Professional Documents
Culture Documents
CAN Interface For FMS: Important!
CAN Interface For FMS: Important!
Introduction
Introduction
This document contains information on the FMS standard. The FMS standard is an More information on the FMS standard can be found at www.fms-standard.com.
open interface developed by several truck manufacturers. FMS-Standard description
version 03 is supported. More information on the C137 connector is found in the C137 document – Connector
for FMS.
The C137 connector is Scania’s interface for FMS standard messages.
Detailed information on CAN messages for FMS is found in the CAN Specification
IMPORTANT! for FMS document which is in English.
For FMS standard messages, it is not permitted to connect to any other connector or
other CAN bus. Incorrect connection can cause functional disorder.
The C137 connector is green and is located under the central electric unit in the cab.
The twisted-pair cable is blue and white. CAN-low is connected to pin 9, CAN-high
351 572
is connected to pin 6.
Connector C137
343 377
Location of C137
Note:
According to section 5.2.1 SAE J1939-21, revised version July 1998, priority bits in
message identifiers must be filtered out and ignored by the receivers.
General guidelines
• Control units connected to a CAN bus must be able to handle up to 100% CAN
bus load with the correct messages with no significant functional limitations or
malfunctions.
• Under normal circumstances the CAN bus load should never exceed 80%.
• Avoid closing control loops over the CAN because the guaranteed access time is
relatively long and fast control loops require a lot of bandwidth. If closed control
loops over the CAN are still required, then they must be fully capable of sending
the necessary CAN messages using only half the transmission frequency.
Connection to FMS-CAN
Topology
The topology is primarily a bus cable with the nodes connected to the bodybuilder’s < 30 m
FMS-CAN network with at least 0.1 metre between each node.
C137 ECU X
• The length of the cables should not exceed 30 metres (main cable) between the > 0.1 m
connector in the truck and the control unit with the other termination resistor.
<3m
• If more than one control unit is connected, the length of the cables between the
main cable and control unit should not exceed 3 metres.
• The cables should be as short as possible to minimise the effect of electromagnet-
ic interference.
ECU Z ECU Y
• The number of control units in the bodybuilder’s FMS-CAN network should not
348 622
exceed 9.
The figure shows the principle of the bodybuilder’s FMS-CAN network topology:
R
Depending on the other control units connected to the CAN bus, there must be a 120
Ohm termination resistor in the control unit which is connected to the FMS-CAN in-
9
terface for bodybuilders. CAN_L CAN_L
b346398
If the control unit is not equipped with an internal termination resistor, an external
termination resistor must be connected as close to the control unit as possible (see
illustration).
A number of different systems can be connected to the cable harness of the body-
builder’s FMS-CAN bus. Certain systems have a built-in termination resistor and
others are unterminated.
The table shows when there is to be a termination resistor in connector C137 or in the
control unit connected to C137.
During normal operation, when the starter key is in the drive position, a message
should not be validated as missed (time-out) until at least 5 times the message period
time. A longer fault validation time is permitted.
During the engine starting sequence, when the starter motor is turning, the supply
voltage can be extremely low. Therefore, communication from the FMS-CAN can-
not be guaranteed during this sequence. For this reason, no fault codes related to
FMS-CAN communication should be set when the system voltage is below 18 V.
When the starter key is turned to the drive position, the FMS-CAN communication
will be started within 10,000 ms. A message cannot be considered missing until after
10,000 ms + 5 x the message period time. Example: If a message has a period time
of 100 ms it cannot be considered missing until after 10,000 + 5 x 100 = 10,500 ms.
Longer fault validation times are permitted.
Source addresses
The source addresses according to the table are used for messages that are forwarded
from Scania’s FMS-CAN bus to the bodybuilder’s FMS-CAN bus via the C137 in-
terface. The addresses in the table must not be used by any other control unit in the
bodybuilder’s FMS-CAN network. This may lead to clashes and functional distur-
bances.
Note:
The table shows the addresses currently in use, but addresses may be added in the
future.