Professional Documents
Culture Documents
KFG Kfgs KFGC (Can Bus) : For Industrial Use
KFG Kfgs KFGC (Can Bus) : For Industrial Use
KFG Kfgs KFGC (Can Bus) : For Industrial Use
2006/42/EC
for partly completed machinery with associated operating instructions EN
for industrial use
Version 02
EN Page 2 Notes
Service
Masthead © SKF Lubrication Systems Germany GmbH
If you have technical questions, please contact
These original assembly instructions with as- This documentation is protected by copyright. the following addresses:
sociated operating instructions according to EC SKF Lubrication Systems Germany GmbH re-
Machinery Directive 2006/42/EC are an inte- serves all rights, including those to the photo- SKF Lubrication Systems Germany GmbH
gral part of the described product and must be mechanical reproduction, duplication, and dis-
kept for future use. tribution by means of special procedures (e.g., Berlin Plant
These original assembly instructions with as- data processing, data media, and data net- Motzener Strasse 35/37
sociated operating instructions have been pre- works) of this documentation in whole or in 12277 Berlin
pared in accordance with the established stan- part. Germany
dards and rules for technical documentation, Tel. +49 (0)30 72002-0
VDI 4500 and EN 292. Subject to changes in contents and technical Fax +49 (0)30 72002-111
information. www.skf.com/lubrication
Hockenheim Plant
2. Industriestrasse 4
68766 Hockenheim
Germany
Tel. +49 (0)62 05 27-0
Fax +49 (0)62 05 27-101
www.skf.com/lubrication
Assembly instructions table of contents Page 3 EN
7.3.5 Display and documentation 12.3 No system monitoring 90 15.2.3 Fault types 103
functions 73 15.2.4 Fault notiication 103
7.3.6 Conigurable parameters 73
12.4 With system monitoring 90
12.5 Fill level monitoring 91 15.2.5 Read faults 103
12.6 Monitoring via piston detector 91 15.2.6 Remedy faults 103
8. Commissioning 74 12.7 Monitoring via pressure switch 92 15.2.7 Warning and malfunction indicator
8.1 General commissioning 74 on KFGC (CAN bus) pump unit 105
13. Shutdown 93
9. Display and control elements 13.1 Temporary shutdown 93 16. Technical data 107
of control screen 75 13.2 Permanent shutdown 93
9.1 KFGS series 75 17. Accessories 111
9.1.1 Three-digit LED display 76 17.1 Connectivity for timer operation
with system monitoring, ill level
14. Maintenance 94
9.1.2 LED display 78 14.1 General information 95
9.1.3 Pushbutton operation 79 14.2 Service 95 control, piston detector and
9.2 KFGC (CAN bus) series 80 indicator light 112
15. Operational and pump faults 97
10. KFGS display mode 82 15.1 KFGS operational malfunctions 97
10.1 KFGS series 82 15.1.1 General 97
15.1.2 Display faults 97
11. KFGS programming 84 15.1.3 Delete fault notiication 97
11.1 Start programming mode 84 15.1.4 Fault types 98
11.2 Change lubrication interval times 84
11.3 Conigure system monitoring 86
15.1.5 Recording fault times 99
15.1.6 Maintenance and repair 99
11.4 Change operating modes 87 15.1.7 Malfunctions on pump unit
11.5 Change access code 88 in progressive system 100
11.6 Programming ranges 89 15.1.8 Malfunctions
11.7 Display ranges 89 on KFG/KFGS pump units 101
15.2 Operational malfunctions on
12. KFGS operating modes 90 KFGC (CAN bus) 103
12.1 Timer operation 90 15.2.1 Pump malfunctions 103
12.2 Counter operation 90 15.2.2 Faults detected by control unit 103
EN Page 6 EC Declaration of Incorporation
The manufacturer SKF Lubrication Systems Germany GmbH ,Plant Hockenheim, 2. Industriestraße 4, DE - 68766 Hockenheim hereby declares that
the partly completed machinery:
Designation: Piston pump aggregate for industrial application
Type: KFG, KFGS, KFGC
Part no.: KFG*; KFG*M*; KFG*R*; 772-*
Year of construction: See type identification plate
complies with the following basic requirements of the EC Machinery Directive 2006/42/EC at the time when first being launched in the market.
1.1.2 · 1.1.3 · 1.3.2 · 1.3.4 · 1.5.1 · 1.5.6· 1.5.8 · 1.5.9 · 1.6.1 · 1.7.1 · 1.7.3 · 1.7.4
The special technical documents were prepared following annex II part B of this directive. Upon justifiable request, these special technical documents can be forwarded
KFG KFGS KFGC
electronically to the respective national authorities. The person empowered to assemble the technical documentation on behalf of the manufacturer is the head of stan-
dardization; see manufacturer‘s address.
Furthermore, the following directives and harmonized standards were applied in the respective applicable areas:
2011/65/EU RoHS II
2014/30/EU Electromagnetic compatibility | Industry
Hockenheim, 2016/05/31
You will find these symbols, which warn of Instructions placed directly on the machines/
specific dangers to persons, material assets, or grease lubrication pump units, such as:
the environment, next to all safety instructions Arrow indicators You are responsible!
in these operating instructions. Labels for luid connections
must be followed and kept in fully legible Please read the assembly and operating in-
Please heed these instructions and proceed condition. structions thoroughly and follow the safety
with special care in such cases. Please forward instructions.
all safety instructions to other users.
Assembly instructions in
accordance with Machinery
Directive 2006/42/EC,
Annex VI
The assembly instructions fulfill the Machinery
Directive indicated above with regard to “partly
completed machinery.” Partly completed ma-
chinery, which includes the product described
herein, is only intended to be incorporated into
or assembled with other machinery or other
partly completed machinery or equipment,
thereby forming machinery to which the
above-mentioned Directive applies.
Assembly instructions Page 9 EN
1. Safety instructions
The operator of the described prod- In addition to the assembly instructions, 1.2 Authorized personnel
uct must ensure that the assembly general statutory regulations and other
instructions are read and understood by regulations for accident prevention Only qualified technical personnel may install,
all persons tasked with the assembly, and environmental protection must be operate, maintain, and repair the products de-
operation, maintenance, and repair of observed and applied. scribed in the assembly instructions. Qualified
the product. The assembly instructions technical personnel are persons who have
must be kept readily available. 1.1 Intended use been trained, assigned and instructed by the
operator of the final product into which the de-
Note that the assembly instructions Pump units of SKF's KFG, KFGS and KFGC scribed product is incorporated. Such persons
form part of the product and must series are used to supply centralized lubrica- are familiar with the relevant standards, rules,
accompany the product if sold to a new tion systems in vehicles, systems and ma- accident prevention regulations, and assembly
owner. chines. They deliver oils and greases (up to conditions as a result of their training, experi-
NLGI Grade 2). ence, and instruction. They are authorized to
identify and perform necessary actions while
The described product is manufactured in ac- The use of synthetic oils requires prior ap. avoiding any risks which may arise.
cordance with the generally accepted rules and The definition of qualified personnel and the
standards of industry practice and with occu- Any other usage is deemed non-compliant prohibition against employing non-qualified
pational safety and accident prevention regula- with the intended use. personnel are laid down in DIN VDE 0105 and
tions. Risks may, however, arise from its usage IEC 364.
and may result in physical harm to persons or
damage to other material assets. Therefore the
product may only be used in proper technical
condition and in observance of the assembly
instructions. In particular, any malfunctions
which may affect safety must be remedied
immediately.
EN Page 10 Assembly instructions
1.3 Electric shock hazard 1.4 System pressure hazard Max. particle size 40 μm
Max. particle density 10mg/m³
Electrical connections for the described product Lubrication systems are pressurized Pressure dew point 7°C
may only be established by qualified and during operation. Centralized lubrication Water content max. 7800 mg/m³
trained personnel authorized to do so by the systems must therefore be depressur- Residual oil content max. 25 mg/m³
operator, and in observance of the local condi- ized before starting assembly, main-
tions for connections and local regulations tenance or repair work, or any system
(e.g., DIN, VDE). Significant bodily injury and modiications or system repairs.
property damage may result from improperly 1.6 Hydraulic pressure hazard
connected products. 1.5 Compressed air hazard
The described product is pressurized
Danger! The described product is pressurized during operation. The product must
Work on products that have not been during operation. The product must therefore be depressurized before
de-energized may result in bodily injury. therefore be depressurized before starting assembly, maintenance or re-
Assembly, maintenance and repair work starting assembly, maintenance or re- pair work, or any system modiications
may only be performed on products pair work, or any system modiications or system repairs.
that have been de-energized by or system repairs. Depending on the model design, the product
qualiied technical personnel. The Depending on the model design, the product may be able to be operated hydraulically.
supply voltage must be switched off may be able to be operated with compressed
before opening any of the product's air. Through the use of the appropriate com-
components. pressed air quality class, compressed air prep-
aration can be optimized and machine down-
time and higher maintenance costs avoided.
