FUARANTEED TECHNICAL PARTICULARS FOR 11OW_CT

'' RATIO":20~-=m1-1-1-1 A
ISI. No. I
I

ITEM DESCRIPTION I
I

UNIT I
I

I
GUARANTEEDVALUES
1 NAME OF THE MANUFACTURER I LAMCO INDUSTRIES PVT. LTD
2 COUNTRY OF ORIGIN " INDIA

I SINGLE PHASE, OIL IMMERSED, DEAD


TANK,OUT DOOR TYPE

FOR LAMCO INDUSTRIES PVT. LTD.

DATE :
11 CLASS OF INSULATION A
ONE MINUTE POWER FREQUENCY WITH STAND
l2 KVms 230
VOLTAGE (DRY & WET)
13 LIGHTNING IMPULSE WITHSTAND VOLTAGE KVp 550

ONE MINUTE POWER FREQUENCY WITH STAND


l4 KVms 3
VOLTAGE ON SECONDARY WINDING
1.5 MINIMUM CREEPAGE DISTANCE mmKV 3813
16 STANDARD TO WHICH OIL CONFORMS IS - 335
17 WEIGHT OF OIL Kg 120&10%
18 TOTAL WEIGHT Kg 450i10%
19 MOUNTlNG DIMENSION mm 400x400
20 OVER ALL DIMENSION AS PER APPROVED G.A DRAWING
21 TANK FINISH PAINTING
22 TERMINAL CONNECTORS ACSR RIGID TYPE

FOR LAMCO INDUSTRIES PVT. LTD.

3
DATE:.@ /? ((I DATE :
I
GUARANTEED TECHNICAL PARTICULARS FOR
96KV lOKA CLASS-3 LIGHTNING ARRESTERS

1. Name of the Manufacturer : LAMCO INDUSTRIES PRIVATE LIMITED.,


B-39, I.E.SanathnagarrHYDERABAD-018 ( A m

2. Type : Heavy Duty Station Class Metal Oxide gapless


Lightning Arrester "MORESTER" type 'LMA.5'-

3. Reference Standard : IEC 99-4 of 2006/ IS 3070(Part-3)1993.


C".?

4. Model (Drg. No.) : 2210969

5. Nc, cf Units : TWO (48KVx2Nosj

6. Rated Voltage
++,
I 7. Nominal discharge current

8. Reference current : 3mA

9. Reference voltage : Greater than the rated


Arrester voltage at
reference current

10. Leakage Current at COV : less than 0.8 mA

! 11. Max. continuous operating voltage : 76.8 KVrms

12. Maximum resldual voltage for discharge


current of (8/20 micro sec. wave)
i. 5000 Amps : 260 KVpeak
ii. 10000 Amps : 273 KVpeak
iii. 20000 Amps : 360 KVpeak

13. Max. steep front residual voltage at


P lOKA with one micro sec. rise time : 360 KVpeak

14. Max. switching impulse residual voltage


with 40/80 micro sec. wave at 500A : 272 KVpeak

15. Energy dissipation capability : 9 KJ/KV


(cumulative of 3 sequential shots)

16. High current 4/10 micro sec. test value: 100 KApeak

17. Long duration current tests


i) Current peak : As per discharge Class-3
of IEC 99-4 (Table-4).
ii) Virtual duration : 2400 us

Continued on page..2
:: 2 ::
(2210969) \ b ..
18. Pressure relief class : Class 'A'

19. Short circuit current capability : 40 KA rms

20. Partial discharge at 1.05 times MCOV : Less than 10 pC

21. Temporary over voltage withstam


value for
a. 0.1 Second : 110 KVrms
b. 1.0 Second : 106 KVrns
c. 10.0 Second : 101 KVrms

22. Insulation withstand strength of


Arrester housing
i) One minute 50 Hz dry & wet : 230 KVrms
ii) Lightning impulse voltage withstand : 550 KVpeak

23. Creepage distance : 3900 mrn

24. Weight of complete unit : 113 5~10%kgs

25. Height of complete unit from base to


the line side : Refer Drg No. 2210969

26. Minimum recommended centre to centre


spacing between Arresters : 1800 rnm

27. Clearance required from ground


equipment at various heights of
Arrester unit : 1500 mrn

28. Earthing arrangement provided for : Ground Terminal Bracket


earthing side of Arrester provided for connecting earth
strip (Drg. No.6220154)

29. Mounting flange dimensional details : End castings,3 holes (12.5mm dia)
120 deg apart at 250 mm PCD.

for LAMCO INDUSTRIES PRIVATE LIMITED.

(B.RAJAIAH)
MANAGER (D&D)
31 q l r t
LlNE TERMINAL CONNECTOR

LlNE TERMINAL BRACKET

UNlT - A, NAME PLATE

GRADING RlNG

PORCELAIN BUSHING

UNlT - B, NAME PLATE

NAME PLATE

GROUND TERMINAL BRACKET

SUPPORT INSLILATOR 078


3 Nos. PLACED 120" APART.

3 MOUNTING HOLES 012.5 ON


250 PCD FOR M I 2 BOLTS.
I I NOTE :
1. FOR SURGE MONITOR REFER Drg. No. : 4249001A.
1500
2. FOR INSTALLATION AND INTERCONNECTION
I -- . REFER Drg. No. : 4320010.
A
3. TOTAL CREEPAGE DISTANCE 3900 mm (NOM).
1500 < 4. ARRESTER VENT PORTS SHOULD BE D!RECTED
E-p p-p 1 p-p TOWARDS SAFE DIRECTION.

- 1500 - 1800 -- 1800 - 1500 - 5. WEIGHT OF THE ARRESTER 1 13k1O%Kgs.

3 P H A S E INSTALLATION

01. GRADING RING DIMENSION MODIFIED & MATERIAL CHANGED TO ALUMINIUM


I REV. No. I BREIF DESCRIPTION I SIGNATURE DATE I

LAMCO
INDUSTRIES PRIVATE LIMITED,
TOLERANCE
AS
INDICATED

Y
B - 38,39,40, SANATHNAGAR I.E,
HYDERABAD-500018,A.P, INDIA.
ALL DIMENSIONS
ARE IN mm
SCALE . NTS APPROVED cG$$b-"&\ 1
121f1q~
TITLE :
96KV, 1OK, LIGHTNING ARRESTER (C.D. : 3900mm)
DRAWING NUMBER
ISSUE - ,
(MORESTER TYPE LMAS) 22 10969 REV - 1

You might also like