Professional Documents
Culture Documents
Annex 2: Technical Specifications For PV Plants
Annex 2: Technical Specifications For PV Plants
Annex 2: Technical Specifications For PV Plants
S.24.XX.P.00000.09.001.11
ENEL GREEN POWER
PAGINA - PAGE
Engineering & Construction
1 di/of 26
ANNEX 2
ELECTRICAL WORKS
S 2 4 X XP 0 0 0 0 0 0 9 0 0 1 1 1
CLASSIFICAZIONE PUBBLICO AZIENDALE RISERVATO RISTRETTO RIF. ARCHIVIO
CLASSIFICATION PUBLIC COMPANY CONFIDENTIAL RESTRICTED ARCHIVE ID
Questo documento contiene informazioni di proprietà di Enel Green Power SpA e deve essere utilizzato esclusivamente dal destinatario in relazione
alle finalità per le quali è stato ricevuto. E’ vietata qualsiasi forma di riproduzione o di divulgazione senza l’esplicito consenso di Enel Green Power SpA.
This document is property of Enel Green Power SpA. It is strictly forbidden to reproduce this document, in whole or in part, and to provide to others
any related information without the previous written consent by Enel Green Power SpA.
CODICE – CODE
INDEX
1. OBJECT ................................................................................................................................. 3
2. MAIN DEFINITIONS AND ACRONYMS ........................................................................................ 3
3. REFERENCE DOCUMENTS ........................................................................................................ 4
1. OBJECT
The aim of this annex, as part of the General Technical Specification, is to facilitate the design and
installation of components and the works required for a fully operative PV system, with the exclusion of
the electrical cabins and all their equipment and accessories, PV modules and supporting structures,
string boxes, combiner boxes and all civil works.
3. REFERENCE DOCUMENTS
Below are listed all the attachments to the present document that shall be taken into account:
• D.24.XX.P.00000.00.003.XX SECTIONS AND DETAILS OF CABLE WAYS (TYPICAL);
• D.24.XX.P.00000.00.004.XX DETAIL CONNECTION STRING BOX (TYPICAL);
• D.24.XX.P.00000.00.005.XX CONNECTION GROUNDING SYSTEM (TYPICAL);
• D.24.XX.P.00000.11.001.XX PHOTOVOLTAIC FIELD LAYOUT AND STRING CONNECTION
(TYPICAL);
• H.24.XX.P.00000.00.006.XX DIAGRAM_EARTH;
• D.24.XX.P.00000.00.007.XX EARTH LAYOUT (TYPICAL).
“XX” is to be intended as the latest revision of the document.
The Contractor shall consider the last releases of the above documents attached.
In case of discordance between technical specifications, the Contractor shall consider what is written in
this technical specification.
The Contractor shall be compliant to the functional requirements, design criteria and system
configuration contained in this technical specification and its attachments. Where there is a conflict
between the requirements of this specification and the Contractor’s current standard
system/technology, this conflict shall be clearly reported as an exception in the Deviations/Exceptions
list, during the technical alignment process.
This technical specification defines the minimum performance level required.
CODICE – CODE
• Heat Shrink Joints or Cold Shrink Joints for MV cables, according to the required voltage level;
• all fiber optic terminals, connectors, patch cords and joints, compatible with the relevant patch
panels;
• LV AC cables between the MV delivery cabin (or HV/MV Substation) and the conversion cabins;
• meteorological monitoring units (described in EGP TS Annex 3, supply in the SoW of CU
supplier);
• wiring of the field sensors;
• wiring of the PV modules;
• string boxes and combiner boxes installation and wiring (described in EGP TS Annex 3, supply in
the SoW of CU supplier);
• fire-resistant, water-resistant and rodent-proof sealant/barrier for all cable conduits and cable
entries (i.e. Multiseal malt by MULTITECNO or similar); polyurethane foams are not allowed;
• labels for all cables and all equipment (pre-parallel boxes, string boxes, combiner boxes,
inverters, MV switchgears, MV cubicles, etc.), as per the EGP code specified hereafter; all labels
shall be UV-resistant, weather-proof and shall be printed on a hard support;
• PPE (Personal Protection Equipment) for the Operation & Maintenance activities according to the
specific risk assessment;
• warning signs providing information on prohibitions, obligations, dangers and safety; quantity
and type of warning equipment and signs shall be compliant with the current norms and
regulations of the specific country.
