MUSE ED / Trouble Shooting Ctrl No.: MUSE ED-TS-03-0


Page: 108/127
○ Operation CPU
TCD 191 Duplicated door open/close command (ER_DOOR_COMMAND) Detection
○ Speed CPU
Application Si220

[Meaning] The open&close signals are inputted to DCD PCB at same time [Countermeasures]

1. Check the voltage of DOC PCB as below

[Explanation] When the When the


command occurs command cut
If the door close &open command are inputted to DCD PCB, it sends an error DO-07(open) 0.7V ±0.1V 24V ±10%
signal to CP through car communication
DO-06(Close) 0.7V ±0.1V 24V ±10%

2. Check the signals through ANN (2 row-13 & 14 column)


3. Even if the open and close command are cut the voltage is not
24V ±10%, check the followings
1) Remove the DO connector from DOC-140 PCB and
proceed the insulation test between 1&2 and earth.
2) If 1) is normal, replace DOC-140 PCB.
4. Replace DCD-231 PCB
Part: TCD Code
MUSE ED / Trouble Shooting Ctrl No.: MUSE ED-TS-03-0
Page: 109/127
○ Operation CPU
TCD 192 Door position trouble Detection Application Si220
○ Speed CPU

[Meaning] Door position detector error [Countermeasures]

( SED1 Door application )

[Explanation] 1. Check the JN2 connector of DCD-231 PCB


JN2-1(red), JN2-2(white), JN2-3(Green), JN2-4(black)
2. Check the voltage of JN2 connector
( SED1 Door application )
1) JN2-1 ⇔JN2-4: 15V±10%
2) in case the voltage is not 15V±10%, remove the JN2
In case of the trouble of door thermal, under voltage, over voltage & current,
connector and check the voltage on DCD-231 PCB.
TCD192 occurs.
3) If the voltage of 2) is 15V±10%, the R.E is detective.
4) But if the voltage of 2) is not 15V±10%, the DCD-231 PCB
detective.

3. Check the phase voltage of JN2 connector


1)Check the phase voltage between JN2-4 and JN2-2(A phase)
as turning a motor with manual.
When the motor stops, if the voltage is 15V±10% or 1V less is
detected any one time in 10times trial, the phase A is normal.
2) Check the phase B as Phase A.
3) The Phase A & B is normal, the DCD-231 PCB is detective.

2. Check if the OLS and CLS are working normally.


Part: TCD Code
MUSE ED / Trouble Shooting Ctrl No.: MUSE ED-TS-03-0
Page: 110/127
○ Operation CPU
TCD 193 Door voltage trouble(ER_DOOR_VOLTAGE) Detection Application Si220
○ Speed CPU

[Meaning] Door input voltage error [Countermeasures]

[Explanation] 1. Check the PJ1 connector of DCD-23X PCB.


The voltage between PJ1-17 and PJ1-8 is
AC 110V±20%. (normal)
Error detected and transmitted to operation CPU when the input voltage of
DCD-231 PCB is over or low voltage.
2. Above 1 is normal : DCD-23X PCB is troubled
1) Low voltage : under AC 77V (110V -30%)
2) High voltage : over AC 154V (110V +40%)
3. Above 1 is abnormal, check below items:
1) Main power voltage is within AC323V~AC418V. (normal)
2) 1) is normal : Control transformer is troubled.
Part: TCD Code
MUSE ED / Trouble Shooting Ctrl No.: MUSE ED-TS-03-0
Page: 111/127
○ Operation CPU
TCD 194 Door motor thermal trouble (ER_DOOR_MOTOR_THERMAL) Detection
○ Speed CPU
Application Si220

[Meaning] Door motor over_heat error [Countermeasures]

1. Check if the door motor is real heat .

[Explanation] * Caution : Motor frame temperature is over 100℃ when the


motor were real heat.

2. In case that the door motor is real heat


Error detected and transmitted to operation CPU when the motor coil
1) Remove any obstacles to door open/close on car
temperature is over 130℃.
or landing sill.
2) Refer to the countermeasure 1), 2) of TCD 191.

