1 - HCPA-Data Center Facility - HUAWEI UPS Training For UPS2000-A&G-1

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 42

Huawei Introduction to UPS2000 Series Products in 2020

1. Overview of Huawei UPS

2. UPS2000 Features
Introduction

3.UPS2000-G li-ion solution

3. Successful Cases
Huawei UPS Solutions(For 2020 years)

Large

Medium FusionPower (1200/1600 kVA)


UPS5000-A UPS5000-E/S
(30-120 kVA)
(400/500/600 kVA) (50 kVA to 800 kVA)

New UPS2000-G Li-ion Solution


Small

Li-ion battery
50/100AH / pcs
UPS2000-A/G UPS2000-G-6K
UPS2000-G-3K
(1 kVA to 20 kVA) UPS2000-G-1K

UPS type R/T model Tower model Modular model Modular model
UPS Family Tree- UPS2000-A/G(For 2020 years)

UPS2000-A/G series is on-line UPS

15-20KVA R/T

6-10KV T typ 6-10KVA R/T

1-3KV T 1-3KVA R/T

Tower UPS2000-A Tower and Rack UPS2000-G


UPS20000-A-6-10kVA can only be sold until 20200930, Other capacities are not affected,including UPS2000-G
1. Overview of Huawei UPS

2. UPS2000 Features
Introduction

3.UPS2000-G li-ion solution

3. Successful Cases
Reliable Efficient Simple

High Adaptability to Extend 50% of Battery Life


Wide input voltage and frequency range
UPS2000-A
• 1/2/3kVA Input voltage range: 110V to 300V
Online double
• 6/10kVA Input voltage range: 80V to 280V conversion, the
wide input voltage
UPS2000-G
• Input voltage range: 80V to 280V
range
• Input frequency range: 40 Hz to 70 Hz
• Supports DG adaptability
Minimizes battery use to extend battery
lifespan. Common Power Problems

80V AC input 280V AC input Spike wave input Serious distortion wave input
Reliable Efficient Simple

High Overload & Adaptability to Ensure Supply Quality


High Overload Capacity
 125% overload for 5 minutes(6kVA-
20kVA)
150%
 150% overload for 1 minute (6kVA-
Overload
20kVA)
Reduces transfer times to bypass
mode, ensuring customer equipment
power supply quality. Electrical load with constant changes

Various Loads

• Output power factor: 0.9


server TV
• Capacitive/inductive loads from lead
0.5 to lag 0.5 Supports
• High output load capacity ensuring various load
expansion demands in future
ATM compressor
Reliable Efficient Simple

Airborne Hygroscopic Dust Test for Higher Reliability

Strengthen measures
Conformal coating

High humidity
Enhance environmental
adaptability

Sulfide dust

Hainan open field

14 days
Reliable Efficient Simple

The Highest Efficiency Up to 96%


High efficiency,saving OPEX Energy star certification

efficiency 10kVA efficiency test curve

Load rate

UPS2000-G:
• System efficiency: 6kVA: 94%
10kVA: 94.5% Batch 1 Energy Star certification:
15kVA/20kVA: up to 95%
• High efficiency up to 98% in ECO mode First in the UPS field worldwide
UPS2000-A
• System efficiency: 1kVA: 88%
2kVA: 89%
3kVA: 90%
6/10kVA: up to 96%
Reliable Efficient Simple

Flexible Backup Time Solutions (UPS2000-A)


Built-in battery External charger

The corresponding gear of the charging current


• Super small volume, more suitable for
office,bank branches and so on 0 1 2 3 4 5 6 7 8 9
• Output interface is IEC socket , easy to 36V charger 1A 3A 6A 9A 12A 15A

use 72V charger 1A 2A 4A 6A 8A 10A 12A

96V charger 1A 2A 4A 6A 8A 10A


Reliable Efficient Simple

Various Installations for Multiple Scenarios (UPS2000-G)


Rack or Tower Friendly Interactive Interface Multiple Formats

Single-phase three-wire Three-phase five-wire

• LCD rotating design, more convenient • LCD displays system status • 6 kVA supports 1ph input, 1ph output

for R/T conversion • Supports five languages: • 10 kVA supports 3ph input, 1ph output;