The compressed air to be used here must
comply with at least quality class 5 as deined
by ISO 8573-1:
Assembly instructions Page 11 EN
Danger! The switching circuits of the ill level The service life of the oil lubrication pump
Only the pump models tested and monitor must be supplied by an intrinsi- is limited. It must therefore undergo a
approved by SKF Lubrication Systems cally safe circuit, e.g., through the installa- function and leak test at regular intervals.
Germany GmbH in accordance with tion of an ATEX-compliant isolating switch Perform appropriate repairs in the event
ATEX Directive 2014/34/EU are permit- by thecustomer. of malfunctions, leaks, or rust. Replace the
ted to be used in areas with explosion The unit must be grounded via a ground pump if necessary.
protection. The relevant class of protec- connection. The customer must install ad-
tion is engraved on the pump's rating equate overload protection for the power The user must make sure through the
plate. consumption of the motor. choice of the lubricant to be delivered that
no chemical reactions capable of serving
When illing lubricant into the pump, To avoid electrostatic discharge, lay as ignition sources will occur in conjunc-
make sure the lubricant is clean. The hydraulic connecting lines in corrosion- tion with the explosive atmospheres
reservoir must be illed in good time (pay resistant metal tubing, e.g., stainless expected.
attention to ill level monitoring). Lubricant steel pipe. The lubricant’s ignition temperature has
must be illed only via the iller socket to be at least 50 kelvin above the pump’s
G 3/8“ (FF) or G 1/2“ (FB) on the pump When setting up the pump, make sure the maximum surface temperature (tempera-
lange. Lubricant may only be illed via setup location is level and not subject to ture class).
the "reservoir cover" if absolutely certain vibrations or jolts.
that no potentially explosive atmosphere
exists. During maintenance work, use only tools
intended for use in potentially explosive
In case of overilling, the excessive spaces or else make certain that there is
amount of lubricant must be removed. no potentially explosive atmosphere
Make sure there is no potentially explosive present.
atmosphere when doing this.
EN Page 12 Assembly instructions
2. Lubricants
All products from SKF Lubrication No products manufactured by SKF Lubrication Observe the instructions from the
Systems Germany GmbH may be used Systems Germany GmbH are approved for use machine manufacturer regarding the
only for their intended purpose and in in conjunction with gases, liquefied gases, lubricants that are to be used.
accordance with the information in the pressurized gases in solution, vapors, or such
product's assembly instructions. fluids whose vapor pressure exceeds normal Warning!
atmospheric pressure (1013 mbar) by more The amount of lubricant required at
Intended use is the use of the products for the than 0.5 bar at their maximum permissible a lubrication point is speciied by the
purpose of providing centralized lubrication/ temperature. bearing or machine manufacturer. It
lubrication of bearings and friction points using Other media which are neither lubricant nor must be ensured that the required
lubricants within the physical usage limits hazardous substance may only be fed after quantity of lubricant is provided to the
which can be found in the documentation for consultation with and written approval from lubrication point. The lubrication point
the devices, e.g., assembly instructions/operat- SKF Lubrication Systems Germany GmbH. may otherwise not receive adequate
ing instructions and the product descriptions, SKF Lubrication Systems Germany GmbH con- lubrication, which can lead to damage
e.g., technical drawings and catalogs. siders lubricants to be a component of the sys- and failure of the bearing.
Particular attention is called to the fact that tem design which must be factored into the Selection of a lubricant suitable for the lubrica-
hazardous materials of any kind, especially the selection of components and the design of tion task is made by the machine/system man-
materials classified as hazardous by CLP centralized lubrication systems. The lubricating ufacturer and/or the operator of the machine/
Regulation EC 1272/2008 may only be used to properties of the lubricants are critically im- system in cooperation with the lubricant supplier.
fill SKF centralized lubrication systems and portant in these considerations. The bearings/friction points that require lubri-
components and delivered and/or distributed cation, their expected load during operation,
with the same after consulting with and re- and the expected ambient conditions are taken
ceiving written approval from SKF. into account during selection, with consider-
ation of economic and environmental aspects.
Assembly instructions Page 13 EN
3. Overview
Components Components
Item Description Chapter
4 3 5 2 1 1 2 5 3 4
1 Assembly holes 4.2.1
7 5 6 9
with CAN bus control
EN Page 16 Assembly instructions
4. Assembly
and systems. accessible so that all other installations can be assembly work.
performed without difficulty and the device can
They deliver greases up to NLGI Grade 2. The be filled easily. The product must not be installed within
KFGS
pump units differ in terms of lubricant reser- The fill level of the reservoir must be easily range of moving parts.
voir capacity, lubricant filling, control and func- visible.
tion monitoring. The installation of volume- The product must be installed at an
specific pump elements permits a single unit The unit is mounted in a vertical position. adequate distance from sources of heat.
KFGC
During assembly and especially when drilling, Shielded cables must be used in places where
always pay attention to the following: electrical interference fields can distort signal
transmissions despite separate laying of
cables.
Assembly instructions Page 17 EN
The rules and empirical values for The pump units are installed on the machine
"EMC-compliant" cabling must be taken into using three M8 screws with a minimum length
consideration. of 20 mm.
KFG
Warning! Fastening material to be provided by the
When drilling the assembly holes, you customer:
must be careful of any supply lines or
KFGS
other units, as well as of other hazards Hexagon head screws (3x) per
such as moving parts. DIN933-M8x....-8.8
Maintain safety clearances and comply Washers (3x) per DIN 125-B8.4-St
with local regulations for assembly and
KFGC
accident prevention. Warning!
The torque of the fastening screws
Warning! depends on the customer’s installation.
Do not tilt the KFG (S) (C) grease Make sure that torque is adequate
lubrication pump unit! when installing the pump unit!
EN Page 18 Assembly instructions
200 ± 0,4
Minimum mounting clearance
E
E = 20 mm
E
C
KFG
75 ± 0,4
Ø 9,0 max
min
KFGS
B
KFGC
D A
The minimum clearance height for KFG5-5... 10 210 585 205 226 15
installation depends on the reservoir KFGS1-5... 1) 2 210 282 180 226 7
design. Add another 20 mm to allow
KFGS3-5... )1
6 210 464 226 226 11
for the total pump height.
KFGS5-5... )1
10 210 637 205 226 15
Assembly instructions Page 19 EN
4.3 Pump elements 4.3.2 KFGC (CAN bus) pump elements Then perform the following:
• Loosen and remove pressure regulat-
4.3.1 KFG/KFGS pump elements 3/2 directional control valves can be employed ing valve (2) (or lubrication line (3)) on an
KFG and KFGS pump units can be equipped so that lubricant connections can also return already mounted pump element (1).
with up to three pump elements. Each pump the lubricant into the reservoir from lubricant • Loosen and remove mounted pump ele-
KFG
element has a connector for, e.g., connecting outlets which are not required at the moment. ment (1).
an independent progressive feeder. A grease • Insert new pump element (1) into housing
return can be attached in place of a pump Close any outlets which are not required using hole and twist in by hand.
KFGS
element. a DIN 910-M20x1.5-5.8 screw plug with a • Tighten pump element (1) at a torque
Close any outlets which are not required using DIN 7603-A20x24-Al washer. of 35 Nm.
a DIN 910-M20x1.5-5.8 screw plug with a • Switch on pump and leave running until
DIN 7603-A20x24-Al washer. grease without bubbles discharges from the
KFGC
pump element outlet.
The pump elements must be ordered accor- 4.3.3 Installation of a pump element • Reconnect pressure regulating valve (2)
ding to the required delivery rate. (or lubrication line (3)) to the pump element
Pump units of the KFG, KFGS und KFGC (1) and tighten at a torque of 25 Nm.
(CAN bus) series are generally delivered with
pump elements installed.
2
1
Perform the following to later add or replace a
pump element:
3
• Turn off pump unit.
• Loosen and remove screw plug.
