (+2000 m ... +3500 m) // (+2000 m ... +3500 m) // (+2000 m ... +3500 m) //
Tmin ... (Tmax - 20K) at Tmin ... (Tmax - 20K) at Tmin ... (Tmax - 20K) at Tmin ... (Tmax - 20K) at
658 hPa ... 540 hPa 658 hPa ... 540 hPa 658 hPa ... 540 hPa 658 hPa ... 540 hPa
(+3500 m ... +5000 m) (+3500 m ... +5000 m) (+3500 m ... +5000 m) (+3500 m ... +5000 m)
Relative humidity
- With condensation, tested in 100%; RH incl. conden- 100%; RH incl. conden- 100%; RH incl. conden- 100%; RH incl. conden-
accordance with IEC 60068-2-38, sation/frost (no commis- sation/frost (no commis- sation/frost (no commis- sation/frost (no commis-
max. sioning under condensation sioning under condensation sioning under condensation sioning under condensation
conditions) conditions) conditions) conditions)
Resistance
- against biologically active Yes; Class 3B2 mold, fungus Yes; Class 3B2 mold, fungus Yes; Class 3B2 mold, fungus Yes; Class 3B2 mold, fungus
substances / conformity with and dry rot spores (with the and dry rot spores (with the and dry rot spores (with the and dry rot spores (with the
EN 60721-3-3 exception of fauna). The exception of fauna). The exception of fauna). The exception of fauna). The
supplied connector covers supplied connector covers supplied connector covers supplied connector covers
must remain on the unused must remain on the unused must remain on the unused must remain on the unused
interfaces during operation! interfaces during operation! interfaces during operation! interfaces during operation!
- against chemically active Yes; Class 3C4 (RH < 75%) Yes; Class 3C4 (RH < 75%) Yes; Class 3C4 (RH < 75%) Yes; Class 3C4 (RH < 75%)
substances / conformity with incl. salt spray according to incl. salt spray according to incl. salt spray according to incl. salt spray according to
EN 60721-3-3 EN 60068-2-52 (degree of EN 60068-2-52 (degree of EN 60068-2-52 (degree of EN 60068-2-52 (degree of
severity 3). The supplied severity 3). The supplied severity 3). The supplied severity 3). The supplied
connector covers must connector covers must connector covers must connector covers must
remain on the unused inter- remain on the unused inter- remain on the unused inter- remain on the unused inter-
faces during operation! faces during operation! faces during operation! faces during operation!
- against mechanically active Yes; Class 3S4 incl. sand, Yes; Class 3S4 incl. sand, Yes; Class 3S4 incl. sand, Yes; Class 3S4 incl. sand,
substances / conformity with dust. The supplied dust. The supplied dust. The supplied dust. The supplied
EN 60721-3-3 connector covers must connector covers must connector covers must connector covers must
remain on the unused inter- remain on the unused inter- remain on the unused inter- remain on the unused inter-
faces during operation! faces during operation! faces during operation! faces during operation!
■ Overview
SIPLUS CMS1200 SM 1281 Condition Monitoring forms part of
SIMATIC S7-1200 and is used for the:
• Monitoring of motors, generators, pumps, fans, or other
mechanical components
• Recording and analysis of vibrations
3
• Expansion capability of up to 7 modules
■ Technical specifications
Article number 6AT8007-1AA10-0AA0 Article number 6AT8007-1AA10-0AA0
SM1281_Condition_Monitoring SM1281_Condition_Monitoring
General information Speed input
Product brand name SIPLUS Number of speed inputs 1
Product category Condition Monitoring IEPE Protocols
Product designation CMS1200 SM 1281 Condition • 24 V DC digital Yes
Monitoring Sensor input
Product description S7-1200 module for the monitoring of Number of IEPE sensor inputs 4
vibrations on mechanical compo-
nents based on parameters and Sampling frequency, max. 46 875 Hz
frequency-selective analysis Interfaces
functions
Type of data transmission Exporting of raw data as WAV file for
Physical measuring principle Vibration acceleration further analyses (e.g. using
Measurement range vibration 0.1 Hz CMS X-Tools) can be downloaded
frequency, min. via browser
Measurement range vibration 10 000 Hz Ethernet interface Yes
frequency, max. Protocols
Installation type/mounting Bus communication Yes
Mounting type Rail or wall mounting Web server
Mounting position Horizontal, vertical • HTTP Yes
Recommended mounting position Horizontal Interrupts/diagnostics/
Supply voltage status information
Type of supply voltage DC Alarms
Rated value (DC) • Diagnostic alarm Yes
• 24 V DC Yes Diagnostics indication LED
permissible range, lower limit (DC) 20.4 V • Status indicator digital input (green) No
permissible range, upper limit (DC) 28.8 V • for status of the inputs Yes
Input current • for maintenance Yes
Current consumption, typ. 200 mA Integrated Functions
Current consumption, max. 250 mA Monitoring functions
from backplane bus 5 V DC, typ. 80 mA • Monitoring of the sensor inputs Yes; Cable break and short-circuit
from backplane bus 5 V DC, max. 85 mA • Vibration characteristic monitoring Yes
via RMS value of the vibration speed
Memory
• Vibration characteristic monitoring Yes
Total memory capacity 1 Gbyte via RMS value of the vibration accel-
Hardware configuration eration
Design of hardware configuration Modular, up to 7 modules per CPU • Frequency-selective monitoring via Yes
vibration speed spectrum
• Frequency-selective monitoring via Yes
vibration acceleration spectrum
• Frequency-selective monitoring via Yes
envelope curve analysis
3
General information
Product type designation SIM 1274 8Ch DI SIM 1274 14Ch DI
Simulator Simulator
Supply voltage
Rated value (DC) 24 V 24 V
Digital inputs
Number of digital inputs 8 14
Digital outputs
Number of digital outputs 0 0
Degree and class of
protection
Degree of protection acc. to
EN 60529
• Simulator module for program testing during commissioning • IP20 Yes Yes
and ongoing operation Dimensions
• Simulation of 8 or 14 inputs Width 43 mm 67 mm
Height 35 mm 35 mm
Depth 23 mm 23 mm
■ Technical specifications
clock; can be plugged into the
signal board slot of an S7-1200
CPU in FW version 3.0 or higher;
Article number 6ES7297-0AX30-0XA0 battery (CR 1025) is not included
■ Overview
SIWAREX WP231 is a versatile, legal for trade weighing module
for all simple weighing and force measuring tasks. The compact
module is easy to install in the SIMATIC S7-1200 automation sys-
tem. It can also be operated without a SIMATIC CPU.
■ Technical specifications
SIWAREX WP231 SIWAREX WP231
Integration in automation systems Load cell powering
S7-1200 SIMATIC S7-1200 system bus Supply voltage 4.85 V DC
(regulated via feedback)
Operator panel and/or automation Via Ethernet (Modbus TCP/IP) or
systems from other vendors RS 485 (Modbus RTU) Permissible load resistance
Communication interfaces • SIMATIC S7-1200 backplane bus • RLmin > 40
• RS 485 (Modbus RTU, Siebert • RLmax < 4 100
remote display) With SIWAREX IS Ex interface
• Ethernet (SIWATOOL V7,
Modbus TCP/IP) • RLmin > 50
• Analog output 0/4 - 20 mA • RLmax < 4 100
• 4 x digital outputs, 24 V DC floating,
Load cell characteristic 1 … 4 mV/V
short-circuit proof
• 4 x digital outputs, 24 V DC, floating Permissible range of the measure- -21.3 ... +21.3 mV
ment signal (with 4 mV/V sensors)
Commissioning options • Using SIWATOOL V7
• Using function block in SIMATIC Max. distance of load cells 500 m (229.66 ft)
S7-1200 CPU / Touch Panel
• Using Modbus TCP/IP Connection to load cells Optionally via SIWAREX IS Ex
• Using Modbus RTU in Ex zone 1 interface (compatibility of the load
cells must be checked)
Measuring accuracy
Approvals/certificates • ATEX Zone 2
EU type approval as non-automatic 3000 d 0.5 V/e • UL
weighing instrument, trade class III • EAC
• KCC
Error limit according to DIN 1319-1 of 0.05%
• RCM
full-scale value at 20 °C ± 10 K
• OIML R76
(68 °F ± 10 K)
• Design approval 2009/23/EC
Internal resolution up to ±4 million parts (NAWI)
Measuring frequency 100 / 120 Hz Calibration approval EU type approval OIML R76
Digital filter Variable adjustable low-pass and Auxiliary power supply
average filter
Rated voltage 24 V DC
Typical applications • Non-automatic weighing
Max. power consumption 200 mA
instruments
• Force measurements Max. power consumption 3 mA
• Fill-level monitoring SIMATIC Bus
• Belt tension monitors
IP degree of protection according to IP20
Weighing functions DIN EN 60529; IEC 60529
Weight values • Gross Climatic requirements
• Net Tmin (IND) ... Tmax (IND)
• Tare (operating temperature)
Limit values • 2 x min/max • Vertical installation -10 ... +40 °C (14 ... 104 °F)
• Empty • Horizontal installation -10 ... +55 °C (14 ... 131 °F)
Zeroing Per command EMC requirements according to EN 45501
Tare Per command Dimensions 70 x 75 x 100 mm
(2.76 x 2.95 x 3.94 in)
Tare specification Per command
Load cells Full-bridge strain gauges in 4-wire or
6-wire system
3
interface or between two JBs. For
permanent installation. Occasional
bending is possible.
External diameter:
approx. 10.8 mm (0.43 in)
Permissible ambient temperature
-40 ... +80 °C (-40 ... +176 °F).
Sold by the meter.
• Sheath color: orange 7MH4702-8AG
• For potentially explosive 7MH4702-8AF
atmospheres. Sheath color: blue
■ Overview
SIWAREX WP241 is a flexible weighing module for belt scales.
The compact module is easy to install in the SIMATIC S7-1200
automation system. It can also be operated as a stand-alone
module, i.e. without a SIMATIC CPU.
SIWAREX WP241
■ Technical specifications
SIWAREX WP241 SIWAREX WP241
Integration in automation systems Load cells Full-bridge strain gauges in 4-wire or
6-wire system
S7-1200 SIMATIC S7-1200 system bus
Load cell excitation
Operator panel and/or automation Via Ethernet (Modbus TCP/IP) or
systems from other vendors RS 485 (Modbus RTU) Supply voltage 4.85 V DC
(regulated via feedback)
Communication interfaces • SIMATIC S7-1200 backplane bus
• RS 485 (Modbus RTU) Permissible load resistance
• Ethernet (SIWATOOL V7, • RLmin > 40
Modbus TCP/IP) • RLmax < 4100
• Analog output 0/4 - 20 mA
• 4 x digital outputs, 24 V DC floating, With SIWAREX IS Ex interface
short-circuit proof • RLmin > 50
• 4 x digital outputs, 24 V DC, floating
• RLmax < 4100
Commissioning options • Using SIWATOOL V7
Load cell characteristic 1 … 4 mV/V
• Using function block in SIMATIC
S7-1200 CPU / Touch Panel Permissible measurement signal -21.3 ... +21.3 mV
• Using Modbus TCP/IP range
• Using Modbus RTU
Max. distance of load cells 500 m (229.66 ft)
Measuring accuracy
Connection to load cells in Optionally via SIWAREX IS Ex
Error limit according to DIN 1319-1 of 0.05% Ex zone 1 interface (compatibility of the load
full-scale value at 20 °C ± 10 K cells must be checked)
(68 °F ± 10 K)
Approvals/certificates • ATEX Zone 2
Internal resolution up to ±4 million parts • UL
• EAC
Measuring frequency 100 / 120 Hz
• KCC
Digital filter Separate, variable adjustable • RCM
low-pass and average filter for
Calibration approvals • EU-type examination certificate
loading and speed
2014/31/EU (NAWI) acc. to OIML R76
Filter for conveyor load Low-pass filter • EU-type examination certificates
(limit frequency 0.05 ... 50 Hz) 2014/32/EU (MID) acc. to OIML R61
Filter for belt speed Low-pass filter and OIML R51
(limit frequency 0.05 ... 50 Hz) Auxiliary power supply
Weighing functions Rated voltage 24 V DC
Readout data • Weight Max. power consumption 200 mA
• Belt load
• Material flow rate Max. power consumption 3 mA
• Accumulated total SIMATIC Bus
• Main total
IP degree of protection to IP20
• Free totals 1 … 4
DIN EN 60529; IEC 60529
• Belt speed
Climatic requirements
Limits (min/max) • Belt load
Tmin (IND) ... Tmax (IND)
• Material flow rate
(operating temperature)
• Belt speed
• Vertical installation -10 ... +40 °C (14 ... 104 °F)
• Horizontal installation -10 ... +55 °C (14 ... 131 °F)
EMC requirements according to EN 45501
Dimensions 70 x 75 x 100 mm
(2.76 x 2.95 x 3.94 in)
3
Setting the scales PC software SIWATOOL (Ethernet),
S7-1200 function block and touch
panel or directly connected operator
panel (Modbus)
Measuring accuracy
Error limit according to DIN 1319-1 of 0.05%
full-scale value at 20 °C ± 10 K
(68 °F ± 10 K)
Internal resolution Up to ±4 million parts
Number of measurements/second 100 or 120 (selectable)
Filter • Low-pass filter 0.1 ... 50 Hz
• Average value filter
Load cells Full-bridge strain gauges in 4-wire or
SIWAREX WP251 electronic weighing module 6-wire system
SIWAREX WP251 is a flexible weighing module for dosing and Load cell powering
filling processes. The compact module can be installed seam-
Supply voltage 4.85 V DC
lessly in the SIMATIC S7-1200 automation system. It can also be (regulated via feedback)
used without a SIMATIC CPU in stand-alone mode.
