Download as pdf or txt
Download as pdf or txt
You are on page 1of 7

Electric Power Systems Research 53 (2000) 105 – 111

www.elsevier.com/locate/epsr

Analysis of overvoltages in overhead ground wires of extra high


voltage (EHV) power transmission line under
single-phase-to-ground faults
I. Dudurych a, E. Rosolowski b,*
a
State Uni6ersity, L6i6 Polytechnic, 12 Bandera str., 290646 L6i6, Ukraine
b
Wroclaw Uni6ersity of Technology, ul. Wybrzerze Wyspianskiego, 27, 50 -370, Wroclaw, Poland

Received 25 January 1999; accepted 6 April 1999

Abstract

Overhead ground wires (GW) of extra high voltage (EHV) power transmission lines, apart from lightning-induced overvoltage
protection are frequently used for carrier-current communication. In this case the ground wires are suspended on insulators, the
dielectric strength of which should be sufficient for the line operational conditions. The insulation level is defined from the
condition of the single-line-to-ground (SLG) fault, thus insulator protecting spark gaps should not be flashed-over during such
conditions — in order to maintain continuity of the communication channel along the line. Overvoltages during such faults
depend on many parameters such as fault place, fault angle, pre-fault load etc. Therefore, designers should investigate the problem
for determination of the worst-case scenario. In this paper, dependence of the overvoltages on 750 kV power transmission line
ground wires upon the SLG fault place and pre-fault load of the line in transient and steady states is investigated. The analysis
was performed by using dynamic arc model incorporated into the EMTP program. The provided simulations show that
adequately introduced primary and secondary arc models are decisive factors for an accurate simulation of the electromagnetic
phenomena in the EHV transmission lines during an arc crossing-over (here the primary arc plays an important role) and during
so called dead-time, when the secondary arc takes place. This paper gives some recommendations for the insulator strings
coordination in the 750 kV earth wires on the basis of computer simulation results. © 2000 Elsevier Science S.A. All rights
reserved.

Keywords: Transmission line; Fault simulation; Arc model; Ground wires; EMTP

1. Introduction short circuits, particularly single-phase-to-ground


faults, is very important, being even a decisive factor
Lightning surge protection is the main function of for the GW construction in both cases.
ground wires (GWs), suspended on towers of extra high The GW designed for carrier-current communication
voltage (EHV) power transmission lines. However, re- systems should maintain continuity of the channel
cently GWs are often used as channels for carrier–cur- along the whole communication circle and be insulated
rent communication systems for utility as well as relay from the ground. Therefore, all GW sections are con-
protection purposes [1]. Moreover, in some countries a nected through very small resistances (for conduction
symmetrical three-phase voltage system, formed from of carrier–currents) and insulated from the earth on all
two ground wires and an earth, is used to deliver power the towers. In order to maintain the continuity of
to small communities along the line [2]. It should be carrier–current communication systems the insulation
noted that the GW schemes in the two above cases are level of GW should be sufficient for flash-over protec-
different. Nevertheless, the influence of the unbalanced tion in continuous duty and for insulation dielectric
strength recovery after the fault clearing.
* Corresponding author. Tel.: +48-71-3203786.
GW insulators of the EHV lines are shunted by spark
E-mail addresses: idudur@polynet.lviv.ua (I. Dudurych), rose@ gaps for protection from heavy arcs during lightning-in-
pwr.wroc.pl (E. Rosolowski) duced flash-over and unbalanced short-circuits. If GW

0378-7796/00/$ - see front matter © 2000 Elsevier Science S.A. All rights reserved.
PII: S 0 3 7 8 - 7 7 9 6 ( 9 9 ) 0 0 0 4 9 - 8
106 I. Dudurych, E. Rosolowski / Electric Power Systems Research 53 (2000) 105–111