Delivery rate ) 1
Number of grooves Max. permiss. oper. pressure Order No.
The pump element must be ordered according [cm3/min] [bar]
to the required delivery rate (see Pump ele-
5.0 0 200 KFG1.U0
ments table).
KFG
1) The values given here apply for a temperature of 20 °C, back pressure of 50 bar and greases of NLGI Grade 2.
The 5.0 cm3/min pump element is preferred for use in single-line centralized lubrication systems.
2 1 3
M20x1,5
Connection for pump elements
M14x1,5
Connection for pump elements
KFG
pump element (2). The cracking pressure set P
6 300 161-210-012
for this valve is 300 bar or 200 bar, depending
A
on the valve design. If a blocked feeder or a lu- 6 200 161-210-032
KFGS
brication point causes operating pressure to
8 300 161-210-018
M14 x 1,5
rise above 300 (200) bar, the valve opens, fol- P
lowed by a noticeable discharge of grease (3). 8 200 161-210-031
This also serves as a form of visual system 10 300 161-210-016
KFGC
monitoring.
10 200 161-210-030
This protects the pump unit against damage.
A further option are pressure regulating valves Pressure regulating valve with
with an emergency lubricant nipple. These can lubricant nipple
A
be used with manual grease presses to provide 6 300 161-210-014
the lubrication system with adequate lubricant pressure regulating valve
8 300 161-210-025
in case of power failure or a defective pump.
Pressure regulating valve with Connections for pressure regulating valves
3 pressure gauge
1 A Connection for pipe Ø
6 300 161-210-046 P Pipe thread for pump element
R Grease discharge at overpressure
8 300 161-210-047
R
R 4.4 Instructions on lubricant illing 4.4.1 Lubricant illing
Only ill using clean lubricant and an Lubricant illing is performed using a
appropriate illing device. Contaminated DIN 71412-AM10x1 conical head nipple (1)
P A lubricants can result in severe system and a conventional grease press.
KFG
M14 x 1,5
8 300 161-210-039
Filler sockets/lubricant return
8 200 161-210-031
10 300 161-210-016
10 200 161-210-030
Assembly instructions Page 23 EN
As an alternative or addition to a conical head The pump unit can also be illed through one A special design for the pump units is illed
nipple (1), the unit can also be equipped with a of the lubricant outlets using a illing cylinder with lubricant through a special hinged lid or a
iller socket (part No. 995-000-705) (2) to ill (1). To do this, remove the M20x1.5 screw plug screw cap.
using a illing pump. A corresponding coupling
KFG
(2) in the lubricant outlet and replace it with a
socket (part No. 995-001-500) (3) must be iller socket (part No. 169-000-174) (3). The Only ill using clean lubricant and an
mounted on the illing pump. The cap on the caps (4) on the socket and illing cylinder must appropriate illing device. Not suitable in
iller socket must be removed before illing. be removed before illing.
KFGS
case of highly contaminated pumps and
surrounding areas.
KFGC
995-001-500
Filling cylinder
169-000-171
Filler socket
169-000-174
KFG1-5W2; KFGS1-5W2 KFGS1-5
(for NLGI Grade 1 greases)
Filling via filler coupling Filling via filling cylinder Filling cover versions
EN Page 24 Assembly instructions
24 V GLEICHSTROM
115 VAC N/A5) 1.5 A 20 A C6A
Grease/Fett NLGI-2
Made in Germany 230 VAC N/A5) 0.9 A 40 A C6A
1) Protective measures that must be applied for designated usage: "Functional Extra Low Voltage,"
"Protective Extra Low Voltage“ (PELV) Standards: EN 60204 Part 1: IEC 60204-1:
DIN VDE 0100 Part 410 / IEC 364-4-41: HD384.4.41
2) Typical value at ambient temperature = 25°C and operating pressure = 150 bar
3) Fuse per DIN 72581 T.3
4) Conductor: cross-section 1.5 mm2, length ≤ 12 m
5) No specification
Assembly instructions Page 25 EN
4.5.2.1 Power supply 12/24 VDC 4.5.2.2 Power supply 90-264 VAC
4.5.2 KFG series
1
1
and 120-370 VDC designs.
KFG
The electrical voltage connection is established
2
2
through a 4-pin cable socket according to
DIN EN 175301-803. KFG...AC
M
Depending on the pump unit design, an addi-
tional plug for ill level control and/or a plug for
DC
KFG...DC
Cable socket per
AC
M
- Cable socket per
DIN EN 175301-803
a pump-side pressure relief valve (single-line + DIN EN 175301-803
X1 1 X1 1 2 3
centralized lubrication system) can be inte- 2 3
lubrication and interval times, as well as agitator is turned downward by the grease re-
to monitor the lubrication process. sistance when the reservoir is full. A pulse is
generated at each revolution of the agitator.
4.5.2.4 Fill level monitoring When the minimum fill level is reached, the
Type: W1 (max. 24 VDC) resistance the grease exerts on the rocker
Socket connection per
for NLGI Grade 2 greases subsides. The rocker turns back and the pulses
EN 60947/IEC 947
are interrupted.
3 4
+ Sig
2 1
1 2 3 4
Technical data
KFG
Fill level . . . . . . . .Switch opens at min.
monitoring fill level, fault Function Cable socket 1) per
notification and on wire breakage. DIN EN 60947/IEC 947
Operating voltage . . . .10 to 30 VDC
Continuous current . . . ≤ 200 mA
Internal power consumption 6 to 12 mA
Voltage drop . . . . . . . .≤1.8 V at Iduration
EC Directives EN 6094752
Connection diagram . . M12x1 circular BN 1/+24 V DC BN 1/+24 V DC
WH 2 1
connectors WH
BU
2/ not assigned
BU
2/ not assigned
3/-OV
3/-OV
Conducted interference per IEC 61000-4-6 BK 4/NO
BK 4/NO 3 4
(test level 3V). Radio interference is possible
between 2.4-2.6 MHz.
See assembly instructions on page 16 1) Cable socket - see Accessories, Chapter 14
Warning!
The W2 ill level switch is not suit-
Cable assignment (on fill level switch) Pin/cable assignment (pump unit)
able for greases ≥ NLGI grade 2. Color Conductor Use Pin Color code Use
code coloring 1 Brown Supply voltage
Note
Customer-speciic designs are available
BN Brown Supply voltage 2 White Not assigned
BU Blue O V (0 volts) 3 Blue O V (0 volts)
in addition to the two standard designs
shown. In this case, ill level switch W2
BK Black NO-contact 4 Black NO-contact
WH White Not assigned
must be connected according to the
provided customer drawing.
EN Page 28 Assembly instructions
The following functions are integrated into the W1_smooth connection same as
KFG pump unit with signal smoothing: W2 control (W1_smooth => isolation of
Ability to isolate supply voltage
KFG
Connection diagram for loating W1 control Connection diagram for energized W1 con-
with signal smoothing for NLGI Grade 2 trol with signal smoothing for NLGI Grade 2
greases (W1G = standard design) greases
KFG
com nc no + - Sig
1 2 3 4 1 2 3 4
W1G connector pin assignment (pump unit) Connector pin assignment (pump unit)
200bar
(for single-line systems with VR distributors)
Technical data
KFG
KFGS
4 PK Pink
underside of the pump unit 5 BK Black
via a cubical plug (supply voltage) on the 6 BK Black
side or a M12x1 4-pin circular connector 7 VT-GN Purple-green
on the underside of the pump unit
4
6
The pump control unit can run in the following
1
control modes: Note
Counter operation without system
3
7
The connector pin assignment depends
on the speciic operating mode. The
2
monitoring
Counter operation with system monitoring Power supply via 7-pin circular connector pins are therefore assigned accord-
Timer operation without system monitoring ing to the following examples, listed in
Timer operation with system monitoring Chapters 4.5.3.2 to 4.5.3.6.
Depending on the pump unit design, an addi- Accessories Unneeded conductor ends on the cable
tional plug for ill level control and/or a plug for set must be individually insulated and
a pump-side pressure relief valve (single-line Description Order No. secured so that no short to ground can
centralized lubrication system) can be inte- Cable harness, 12m long, occur.
grated into the pump housing. in corrugated pipe,
The standard connections are presented below. with pump-side socket 997-000-630
EN Page 32 Assembly instructions
BN
BU
RD-BK
KFGS
Accessories
Programming:
MK-machine contact
Description Order No.
cPA, tCO, COP = OFF - see Chapter 6 Cable harness, in corrugated pipe,
with pump-side socket
F
8 m length 997-000-760
13.12 yd length 997-000-630
M L+
17.50 yd length 997-000-650
(Please consider the starting current !)