Permissible load resistance
■ Overview
• For quick, high-performance serial data exchange via
point-to-point connection
• Implemented protocols: ASCII, USS drive protocol,
Modbus RTU, 3964(R)
• Additional protocols can also be loaded
3
• Simple parameterization with STEP 7 Basic
■ Technical specifications
Article number 6ES7241-1CH32-0XB0 6ES7241-1AH32-0XB0
COMMUNICATION MODULE CM 1241, RS 422/485 COMMUNICATION MODULE CM 1241, RS 232
General information
Product type designation CM 1241 RS 422/485 CM 1241 RS 232
Supply voltage
Rated value (DC)
• 24 V DC Yes Yes
Input current
Current consumption, max. 220 mA; From backplane bus 5 V DC 200 mA; From backplane bus 5 V DC
Power loss
Power loss, typ. 1.1 W 1.1 W
Interfaces
Number of interfaces 1 1
Interface physics, RS 232C (V.24) Yes
Interface (physical) RS 422/485 (X.27) Yes
Point-to-point
• Cable length, max. 1 000 m 10 m
Integrated protocol driver
- Freeport Yes Yes
- ASCII Yes; Available as library function Yes; Available as library function
- Modbus Yes Yes
- Modbus RTU master Yes Yes
- MODBUS RTU slave Yes Yes
- USS Yes; Available as library function
Protocols
Integrated protocols
Freeport
- Telegram length, max. 1 kbyte 1 kbyte
- Bits per character 7 or 8 7 or 8
- Number of stop bits 1 (Standard), 2 1 (Standard), 2
- Parity No parity (standard); No parity (standard);
even, uneven, mark (parity bit always 1); even, uneven, mark (parity bit always 1);
space (parity bit always 0) space (parity bit always 0)
3964 (R)
- Telegram length, max. 1 kbyte 1 kbyte
- Bits per character 7 or 8 7 or 8
- Number of stop bits 1 (Standard), 2 1 (Standard), 2
- Parity No parity (standard); No parity (standard);
even, uneven, mark (parity bit always 1); even, uneven, mark (parity bit always 1);
space (parity bit always 0) space (parity bit always 0)
■ Overview
• For fast, high-performance serial data exchange via • Additional protocols can be loaded later
point-to-point connection • Simple parameterization with STEP 7 Basic
• Implemented protocols: ASCII, USS drive protocol, • Can be plugged directly into the CPU
Modbus RTU
■ Technical specifications
3 Article number 6ES7241-1CH30-1XB0 Article number 6ES7241-1CH30-1XB0
COMMUNICATION BOARD COMMUNICATION BOARD
CB 1241, RS 485 CB 1241, RS 485
General information Interrupts/diagnostics/
Product type designation CB 1241 RS 485 status information
Input current Diagnostic functions Yes
from backplane bus 5 V DC, typ. 50 mA Degree and class of protection
Power loss Degree of protection acc. to
EN 60529
Power loss, typ. 1.5 W
• IP20 Yes
Interfaces
Standards, approvals, certificates
Point-to-point
CE mark Yes
• Cable length, max. 1 000 m
cULus Yes
Integrated protocol driver
FM approval Yes
- Freeport Yes
RCM (formerly C-TICK) Yes
- ASCII Yes; Available as library function
KC approval Yes
- Modbus Yes
Ambient conditions
- Modbus RTU master Yes
Free fall
- MODBUS RTU slave Yes
• Fall height, max. 0.3 m; five times, in product package
- USS Yes; Available as library function
Ambient temperature during
Protocols operation
Integrated protocols • permissible temperature range -20 °C to +60 °C horizontal
Freeport mounting, -20 °C to 50 °C vertical
mounting, 95% humidity, non-
- Telegram length, max. 1 kbyte condensing
- Bits per character 7 or 8 Mechanics/material
- Number of stop bits 1 (Standard), 2 Enclosure material (front)
- Parity No parity (standard); • Plastic Yes
even, uneven, mark
(parity bit always 1); Dimensions
space (parity bit always 0) Width 38 mm
3964 (R) Height 62 mm
- Telegram length, max. 1 kbyte Depth 21 mm
- Bits per character 7 or 8 Weights
- Number of stop bits 1 (Standard), 2 Weight, approx. 40 g
- Parity No parity (standard);
even, uneven, mark
(parity bit always 1);
space (parity bit always 0)
Modbus RTU master
- Address area 1 through 49 999
(Standard Modbus addressing)
- Number of slaves, max. 247; slave numbers 1 through 247,
per MODBUS network segment
maximum 32 devices, additional
repeaters needed to expand the
network to maximum configuration
MODBUS RTU slave
- Address area 1 through 49 999 (Standard Modbus
addressing)
■ Overview
The CM 1242-5 communication module is used to connect a
SIMATIC S7-1200 to PROFIBUS as a DP slave and has the
following characteristics:
• PROFIBUS DPV1 slave in accordance with IEC 61158
• Module replacement without PG supported
3
• Power is supplied via the backplane bus so that no extra
cabling is required
• Support of all standard baud rates from 9.6 Kbit/s to 12 Mbit/s
• Compact industry-standard enclosure in S7-1200 design for
mounting on a standard mounting rail
• Fast commissioning thanks to easy configuration using
STEP 7 without additional programming overhead
The CM 1242-5 is intended for use in factory automation.
Low-cost PROFIBUS-based automation solutions can be
created on the basis of the S7-1200 for optimal production.
■ Technical specifications
Article number 6GK7242-5DX30-0XE0 Article number 6GK7242-5DX30-0XE0
Product type designation CM 1242-5 Product type designation CM 1242-5
Transmission rate Permitted ambient conditions
Transfer rate Ambient temperature
• at the 1st interface acc. to 9.6 kbit/s ... 12 Mbit/s • for vertical installation during 0 ... 45 °C
PROFIBUS operation
Interfaces • for horizontally arranged busbars 0 ... 55 °C
Number of interfaces acc. to Industrial 0 during operation
Ethernet • during storage -40 ... +70 °C
Number of electrical connections • during transport -40 ... +70 °C
• at the 1st interface acc. to 1 Relative humidity at 25 °C without 95 %
PROFIBUS condensation during operation
• for power supply 0 maximum
Type of electrical connection Protection class IP IP20
• at the 1st interface acc. to 9-pin Sub-D socket (RS 485) Design, dimensions and weight
PROFIBUS Module format Compact module S7-1200 single
Supply voltage, current width
consumption, power loss Width 30 mm
Type of voltage of the supply voltage DC Height 100 mm
Supply voltage 1 from backplane bus 5 V Depth 75 mm
Consumed current Net weight 0.115 kg
• from backplane bus at DC at 5 V 0.15 A Mounting type
typical • 35 mm DIN rail mounting Yes
Power loss [W] 0.75 W • S7-300 rail mounting No
• wall mounting Yes
Note:
You can find order information for software in the Catalog IK PI
or in the Industry Mall.
■ Overview
Function
The CM 1243-2 supports all specified functions of the
AS-Interface Specification V3.0.
The values of the digital AS-i slaves can be activated via the
process image of the S7-1200. During configuration of the
3
slaves in the TIA Portal, the values of the analog AS-i slaves can
also be accessed directly in the process image.
It is also possible to exchange all data of the AS-i master and the
connected AS-i slaves with the S7-1200 via the data record
interface.
Changeover of the operating mode, automatic application of the
slave configuration and the re-addressing of a connected AS-i
slave can be implemented via the control panel of the
CM 1243-2 in the TIA Portal.
The optional DCM 1271 data decoupling module (see
"Accessories" and Catalog IC 10) has an integrated detection
unit for detecting ground faults on the AS-Interface cable.
CM 1243-2 communication module for S7-1200 The integrated overload protection also disconnects the
AS-Interface cable if the drive current required exceeds 4 A.
The CM 1243-2 communication module is the AS-Interface
master for the SIMATIC S7-1200 and has the following features: Notes on safety
• As many as 62 AS-Interface slaves can be connected In order to protect plants, systems, machines and networks
• Integrated analog value transmission against cyber threats, it is necessary to implement – and contin-
uously maintain – a holistic, state-of-the-art industrial security
• Supports all AS-Interface master functions in accordance with concept. Siemens products and solutions only represent one
the AS-Interface specification V3.0 component of such a concept.
• Indication of the operating state on the front of the device
displayed via LED For more information on the topic of Industrial Security, see
http://www.siemens.com/industrialsecurity.
• Display of operating mode, AS-Interface voltage faults,
configuration faults and peripheral faults via LED behind the Configuration
front panel
To configure CM 1243-2, you require STEP 7 V11 + SP2 or
• Compact enclosure in the design of the SIMATIC S7-1200 higher.
• Suitable for AS-i Power24V: In combination with the optional For STEP 7 V11 + SP2 or higher, the additional Hardware
DCM 1271 data decoupling module, a standard 24 V power Support Package for CM 1243-2 is required. This is available
supply unit can be used from the Industry Online Support Portal. See
• Configuration and diagnostics via the TIA portal https://support.industry.siemens.com/cs/ww/en/view/54164095.
Design The software enables user-friendly configuration and
diagnostics of the AS-i master and any connected slaves.
The CM 1243-2 communication module is positioned to the left
of the S7-1200 CPU and linked to the S7-1200 via lateral con- Alternatively, you can also apply the AS-Interface ACTUAL
tacts. configuration at the "touch of a button" via the control panel
integrated in the TIA portal/STEP7.
It has:
• Terminals for two AS-i cables (internally jumpered) via two When operated on a S7-1200 CPU with firmware version V4.0 or
screw terminals each higher, the firmware version V1.1 (or higher) is required for the
CM 1243-2.
• One terminal for connection to the functional ground
• LEDs for indication of the operating state and fault statuses of
the connected slaves
The screw terminals (included in scope of supply) can be re-
moved to facilitate installation.
3 supply)
• Dimensions (W × H × D / mm):
30 × 100 × 75
ed addressing mode (A/B slaves)
• With input/output test function and
many other commissioning functions
• Battery operation with four type AA
Accessories batteries (IEC LR6, NEDA 15)
DCM 1271 data decoupling module 3RK7271-1AA30-0AA0 • Degree of protection IP40
• With screw terminals, removable • Dimensions (W × H × D / mm):
terminals (included in the scope of 84 × 195 × 35
supply) • Scope of supply:
• Dimensions (W × H × D / mm): - Addressing unit with 4 batteries
30 × 100 × 75 - Addressing cable, with M12 plug
to addressing plug (hollow plug),
Screw terminals (replacement) length 1.5 m
• 5-pole 3RK1901-3MA00 More information
for AS-i master CM 1243-2 and
AS-i DCM 1271 data decoupling unit For manuals, see
• With screw terminals https://support.industry.siemens.com/
• 3-pole 3RK1901-3MB00 cs/ww/en/ps/15750/man.
for AS-i DCM 1271 data decoupling
unit for connecting the power supply
unit
• With screw terminals
■ Overview
The CM 1243-5 communication module is used to connect a
SIMATIC S7-1200 to PROFIBUS as a DP master and has the
following characteristics:
• PROFIBUS DPV1 master in accordance with IEC 61158
• Support of up to 16 PROFIBUS DP slaves
3
• Communication with other S7 controllers based on
S7 communication
• Allows the connection of programming devices and operator
panels with a PROFIBUS interface to the S7-1200
• Module replacement without PG supported
• Support of all standard baud rates from 9.6 Kbit/s to 12 Mbit/s
• Compact industry-standard enclosure in S7-1200 design for
mounting on a standard mounting rail
• Fast commissioning thanks to easy configuration using
STEP 7 without additional programming overhead
The CM 1243-5 is intended for use in factory automation.
Low-cost PROFIBUS-based automation solutions can be
DP-M DP-S FMS PG/OP S7
created on the basis of the S7-1200 for optimal production.
G_IK10_XX_10323
■ Technical specifications
Article number 6GK7243-5DX30-0XE0 Article number 6GK7243-5DX30-0XE0
Product type designation CM 1243-5 Product type designation CM 1243-5
Transmission rate Permitted ambient conditions
Transfer rate Ambient temperature
• at the 1st interface acc. to 9.6 kbit/s ... 12 Mbit/s • for vertical installation during 0 ... 45 °C
PROFIBUS operation
Interfaces • for horizontally arranged busbars 0 ... 55 °C
Number of interfaces acc. to Industrial 0 during operation
Ethernet • during storage -40 ... +70 °C
Number of electrical connections • during transport -40 ... +70 °C
• at the 1st interface acc. to 1 Relative humidity at 25 °C without 95%
PROFIBUS condensation during operation
• for power supply 1 maximum
Type of electrical connection Protection class IP IP20
• at the 1st interface acc. to 9-pin Sub-D socket (RS 485) Design, dimensions and weight
PROFIBUS Module format Compact module S7-1200 single
• for power supply 3-pole terminal block width
Supply voltage, current Width 30 mm
consumption, power loss Height 100 mm
Type of voltage of the supply voltage DC Depth 75 mm
Supply voltage external 24 V Net weight 0.134 kg
Supply voltage external 24 V Mounting type
at DC Rated value • 35 mm DIN rail mounting Yes
Relative positive tolerance 20% • S7-300 rail mounting No
at DC at 24 V
• wall mounting Yes
Relative negative tolerance 20%
at DC at 24 V Product properties, functions,
components general
Consumed current
Number of units
• from external supply voltage 0.1 A
at DC at 24 V typical • per CPU maximum 3
Power loss [W] 2.4 W
3
Number of DP slaves on DP master 16 PROFIBUS FastConnect
usable connection plug RS 485
Amount of data With 90° cable outlet;
• of the address area of the inputs as 512 byte insulation displacement technology,
DP master total max. transmission rate 12 Mbit/s
• of the address area of the outputs as 512 byte • Without PG interface 6ES7972-0BA52-0XA0
DP master total • With PG interface 6ES7972-0BB52-0XA0
• of the address area of the inputs per 244 byte PROFIBUS FC Standard Cable
DP slave
2-core bus cable, shielded, 6XV1830-0EH10
• of the address area of the outputs 244 byte special design for fast mounting,
per DP slave delivery unit: max. 1000 m,
• of the address area of the diagnostic 240 byte minimum order 20 m,
data per DP slave sold by the meter
Service as DP slave PROFIBUS FastConnect
• DPV0 No Stripping Tool
• DPV1 No Stripping tool for fast stripping of the 6GK1905-6AA00
PROFIBUS FastConnect bus cable
Performance data
S7 communication PROFIBUS bus terminal 12M
Number of possible connections for Bus terminal for connection of 6GK1500-0AA10
S7 communication PROFIBUS nodes up to 12 Mbps with
• maximum 8 connecting cable
• with PG connections maximum 1
• with PG/OP connections maximum 3
• Note max. 4 connections to other
S7 stations
Performance data
multi-protocol mode
Number of active connections with
multi-protocol mode
• without DP maximum 8
• with DP maximum 8
Performance data telecontrol
Protocol is supported
• TCP/IP No
Configuration software
• required STEP 7 Basic/Professional V11
(TIA Portal) or higher
Note:
You can find order information for software in the Catalog IK PI
or in the Industry Mall.
