Download as pdf or txt
Download as pdf or txt
You are on page 1of 22

MOMENT CONNECTION BETWEEN COLUMN AND BEAM

TYPE OF CONNECTION :- BEAM TO COLUMN CONNECTION

BEAM ISMB500 COLUMN ISMB600

Over all Depth, h = 500 mm. Over all Depth, hcol = 600 mm
Width of flange, bf = 180 mm. Width of flange, bfcol = 210 mm
Width of outstanding flange b = 90 mm. Thk of flange, tfcol = 20.8 mm
Web thickness, tw = 10.2 mm. Thk of Web, twcol = 12 mm
Flange thickness, tf = 17.2 mm. Depth dcol = 558.4 mm
Depth between the flanges, d = 465.6 mm. Root radius, rcol = 20 mm
Root radius, r = 17 mm.
C/S Area, A = 110.7 cm2
3
Section modulus, Ze = 1808.7 cm
Section modulus, Zp = 2075 cm3

Classification of material (Grade of steel) IS: 2062 Fe 410


(IS:800-2007,Table-1, IS:2062)
Based on grade of steel Fe 410 and thickness of flange which is less than or equal to 40, fy = 240 N /mm2
Yield stress, fy = 240 N/mm2 (IS:800-2007,Table-1, IS:2062)
2
Ultimate stress, fu = 410 N/mm (IS:800-2007,Table-1, IS:2062)
Actual Max Shear Force coming in the member, V = 146 KN
Percentage of actual shear force coming into the
= 23%
member wrt its total capacity
Shear connections are designed for (in percentage) = 60%
Moment connections are designed for (in percentage) = 100%
Partial safety factor for shear in yielding, ϒmo = 1.1 (IS:800-2007,Table-5, Cl 5.4.1)
Partial safety factor for ultimate stress, ϒm1 = 1.25 (IS:800-2007,Table-5, Cl 5.4.1)
Partial safety factor for connection weld, ϒmw
Partial safety factor for shop weld = 1.25 (IS:800-2007,Table-5, Cl 5.4.1)
Partial safety factor for field weld = 1.5 (IS:800-2007,Table-5, Cl 5.4.1)

SECTION CLASSIFICATION

Constant ε  250 
 =  
 = 1.02
 fY  (IS:800-2007,Table-2)
Outstanding element of compression  b 
  = 5.23
flange  t 
 f 

For Web of an I-section  d 


  = 45.65
 tw 

Actual Max Axial Force coming in the member, Af = 43 KN

Constant r1 = Actual average axial stress


Design compressive stress of web alone

= Af / (d*tw)
fy
= 43 * 1000
465.6 * 10.2 * 240

= 0.04

Constant r2 = Actual average axial stress


Design compressive stress of overall section

= Af / (A)
fy
= 43 * 1000
110.7 * 240 * 100

= 0.02

Flange Classification:
b/tf ≤ 9.4ε
Web Classification
d/tw ≤ 84ε / (1+r1)

Section is a PLASTIC SECTION (CLASS-1) (IS:800-2007,Table-2)


DESIGN FORCES FOR BEAM

Design Shear Strength of the beam, Vd = fy * Aw (IS:800-2007, Cl 8.4, Cl 8.4.1)


ϒmo * √3

where, for major axis bending Aw = h*tw (IS:800-2007, Cl 8.4.1.1)


Aw = 5100.0 mm2

Assuming that the shear is transferred only through the web of the beam
Hence, Aw is considered only for major axis bending
Shear capacity of the beam, Vd = 240 * 5100
1.1 * √3
Vd = 642.4 KN
Connection is designed for 60 % capacity
So, Shear capacity for connection Vd1 = 385.4 KN

MOMENT CAPACITY OF BEAM

Check for web buckling under shear before yielding (IS:800-2007, Cl 8.2.1)

As d/tw = 45.65 , ≤ 67 ε, So Beam section is not suseptible to web buckling (IS:800-2007, Cl 8.4.2)

