Energia Incidente

You might also like

Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 5

D,4,7

0.377 12.5
Ibf (KA) 50 Ibf 50
1.36 428

j/cm2 20.21 mm 1053


Cal/cm2 4.83 Pulgadas 41.46
G X
Ia (4,2)
k -0.097
Ibf (KA) 25
v 0.48

1.15667191
Ia 14.344
4.3
k1 -0.555
k2 -0.113
G 25

0.60986233
En j/cm2 4.0725116

4,3c d
cf 1.5 1 superiores a 1 kV
t 0.05 1,5 menores que 1 kV
x 1.641
d 455 18

j/cm2 10.34
Cal/cm2 2.47
Cal/cm2 2.926
4,5b
Eb 5.00 1.20

Db mm 708.33
Pulgadas 27.89
Pulgadas 31.50

0.00980763 https://www.easypower.com/resources/arc-flash-calcul
m/resources/arc-flash-calculator#afc-results
Typical Flash Protection Boundaries for 3-Phase, 480-volt systems
(Arc-in-Box)

Clearing Calculated Flash Arc Incident Energy


3-Phase Bolted Time Protection Boundary (inches) cal/cm2 at 18 Inches
Fault Current (kA) (sec) Arc in a Box Arc in a Box
0.05 52 6.63
50 0.10 81 13.26
0.20 125 26.52
0.05 51 6.44
48 0.10 79 12.89
0.20 122 25.77
0.05 50 6.25
46 0.10 78 12.50
0.20 120 25.00
0.05 49 6.05
44 0.10 76 12.10
0.20 118 24.20
0.05 48 5.84
42 0.10 75 11.69
0.20 115 23.37
0.05 47 5.63
40 0.10 73 11.26
0.20 113 22.52
0.05 46 5.41
38 0.10 71 10.82
0.20 110 21.64
0.05 45 5.18
36 0.10 69 10.37
0.20 107 20.74
0.05 44 4.95
34 0.10 67 9.90
0.20 104 19.81
0.05 42 4.71
32

1.0/sp00e230.xls (5/07)
32 0.10 65 9.43
0.20 101 18.85
0.05 41 4.47
30 0.10 63 8.94
0.20 97 17.87
0.05 39 4.22
28 0.10 61 8.43
0.20 94 16.86
0.05 38 3.96
26 0.10 59 7.91
0.20 90 15.83
0.05 36 3.69
24 0.10 56 7.38
0.20 86 14.77
0.05 35 3.42
22 0.10 53 6.84
0.20 82 13.68
0.05 33 3.14
20 0.10 51 6.28
0.20 78 12.57
0.05 31 2.86
18 0.10 48 5.71
0.20 74 11.43
0.05 29 2.57
16 0.10 45 5.13
0.20 69 10.26
0.05 27 2.27
14 0.10 41 4.54
0.20 64 9.07
0.05 24 1.96
12 0.10 38 3.93
0.20 58 7.85

1.0/sp00e230.xls (5/07)
0.05 22 1.65
10 0.10 34 3.30
0.20 52 6.61
0.05 19 1.33
8 0.10 30 2.67
0.20 46 5.34
0.05 16 1.01
6 0.10 25 2.02
0.20 38 4.04
0.05 13 0.68
4 0.10 19 1.36
0.20 30 2.72

1.0/sp00e230.xls (5/07)