3. In case that the door motor is not real heat.


Check if between PJ2-4 and PJ2-5 pins are shortage
after power off and disconnecting PJ2 connector from
DCD-23X PCB.
1) Shortage: DCD-23X PCB is troubled
2) Open: Motor is troubled.
Part: TCD Code
MUSE ED / Trouble Shooting Ctrl No.: MUSE ED-TS-03-0
Page: 112/127
○ Operation CPU
TCD 195 Door motor over current trouble(ER_DOOR_OC) Detection Application Si220
○ Speed CPU

[Meaning] Door motor over_current error [Countermeasures]

1. Check the below items (Motor side) after disconnecting


PJ2 connector from DCD-23X PCB.
[Explanation] 1) Check the isolation of between PJ2-1,2,3 pin and Earth.
2) Check resistance value between PJ2-1 and PJ-2 pin.
Value for 50W Door Motor: 17.6Ω±10%
Value for 80W Door Motor: 10Ω±10%
Error detected and transmitted to operation CPU when the over current flows in
3) Check the resistance as above PJ2-1,3 and PJ-2,3 pin.
inverter part .
4) In case that the test result were not good, motor is troubled

2. If the result is normal, check below Items after power off.


1) Check the isolation of between PJ2-1,2,3 pin and Earth.
2) Check the isolation at PJ2-1,2 , PJ2-1,3 and PJ-2,3 pin.

3. Check shortage between DCD-23X & door box frame.

4. Replace DCD-23X PCB.


Part: TCD Code
MUSE ED / Trouble Shooting Ctrl No.: MUSE ED-TS-03-0
Page: 113/127
○ Operation CPU
TCD 196 Photo-Shoe input error Detection Application Si220
○ Speed CPU

[Meaning] Reopen count by Photo sensor [Countermeasures]

1. Check the photo condition and connection


2. Check the Spec address 07CE. Default data is ’05’.
[Explanation] 3. Check the landing door switch and car door switch.

If the door is reopened 5 times continuously by photo shoe, it will be display error.
And a case that car door is opened fully as detecting ‘DOLS’ signal but system
detects that car door switch or landing door switch is closed.
Part: TCD Code
MUSE ED / Trouble Shooting Ctrl No.: MUSE ED-TS-03-0
Page: 114/127
○ Operation CPU
TCD 199 ER_PCB_Protect_Fail (Korea domestic only) Detection Application Si220
○ Speed CPU

[Meaning] The security approval for PCB is failed. [Countermeasures]


When a DOC or DCL PCB is replaced, it detects error.
Or SPEC data is damaged, it also detects an error 1. If this error is founded in your field, request new PCB.
And the wrong PCB that makes TCD199 must be back to
[Explanation] manufacturer with claim letter.

Whenever a DOC PCB or DCL PCB is replaced in Korea, the security system in
CP request serviceman’s ID and approval number. If this requirement is not
satisfied, the PCB protection program will not removed. So, its operation shall be
locked.
Part: TCD Code
MUSE ED / Trouble Shooting Ctrl No.: MUSE ED-TS-03-0
Page: 115/127
○ Operation CPU
TCD 200 CNET LON communication trouble Detection Application Si220
○ Speed CPU

[Meaning] DPRAM communication between Main LON and i186 does not operate [Countermeasures]
1. If the trouble doesn’t disappear after system reset on DOC-140,
Check if ROM(OS ROM) of DOC-140 & ROM of main LON are
mounted correctly.
[Explanation]
1.It will detect an error if the 4th bit(DPRAM: 0x10) of input port of i186 2. If the trouble doesn’t disappear after performing 1 item above,
system is ‘HIGH’ condition and a condition that the TOKEN is not passed Replace ROM(OS ROM) of DOC-140 & ROM of main LON.
through LON continuously more than 6 cycle (180msec).
3. Replace DOC-140 even if nothing is improved after performing
2. In case the main LON CPU of DOC-140 PCB is unable to work. item 2 above.
(The 2nd bit(CNET_CPU_ERR:0x04) of input port of i186 system is
‘HIGH’ condition)

I186EC_Port3_Input & 0x20


Coil[VALID_186_TOKEN]

*SYS_INPUT_PORT & 0x10 Coil[VALID_186_TOKEN]


+1 err_count

0x9300

err_count > 5
TCD 200

*SYS_INPUT_PORT & 0x04

[Condition]
LON LED on DOC-140 will light off.
Part: TCD Code
MUSE ED / Trouble Shooting Ctrl No.: MUSE ED-TS-03-0
Page: 116/127
○ Operation CPU
TCD 202 Car communication trouble Detection Application Si220
○ Speed CPU

[Meaning] Car LON communication trouble on main OPB( OPB ID = 1 ) [Countermeasures]


