Fire

Alarm
System
Addressable Fire Alarm System

Features
The Mega-Guard Fire Alarm System
(FAS) is available in two different
versions: an addressable and a
conventional marine fire alarm
system. This section describes the
addressable Fire Alarm System.
The addressable FAS monitors up to
8 different loops on the ship in
compliance with EN54-2 and type
approved by classification societies.
A single loop supports up to 120
addressable fire detectors divided in
up to 16 zones. The Mega-Guard
addressable FAS supports a maximum
of 480 fire detectors. Each detector is
individually monitored and configured
by the addressable Fire Alarm System.

A total of 16 different fire detectors are


available in order to suit all marine
applications. The Mega-Guard
addressable FAS is powered by two
19~32VDC power supplies: one main
supply and one back-up supply. FAS Operator Panel with a Fire Alarm and a Loop Fault

Mega-Guard FAS Operator Panel

Touchscreen 5.7"
System lay-out and operation
Pushbuttons 6 The Mega-Guard addressable FAS consists of the following items:
Front metal or glass
FAS Operator Panel for flush panel mounting in bridge console
Microprocessor ARM
Ethernet ports 4 Addressable FAS Controller for din-rail mounting inside bridge console
Number of detectors 480 Addressable Detectors connected to the FAS Controller
Number of FAS Controllers 4
I/O Cable connecting the FAS Operator Panel with FAS Controller
Number of zones 32
The FAS Operator Panel is operated through a user friendly 5,7" touchscreen
for intuitive operation and monitoring. This Operator Panel is available in
Mega-Guard Addressable FAS Controller
two different versions, a panel with a metal front for commercial and navy
Number of loops 2
Number of detectors 120 each loop ships and a panel with glass front for mega yachts. The FAS Operator Panel has
Power supply 24VDC (-25% ~+30%) two operating levels; one accessible for all crew members and a second level
main and back-up which is only accessible for authorized crew members via entering a password.
The Addressable FAS Controller is DIN rail mounted inside bridge console and
FAS environmental and approvals
the detectors are wired in a loop and connected to this Controller.
Ambient temperature -25 ~ 70°C Addressable Detectors have their own address so that the Mega-Guard
IMO approval ü addressable FAS is able to distinguish each individual detector.
Class approval LRS,DNV-GL, ABS
RINA, BV, RMRS, The I/O Cable with length of 3 or 5 meter, inter-connects the FAS Operator
CCS, NKK, PRS, KR Panel with the FAS Controller.

2
Fire Alarm procedure
A Fire Alarm is generated when one or more of the FAS
detectors comes into alarm condition. The Fire Alarm System
A A

is able to distinguish all individual detector alarms. B 1


24Vdc IN
MAIN SUPPLY
24Vdc IN
BACKUP SUPPLY
13 B
C C

The Fire Alarm procedure is as follows: A


24VDC OUT
A

B 2 14 B
REDUNDANT SUPPLY
Activation of: Fire Alarm lamp, internal buzzer (2Hz), C C

A A

external Siren (continuous) and identification of detector in B 3 15B


C C

alarm on the FAS Operator Panel. A A

B 4 16 B

When Stop Horn is pressed in Level 2 the internal buzzer and C C

A A

external siren are silenced. This function is also available in B 5 FIRE ALARM DIGITAL OUTPUT 1 17 B
C C

Level 1 when selected during installation. A A

B 6 FAULT DIGITAL OUTPUT 2 18 B


When Reset pressed in Level 2 the system is reset. C C

Fire Alarm lamp will extinguish and detector alarm on BARCODE LABEL PRODUCT LABEL

A A
touchscreen will be cleared when fire alarm condition has B 7 LOOP 1 'A' ACTIVE LOOP 1 'A' END FAIL 19 B

disappeared. C

A
C

B 8 LOOP 1 'B' ACTIVE LOOP 1 'B' END FAIL 20 B


C C

Fault Alarm procedure


A A

B 9 LOOP 2 'A' ACTIVE LOOP 2 'A' END FAIL 21 B


C C

A Fault Alarm is generated when one of following conditions: A A

B 10 LOOP 2 'B' ACTIVE LOOP 2 'B' END FAIL 22 B


C C
Loop fault Earth fault A A

B 11 23 B
Siren fault Main or back-up supply failure C C

A A

The Fault Alarm procedure is as follows: B 12 SIREN HEALTHY SIREN OUTPUT 24 B


C C

Activation of: Fault Alarm lamp, internal buzzer,


external Siren (when selected during installation) and
Addressable FAS Controller
identification of fault on the FAS Operator Panel.
When Stop Horn is pressed in Level 2 the internal buzzer
and external siren are silenced. This function is also available in Level 1 when selected during installation.
When automatic Reset selected during installation, the FAS returns to normal condition in case fault disappears
When manual Reset is selected during installation, the FAS will return to normal condition after pressing Reset
when fault disappears.