■ Overview
• Unmanaged switch for connecting a SIMATIC S7-1200 to an
Industrial Ethernet network with a line, tree or star topology
• Multiplication of Ethernet interfaces on a SIMATIC S7-1200 for
additional connection of up to three programming devices,
operator controls, and further Ethernet nodes
• Simple, space-saving mounting on the SIMATIC S7-1200
mounting rail
• Low-cost solution for implementing small, local Ethernet
3
networks
• Connection without any problems using RJ45 plugs
• Simple and fast status display via LEDs on the device
• Integral autocrossover function permits use of uncrossed
connecting cables
■ Technical specifications
Article number 6GK7277-1AA10-0AA0 Article number 6GK7277-1AA10-0AA0
Product type designation CSM 1277 Product type designation CSM 1277
Transmission rate Permitted ambient conditions
Transfer rate 10 Mbit/s, 100 Mbit/s Ambient temperature
Interfaces for communication • during operation 0 ... 60 °C
integrated • during storage -40 ... +70 °C
Number of electrical connections • during transport -40 ... +70 °C
• for network components or terminal 4 Relative humidity
equipment
• at 25 °C without condensation 95%
Number of 100 Mbit/s SC ports during operation maximum
• for multimode 0 Protection class IP IP20
Number of 1000 Mbit/s LC ports Design, dimensions and weight
• for multimode 0 Design SIMATIC S7-1200 device design
• for single mode (LD) 0 Width 45 mm
Interfaces others Height 100 mm
Number of electrical connections Depth 75 mm
• for power supply 1 Net weight 0.15 kg
Type of electrical connection Mounting type
• for power supply 3-pole terminal block • 35 mm DIN rail mounting Yes
Supply voltage, current • wall mounting Yes
consumption, power loss
• S7-300 rail mounting No
Type of voltage of the supply voltage DC
• S7-1500 rail mounting No
Supply voltage
Product functions management,
• external 24 V configuration
• external 19.2 ... 28.8 V Product function
Product component fusing at power Yes • multiport mirroring No
supply input
• switch-managed No
Fuse protection type at input for 0.5 A / 60 V
supply voltage Product functions Redundancy
Consumed current maximum 0.07 A Product function
Power loss [W] • Parallel Redundancy Protocol (PRP)/ Yes
operation in the PRP-network
• at DC at 24 V 1.6 W
• Parallel Redundancy Protocol (PRP)/ No
Redundant Network Access (RNA)
■ Overview
The CP 1243-1 communications processor is used for
connecting a SIMATIC S7-1200 to the TeleControl Server Basic
control center software via Ethernet, and for safe communication
via IP-based networks.
The CP has the following features:
• Ethernet-based connection to TeleControl Server Basic,
e.g. via Internet 3
• Data transfer of measured values, control variables, or alarms
optimized for telecontrol systems
• Automatic sending of alert emails
• Data buffering of up to 64,000 values ensures a secure
database even with temporary connection failures
• Secure communication via VPN connections based on IPSec
• Access protection via Stateful Inspection Firewall
• Clearly laid out LED signaling for fast and easy diagnostics
• Compact industrial enclosure in S7-1200 design for mounting
on a standard mounting rail
• Fast commissioning thanks to easy configuration using
STEP 7
■ Technical specifications
Article number 6GK7243-1BX30-0XE0 Article number 6GK7243-1BX30-0XE0
Product type designation CP 1243-1 Product type designation CP 1243-1
Transmission rate Permitted ambient conditions
Transfer rate Ambient temperature
• at the 1st interface 10 ... 100 Mbit/s • for vertical installation during -20 ... +60 °C
Interfaces operation
Number of interfaces acc. to Industrial 1 • for horizontally arranged busbars -20 ... +70 °C
Ethernet during operation
Number of electrical connections • during storage -40 ... +70 °C
• at the 1st interface acc. to Industrial 1 • during transport -40 ... +70 °C
Ethernet Relative humidity at 25 °C without 95%
• for power supply 0 condensation during operation
maximum
Type of electrical connection
Protection class IP IP20
• at the 1st interface acc. to Industrial RJ45 port
Ethernet Design, dimensions and weight
Supply voltage, current Module format Compact module S7-1200 single
consumption, power loss width
Type of voltage of the supply voltage DC Width 30 mm
Supply voltage 1 from backplane bus 5 V Height 110 mm
Consumed current Depth 75 mm
• from backplane bus 0.25 A Net weight 0.122 kg
at DC at 5 V typical Mounting type
Power loss [W] 1.25 W • 35 mm DIN rail mounting Yes
• wall mounting Yes
3
Type of encryption algorithms with AES-256, AES-192, AES-128,
Performance data VPN connection 3DES-168
S7 communication Type of authentication procedure with Preshared key (PSK),
Number of possible connections for VPN connection X.509v3 certificates
S7 communication Type of hashing algorithms with MD5, SHA-1
• Note like CPU VPN connection
Performance data telecontrol Number of possible connections with 8
Suitability for use VPN connection
• Node station No Product function
• substation Yes • password protection for Web No
applications
• TIM control center No
• password protection for teleservice No
Control center connection to be used with Telecontrol Server access
Basic
• encrypted data transmission Yes
• by means of a permanent supported
connection • ACL - IP-based No
• Note Connection to SCADA system via • ACL - IP-based for PLC/routing No
Telecontrol Server Basic • switch-off of non-required services Yes
Protocol is supported • Blocking of communication via No
• DNP3 No physical ports
• IEC 60870-5 No • log file for unauthorized access No
Product function data buffering if Yes; 64,000 values Product functions Time
connection is aborted Protocol is supported
Number of data points per station 200 • NTP Yes
maximum time synchronization
Performance data Teleservice • from control center Yes
Diagnostics function online Yes
diagnostics with SIMATIC STEP 7
Product function
• program download with Yes
SIMATIC STEP 7
• Remote firmware update Yes
Configuration software
• required STEP 7 Basic/Professional V13
Update 2 + HSP (TIA Portal) or
higher
■ Overview
In conjunction with the TeleControl Server Basic software, the
CP 1242-7 forms a telecontrol system with additional properties:
• Connection of up to 5000 telecontrol stations to the control
center via an OPC interface
• Data buffering in the substations in the event of connection
failures
3 • Central status monitoring of the substations
• No special provider services required for fixed IP addresses
• Teleservice access with STEP 7 to the substations via the
Internet
The CP 1242-7 V2 is a new product version of the CP 1242-7.
The concept for process data transmission has been expanded
with a simple data point configuration, which enables substan-
tially easier commissioning without high programming overhead
and minimizes susceptibility to errors during the projects imple-
mentation phase. CP 1242-7 has also been equipped with new
functions, such as access to the internal Web server of the
S7-1200. This opens up numerous new application areas.
The CP 1242-7 GPRS V2 communications processor is used to
connect a SIMATIC S7-1200 to the globally available GSM/GPRS
mobile radio network and has the following characteristics:
• Worldwide wireless exchange of data between S7-1200
controllers and/or between S7-1200 controllers and control
centers with an Internet connection
• Communication based on the GPRS (General Packet Radio
Service) mobile wireless service with data transmission
speeds of up to 86 Kbit/s in the downlink and 43 Kbit/s in the
uplink
• GPRS mode with fixed IP addresses and dynamic IP
addresses with standard mobile phone contract
• Time synchronization on the basis of NTP (Network Time
Protocol)
• Sending and receiving of text messages
• LED signaling for fast diagnostics
• Compact industrial enclosure in S7-1200 design for mounting
on a standard mounting rail
• Fast commissioning thanks to easy configuration using
STEP 7
■ Technical specifications
Article number 6GK7242-7KX31-0XE0 Article number 6GK7242-7KX31-0XE0
Product type designation CP 1242-7 V2 Product type designation CP 1242-7 V2
Transmission rate Wireless technology
Transfer rate Type of mobile wireless service
• for GPRS transmission • is supported SMS Yes
- with downlink maximum 86 kbit/s • is supported GPRS Yes
- with uplink maximum 43 kbit/s • Note GPRS (Multislot Class 10)
Interfaces Type of mobile network is supported
Number of interfaces acc. to Industrial 0 • GSM Yes
Ethernet • UMTS No
Number of electrical connections • LTE No
• for external antenna(s) 1 Operating frequency
• for power supply 1 • 850 MHz Yes
Number of slots • 900 MHz Yes
• for SIM cards 1 • 1800 MHz Yes
Type of electrical connection • 1900 MHz Yes
• for external antenna(s) SMA socket (50 ohms) Transmit power
• for power supply 3-pole terminal block • at operating frequency 900 MHz 2W
Slot version • at operating frequency 1800 MHz 1W
• for SIM card Standard • at operating frequency 1900 MHz 1W
■ Overview
• 1 connection to LTE (4G) mobile wireless network
(various versions for EU and North America)
• Data transfer of measured values, control variables, or alarms
optimized for telecontrol systems
• Operation with fixed IP addresses and dynamic IP addresses
with standard cellular phone contract
• Time synchronization based on NTP (Network Time Protocol) 3
• On-demand connection buildup via voice call or text message
• Sending and receiving of text messages
• TeleService access with STEP 7 to substations via mobile
wireless networks
• Compact industrial enclosure in S7-1200 design for mounting
on a standard mounting rail
• Temperature range in operation: -20 °C to +70 °C
• Installation on standard mounting rails
• Diagnostics LEDs (overall status and details)
CP 1243-7 LTE is used to connect the S7-1200 to a mobile • Integrated security functions (VPN and firewall)
wireless network of the 4th Generation LTE (Long Term • Access to the CPU Web server
Evolution). The increased data rates compared to GPRS and • Fast commissioning due to simplified configuration with
widespread introduction of LTE open up new areas of appli- STEP 7
cation. The CP1243-7 is characterized by the following
properties: • Data buffering of up to 64,000 values ensures a secure
database even with temporary connection failures
■ Technical specifications
Article number 6GK7243-7KX30- 6GK7243-7SX30- Article number 6GK7243-7KX30- 6GK7243-7SX30-
0XE0 0XE0 0XE0 0XE0
Product type designation CP 1243-7 LTE EU CP 1243-7 LTE US Product type designation CP 1243-7 LTE EU CP 1243-7 LTE US
Transmission rate Wireless technology
Transfer rate Type of mobile wireless
• for LTE transmission service
- with downlink maximum 42 Mbit/s 42 Mbit/s • is supported SMS Yes Yes
- with uplink maximum 5.76 Mbit/s 5.76 Mbit/s • is supported GPRS Yes Yes
Interfaces • Note GPRS (Multislot Class GPRS (Multislot Class
10) 10)
Number of interfaces acc. to 0 0
Industrial Ethernet Type of mobile network is
supported
Number of electrical
connections • GSM Yes Yes
• for external antenna(s) 1 1 • UMTS Yes Yes
• for power supply 1 1 • LTE Yes Yes
Number of slots Operating frequency
• for SIM cards 1 1 • 850 MHz Yes
Type of electrical connection • 1900 MHz Yes
• for external antenna(s) SMA socket SMA socket Operating frequency
(50 ohms) (50 ohms) • for GSM transmission Yes
• for power supply 3-pole terminal block 3-pole terminal block 900 MHz
Slot version • for GSM transmission Yes
1800 MHz
• for SIM card Standard Standard
• with UMTS transmission Yes
900 MHz
• with UMTS transmission Yes
2100 MHz
• for LTE transmission Yes
700 MHz
• for LTE transmission Yes
800 MHz
• for LTE transmission Yes
1700 MHz
• for LTE transmission Yes
1800 MHz
• for LTE transmission Yes
2600 MHz
3
voltage
Control center connection Telecontrol Server Telecontrol Server
Supply voltage external 24 V 24 V Basic Basic
Supply voltage external 24 V 24 V • by means of a permanent supported supported
at DC Rated value connection
Relative positive tolerance 20% 20% • by means of demand- supported supported
at DC at 24 V oriented connection
Relative negative tolerance 20% 20% • Note Connection to Connection to
at DC at 24 V SCADA system using SCADA system using
Consumed current OPC interface OPC interface
• from external supply voltage 0.1 A 0.1 A Protocol is supported
at DC at 24 V typical • DNP3 No No
• from external supply voltage 0.22 A 0.22 A • IEC 60870-5 No No
at DC at 24 V maximum
Product function data Yes; 64,000 values Yes; 64,000 values
Permitted ambient conditions buffering if connection is
Ambient temperature aborted
• for vertical installation during -20 ... +60 °C -20 ... +60 °C Performance data
operation Teleservice
• for horizontally arranged -20 ... +70 °C -20 ... +70 °C Diagnostics function online Yes Yes
busbars during operation diagnostics with SIMATIC
• during storage -40 ... +70 °C -40 ... +70 °C STEP 7
• during transport -40 ... +70 °C -40 ... +70 °C Product function
Relative humidity at 25 °C 95% 95% • program download with Yes Yes
without condensation during SIMATIC STEP 7
operation maximum • Remote firmware update Yes Yes
Protection class IP IP20 IP20 Configuration software
Design, dimensions and • required STEP 7 Basic/ STEP 7 Basic/
weight Professional V13 SP1 Professional V13 SP1
Module format Compact module Compact module or higher + HSP or higher
S7-1200 single width S7-1200 single width Product functions Diagnosis
Width 30 mm 30 mm Product function Web-based Yes Yes
Height 100 mm 100 mm diagnostics
Depth 75 mm 75 mm Product functions Security
Net weight 0.133 kg 0.133 kg Firewall version stateful inspection stateful inspection
Mounting type Product function with VPN IPSec IPSec
connection
• 35 mm DIN rail mounting Yes Yes
Type of encryption algorithms AES-256, AES-192, AES-256, AES-192,
• S7-300 rail mounting No No with VPN connection AES-128, 3DES-168, AES-128, 3DES-168,
• wall mounting Yes Yes DES-56 DES-56
Product properties, Type of authentication Preshared key (PSK), Preshared key (PSK),
functions, components procedure with VPN X.509v3 certificates X.509v3 certificates
general connection
Number of units Type of hashing algorithms MD5, SHA-1 MD5, SHA-1
with VPN connection
• per CPU maximum 3 3
Number of possible connec- 1 1
Performance data tions with VPN connection
Number of users/telephone 10 10 Product function
numbers definable maximum
• password protection for Yes Yes
Performance data open teleservice access
communication
• encrypted data transmission Yes Yes
Number of possible connec-
tions for open communication Product functions Time
• by means of T blocks like CPU like CPU Protocol is supported
maximum • NTP Yes Yes
Performance data IT time synchronization
functions
• from control center Yes Yes
Number of possible
connections
• as e-mail client maximum 1 1
■ Overview
• Both WAN interfaces can also be operated simultaneously:
Route redundancy
• Data transfer optimized for telecontrol systems on the basis of
SINAUT ST7
• Automatic transmission of alarms per email or SMS
3
• Time synchronization based on NTP (Network Time Protocol)
or via the SINAUT system
• Data buffering of up to 16,000 data messages prevents data
loss in the event of temporary connection failures
• Secure communication via VPN connections based on IPSec
• Access protection via Stateful Inspection Firewall
• Fast and simple diagnostics via clear LED indicators, STEP 7
and web browser
• Compact industrial enclosure in S7-1200 design for mounting
on a standard mounting rail
The integrated Ethernet interface and the option of using the
TS modules provide flexible connection options for the CP. The
The CP 1243-8 IRC communications processor (Industrial following TS modules are available:
Remote Communication) is used for connecting a
SIMATIC S7-1200 in the TeleControl Professional system via the • TS module RS 232
SINAUT ST7 telecontrol protocol to higher-level ST7 stations or • TS module MODEM
to an ST7 control center. • TS module ISDN and
The CP has the following features: • TS module GSM.
