Professional Documents
Culture Documents
Desigo V6.0 Service Pack Product Release
Desigo V6.0 Service Pack Product Release
Desigo V6.0 Service Pack Product Release
Product(s)
Desigo
Internal
Contents
1 Overview ........................................................................................................................................ 3
2 New TX Open module .................................................................................................................... 3
3 PXC CAS27 – Library Extension2.................................................................................................... 4
4 Room automation - Desigo V6.0 Service Pack ............................................................................... 6
4.1 New compact DXR2 room automation stations ................................................................ 6
4.2 Application extensions ...................................................................................................... 7
4.3 Engineering tools ............................................................................................................... 8
4.3.1 Desigo Tools ................................................................................................................... 8
4.3.2 Desigo Room Automation tools ........................................................................................ 8
4.4 Application selection in HIT ............................................................................................... 9
5 New user interface for Desigo document collection..................................................................... 9
6 Software download........................................................................................................................ 9
7 Desigo V6.0 contact persons ....................................................................................................... 10
This document describes the new functionality included in the Desigo V6.0 Service Pack:
The new TX Open Module, i.e. TXI2.OPEN replaces the TXI1.OPEN and offers extended
functionality.
The CAS library extensions 2 provides enhancements as well as improved usability and
engineering efficiency.
As part of room automation, the Desigo V6.0 Service Pack includes two new compact DXR2 room
automation stations. Extensions to the existing application types fan coil unit, fan-powered box
and variable air volume include chilled beam applications. The engineering tools were also
improved.
Serviceability has been improved as well as the interface to the Desigo documentation collection.
A TXI2.OPEN can be used like a TXI1.OPEN in compatibility mode. This allows it to use existing projects
that already have installed PX firmware (V4.1, V5.0, V5.1 or V6.0) or replace defective TXI1.OPENs 1:1. Up
to 100 data points are supported in compatibility mode, there is no remote access.
XWP V6.0 or V6.0 SP (recommended) required for engineering. In XWP, the workflow online helps are
integrated for TXI2.OPEN.
ASN: TXI2.OPEN
SSN: S55661-J120
TXI1.OPEN available only as long as stocks last.
The ongoing collection of suggested improvements from the field were prioritized and implemented as
part of "CAS Library Extension 2" . They are now introduced as part of Desigo V6.0 Service Pack as an
extension to the current CAS Library for Desigo PX.
Overview:
The following was harmonized, extended and enhanced:
1. Harmonization
Plant operation – every plant with soft& hardware switches and operating mode indication
OpModSel, OpModMan, OpModSwi, PrOpMod and RsPrOpMod)
Every plant with delay after power restoration (DlyPwrRtr)
Improvement of plant-switching-off behavior, caused by sensor disturbance (mixing circuits,
domestic hot water)
All plants are equipped with trends
Same „Look and Feel“ in the CFC charts on plant level
2. Heating generation
4 new burner (new family BuItf) and 5 new boiler compounds (new family BoItf)
New StepUp/Down Logic (4 compounds) Note: The new compounds are also used in cooling
(criteria: integral, PID, delays).
New plant with up to 8 boilers (HGen30)
Documentation
All additions and changes are fully documented.
The following documentation is included in the Libset_LED24-HQ-600342-10 :
News_Details_LED24_en.xls Table showing all changes & extensions
A6V10989520en Multi-Boiler plant description
CM110713en-CAS27_01 Compound Library Reference Handbook
Desigo room automation was further developed and improved with Desigo V6.0 Service Pack. The
sections below outlines the latest improvements:
Extension to the Desigo Room Automation standard portfolio with additional room automation
stations
Functional extensions to configurable applications for use with ABT Site
Improvements of tools
* The DXR2.M.. Room Automation stations with BACnet MS/TP are not available in Europe.
Desigo CC V2.1 SR4 supports the new room automation stations DXR2.E12PX. Desigo Insight does not
support the new types.
UI (Universal Input) supports: DI (Digital Input for HVAC only) – as well as LG-NI1000, PT1000, 0..10V,
NTC 100k, NTC 3k, NTC 10k.
All DXR2.E.. have internal KNX PL-Link bus power (AC 24 V 50 mA), a bus length of up to 80 meters, and
an additional USB interface for tooling.
Passive chilled beam in all applications (Fan Coil Unit, Variable Air
Volume and Fan Powered Box)
Active chilled beam in all applications (Fan Coil Unit, Variable Air Volume
and Fan Powered Box)
Dew point calculation for all cooling applications including coordination
with central function for chilled water supply
All features are configurable in ABT Site and programmable in ABT Pro for DXR2
and PXC3.
A new user interface for the Desigo documentation is now available and includes the following features:
Filter (Assortment, Document type, …)
Sorting
Download filtered files to a ZIP file
Responsive design (scalable: PC – Tablet – Mobile)
6 Software download
All Desigo tools are now available as V6.00.243 on the following linke:
The entire Desigo Team wishes you a lot of success with Desigo V6.0!
Kind regards
Gerhard Schmidt
Technical Support CPS - SEE - DESIGO
Siemens AG Österreich
BT EU ZE CPS1 PRM&TS
1210 Vienna, Austria, Siemensstraße 90
Tel.: +43 (0) 51707 - 32332
Mobil: +43 (0) 664/8011732332
mailto: gerhardschmidt@siemens.com