Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

UCG55-12

12V 55Ah (C10)


12V 64Ah (C100)
Solar Series

216 ± 2

13
8± 2
2 229 ±

17 kg
Approx

Technical Dimensions (mm)

229±2

216±2

210±2 138±2

Ultracell (UK) Ltd | Vesty Business Park, Vesty Road, Liverpool, L30 1NY, United Kingdom
Tel: +44 (0) 151 523 2777 | Fax: +44 (0) 151 523 0855 | Email: info@ultracell.co.uk UCG-V2-REV1 01/20
www.ultracell.co.uk ALL DATA IS SUBJECT TO CHANGE WITHOUT NOTICE
Image Terminal Dimensions (mm)

Standard
Terminal: F6

16

M6

Technical Specification
Output Nominal Voltage 12V
Nominal Capacity (10HR) 55Ah
Terminal Type Standard Terminal F6

Container Material Standard Option ABS


Flame Retardant Option (FR) ABS (UL94:VO)
Rated Capacity (100HR 1.80V/cell, 25°C) 64 Ah/0.64A
(20HR 1.80V/cell, 25°C) 57.8 Ah/2.89A
(10HR 1.80V/cell, 25°C) 55.0 Ah/5.50A
(5HR 1.75V/cell, 25°C) 48.5 Ah/9.69A
(3HR 1.75V/cell, 25°C) 42.0 Ah/14.0A
(1HR 1.60V/cell, 25°C) 34.8 Ah/34.8A

Max Discharge Current 550A (5s)


Internal Resistance Approx 9mΩ
12V 55Ah (C10)
12V 64Ah (C100)
UCG55-12

Solar Series

Discharge Characteristics Operating Temp Range Discharge: -15 ~ 50°C


Charge: 0 ~ 40°C
Storage: -15 ~ 40°C
Nominal Operating Temp Range 25 ± 3°C
Cycle Use Initial Charging Current less than 13.8A.
Voltage 14.1V ~ 14.4V @ 25°C Temp. Coefficient -30mV/°C
Standby Use No limit on initial charging current.
Voltage 13.5V ~ 13.8V @ 25°C Temp. Coefficient -20mV/°C
Capacity affected by Temperature 40°C 103%
25°C 100%
0°C 86%
Design Floating Life at 20°C 15 Years

Self Discharge
Ultracell® UCG batteries may be stored for up to 6 months at 25°C and then a refresh charge is required. For higher
temperatures the time intervals will be shorter.

Constant Current Discharge / Constant Power Discharge At 25°C (Amperes & Watts/Cell)
A = Amperes W = Watts
F.V/TIME 30 60 2 3 4 5 6 8 10 20
A W min min hours hours hours hours hours hours hours hours
44.9 28.6 16.3 13.0 10.6 9.04 7.79 6.37 5.11 2.68
1.85V/cell
86.1 55.4 31.7 25.3 20.7 17.8 15.4 12.6 10.2 5.34
50.1 30.3 17.2 13.8 11.1 9.37 8.11 6.53 5.50 2.89
1.80V/cell
94.8 58.4 33.3 26.7 21.6 18.3 15.9 12.9 10.9 5.73
52.3 32.1 17.9 14.0 11.5 9.69 8.25 6.64 5.55 2.92
1.75V/cell
98.1 61.6 34.6 27.1 22.4 18.9 16.2 13.1 11.0 5.78
52.9 33.6 18.6 14.4 11.8 9.86 8.39 6.75 5.61 2.94
1.70V/cell
98.6 64.2 35.8 27.9 22.8 19.2 16.4 13.3 11.1 5.83
53.7 34.8 19.2 14.9 12.0 10.0 8.48 6.86 5.66 2.97
1.67V/cell
ISO9001 99.2 66.0 36.7 28.6 23.3 19.5 16.5 13.5 11.2 5.88
CERTIFIED
54.5 35.2 19.5 15.1 12.2 10.2 8.53 6.92 5.72 3.00
1.60V/cell
99.8 66.4 37.1 29.0 23.5 19.7 16.6 13.6 11.3 5.93

Ultracell (UK) Ltd | Vesty Business Park, Vesty Road, Liverpool, L30 1NY, United Kingdom
Tel: +44 (0) 151 523 2777 | Fax: +44 (0) 151 523 0855 | Email: info@ultracell.co.uk UCG-V2-REV1 01/20
www.ultracell.co.uk ALL DATA IS SUBJECT TO CHANGE WITHOUT NOTICE
Discharge Characteristics Float Charging Characteristics
Charge Charging Charging
Volume Current Voltage
Temperature: 25ºC % (A) (V/Cell) (0.1CA-2.25V/Cell) Temperature: 25ºC
1 3 .0 120

1 2 .0 100 0.1 C 2 .4
Charged Volume

Terminal Voltage (V) 1 1 .0 80 0.0 8C 2 .3


Charge Voltage
0.1C 0.052C
0.2C (Constant 2.25V/Cell)
0.4C 60 2 .2
1 0 .0 0.0 6C
0.6C After 50% Discharge
2C 1C After 100% Discharge
9 .0 40 0.0 4C 2 .1

C=C20
8 .0 20 0.0 2C 2 .0
Charging Current
C=C10
0 0C
1 2 4 6 8 10 20 40 60 2 4 6 8 10 20 0 4 8 12 16 20 24 28 32
Min H

Discharge Time Charging Time (hours)

Temperature Effects in Relation to Battery Capacity Effect of Temperature on Long Term Float Life

110
14
100
C10 12
90
Available Capacity (%)

Charging Voltage

Float Life (years)


10 2.25V/cell
80 C5

70
C3 5
60
C1
50
2
40

30 0.5
-20 -15 -10 -5 0 5 10 15 20 25 30 20 30 40 50

Battery Temperature (ºC) Battery Temperature (ºC)


12V 55Ah (C10)
12V 64Ah (C100)
UCG55-12

Solar Series

Cycle Life in Relation to Depth of Discharge General Relation of Capacity vs. Storage Time

Acc.to IEC 896-2 (25ºC) Residual average capacity in % of C20


100 120
90
100 A
80
Remaining Capacity (%)
Extracted Capacity (%)

70
80
60 10ºC
B
50 60

40 40ºC 30ºC 20ºC


40
30
C
20
20
10

400 800 1200 1600 2000 2400 2800 3200 3600 4000 0 5 10 15 20 25

Number of Cycles Storage Time in Months

General Relation of Capacity vs. Storage Time (Notes)

A) No supplementary charge required.


(Carryout supplementary charge before use if 100% capacity is required.)

B) Supplementary charge required before use. Optional charging way as below:


1. Charged for above 3 days at limited current 0.25CA and constant voltage 2.25V/cell.
2. Charged for above 20 hours at limited current 0.25CA and constant voltage 2.25Vcell.
3. Charged for 8 ~ 10 hours at limited current 0.05 CA.

C) Supplementary charge may often fail to recover the capacity.


The battery should never be left standing till this is reached.

ISO9001
CERTIFIED

Ultracell (UK) Ltd | Vesty Business Park, Vesty Road, Liverpool, L30 1NY, United Kingdom
Tel: +44 (0) 151 523 2777 | Fax: +44 (0) 151 523 0855 | Email: info@ultracell.co.uk UCG-V2-REV1 01/20
www.ultracell.co.uk ALL DATA IS SUBJECT TO CHANGE WITHOUT NOTICE

You might also like