• SINAUT ST7 telecontrol protocol supported
• Two WAN connections for selecting the communication paths:
- Ethernet-based connection: RJ45 port on the module for
connecting external routers, e.g. SCALANCE M
- Additional connection configurable via plug-in TS modules
■ Technical specifications
Article number 6GK7243-8RX30-0XE0 Article number 6GK7243-8RX30-0XE0
Product type designation CP 1243-8 IRC Product type designation CP 1243-8 IRC
Transmission rate Consumed current
Transfer rate • from backplane bus at DC at 5 V 0.25 A
• at the 1st interface 10 ... 100 Mbit/s typical
• at the 2nd interface 0.3 ... 115.2 kbit/s • from external supply voltage at DC at 0.1 A
24 V typical
Interfaces
Power loss [W] Note 1.25 W from S7-1200 backplane
Number of interfaces acc. to Industrial 1 without TS module. 2.4 W from
Ethernet 24 V DC external with TS module
Number of electrical connections Power loss [W] 2.4 W
• at the 1st interface acc. to Industrial 1 Permitted ambient conditions
Ethernet
Ambient temperature
• for power supply 1
• for vertical installation during -20 ... +60 °C
Type of electrical connection operation
• at the 1st interface acc. to Industrial RJ45 port • for horizontally arranged busbars -20 ... +70 °C
Ethernet during operation
• at interface 2 for external data Interface to the TS Module • during storage -40 ... -70 °C
transmission
• during transport -40 ... +70 °C
• for power supply 3-pole terminal block
Relative humidity at 25 °C without 95%
Supply voltage, current condensation during operation
consumption, power loss maximum
Type of voltage of the supply voltage DC Protection class IP IP20
Supply voltage 1 from backplane bus 5 V
Supply voltage external 24 V
Supply voltage external 19.2 ... 28.8 V
Supply voltage external at DC Rated 24 V
value
Supply voltage external at DC rated 19.2 ... 28.8 V
value
■ Overview
The CP 1243-1 DNP3 communications processor is used to
connect a SIMATIC S7-1200 to a control center system via the
DNP3 protocol and has the following characteristics:
• Support for the established DNP3 telecontrol protocol for
standardized linking of the SIMATIC S7-1200 to WinCC,
PCS 7, or other commercially available control center systems
• Data transfer of measured values, control variables, or alarms
optimized for telecontrol systems
3
• Automatic sending of alert emails
• Clearly laid out LED signaling for fast and easy diagnostics
• Compact industrial enclosure in S7-1200 design for mounting
on a standard mounting rail
• Fast commissioning thanks to easy configuration using
STEP 7
• Data buffering of up to 64,000 values ensures a secure
database even with temporary connection failures
■ Technical specifications
Article number 6GK7243-1JX30-0XE0 Article number 6GK7243-1JX30-0XE0
Product type designation CP 1243-1 DNP3 Product type designation CP 1243-1 DNP3
Transmission rate Design, dimensions and weight
Transfer rate Module format Compact module S7-1200 single
• at the 1st interface 10 ... 100 Mbit/s width
Interfaces Width 30 mm
Number of interfaces acc. to Industrial 1 Height 110 mm
Ethernet Depth 75 mm
Number of electrical connections Net weight 0.122 kg
• at the 1st interface acc. to Industrial 1 Mounting type
Ethernet • 35 mm DIN rail mounting Yes
• for power supply 0 • wall mounting Yes
Type of electrical connection Product properties, functions,
• at the 1st interface acc. to Industrial RJ45 port components general
Ethernet Number of units
Supply voltage, current • per CPU maximum 3
consumption, power loss
Performance data
Type of voltage of the supply voltage DC S7 communication
Supply voltage 1 from backplane bus 5 V Number of possible connections for
Consumed current S7 communication
• from backplane bus at DC at 5 V 0.25 A • Note like CPU
typical Performance data IT functions
Power loss [W] 1.25 W Number of possible connections
Permitted ambient conditions • as e-mail client maximum 1
Ambient temperature
• for vertical installation during -20 ... +60 °C
operation
• for horizontally arranged busbars -20 ... +70 °C
during operation
• during storage -40 ... +70 °C
• during transport -40 ... +70 °C
Relative humidity at 25 °C without 95%
condensation during operation
maximum
Protection class IP IP20
3
• substation Yes
• TIM control center No • program download with SIMATIC Yes
STEP 7
Control center connection control center with DNP3 function
• Remote firmware update Yes
• by means of a permanent supported
connection Configuration software
• Note Connection to SCADA system using • required STEP 7 Basic/Professional V12 SP1
DNP3 services (TIA Portal) or higher
Protocol is supported Product functions Time
• DNP3 Yes Protocol is supported
• IEC 60870-5 No • NTP No
Product function data buffering if Yes; 64,000 values time synchronization
connection is aborted • from control center Yes
Number of data points per station 200
maximum
■ Overview
The CP 1243-1 IEC communications processor is used to
connect a SIMATIC S7-1200 to a control center system via the
IEC 60870 protocol and has the following characteristics:
• Support for the established communication standard in
accordance with IEC 60870-5-104 for standardized linking of
the SIMATIC S7-1200 to WinCC, PCS 7, or other commercially
available control center systems
• Data transfer of measured values, control variables, or alarms
3
optimized for telecontrol systems
• Automatic sending of alert emails
• Clearly laid out LED signaling for fast and easy diagnostics
• Compact industrial enclosure in S7-1200 design for mounting
on a standard mounting rail
• Fast commissioning thanks to easy configuration using
STEP 7
• Data buffering of up to 64,000 values ensures a secure
database even with temporary connection failures
■ Technical specifications
Article number 6GK7243-1PX30-0XE0 Article number 6GK7243-1PX30-0XE0
Product type designation CP 1243-1 IEC Product type designation CP 1243-1 IEC
Transmission rate Design, dimensions and weight
Transfer rate Module format Compact module S7-1200 single
• at the 1st interface 10 ... 100 Mbit/s width
Interfaces Width 30 mm
Number of interfaces acc. to Industrial 1 Height 110 mm
Ethernet Depth 75 mm
Number of electrical connections Net weight 0.122 kg
• at the 1st interface acc. to Industrial 1 Mounting type
Ethernet • 35 mm DIN rail mounting Yes
• for power supply 0 • wall mounting Yes
Type of electrical connection Product properties, functions,
• at the 1st interface acc. to Industrial RJ45 port components general
Ethernet Number of units
Supply voltage, current • per CPU maximum 3
consumption, power loss
Performance data S7 communi-
Type of voltage of the supply voltage DC cation
Supply voltage 1 from backplane bus 5 V Number of possible connections for
Consumed current S7 communication
• from backplane bus 0.25 A • Note like CPU
at DC at 5 V typical Performance data IT functions
Power loss [W] 1.25 W Number of possible connections
Permitted ambient conditions • as e-mail client maximum 1
Ambient temperature
• for vertical installation during -20 ... +60 °C
operation
• for horizontally arranged busbars -20 ... +70 °C
during operation
• during storage -40 ... +70 °C
• during transport -40 ... +70 °C
Relative humidity at 25 °C without 95%
condensation during operation
maximum
Protection class IP IP20
3
• substation Yes
• TIM control center No • program download with SIMATIC Yes
STEP 7
Control center connection control center with IEC 60870-5
function • Remote firmware update Yes
• by means of a permanent supported Configuration software
connection • required STEP 7 Basic/Professional V13
• Note Connection to SCADA system using (TIA Portal) or higher
IEC 60870-5 Product functions Time
Protocol is supported Protocol is supported
• DNP3 No • NTP No
• IEC 60870-5 Yes time synchronization
Product function data buffering if Yes; 64,000 values • from control center Yes
connection is aborted
Number of data points per station 200
maximum
■ Overview
The SIMATIC RF120C is a communication module for
connecting the SIMATIC identification systems directly to the
SIMATIC S7-1200. The readers of all RFID systems as well as the
MV400 optical readers can be operated on the
SIMATIC RF120C.
Integration into the TIA Portal and the uniform plug-in connection
systems permit fast and simple commissioning.
3
■ Technical specifications
Article number 6GT2002-0LA00 Article number 6GT2002-0LA00
Product type designation RF120C communication module Product type designation RF120C communication module
Suitability for operation SIMATIC S7-1200 together with Permitted ambient conditions
RF200/300/600, MV400, MOBY D/U Ambient temperature
Transmission rate • during operation 0 ... 55 °C
Transfer rate at the point-to-point 115.2 kbit/s • during storage -40 ... +70 °C
connection serial maximum
• during transport -40 ... +70 °C
Interfaces
Protection class IP IP20
Design of the interface for point-to- RS 422
point connection Shock resistance According to IEC 61131-2
Number of readers connectable 1 Shock acceleration 300 m/s²
Type of electrical connection Vibrational acceleration 100 m/s²
• of the backplane bus S7-1200 backplane bus Design, dimensions and weight
• for supply voltage Screw terminals Width 30 mm
Design of the interface to the reader D-sub, 9-pin, socket Height 100 mm
for communication Depth 75 mm
Mechanical data Net weight 0.15 kg
Material Xantar MX 1094 Mounting type S7-1200 rack
Color Ti-grey 24L01 Cable length for RS 422 interface 1 000 m
Tightening torque of the screw for 0.45 N·m maximum
securing the equipment maximum Product properties, functions,
Supply voltage, current components general
consumption, power loss Display version 4 LEDs for reader connection,
Supply voltage 1 LED for device status
• at DC Rated value 24 V Product function transponder file No
handler can be addressed
• at DC 20 ... 30 V
Protocol is supported
Consumed current at DC at 24 V
• S7 communication Yes
• without connected devices typical 0.03 A
Type of parameterization HSP
• with connected devices maximum 1A
Type of programming Library with functions
Type of computer-mediated communi- acyclic communication
cation
Standards, specifications,
approvals
Certificate of suitability CE, FCC, cULus, KCC, C-Tick, FM,
Ex: II 3G Ex nAA IIC T4 Gc
MTBF 196 y
3
Reader cable for SIMATIC 5 m, straight connector 6GT2891-4FH50
RF200 / RF300 / RF600 / MV400
PUR material, CMG approval, 10 m, straight connector 6GT2891-4FN10
suitable for cable carriers, 20 m, straight connector 6GT2891-4FN20
straight reader connector
50 m, straight connector 6GT2891-4FN50
2m 6GT2091-4LH20
2 m, plug angled at reader 6GT2891-4JH20
5m 6GT2091-4LH50
5 m, plug angled at reader 6GT2891-4JH50
10 m 6GT2091-4LN10
10 m, plug angled at reader 6GT2891-4JN10
Reader adapter cable for MOBY D 6GT2691-4FH20
Material PUR, CMG approval,
suitable for cable carriers, 2 m.
A cable of the type 6GT2091-4L... is
also required.
DVD "RFID Systems Software & 6GT2080-2AA20
Documentation"
■ Overview
• For fast, high-performance serial data exchange via
point-to-point coupling
• Implemented protocols: ASCII, USS drive protocol,
Modbus RTU
• Additional protocols can also be loaded
3
• Simple parameterization with STEP 7 Basic
Note:
SIPLUS extreme products are based on SIMATIC standard
products. The contents listed here were taken from the respec-
tive standard products. SIPLUS extreme-specific information
was added.
■ Technical specifications
Article number 6AG1241-1AH32-4XB0 6AG1241-1AH32-2XB0 6AG1241-1CH32-4XB0 6AG1241-1CH32-2XB0
Based on 6ES7241-1AH32-0XB0 6ES7241-1AH32-0XB0 6ES7241-1CH32-0XB0 6ES7241-1CH32-0XB0
SIPLUS S7-1200 CM 1241 SIPLUS S7-1200 CM1241 SIPLUS S7-1200 CM 1241 SIPLUS S7-1200 CM 1241
RS 232 RS 232 RS 422/485 RS 422/485
Ambient conditions
Free fall
• Fall height, max. 0.3 m; five times, in product 0.3 m; five times, in product 0.3 m; five times, in product 0.3 m; five times, in product
package package package package
Ambient temperature during
operation
• min. -20 °C; = Tmin; -40 °C; = Tmin; -20 °C; = Tmin; -40 °C; = Tmin;
Startup @ 0 °C Startup @ -25 °C Startup @ 0 °C Startup @ -25 °C
• max. 60 °C 70 °C; = Tmax 60 °C; = Tmax 70 °C; Tmax > 60 °C,
derating: Max. one module
may be configured; this
module must be the last
module on the CM bus;
minimum clearance on the
left side of at least 45 mm
3 atmospheric pressure-installation
altitude
1080 hPa ... 795 hPa
(-1000 m ... +2000 m) //
Tmin ... (Tmax - 10K) at
1080 hPa ... 795 hPa
(-1000 m ... +2000 m) //
Tmin ... (Tmax - 10K) at
1080 hPa ... 795 hPa
(-1000 m ... +2000 m) //
Tmin ... (Tmax - 10K) at
1080 hPa ... 795 hPa
(-1000 m ... +2000 m) //
Tmin ... (Tmax - 10K) at
795 hPa ... 658 hPa 795 hPa ... 658 hPa 795 hPa ... 658 hPa 795 hPa ... 658 hPa
(+2000 m ... +3500 m) // (+2000 m ... +3500 m) // (+2000 m ... +3500 m) // (+2000 m ... +3500 m) //
Tmin ... (Tmax - 20K) at Tmin ... (Tmax - 20K) at Tmin ... (Tmax - 20K) at Tmin ... (Tmax - 20K) at
658 hPa ... 540 hPa 658 hPa ... 540 hPa 658 hPa ... 540 hPa 658 hPa ... 540 hPa
(+3500 m ... +5000 m) (+3500 m ... +5000 m) (+3500 m ... +5000 m) (+3500 m ... +5000 m)
Relative humidity
- With condensation, tested in 100%; RH incl. conden- 100%; RH incl. conden- 100%; RH incl. conden- 100%; RH incl. conden-
accordance with IEC 60068-2-38, sation/frost (no commis- sation/frost (no commis- sation/frost (no commis- sation/frost (no commis-
max. sioning under condensation sioning under condensation sioning under condensation sioning under condensation
conditions) conditions) conditions) conditions)
Resistance
- against biologically active Yes; Class 3B2 mold, fungus Yes; Class 3B2 mold, fungus Yes; Class 3B2 mold, fungus Yes; Class 3B2 mold, fungus
substances / conformity with and dry rot spores (with the and dry rot spores (with the and dry rot spores (with the and dry rot spores (with the
EN 60721-3-3 exception of fauna). The exception of fauna). The exception of fauna). The exception of fauna). The
supplied connector covers supplied connector covers supplied connector covers supplied connector covers
must remain on the unused must remain on the unused must remain on the unused must remain on the unused
interfaces during operation! interfaces during operation! interfaces during operation! interfaces during operation!