• High power density, 2U/3U high, 650 English, Chinese, French, 1ph input, 1ph output

mm depth Spanish, and Russian • 15 kVA/20 kVA supports 3ph input, 3ph

• Can be installed in 900 mm deep, 19- output; 3ph input, 1ph output; 1ph input,

inch rack 1ph output


Reliable Efficient Simple

Parallel System: Up to Four Units(UPS2000-G 6kVA~20kVA)


Parallel system: Up to four units, easy to expand Hierarchical power distribution
Bypass
main main main main

UPS 1 UPS 2 UPS 3 UPS 4

load load load


Ring parallel line

• Auto-sensing parallel, easy to form N + X configuration Primary load Secondary load

• Parallel systems require only one communication card


• The primary load is turned off when the system is
• The ring parallel line eliminates the failure of a single parallel
overloaded or in battery mode to extend quality of
cable
the main load power supply.
• The 15/20 kVA parallel system shares batteries, reducing
customer battery costs
1-3kVA doesn’t support UPS in parallel.
Reliable Efficient Simple

Intelligent Management to Extend Battery Life


Flexible Configuration and Maintenance Intelligent Charge and Discharge Senior Management

• 20 to 16 cells per string for 6K/10K; 32 to • Automatic equalized and float-charging • Automatic identification of electrical
40 cells per string for 15/20K. When conversion and temperature environment, enabling intelligent
removing damaged batteries, the compensation function prevent battery hibernation mode in a healthy grid.
remaining batteries will work normally. over- or under-charging to extend
battery life.
• Automatically adjusts discharge
termination voltage in accordance with
load condition and the discharge time.
Constant Battery
Battery voltage

×
voltage hibernation

Temperature
compensation

Damaged battery due to thermal


Old batteries can be reused. Battery discharging curve runaway
Reliable Efficient Simple

Integrated Monitoring System


Easy to manage

• Displays real-time system running state.


• Power supply and battery testing systems can be
controlled.
Remote online upgrade

• Monitoring unit supports remote online upgrade.


• Supports RS485, SNMP, USB, and dry contact.
NetEco 1000U interface

Single UPS monitoring (USB) Multiple UPS network management system SMS alarm Terminal remote management
Real-time monitoring
Output report
Pre-failure

Asset management
UPS Ports Introduction—1kVA
Standard(Oversea) Long Run(Oversea)

8 8
9 9

1. AC input socket 2.Input Socket Breaker 3. USB 4. RS-232

5 .Monitor card slot(optional) 6.External battery access 国内版的


7. AC output socket输出插座 8. LCD Display Panel

9. Control Button
UPS Ports Introduction—2kVA
Standard(Oversea) Long Run(Oversea)

5
8 8
9 9

1. AC input socket 2. Input Socket Breaker 3. USB 4. RS-232


国内版的 输出插座
5. Monitor card slot(optional) 6. External battery access 7. AC output socket 8. LCD Display Panel

9. Control Button
UPS Ports Introduction—3kVA
Standard(Oversea) Long Run(Oversea)

9
10 9
10

1. AC input socket 2. Input Socket Breaker 3. USB 4. RS-232

5. Monitor card slot(optional) 6. External battery access 7. AC国内版的 输出插座 8. C19 output socket
output socket

9. LCD Display Panel 10. Control Button


UPS Ports Introduction—6/10kVA

(1) AC input circuit breaker (2) Optional card slot (3) USB port (4) MBS port

(5) EPO port (6) AC input terminal block (7) AC output terminal block (8) Battery wiring terminal block

UPS2000-A support 1 phase in, 1 phase out.


UPS2000-G Port Introduction (1K to 3K)
GB Long Run Model IEC Long Run Model

1KVA

3 10A output 10A input Battery Terminals 4 C13 output C14 input Battery Terminals

2KVA

4 10A output 10A input Battery Terminals 6 C13 output C14 input Battery Terminals

3KVA

OT Terminals 4 10A output 16A input Battery Terminals C19 Terminals 6 C13 output C20 input Battery Terminals

Standard Model: No external battery interface


UPS2000-G Port Introduction (6K to 20K)
Battery ports: PP45 Input circuit
Emergency Power Off Temperature sensor
breaker port : (40~80℃)

AC input ports AC output Maintenance


ports bypass port • Optional card slot
(MBS) • SNMP card
Parallel ports • Modbus card
• Dry contact card

Controller Area Network


(CAN) communications
10K Model Example
Flexible Installation: Tower/Rack

Open the panel Rotate LOGO

Rotate control panel


Support bases Adjustable guide rails
(Tower-installation ) ( Rack-installation) Tower installation
• The support bases are
delivered with the UPS. • The installation brackets are
delivered with the UPS.
• The support base length is
adjustable, you can add • The guide rails are optional
components to increase the accessories
length.
Multiple Formats: 1/1,3/1,3/3
• Formats transformation is realized by short-circuit busbars.
• Output format can be set on the LCD display.