The requirements of this specification are binding and any change shall be agreed in advance with EGP.
7. SAFETY REQUIREMENTS
The Contractor shall comply with all local norms and laws for that specific country, instructions and
operational procedures issued by EGP. For Italy and rest of the European countries, the following
norms and laws as stated below have to be considered. Additionally, the Contractor shall comply with
the equivalent corresponding norms (as stated below) according to the location of the project.
• EN 50110-1/2 (CEI 11-48/49) “Operation of electrical installations”;
CODICE – CODE
• CEI 0-15 “Maintenance of the MV/LV electric substations of the final costumers/users” (only for
Italy);
• EN 50110-1:2014-01 (CEI 11-27) “Works on electrical installations”;
• CEI 0-10 “Electrical installations - Maintenance criteria” (only for Italy).
All devices and equipment for electrical risk assessment shall be properly sized according to their
application (nominal voltage, grounding fault, current and short-circuit duration).
All machineries, as well as the equipment used for carrying out the work, shall comply with the current
safety regulations for that country. In case of machineries and components made in foreign countries,
reference should be made to the regulations valid for that specific country (where the PV plant will be
installed), IEC norms, EN norms and EGP requirements.
All electrical installations shall guarantee Insulation Class II (Insulation Class II is valid only for Italy.
Equivalent insulation class should be identified and considered for other countries).
insulated;
• it’s forbidden every electrical continuity of electrical mass/exposed-conductive-parts between
the PV plant and the HV/MV substation.
In case the fence is of metallic type (both PV plant and HV/MV substation), the following prescriptions
shall be respected:
• every 20 m the metallic fence must be insulated (refer to Annex1);
• the metallic fence must be locally grounded but not connected to the PV plant ground grid;
• one copper ground wire (min. cross-section area 50 mm², min. laying depth 0.5 m) for the
fence earthing shall be 1 meter outside the fence perimeter in a ring configuration and shall not
be connected to the main grounding system (it could be connected only if touch & step voltages
report points out dangerous voltages);
• if a ground wire goes below the fence, then the fence shall be of insulated type for minimum 2
meters on both the sides (for instance using insulated panels 2m left and 2m right from the
ground wire).
• in case HV/MV substation and PV plant grounding systems are interconnected, a direct buried
horizontal stranded copper cable, shall be installed outside the HV/MV substation area,
positioned at 1 meter from the fence perimeter in a ring type configuration.
According to the documents “D.24.XX.P.00000.00.005.XX_CONNECTION GROUNDING SYSTEM
(TYPICAL)”, “H.24.XX.P.00000.00.006.XX_DIAGRAM_EARTH” and “D.24.XX.P.00000.00.007.XX”, a list
of the main components for the PV plant grounding system to be installed is mentioned below:
• A direct buried horizontal stranded copper cable shall be appropriately sized (min. cross-section
area 50 mm²) according to the fault current (the highest possible value obtained from the grid
and the PV plant, multiplied by 1,05). This grounding cable shall be the only equipotential
connection among the electrical cabins and the support structures. This grounding cable shall
run inside the LV and MV cables trenches assuring that the safe distance is maintained as per
the norms and laws. Furthermore, the same grounding cable (min. cross-section area 50 mm²)
shall run at 1 meter from the metallic support structures in a ring type configuration;
• Metallic support structures shall be interconnected together with 35mm2 copper cables;
• Insulated copper cables (for the Italian norms, the Yellow/Green equipotential conductors) with
at least 25 mm² of cross-section area in order to connect all the metallic support structures and
all the electrical equipment in the field;
• The direct buried horizontal copper cables shall connect the grounding terminals of each cabin
including the HV/MV Substation and/or the cabins supplied by EGP.