- against chemically active Yes; Class 3C4 (RH < 75%) Yes; Class 3C4 (RH < 75%) Yes; Class 3C4 (RH < 75%) Yes; Class 3C4 (RH < 75%)
substances / conformity with incl. salt spray according to incl. salt spray according to incl. salt spray according to incl. salt spray according to
EN 60721-3-3 EN 60068-2-52 (degree of EN 60068-2-52 (degree of EN 60068-2-52 (degree of EN 60068-2-52 (degree of
severity 3). The supplied severity 3). The supplied severity 3). The supplied severity 3). The supplied
connector covers must connector covers must connector covers must connector covers must
remain on the unused inter- remain on the unused inter- remain on the unused inter- remain on the unused inter-
faces during operation! faces during operation! faces during operation! faces during operation!
- against mechanically active Yes; Class 3S4 incl. sand, Yes; Class 3S4 incl. sand, Yes; Class 3S4 incl. sand, Yes; Class 3S4 incl. sand,
substances / conformity with dust. The supplied dust. The supplied dust. The supplied dust. The supplied
EN 60721-3-3 connector covers must connector covers must connector covers must connector covers must
remain on the unused inter- remain on the unused inter- remain on the unused inter- remain on the unused inter-
faces during operation! faces during operation! faces during operation! faces during operation!
■ Overview
• For fast, high-performance serial data exchange via Note:
point-to-point connection
SIPLUS extreme products are based on SIMATIC standard
• Implemented protocols: ASCII, USS drive protocol, products. The contents listed here were taken from the respec-
Modbus RTU tive standard products. SIPLUS extreme-specific information
• Additional protocols can be loaded later was added.
• Simple parameterization with STEP 7 Basic
• Can be plugged directly into the CPU 3
■ Technical specifications
Article number 6AG1241-1CH30-5XB1 Article number 6AG1241-1CH30-5XB1
Based on 6ES7241-1CH30-1XB0 Based on 6ES7241-1CH30-1XB0
SIPLUS S7-1200 CB 1241 RS 485 SIPLUS S7-1200 CB 1241 RS 485
General information Extended ambient conditions
Product type designation CB 1241 RS 485 • relative to ambient temperature- Tmin ... Tmax at
Input current atmospheric pressure-installation 1080 hPa ... 795 hPa
altitude (-1000 m ... +2000 m) //
from backplane bus 5 V DC, typ. 50 mA Tmin ... (Tmax - 10K) at
Power loss 795 hPa ... 658 hPa
(+2000 m ... +3500 m) //
Power loss, typ. 1.5 W Tmin ... (Tmax - 20K) at
Interrupts/diagnostics/ 658 hPa ... 540 hPa
status information (+3500 m ... +5000 m)
Diagnostic functions Yes • At cold restart, min. -25 °C
Diagnostics indication LED Relative humidity
• for status of the outputs Yes - With condensation, tested in 100%; RH incl. condensation/frost
accordance with IEC 60068-2-38, (no commissioning under
Degree and class of protection
max. condensation conditions)
Degree of protection acc. to
Pollutant concentrations
EN 60529
- SO2 at RH < 60% without S02: < 0.5 ppm; H2S: < 0.1 ppm;
• IP20 Yes
condensation RH < 60 % condensation-free
Standards, approvals, certificates
Resistance
CE mark Yes
- against biologically active Yes; Class 3B2 mold, fungus and dry
RCM (formerly C-TICK) Yes substances / conformity with rot spores (with the exception of
KC approval Yes EN 60721-3-3 fauna). The supplied connector
covers must remain on the unused
Ambient conditions interfaces during operation!
Free fall - against chemically active Yes; Class 3C4 (RH < 75%) incl. salt
• Fall height, max. 0.3 m; five times, in product package substances / conformity with spray according to EN 60068-2-52
EN 60721-3-3 (degree of severity 3). The supplied
Ambient temperature during connector covers must remain on the
operation unused interfaces during operation!
• min. -40 °C; = Tmin; Startup @ -25 °C - against mechanically active Yes; Class 3S4 incl. sand, dust. The
• max. 55 °C substances / conformity with supplied connector covers must
EN 60721-3-3 remain on the unused interfaces
during operation!
• Support of all standard baud rates from 9.6 Kbit/s to 12 Mbit/s SIPLUS CM 1243-5
communication module
• Compact industry-standard enclosure in S7-1200 design for
mounting on a standard mounting rail (Extended temperature range and
exposure to media)
• Fast commissioning thanks to easy configuration using
Communication module for 6AG1243-5DX30-2XE0
STEP 7 without additional programming overhead electrical connection of
SIMATIC S7-1200 to PROFIBUS as
The CM 1243-5 is intended for use in factory automation. a DPV1 master
Low-cost PROFIBUS-based automation solutions can be
created on the basis of the S7-1200 for optimal production. Accessories See SIMATIC S7-1200 CM 1243-5
communication module,
Note: page 3/130
■ Overview
• Digital inputs as supplement to the integral I/O of the CPUs
• Integrated into the overall automation for the implementation
of safety-related requirements
• With integrated safety functions
• Communication with fail-safe CPUs via PROFIsafe
3
mechanisms
• For flexible adaptation of the controller to the corresponding
task
• For subsequent expansion of the system with additional inputs
• Operable exclusively in the central system
■ Technical specifications
Article number 6ES7226-6BA32-0XB0 Article number 6ES7226-6BA32-0XB0
DIGITAL INPUT SM 1226, DIGITAL INPUT SM 1226,
F-DI 16X 24VDC F-DI 16X 24VDC
General information Cable length
Product type designation SM 1226 F-DI 16x24VDC • shielded, max. 200 m; Unshielded with input filter
Supply voltage time of 1.6 ms to 12.6 ms (With an
input delay of 0.8 ms, shielded
Rated value (DC) cables must be used for the digital
• 24 V DC Yes inputs and the sensor supply)
Input current • unshielded, max. 200 m; Shielded with input filter time
of 0.8 ms to 12.6 s (With an input
from backplane bus 5 V DC, max. 155 mA; Current consumption delay of 0.8 ms, shielded cables
(SM Bus, 5 V DC): 155 mA must be used for the digital inputs
Digital inputs and the sensor supply)
• from load voltage L+ (without load), 130 mA; 130 mA + 6 mA / input used Diagnostics indication LED
max. + any Vs1/Vs2 current used • for status of the inputs Yes
Power loss Standards, approvals, certificates
Power loss, typ. 7W CE mark Yes
Digital inputs cULus Yes
Number of digital inputs 16; 16 (1oo1) or 8 (1oo2); FM approval Yes
Note: You can individually assign
each pair of inputs "a.x" and "b.x" as Highest safety class achievable in
a single (1oo2)-channel or as safety mode
2 separate (1oo1)-channels • SIL acc. to IEC 61508 SIL 2 (single-channel),
horizontal installation SIL 3 (two-channel)
- up to 50 °C, max. 16; 16 inputs at 55 °C horizontal Ambient conditions
vertical installation Free fall
- up to 40 °C, max. 16; 16 inputs at 45 °C vertical • Fall height, max. 0.3 m; five times, in product package
Input voltage Ambient temperature during
operation
• Type of input voltage DC
• min. 0 °C
• for signal "0" -30 V DC to +5 V DC
• max. 55 °C
• for signal "1" 15 V DC to 30 V DC
Mechanics/material
Input current
Enclosure material (front)
• for signal "0", max. (permissible 0.5 mA
quiescent current) • Plastic Yes
Input delay Dimensions
(for rated value of input voltage) Width 70 mm
for standard inputs Height 100 mm
- parameterizable Yes; 0.8 / 1.6 / 3.2 / 6.4 / 12.8 ms Depth 75 mm
Weights
Weight, approx. 250 g
SM 1226 fail-safe digital input 6ES7 226-6BA32-0XB0 STEP 7 Safety Basic V14 SP1
signal module
Task:
16 inputs, 24 V DC Engineering tool for configuring
(SIL 2/category 3/PL d) or fail-safe user programs for
8 inputs 24 V DC SIMATIC S7-1200 FC
(SIL 3/category 3 or Requirement:
category 4/PL e) STEP 7 Basic V14 SP1 and higher
3 or a combination of both
Accessories
Floating license for 1 user;
software and documentation on
6ES7833-1FB14-0YA5
■ Overview
• Digital outputs as a supplement to the integral I/O of the CPUs
• Integrated into the overall automation for the implementation
of safety-related requirements
• With integrated safety functions
• Communication with fail-safe CPUs via PROFIsafe mecha-
3
nisms
• For flexible adaptation of the controller to the corresponding
task
• For subsequent expansion of the system with additional
outputs
• Operable exclusively in the central system
■ Technical specifications
Article number 6ES7226-6DA32-0XB0 Article number 6ES7226-6DA32-0XB0
DIGITAL OUTPUT SM 1226, DIGITAL OUTPUT SM 1226,
F-DQ 4X 24VDC F-DQ 4X 24VDC
General information Standards, approvals, certificates
Product type designation SM 1226 F-DQ 4 x 24 V DC CE mark Yes
Supply voltage cULus Yes
Rated value (DC) FM approval Yes
• 24 V DC Yes Highest safety class achievable in
Input current safety mode
from backplane bus 5 V DC, max. 125 mA • SIL acc. to IEC 61508 SIL 3
Digital outputs Ambient conditions
• from load voltage L+, max. 170 mA Free fall
Power loss • Fall height, max. 0.3 m; five times, in product package
Power loss, typ. 8W Ambient temperature during
operation
Digital outputs
• min. 0 °C
Number of digital outputs 4
• max. 55 °C
• in groups of 1
Mechanics/material
Short-circuit protection Yes
Enclosure material (front)
Switching capacity of the outputs
• Plastic Yes
• with resistive load, max. 30 Hz
Dimensions
• on lamp load, max. 10 Hz
Width 70 mm
Output voltage
Height 100 mm
• Rated value (DC) 24 V
Depth 75 mm
Output current
Weights
• for signal "1" rated value 2A
Weight, approx. 270 g
• for signal "1" permissible range, 10 mA to 2.4 A
max.
• for signal "0" residual current, max. P-switch: 0.5 mA, maximum;
M-switch: 0.5 mA, maximum
Cable length
• shielded, max. 200 m
• unshielded, max. 200 m
Diagnostics indication LED
• for status of the outputs Yes
SM 1226 fail-safe digital output 6ES7226-6DA32-0XB0 STEP 7 Safety Basic V14 SP1
signal module
Task:
4 outputs; 24 V DC, Engineering tool for configuring
current sourcing/sinking fail-safe user programs for
SIMATIC S7-1200 FC
Accessories Requirement:
STEP 7 Basic V14 SP1 and higher
3
Terminal block (spare part)
With 11 screws, tin-coated; 4 units 6ES7292-1AL30-0XA0 Floating license for 1 user; 6ES7833-1FB14-0YA5
software and documentation on
Front flap set (spare part) DVD; license key on USB flash drive
For modules with a width of 70 mm 6ES7291-1BB30-0XA0 Floating license for 1 user; 6ES7833-1FB14-0YH5
software, documentation and
STEP 7 Safety Advanced V14 SP1
license key for download1);
Task: email address required for delivery
Engineering tool for configuring and
programming fail-safe user
programs for SIMATIC S7-1200 FC,
S7-1500F, S7-1500F Software
Controller, S7-300F, S7-400F,
WinAC RTX F, ET 200SP F Controller
and the fail-safe ET 200SP,
ET 200S, ET 200M, ET 200iSP,
ET 200pro and ET 200eco I/O
Requirement:
STEP 7 Professional V14 SP1
Floating license for 1 user, software 6ES7833-1FA14-0YA5
and documentation on DVD; license
key on USB flash drive
Floating license for 1 user, software, 6ES7833-1FA14-0YH5
documentation and license key for
download1);
email address required for delivery
1)
For up-to-date information and download availability, see:
http://www.siemens.com/tia-online-software-delivery
■ Overview
• Relay outputs as a supplement to the integral I/O of the CPUs
• Integrated into the overall automation for the implementation
of safety-related requirements
• With integrated safety functions
• Communication with fail-safe CPUs via PROFIsafe
3
mechanisms
• For flexible adaptation of the controller to the corresponding
task
• For subsequent expansion of the system with additional
outputs
• Operable exclusively in the central system
■ Technical specifications
Article number 6ES7226-6RA32-0XB0 Article number 6ES7226-6RA32-0XB0
DIGITAL OUTPUT SM 1226, DIGITAL OUTPUT SM 1226,
F-DQ 2X RELAY F-DQ 2X RELAY
General information Standards, approvals, certificates
Product type designation SM 1226 F-DQ 2 x Relay CE mark Yes
Supply voltage cULus Yes
Rated value (DC) FM approval Yes
• 24 V DC Yes Highest safety class achievable in
Input current safety mode
from backplane bus 5 V DC, max. 120 mA • SIL acc. to IEC 61508 SIL 3
Digital outputs Ambient conditions
• from load voltage L+, max. 300 mA Free fall
Power loss • Fall height, max. 0.3 m; five times, in product package
Power loss, typ. 10 W Ambient temperature during
operation
Digital outputs
• min. 0 °C
Number of digital outputs 2
• max. 55 °C
Short-circuit protection No
Mechanics/material
Output voltage
Enclosure material (front)
• Rated value (DC) 5 V DC to 30 V DC
• Plastic Yes
• Rated value (AC) 5 V AC to 250 V AC
Dimensions
Output current
Width 70 mm
• for signal "1" permissible range, 5 A maximum per circuit and 10 A
max. maximum of all circuits per module Height 100 mm
Relay outputs Depth 75 mm
• Number of relay outputs 2; 2 circuits per output Weights
Switching capacity of contacts Weight, approx. 300 g
- with inductive load, max. 0.1 Hz, accordance with IEC 60947-
5-1, DC-13; 2 Hz, accordance with
IEC 60947-5-1, AC-15
- with resistive load, max. 2 Hz
Cable length
• shielded, max. 200 m
• unshielded, max. 200 m
Diagnostics indication LED
• for status of the outputs Yes
SM 1226 fail-safe relay output 6ES7226-6RA32-0XB0 STEP 7 Safety Basic V14 SP1
signal module
Task:
2 relay outputs Engineering tool for configuring
fail-safe user programs for
Accessories SIMATIC S7-1200 FC
Terminal block (spare part) Requirement:
STEP 7 Basic V14 SP1 and higher
3 With 11 screws, tin-coated, coded;
4 units
6ES7292-1AL40-0XA0
Floating license for 1 user; software
and documentation on DVD; license
6ES7833-1FB14-0YA5
operation
• min. -25 °C; = Tmin
• max. 55 °C; = Tmax
Extended ambient conditions
• relative to ambient temperature- Tmin ... Tmax at 1080 hPa ... 795 hPa
atmospheric pressure-installation (-1000 m ... +2000 m)
altitude
Relative humidity
- With condensation, tested in 100%; RH incl. condensation/frost
accordance with IEC 60068-2-38, (no commissioning under conden-
max. sation conditions)
• Digital outputs as a supplement to the integral I/O of the CPUs
Resistance
• Integrated into the overall automation for the implementation - against biologically active Yes; Class 3B2 mold, fungus and dry
of safety-related requirements substances / conformity with rot spores (with the exception of
• With integrated safety functions EN 60721-3-3 fauna). The supplied connector
covers must remain on the unused
• Communication with fail-safe CPUs via PROFIsafe interfaces during operation!
mechanisms - against chemically active Yes; Class 3C4 (RH < 75%) incl. salt
• For flexible adaptation of the controller to the corresponding substances / conformity with spray according to EN 60068-2-52
EN 60721-3-3 (degree of severity 3). The supplied
task connector covers must remain on the
• For subsequent expansion of the system with additional unused interfaces during operation!
outputs - against mechanically active Yes; Class 3S4 incl. sand, dust. The
substances / conformity with supplied connector covers must
• Operable exclusively in the central system EN 60721-3-3 remain on the unused interfaces
Note during operation!