1. Check the ON/OFF state of LON LED in DOC-140
(0.06 sec. cycle when normal).
2. Check the ON/OFF state of DCL-243 LED
[Explanation] (0.2 sec. cycle when normal).
3. Verify if the connector(SC) for LON communication is
CND_OPB_Node_State & 0x01 normally connected.
TCD 202
4. Verify if OPB ID is 1 (DIP 1 ‘ON’).
5. Verify if DCL-243 has a terminal resistor(DIP 8) set.
6. Measure the resistance between pins No. 1, 2 of SC connector.
If it is approximately 10 OHM, normal.
If there is no resistance, check for disconnection.
* TCD 202 is detected on MAIN LON and write in DPRAM.
7. Replace ROM(OS ROM) of DOC-120 & ROM Main LON.
variable of appropriate data is read and saved is CND_OPB_Node_State.
8. Replace DCL-243.
9. Replace DOC-140.

[Condition]
LON LEDs of DOC-140 and DCL-243 are flickering with 1.2 sec. cycle
Part: TCD Code
MUSE ED / Trouble Shooting Ctrl No.: MUSE ED-TS-03-0
Page: 117/127
○ Operation CPU
TCD 205 DES communication trouble Detection Application Si220
○ Speed CPU

[Meaning] DES PCB LON communication trouble ( OPB ID = 4 ) [Countermeasures]

1. Check the flickering state of LON LED in DES-102 PCB


( 1 sec. cycle when normal ).
[Explanation] 2. Verify if the connector(P7) for LON communication is
normally connected.
CND_OPB_Node_State & 0x04 3. Measure the resistance between pins No. 3, 4 of P7 connector.
TCD 205 If it is approximately 10 OHM, normal.
If there is no resistance, check for disconnection.
4. Replace ROM(Main LON ROM) of DOC-120 &
DES-100 PCB ROM.
5. Replace DES-102 PCB
6. Replace DOC-140 PCB.

[Condition]
LON_OK LED of DES PCB is hold
Part: TCD Code
MUSE ED / Trouble Shooting Ctrl No.: MUSE ED-TS-03-0
Page: 118/127
○ Operation CPU
TCD 206 ER_REAR_OPB_COM Detection Application Si220
○ Speed CPU

[Meaning] Car LON communication trouble on main OPB( OPB ID = 5 )


1. Check the ON/OFF state of LON LED in DOC-140
(0.06 sec. cycle when normal).
2. Check the ON/OFF state of DCL-243 LED
[Explanation] (0.2 sec. cycle when normal).
3. Verify if the connector(SC) for LON communication is
normally connected.
* TCD 202 is detected on MAIN LON and write in DPRAM. 4. Verify if OPB ID is 5 (DIP 1,3 ‘ON’).
variable of appropriate data is read and saved is CND_OPB_Node_State. 5. Verify if DCL-243 has a terminal resistor(DIP 8) set.
6. Measure the resistance between pins No. 1, 2 of SC connector.
If it is approximately 10 OHM, normal.
If there is no resistance, check for disconnection.
7. Replace ROM(OS ROM) of DOC-140 & ROM Main LON.
8. Replace DCL-243.
9. Replace DOC-140.
10. Check the ROM version of DCL PCB.

[Condition]
LON LEDs of DOC-140 and DCL-243 are flickering with 1.2 sec. cycle
Part: TCD Code
MUSE ED / Trouble Shooting Ctrl No.: MUSE ED-TS-03-0
Page: 119/127
○ Operation CPU
TCD 209 ER_NPLEX_MASTER_COM Detection Application Si220
○ Speed CPU

[Meaning] Communication Error to N-PLEX Module

1. Check if N-plex system is applied or not.


(If the system is applied to SPEC data where N-plex is not
configured at elevators, it will detect error)
[Explanation]
In case there is non signal reply from N-PLEX Module about 3 seconds more or <<N-PLEX - SPEC DATA>>
signal transmitting failure to N-PLEX module 4 times more, it detects an error Addr Label Contents
(TCD209)
1D00 Enable IN-PLEX application, 0x01
1D02 Car ID Lift ID under N-PLEX (0x01~0x04)

G_Signal_Wait_Counter == 0
TCD 209
2. Check the N-PLEX communication line. (SH connector)
The communication line should be twisted shield cable.
Group_Fail_Count > 3 3. Check the terminal resistor setting
(HJP-SH jumper must be connected)

