Professional Documents
Culture Documents
Addressing Defective Cathodic Protection Systems On Above Grade Storage Tanks
Addressing Defective Cathodic Protection Systems On Above Grade Storage Tanks
Several states, the DOT and the DoD require the use of cathodic
protection to reduce product release
Cathodic Protection Types
Galvanic
Impressed Current
Single Bottom Storage Tanks
Rectifier Tank
(-)
(+)
Foundation
Protective Anode
Current
Cathodic Protection Arrangement
Many above grade tanks are equipped with under floor containment
liners
Tank
Rectifier
(-)
Soil
(+)
Tank
Rectifier
(-)
Tank Floor
(+) Sand
Plastic Liner
Current will not
Anode
pass through liner
Tank Shell
Bottom
Sand
Foundation
Anode Liner
Sand fill can not be corrosive, and must remain relatively dry
Zinc ribbon
36 to 60 inches
Test Box
Cable
Connections
Tank Shell
Magnesium Anode Ribbons
24” Centers
Magnesium Ribbons
#10 RHW-USE
Permanent
reference cell
centered
between ribbons
Tank Shell
Galvanic Anode Splice
Live Shell
Test
Box
Seal off
New Floor
Liner
Sand Seal
1 ½” dia. conduit
Reference Cells
Anode Ribbon
Grade
Couple
Current Flow
Live Shell
Cable
connection
to tank Test
Box
Newer Tank Floor Weld
New Floor
Liner
Seal
Protective Sand
current Current return
flow Cable in cable
To next anode
Anode
Old Floor
Live Shell
Chime
Defect in plate
Weld defect New Floor
Sand
Leak
detection
port not
sealed
Old Floor
Impressed Current
Shell
Test Box
Rectifier
Negative
Floor
Connection
Sand
Foundation
Anode Liner Reference Cells
Lift the tank or remove the floor and replace the cathodic protection
system
Shell
Floor
Sand
Cable Splice Box
Containment Liner
Inserted Anode
Ringwall
Inject Water Based Inhibitor
Monitor Discharge
Inject Water Based
Inhibitor
Shell
Conclusions