4.5.3.3 Connectivity for counter operation 4.5.3.4 Connectivity for counter operation Control using machine pulses
without system monitoring with system monitoring (progressive (Counter mode = load-dependent lubrication)
centralized lubrication systems) The duration of the interval time is determined
Programming: cPA, tCO, COP = OFF Programming: cPA, tCO, COP = CS by a pulse generator that sends pulses to the
control unit based on how long the machine
KFGS... KFGS... has been running. The control unit counts the
pulses that are received and starts the pump
after the pre-set number of pulses.
The pump cycle time is deined by a time
X1 1 2 3 4 5 6 7 X1 1 2 3 4 5 6 7
KFGS
BN
BU
PK
BK
BK
VT-GN
RD-BK
BN
BU
PK
VT-GN
RD-BK
4.5.3.5 Connectivity for timer operation 4.5.3.6 Connectivity for timer operation Timer mode
without system monitoring with system monitoring In timer mode, the interval time is determined
(single-line centralized lubrication system) by a time value. It is conigured by entering a
time value in hours.
Programming: tPA, tCO, COP = OFF Programming: tPA, tCO, COP = PS The pump cycle time is conigured using a time
value in minutes.
KFGS... KFGS... The ill level monitoring unit (W1 control) is
internally connected to the integrated pump
control unit. A fault notiication can be sent to
KFGS
X1 1 2 3 4 5 6 7 X1 1 2 3 4 5 6 7
BU
PK
VT-GN
RD-BK
BN
BU
PK
BK
BK
VT-GN
RD-BK
DK SL2 SL1 DK PS
SL2 SL1
+
2,4 W 2,4 W 2,4 W 2,4 W
F F
M L+ (Industrie) M L+ (Industrie)
3
You can ind technical data and the The "Timer operation with system
monitoring and ill level control" con-
1
KFGS
customer in brochure No. 1-1730, with a piston detector and fault signal.
KFG...DC "Electric Plug-and-Socket Connectors." A T connector with a special cable
M
adapter is required for this.
You can ind this, along with an illus-
-
+
X1 1 2 3
tration of the connection, under
Connector pin Accessories, Chapter 17.
assignment per
DIN EN 175 301-803
L+ L-
PIN Description
1 (Current) = L + Supply voltage
potential (Main machine switch ON)
2 - (Ground) = M - Supply
voltage potential (0 V, GND)
EN Page 36 Assembly instructions
4.5.3.8 12/24 VDC connections for 4.5.3.9 Connectivity for timer operation 4.5.3.10 Connectivity for timer operation
system monitoring using an without system monitoring with system monitoring
M12x1 circular plug socket (and ill level control) (and ill level control)
Programming: tPA, tCO, COP = OFF Programming: tPA, tCO, COP = CS or PS
2
3
4
1
3
4
X2 X2
WH
BU
BN
BU
BK
BK
M12x1 circular plug socket
X5
per EN60947-5-2
2
1
3
3 4
BN
BU
BK
2 1
SL2 SL2
2,4W CS/PS 2,4W
Socket pin assignment Connector pin assignment in timer operation Connector pin assignment in timer operation
PIN Color code Conductor coloring PIN Code Assignment PIN Code Assignment
1 BN Brown 3 SL2 "Fault" indicator light ( - ) 1 Voltage ( + )
2 WH White 4 SL2 "Fault" indicator light ( + ) 2 CS/PS Cycle/pressure switch (signal)
3 BU Blue 3 SL2 "Fault" indicator light ( - )
4 BK Black 4 SL2 "Fault" indicator light ( + )
Assembly instructions Page 37 EN
200bar
(for single-line systems with VR distributors)
Technical data
KFGS
Rated output . . . . . . . . . . . . . 26 W A
Rated current . . . . . . . . . . . . 1.2 A
Hydraulic block diagram
ON-time . . . . . . . . . . . . . . . . 100%
Protection class . . . . . . . . . . . IP65
4.5.5 KFGS 90-264 VAC series with 4.5.5.1 Power supply 90-264 VAC
integrated control unit
1
plug-in connector per DIN EN 17530-803 for order number of the M12x1
the power supply (on the front of the unit) and circular connector (mating part for
2
a 4-pin M12x1 plug-in connector per circular plug socket) required by the
EN 60947-5-2 (on the underside of the unit). customer in brochure No. 1-1730,
KFGS
4.5.5.2 Connections for system monitoring 4.5.5.3 Connectivity for timer operation 4.5.5.4 Connectivity for timer operation with
without system monitoring system monitoring (and ill level control)
(and ill level control)
Programming: tPA, tCO, COP = OFF Programming: tPA, tCO, COP = CS or PS
KFGS
1
2
3
4
1
3
4
X2 X2
WH
BN
BU
BU
BK
BK
3 4
2
1
3
EN60947-5-2
BN
BU
BK
SL2 SL2
CS/PS 2,4W
2,4W
Socket pin assignment Connector pin assignment in timer operation Connector pin assignment in timer operation
PIN Color code Conductor coloring PIN Code Assignment PIN Code Assignment
1 BN Brown 3 SL2 "Fault" indicator light ( - ) 1 Voltage ( + )
2 WH White 4 SL2 "Fault" indicator light ( + ) 2 CS/PS Cycle/pressure switch (signal)
3 BU Blue 3 SL2 "Fault" indicator light ( - )
4 BK Black 4 SL2 "Fault" indicator light ( + )
EN Page 40 Assembly instructions
The KFGC (CAN bus) pump unit is available in Connector pin assignment for power supply
the voltage designs 12 VDC and 24 VDC.
In this version, the electrical connection is PIN Color code Function
1 BN Brown 31 M
established via a 7-pin plug-in connection on
2 RD-BK Red-black 15 +
the underside of the pump unit. There is also
3 BU Blue MC+/CS4+
a 3-pin Deutsch connector on the underside
4 PK Pink MC-/CS4-
for the CAN bus connection. Up to six circular
5 BK Black VT4 +
connectors can also be attached to control the
6 BK Black Vt4 -
reversing valves and sensors. 7 VT-GN Purple-green NC
KFGC
4
6
Accessories
1
3
7
KFGC
B
1 2
C
4 3
CAN bus connection, plug type DEUTSCH DT04-3P-L012 Connection for reversing valve/piston detector
(max. 6 connections)
Connector pin assignment for CAN bus Connector pin assignment for reversing valve/piston detector
PIN Color code Function PIN Color code Input Cs2/Cs3 Output VT1 to VT3
A YE Yellow CAN_H 1 BN Brown + NC
B GN Green CAN-B 2 WH White NC NC
C BK Black CAN-SHLD 3 BU Blue NC -
4 BK Black - +
EN Page 42 Assembly instructions
4.5.6.2 Connectivity
5
B
4
6
1 2
C
1
4 3
3
7
Example of connecting four reversing valves A
2
and four piston detectors on devices with the Assignment of Assignment of Assignment of
maximum equipment level (6x M12x1 circular round 7-pin plug CAN bus plug M12x1 4-pin round plug
Customer-speciic deviations
CS1 CS2 CS3 V1 V2 V3
A B C
1
1
1
2
3
4
X1
2
3
4
2
3
4
2
3
4
2
3
4
2
3
4
1 2 3 4 5 6 7
M 12 x 1
M 12 x 1
M 12 x 1
M12x1
M12x1
M12x1
are possible. CAN-BUS
BN
BU
PK
VT-GN
BK
BK
RD-BK
KFGC
M 1 2x 1
M 1 2x 1
M 1 2x 1
M12x1
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
1
F1
15 SL2
CS4 (MC) V4 RD CS1 CS2 CS3 V1 V2 V3
S1
31 30
CS.. = Piston detectors V.. = Reversing valves
M L+
5
B
4
6
machine contact and a reversing valve to a C
1
3
7
device with minimum equipment level (without A
2
M12x1 circular connectors) for operating a Assignment of 7-pin circular connector Assignment of CAN bus plug
A B C
X1 1 2 3 4 5 6 7
CAN-BUS
BN
BU
PK
VT-GN
BK
BK
RD-BK
KFGC
M12x1
1
2
3
4
2
F1
15 SL2
S1 CS4 (MC) V4 RD
31 30
M L+
Piston detector V.. = Reversing valves
4.5.6.3 Example of CAN bus control with up to four independent zones can be supplied 4.5.6.4 CAN bus system coniguration
5/4 directional solenoid valve with lubricant, controlled and monitored. The with connection to CAN bus system
5/4 directional control valve thus replaces up
The 5/4 directional control valve is intended for to four 2/2 directional control valves. During These systems are conigured via the CAN bus
use in progressive feeder lubrication systems the switching process, there may be a brief connection. Please see the "LC-CAN 5000
and in the industrial sector. It possesses an connection (approx. 0.1 s) between the main Coniguration and Control Interface Protocol"
input which can be switched to one of the four line and non-actuated lubrication lines. The manual for details on coniguring and com-
outputs at a time. Using this valve, especially in DCV5-4+924 5/4 directional control valve is municating with the control unit over the CAN
combination with the KFG CAN bus pump unit, electrically actuated with 24 VDC. network using the SAE J1939 communication
protocol.