As V ≤ 0.6 Vd
To avoid irreversible deformation under serviceability loads, Md shall be less than 1.2 *Ze* fy /ϒmo incase of
simply supported and 1.5 *Ze* fy /ϒmo in cantilever beams

Md = Plastic design moment of the whole section disregarding


high shear force effect considering web buckling effects

Support condition for this check = Simply Supported

  *Zp * fy  1.2 * Ze * fy For Simply Supported beams


M d =  b  <
  mo  ϒmo (IS:800-2007, Cl 8.2.1.2)

where βb = 1.0 for Plastic and Compact Sections

Md = 1 * 2075 * 240
1.1* 1000

= 452.73 KNm

1.2 * Ze * fy = 1.2 * 1808.7 * 240


ϒmo 1.1

= 473.55 KNm

And 452.73 < 473.55 KNm

Hence 452.73 KNm will be considered

All beam to column connections shall be designed to withstand a moment of at least 1.2 times the full
plastic moment of connected beam. (IS:800-2007, Cl 12.11.2.1)
1.2Md = 452.73 * 1.2 KNm
= 543.28 KNm
DESIGN FORCES SUMMARY

Connection is designed for 120% Moment capacity and 60% Shear capacity of section
Design Shear (0.6 Vd) = 385.4 KN
Design Moment (1.2 Md) = 543.3 KNm

Flange force = 1.2 Md


h
= 543.3
500.0

= 1086.6 KN

CALCULATION OF WIDTH OF COVER PLATES (B1 & B2)

TOP COVER PLATE WIDTH

Max width of top cover plate, B1 = Flange width + 2* size of weld +4


Consider size of weld , w1 = 10.0 mm
(field weld) B1 = 180 +2* 10 +4
= 204.0 mm
Say, B1 = 205.0 mm

BOTTOM COVER PLATE WIDTH

Min width of bottom cover plate, B2 = Flange width + 2* size of weld +4


Consider size of weld, w2 = 10.0 mm
(field weld) B2 = 180 +2* 10 +4
= 204.0 mm
Say, B2 = 205.0 mm
CALCULATIONS OF THICKNESS FOR COVER PLATES (T1 & T2)

TOP COVER PLATE THICKNESS (T1)

Design strength of Top plate in tension can be only because of yielding

Ag * fy (IS:800-2007, Cl 6.2)
Tdg =
ϒmo

Assuming thickness of the top plate, T1 = 25.0

Based on grade of steel Fe 410 & thickness of top plate which is less than or equal to 40, fyq for top plate = 240 N /mm2

fyq = Yield stress of stiffener


fyq = 240 N/mm2 (IS:800-2007,Table-1,
IS:2062)
Equating this design strength in tension to the flange force

1086.56 * 1000 = Ag * 240


1.1
2
Ag = 4980.07 mm
Therefore, Thickness of the top plate
T1 = Ag mm
B1

= 4980.07 mm
205.0

= 24.3 mm

BOTTOM COVER PLATE THICKNESS (T2)

Design strength of Bottom plate in tension can be minimum because of yielding, rupture or block shear

Assuming thickness of the top plate, T2 = 25.0

Based on grade of steel Fe 410 & thickness of top plate which is less than or equal to 40, fyq for top plate = 240 N /mm2

fyq = Yield stress of stiffener


2 (IS:800-2007,Table-1,
fyq = 240 N/mm
IS:2062)
Design Strength Due to Yielding of Gross Section
Ag * fy (IS:800-2007, Cl 6.2)
Tdg =
ϒmo
Equating this design strength in tension to the flange force
1086.56 * 1000 = Ag * 240
1.1
2
Ag = 4980.07 mm
Therefore, Thickness of the bottom plate
T2 = Ag mm
B2

= 4980.07 mm
205.0
= 24.3 mm
Design Strength Due to Rupture of Critical Section

0.9*An*fu (IS:800-2007, Cl 6.3.1)