This paper is organized as follows. First, the selected


transmission system is described (Section 1). Section 2
gives detailed information on modeling of the system
elements, especially the primary and secondary arc
models. Results of overvoltage investigations during
Fig. 1. Single-line diagram of the analyzed system. SLG fault at the line are presented in Section 4, and
Section 5 draws the conclusion.
is used for the relay protection channel these spark gaps
should not be flashed-over during unbalanced faults.
2. Description of the studied system
Thus insulator strings of GWs should be chosen to
withstand maximum voltage of the unbalanced short-
circuit. The scheme of the studied system is presented in Fig.
Ground wires designed for carrier – current communi- 1. It consists of Ukrainian and Hungarian power sys-
cation systems usually comprise a stranded steel core tems connected through a 750 kV power transmission
surrounded by aluminium wires. Such wires are chosen line of 459 km length. The line has four transposition
for the light line attenuation. Suspension of properly sections of phase wires of 85.4, 163.3, 134.6 and 74.2
conducting GWs, grounded at the ends of the line km in length (Fig. 2). Phase wires are triple bundles of
through small inductances of carrier – current protec- AC-500/65 wires on the Hungarian sections and quad
tors, leads to noticeable decreasing of the zero sequence bundles of AC-400/93 wires on the Ukrainian side.
reactance value of the line. It is because currents circu- Ground wires are adequately specified as AC-95/142 on
lating through the ground wires, towers and earth the Hungarian side and AC-95/141, and AC-70/72 on
create a magnetic field, there is a decrease in the the Ukrainian side.
resulting magnetic couplings with the phase wires. On Sources are characterized by the following
the other hand, decreasing zero sequence impedance impedances:
leads to increasing single-line-to-ground (SLG) fault Z1 = 0.3+ j 30.9V, Z0 = 0.4+ j 36.8V
current, which can be used for determination of a
definitive value of voltage induced in the GWs [3]. from Ukrainian side (PS1),
Therefore, EHV transmission lines with overvoltage Z1 = 0.7+ j 80.8V, Z0 = 0.9+ j 86.8V
ground wires used for lightning surge protection as well
from Hungarian side (PS2).
as for carrier–current communication and relay protec-
tion systems, should be properly tested under single- The line is equipped with two shunt reactors of
phase-to-ground fault conditions in the line. To explain 2× 110 MVA rating power placed at both ends. Two
the concept and for investigation of the above phenom- earth wires are grounded at both ends of the line
ena from the point of view of GW insulation coordina- through small inductances of carrier–current protec-
tion, a real 750 kV transmission line was taken for tors. They are crossed over 12 times along the line (Fig.
study. 2).

Fig. 2. Transposition and crossing over scheme for the considered line.
I. Dudurych, E. Rosolowski / Electric Power Systems Research 53 (2000) 105–111 107

adapted to the considered problem. Primary arc occurs


during flash-over of the line insulator string, caused by
lightning stroke or other reasons. Secondary arc follows
the primary one when the faulted phase circuit breaker
trips, as is sustained by mutual coupling between the
healthy and faulted phases.
The dynamic volt-ampere characteristics (VACs) of
the electric arc have features of hysteresis. For the
primary arc simulation the VAC shape was taken from
Fig. 3. Position of phase conductors and ground wires. the investigation results [6] for the heavy-current arcs
with peak current of 1.3 and 14 kA. For the secondary
3. Model of the 750 kV power transmission system arc simulation the VAC shape was taken from the
investigation results for the low-current arcs with peak
As it is seen from Fig. 2, for adequate representation current of 145 A [6]. Extensive study in [7,8] has shown
of the transmission system the used model should exem- that the dynamic volt–ampere characteristics of the
plify the system structure with detailed representation electric arc can be exactly simulated by the empirical
of all basic components. differential equation

3.1. Power systems dgk 1


= (1)
dt Tk(Gk − gk)
Power systems connected to the line are represented
where gk is the dynamic arc conductance, Tk is the time
in EMTP by their positive and zero sequence
constant; Gk is the stationary arc conductance; sub-
impedances using 51, 52, 53-type branches [4] for mutu-
script k indicates the kind of arc (k=p for primary arc;
ally coupled RL elements. It was concluded from the
k= s for secondary arc).
performed experiments that equivalent capacitances of
The stationary arc conductance Gk can be physically
the systems have no significant influence on the ob-
interpreted as the arc conductance value when the arc
tained results, therefore, they were not included in the
current is maintained for a sufficiently long time under
model.
constant external conditions. So, Gk is the static charac-
teristic of the arc, which can be evaluated from
3.2. Power transmission line
i
Power transmission line is represented by the dis- Gk = (2)
(uok + R i )lk
tributed-parameter line model [4] of 16 sections as in
Fig. 2. Each uniform section is considered to be un- where i is the arc current; uok is the arc voltage drop per
transposed phase and uncrossed-over two ground wire unit length along the main arc column; lk is the arc
element (five-phase line model). The travelling-wave length; R is the constant part of the arc cathode and
model is based on d’Alambert’s solution of the lossless anode resistance.
single-phase line equations in combination with the For the primary arc uop is constant and equal to
phase variables transformation into mode variables [5]. about 15 V/cm for the range of current 1.3–24.0 kA [9]
The line parameters were calculated from tower geome- and lp may be assumed constant and somehow wider
try and bundle conductors dimensions (Fig. 3), aver- than the length of the line insulator string. The value of
aged over three phases. the constant voltage parameter of the secondary arc uos
Frequency dependence of transformation matrices is is evaluated empirically on the basis of numerous inves-
being taken into account by appropriate dominant fre- tigation results in the range of low values of current,
quency selection during the transient. Solution equa- collected in [9]. For the range of peak currents Is, from
tions in the modal domain are independent from each approximately 1–55A it can be roughly defined as
other and may be reached by the algorithm for the uos = 75I −
s
0.4
V/cm [7]. The arc length of the secondary
single-phase line using its modal travel time and its current ls changes with time, and for relatively low wind
modal characteristic impedance. In this model the line velocities (up to 1 m/s), can be approximated as ls =
resistance is taken into consideration by adequate inclu- 10lptr for tr \ 0.1s but when the secondary arc reigni-
sion of lumped resistances [4]. tion time tr 5 0.1s ls = lp.
The secondary arc reignition voltage (in V/cm) is
3.3. Arcing single phase faults calculated by empirical formula [7] as