CS4
CS2
CS3 without connection to CAN bus system
CS1
4 5 6 7
Systems without a connection to a CAN bus
system are conigured using a PC with an IrDA
24 VDC
interface.
KFGC (CAN bus) 1 A coniguration program needs to be installed
pump unit 4
1
3
5 2 on the PC to do this. You can obtain this pro-
M gram from the SKF Service Center.
M 3
2 Connector 3
Legend for connection diagram example with a 5/4 directional solenoid valve
1 KFG CAN bus pump unit 2 Pressure regulating valve
3 DCV5-4+924 5/4 directional control valve 4 - 7 Progressive feeders
CS1 – CS4 Piston detectors for zones 1 – 4
Assembly instructions Page 45 EN
4.6 Fill level control for pump unit 4.7 Progressive system ventilation 4.8 Single-line system ventilation
KFG
on a regular basis for safety reasons. bubbles is discharged at the straight con-
nector on the pump element. bubbles is discharged at the straight con-
The entire system must be ventilated if Mount main lines. nector.
Allow pump to run until grease can be seen Mount main lines.
KFGS
the reservoir has been emptied below
the "min" mark. discharging at all lubrication points. Remove screw plug or pressure switch at
end of main and branch lines.
Automatic Allow pump to run until air is no longer
KFGC
Pumps of the KFGS series allow for automatic discharged at the end of the spool pieces.
ill level control. If the ill level falls below the Mount screw plug or pressure switch.
"min" mark, the lubrication process is stopped Vent lubrication lines and lubrication points
and the fault notiication "FLL" is issued on the and inspect for proper function.
display.
EN Page 46
Type designation
KFG ....
Power supply
24 V DC
cal personnel/operator before assembly Caused by contaminated or unsuitable tions to these operating instructions.
and commissioning. lubricants
The safety instructions listed in Chapter 1, Caused by the installation of non-original
KFGS
"Safety instructions," of the assembly instruc- SKF components or SKF spare parts
tions also apply without restrictions to these Caused by inappropriate usage
operating instructions. Resulting from improper assembly, conigu-
ration or illing
KFGC
SKF Lubrication Systems Germany GmbH 3.1 Lubrication units 3.3 General notes
products are packaged in accordance with
standard commercial practice according to the Ambient conditions: dry and dust-free The product(s) can be enveloped in plastic
regulations of the recipient's country and DIN surroundings, storage in well ventilated film to provide low-dust storage.
ISO 9001. During transport, safe handling dry area Protect against ground moisture by
KFG
must be ensured and the product must be Storage time: max. 24 months storing on a shelf or wooden pallet.
protected from mechanical effects such as im- Permissible humidity: < 65% Bright-finished metallic surfaces, espe-
pacts. The transport packaging must be Storage temperature: 10 - 40°C cially wearing parts and assembly surfac-
KFGS
marked "Do not drop!" Light: avoid direct sun or UV exposure and es, must be protected using long-term
Warning! shield nearby sources of heat anti-corrosive agents before storage.
The product must not be tilted or At approx. 6-month intervals: Check for
dropped. 3.2 Electronic and electrical devices corrosion. If there are signs of corrosion,
KFGC
reapply anti-corrosive agents.
There are no restrictions for land, air or sea Ambient conditions: dry and dust-free Drives must be protected from mechanical
transport. surroundings, storage in well ventilated damage.
After receipt of the shipment, the product(s) dry area
must be inspected for damage and for com- Storage time: max. 24 months
pleteness according to the shipping docu- Permissible humidity: < 65%
ments. The packaging material must be pre- Storage temperature: 10 - 40°C
served until any discrepancies are resolved. Light: avoid direct sun or UV exposure and
SKF Lubrication Systems Germany GmbH shield nearby sources of heat
products are subject to the following storage
conditions:
EN Page 50 4. Assembly/Connection
4. Assembly
4.1 Information on assembly 4.2 Assembly procedure for KFG (S) (C) 4.3 Dismantling and disposal
pump units
The assembly procedure for KFG grease lubri- Assembly must be performed in accordance Warning!
cation pump units is described in detail in the with the included assembly instructions The applicable national environmental
assembly instructions associated with these and the additional information/instructions regulations and statutes are to be ad-
KFG
operating instructions. Information/instruc- contained in this chapter. hered to when dismantling and dispos-
tions about assembling the KFG (S) (C) grease ing of the multiline pump unit.
lubrication pump units beyond the scope of the The product can also be returned to
KFGS
5. Design
5.1 General information 5.2 Design design has a display attached. An IrDA inter-
face is integrated into this, which can optionally
Pump units of the KFG, KFGS and KFGC series Pump units of the KFG and KFGS series are be used to program the pump.
are electrically driven reservoir pump units characterized by their compact construction Depending on the pump version and voltage
available with and without an integrated con- and are divided into assemblies for pump design, the electrical connections are located
KFG
trol unit. The pump provides on-demand lubri- housing, lubricant reservoir, control unit on the left front and/or the underside of the
cant supply to centralized lubrication systems and ill level monitoring. pump housing.
with progressive feeders or single-line distrib- A short description of the individual assemblies
KFGS
utors on machines, systems and vehicles. follows below. 5.2.2 Lubricant reservoir
The pump units differ in terms of the size and
type of lubricant reservoir, the lubricant filling 5.2.1 Pump housing The lubricant reservoir is available in 2 kg,
and their control and function monitoring. 6 kg and 10 kg sizes. The reservoirs are made
Powerful CAN bus versions allow one unit and The pump housing contains, among other of transparent plastic and have fill level mark-
a special valve to supply up to four indepen- things, the pump drive, control unit (KFGS) and ings that allow the fill level to be monitored vi-
dent zones according to demand. three lubricant outlets for installing a maxi- sually. The pump fill level can be monitored
mum of three pump elements. One pressure using an integrated rocker switch or, optionally,
Note regulating valve can be attached to each pump an inductive level switch attached to the cover.
The exact pump designation of the CAN bus element. When used in single-line systems, a
version consists of the particular order code pressure relief valve is also attached to the 5.2.3 KFGS control unit
and begins with the KFGC designation. This pump element together with a pressure regu-
pump design is listed below under the KFGC lating valve. Pump units of the KFGS series are equipped
designation for the sake of simplifying the A conical head nipple can optionally be at- with an integrated IG502-I control unit with a
descriptions. tached to the pump housing via the alternative control display.
connections to fill the pump. A filler socket or Parameters for interval times (timer), interval
grease return can also be attached. pulses (counter) and pump cycle times (con-
A display and control screen is mounted on the tact) can be entered through the control unit.
front side of the KFGS design, while the KFGC
EN Page 52 5. Design
Pump units of the KFG series are reservoir Pump units of the KFGS series are reservoir
pump units without an integrated control unit. pump units with an integrated control unit.
