7XV5664 /7XV5654 GPS/DCF77 Time Synchronization System: Function Overview
7XV5664 /7XV5654 GPS/DCF77 Time Synchronization System: Function Overview
7XV5664 /7XV5654 GPS/DCF77 Time Synchronization System: Function Overview
7XV5664 /7XV5654
GPS/DCF77 Time Synchronization System
Function overview
LSP2410-afp.tif
• An optical output with ST connector is
provided for potential and interference-
free direct transmission of DCF77 or
IRIG-B time synchronization telegrams
to the SIPROTEC 4 units. There they
are converted to an electrical signal by a
7XV5654-0BA00 time synchronization
unit and injected via the time synchro-
nization interface of the SIPROTEC 4
LSP2508.eps
units (Port A) (see Fig. 15/52).
• On a second optical output, a high-
precision minute or second pulse can be
7XV5664 time 7XV5654 time issued with microsecond accuracy.
signal receiver synchronization unit • With this minute pulse, the SIPROTEC 4
(sync.-transceiver) unit internal clock can be synchronized
Fig. 15/51 via a binary input. The opto-electrical
GPS/DFC77
converter 7XV5654-0BA00 supports
time synchronization system
this process.
• A special application of the pulse-per-
Description second function is the highly accurate
synchronization of 7SD52 differential
The 7XV5664 GPS/DCF77 time signal re-
protection unit versions that feature the
ceiver (TSR) is part of the time synchroni-
zation system for all SIPROTEC 4 units. It GPS synchronization function. This fa-
is equipped with an antenna and a 25-m cilitates the exact detection of the trans-
screened cable. The other devices of the fer time of telegrams between the units
time synchronization system are the in both the transmit (send) and the
7XV5450 mini star-coupler (optional) and receive direction.
the 7XV5654-0BA00 time synchronization
• The receiver requires 24 V DC power
unit (sync.-transceiver).
A user-friendly software package for PC
supply. Other auxiliary voltages may be
(included in the scope of delivery) facili- converted to 24 V DC by the DC/DC
tates configuration of the receiver via an converter 7XV5810-0BA00.
RS232 interface.
The optical outputs provide interference-
free transmission of the time signals to the
relays. Close to the relays, the sync.-trans-
ceiver 7XV5654 converts these optical sig-
nals to electrical signals. These signals are
input signals for Port A of SIPROTEC 4
units or for binary inputs, which can also
be used for time synchronization.
15
Application