3/3 3/3
Two mains input Two mains input

3/3 3/3
One mains input One mains input

3/1 3/1
Two mains input Two mains input

3/1 3/1 3/1


One mains input One mains input One mains input

1/1 1/1 1/1 1/1


One mains input One mains input One mains input One mains input

6K model 10K model 15K model 20K model


UPS2000-G Optional Accessories SNMP card
Battery temperature sensor
Description Remarks
Modbus card
1kVA long backup time model
3kVA long backup time model
6kVA Standard/long backup time model
UPS
10kVA Standard/long backup time model
UPS
15kVA long backup time model Transformer
Dry contact card
20kVA long backup time model
Battery pack 240V ,7/9Ah; 36V,7Ah; 96V,7Ah
Battery box 40Ah/65Ah,36V;40Ah,96V
Power 3/1 PDU Only for 6kVA to 20kVA UPS
distribution 3/3 PDU Only for 6kVA to 20kVA UPS
6kVA transformer 2:1:1 (Only for 6kVA to 20kVA UPS) GSM Modem
Battery pack
10kVA transformer 2:1:1 (Only for 6kVA to 20kVA UPS)

SNMP card SNMP/Web monitoring management Power Distribution Unit


(PDU)
Modbus card RS485 networking
Optional Temperature
Dry contact card Input and output signal
accessories and humidity
Battery temperature sensor
Battery temperature monitoring
sensor
Temperature and Environment temperature and humidity
humidity sensor monitoring

Page23
UPS2000-A Optional Accessories
SNMP card

GSM Modem
Modbus card

UPS2000-A Dry contact card


UPS fixing stand
1/2/3kVA 6/10kVA

External Charger
Temperature and
humidity sensor

Transformer Battery Rack

Battery pack

Battery switch box


Dry Contact Card
Flexible Monitoring-----USB/SNMP/Modbus/Dry Contact
Single monitoring:USB + NetEco1000U Network monitoring : RS485 (Modbus)

Modbus protocol
YDN-23 protocol
UPS and PC are connected by USB line in single UPS system

Modbus networking mode


Network monitoring : Network monitoring :
SNMP+ Ethernet Dry contact +User interface Single UPS
networking

Parallel networking

Only one
Standard cable communication
card
Parallel system networking
Battery Installation Type

6K/10K model :Battery ports: PP45

Battery pack 15K/20K model : Battery ports: OT

Battery Battery
pack rack

Short backup time mode Long backup time mode


(Battery pack) (Battery rack)

IMPORTANT: 15K/20K requires cable distribution box in battery pack mode!!


Optional Accessories: Battery Pack and Box (1K to 3K)
Type Model Capacity Brand UPS
ESS-36V9Ah*2-BPVBB 36V/9Ah YUSA 1K
Battery
ESS-72V9Ah*2-BPVBB 72V/9Ah YUSA 2K
pack
ESS-96V9Ah*1-BPVBB 96V/9Ah YUSA 3K
ESS-36V40Ah*1-BBNBB 36V/40Ah Shoto/B.B. 1K
Battery
ESS-36V65Ah*1-BBNBB 36V/65Ah Shoto/B.B. 1K
box
ESS-96V40Ah*1-BBNBB 96V/40Ah Shoto/B.B. 3K

1K: Backup time schedule of battery pack 2K: Backup time schedule of battery pack 3K: Backup time schedule of battery pack

