Professional Documents
Culture Documents
Argonite Marketing Guide
Argonite Marketing Guide
ANTINCENDI S.p.A.
ARGONITE
R
Y2K
Fire Suppression System
SILVANI
ANTINCENDI S.p.A.
ARGONITE
R
Y2K
Fire Suppression System
NEW TECHNOLOGY FIRE PROTECTION
ALTERNATIVES FOR FIXED HALON SYSTEM
OZONE DEPLETION
GLOBAL WARNING
ARGONITE
R
Y2K
Fire Suppression System
NEW GASEOUS FIRE EXTINGUISHING SYSTEMS
Level after
release NEW “CLEAN AGENTS”
ARGONITE
R
Y2K
Fire Suppression System
NEW GASEOUS FIRE EXTINGUISHING SYSTEMS
HALON 1301
ARGONITE
R
Y2K
Fire Suppression System
NEW GASEOUS FIRE EXTINGUISHING SYSTEMS
INERT GAS
ARGONITE
R
Y2K
Fire Suppression System
ARGONITE EXTINGUISHANT
DESCRIPTION AND PROPERTIES
WHAT IS ARGONITE?
WHY Ar AND N2 ?
SYSTEM RELEASE
50 % Argon
50 % Nitrogen One method is to release Argonite in the entire room :
total flooding application
- engineered or modular systems.
Another method is to release Argonite inside the protected unit
- modular systems
A CLEAN AGENT
ARGONITE
R
Y2K
Fire Suppression System
ARGONITE EXTINGUISHANT
DESCRIPTION AND PROPERTIES
WHERE CAN ARGONITE BE USED ?
- Bureau Veritas
- Danish Maritime Authority
- VdS, Components have been listed
- C.N.P.P.
- EPA
- Norske Veritas
- Lloyds Register
- LPCB Loss Prevention Certification Boad, UK
- NFPA 2001 - IG 55
ARGONITE
R
Y2K
Fire Suppression System
ARGONITE EXTINGUISHANT
DESCRIPTION AND PROPERTIES
EFFECTIVE AND SAFE
WORKING PRESSURE
ARGONITE STORAGE
ARGONITE
R
Y2K
Fire Suppression System
ARGONITE EXTINGUISHANT
DESCRIPTION AND PROPERTIES
ARGONITE - A SUMMARY
ADVANTAGES
DISADVANTAGES
ARGONITE
R
Y2K
Fire Suppression System
AIR BEFORE
DISCHARGE ARGONITE SYSTEM DESIGN
The Basics
78,08%
SYSTEM DESIGN
21%
0,93%
Oxygen
Carbon
Dioxide
- Ventilation details
Argon
EVALUATION OF RISK
Oxygen
Carbon
Dioxide
Argon
ARGONITE
R
Y2K
Fire Suppression System
ARGONITE SYSTEM DESIGN
The Basics
PRINCIPLES OF RELEASE
ARGONITE
R
Y2K
Fire Suppression System
ARGONITE SYSTEM DESIGN
The Basics
WORKING PRESSURE
- 1x140lt = 55 cu.m
- 2x140lt = 110 cu.m
- 3x140lt = 165 cu.m
- 4x140lt = 221 cu.m
- 5x140lt = 276 cu.m
- 6x140lt = 331 cu.m
- 7x140lt = 387 cu.m
- 8x140lt = 442 cu.m
ARGONITE
R
Y2K
Fire Suppression System
ARGONITE SYSTEM DESIGN
The Basics
Typically :
CALCULATION OF NOZZLES
ARGONITE
R
Y2K
Fire Suppression System
MARKET POSITIONING OF ARGONITE
- Inergen Ansul/Wormald
- Fm200 Great Lakes
- FE-13 DuPont
Comparison List
HALON ARGONITE INERGEN FM-200 FE-13
1301
Chemical CBrF3 50% N2 52% N2 CF3CHFCF3 CHF3
Formula 50% Ar 40% Ar
8% C02
Manufacturer - Locally Locally available Great Lakes DuPont
available
ODP approx. 15 0 0 0 0
GWP - 0 0 3300 12100
Atmospheric >110 - - 32-41 250
Lifetime
Required 1 10 10 1.7 2.5
storage volume
Storage pressure 25/42 150/200 150/200 25 40
ARGONITE
R
Y2K
Fire Suppression System
SYSTEM TESTING AND VERIFICATION
PURPOSE
MAINTENANCE
- mounthly
- check the contents of the cylinder
- check that the cylinder valves are in a closed and sealed position
- check that the bleed valve is in the “standby” position
- once a year
ARGONITE
R
Y2K
Fire Suppression System
SYSTEM TESTING AND VERIFICATION
- Every 5 years
all electric “single-shot” cartridges are substituted every 5 years
- Every 10 years
normally control and pressure testing of the cylinders must be
carried out every 10 years
ARGONITE
R
Y2K
Fire Suppression System
QUOTING A SYSTEM
PROTECTED VOLUME
Example :
PROTECTED VOLUME
ARGONITE
R
Y2K
Fire Suppression System
ARGONITE MARKETING PROGRAMME
- Literature
Company Profile
Argonite Brochure
Argonite Data sheet
- Argonite Video
- Exhibitions
Firex 97 (UK)
- Advertising
- Argonite sales manual
ARGONITE
ARGONITE
R
Y2K
Fire Suppression System
ARGONITE MARKETING PROGRAMME
SUMMARY
PIPE CALCULATION
GENERAL DESCRIPTION
ARGONITE
R
Y2K
Fire Suppression System
ARGONITE MARKETING PROGRAMME
INPUT/OUTPUT
pipe dimensions
restrictor orifice diameters
nozzle orifice diameters
SYSTEM ENGINEERING
Case study
ARGONITE
R
Y2K
Fire Suppression System
ARGONITE MARKETING PROGRAMME
AGENT REQUIRED
0,7214 Kg/cu. m.
Volume x 0,7214
ARGONITE
R
Y2K
Fire Suppression System
ARGONITE MARKETING PROGRAMME
NOZZLE REQUIREMENT
- coverage
- room dimensions
- building structure, including obstructions and equipment
- ceiling tile arrangement
ROOM INTEGRITY
CYLINDER STORAGE
ARGONITE
R
Y2K
Fire Suppression System
ARGONITE MARKETING PROGRAMME
PIPE LAYOUT
ISOMETRIC DRAWING
- add dimensions
- add node points
ARGONITE
R
Y2K
Fire Suppression System
ARGONITE MARKETING PROGRAMME
L= section length
The section length is the actual length of the pipe between the knot
points. The length of a section with restrictor should be 0.5m.
ARGONITE
R
Y2K
Fire Suppression System
ARGONITE MARKETING PROGRAMME
FL/MD
Depending on the section type:
starting section : number of storage containers
nozzle section : nozzle discharge quantity in Kg
pipe section : joining pipe
in case of a joining section you have to enter -1, otherwise 0.
ARGONITE
R
Y2K
Fire Suppression System
ARGONITE MARKETING PROGRAMME
COMPUTER OUTPUT
The print-out from the calculation package provides us with the following:
Details from this print-out are then transferred to the system layout
drawings, such as:
- pipe diameters
- nozzle orifice size and position
- calculation number