Tdn =
ϒm1
Equating this design strength in tension to the flange force

1086.56 * 1000 = 0.9*An* 410


1.25

An = 3680.8 mm2
Therefore, Thickness of bottom plate

T2 An
=
B2-2*18

3680.8
=
169.0

= 21.8 mm

CALCULATION FOR LENGTH OF COVER PLATES (L1 & L2)


Let,
a = Weld length
Size of weld for top plate , w1 = 10.0 mm
Size of weld for bottom plate , w2 = 10.0 mm
Throat thickness of weld, t = 0.7s

TOP COVER PLATE

Equating
Weld strength = Tensile force in flange

(2 * atp + B1) * t * fu = 1086.6 KN


√3* ϒmw
atp = Weld length for top plate
For field weld
(2 * atp + 205) * 0.7 * 10 = 1086.56 * 1000* √3 * 1.5 (IS:800-2007, Cl 10.5.7.1.1 &
410 Table 22 & k = 0.7)

atp = 389.3 mm
However providing atp = 750 mm

BOTTOM COVER PLATE


Equating
Weld strength = Tensile force in flange
(2 * abp) * t * fu = 1086.6
√3* ϒmw

abp = Weld length for bottom plate


For field weld
(2 * abp) * 0.7 * 10 = 1086.56 * 1000* √3 * 1.5 (IS:800-2007, Cl 10.5.7.1.1 &
410 Table 22 & k = 0.7)

abp = 491.8 mm
However providing abp = 820 mm

Provide Length of cover plates


Top plate, atp = 750 mm
Bottom plate, abp = 820 mm

DESIGN OF BEARING BRACKET

Assume length of the bracket, L3 = 150 mm

CHECK FOR DEPTH OF BEARING PLATE (D)


ss =
s ==
000
..7.
7
q
q
7
q
**
*
r
r




r

v
v
v p
p
p

Check for Eccentric Shear

Depth of the bearing plate is decided based on weld (w3) length required ((IS:800-2007,Table-1, IS:2062,
fu = 410 IS:814-1991,Table-5, )
Assuming thickness of the plate = 16 mm

Assume, size of weld W3 = 8 mm

Assume depth of bearing plate (D) as = 400 mm


Permissible stress for shop weld  fu   1  (IS:800-2007,Table-5,Cl 10.5.7)
= 
 *
 
 3  
 mw

= 189.37 N/mm2

Section modulus of weld group Zw = 2 * t * D * D/6


= 2*0.7*8 * 400*400/6
3
= 298666.67 mm

Direct shear stress, q = Shear force (IS:800-2007, Cl 10.5.9)


2 * D *t

= 385.4 * 1000
2 * 400 * 0.7 * 8

2
= 86.03 N/mm

Normal stress due to bending moment, fa = M


Zw
= Shear force * e
Zw
where e = (L3/2)+15

= 90 mm

fa = 385.4 * 1000 * 90 (IS:800-2007, Cl 10.5.9)


298666.67

2
= 116.14 N/mm
fu
= f a + 3q 2 
2
Resultant stress, fe (IS:800-2007, Cl 10.5.10.1.1)
3 *  mw
2
= 188.92 N/mm
≤ 189.37 N/mm2 , Hence OK
DESIGN OF THICKNESS OF BEARING PLATE (T3)

From Bearing consideration

Total shear force to be carried out by the bearing plate should always be less than its capacity of bearing.
Bearing strength of the plates is given by
A q * f yq
Fpsd = (IS:800-2007, Cl 8.7.5.2)
where, 0 . 8 *  mo
Aq = Area of stiffener in contact with flange

Based on grade of steel Fe 410 & thickness of stiffeners which is less than 20, fyq for stiffeners = 250 N /mm2

fyq = Yield stress of stiffener (IS:800-2007,Table-1,


2
fyq = 250 N/mm IS: 2062)

Ymo = 1.1
So to get min thickness of the bracket, equating

Shear force to be transferred through bracket = Bearing strength of the plate


Fx = Fpsd

385.4 = Aq*250 (IS:800-2007, Cl 8.7.5.2)