Pumps in the KFG series have different reser- Parameters for interval times (timer), interval
KFG
voir designs and reservoir capacities (2 kg, pulses (counter) and pump cycle times (con-
6 kg and 10 kg) depending on their ield of tact) can be entered through the control panel.
application. A piston detector is used to monitor the feed-
KFGS
Pump units of the KFGC (CAN bus) series are Aside from valve control, the outputs can Important system events such as a low ill
pump units from the KFGS series with an also be conigured as digital outputs for other level in the lubricant reservoir are saved by
integrated CAN bus control unit. purposes. the control unit and given a time stamp. This
The integrated LC-CAN 5000 control unit of- allows the causes of operational faults to be
fers the following special features: In addition to the above-mentioned outputs, determined more easily. A description of the
up to four digital inputs are available, e.g., for functions for operational malfunctions can be
CAN bus interface (SAE J1939), which al- monitoring piston detectors, pressure switches found in Chapter 15.
lows units to be seamlessly integrated into or other switching contacts. A detailed descrip- The lexible parameters and coniguration
the CAN bus networks. tion of the electrical connections can be found options allow custom lubrication concepts to
The lubrication system can be monitored, in Chapter 4 in the assembly instructions. be implemented for each individual lubrica-
operated and conigured through the
KFGC
The control unit‘s comprehensive monitoring tion zone in the system. The control unit can
CAN bus. functions allow potential faults to be detected store up to 16 pre-set sets of parameter data
There is also the option of coniguring and early. This includes, among other things, which can be programmed as desired. Each
operating the pump unit using the existing monitoring the ill level in the lubricant reser- set of parameters contains all the information
IrDA interface. voir, monitoring the signal lines on attached required to control and monitor the lubrication
components for line breakage, and monitor- process. This means that different lubrication
Moreover, the control unit is able to control ing the switching outputs for short circuits. scenarios can be prepared and saved then
and monitor up to four independent zones and Chapter 4 contains a complete description of called on when needed.
to supply them from a single pump unit. the monitoring functions for use in progressive Chapter 11 contains instructions on conigur-
To achieve this capability, electric switch valves feeder systems. ing the system.
which are controlled based on the parameters Chapter 7 contains a complete description of
set for each individual lubrication zone are the monitoring functions for use in single-line
placed in the main line. The control unit has up centralized lubrication systems.
to four solid-state switching outputs for this
purpose.
EN Page 54 5. Design
KFG pump unit without integrated control unit, KFGS pump unit with integrated control unit and KFGC (CAN bus) pump unit with
with 2 kg lubricant reservoir 2 kg lubricant reservoir 6 kg lubricant reservoir
6. Functional description in progressive systems Page 55 EN
6.1 Functional description of progressive 6.1.1 Pump element regulating valve (see Technical Data, Chap-
systems with KFG pump unit ter 4.3.5 in the assembly instructions), the
A general progressive feeder system con- The pump element(s) meter the lubricant then valve opens and the lubricant lows back (on
sists of the following components: pass it to the downstream lubrication points or versions with a return line) into the lubricant
feeders. Five different pump elements with a reservoir.
• Pump unit with pump element and pressure delivery volume ranging from 0.8 to 5 cm3/min.
KFG
regulating valve are available to provide the required quantity
• Lubrication lines, consisting of main and of lubricant (see Chapter 4.3.4 in the assembly 6 6
possibly branch lines instructions). 7
• Progressive feeders 1
When the pump motor is turned on, the piston
pump delivers lubricant from the lubricant res- 2
4
ervoir to the lubricant outlet. The pump ele- 4
5
ment attached to the outlet delivers the lubri- 3
cant further, into the downstream main line.
The lubricant flows through the main line to 4
the progressive feeder. There, the lubricant is
distributed according to the volume required Layout of pump elements Example of progressive system with KFG pump unit
by the lubrication point being supplied.
In progressive systems with a master feeder Progressive system with KFG pump unit
and secondary feeder, the lubricant coming 6.1.2 Pressure regulating valve
1 KFG unit
from the pump unit is delivered to the master 2 Pump element with pressure
feeder. The master feeder distributes the lubri- A pressure regulating valve must be installed regulating valve
3 Electrical pump connection
cant to the secondary feeders according to on the pump element on progressive systems 4 Lubrication lines
their individual volume requirements. From to prevent excessive operating pressure in the 5 Master feeder
6 Secondary feeder
there, the lubricant flows to the lubrication lubrication system. If the operating pressure 7 Lubrication points
points. exceeds the cracking pressure of the pressure
EN Page 56 6. Functional description in progressive systems
7
5
Interval time and pump cycle time can
5
6.3 Functional description of progressive When CAN commands are used for control, 6.3.1 Explanations of the lubrication pro-
system with KFGC (CAN bus) pump unit valve opening must be ensured by selecting cess and lubrication cycle
the appropriate contact and interval times or
The general functional description for pro- by using appropriately programmed processes The lubrication cycle/process is divided into a
gressive systems with a KFGS pump unit also in the external lubrication program to switch pump cycle time and an interval time because
applies for the design with CAN bus pump the valves in a carefully coordinated sequence the lubrication points only require lubrication
control. so that only one valve is activated at a time. at certain intervals. A lubrication cycle always
The integrated LC-CAN 5000 control unit begins with a pump cycle.
permits the lubrication zone of a progressive
feeder system to be distributed into individual
lubrication zones which can be conigured with
individual parameters (e.g., contact and inter-
KFGC
val times). Up to four lubrication zones can be
installed in total.
To distribute the lubricant, a corresponding
number of electric switch valves is installed in
the lubrication line leading from the pump ele-
ment. A valve is opened as soon as the control
unit starts a pump cycle for the corresponding
lubrication zone.
The pump can only provide adequate lubrica-
tion to one lubrication zone at a time, so it
must be ensured that only one valve is opened
during operation. This is handled by the control
unit in automatic and semiautomatic opera- CAN-Bus (SAE J1939)
tion.
Progressive system with KFGC (CAN bus) pump unit
EN Page 58 6. Functional description in progressive systems
Pump cycle time Interval time Block operation, pump delay time
The pump cycle time is the time during which During an interval time, also called interval for and waiting time
the pump delivers lubricant. When multiple short, the pump is idle or, if multiple lubrica- On systems with piston detector monitoring,
lubrication zones are used, one of the zone tion zones are used, the valve for the lubrica- there may be various non-critical reasons for
valves is opened and then closed once the tion zone in question is closed. the set number of piston detector signals not
pump cycle ends. The duration of the interval time can be being received during the pump cycle time. In
The duration of the pump cycle time is a time conigured. this case, a second pump cycle time is started
value conigurable in hours, minutes and sec- In automatic mode, the interval time can be after a certain delay.
onds. The pump cycle time for units with W1 determined in two different ways: by specify- This process can be repeated multiple times.
ill level control can also be set in pulses, i.e., ing either a time value (interval timer) or a This process is also referred to as block opera-
the number of agitator revolutions. The quan- number of pulses (interval counter) sent to the tion, as the pump starts and stops quickly
tity of lubricant to be delivered is thus largely control unit by the machine depending on how several times.
KFGC
independent of ambient conditions. long it has been running. This provides two Block operation is interrupted as soon as the
It is also possible to limit the pump cycle time different means of control: timer mode and set number of piston detector signals has
based on the pulses (strokes) received from counter mode. been received. The length of an interval time
the piston detector. In semi-automatic mode, the user sets the following a successful block operation is not
The pump unit switches off after the deined interval between two lubrications. changed. Operation continues as normal.
number of pulses (strokes) is reached. The When coniguring the lubrication scenario, If the set number of piston detector signals is
pulses must be received within a deined pe- the interval time is a delay for consecutively not reached during block operation, the control
riod of time, otherwise the pump unit switches opening the valves of the individual lubrica- unit switches off the affected lubrication zone
to block operation. tion zones after a lubrication cycle has been or the entire lubrication system and issues a
started. This prevents all valves from opening fault notiication.
at the same time. The number of blocks to be cycled through can
be conigured.
6. Functional description in progressive systems Page 59 EN
KFGC
mands. Only the CAN command START/STOP Control using machine pulses
is allowed. (Counter mode = load-dependent lubrication)
The control unit controls the following func- The duration of the interval time is determined
tions based on the set parameters: by a pulse generator that sends pulses to the
control unit based on how long the machine
Starting and switching off the pump has been running. The control unit counts the
Opening and closing the valves of the pulses that are received and starts the pump
lubrication zones or opens the corresponding zone valve after
the preset number of pulses. The pump cycle
The interval time and pump cycle time are time is deined by a time value. Both the num-
the most important parameters for controlling ber of pulses that determine the interval time
these processes. They can be set in different and the pump cycle time can be conigured.
ways.