■ Overview
In terms of design and functionality, the SIMATIC PM 1207
single-phase load power supply (PM = power module) with
automatic range selection of the input voltage is an optimal
match to the SIMATIC S7-1200 PLC. It provides the supply to
CPUs with 24 V input as well as to signal modules, and to 24 V
loads connected to the modules. Comprehensive certifications,
3
such as UL, ATEX and GL facilitate universal use.
■ Technical specifications
Article number 6EP1332-1SH71 Article number 6EP1332-1SH71
Product S7-1200 PM1207 Product S7-1200 PM1207
Power supply, type 24 V/2.5 A Power supply, type 24 V/2.5 A
Input Output
Input 1-phase AC Output Controlled, isolated DC voltage
Supply voltage Rated voltage Vout DC 24 V
• 1 at AC Rated value 120 V Total tolerance, static ± 3%
• 2 at AC Rated value 230 V Static mains compensation, approx. 0.1%
• Note Automatic range selection Static load balancing, approx. 0.2%
Input voltage Residual ripple peak-peak, max. 150 mV
• 1 at AC 85 ... 132 V Spikes peak-peak, max. 240 mV
• 2 at AC 176 ... 264 V (bandwidth: 20 MHz)
Wide-range input No Product function Output voltage No
adjustable
Overvoltage resistance 2.3 × Vin rated, 1.3 ms
Output voltage setting -
Mains buffering at Iout rated, min. 20 ms; at Vin = 93/187 V
Status display Green LED for 24 V OK
Rated line frequency 1 50 Hz
On/off behavior No overshoot of Vout (soft start)
Rated line frequency 2 60 Hz
Startup delay, max. 6 s; 2 s at 230 V, 6 s at 120 V
Rated line range 47 ... 63 Hz
Voltage rise, typ. 10 ms
Input current
Rated current value Iout rated 2.5 A
• at rated input voltage 120 V 1.2 A
Current range 0 ... 2.5 A
• at rated input voltage 230 V 0.67 A
Supplied active power typical 60 W
Switch-on current limiting (+25 °C), 13 A
max. Short-term overload current
Duration of inrush current limiting at • on short-circuiting during the 6A
25 °C start-up typical
• maximum 3 ms • at short-circuit during operation 6A
typical
I²t, max. 0.5 A²·s
Duration of overloading capability for
Built-in incoming fuse T 3,15 A/250 V (not accessible) excess current
Protection in the mains power input Recommended miniature circuit • on short-circuiting during the 100 ms
(IEC 898) breaker: 16 A characteristic B or start-up
10 A characteristic C
• at short-circuit during operation 100 ms
Parallel switching for enhanced Yes
performance
Numbers of parallel switchable units 2
for enhanced performance
3
Supply harmonics limitation not applicable
Power loss at Vout rated, Iout rated, 12 W Noise immunity EN 61000-6-2
approx.
Operating data
Closed-loop control
Ambient temperature
Dynamic mains compensation 0.3%
(Vin rated ±15%), max. • during operation 0 ... 60 °C
Dynamic load smoothing 3% - Note with natural convection
(Iout: 50/100/50%), Uout ± typ. • during transport -40 ... +85 °C
Load step setting time 50 to 100%, 5 ms • during storage -40 ... +85 °C
typ.
Humidity class according to Climate class 3K3, no condensation
Load step setting time 100 to 50%, 5 ms EN 60721
typ.
Mechanics
Setting time maximum 5 ms
Connection technology screw-type terminals
Protection and monitoring
Connections
Output overvoltage protection < 33 V
• Supply input L, N, PE: 1 screw terminal each for
Current limitation, typ. 2.65 A 0.5 ... 2.5 mm²
Property of the output Short-circuit Yes • Output L+, M: 2 screw terminals each for
proof 0.5 ... 2.5 mm²
Short-circuit protection Constant current characteristic • Auxiliary -
Enduring short circuit current RMS Width of the enclosure 70 mm
value
Height of the enclosure 100 mm
• typical 2.7 A
Depth of the enclosure 75 mm
Overload/short-circuit indicator -
Required spacing
Safety
• top 20 mm
Primary/secondary isolation Yes
• bottom 20 mm
Galvanic isolation Safety extra-low output voltage Uout
acc. to EN 60950-1 and EN 50178 • left 0 mm
Protection class Class I • right 0 mm
Leakage current Weight, approx. 0.3 kg
• maximum 3.5 mA Product feature of the enclosure Yes
housing for side-by-side mounting
CE mark Yes
Installation Snaps onto DIN rail EN 60715
UL/cUL (CSA) approval cULus-Listed (UL 508, CSA C22.2 35x7.5/15, wall mounting
No. 107.1), File E197259;
cURus-Recognized (UL 60950-1, MTBF at 40 °C 1 492 537 h
CSA C22.2 No. 60950-1) Other information Specifications at rated input voltage
File E151273 and ambient temperature +25 °C
Explosion protection ATEX (EX) II 3G Ex nA II T4; (unless otherwise specified)
cULus (ISA 12.12.01, CSA C22.2
No.213) Class I, Div. 2, Group ABCD,
T4, File E330455
FM approval Class I, Div. 2, Group ABCD, T4
CB approval Yes
Marine approval GL, ABS, BV, DNV, LRS, NK
Degree of protection (EN 60529) IP20
■ Overview
• Stabilized power supply for SIPLUS S7-1200
• In the S7-1200 design
• Input 120/230 V AC, output 24 V DC, 2.5 A
(derating: 1.5 A above 60 °C)
Note:
■ Overview
Basic Panels 2nd Generation
SIMATIC HMI Basic Panels 2nd Generation with their fully devel-
oped HMI basic functions are the ideal entry level series for sim-
ple HMI applications.
The device family offers panels with 4", 7", 9" and 12" widescreen
3
displays, as well as combined key and touch operation.
The innovative high-resolution widescreen displays with
64 000 colors are also suitable for upright installation, and they
can be dimmed down to 100%. The innovative operator inter-
face with improved usability opens up a diverse range of options
thanks to new controls and graphics. The new USB interface en-
SIMATIC HMI Basic Panels 2nd Generation ables the connection of keyboard, mouse or barcode scanner,
and supports the simple archiving of data on a USB flash drive
as well as the manual backup and restoring of the complete
panel.
The integrated Ethernet or RS 485/422 interface
(version-specific) enables simple connection to the controller.
■ Overview
Basic Panels 1st Generation
• Ideal entry-level series from 3" to 15" for operating and
monitoring compact machines and systems
• Clear process representation thanks to use of pixel-graphics
displays
3
• Intuitive operation using Touch and tactile function keys
• Equipped with all the necessary basic functions such as alarm
logging, recipe management, plots, vector graphics, and
language switching
• Simple connection to the controller via integral Ethernet
interface or separate version with RS 485/422
• Faster commissioning thanks to integrated diagnostics viewer
and IP setting for SIMATIC S7-1200 and S7-1500 PLCs
■ Overview
SIMATIC HMI Comfort Panels - Standard devices
• Excellent HMI functionality for demanding applications
• Widescreen TFT displays with 4", 7", 9", 12", 15", 19" and
22" diagonals (all 16 million colors) with up to 40% more
visualization area as compared to the predecessor devices
3
• Integrated high-end functionality with archives, scripts,
PDF/Word/Excel viewer, Internet Explorer, Media Player and
Web Server
• Dimmable displays from 0 to 100% via PROFIenergy, via the
HMI project or via a controller
• Modern industrial design, cast aluminum fronts for 7" upwards
• Upright installation for all touch devices
• Optimal selection option: seven touch and five key versions
are available
• Data security in the event of a power failure for the device and
for the SIMATIC HMI Memory Card
Comfort Panel family, KP, TP, KTP • Innovative service and commissioning concept through
second SD card (automatic backup)
• Maximum performance with short screen refresh times
• Suitable for extremely harsh industrial environments thanks to
extended approvals such as ATEX 2/22 and marine approvals
• Wide range of communication options: PROFIBUS and
PROFINET onboard; 2 x PROFINET with integrated switch for
7" models or larger; plus 1 x PROFINET with Gigabit support
for 15" models or larger
• All versions can be used as an OPC UA client or as an
OPC DA server
• Key-operated devices with LED in every function key and new
text input mechanism, similar to the keypads of mobile phones
• All keys have a service life of 2 million operations
• Configuring with the WinCC engineering software of the
TIA Portal
Note:
A 7" and 15" Comfort Outdoor version will be available soon.
For further information, please go to:
http://www.siemens.com/hmi
3
Touch devices SIMATIC HMI memory card 2 GB
10 protective films for touch screen
SIMATIC HMI TP700 Comfort 6AV2124-0GC01-0AX0
devices
Touch-screen operation;
7" widescreen display Starter kit for SIMATIC HMI 6AV2181-4DB20-0AX0
KTP400 Comfort,
SIMATIC HMI TP900 Comfort 6AV2124-0JC01-0AX0 Key and Touch
Touch-screen operation;
9" widescreen display Starter kit for SIMATIC HMI TP700 6AV2181-4GB00-0AX0
Comfort, Touch
SIMATIC HMI TP1200 Comfort 6AV2124-0MC01-0AX0
Starter kit for SIMATIC HMI TP900 6AV2181-4JB00-0AX0
Touch-screen operation;
Comfort, Touch
12" widescreen display
Starter kit for SIMATIC HMI 6AV2181-4MB00-0AX0
SIMATIC HMI TP1500 Comfort 6AV2124-0QC02-0AX0
TP1200 Comfort, Touch
Touch-screen operation;
15" widescreen display Starter kit for SIMATIC HMI 6AV2181-4QB00-0AX0
TP1500 Comfort, Touch
SIMATIC HMI TP1900 Comfort 6AV2124-0UC02-0AX0
Touch-screen operation; Starter kit for SIMATIC HMI 6AV2181-4UB00-0AX0
19" widescreen display TP1900 Comfort, Touch
SIMATIC HMI TP2200 Comfort 6AV2124-0XC02-0AX0 Starter kit for SIMATIC HMI 6AV2181-4XB00-0AX0
TP2200 Comfort, Touch
Touch-screen operation;
22" widescreen display Starter kit for SIMATIC HMI 6AV2181-4DB10-0AX0
KP400 Comfort, Key
Key devices
Starter kit for SIMATIC HMI 6AV2181-4GB10-0AX0
SIMATIC HMI KP400 Comfort 6AV2124-1DC01-0AX0 KP700 Comfort, Key
Key operation;
4" widescreen display Starter kit for SIMATIC HMI 6AV2181-4JB10-0AX0
KP900 Comfort, Key
SIMATIC HMI KP700 Comfort 6AV2124-1GC01-0AX0
Key operation; Starter kit for SIMATIC HMI 6AV2181-4MB10-0AX0
7" widescreen display KP1200 Comfort, Key
SIMATIC HMI KP900 Comfort 6AV2124-1JC01-0AX0 Starter kit for SIMATIC HMI 6AV2181-4QB10-0AX0
KP1500 Comfort, Key
Key operation;
9" widescreen display Accessories See catalog ST 80 / ST PC
or Industry Mall
SIMATIC HMI KP1200 Comfort 6AV2124-1MC01-0AX0
Key operation;
12" widescreen display
SIMATIC HMI KP1500 Comfort 6AV2124-1QC02-0AX0
Key operation;
15" widescreen display
■ Overview
With their fully developed HMI basic functions, 2nd generation
SIPLUS Basic Panels are the ideal entry level series for simple
HMI applications.
The device family offers panels with 4", 7", 9" and 12" displays,
as well as combined key and touch operation.
3
The innovative high-resolution widescreen displays with
64 000 colors are also suitable for upright installation, and they
can be dimmed down to 100%. The innovative operator inter-
face with improved usability opens up a diverse range of options
thanks to new controls and graphics. The new USB interface
enables the connection of keyboard, mouse or barcode scanner,
and supports the simple archiving of data on a USB stick.
The integrated Ethernet or RS 485/422 interface (version-spe-
cific) enables simple connection to the controller.
Note
SIPLUS extreme products are based on SIMATIC standard
products. The contents listed here were taken from the respec-
tive standard products. SIPLUS extreme specific information
was added.