0.8*1.1

Aq = 385.4*1000*0.8*1.1
250
2
Area of stiffeners in contact with flange, Aq = 1356.61 mm

Thickness of bracket, T3 = Area of bracket


Effective width of bearing bracket (L3-15)

= 10.05 mm

Hence provide thickness of bearing plate, = 16 mm


Check for shear and bending stress

Vs fy
Shear stress, τab = 
t*D 3 *  mo
where
Vs = 385.4 KN

t = T3
= 16
D = 400
fy 250
=
3 *  mo √3*1.1

= 131.22 N/mm2

τab = 385.4*1000
16*400

2
τab = 60.21875 N/mm
< 131.22 N/mm2 , Hence OK

M s fy
Bending stress, fbc = 
Z ec  mo
where
Ms = Vs * e

e = 15+(L3/2)

= 90 mm

2
Zec = T3*D
6
3
= 426666.67 mm
fy
 mo f y
=
250
 mo 1.1

2
= 227.27 N/mm

fbc = 385.4*1000*90
426666.67

2
= 81.3 N/mm
< 227.27 N/mm2 , Hence OK
CHECK REQUIREMENT OF WEB STIFFENER

LOCAL CAPACITY OF THE BEAM WEB (BEARING STRENGTH) (IS:800-2007, Cl 8.7.4)

Local capacity of the beam web at its connection to the column flange is given by
f
Fw = (b1 + n2 )* tw * yw
(IS:800-2007, Cl 8.7.4)
 mo
where
b1 = Stiff bearing bracket length (IS:800-2007, Cl 8.7.1.3)
= L3 + 15 - erection gap (5mm)
= 160 mm

n2 = Length obtained by dispersion through the flange


to the web junction at a slope of 1:2.5 to the
plane of flange

= 2.5 * (tf + r)
= 85.5 mm

tw = 10.2 mm

fyw = Yield stress of the web


= 240 N/mm2

ϒmo = 1.1

Fw = (160+85.5) * 10.2*240
1.1

= 546.3 KN
≥ 385.4 KN, stiffener not required for bearing purpose,
Hence SAFE
BUCKLING STRENGTH OF THE BEAM WEB

Fcdw = (b1 + n 1 ) * t w f cd (IS:800-2007, Cl 8.7.3.1)

where Fcd = Design compressive stress

b1 = Stiff bearing bracket length (IS:800-2007, Cl 8.7.1.3)


= L3 + 15 - erection gap (5mm)
= 160 mm

n1 = Dispersion of the load through the web at 45


degrees to the level of half depth of cross section
= 0.5 *h

= 250 mm

Effective slendnerness ratio, λ = KL/r

r = Radius of gyration
r = √I
√A
3
= √ ((b1+n1)*tw )
√ (12*(b1+n1)*tw)

= 2.94 mm

Considering flanges not so restrained


Effective length, KL = 1*d (IS:800-2007, Cl 8.7.1.5(b))

= 465.6 mm
λ = 158.37
(For curve - C) (IS:800-2007, Cl 8.7.1.5,
2
Fcd = 53.86 N/mm Table-9c

Fcdw = (160+250)*10.2*53.86

= 225.24 KN
< 385.4 KN, Hence End Stiffeners are required to
prevent buckling failure of web

DESIGN OF END STIFFENERS

stiffener is required to prevent web from failing in buckling

Assuming thickness for pair of stiifeners, tq = 16 mm

Based on grade of steel Fe 410 & thickness of stiffeners which is less than 20, fyq for stiffeners = 250 N /mm2

fyq = Yield stress of stiffener (IS:800-2007,Table-1,


2
fyq = 250 N/mm IS: 2062)
Check for web buckling (with stiffeners) under shear before yielding (IS:800-2007, Cl 8.2.1)

where, Kv = shear buckling coefficient


= 5.35 for transverse stiffeners provided only at supports
(IS:800-2007, Cl 8.4.2.2)
d = Depth between flanges of the beam
tw = Thickness of beam web