Mounting & dimensions


144 28,5 127

TS35 DIN-Rail Text sheet insertion

A A

B 1
24Vdc IN 24Vdc IN 13 B
MAIN SUPPLY BACKUP SUPPLY
C C

A A

B 2
24VDC OUT 14 B
REDUNDANT SUPPLY
C C

A A

B 3 15B
C C

A A
144

B 4 16 B
C C

A A

B 5 FIRE ALARM DIGITAL OUTPUT 1 17 B


C C

A A

B 6 FAULT DIGITAL OUTPUT 2 18 B


280
220

C C

BARCODE LABEL PRODUCT LABEL

A A

B 7 LOOP 1 'A' ACTIVE LOOP 1 'A' END FAIL 19 B


C C

A A

B 8 LOOP 1 'B' ACTIVE LOOP 1 'B' END FAIL 20 B


C C

A A

B 9 LOOP 2 'A' ACTIVE LOOP 2 'A' END FAIL 21 B


C C
50

A A

B 10 LOOP 2 'B' ACTIVE LOOP 2 'B' END FAIL 22 B


C C

A A

B 11 23 B
C C

A A

B 12 SIREN HEALTHY SIREN OUTPUT 24 B


C C

Connector to/from
FAS Operator Panel
to/from FAS Controller End bracket
FAS Operator Panel Mounting bracket
I/O Cable L=3m or 5m Side view Front view
5,7" touchscreen metal or glass front Addressable FAS Controller
PMS Controller

Ship automation, navigation and electric propulsion


3
Addressable FAS lay-out

Smoke Detector Heat Detector Multi Sensor Detector

Manual Smoke
Addressable FAS FAS
Sounder Call Point Detector FAS Controllers Operator Panel Operator Panel
19~32Vdc Main
A

B
1

2
24Vdc IN
MAIN SUPPLY

24VDC OUT
REDUNDANT SUPPLY
24Vdc IN
BACKUP SUPPLY
A

13 B
C

14 B
VDR
output
C C

A A

B 3 15B

19~32Vdc Backup
C C

A A

B 4 16 B
C C

A A

Loop 1 19~32Vdc supply 19~32Vdc supply


B 5 FIRE ALARM DIGITAL OUTPUT 1 17 B
C C

A A

B 6 FAULT DIGITAL OUTPUT 2 18 B


Bridge

C C

BARCODE LABEL PRODUCT LABEL

Loop 1
A A

I/O Cable Ethernet Cable


B 7 LOOP 1 'A' ACTIVE LOOP 1 'A' END FAIL 19 B
C C

A A

B 8 LOOP 1 'B' ACTIVE LOOP 1 'B' END FAIL 20 B


C C

Siren output
A A

B 9 LOOP 2 'A' ACTIVE LOOP 2 'A' END FAIL 21 B

Ethernet Cable
C C

A A

B 10 LOOP 2 'B' ACTIVE LOOP 2 'B' END FAIL 22 B


C C

Loop 2 Loop 2
A A

B 11 23 B
C C

A A

B 12 SIREN HEALTHY SIREN OUTPUT 24 B


C C

A A

B 1
24Vdc IN 24Vdc IN 13 B
MAIN SUPPLY BACKUP SUPPLY
C C

A A

Main Repeater
B 2
24VDC OUT 14 B
REDUNDANT SUPPLY
C C

A A

B 3 15B
C C

A A

B 4 16 B
C C

Loop 3 Loop 3
A A

B 5 FIRE ALARM DIGITAL OUTPUT 1 17 B


C C

A A

B 6 FAULT DIGITAL OUTPUT 2 18 B


C C

Loop 4 A

C
7
BARCODE LABEL

LOOP 1 'A' ACTIVE


PRODUCT LABEL

LOOP 1 'A' END FAIL


A

19 B
C
Loop 4
A A

B 8 LOOP 1 'B' ACTIVE LOOP 1 'B' END FAIL 20 B


C C

A A

B 9 LOOP 2 'A' ACTIVE LOOP 2 'A' END FAIL 21 B


C C

A A

B 10 LOOP 2 'B' ACTIVE LOOP 2 'B' END FAIL 22 B


C C

A A

B 11 23 B
C C

A A

B 12 SIREN HEALTHY SIREN OUTPUT 24 B


C C

Smoke Smoke Smoke Manual Heat Smoke


Main Deck

Main Deck

Exit Door
Corridor

Captain

Sounder Detector Detector Detector Call Point Detector Detector


Galley

Mess

Smoke Smoke Smoke Manual Optical/Heat Flame


Engine Room Below Deck

Esc. Hatch
Chief Eng.