EN Page 60 6. Functional description in progressive systems
In this operating mode, every lubrication cycle The pump cycle time for each zone is based on In this operating mode, both the pump motor
must be started by a CAN START command. time or pulses and is conigured by entering and the lubrication zone valves can be con-
When the control unit receives the START the time in hours, trolled as desired via CAN commands. Interval
command, the lubrication scenario conigured minutes and seconds or a number of pulses and pump cycle times which are conigured in
in the selected parameter set is loaded and (corresponding to revolutions of the pump's the parameter sets are ignored.
processed. agitator). When multiple lubrication zones are used,
The valve for the lubrication zone conigured in care must be taken that multiple valves are
the parameter set as the start zone is opened. The lubrication cycle can only be aborted using not opened at the same time during a pump
The valves for the other zones are opened a CAN STOP command. If a new lubrication cycle, as this can result in undersupply of the
after a delay, which is conigured as "interval cycle is started by a CAN START command lubrication points.
KFGC
time." If interval times are the same in multiple while another lubrication process is ongoing,
zones, the valves are actuated according to the the ongoing process is aborted and the new
numerical sequence conigured. This prevents process is started.
the pump from having to supply multiple lu- The system stops after completion of the lubri-
brication zones at the same time. If the pump cation cycle. The next lubrication cycle must be
cycle times for multiple zones still overlap, e.g., initiated by another CAN command.
in block operation, the control unit actuates the
zones as described in the preceding section.
6. Functional description in progressive systems Page 61 EN
6.3.3 Monitoring functions 6.3.3.1 System monitoring 6.3.3.2 Fill level monitoring
The following functions are available for moni- This function includes the following monitoring Depending on the lubricant, either mechanical
toring the lubrication system: functions: or capacitive sensors are used to monitor the
• Fill level monitoring ill level in the lubricant reservoir. In the stan-
Fill level monitoring • Monitoring the lubrication cycle dard design, a mechanical sensor (W1 or W1G)
Monitoring the lubrication cycle via via piston detector monitors whether the lubricant falls below the
piston detector System monitoring can be activated and "min." mark. This is preferred for use with
Monitoring signal cables for cable deactivated. The monitoring functions men- greases of NLGI Grade 2.
breakage and monitoring valves and tioned above are deactivated when system For NLGI Grade ≤ 1 greases, a capacitive sen-
piston detectors monitoring is deactivated. This means that no sor (W2) is provided which is integrated into
Monitoring switch outputs for short circuit fault notiication is issued if, for example, the ill the reservoir cover. The sensor sends a signal
KFGC
Monitoring power consumption of the level in the lubricant reservoir falls below the to the control unit if the lubricant level reaches
pump motor "min" mark. the "min" mark. The control unit then gener-
Monitoring the temperature in the It only makes sense to deactivate system ates a fault notiication (see Chapter 15).
pump unit monitoring if the functions mentioned above
Diagnostics memory (real-time) cannot be used because the required sensors Fault notiications due to insuficient
are not connected. ill level are only issued when system
monitoring is active.
EN Page 62 6. Functional description in progressive systems
6.3.3.3 Monitoring lubrication cycle via 6.3.3.4 Monitoring signal cables for cable
piston detector breakage and monitoring valves and
piston detectors
The progressive feeders installed on the lubri- If the speciied number of piston detector Every signal input conigured for connecting a
cation system are supplied with lubricant sev- pulses is not reached during the pump cycle, piston detector to the control unit is constantly
eral times during the pump cycle. They then the control unit reacts by starting block opera- monitored for cable breakage.
deliver the lubricant to the lubrication point. tion.
The complete piston movement of a progres- In contrast with the KFGS pump unit, the KFGC On a lubrication system with multiple zones,
sive feeder forward and back to the normal (CAN bus) design can repeat the lubrication the piston detector assigned to a zone is
position is also called a cycle. The piston move- cycle as often as desired. queried before the zone valve is opened. If the
ment can be detected via a contact switch, If the speciied number of pulses (strokes) is piston detector is not found, the control unit
a "piston detector," which sends the corre- reached during the repeat lubrication cycle, the assumes a cable has been broken. In this case,
the lubrication cycle is irst started according to
KFGC
sponding signals to the control unit. There, the pump unit switches back to normal operation.
signals are registered and evaluated. the speciied pump cycle time. The lubrication
The number of cycles which must occur before If the set number of piston detector signals is zone is then deactivated until the piston detec-
an interval time is started can be speciied not reached during block operation, the control tor fault is resolved.
in order to monitor the lubrication cycle and unit switches off the affected lubrication zone Block operation is not initiated.
ensure suficient lubrication of the lubrication or the entire lubrication system and issues a On a system without multiple lubrication
points. fault notiication. (see Chapter 15.2). zones, the unit is fully deactivated after the
A coniguration setting also determines pump cycle time is inished.
whether the pump cycle should be ended after A fault notiication is generated in all cases (see
the speciied number of piston detector pulses Chapter 15.2).
has been reached or whether the pump should
continue to operate until the speciied time
value or number of pulses (revolutions of the
agitator) is reached.
6. Functional description in progressive systems Page 63 EN
The signal inputs can be linked to the outputs. The control unit is capable of detecting short The power consumption of the pump motor
This allows indirect monitoring of whether circuit faults on the outputs. In such cases, the is monitored to avoid motor overload. If the
a valve attached to the output has actually output is switched off, which idles the cor- limit values are exceeded (see Technical Data,
opened to allow lubricant through. The inputs responding valve, and a fault notiication is Chapter 4.5.1 in the assembly instructions),
and outputs must be clearly assigned. A signal generated. the system is switched off and enters fault
input used to, for example, operate a cycle Unaffected valves continue to operate. mode (see Chapter 15.2).
switch can only monitor the valve of the lubri-
cation zone that contains the piston detector.
KFGC
EN Page 64 6. Functional description in progressive systems
6.3.3.7 Monitoring unit temperature 6.3.4 Display and documentation functions 6.3.5 Conigurable parameters
The printed circuit board of the LC-CAN 5000 During system operation, current operational The control unit contains 16 pre-set sets of
control unit contains a temperature sensor. If data (status data) is stored in the FRAM and parameter data which can be programmed
the temperature in the unit exceeds the limit can be read at any time. as desired. A parameter set contains all the
value (see Technical Data, Chapter 13), the If the control unit is switched off or loses information required to control and monitor
system is switched off and enters fault mode power, the most recent status data remains in the lubrication process, e.g., the number of
(see Chapter 11). the FRAM. When the control unit is turned on lubrication zones, the interval times, the pump
again, it reads the saved data and the lubrica- cycle times, the number of cycles, etc.
tion process continues where it left off, unless
the coniguration has been changed (zero
voltage signal).
KFGC
KFG
regulating valve, pressure relief valve main line able with different metering volumes.
and single-line distributors.
4
When the pump motor is turned on, the pump 7.1.2 Pressure regulating valve
unit delivers lubricant from the reservoir to the
lubricant outlet. The pump element attached to A pressure regulating valve must be installed 4
the outlet meters the lubricant and delivers it on the pump element on single-line systems
further through the pressure relief valve at- to prevent excessive operating pressure in the
tached to the pump element on to the main lubrication system. If the operating pressure
3
line. The lubricant flows through the main line exceeds the cracking pressure of the pres- 1
to the single-line distributors, where it is me- sure regulating valve, the valve opens and the
lubricant escapes through the valve or lows
2
tered and passed to the lubrication points. This
is performed during or after the pump cycle back into the reservoir. This protects the pump
time, depending on the type of distributors unit against overload.
used (prelubrication or relubrication distribu-
tors). After metering is complete, the pump 7.1.3 Pressure relief valve Single-line system with KFG pump unit
unit is cutoff by a pressure switch and the
1 KFG unit
pressure relief valve is switched. After the main In order to allow another lubrication cycle after
metering is complete, the main line must irst
2 Pump element with pressure relief
line has been relieved, the pump unit is now valve with integrated pressure
prepared for another lubrication cycle. be relieved of pressure, which also relieves the regulating valve
downstream single-line distributors. The main 3 Main line
line and single-line distributors relieve into the 4 Single-line distributor
lubricant reservoir. 5 Pressure switch
EN Page 66 7. Functional description in single-line systems
monitored systems 4
3
7.3. Functional description in single-line 7.3.1 Systems with directional 7.3.2 Multiple lubrication zones
systems with KFGC (CAN bus) solenoid valves
pump unit Using the integrated LC-CAN 5000
Directional solenoid valves can be used to control unit, a single-line system can be
The general functional description for single- create a single-line system with up to four divided into up to four individually controllable
line systems with a KFG pump unit also applies lubrication zones. The system can be equipped lubrication zones. This is performed using
for the design with CAN bus pump control. with or without functionality to monitor pres- electric switch valves which separate the indi-
sure build-up and reduction. vidual lubrication zones from each other.