The grounding system shall include the following elements for each cabin:
• 1 (one) direct buried ring grounding conductor (stranded copper cable) along the perimeter of
the buildings and sized according to the fault current of the system (see picture below);
CODICE – CODE
• 2 (two) diagonal conductors (stranded copper cable), as per the picture shown below, in order
to connect four points of the ring grounding system made of stranded copper as described
above;
• 4 (four) galvanized steel rods in the concrete manholes properly designed for the system fault
current with a minimum size of 50x50x5 mm and 2 m in length;
• 2 (two) grounding conductors (at least 50 mm² cross-section insulated conductors – in Italy the
yellow/green conductors) in order to connect the grounding collector for each room of the cabin.
Anyway, the Supplier must verify with a specific grounding system study if further
components/equipment are necessary in order to be compliant with the applicable norms and laws.
The Contractor shall supply and install connection accessories, stainless steel bolts, lugs and crimp
joints and all the components needed to complete the work as per the latest technical state of art.
The above mentioned components shall be designed and purchased according to the electrical
calculations. In case some of those components will be buried or casted in concrete, the Contractor
shall take a picture of the components before the casting and show the details of the installation for
approval by EGP. The Contractor shall carry out the proper grounding measures and prepare the
grounding calculation report, in compliance with local applicable laws and norms (in Italy, Decreto
Legislativo 462/01 and modifications and integrations), stamped and signed by a Professional Engineer
(PE). The measures shall be carried out taking into account the complete grounding system including
the cabin grounding system.
The Contractor shall assess the risk of a lightning strike and properly design an Anti-Lightning System
in order to protect the PV plant both during its construction and its operational life (approximately 30
years) in full compliance with local norms and laws. The international standard to be considered is the
IEC/EN 62305 (“Protection against lightning”).
The Contractor shall strictly comply with the requirements as per the module installation manual in
order to guarantee proper grounding of the modules.
CODICE – CODE
• SB #.#.#: the digit from the right indicates the incremental number of the string box
e.g.: SB 1.2.3= String box 3 connected to the Inverter 2, in the Cabin 1;
• S #.#.#.#: the digit from the right indicates the incremental number of the string connected to
the string box, e.g. S 1.2.3.4= String 4 connected to the String box 3, related to the Inverter 2,
in the Cabin 1.
Then, in case of pre-parallel boxes, the following code shall be considered:
• PP #.#.#.#: the digit from the right indicates the incremental number of the pre-parallel box,
e.g. PP 1.2.3.4= Pre-parallel box n.4 connected to the String box 3, related to the Inverter 2, in
the Cabin 1;
• S #.#.#.#.a: the fifth letter on the right identifies the PV string of a pre-parallel arrangement of
strings before the input of the string box, e.g. S 1.2.3.4.a= String a of the Pre-parallel box 4,
connected to the String box 3, related to the Inverter 2, in the Cabin 1.
In case more than one conversion/transformation cabin (more than one PV subfield) are installed in the
same area, the numbering should start from the beginning since it is assumed that the subfields are
independent of each other.
The cable-trays shall be arranged in a way to minimize any visual impact. The trays shall be laid down
either using the free space of the support structure or within the channels or metal walkways anchored
to support structures. The cables shall be mechanically protected up to the string boxes. The supply of
the channels or metal walkways, the related accessories (bends, T branches, etc.), nuts and bolts and
whatever is required to carry out the work properly is the responsibility of the Contractor.
no self-powered solution);
• Supply and installation of connections for data signals from trackers (in case of PV trackers, no
Wi-Fi solution);
• Supply and installation of operational and safety connections;
• Supply and installation of connections for sensors, control and network signals cables, cable
ways, cabling and relevant connections.
The Contractor shall arrange and identify all the cables incoming from and outgoing to any electrical
equipment.
