SECTION 2 – SYSTEM COMPONENTS

Solenoid Adaptor Manifold Check Valve


The adaptor enables the actuator to be removed safely without Manifold check valves are of mushroom pattern type and lift
actuation of the tank valve. To remove the solenoid, the adapter into the manifold as discharge occurs. The function of the
body should be unscrewed in the counterclockwise direction. check valve is to prevent loss of extinguishing agent during
This action will close the schrader valve and then allow the discharge from an outlet, should a tank have been removed. All
pressure between the schrader and solenoid actuator to be check valves are supplied ready fitted to the manifold
released safely through the threads of the adaptor body. assembly.
1.25 in. (32mm) Check Valve Assy. Part No. 570111
2 in. (50mm) Check Valve Assy. Part No. 570121

1 1/2 IN.BSP

004809

Figure 12 - Solenoid Adaptor (Part No. 570135)

Technical Information 004814

Body: Brass CZ121 1.25 in. Check Valve (Threaded)


Circlip: Stainless Steel
Max Working Pressure: 1088 psi (75 bar)
Proof Pressure: 2175 psi (150 bar)
Solenoid Connection: 1/8 in. NPT

004815

2 in. Check Valve (Flanged)

Figure 13 - Manifold Check Valve

Technical Information
Body: Brass CZ122
Stem: Stainless Steel
Spring: Stainless Steel

13 Rev. 1 UL EX 4986 April 2, 2001