AC Room

Dry Store
Corridor

Sounder Detector Detector Detector Call Point Detector Detector


Crew

Smoke Manual Optical/Heat Manual Heat Smoke


Sounder Detector Call Point Detector Call Point Detector Detector

Mega-Guard Addressable FAS Detectors

Type Model Base Location


Optical smoke detector P600MAR P210MAR Bridge, control room, machinery spaces, accommodation
Ionisation smoke detector P500MAR P210MAR Bridge, control room, machinery spaces, accommodation
Heat detector P400MAR P210MAR Bridge, control room, accommodation, open deck, smoking area
Optical smoke / Heat detector P700MAR P210MAR Bridge, control room, machinery spaces, accommodation
UV Flame detector P027MAR - Machinery spaces, open deck
Manual call point * P970MAR - Bridge, control room, machinery spaces, accommodation
Manual call point IP67 * P975MAR - Machinery spaces, open deck
Isolator P721 MAR P211MAR Bridge, control room, machinery spaces, accommodation
* Manual call points can also be delivered including Isolator

4
Conventional FAS lay-out

Manual Call Point Multi Tone Sounder Fire Alarm Bell 6"

Manual Smoke
Conventional FAS FAS
Sounder Call Point Detector FAS Controller Operator Panel Operator Panel
A
1
24Vdc
0Vdc
24Vdc IN MAIN 24Vdc IN BACKUP
24Vdc
0Vdc
8
A
19~32Vdc supply VDR
19~32Vdc Main
B B

A 24Vdc
B
2
0Vdc
24Vdc OUTPUT FAS SYSTEM

I/O Cable output


19~32Vdc Backup
+IN A
ZONE 1 7
-IN B

A ACTIVE +IN A
3 SIRENE ZONE 2 8
B FAIL -IN B

A NC +IN A
4 FIRE ALARM ZONE 3 9
C -IN

19~32Vdc supply
B B

A SYSTEM +IN A
5 FAILURE ZONE 4 10
B GENERAL -IN B
Bridge

PRODUCT LABEL BARCODE LABEL

Zone 1 Ethernet Cable


Siren output
Ethernet Cable

Zone 2
Main Repeater
Zone 3
Zone 4

Smoke Smoke Smoke Manual 60° Heat Smoke


Main Deck

Main Deck

Exit Door
Corridor

Captain

Sounder Detector Detector Detector Call Point Detector Detector


Galley

Mess

Smoke Smoke Smoke Manual Optical/Heat Flame


Engine Room Below Deck

Esc. Hatch
Chief Eng.

AC Room

Dry Store
Corridor

Sounder Detector Detector Detector Call Point Detector Detector


Crew

Smoke Manual Optical/Heat Manual 90° Heat Smoke


Sounder Detector Call Point Detector Call Point Detector Detector

Mega-Guard Conventional FAS Detectors

Type Model Base Location


Optical smoke detector P42001MAR P0001MAR Bridge, control room, machinery spaces, accommodation
Heat detector BR rate of rise P41003MAR P0001MAR Bridge, control room, open deck
Heat detector BS 60degr P41004MAR P0001MAR Bridge, control room, accommodation
Heat detector CS 90 degr P41006MAR P0001MAR Machinery spaces, open deck
Optical smoke / Heat detector P43001MAR P0001MAR Bridge, control room, machinery spaces, accommodation
UV Flame detector P026MAR - Machinery spaces, open deck
Manual call point P021MAR - Bridge, control room, accommodation
Manual call point IP67 P022MAR - Machinery spaces, open deck
Other types available on request

Ship automation, navigation and electric propulsion


5
Conventional Fire Alarm System

Features
The Mega-Guard Fire Alarm System
(FAS) is available in two different
versions: an addressable and a
conventional marine fire alarm
system. This section describes the
conventional Fire Alarm System.
The conventional FAS monitors up to
4 different zones on the ship in
compliance with EN54-2 and type
approved by classification societies.
A single zone supports up to
32 conventional fire detectors.
The Mega-Guard conventional FAS
supports a maximum of 128 fire
detectors. Each zone is individually
monitored and a distinction can be
made in between Heat/Smoke
Detectors and Manual Call Points.

A total of 16 different fire detectors


are available in order to suit all marine
applications. The Mega-Guard
conventional FAS is powered by two
19~32VDC power supplies: one main FAS Operator Panel
supply and one back-up supply.