※ See the N-plex manual for terminal resistor setting

[Condition] ※ If terminal resistor is not properly set, following


condition may happen
- Communication failure is happened frequently
and hall call registration is impossible.
- Lift goes under back-up operation (ACD=26)
Part: TCD Code
MUSE ED / Trouble Shooting Ctrl No.: MUSE ED-TS-03-0
Page: 120/127
○ Operation CPU
TCD 211 Other elevator trouble Detection Application Si220
○ Speed CPU

[Meaning] Communication error with other car is detected in duplex operation. [Countermeasures]

1. In case of duplex, No.1 of the SPEC1(DIP S/W) must be on.


In case of simplex, it must be off.
2. Check the condition of communication line between 2 elevators.
[Explanation] The communication line must be a shield wire.
3. Check if terminal resistor(HJP-SH Jumper) is connected.
1. In duplex, In case there is no transmission data for 1 sec. from other elevator,
In case of figure below, don’t connect terminal resistor of No. 1
the trouble occurs.
but No. 2.
2. When G/A transmission from other is failed 4 times in series, the trouble occurs.
No. 1 No. 2

HJP SH
HJP SH

SH SL SL SH

DHG-16X

DHG-16X

DHG-16X
Part: TCD Code
MUSE ED / Trouble Shooting Ctrl No.: MUSE ED-TS-03-0
Page: 121/127
○ Operation CPU
TCD 217 Hall button jam detection Detection Application Si220
○ Speed CPU

[Meaning] When hall button is being pushed continuously, the trouble is detected. [Countermeasures]

1. Check the floor where button jam is detected.


The floor can be checked by ‘A21E’.
[Explanation]
2. If abnormal, replace the button.
When hall button is being pushed for the time(Default :180 sec.) that is designated
by SPEC, TCD 217 will occur.

Button_Jam_Detect[0][UP_INDX]
TCD 217

Button_Jam_Detect[0][DN_INDX]

The floor button Jam detected

Address Floor
0x9954 1st floor ~ 8th floor UP Button
0x9955 9th floor ~ 16th floor UP Button
0x9956 17th floor ~ 24th floor UP Button
0x9957 25th floor ~ 32nd floor UP Button
0x9958 1st floor ~ 8th floor DOWN Button
0x9959 9th floor ~ 16th floor DOWN Button
0x995A 17th floor ~ 24th floor DOWN Button
0x995B 25th floor ~ 32nd floor DOWN Button

Each floor is matched with each Bit.


Part: TCD Code
MUSE ED / Trouble Shooting Ctrl No.: MUSE ED-TS-03-0
Page: 122/127
○ Operation CPU
TCD 223 Hall CPU trouble Detection Application Si220
○ Speed CPU

[Meaning] 1 or more communication trouble on Hall Station B/D, detected. [Countermeasures]


1. Check the floor of communication not activated by
ANN - A21E and the type of button to check DHG-16X of the
failed floor for failure.
[Explanation]
[Checking of hall button trouble]
Enter as below on annunciator
HND_Fail_Node[ 0 ]
TCD 223 K: A21E
ADDR:DAT K : 8762E
0x8762
If 8762=x02(0000 0010)
DFG-16X of 2nd floor is failure.
If 8762 =x30(0011 0000)
* HND_Fail_Node : 4Byte( 32bit ) DFG-16X of 5th, 6th floors are failure.

To see floor 8th or higher is required to enter KEY-PAD ‘0’ of


annunciator.

2. Verify if controller DOJ PCB XHA MIC is connected,


Address Floor
and see if voltage between HA plug pin 3-4 of DHG-16X at
0x8762 1st floor ~ 8th floor failed floor is DC24V.
3. Verify if the ID of DHG-16X at failed floor is set correctly.
0x8763 9th floor ~ 16th floor 4. Resistance between HA connector pin1-2 in DHG-16X at the
0x8764 17th floor ~ 24th floor failed floor must be 2±0.5Ω.
If not so, the pulse transformer(PT1, position in DHG-16X)
0x8765 25th floor ~ 32nd floor in DHG-16X is a failure.
5. Check between pin 3-4 of HA connector in DHG-16X at the
Each floor is matched with each Bit. failed floor. if it is open circuit, replace DHG-16X.
Ex) ADDR:0x8762 - DATA:0x04 means 3rd floor is out of order.
Part: TCD Code
MUSE ED / Trouble Shooting Ctrl No.: MUSE ED-TS-03-0
Page: 123/127
○ Operation CPU
TCD 224 Hall nod trouble (All) Detection Application Si220
○ Speed CPU