Technical documentation on SIPLUS can be found here:
http://www.siemens.com/siplus-extreme
■ Technical specifications
Article number 6AG1123-2DB03-2AX0 6AG1123-2GB03-2AX0 6AG1123-2GA03-2AX0
Based on 6AV2123-2DB03-0AX0 6AV2123-2GB03-0AX0 6AV2123-2GA03-0AX0
SIPLUS HMI KTP400 BASIC SIPLUS HMI KTP700 BASIC SIPLUS HMI KTP700 BASIC DP
Ambient conditions
Suited for indoor use Yes Yes Yes
Suited for outdoor use No No No
Ambient temperature during
operation
• Operation (vertical installation)
- For vertical installation, min. -20 °C -20 °C -20 °C; = Tmin
- For vertical installation, max. 50 °C 50 °C 50 °C
Extended ambient conditions
• relative to ambient temperature- Tmin ... Tmax at Tmin ... Tmax at Tmin ... Tmax at
atmospheric pressure-installation 1080 hPa ... 795 hPa 1080 hPa ... 795 hPa 1080 hPa ... 795 hPa
altitude (-1000 m ... +2000 m) // (-1000 m ... +2000 m) // (-1000 m ... +2000 m) //
Tmin ... (Tmax - 10K) at Tmin ... (Tmax - 10K) at Tmin ... (Tmax - 10K) at
795 hPa ... 658 hPa 795 hPa ... 658 hPa 795 hPa ... 658 hPa
(+2000 m ... +3500 m) // (+2000 m ... +3500 m) // (+2000 m ... +3500 m) //
Tmin ... (Tmax - 20K) at Tmin ... (Tmax - 20K) at Tmin ... (Tmax - 20K) at
658 hPa ... 540 hPa 658 hPa ... 540 hPa 658 hPa ... 540 hPa
(+3500 m ... +5000 m) (+3500 m ... +5000 m) (+3500 m ... +5000 m)
Relative humidity
- With condensation, tested in 100%; RH incl. condensation/frost 100%; RH incl. condensation/frost 100%; RH incl. condensation/frost
accordance with IEC 60068-2-38, (no commissioning under conden- (no commissioning under conden- (no commissioning when condensation
max. sation conditions) sation conditions) present), vertical mounting position
Resistance
- against biologically active Yes; Class 3B2 mold, fungus and dry Yes; Class 3B2 mold, fungus and dry Yes; Class 3B2 mold, fungus and dry
substances / conformity with rot spores (with the exception of rot spores (with the exception of rot spores (with the exception of
EN 60721-3-3 fauna). The supplied connector covers fauna). The supplied connector covers fauna). The supplied connector covers
must remain on the unused interfaces must remain on the unused interfaces must remain on the unused interfaces
during operation! during operation! during operation!
- against chemically active Yes; Class 3C4 (RH < 75%) incl. salt Yes; Class 3C4 (RH < 75%) incl. salt Yes; Class 3C4 (RH < 75%) incl. salt
substances / conformity with spray according to EN 60068-2-52 spray according to EN 60068-2-52 spray according to EN 60068-2-52
EN 60721-3-3 (degree of severity 3). The supplied (degree of severity 3). The supplied (degree of severity 3). The supplied
connector covers must remain on the connector covers must remain on the connector covers must remain on the
unused interfaces during operation! unused interfaces during operation! unused interfaces during operation!
- against mechanically active Yes; Class 3S4 incl. sand, dust. The Yes; Class 3S4 incl. sand, dust. The Yes; Class 3S4 incl. sand, dust. The
substances / conformity with supplied connector covers must supplied connector covers must supplied connector covers must
EN 60721-3-3 remain on the unused interfaces remain on the unused interfaces remain on the unused interfaces
during operation! during operation! during operation!
3
Suited for outdoor use No No No
Ambient temperature during
operation
• Operation (vertical installation)
- For vertical installation, min. -20 °C -10 °C; = Tmin -10 °C; = Tmin
- For vertical installation, max. 50 °C 50 °C 50 °C
Extended ambient conditions
• relative to ambient temperature- Tmin ... Tmax at Tmin ... Tmax at Tmin ... Tmax at
atmospheric pressure-installation 1080 hPa ... 795 hPa 1080 hPa ... 795 hPa 1080 hPa ... 795 hPa
altitude (-1000 m ... +2000 m) // (-1000 m ... +2000 m) // (-1000 m ... +2000 m) //
Tmin ... (Tmax - 10K) at Tmin ... (Tmax - 10K) at Tmin ... (Tmax - 10K) at
795 hPa ... 658 hPa 795 hPa ... 658 hPa 795 hPa ... 658 hPa
(+2000 m ... +3500 m) // (+2000 m ... +3500 m) // (+2000 m ... +3500 m) //
Tmin ... (Tmax - 20K) at Tmin ... (Tmax - 20K) at Tmin ... (Tmax - 20K) at
658 hPa ... 540 hPa 658 hPa ... 540 hPa 658 hPa ... 540 hPa
(+3500 m ... +5000 m) (+3500 m ... +5000 m) (+3500 m ... +5000 m)
Relative humidity
- With condensation, tested in 100%; RH incl. condensation/frost 100%; RH incl. condensation / frost (no 100%; RH incl. condensation/frost
accordance with IEC 60068-2-38, (no commissioning under conden- commissioning in bedewed state), (no commissioning when condensation
max. sation conditions) horizontal installation present), vertical mounting position
Resistance
- against biologically active Yes; Class 3B2 mold, fungus and dry Yes; Class 3B2 mold, fungus and dry Yes; Class 3B2 mold, fungus and dry
substances / conformity with rot spores (with the exception of rot spores (with the exception of rot spores (with the exception of
EN 60721-3-3 fauna). The supplied connector covers fauna). The supplied connector covers fauna). The supplied connector covers
must remain on the unused interfaces must remain on the unused interfaces must remain on the unused interfaces
during operation! during operation! during operation!
- against chemically active Yes; Class 3C4 (RH < 75%) incl. salt Yes; Class 3C4 (RH < 75%) incl. salt Yes; Class 3C4 (RH < 75%) incl. salt
substances / conformity with spray according to EN 60068-2-52 spray according to EN 60068-2-52 spray according to EN 60068-2-52
EN 60721-3-3 (degree of severity 3). The supplied (degree of severity 3). The supplied (degree of severity 3). The supplied
connector covers must remain on the connector covers must remain on the connector covers must remain on the
unused interfaces during operation! unused interfaces during operation! unused interfaces during operation!
- against mechanically active Yes; Class 3S4 incl. sand, dust. The Yes; Class 3S4 incl. sand, dust. The Yes; Class 3S4 incl. sand, dust. The
substances / conformity with supplied connector covers must supplied connector covers must supplied connector covers must
EN 60721-3-3 remain on the unused interfaces remain on the unused interfaces remain on the unused interfaces
during operation! during operation! during operation!
■ Overview
• Ideal entry-level series of 3.8 inches to 15 inches for operating
and monitoring compact machines and systems
• Clear process representation through the use of full-graphic
displays
• Intuitive operation via touch and tactile function keys
3
• Equipped with all the necessary basic functions such as
reporting, recipe management, curve representation, vector
graphics, and language selection
• Easy connection to the controller via integrated Ethernet
interface or a separate version with RS 485/422
Note:
SIPLUS extreme products are based on SIMATIC standard
products. The contents listed here were taken from the respec-
tive standard products. SIPLUS extreme specific information
was added.
Technical documentation on SIPLUS can be found here:
http://www.siemens.com/siplus-extreme
■ Technical specifications
Article number 6AG1647-0AH11-2AX0 6AG1647-0AA11-2AX0 6AG1647-0AD11-2AX0
Based on 6AV6647-0AH11-3AX0 6AV6647-0AA11-3AX0 6AV6647-0AD11-3AX0
SIPLUS HMI KP300 BASIC MONO PN SIPLUS KTP400 BASIC MONO PN 3,8" SIPLUS KTP600 BASIC COLOR PN
3,6"
Ambient conditions
Suited for indoor use Yes Yes Yes
Suited for outdoor use No No No
Ambient temperature during
operation
• Operation (vertical installation)
- For vertical installation, min. -25 °C -10 °C -25 °C
- For vertical installation, max. 60 °C 60 °C 60 °C
Extended ambient conditions
• relative to ambient temperature- Tmin ... Tmax at Tmin ... Tmax at Tmin ... Tmax at
atmospheric pressure-installation 1080 hPa ... 795 hPa 1080 hPa ... 795 hPa 1080 hPa ... 795 hPa
altitude (-1000 m ... +2000 m) // (-1000 m ... +2000 m) // (-1000 m ... +2000 m) //
Tmin ... (Tmax - 10K) at Tmin ... (Tmax - 10K) at Tmin ... (Tmax - 10K) at
795 hPa ... 658 hPa 795 hPa ... 658 hPa 795 hPa ... 658 hPa
(+2000 m ... +3500 m) // (+2000 m ... +3500 m) // (+2000 m ... +3500 m) //
Tmin ... (Tmax - 20K) at Tmin ... (Tmax - 20K) at Tmin ... (Tmax - 20K) at
658 hPa ... 540 hPa 658 hPa ... 540 hPa 658 hPa ... 540 hPa
(+3500 m ... +5000 m) (+3500 m ... +5000 m) (+3500 m ... +5000 m)
Relative humidity
- With condensation, tested in 100%; RH incl. condensation/frost 100%; RH incl. condensation/frost 100%; RH incl. condensation/frost
accordance with IEC 60068-2-38, (no commissioning under conden- (no commissioning under conden- (no commissioning under conden-
max. sation conditions) sation conditions) sation conditions)
Resistance
- against biologically active Yes; Class 3B2 mold, fungus and dry Yes; Class 3B2 mold, fungus and dry Yes; Class 3B2 mold, fungus and dry
substances / conformity with rot spores (with the exception of rot spores (with the exception of rot spores (with the exception of
EN 60721-3-3 fauna). The supplied connector covers fauna). The supplied connector covers fauna). The supplied connector covers
must remain on the unused interfaces must remain on the unused interfaces must remain on the unused interfaces
during operation! during operation! during operation!
- against chemically active Yes; Class 3C4 (RH < 75%) incl. salt Yes; Class 3C4 (RH < 75%) incl. salt Yes; Class 3C4 (RH < 75%) incl. salt
substances / conformity with spray according to EN 60068-2-52 spray according to EN 60068-2-52 spray according to EN 60068-2-52
EN 60721-3-3 (degree of severity 3). The supplied (degree of severity 3). The supplied (degree of severity 3). The supplied
connector covers must remain on the connector covers must remain on the connector covers must remain on the
unused interfaces during operation! unused interfaces during operation! unused interfaces during operation!
- against mechanically active Yes; Class 3S4 incl. sand, dust. The Yes; Class 3S4 incl. sand, dust. The Yes; Class 3S4 incl. sand, dust. The
substances / conformity with supplied connector covers must supplied connector covers must supplied connector covers must
EN 60721-3-3 remain on the unused interfaces remain on the unused interfaces remain on the unused interfaces
during operation! during operation! during operation!
SIPLUS HMI KP300 Basic 6AG1647-0AH11-2AX0 SIPLUS HMI KTP1000 Basic 6AG1647-0AE11-4AX0
mono PN color DP
For areas with extreme medial For areas with extreme medial
exposure (conformal coating); exposure (conformal coating);
ambient temperature ambient temperature 0 ... +50 °C
-25 ... +60 °C
SIPLUS HMI KTP1000 Basic 6AG1647-0AF11-4AX0
SIPLUS HMI KTP400 Basic 6AG1647-0AA11-2AX0 color PN
mono PN
For areas with extreme medial
For areas with extreme medial exposure (conformal coating);
exposure (conformal coating); ambient temperature 0 ... +50 °C
ambient temperature
-10 ... +60 °C SIPLUS HMI TP1500 Basic 6AG1647-0AG11-4AX0
color PN
SIPLUS HMI KTP600 Basic 6AG1647-0AD11-2AX0
color PN For areas with extreme medial
exposure (conformal coating);
For areas with extreme medial ambient temperature 0 ... +50 °C
exposure (conformal coating);
ambient temperature Accessories See catalog ST 80 / ST PC
-25 ... +60 °C or Industry Mall
■ Overview
• Easy project transfer via standard cable (standard Ethernet
cable, standard USB cable)
• Maximum performance with short screen refresh times
• Suitable for extremely harsh industrial environments thanks to
extended approvals such as ATEX 2/22
3
• Wide range of communication options: PROFIBUS and
PROFINET onboard; 2x PROFINET with integrated switch for
7" models or larger; plus 1 additional PROFINET with Gigabit
support for 15" models or larger
• All variants can be used as an OPC UA client or as an OPC DA
server
• Key-operated devices with LED in every function key and new
text input mechanism, similar to the keypads of mobile phones
• Key-operated devices with stamped keys for optimum tactile
feedback
• All keys have a service life of 2 million operations
• Configuring with the WinCC engineering software of the
• Excellent HMI functionality for demanding applications TIA Portal
• Widescreen TFT displays with 4", 7", 9", 12", 15", 19" and Note:
22" diagonals (all 16 million colors) with up to 40% more SIPLUS extreme products are based on SIMATIC standard
visualization area as compared to the predecessor devices products. The contents listed here were taken from the respec-
• Integrated high-end functionality with archives, scripts, tive standard products. SIPLUS extreme-specific information
PDF/Word/Excel viewer, Internet Explorer, Media Player was added.