All the cableways for the incoming and outgoing lines of the cabins shall be sealed using suitable
rodent-resistant, fire and waterproof resin-based thermoplastics. The Contractor shall install pierceable
and resealable barriers inside the cableways in order to allow additional cables to be fed through the
cableways in case of future modifications and/or expansions of the system.
13. CABLEWAYS
According to the document “D.24.XX.P.00000.00.003.XX_SECTIONS AND DETAILS OF CABLE WAYS
(TYPICAL)”, the cables shall be segregated depending on the function and the voltage level (i.e. power
cables, digital signal cables, analog signal cables, communication signal cables, etc..).
The Contractor shall foresee dedicated and segregated cableways (cable trays and/or conduits) for:
• LV power cables;
• MV power cables;
• Signal and field sensors cables;
• Anti-fire cables;
CODICE – CODE
• Data network cables (fiber optic, serial communication cable, Ethernet cables, etc..).
The internal diameter of the pipes shall be at least 1.5 times (for piping and cable ducts) of the
maximum external diameter of the cable bundle. Pipes and cable ducts shall be large enough to allow
the cables to be easily unthreaded and re-threaded without damaging the cables or the pipes. The
number of cables installed inside the cable tray shall not occupy more than 50% of the space available
in the channels. All signals cables shall be separated (piping, ducts, manholes, etc.) from power cables.
Power cables with different nominal voltages shall be separated by suitable barriers or shall have the
insulation fit for max voltage. All cables shall be mechanically protected by flexible conduits and cables
gland.
The layout of the trenches shall reflect the arrangement of the rows of the PV plant and in general shall
be parallel to them. Unless otherwise indicated, the trenches shall converge at the edge of the internal
road network and/or pathways and stay reasonably far from the foundations of the support structures.
A 100mm wide “underground warning tape” shall be laid at approximately 30 cm above the live cables
and for the entire trenches.
The specific requirements for the different buried cables are listed below:
• For MV lines: Red tape with the wording “WARNING MV ELECTRICAL CABLES XX kV”;
• For LV lines: Green tape with the wording “WARNING ELECTRICAL CABLES”.
1
The voltage level indicated in this section is indicative; please to refer to the system voltage level specified in the
General Technical Specification.
CODICE – CODE
mechanical, and environmental requirements of this specification. Optical fibre splices within individual
cable lengths shall not be permitted.
The cable must contain no metallic elements (dielectric) unless armouring is requested.
The buffer tube(s) shall be filled with a non-hygroscopic, non-nutritive to fungus, electrically non-
conductive, homogenous gel. The gel shall be free from dirt and foreign matter. The gel shall be readily
removable with conventional non-toxic solvents.
Cables shall be anti-rodent and resistant to UV radiation from the sun and details are to be provided as
to the measures taken to attain the necessary immunity to ensure a guaranteed design lifetime of at
least 25 years.
In the following list the main technical particulars are reported:
1. No. of Fibres: 24
2. Type of Fibres: Single mode
3. Mode field diameter:
a) at 1300 nm: 9.2 ± 0.4 µm
b) (ii) at 1550 nm: 10.50 ± 1.0 µm
4. Cladding diameter: 125 µm ± 1.0µm
5. Mode field concentricity error: ≤ 0.5 µm
6. Cladding non-circularity: ≤ 1.0 %
7. Attentuation Coefficient
(a) at 1290-1340 nm: < 0.36 dB / km
(b) at 1550 nm: < 0.25 dB / km
8. Chromatic dispersion coefficient
a) at 1300 nm: < 3.5 ps / nm.km
b) at 1550 nm: < 18 ps / nm.km
9. Proof Test: ≥ 1%
10. Polarisation Mode Dispersion (PMD): ≤ 0.5 ps / √ km
11. Fibre Curl (ROC): ≥ 4.0 m
12. Macrobending performance: < 0.05 dB
13. Minimum Bending Radius (mm): ≤ 150 mm
14. Crush Resistance: ≥ 2500 N
15. Impact Resistance: ≥ 10x 2 Nm
Finally, regarding the configuration/layout of the fiber optic, each block of 40 MWac of conversion units
shall be connected to the step-up station/delivery station with a fiber optic cable (with 24 cores) in a
physical ring configuration. It is not allowed to reclose the fiber optic ring via the patch panel installed
inside the conversion unit.