Constant ε  250 
 =  

= 1 (IS:800-2007,Table-2)
 fY 

As d/tw = 45.65 , ≤ 67 ε*√(Kv/5.35), So section is not suseptible to web buckling (IS:800-2007, Cl 8.4.2)

CHECK FOR OUTSTAND

Available width/outstand of stiffener = (bf - tw - 4)/2


= (180-10.2-4)/2

= 82.90 mm
As the outer edge is not continuously stiffened,
Outstand from the face of web should not exceed = 20tqε (IS:800-2007,Cl.8.7.1.2)

where tq = Thickness of stiffener, tq


= 16 mm
Constant ε  
250
 = 


 = 1 (IS:800-2007,Table-2)
 fY 

20tqε = 20*16*1

= 320

≥ Outstand of stiffener (82.9mm), Hence OK

For design, core section should be taken with outstand limited to 14tqε
bs = minimum of 82.9mm or 14*tq*ε
(IS:800-2007,Cl.8.7.1.2)
bs = 82.9 mm
Provide plate of width ≈ 80.00 mm

CHECK FOR BUCKLING STRENGTH (IS:800-2007,Cl.8.7.1.5)

Moment of Inertia along axis parallel to web

MI considering only sttiffener, Ixxs = 16*80^3 16*80*(80/2+10.2/2)^2 *2


+
12
MI considering only web, Ixxw = (20*10.2+16)*10.2^3
12
Total Moment of Inertia Ixx = Ixxs+ Ixxw

= 6591854.4 mm4

Effective area, Ae = (2*16*80)+(20*10.2)*10.2

= 4640.8 mm2

Radius of gyration, r = √Ixx


√Ae

= 37.69 mm

Considering flanges are not so restrained


Effective Length, KL = 1.0 * d (IS:800-2007, Cl 8.7.1.5(b))
= 1*465.6
= 465.6 mm

Effective slenderness ratio λ = KL


r
= 465.6
37.69

= 12.35
fcd = 226.3 N/mm2 (IS:800-2007,Cl.8.7.1.5
Table: 9c)
Buckling strength of End stiffeners = Ae*fcd
1000
= 226.3 * 4640.8 / 1000
= 1050.21 KN
≥ 385.4 KN, Hence SAFE

Hence providing end stiffener of thickness, tq = 16 mm

Design of Weld for End Stiffener

Shear force, Fw = 385.4 KN


Thickness of stiffener = 16.0 mm

End fillet weld, normal to the direction of force shall be of unequal size with a throat thickness not less than 0.5t,
Effective min throat thickness of weld = 0.5*tw (IS:800-2007,Cl.10.5.8.5)
Effective min size of weld = 0.5*10.2/0.7 mm
= 7.28 mm

Weld strength = 0.7 * 8 * fu (IS:800-2007, Table:22)


√3*ϒmw

fu = 410
Strength of weld for shop weld = 1060.48 N/mm of weld length

Chamfer size to be considered = 15


Strength of weld = 1060.48*4*(465.6-2*15)

= 1847.7804 KN
≥ 385.4 KN, Hence SAFE

Provide a weld of size = 8.0 mm

CHECK REQUIREMENT OF CONTINUITY PLATES

LOCAL CAPACITY OF THE COLUMN WEB (BEARING STRENGTH) (IS:800-2007,Cl.8.7.4)

Local capacity of the column web at its connection to the beam is given by
f yw
Fw = (b1 + n2 )*tw * (IS:800-2007,Cl.8.7.4)
where  mo
b1 = Stiff bearing length (IS:800-2007, Cl 8.7.1.3)
= T2
= 25.0 mm

n2 = Length obtained by dispersion through the flange to


the web junction at a slope of 1:2.5 to the plane of
flange.

= 2.5 * 2 * (tfcol + rcol)


= 2.5 * 2* (20.8+20)

= 204 mm
For column, tw = twcol
= 12 mm

fyw = Yield stress of the web


2
= 240 N/mm

ϒmo = 1.1

Fw = (25+204)*12*240
1.1

= 599.56 KN
< 1086.56 KN, Web is failing in bearing strength,
Continuity plates are required.