Mega-Guard FAS Operator Panel

Touchscreen 5.7"
System lay-out and operation
Pushbuttons 6 The Mega-Guard addressable FAS consists of the following items:
Front metal or glass FAS Operator Panel for flush panel mounting in bridge console
Microprocessor ARM
Conventional FAS Controller for din-rail mounting inside bridge console
Ethernet ports 4
Number of detectors 128 Conventional Detectors connected to the FAS Controller
Number of zones 4 I/O Cable connecting the FAS Operator Panel with FAS Controller
The FAS Operator Panel is operated through a user friendly 5,7" touchscreen
Mega-Guard Conventional FAS Controller for intuitive operation and monitoring. This Operator Panel is available in
Number of zones 4 two different versions, a panel with a metal front for commercial and navy
Number of detectors 32 each zone ships and a panel with glass front for mega yachts. The FAS Operator Panel has
Power supply 24VDC (-25% ~+30%)
two operating levels; one accessible for all crew members and a second level
main and back-up
which is only accessible for authorized crew members via entering a password.
The Conventional FAS Controller is DIN rail mounted inside bridge console and
FAS environmental and approvals
the detectors are wired in parallel and connected to this Controller.
Ambient temperature -25 ~ 70°C
Conventional Detectors in a single zone cannot be extinguished from each
IMO approval ü
Class approval LRS,DNV-GL, ABS other; except for Manual Call Points.
RINA, BV, RMRS, The I/O Cable with length of 3 or 5 meter, inter-connects the FAS Operator
CCS, NKK, PRS, KR Panel with the FAS Controller.

6
Fire Alarm procedure
A Fire Alarm is generated when one or more of the FAS
detectors (heat/smoke/flame/mnual call point) comes into A 24Vdc 24Vdc A
1 24Vdc IN MAIN 24Vdc IN BACKUP 8
alarm condition. The Fire Alarm System is able to distinguish B 0Vdc 0Vdc B

A 24Vdc
all individual zone alarms. B
2
0Vdc
24Vdc OUTPUT FAS SYSTEM

The Fire Alarm procedure is as follows:


Activation of: Fire Alarm lamp, internal buzzer (2Hz),
external Siren (continuous) and identification of zone in ZONE 1
+IN
-IN
7
A

alarm on the FAS Operator Panel. A

B
3
ACTIVE
FAIL
SIRENE ZONE 2
+IN
-IN
8
A

When Stop Horn is pressed in Level 2 the internal buzzer A

B
4
NC
C
FIRE ALARM ZONE 3
+IN
-IN
9
A

and external siren are silenced. This function is also A

B
5
SYSTEM
GENERAL
FAILURE ZONE 4
+IN
-IN
10
A

available in Level 1 when selected during installation. PRODUCT LABEL BARCODE LABEL

When Reset pressed in Level 2 the system is reset.


Fire Alarm lamp will extinguish and detector alarm on
Conventional FAS Controller
touchscreen will be cleared when fire alarm condition
has disappeared.
The internal buzzer and external siren can be activated again
in Level 2 by pressing Stop Horn for more than 2 seconds.

Fault Alarm procedure


A Fault Alarm is generated when one of the following conditions occurs:
Loop fault Earth fault
Siren fault Main or back-up supply failure
The Fault Alarm procedure is as follows:
Activation of: Fault Alarm lamp, internal buzzer, external Siren (when selected during installation) and
identification of fault on the FAS Operator Panel.
When Stop Horn is pressed in Level 2 the internal buzzer and external siren are silenced. This function is also
available in Level 1 when selected during installation.
When automatic Reset selected during installation, the FAS returns to normal condition in case fault disappears
When manual Reset is selected during installation, the FAS will return to normal condition after pressing Reset
when fault disappears.

Mounting & dimensions


144 28,5 127
Text sheet insertion

A 24Vdc 24Vdc A
1 24Vdc IN MAIN 24Vdc IN BACKUP 8
B 0Vdc 0Vdc B

A 24Vdc
B
2
0Vdc
24Vdc OUTPUT FAS SYSTEM
144

180
120

+IN A
ZONE 1 7
-IN B

A ACTIVE +IN A
3 SIRENE ZONE 2 8
B FAIL -IN B

A NC +IN A
4 FIRE ALARM ZONE 3 9
B C -IN B

A SYSTEM +IN A
5 FAILURE ZONE 4 10
B GENERAL -IN B
50

PRODUCT LABEL BARCODE LABEL

Connector to/from
FAS Operator Panel
End bracket

to/from FAS Controller TS35 DIN-Rail


FAS Operator Panel Mounting bracket
I/O Cable L=3m or 5m Side view Front view
5,7" touchscreen metal or glass front Conventional FAS Controller
PMS Controller

Ship automation, navigation and electric propulsion


7
Vessel Power Fire CCTV
Management System Management System Alarm System Video Distribution

Ship Fleet Integrated Heading


Performance Monitor Management System Navigation System Control System

Propulsion Dynamic BNWAS Navigation


Control System Positioning System Watch Alarm System Light Control

Wiper Energy Electric Electric


Control System Management System Propulsion Motor Steerable POD

High DC bus Electric Electric Fin


Power Inverter Generator Energy Storage Stabilizer

Ship automation,
navigation and
electric propulsion