• Dimmable displays from 0 to 100% via PROFIenergy, via the
HMI project or via a controller
• Modern industrial design, cast aluminum fronts for 7" upwards
• Upright installation for all touch devices
• Optimal selection option: seven touch and five key versions
are available
• Data security in the event of a power failure for the device and
for the SIMATIC HMI Memory Card
• Innovative service and commissioning concept through
second SD card (automatic backup)
■ Technical specifications
Article number 6AG1124-2DC01-4AX0 6AG1124-0GC01-4AX0 6AG1124-0JC01-4AX0 6AG1124-0MC01-4AX0
Based on 6AV2124-2DC01-0AX0 6AV2124-0GC01-0AX0 6AV2124-0JC01-0AX0 6AV2124-0MC01-0AX0
SIPLUS HMI KTP400 SIPLUS HMI TP700 SIPLUS HMI TP900 SIPLUS HMI TP1200
COMFORT COMFORT COMFORT COMFORT
Ambient conditions
Suited for indoor use Yes Yes Yes Yes
Suited for outdoor use
Ambient temperature during
No No No No 3
operation
• Operation (vertical installation)
- For vertical installation, min. 0 °C; = Tmin 0 °C; = Tmin 0 °C; = Tmin 0 °C; = Tmin
- For vertical installation, max. 50 °C; = Tmax 50 °C; = Tmax 50 °C; = Tmax 50 °C; = Tmax
Extended ambient conditions
• relative to ambient temperature- Tmin ... Tmax at Tmin ... Tmax at Tmin ... Tmax at Tmin ... Tmax at
atmospheric pressure-installation 1080 hPa ... 795 hPa 1080 hPa ... 795 hPa 1080 hPa ... 795 hPa 1080 hPa ... 795 hPa
altitude (-1000 m ... +2000 m) // (-1000 m ... +2000 m) // (-1000 m ... +2000 m) // (-1000 m ... +2000 m) //
Tmin ... (Tmax - 10K) at Tmin ... (Tmax - 10K) at Tmin ... (Tmax - 10K) at Tmin ... (Tmax - 10K) at
795 hPa ... 658 hPa 795 hPa ... 658 hPa 795 hPa ... 658 hPa 795 hPa ... 658 hPa
(+2000 m ... +3500 m) // (+2000 m ... +3500 m) // (+2000 m ... +3500 m) // (+2000 m ... +3500 m) //
Tmin ... (Tmax - 20K) at Tmin ... (Tmax - 20K) at Tmin ... (Tmax - 20K) at Tmin ... (Tmax - 20K) at
658 hPa ... 540 hPa 658 hPa ... 540 hPa 658 hPa ... 540 hPa 658 hPa ... 540 hPa
(+3500 m ... +5000 m) (+3500 m ... +5000 m) (+3500 m ... +5000 m) (+3500 m ... +5000 m)
Relative humidity
- With condensation, tested in 100%; RH incl. conden- 100%; RH incl. conden- 100%; RH incl. conden- 100%; RH incl. conden-
accordance with IEC 60068-2-38, sation/frost (no commis- sation/frost (no commis- sation/frost (no commis- sation/frost (no commis-
max. sioning under condensation sioning under condensation sioning under condensation sioning under condensation
conditions) conditions) conditions) conditions)
Resistance
- against biologically active Yes; Class 3B2 mold, fungus Yes; Class 3B2 mold, fungus Yes; Class 3B2 mold, fungus Yes; Class 3B2 mold, fungus
substances / conformity with and dry rot spores (with the and dry rot spores (with the and dry rot spores (with the and dry rot spores (with the
EN 60721-3-3 exception of fauna). The exception of fauna). The exception of fauna). The exception of fauna). The
supplied connector covers supplied connector covers supplied connector covers supplied connector covers
must remain on the unused must remain on the unused must remain on the unused must remain on the unused
interfaces during operation! interfaces during operation! interfaces during operation! interfaces during operation!
- against chemically active Yes; Class 3C4 (RH < 75%) Yes; Class 3C4 (RH < 75%) Yes; Class 3C4 (RH < 75%) Yes; Class 3C4 (RH < 75%)
substances / conformity with incl. salt spray according to incl. salt spray according to incl. salt spray according to incl. salt spray according to
EN 60721-3-3 EN 60068-2-52 (degree of EN 60068-2-52 (degree of EN 60068-2-52 (degree of EN 60068-2-52 (degree of
severity 3). The supplied severity 3). The supplied severity 3). The supplied severity 3). The supplied
connector covers must connector covers must connector covers must connector covers must
remain on the unused inter- remain on the unused inter- remain on the unused inter- remain on the unused inter-
faces during operation! faces during operation! faces during operation! faces during operation!
- against mechanically active Yes; Class 3S4 incl. sand, Yes; Class 3S4 incl. sand, Yes; Class 3S4 incl. sand, Yes; Class 3S4 incl. sand,
substances / conformity with dust. The supplied dust. The supplied dust. The supplied dust. The supplied
EN 60721-3-3 connector covers must connector covers must connector covers must connector covers must
remain on the unused inter- remain on the unused inter- remain on the unused inter- remain on the unused inter-
faces during operation! faces during operation! faces during operation! faces during operation!
3
Ambient conditions
Suited for indoor use Yes Yes Yes Yes Yes
Suited for outdoor use No No No No No
Ambient temperature during
operation
• Operation (vertical installation)
- For vertical installation, min. 0 °C; = Tmin 0 °C; = Tmin 0 °C; = Tmin 0 °C; = Tmin 0 °C; = Tmin
- For vertical installation, max. 50 °C; = Tmax 50 °C; = Tmax 50 °C; = Tmax 50 °C; = Tmax 50 °C; = Tmax
Extended ambient conditions
• relative to ambient temperature- Tmin ... Tmax at Tmin ... Tmax at Tmin ... Tmax at Tmin ... Tmax at Tmin ... Tmax at
atmospheric pressure-installation 1080 hPa ... 795 hPa 1080 hPa ... 795 hPa 1080 hPa ... 795 hPa 1080 hPa ... 795 hPa 1080 hPa ... 795 hPa
altitude (-1000 m ... +2000 m) (-1000 m ... +2000 m) (-1000 m ... +2000 m) (-1000 m ... +2000 m) (-1000 m ... +2000 m)
// // // // //
Tmin ... (Tmax - 10K) Tmin ... (Tmax - 10K) Tmin ... (Tmax - 10K) Tmin ... (Tmax - 10K) Tmin ... (Tmax - 10K)
at 795 hPa ... 658 hPa at 795 hPa ... 658 hPa at 795 hPa ... 658 hPa at 795 hPa ... 658 hPa at 795 hPa ... 658 hPa
(+2000 m ... +3500 m) (+2000 m ... +3500 m) (+2000 m ... +3500 m) (+2000 m ... +3500 m) (+2000 m ... +3500 m)
// // // // //
Tmin ... (Tmax - 20K) Tmin ... (Tmax - 20K) Tmin ... (Tmax - 20K) Tmin ... (Tmax - 20K) Tmin ... (Tmax - 20K)
at 658 hPa ... 540 hPa at 658 hPa ... 540 hPa at 658 hPa ... 540 hPa at 658 hPa ... 540 hPa at 658 hPa ... 540 hPa
(+3500 m ... +5000 m) (+3500 m ... +5000 m) (+3500 m ... +5000 m) (+3500 m ... +5000 m) (+3500 m ... +5000 m)
Relative humidity
- With condensation, tested in 100%; RH incl. 100%; RH incl. 100%; RH incl. 100%; RH incl. 100%; RH incl.
accordance with IEC 60068-2-38, condensation/frost condensation/frost condensation/frost condensation/frost condensation/frost
max. (no commissioning (no commissioning (no commissioning (no commissioning (no commissioning
under condensation under condensation under condensation under condensation under condensation
conditions) conditions) conditions) conditions) conditions)
Resistance
- against biologically active Yes; Class 3B2 mold, Yes; Class 3B2 mold, Yes; Class 3B2 mold, Yes; Class 3B2 mold, Yes; Class 3B2 mold,
substances / conformity with fungus and dry rot fungus and dry rot fungus and dry rot fungus and dry rot fungus and dry rot
EN 60721-3-3 spores (with the spores (with the spores (with the spores (with the spores (with the
exception of fauna). exception of fauna). exception of fauna). exception of fauna). exception of fauna).
The supplied The supplied The supplied The supplied The supplied
connector covers must connector covers must connector covers must connector covers must connector covers must
remain on the unused remain on the unused remain on the unused remain on the unused remain on the unused
interfaces during interfaces during interfaces during interfaces during interfaces during
operation! operation! operation! operation! operation!
- against chemically active Yes; Class 3C4 (RH < Yes; Class 3C4 (RH < Yes; Class 3C4 (RH < Yes; Class 3C4 (RH < Yes; Class 3C4 (RH <
substances / conformity with 75%) incl. salt spray 75%) incl. salt spray 75%) incl. salt spray 75%) incl. salt spray 75%) incl. salt spray
EN 60721-3-3 according to according to according to according to according to
EN 60068-2-52 EN 60068-2-52 EN 60068-2-52 EN 60068-2-52 EN 60068-2-52
(degree of severity 3). (degree of severity 3). (degree of severity 3). (degree of severity 3). (degree of severity 3).
The supplied The supplied The supplied The supplied The supplied
connector covers must connector covers must connector covers must connector covers must connector covers must
remain on the unused remain on the unused remain on the unused remain on the unused remain on the unused
interfaces during interfaces during interfaces during interfaces during interfaces during
operation! operation! operation! operation! operation!
- against mechanically active Yes; Class 3S4 incl. Yes; Class 3S4 incl. Yes; Class 3S4 incl. Yes; Class 3S4 incl. Yes; Class 3S4 incl.
substances / conformity with sand, dust. The sand, dust. The sand, dust. The sand, dust. The sand, dust. The
EN 60721-3-3 supplied connector supplied connector supplied connector supplied connector supplied connector
covers must remain on covers must remain on covers must remain on covers must remain on covers must remain on
the unused interfaces the unused interfaces the unused interfaces the unused interfaces the unused interfaces
during operation! during operation! during operation! during operation! during operation!
3
Suited for outdoor use No No No
Ambient temperature during
operation
• Operation (vertical installation)
- For vertical installation, min. 0 °C; = Tmin 0 °C; = Tmin 0 °C; = Tmin
- For vertical installation, max. 50 °C; = Tmax 45 °C; = Tmax 45 °C; = Tmax
Extended ambient conditions
• relative to ambient temperature- Tmin ... Tmax at Tmin ... Tmax at Tmin ... Tmax at
atmospheric pressure-installation 1080 hPa ... 795 hPa 1080 hPa ... 795 hPa 1080 hPa ... 795 hPa
altitude (-1000 m ... +2000 m) // (-1000 m ... +2000 m) // (-1000 m ... +2000 m) //
Tmin ... (Tmax - 10K) at Tmin ... (Tmax - 10K) at Tmin ... (Tmax - 10K) at
795 hPa ... 658 hPa 795 hPa ... 658 hPa 795 hPa ... 658 hPa
(+2000 m ... +3500 m) // (+2000 m ... +3500 m) // (+2000 m ... +3500 m) //
Tmin ... (Tmax - 20K) at Tmin ... (Tmax - 20K) at Tmin ... (Tmax - 20K) at
658 hPa ... 540 hPa 658 hPa ... 540 hPa 658 hPa ... 540 hPa
(+3500 m ... +5000 m) (+3500 m ... +5000 m) (+3500 m ... +5000 m)
Relative humidity
- With condensation, tested in 100%; RH incl. condensation/frost 100%; RH incl. condensation/frost 100%; RH incl. condensation/frost
accordance with IEC 60068-2-38, (no commissioning under conden- (no commissioning under conden- (no commissioning under conden-
max. sation conditions) sation conditions) sation conditions)
Resistance
- against biologically active Yes; Class 3B2 mold, fungus and dry Yes; Class 3B2 mold, fungus and dry Yes; Class 3B2 mold, fungus and dry
substances / conformity with rot spores (with the exception of rot spores (with the exception of rot spores (with the exception of
EN 60721-3-3 fauna). The supplied connector covers fauna). The supplied connector covers fauna). The supplied connector covers
must remain on the unused interfaces must remain on the unused interfaces must remain on the unused interfaces
during operation! during operation! during operation!
- against chemically active Yes; Class 3C4 (RH < 75%) incl. salt Yes; Class 3C4 (RH < 75%) incl. salt Yes; Class 3C4 (RH < 75%) incl. salt
substances / conformity with spray according to EN 60068-2-52 spray according to EN 60068-2-52 spray according to EN 60068-2-52
EN 60721-3-3 (degree of severity 3). The supplied (degree of severity 3). The supplied (degree of severity 3). The supplied
connector covers must remain on the connector covers must remain on the connector covers must remain on the
unused interfaces during operation! unused interfaces during operation! unused interfaces during operation!
- against mechanically active Yes; Class 3S4 incl. sand, dust. The Yes; Class 3S4 incl. sand, dust. The Yes; Class 3S4 incl. sand, dust. The
substances / conformity with supplied connector covers must supplied connector covers must supplied connector covers must
EN 60721-3-3 remain on the unused interfaces remain on the unused interfaces remain on the unused interfaces
during operation! during operation! during operation!
3
• Connection of up to 3 modules per CPU
• 3 LEDs for module, network and I/O status diagnostics
• Possible integration of the module into the hardware catalog
of the TIA Portal configuration suite
• Supports Transparent CAN 2.0A for processing customer-
specific protocols
• CANopen implementation according to communication
profiles CiA 301 Rev. 4.2 and CiA 302 Rev. 4.1 (master)
■ More information
The CANopen bus can be configured via any commercially
Note available CANopen configuration tool. The HMS company also
supplies suitable "CM CANopen Configuration Studio" software
The CM CANopen module is an HMS product and can only be with the product. The configuration is saved directly on the mod-
obtained through HMS. ule by means of a USB connection. Routing via PROFIBUS/
The following description contains information on supplemen- PROFINET is not possible.
tary products that are manufactured and marketed, not by Preprogrammed function blocks are available for easier
Siemens, but by third-parties outside the Siemens group PLC programming in the TIA Portal.
("external companies"). These external companies organize the
manufacture, sale and delivery of their products independently. For further information, please contact HMS directly:
Their own terms and conditions of business and delivery apply. http://www.hms-networks.com/can-for-s7-1200
Responsibility for these supplementary products and for the
associated information presented here rests exclusively with the Ordering and Support
respective external company. Unless compulsory by law, Please note that ordering and support for the module are exclu-
Siemens assumes no liability and makes no guarantee for sively carried out via HMS. Please contact HMS directly should
supplemental products of external companies. Please refer also you have any questions concerning this module. The relevant
to the note on "Exemption from liability/Use of hyperlinks" contact details can be found on the Internet at
(see "More information").
http://www.hms-networks.com/can-for-s7-1200
Overview
Exemption from liability/Use of hyperlinks
An interface module is available for operating the S7-1200 on
CANopen. It can be used together with system and Siemens has prepared this description with great care. It is not
IO components of the S7-1200 automation system. possible, however, for Siemens to verify that the data supplied
by external companies is complete, correct or up to date. The
CiA and CANopen are registered Community Trademarks of possibility that individual items of information might be incorrect,
CAN in Automation e.V. incomplete, or not up-to-date cannot therefore be ruled out.
Unless compulsory by law, Siemens accepts no liability for the
■ Application usability of the data or of the product for the user per se.
CANopen is a widely used industrial bus system and can be This article contains third-party Web addresses. Siemens is not
used for a variety of different applications. The module allows responsible for the contents of these Web sites, nor does
simple and cost-effective connection of CANopen applications Siemens adopt these Web sites and their contents, as Siemens
to SIMATIC. does not control the presented information and cannot be held
responsible for the content and information they contain. You
• Control of hydraulic valves/axes in vehicles therefore use these links at your own risk.
• Control of motors in packaging machines or conveyors
• Capturing of angular encoder positions in wind turbines
• Capturing of control devices on machines, e.g. joysticks
• Capturing the measured data of path encoders, inclinometers
or angular encoders, e.g. for tower cranes and gantry cranes