Design wind force on chimneys, tanks & similar structures classified as rigid structure
;;;;;
Velocity pressure at height z of centroid of area A f; qz= 43.67 psf ;
Gust effect factor, net force coefficient, design wind force
h_upon_D = h / D = 2.7;
Table = "ASCE (7-02) Figure 6-19";
From ASCE (7-02) Figure 6-19;
Dimensional ratio; h_upon_D = 2.67;
Gust effect factor; G = 0.85;
Sect. 6.5.8.
Net force coefficient; Cf = 0.73;
Figure. 6-19;
Design wind force; F = max(10 psf, q zGCf)Af = 5510.43 lb;
Eq. 6-25;
Note: Per Section 6.1.4.1 the design wind force for structures shall be not less than 10psf multiplied
Project Job Ref.
by the area of the structure projected onto a vertical plane normal to the wind direction
Library item - F-Other Rigid Structures(T6-19)