Molded case circuit breaker has two elements which are the long-time
delay for small over-current such as overloads and the instantaneous
elements for short-circuits. Also it shall be sized adequately to handle
locked-rotor current during starting. Shown in Figure 7.2 CB “A” is used
for over current protection device for the 200HP motor with code letter
“G” locked-rotor kVA per HP is equivalent of base from PEC 2017 Table
4.30.1.7.(B) Locked-Rotor Indicating Code Letter @ page 345.
6.29kVA
200HP ( )
HP
ILR@FULL VOLATGE = = 1578.93 Amp. (full voltage starting)
460 √3
Thus, motor controller is a wye-delta starter that reduces the starting
1 2
current by ( ) calculated below,
√3
2
1
ILR@WYE-DELTA = ILR@FULL VOLATGE X ( )
√3
2
1
ILR@WYE-DELTA = 1578.93 X ( )
√3
ILR@WYE-DELTA = 526.31 Amp.
a. Long-time element;
ILONG-TIME SETTING CB “B” = ILONG-TIME SETTING CB “A” + All other loads IFLA
ILONG-TIME SETTING CB “B” = 252 + (2079.00 – 240.00)
ILONG-TIME SETTING CB “B” = 2091.00 Amp. – 2000A Set Etap
b. Instantaneous element;
a. Long-time element;
ILONG-TIME SETTING CB “C” = ILONG-TIME SETTING CB “B” + All other loads IFLA
ILONG-TIME SETTING CB “C” = 2091 + ( 252 + 240.00 )
ILONG-TIME SETTING CB “C” = 2583.00 Amp. -2500A Set Etap
b. Instantaneous element;
c. Long-time element;
ILONG-TIME SETTING CB “D” = ILONG-TIME SETTING CB “C” + All other loads IFLA
ILONG-TIME SETTING CB “D” = 2583.00 + (132.00 + 359.30 + 221.43)
ILONG-TIME SETTING CB “D” = 3295.73 Amp. – 3500A Set Etap
d. Instantaneous element;
1∠0
= 3007.03 x
0.0666∠81.23
= 45,150.60 Amp.
Therefore:
Motor SC-CONTR. = Fault 1 - 3Ø Fault @ MDP Terminal
= 54,006.25 – 45,150.60 = 8855.65 Amp.