Table 2
Soil Type of insulation
Temperature
[°C] PVC EPR
10 1.10 1.07
15 1.05 1.04
20 1.00 1.00
25 0.95 0.96
30 0.89 0.93
35 0.84 0.89
40 0.77 0.85
45 0.71 0.80
50 0.63 0.76
55 0.55 0.71
60 0.45 0.65
Table 2 – The correction factor k1 to be applied when the soil temperature is different from
20°C.
• k2 is the correction factor to be applied for groups of three-phase circuits installed on the same
level, according to IEC 60364-5-52:2001 Table A.52-18 for cables laid directly in the ground
(see Table 3 below); IEC 60364-5-52:2001 Tables A.52-19, A.52-20, A.52-21 shall be
CODICE – CODE
considered for cables in ducts in the ground and cables in the air.
Table 3
Single-core / Multi-core cables
Table 3 – The correction factor k2 to be applied for groups of three-phase circuits installed
on the same level (direct buried cables).
• k3 is the correction factor to be applied for burial depth different from the value used as a
reference, equal to 0.8 m (see Table 4 below);
Table 4
Burial depth [m] 0.5 0.8 1.0 1.2 1.5
Correction Factor 1.02 1.00 0.98 0.96 0.94
Table 4 – The correction factor k3 for burial depth different from the value used as a
reference, equal to 0.8 m.
• k4 is the correction factor to be applied for soil thermal resistivity different from the value taken
as a reference equal to 2.5 K * m / W, according to IEC 60364-5-52:2001 Table A.52-16 for
both single-core and multi-core cables (see Table 5).
Table 5
Single-core / Multi-core tables
Soil thermal resistivity [K x m / W] 1.0 1.5 2.0 2.5 3.0
Correction factor 1.18 1.10 1.05 1.00 0.96
Table 5 - The correction factor k4 for soil thermal resistivity different from the value taken as
a reference equal to 2.5 K * m / W.
Where the soil thermal resistivity is not known, k4 shall be equal to 0.96 and applied to the cable rated
current @ 2.5 K * m / W.
Therefore, the cross section of cables shall be designed in order to have:
Iz’ = Iz * Ktot = Iz * k1 * k2 * k3 * k4 ≥ Ib,
where:
• Ib = The operating current; on the DC side, the reference value for the operating current is
equal to 1.25 Isc. Hence, Iz’ = Iz x Ktot ≥ 1.25 Isc;
• Iz = The permissible current rating of the cables reported in the datasheets or in the IEC
60364-5-52 tables.
CODICE – CODE
In particular, the Contractor shall calculate a corrective coefficient (Ktot) as product of the coefficients
k1, k2, k3 and k4, where:
• k1 is the correction factor to be applied when the ambient air temperature is different from
30°C or the ambient ground temperature is different from 20°C, according to IEC 60502-2:2005
Tables B.10 and B.11 (see Table 6 below);
Table 6
Type of laying
Temperature [°C]
Air laying Ground laying
10 1.07
15 1.04
20 1.08 1.00
25 1.04 0.96
30 1.00 0.93
35 0.96 0.89
40 0.91 0.85
45 0.87 0.80
50 0.82 0.76
55 0.76
60 0.71
Table 6 - The correction factor k1 to be applied when the ambient air temperature is different
from 30°C or the ground ambient temperature is different from 20°C.