No. Load Backup time No. Load Backup time No. Load Backup time
100% 15.0min 100% 6.5min 100% 7min
1 1
75% 21.0min 75% 10.0min 75% 11min
1
50% 39.0min 100% 17.0min 100% 16min
2 2
25% 77.0min 75% 25.0min 75% 25min
100% 36.0min 100% 39min 100% 31min
3 3
75% 47.0min 75% 55min 75% 45min
2
50% 83.0min 100% 63min 100% 39min
4 4
25% 159.0min 75% 87min 75% 55min
Optional Accessories: Battery Pack (6K to 20K)
Model Capacity Brand
ESS-240V12-7AhBPVBA01 7Ah B.B.
ESS-240V12-7AhBPVBA02 7Ah Panasonic
ESS-240V12-9AhBPVBA01 9Ah B.B.
ESS-240V12-9AhBPVBA02 9Ah Panasonic
Part backup time schedule :
B.B. 7Ah B.B. 9Ah B.B. 9Ah
Battery Backup Battery Backup Battery Backup
UPS UPS model
number time number time number time
6K 15K long 4 19min
6K
Standard 1 6min Standard 1 4min backup
6 32min
model model time
model 8 48min
2 19min 10K long 2 12min
6K long 4 12min
20Klong
backup backup
3 29min 3 23min backup
time time 6 23min
time
model model 4 32min
4 46min model 8 32min
Optional Accessories –Battery Rack and Switch Box

Model Specifications UPS


More connection type of battery racks
PDC-63DC-440V 440VDC 63A 3K/6K/10K
PDC-63DC-660V 630VDC 63A 15K/20K

UPS
Battery switch box
+ -

Battery rack

• Type of battery rack depends on


battery number and capacity. +Rack 1- + Rack -2 + Rack-3 +Rack 4-
• 2V and 12V series battery rack
more battery racks connections
Optional Accessories -PDU
PDU model UPS model
PDC-0038V4ACIOA 15K/20K(3/3)

PDC-0091V2ACIOA 6K/10K/15K/20K (3/1,1/1)

Functions :
• Input and output power distribution of
parallel system. 1. Maintenance 2. DIP switch 3. Voltage monitoring 4. Output ports
bypass ports (MBS) ports
(6K/10K 1+1,2+0 & 15K/20K 1+1)
5. Bypass input ports 6. Mains input ports 7. Output socket group 1 8. Output socket
• Provide maintenance bypass in UPS single or (250 V AC, 15 A) group 1 fuses

parallel system. 9. Output socket 10. Output socket 11. UPS 1 mains input port 12. UPS 2 mains
group 2 fuses group 2 (250 V AC, 10 (under the cover) input port (under the
• Provide output sockets: OT ;4*C13;2*C19. A) cover)
13. UPS 1 bypass 14. UPS 2 bypass 15. UPS 1 output port 16. UPS 2 output
• Report voltage signals of PDU to UPS. input port (under the input port (under the (under the cover) port (under the
cover) cover) cover)
Optional Accessories -PDU
Maintenance bypass
opening will trigger the
maintenance bypass
PDU front panel switch(MBS ) signal
( Logo panel removed )

Input and
output circuit
breakers

端口连接

PDU rear panel


(Cover plate removed)
Optional Accessories - Transformer
Functions Configuration
• Realize electric isolation 15K 3/3:3 x 6kVA transformers
• Transformer ratio 2:1:1 20K 3/3:3 x 10kVA transformers
• Output dual 110V or another 220V 15/20K 3/1,1/1:2pcs 10kVA transformers

Types
• 6kVA transformers for 6K&15K UPS
• 10kVA transformers for 10K&20K UPS
Optional Accessories –Monitoring Card
Monitoring
card slot SNMP card
• Monitors, via NMS, NetEco, and the Web, the UPS. operating
status based on the computer network type.
• Environment temperature and humidity sensor can be
inserted in SNMP to monitor surrounding information.

Modbus card
• RS485 networking.
• Monitoring via the NetEco 1000U.
Monitoring
• Only one card required in parallel system.
card slot

Dry contact card


Card slot can hold three types • 6 alarm outputs :( Normal mode ,battery mode,
of monitoring cards. bypass mode , Low battery voltage, Bypass backfeed
, UPS faults )
• 2 control inputs: Shutdown , reserved.
Optional Accessories -NetEco1000U
• Real-time monitoring. NetEco1000U monitors UPSs in real time
and allows users to configure and control UPSs
• Delay shutdown, shut down the computer application system
and operating system
• USB, SNMP, Modbus networking communication
• Historical data query. Query historical data and UPS alarm logs
through the NetEco1000U.
• Remote alarm notification. NetEco1000U notifies users via by
emails or SMS short messages immediately after a UPS
reports an alarm
Notes: The SMS alarm requires GSM MODEM :

The NetEco1000U is configured on SCT, software can download from support.


