IMP/001/909 Code of Practice For Distribution System Parameters
IMP/001/909 Code of Practice For Distribution System Parameters
IMP/001/909 Code of Practice For Distribution System Parameters
2 Scope
This document applies to the existing distribution systems of Northern Powergrid and any future modifications to
them, and to all providers of connections to the distribution systems. The following system parameters are covered
by this policy:
System voltages,
System phasing,
Distribution short circuit levels and clearance times,
Standard of security on the distribution systems,
Power Frequency and Lightning Impulse Withstand to Earth Tests.
As distribution systems develop through new connections, refurbishment of existing assets and reinforcement,
consideration should be given to the harmonisation of operating parameters when it is economic to do so in order
to improve safety, cost, security of supply and operational performance. For example, rationalising voltages to
1 st
This includes The ESQC (Amendment) Regulations 2006 (No. 1521, 1 October 2006) and The ESQC (Amendment)
th
Regulations 2009 (No. 639, 6 April 2009)
facilitate interconnection and hence improve security of supply. Relevant investment appraisals shall consider, as
one of the options, harmonising voltages and assess the costs and benefits thereof.
The document does not include the functional requirements of new switchgear, transformers, overhead lines or
cables. These will be included in policies relevant to that particular asset class.
3 Policy
3.1 Assessment of Relevant Drivers
The key internal business drivers relating to establishing distribution system parameters within which the
distribution system will operate are:
Employee commitment: by establishing parameters within which the system operates and the use of
adequately rated equipment to form the distribution system will ensure that employees are not exposed to
risks to their health as far as reasonably practicable.
Financial strength: by defining standard parameters, financial gains may be made through economies of
scale in the purchase of standard plant and the adoption of standard designs and construction techniques.
Regulatory integrity: by ensuring compliance with external regulations regarding distribution system
parameters.
The external business drivers relating to distribution system parameters are detailed in the following sections.
3.1.2 Requirements of the Electricity Safety, Quality and Continuity (ESQC) Regulations
2002(including amendments 2006 and 2009)
The ESQC Regulations 2002 (as amended 2006 and 2009) impose a number of obligations on the business, mainly
relating to safety and quality of supply. All the requirements of the ESQC Regulations that are applicable to
distribution system parameters shall be complied with, specifically:
Reg. No Extract Application to this policy
…distributors…shall ensure that their equipment is The operating parameters and hence the
sufficient for the purposes for and the maximum duties of plant used on the distribution
3(1)(a) circumstances in which it is used; system will be defined to help ensure that any
plant procured is adequate for purpose.
Rated frequency 50 50 50 50 50 50 Hz
Neutral earthing point multiple source source source source all ends -
2
Interconnection at LV and HV voltages between Northern Powergrid (Northeast) Ltd and Northern Powergrid
(Yorkshire) plc is unlikely to be viable because of the phase differences. Interconnection at 66kV would require a 90°
phase shift. Interconnection at 33kV is most tenable since this could be achieved by rolling the connections.
Figure 1: Northern Powergrid (Northeast) Ltd 132kV and EHV Vector Relationships.
R
400kV, 275kV, 132kV and 66kV Voltage Vectors
R 0°
Y −120°
B +120°
B Y
R −30°
B Y −150°
B +90°
R 0°
Y −120°
B +120°
B Y
Y
66kV and 33kV and 11kV Voltage Vectors
R +90°
Y −30°
R B −150°
Y
0.400kV Voltage Vectors
R +120°
Y 0°
B −120°
R B
system connections are changed in order to avoid incorrect rotation of motors. Reversal of the phasing to restore
correct rotation shall normally be made by interchanging two of the incoming phases at the customer’s intake point
with suitable identification made on all phases.
To ensure that there is no adverse impact on metering equipment, the appointed metering agent should be
informed, through liaison with the customer and electricity supplier, of any proposed changes to system phasing.
Note that whilst a duty of 25 kA at an X/R of 36 is generally within the anticipated performance curve of a circuit
breaker rated to 40 kA at an X/R of 14, it is not certain that a breaker with the latter rating will actually deliver the
required performance, as studies do not confidently support re-rating breakers by more than one step in the
standard IEC preferred ratings table R10. Testing at a higher X/R ratio may therefore be required, particularly given
the absolute sufficiency requirements of ESQC regulation 3.
132 1
EHV 2
HV 2
The time related short circuit requirements of cables and overhead lines are included in policies relevant to those
particular asset classes, however, switchgear is generally type tested to carry the rated short circuit current for a
minimum of 3 seconds, hence a maximum fault clearance time of 3 seconds should be used when specifying 6kV,
11kV, 20kV, 33kV and 66kV switchgear.
3.9 Assumptions
Minimum break rating for new switchgear short circuit levels stated in Table 4 are based on findings of the
2005 Fault Level Survey. It is envisaged that these values will be reviewed in the next version of the policy
based on findings of the ENA work group.