BUCKLING STRENGTH OF THE COLUMN WEB

Fcdw = (b1 + n 1 ) * t w f cd (IS:800-2007, Cl 8.7.3.1)

where fcd = Design compressive stress


where
b1 = Stiff bearing length (IS:800-2007, Cl 8.7.1.3)
= T2
= 25.0 mm

n1 = dispersion of the load through the web at 45°, to the


level of half the depth of the crosssection.
= 0.5* h col

= 300 mm
Slendnerness ratio, λ = KL/r

r = Radius of gyration

= √I
√A
= √ ((b1+n1)*twcol3)
√ (12*(b1+n1)*twcol)

2
= √ (twcol /12)

= √ (12^2/12)

= 3.46 mm

KL = 1*d (IS:800-2007, Cl 8.7.1.5(b))

= 558.4 mm
λ = 161.39
(For curve - C) (IS:800-2007,
2
Fcd = 52.19 N/mm Cl 8.7.1.5, Table-9c

Fcdw = (25+300)*12*52.19

= 203.54 KN
< 1086.56 KN, Hence Continuity plates are required to
prevent buckling failure of web

DESIGN OF CONTINUITY PLATES (IS:800-2007, Cl 12.11.2.5)

Continuity plates are required to prevent both bearing and buckling of web

Assuming thickness of the continuity plates to be, T4 = 16 mm

Based on grade of steel Fe 410 & thickness of continuity plate which is less than 20, fyq for continuity plate = 250 N /mm2

fyq = Yield stress of continuity plate


2
fyq = 250 N/mm (IS:800-2007,Table-1,
IS:2062)

Check for web buckling (with continuity plate) under shear before yielding (IS:800-2007, Cl 8.2.1)

where, Kv = shear buckling coefficient


= 5.35 for transverse stiffeners provided only at supports
(IS:800-2007, Cl 8.4.2.2)
d = Depth between flanges of the beam
tw = Thickness of beam web
Constant ε  250 
 =  

= 1 (IS:800-2007,Table-2)
 fY 

As d/tw = 45.65 , ≤ 67 ε*√(Kv/5.35), So section is not suseptible to web buckling (IS:800-2007, Cl 8.4.2)

CHECK FOR OUTSTAND


Consider width/outstand of continuity plates = (bfcol - twcol - 4)/2
= (210-12-4)/2

= 97.00 mm

As the outer edge is not continuously stiffened,


Outstand from the face of web should not exceed = 20tqε (IS:800-2007,Cl.8.7.1.2)

where tq = Thickness of continuity plates, T4


= 16 mm
Constant ε  
250
 = 


 = 1 (IS:800-2007,Table-2)
 fY 

20tqε = 20*16*1

= 320

≥ Outstand of continuity plates (97mm), Hence OK

For design, core section should be taken with outstand limited to 14tqε
bs = minimum of 97mm or 14*tq*ε
(IS:800-2007,Cl.8.7.1.2)
bs = 97 mm
Provide plate of width = 95.00 mm
CHECK FOR BUCKLING STRENGTH (IS:800-2007,Cl.8.7.1.5)

Moment of Inertia along axis parallel to web


MI considering only sttiffener, Ixxs = 16*95^3 16*95*(95/2+12/2)^2 *2
+
12
MI considering only web, Ixxw = (40*12+16)*12^3
12
Total Moment of Inertia Ixx = Ixxs+ Ixxw

= 11058997 mm4

Effective area, Ae = (2*95*16) + (40*12+16)*12

2
= 8992 mm

Radius of gyration, r = √Ixx


√Ae

= 35.07 mm
Considering flanges are not restrained
KL = 1.0 * dcol (IS:800-2007,Cl.8.7.1.5(b))
= 1.0*558.4