[Meaning] Communication error with all floor in hall line is detected [Countermeasures]

1. Check if the jumper(HJP-SH) of DOC-140 is set correctly.


2. Check if XHA MIC of DOJ-130 PCB is connected.
3. Check if SH connector of DOC-140 is connected.
[Explanation] 4. Check if terminal resistor(120Ω) in diverging box at bottom floor
is connected.
5. Check if the volt of XHA MIC of DOJ-130 PCB is DC24V after
Normal_Floor[ 0 ] NCD_P_SVC_Fl[ 0 ]
check_floor removing XHA MIC .
1) 1th ~ 8th floor: XHA 3-4 is to be DC24V.
2) 9th ~ 16th floor: XHA 5-6 is to be DC24V.
3) 17th ~ 24th floor: XHA 7-8 is to be DC24V.
check_floor
TCD 224 4) 25th ~ 32th floor: TB2 (Terminal Block) 5-6 is to be DC24V.

H_Data_Receive_Wait_Counter == 0

[Condition]
When TCD224 occurs, operation mode would be ACD26 and perform backup
operation.
Part: TCD Code
MUSE ED / Trouble Shooting Ctrl No.: MUSE ED-TS-03-0
Page: 124/127
○ Operation CPU
TCD 236 TCI LOCK trouble Detection Application Si220
○ Speed CPU

[Meaning] Abnormal E.M switch ON is detected under CAR TOP MAINT operation. [Countermeasures]

1. ERO switch ON / OFF in E&I panel


2. Main power OFF / ON
[Explanation]

When TCD236 occurs, TOCI switch is switched to NORMAL side under Car TOP
Maintenance operation.
Part: TCD Code
MUSE ED / Trouble Shooting Ctrl No.: MUSE ED-TS-03-0
Page: 125/127
○ Operation CPU
TCD 237 CRT communication trouble Detection Application Si220
○ Speed CPU

[Meaning] When communication error between CRT & CP occurs [Countermeasures]

1. Check if CRT option is applied.


(When SPEC has CRT option even if a project does not apply
for CRT, the trouble will occur)
[Explanation]
Crt_Id ADDR:0x0002
In case that there is no receive data from CRT for 8 sec., TCD237 would be occurs.
Crt_Operation ADDR:0x0020

2. Check if the connection between CRT & CP is correct.


CRT_Comm_Error_Counter == 0 (SM connector)
TCD 237
Communication cable should be twisted & shielded.
3. Check if HJP-SL jumper is connected.
Part: TCD Code
MUSE ED / Trouble Shooting Ctrl No.: MUSE ED-TS-03-0
Page: 126/127
○ Operation CPU
TCD 238 DES PCB trouble Detection Application Si220
○ Speed CPU

[Meaning] DES PCB error occurs [Countermeasures]

Refer to explanation of DES-102 PCB on PCB part

[Explanation]

In case of below condition, TCD238 will occur.


1. DES parameter error
2. Speed error
3. Temperature error
4. LCD error
5. Over speed detected
6. Communication error
7. Battery fault
8. Direction error
Part: TCD Code
MUSE ED / Trouble Shooting Ctrl No.: MUSE ED-TS-03-0
Page: 127/127
○ Operation CPU
TCD 240 ER_RUSSIA_OPZX Detection Application Si220
○ Speed CPU

[Meaning] When elevator stops a floor, a landing door at another floor is [Countermeasures]
opened Then, it detects an error (Russia code area only)
1. Check if the Russia code application
1) In case of Si210, The following 2 options effect on this
error
[Explanation] 2) In case of Si25x and Si23x, Russia code(0042) effects on
this error
The elevator will be stop immediately under normal operation mode, the error is
hold until the main power is turned off. It does not detects this error under <<OPZX error detects Spec>>
inspection mode.
Addr Label Contents
0042 Russia Russia code application, 0x01
Normal Mode VI_OPZX
TCD240 07CA OPZX Landing door detection function
application, 0x01
803C

2. Check the input buffer ( 0x803C)and voltage level at connector.


Normal : Input buffer is 0x00, Voltage level is 48V(24V-Si25x).
Error : Input buffer is 0x01, Voltage level is 0V
In case of Si25X, Check the DOX-100 PCB의 connection

3. Check the each landing door condition.

4. This error can be erased by power reset in CP.