• k2 is the correction factor to be applied for groups of three-phase circuits installed on the same
level, according to IEC 60502-2:2005 Table B.19 for single-core cables laid directly in the
ground (see Table 7 below); IEC 60502-2:2005 Tables B.18, B.20 and B.21 shall be considered
for single-core cables in buried ducts or three-core cables;
Table 7
Single-core directly buried cables
Table 7 – The correction factor k2 to be applied for groups of three-phase circuits installed
CODICE – CODE
• k3 is the correction factor to be applied for burial depth different from the value used as a
reference, equal to 0.8 m, according to IEC 60502-2:2005 Table B.12 for directly buried cables
(see Table 8 below); IEC 60502-2:2005 Table B.13 shall be considered for cables in buried
ducts;
Table 8
Burial depth [m] 1.00 1.25 1.50
Correction factor
Single-core < 185mm2 0.98 0.96 0.95
Single-core > 185mm2 0.97 0.95 0.93
Three-core 0.99 0.97 0.96
Table 8 – The correction factor k3 to be applied for burial depth different from the value used
as a reference, equal to 0.8 m (direct buried cables)
• k4 is the correction factor to be applied for soil thermal resistivity different from the value taken
as a reference, equal to 1.5 K * m / W, according to IEC 60502-2:2005 Table B.14 for directly
buried single-core cables (see Table 9 below); IEC 60502-2:2005 Tables B.15, B.16 and B.17
shall be considered for single-core cables in buried ducts or three-core cables; for cross-sections
over 400mm2 the manufacturer tables shall be considered;
Table 9
1 2 2,5
16 1.15 0.89 0.82
25 1.16 0.89 0.81
35 1.16 0.89 0.81
50 1.16 0.89 0.81
70 1.17 0.89 0.81
95 1.18 0.89 0.80
120 1.18 0.88 0.80
150 1.18 0.88 0.80
185 1.18 0.88 0.80
240 1.18 0.88 0.80
300 1.19 0.88 0.80
400 1.19 0.88 0.79
Table 9 – The correction factor k4 to be applied for soil thermal resistivity different from the
value taken as a reference equal to 1.5 K x m / W (single-core directly buried cables)
Where the soil thermal resistivity is not known, k4 shall be equal to 0.77 and applied to the cable rated
current @ 1.5 K * m / W.
Therefore, the cross-section of cables shall be chosen in order to have:
Iz’ = Iz * Ktot = Iz * k1 * k2 * k3 * k4 ≥ Ib,
CODICE – CODE
where:
• Ib = The operating current [A];
• Iz = The admissible current rating [A] of the cables reported in the datasheets or in the IEC
60502-2 tables.
The MV cables shall be sized also for the maximum short-circuit current by taking into account the
maximum temperature admissible for the cable during a short period of time (normally 250°C).
∗
The formula is: (A)
√
Where:
• ICC is the maximum short-circuit current admissible for the cable [A]
• K is factor of the conducting material
• S is area of conductor (mm2)
• t is the duration of short-circuit (s)
Once the installation is completed, all MV cables shall be tested and certified. The minimum tests are
the insulation test and/or the partial discharge test.
All MV connections shall have maximum one MV cable per phase and the maximum cable cross-section
must be 630mm2. Furthermore, the maximum apparent power [MVA] per MV feeder depends on the
MV level [kV] according to the following Table 10.
Table 10 - The maximum apparent power [MVA] per MV feeder, depending on MV level [kV].
The Contractor shall be aware that the maximum apparent power values per MV feeder, in any case
could be lower than the ones in Table 10 above, according to ambient temperature (k1), groups of more
circuits on the same level (k2), laying depth (k3), soil thermal resistivity (k4), maximum voltage drop
per single MV feeder and maximum AC active power losses for the entire PV park (according to next
section).
Segment between the delivery point / metering point (or HV/MV Substation) and the
1.00% *
last cabin
Segment between the MV Switchgear and the MV/LV transformer 0.10% *
Segment between the MV/LV transformer and the inverter output 0.40% *
Segment between the inverter input and the string boxes 1.00% **
Segment between the string boxes and the PV strings (including pre-parallel boxes) 1.00% **
* The showed values shall be considerate as maximum ones that shall be respected in each path. The
average value of AC losses shall not overcome 0.5% inside the entire PV park.