Arcing single-phase faults are simulated using models 5+ 1620Te


ur = (3)
of the primary and the secondary arcs adequately (2.15+ Is)(tr − Te)
108 I. Dudurych, E. Rosolowski / Electric Power Systems Research 53 (2000) 105–111

where Te is the secondary arc extinguishing time (when 3.5. Shunt reactors
tr 5 Te, ur =0); Is is the peak value of current on the
volt –ampere arc characteristic. Shunt reactors are represented by the ordinary RL
Time constants are determined as follows: uncoupling branches.
The developed model has been used for transient
akIk
Tk = (4) study under the single-phase-to-ground faults.
lk
where ak is the empirical coefficients.
The empirical coefficients ak can be obtained by 4. Simulation experiments
fitting Eq. (1) with Eq. (2) and Eq. (4) to match the
experimental VACs of the heavy- and low-current arcs, For investigation of the problem many different cases
accordingly. were analyzed. Consider the following scheme, the sin-
The described models of the primary and the sec- gle-phase-to-ground fault in phase C of the line from
ondary arcs were incorporated into EMTP through the the 750 kV power transmission system shown in Fig. 1
MODELS capability [4] using the TACS (transient is initiated at 5 ms. Circuit breakers of the sending and
analysis of control systems) – controlled type-91 time- receiving power systems open their contacts after 70
varying resistances. Besides that, the secondary arc ms. The secondary arc extinction occurs approximately
model comprises type-11 TACS-controlled switch. at 140 ms.
The implementation of the arc model is shown in Fig. As the GW are considered in this application to serve
4. It operates as follows, the integration step gk is as the communication channel for the emergency con-
evaluated by Eq. (1) and Eq. (2) on the basis of arc trol schemes, the ground wire insulation and protecting
current and voltage values from the previous step. spark gaps should not be flashed over during SLG
Type-11 switch is being opened when the secondary arc faults. Therefore, spark gaps were not simulated in the
extinguishing conditions occur and closed when the study.
recovery voltage exceeds the dielectric strength of In normal duty the voltage induced in the GW is
heated air around the short-circuit arcing column by relatively low (500–700 V for this case) and does not
previous arc ignition. define the GW insulation characteristics. They are
The simulation results obtained with the EMTP im- defined by voltages induced during single-phase-to-
plemented arc model were compared with the real-field ground faults. Therefore, the simulation experiments
on the power transmission line 1150 kV [10] and good for faults occurring in different locations along the line
matching was obtained. have been conducted. Maximum values of the over-
voltages under the SLG faults along the line are pre-
3.4. Circuit breakers sented in Fig. 5. It can be seen that the maximum
values of overvoltages depend upon the fault location
Circuit breakers are presented by time-controlled and are concentrated in the middle region of the line. It
EMTP switches [4], which are opened when current should be mentioned that maximum overvoltages occur
goes through zero after the prescribed opening time and in the vicinity of the position of the applied single-
closed after the prescribed closing moment, when the phase-to-ground fault. Exceptions are for the cases
current passes through zero. The same switches are when the fault occurs at one end of the line. Moreover,
used in the short circuit making scheme for the short- overvoltages occurring after the fault clearing are also
circuit initialization. dangerous and may reach values commensurate with
those induced by the fault current, especially when the
fault occurs far away from the substation.
As is seen from Fig. 5, the insulation level of the GW
in the middle of the line should be chosen higher than
that of the rest. For example, according to the maximal
GW overvoltage value of 206.3 kV (in node 10 of Fig.
2, under the SLG fault at this location) the number of
insulators n in the GW insulator chain (string) of the

! " ! "
750 kV line should be chosen from [1]:
umax 206.3
n=int = int =7
Emdll 1.1 · 29
Fig. 4. Primary and secondary arc models implementation: u, i is the
voltage and current at the fault place; Ra is the non-linear resistance where umax is the GW insulator string affecting voltage,
of the arc; on – off-signal switching-on when the secondary arc kV; ll is the leakage path length, cm (for the glass
reignites, and switching-out when it extinguishes. insulators of the 750 kV line ll = 29 cm); Emd =(0.5–
I. Dudurych, E. Rosolowski / Electric Power Systems Research 53 (2000) 105–111 109

Fig. 5. Overvoltages under faults at nodes: 1, 5, 10, 13, 16 in the line.