1. Overview of Huawei UPS

2. UPS2000 Features
Introduction

3.UPS2000-G li-ion solution

3. Successful Cases
UPS2000-G Li-ion Solution Intrduction

Li-ion battery
50/100AH / pcs

UPS2000-G-6K
UPS2000-G-3K
UPS2000-G-1K

Be available in 2020 Q2 (20200530)


UPS2000-G-3K & UPS2000-G-6K
UPS technical specifications

Model 3KL48 6KL48


Rated capacity 3 kVA/2.7 kW 6 kVA/5.4 kW
power factor 0.9 0.9
Input
Rated input voltage 230 VAC 230 VAC
Input voltage range 110-280 VAC 110-280 VAC
Input frequency range 50 Hz/60 Hz (adaptive) ±4 Hz 50 Hz/60 Hz (adaptive) ±4 Hz
Input power factor ≥ 0.99 @ Nominal voltage (100% load) ≥ 0.99 @ Nominal voltage (100% load)
waveform distortion ≤ 5% (100% linear load) ≤ 5% (100% linear load)
Output

AC Voltage Regulation (Line&Batt. Mode) 230 V AC±1% 230 V AC±1%

Frequency Range (Synchronization Range) 46–54 Hz or 56–64 Hz 46–54 Hz or 56–64 Hz


Efficiency
Online mode 90% 93.5%
ECO mode 98%
Battery mode 88% 91.5%
Battery
Battery voltage 44–57 VDC
Maximum charge current 60 A
Float charging voltage 54 VDC
Overcharge protection 57 VDC
Physical dimensions and ports
Dimensions (H x W x D) 420 x 438 x 88 420 x 438 x 132.5
Huawei Li-ion battery
Product Model ESM48100B1

cathode material lithium iron phosphate

Nominal voltage 48 V DC

Rated charging voltage 53.5 V DC

Maximum charge/discharge current 100 A/100 A @35°C@100AH, 50 A/50 A @35°C@50AH,

Maximum charge/discharge power 4800 W

cycle life 3500 times @ 0.5C, 85% DOD, 70% EOL, 35°C

Standard capacity 100 Ah @ 0.2C, 35 C (4800Wh @ 0.2C, 35C); 50 Ah @ 0.2C, 35 C (2400Wh @ 0.2C, 35C)

Weight About 43 kg
Parameter Specifications (W x D x H) 442 mm x 396 mm x 130 mm (excluding mounting ears)

Self-discharge rate@25C < 5% (90-day storage)

Communications port CAN/RS485; Two dry contacts


Maximum number of parallel cables CAN: 32; RS485:16
Maximum parallel power 24 kW(100AH); 12 kW(100AH)

Wiring terminal M6, torque: 4 N·m

Installation Mode Installing a 19-inch support


Overtemperature protection, overcurrent protection, short-circuit protection, overcharge protection, and
Protection Function
overdischarge protection
Authentication CE, UN38.3

design life 15 years


1. Overview of Huawei UPS

2. UPS2000 Features
Introduction

3.UPS2000-G li-ion solution

3. Successful Cases
Module market share ranked No. 1 in global

Modular market share (global) DCS 2019: Annual Best Power Supply and DCS 2019: Annual New Design / Build Data
No. 1 Distribution Innovation Award Center Project Award

O, 23.7%

34.30%
E2, 5.3%

A, 7.0%
E1,
S: 15.9%
13.7%

HUAWEI S E1 A E2 Others

Data source: Frost & Sullivan 2019


Huawei UPS Cases

Huawei UPS helped Harbin Mobile 17 Huawei 500kVA UPSs 19 Huawei 400kVA UPSs Huawei UPS supported
win “Award of DCD Green Data supported China Unicom helped 21 VIANET establish cloud data center in
Center” Tianjin Airport IDC highly reliable green data Karamay
center

Huawei UPS was highly Huawei UPS helped London Huawei provided reliable and efficient Huawei UPS was highly
recognized by Singapore Underground establish integrated power supply solution recognized by Turkey
StartHub communications solution for CongoKing Branch, Chinese Academy of
Sciences
THANK YOU

Copyright©2016 Huawei Technologies Co., Ltd. All Rights Reserved.


The information in this document may contain predictive statements including, without limitation, statements regarding the future financial and operating results, future product portfolio, new
technology, etc. There are a number of factors that could cause actual results and developments to differ materially from those expressed or implied in the predictive statements. Therefore, such
information is provided for reference purpose only and constitutes neither an offer nor an acceptance. Huawei may change the information at any time without notice.

You might also like