Electronic Single Phase Meter For Smart Metering Application

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

AS220

Smart Single Phase Meter

Electronic Single Phase Meter for Smart Metering


Application

Features
• EN 62053-21: Accuracy Class 1 or Class 2 The AS220 AMI domestic Smart Meter offers multi-tariff
EC Directive 2004/22/EC (MID): Class A or B metering and modular communications to interface directly to
the utility via a Wide Area Network (WAN) or Local Area
• kWh, kvarh and kVAh energy measurement Network (LAN) and to connect to a consumer's Home
• Import/Export Automation Network (HAN).
• Modular WAN/LAN, HAN capability The module provides the platform for many different forms of
• Comprehensive Tariff Structure communications including GSM/GPRS, PLC and Lower
• Maximum demand registration Power Radio for WAN/LAN communications. The modular
and optical port can be used to read data from any meter
• Load profile recording (4 channels) connected to the HAN.
• Instrumentation profile recording
The meter measures a combination of import and export
• Instantaneous power quality parameters active energy, four-quadrant reactive energy and apparent
• Extensive security features energy. Extensive security features protect the meter from
fraud or tampering.
• Internal Disconnect
• Product design life 15 years The AS220 meter records up to 120 days of load profile data
for one channel (15 minute period). Instrumentation values
• Optical communications port (EN 62056-21) are available to aid meter commissioning. An additional
• Internal clock with battery back-up feature observes the network regarding power quality.
• Compact Design The meter is supported by the user friendly reading,
• IP53 in accordance with IEC 60529 configuring and programming tool alphaSET.
Meters can be supplied to meet EC Directive 2004/22/EC
Options (MID): accuracy Class A or Class B.
• Modular remote communications unit kvarh is to EN 62053-23 Class 2 or 3.

• DLMS protocol The meter has an ingress protection rating of IP53 to IEC
60529:1989.
• Read without power
• SO output (DIN 43864)
• DIN or BS case
• RS232 or RS485
• Backlit Display

Display
Programmable display
sequence with OBIS
identifiers. There is an
option to back light the
display.
Communications Modules
Communications
Local
• Optical bi-directional port, max baud rate 9600 (IEC
62056-21)
Remote (optional)
• CLO, RS232, RS485 (max baud rate 9600))
Electronic Output (optional)
• Control or pulse output (DIN 43864)
A module can be fitted under the terminal cover for smart
metering or C&I applications.
AM100 - GSM/GPRS module. Option of wireless or wired M-bus
Tariff Structure AM200 - Wireless M-Bus only
• 6 Energy register sets AM500 - PLC module using DLMS/COSEM protocol. Option of
• 4 Maximum demand registers wireless or wired M-bus
• 4 Seasons AM600 - Wavenis based RF communications, 868MHz
AM700 - RS485, multi-drop up to 32 meters

Load Profile (Optional)


Contactor
• Programmable interval (1 to 60 minutes) The main 100A contactor can be disconnected locally or remotely
• Up to 8 channels by the Utility. This can be driven directly or by the meter at load
• Up to 260 days (1 channel, 15 minutes) limiting thresholds.
• Storage modes
- demand per period Technical Data
- energy per period Current Range DIN: 5(60)A, 5(100A) BS: 5/100A, 20/100A
Voltage Range 220 .. 240V (-20% .. 15%)
- total energy per period Frequency 50 / 60Hz, +/- 5%
Impulse withstand 6kV, Rsource = 2 Ohm
Surge withstand (1,2/50 s) 12kV, Rsource = 40 Ohm (Between main terminals)
Dielectric test 4kV, 1min, 50Hz
Display LCD size: 47mm x 28mm
Instrumentation Digit size: 8mm x 3.6mm
• Voltage and Current Baud rates Optical: 9600 baud
Electrical: 9600 baud
• Power factor Comms module
E-Meter EN 62056-21 protocol, 9600 baud
• Active, reactive and apparent power WAN AM100 GSM/GPRS
• Frequency Transparent mode, EN 62056-21
LAN DLMS/COSEM protocol
Wireless M-Bus or
Wired M-Bus acc. EN 13757-4
Contactor Mechanical life - 100.000 switching cycles
Security Electrical Endurance - 10.000 cycles (100A)
• Terminal cover removal detection Temperature -40o...+70o (Operating)
-40o...+80o (Storage)
• Main cover removal protection Humidity 0 to 100% rel. humidity, non-condensing
• Always run positive measurement Test indicator output Configurable
Power consumption < 0,7W, <0,8VA
• Magnetic field detection
Dimensions (mm) 132(wide) x 170(high) x 65(deep)
• Reverse run detection Long terminal cover 132(wide) x 219(high) x 65(deep)
• Extensive log filing of security data with time and date Weight <400g
stamps Specifications EC Directive 2004/22/EC (MID)
kWh Class A or Class B
kvarh Class 2 or Class 3 EN 62053 - 23
Case IP53 to IEC 62059
DIN Meter: 43857 Part 2
BS Meter: BS7856

Elster Metering Systems


Tollgate Business Park,
Paton Drive, Beaconside
Stafford, Staffordshire, ST16 3EF the
The company’s policy is one of continuous product improvement and

United Kingdom right is reserved to modify the specification contained herein


without notice.
Tel: +44 (0) 1785 275200
Fax: +44 (0) 1785 275300
www.elstermetering.com
AS220 ESM 1A 2.2010

You might also like