** The partial DC voltage drops in the two segments (inverter / string boxes and string boxes / PV
strings) may be different from the showed values, but the total voltage drop shall be maximum 2%.
The average value of DC losses shall not overcome 1% inside the entire PV park.
For the DC voltage drop verification, maximum operating values under standard conditions (STC)
(Imppt and Vmppt) shall be used as reference values.
• the cables shall not be subjected to any sudden bending, denting, scratching or stretching of
the sheath;
• the temperature of the cables along the entire length and during the time they could be bent or
straightened shall never drop below the value indicated in the technical standards and
manufacturer requirements;
• the cables shall not be subjected to any bending with a radius lower than the indicated value in
the technical standards and manufacturer requirements;
• the connection shall be carried in accordance with best practices (e.g. by using heat shrinking
sheathing etc.).
The MV junction points laid in the same trench shall be at least 2 meters away from each other. The
cables shall never be directly buried in the walls. The Contractor shall use pipes (PVC pipes, Transit
multi-cable ROXTEC or analogue type) for any wall crossing. The cables shall be sealed with self-
hardening expanding foam with anti-rodent certification.
In general, the laying and installation of cables shall be done in accordance with the installation
instructions as per the current norms and regulations and the technical documentation provided by EGP.
The unraveling of the cable into the pipe shall be done after an inspection and after a proper cleaning of
the pipe. The cable shall be inserted into the pipe with a suitable device designed to prevent any
damage on the sheath. During the installation of the cable the Contractor shall avoid any damages on
the external insulation layer of the cable. All cable conduits and cable entries shall be sealed with fire
resistant, water resistant and rodent proof sealant/barrier (i.e. Multiseal Malt by MULTITECNO or
similar).
Cables shall be identified by using clear legible labels arranged before their entry into the panel. These
labels shall last for at least twenty years.
In case aluminum cables are used and that are not compatible with the installed equipment (in terms of
rigidity, cross-section, etc.) the Contractor shall provide with interface boxes to fit cables and
equipment.
The Contractor shall guarantee the proper matching of aluminum and copper cables to avoid any issues
that may arise due to the different metals. To avoid that issues EGP requires to install bimetallic
copper/aluminum connectors.
For each cable the Contractor shall provide a document containing the following information:
• point of departure;
• point of arrival;
• length;
• routing path;
• for each wire, the terminal block and the terminal where the wire is attested.
indicating the names of the coordinators and a list of applicable quality assurance procedures. The QCP
proposed by the Manufacturer during the tender phase shall be examined and approved by EGP.
EGP will indicate which tests it intends to be convened for, in order to be present with its own test
coordinator (refer to the indications of the section “Plans and Controls” of the General Technical
Specification); for tests where the presence of EGP inspectors is not deemed necessary, the
Manufacturer shall anyway release the related certification. Failure by the EGP’s representative to
participate in notified and convened tests (non-binding) will not entail any stoppage of the production
cycle of the Manufacturer. Following the positive outcome of all scheduled tests, the Manufacturer shall
deliver the certifications.
15. WARRANTY
Unless otherwise specified in the contract of service, the Contractor shall:
• guarantee a two years warranty from the completion of the works on installation, equipment,
materials and accessories;
• provide a technical support during the duration of the warranty (two years) and assure a
prompt intervention within 24 hours from the call;
• identify and replace the broken or faulty component/s and extend the warranty period for
additional 12 months from the date of the intervention on the component/s.
each system;
• Tests and inspections of the entire project;
• Assistance with commissioning;
• Any operations for the reinstatement of services during the warranty period;
• Fiber optic for the connection of the security and antitheft system up to the control panel of the
delivery cabin;
• Any other thing necessary even if not expressly stated, to guarantee the correct operation of
the equipment in accordance with the principles and instructions contained in the documents
provided by EGP.
All the supplies and necessary work shall be included, in order to obtain, from the electrical point of
view, a fully functional system.