The 132kV phase to earth column in table 4 will be populated in the next edition of the policy based on the
ENA findings. It is also recognised that further guidance is required with regard to time limits for both three
phase symmetrical and earth faults.
4 References
4.1 External Documentation
Reference Title Version and date
BS 159 High-voltage busbars and busbar connections 1992
BS EN62271-100 HV switchgear and controlgear, HV AC circuit breakers 2001
BS 7671 IET Wiring Regulations 2008
Planning levels for harmonic voltage distortion & the
ER G5/4 connection of non-linear equipment to transmission systems Issue 4 2006
and distribution networks in the UK
Planning limits for voltage fluctuations caused by industrial,
ER P28 Issue 1 1989
commercial and domestic equipment in the UK
Planning limits for voltage unbalance in the UK for 132kV and
ER P29 Issue 1 1990
below
ENATS 35-1 Distribution Transformers (from 16kVA to 1000kVA) Issue 5 2007
ER P2/6 Engineering Recommendation P2/6, Security of Supply Issue 2 2006
Title Date
Long Term Development Statement (Northern Powergrid Northeast) November 2013
Long Term Development Statement (Northern Powergrid Yorkshire) November 2013
5 Definitions
Term Definition
Northern Powergrid Northern Powergrid (Northeast) Limited and Northern Powergrid (Yorkshire)
plc
Design Manager The manager appropriate to the part of the network where the policy is being
applied, who is accountable for the implementation of this policy. They will
ensure responsible persons are appointed to implement this policy.
Distributor The term distributor is intended to encompass operators transmitting and
distributing electricity under the terms of the Electricity Act 1989 (as amended
by the Utilities Act 2000)
Ofgem The Office of Gas and Electricity Markets, or its successor.
Distribution Licence Standard condition of the Electricity Distribution Licence based on Electricity
Act 1989 for all electricity distributors
Sign Date
Lynn Donald CDS Administrator Lynn Donald 27/02/14
6.2 Author
I sign to confirm that I have completed and checked this document and I am satisfied with its content and
submit it for approval and authorisation.
Review Period - This document should be reviewed within the following time period.
Standard CDS
Non Standard Review Period & Reason
review of 3 years
No Period: 1 year Reason: Major review of IMP documents planned for 2015
Sign Date
Saeed Samani System Planning Engineer Saeed Samani 26/02/14
Sign Date
Alan Creighton Asset Management Engineer Alan Creighton 26/02/14
Mick Walbank System Planning Manager Mick Walbank 26/02/14
Derek Fairbairn Customer Connections Design Manager Derek Fairbairn 26/02/14
6.4 Approval
Approval is given for the content of this document.
Sign Date
Mark Nicholson Head of System Strategy Mark Nicholson 26/02/14
6.5 Authorisation
Authorisation is granted for publication of this document.
Sign Date
Mark Drye Director of Asset Management Mark Drye 26/02/14
Appendix 3
Table a: Northern Powergrid (Northeast) Ltd Standard EHV and HV Systems
Transformer Terminal Markings
Phase shift
Ratio (kV) Vector Group Connected as Primary Secondary
A B C a b c from to
132/66 Yy0 Yy0 R Y B r y b 0° 0°
Yd1 Yd1 R Y B r y b 0° -30°
132/33
Yd11 Yd1 B Y R b y r 0° -30°
132/11 Yd11 Yd11 R Y B r y b 0° +30°
Yd1 Yd1 R Y B r y b 0° -30°
66/33
Yd11 Yd1 B Y R b y r 0° -30°
66/HV Dy11 Dy11 R Y B r y b 0° +30°
Yy6 Yy10 Y B R r y b -30° +30°
33/HV
Yy6 Yy10 R B Y b y r -30° +30°
33/LV Dy11 Dy9 B Y R r b y -30° +60°
HV/LV Dy11 Dy11 R Y B r y b +30° +60°
3 4
HV refers to standard 11kV systems, Tyneside 6kV and Sunderland 5 kV Systems.
3
Carville/Wardley/Hebburn and Highfield South
4
Cloisters/Sunderland St Lukes/Deptford (customer sub)
5
Table c: Northern Powergrid (Northeast) Ltd York 11kV System
Transformer Terminal Markings
Phase shift
Ratio (kV) Vector Group Connected as Primary Secondary
A B C a b c from to
R Y B b y r 0° +120°R
132/11 Yy0 Yy8
B Y R r y b 0° +120°R
Dy11 R Y B b y r -30° +120°R
33/11 Dy7
Dy1 B Y R r y b -30° +120°R
11/LV Dy11 Dy11 R Y B r y b +120°R +90°R
6
Table d: Northern Powergrid (Northeast) Ltd Darlington 6kV System
Note: This system will not parallel with others in the vicinity.
Table e: Northern Powergrid (Northeast) Ltd Middlesbrough LV System
5
Poppleton/Melrosegate/Foss Island
6
Darlington PS/Rise Carr