Fig. 6. Ground wires voltage measured at node 1 during SLG fault at node 13.

1.1) kV/cm (maximum value)-moisture discharge elec- and in nodes 1 and 15—only three insulators for
tric field intensity, int{ } is the rounding to the nearest ground wire suspending.
greater or equal integer value. At the same time the In Fig. 6, overvoltages in node 15 (see Fig. 2)
number of insulators in node 2 may be chosen as n= 5 (18.5 km from the sending end of the line) induced by
110 I. Dudurych, E. Rosolowski / Electric Power Systems Research 53 (2000) 105–111

the SLG short-circuit in node 13 (74.8 km from is seen from Figs. 6 and 7 that overvoltages in GWs
the sending end) are shown. Similar picture of over- drastically depend upon location along the line and they
voltage are observed in node 1 (21 km from the receiving are higher in GW located just over the faulted phase.
end). In Figs. 8 and 9 GW’s currents at the beginning
In Fig. 7. GW’s overvoltages in node 5 (145 km from and at the end of the line under considered faults
the receiving end of line) induced by the SLG fault in are shown. These currents contain high harmonics, which
node 13 (74.8 km from the sending end) are shown. It influence the communication quality along the GW.

Fig. 7. Ground wires voltage measured at node 5 during SLG fault at node 13.

Fig. 8. Ground wires current at the beginning of line during SLG fault at node 13.
I. Dudurych, E. Rosolowski / Electric Power Systems Research 53 (2000) 105–111 111

Fig. 9. Ground wires current at the end of line during SLG fault at node 13.

5. Conclusions given by the Deputy Director of the Western Dispatch


Center Relay Service in Lviv Mr. V. Ivanonkiv.
This paper presents a method for assessment of
overvoltage induced in overhead ground wires during
single-line-to-ground faults. The value of this over-
voltage can be used for insulation coordination when
References
GWs are used for communication purposes. For analy-
sis of the problem in the EHV lines the detailed model [1] S.H. Braclawski, A.I. Gershengorn, S.B. Losev, Special Calcula-
of the considered system is presented. The primary and tions of the Extra High Voltage Power Transmissions, Energoat-
secondary arcs were adequately adapted and incorpo- omizdat, Moscow, 1985, pp. 275 – 301.
rated into EMTP model. [2] A. D’Ajuz, M.I. Martinez, F.A. Blanko, Supplying Small Loads
A digital model of the EHV transmission line is at Reasonable Cost, Spectrum, 1996, pp. 34 – 35.
[3] I.M. Dudurych, UHV power transmission line electromagnetic
developed for the investigation of phenomena in the
transients in the single-phase reclosing currentless pause, Proc. of
overhead ground wires under the arc during single- the 7th Int. Symposium on Short Circuit Currents in Power
phase-to-ground faults. It has been shown that analysis Systems, Warsaw 1996, report 1.33.
of these faults are vital for insulation coordination for [4] H. Dommel, Electromagnetic Transient Program, BPA, Port-
ground wires. land, Oregon, 1986.
[5] J.R. Marti, Accurate modeling of frequency-dependent transmis-
The accurate arc model gives the opportunity to
sion lines in electromagnetic transient simulations, IEEE Trans.
obtain realistic data on overvoltages and overcurrents on Power Apparatus and Systems, PAS-101 1 (1982) 147–155.
in ground wires under the arc single-phase-to-ground [6] A.P. Strom, Long 60-cycle arcs in air, Trans. AIEE 65 (1946)
faults, which are decisive from this purposes. 27 – 37.
These investigations have shown that the insulation [7] Y.H. Song, R.K. Aggarwal, A.T. Johns, Digital simulation of
fault arcs on long-distance compensated transmission systems
level of GW at the ends of the line may be taken lower
with particular reference to adaptive autoreclosure, European
than those positioned at the middle of it. Transactions on Electric Power, Vol. 5. September/October
1995, pp. 315 – 324.
[8] M. Kizilcay, T. Pniok, Digital simulation of fault arcs in power
systems, ETEP, Vol. 1, No. 1, January/February 1991, pp.
Acknowledgements 55 – 60.
[9] A.S. Maikopar, Arc Short Circuits at Power Transmission Lines,
Energia, Moscow, 1965.
The authors appreciate the valuable information on [10] I. Dudurych, E. Rosolowski, Simulation of the EHV power
the technical data of the real power transmission line,. system using EMTP, Techn. Electrodyn. 1 (1998) 57 – 62.

You might also like