= 558.4 mm

Effective slenderness ratio λ = KL


r
= 558.4
35.07

λ = 15.92
2
fy = 250.00 N/mm
For this fy and λ, Using table 9c
2
fcd = 225.22 N/mm (IS:800-2007,Cl.8.7.1.5
Table: 9c)
Buckling strength of continuity plate, Pd = Ae*fcd
1000

= 2025.18 KN

> 1086.56 KN, Hence OK


CHECK FOR BEARING STRENGTH (IS:800-2007,Cl.8.7.5.2)

Force to be carried by stiffeners, Fx = Flange force - Fw (IS:800-2007,Cl.8.7.6)


= 1086.56 - 599.56

= 487.00 KN

Total load to be carried out by stiffeners should always be less than the bearing strength of stiffener.
Bearing strength of the stiffeners is given by
A q * f yq
Fpsd = (IS:800-2007,Cl.8.7.5.2)
where, 0 . 8 *  mo
Aq = Area of stiffener in contact with flange

Ymo = 1.1
So to get min thickness of the stiffener, Equating

Load transferred through stiffeners = Bearing strength of the stiffeners


Fx = Fpsd
487.0 = Aq*250
0.8*1.1
Aq = 487*1000*0.8*1.1
250

2
Total area of stiffeners in contact with flange Aq = 1714.24 mm
Area of one stiffener in contact with flange = 857.12 mm2

Thickness of stiffener . T4 = Area of stiffener/width of stiffener


= 857.12/80
= 10.7 mm

Hence providing continuity plates of thickness, T4 = 16 mm

Design of Weld for Continuity Plates

Flange force, Fw = 1086.6 KN


Thickness of stiffener = 16.0 mm

End fillet weld, normal to the direction of force shall be of unequal size with a throat thickness not less than 0.5t,

Effective min throat thickness of weld = 0.5*twcol (IS:800-2007,Cl.10.5.8.5)


Effective min size of weld = 0.5*12/0.7 mm (IS:800-2007, Table:22)
= 8.57 mm

Weld strength = 0.7 * 10 * fu


√3*ϒmw

fu = 410
Strength of weld for shop weld = 1325.6 N/mm of weld length

Chamfer size as chosen = 15


Strength of weld = 1325.6*4*{(558.4-2*O1213)+(95-O1213)*2}

= 3650.1722 KN
≥ 1086.56 KN, Hence SAFE

Provide a weld of size = 10.0 mm


CHECK FOR COLUMN WEB THICKNESS

Thickness of column web/doubler plate shall satisfy following criteria (IS:800-2007,Cl.12.11.2.4)

t ≥ (d p + b p )
where, 90
dp = panel zone depth between continuity plate
= h
bp = panel zone width between column flanges
= dcol
t = twcol in case of columns or thickness of doubler plate if
needed

(h + d col )
twcol ≥
90

= 500+558.4
90

= 11.76 mm

≤ Column web thickness of (12mm), Hence OK


SUMMARY
1 Beam ISMB500 is connected to Column ISMB600

2 Based on flange & web classfication, Beam Section is a PLASTIC SECTION (CLASS-1)
3 Connection is designed for 120% Moment capacity and 60% Shear capacity of section
4 As d/tw = 45.65 , ≤ 67 ε, So Beam section is not suseptible to web buckling
5 Top Plate properties:
a Width : 205.00 mm
b Thickness 25.00 mm
c Length: 750.00 mm
d Weld 10.00 mm
6 Bottom Plate properties:
a Width : 205.00 mm
b Thickness 25.00 mm
c Length: 820.00 mm
d Weld 10.00 mm
7 Web Stiffener for Beam
stiffener is required to prevent web from failing in buckling
a Thickness 16.00 mm
b Width 80.00 mm
c Weld 8.00 mm
8 Bearing Plate properties
a Thickness 16.00 mm
b Weld 8.00 mm
c Length: 150.00 mm
d Depth 400.00 mm

7 Continuity Plates for Column


Continuity plates are required to prevent both bearing and buckling of web
a Thickness 16.00 mm
b Width 95.00 mm
c Weld 10.00 mm

You might also like