Note Four conigurable digital inputs/outputs are
Depending on the ield of application and the available to control each lubrication zone. This,
system design, a compact 5/4 directional as well as the type of valves used, provides
solenoid valve can be used in place of individual various possibilities for setting up lubrication
KFGC
3/2 directional solenoid valves. zones.
1 Legend
CAN KFG
7.3.3 Control unit Pump cycle time on systems without Pump cycle time and pump delay time on
pressure build-up monitoring systems with pressure build-up
Explanations of the lubrication process During the pump cycle time, the system monitoring
pressure required for lubrication is built up in The pressure switch monitors whether the
A differentiation is made between lubrication the lubrication line. When multiple lubrication required pressure buildup occurs in the lubri-
cycles with and without pressure build-up zones are used, the inlet valve of the relevant cation line during the pump cycle time. If the
monitoring. lubrication zone is opened at the start of the pressure (switching point) set on the pressure
pump cycle time. The associated pressure switch is reached, the control unit receives the
Lubrication cycle without pressure build-up relief valve is closed. switching signal from the pressure switch and
monitoring Change-over can alternately be performed via then ends the pump cycle time. The pump
On single-line systems without pressure build- a 3/2 directional solenoid valve instead of the delay time is started at the same time.
up monitoring, the lubrication cycle consists of two required 2/2 directional solenoid valves.
Once the pump cycle time is inished, the
KFGC
KFGC
or an external number of pulses sent to the is allowed. Control using machine pulses
control unit by the machine depending on how (Counter mode = load-dependent lubrication)
long it has been running. This provides two The control unit controls the following func- The duration of the interval time is determined
different means of control: timer mode and tions based on the set parameters: by a pulse generator that sends pulses to the
counter mode. control unit based on how long the machine
Starting and switching off the pump has been running. The control unit counts the
Opening and closing the valves of the pulses that are received and starts a pump
lubrication zones cycle after the preset number of pulses. Both
the number of pulses that determine the
The interval time and pump cycle time are interval time and the pump cycle time can be
the most important parameters for controlling conigured.
these processes. They can be set in different
ways. When multiple lubrication zones are used,
multiple zone valves may be addressed at the
same time in automatic mode.
EN Page 70 7. Functional description in single-line systems
In this case, the control unit opens the valves the preceding section. 7.3.3.3 Control via CAN commands
in a carefully coordinated sequence so that The pump cycle time for each zone is time-
only one valve is activated at a time, while still dependent and is conigured by entering a In this operating mode, both the pump mo-
providing all feeders with lubrication. The re- time value in hours, minutes and seconds. tor and the lubrication zone valves can be
sult is that the pump cycle time for each zone The pump cycle time for units with W1 ill controlled as desired via CAN commands. Any
is maintained. level control can also be set in pulses, i.e., the parameter values that have been programmed
number of agitator revolutions. for interval and pump cycle times are ignored.
7.3.3.2 Semi-automatic control The lubrication cycle can only be aborted using
a CAN STOP command. If a new lubrication When multiple lubrication zones are used,
In this operating mode, every lubrication cycle cycle is started by a CAN START command care must be taken that multiple valves are
must be started by a CAN command. while another lubrication process is ongoing, not opened at the same time during a pump
When the control unit receives the START the ongoing process is aborted and the new cycle, as this can result in undersupply of the
command, the lubrication scenario conigured
KFGC
7.3.4 Monitoring functions 7.3.4.1 Fill level monitoring 7.3.4.2 Pressure build-up monitoring
(single-line systems)
The following functions are available for moni- Depending on the unit design, either mechani-
toring the lubrication system: cal or capacitive sensors are used to monitor The pressure switch monitors whether the re-
the ill level in the lubricant reservoir. On units quired pressure buildup occurs in the lubrica-
Fill level monitoring with ill level monitoring, a mechanical sensor tion line during the pump cycle time. A signal is
Pressure build-up monitoring monitors whether the ill level falls below the sent to the control unit when the set pressure
Pressure reduction monitoring "min." mark (approx. 300 g remaining for NLGI is reached. The signal from the pressure switch
Monitoring signal cables for Grade 2 grease). A second, optional sensor can be used to control the pump cycle time. If
cable breakage and monitoring valves and can be used to generate a pre-warning so the the pressure in the lines reaches the speciied
piston detectors operator is prompted to top up in time. value within a certain time (pump cycle time),
Monitoring outputs for short circuit The sensor sends a signal to the control unit if the pump will continue to be operated for a
Monitoring power consumption of the
KFGC
the lubricant level reaches the "min" mark. The certain time (delay time) and then switched off,
pump motor control unit then generates a fault notiication or the lubrication zone will be closed and the
Monitoring the temperature in the (see Chapter 15). relief procedure initiated.
pump unit
If the pressure in the lubrication line does not
reach the speciied value within the pump
cycle time, this is considered an operational
malfunction. The operational sequence will be
stopped and a fault notiication will be gener-
ated (see also Chapter 15).
EN Page 72 7. Functional description in single-line systems
7.3.4.3 Pressure reduction monitoring 7.3.4.4 Monitoring signal cables for cable 7.3.4.5 Monitoring outputs for short circuit
(single-line systems) breakage and monitoring valves and pres-
sure switches The control unit is capable of detecting short
The pressure reduction in the lubrication line circuit faults on the outputs. In such cases, the
during the relief procedure can also be moni- Every signal input conigured for connecting a output is switched off, which idles the cor-
tored using a pressure switch. The signal from pressure switch to the control unit is constantly responding valve, and a fault notiication is
the pressure switch is evaluated differently monitored for cable breakage. generated.
depending on the pressure relief valve used. On systems with multiple lubrication zones, the Unaffected valves continue to operate.
When 2/2 valves are used, they are closed pressure switch assigned to a zone is queried
once the set minimum pressure is reached in before a valve is opened. If the pressure switch 7.3.4.6 Monitoring power consumption of
the lubrication line. This retains a minimum is not found, the control unit assumes a cable the pump motor
pressure in the lubrication line. has been broken. In this case, the lubrication
KFGC
When 3/2 directional control valves are used, zone is deactivated until the pressure switch The power consumption of the pump motor
the signal from the pressure switch provides fault is resolved. is monitored to avoid motor overload. If the
notiication that the lines have been relieved. If On a system without multiple lubrication zones, limit values are exceeded (see Technical Data,
this is not the case, it is considered a malfunc- the unit is fully deactivated. A fault notiication Chapter 16), the system is switched off and
tion. The operational sequence will be stopped is generated in all cases (see Chapter 15). enters fault mode (see Chapter 15).
and a fault notiication will be generated (see The signal inputs can be linked to the outputs.
also Chapter 15) This allows indirect monitoring of whether 7.3.4.7 Monitoring unit temperature
When 3/2 valves are used, no minimum pres- a valve attached to the output has actually
sure can be established in the lines, as the opened to allow lubricant through. The inputs The printed circuit board of the LC-CAN 5000
valve either opens for pressure build-up or and outputs must be clearly assigned. A signal control unit contains a temperature sensor. If
closes the line while simultaneously relieving input used, e.g., to operate a pressure switch the temperature in the unit exceeds the limit
it. This is not considered a problem on grease can only monitor the valve of the lubrication value (see Technical Data, Chapter 16), the
lubrication systems. zone that contains the pressure switch. system is switched off and enters fault mode
(see Chapter 15).
7. Functional description in single-line systems Page 73 EN
During system operation, current operational The control unit contains 16 sets of param-
data (status data) is stored in the FRAM and eter data. A parameter set contains all the
can be read at any time. information required to control and monitor
If the control unit is switched off or loses the lubrication process, e.g., the number of
power, the most recent status data remains in lubrication zones, the interval times, the pump
the FRAM. When the control unit is turned on cycle times, etc.
again, it reads the saved data and the lubrica-
tion process continues where it left off, unless
the coniguration has been changed.
All faults detected by the lubrication system's
KFGC
monitoring functions are also given a time
stamp and stored persistently in the control
unit's non-volatile memory area.
EN Page 74 8. Commissioning
8. Commissioning
cleaning of the product/centralized The lubricant may only be fed without bubbles.
The lubricant fill level in the lubricant reservoir, lubrication system. The lubricant reservoir, if present, must be
if present, should likewise be subjected to reg- It is recommended that an indication of filled with clean lubricant without introducing
KFGS
ular visual inspection. If the lubricant fill level is the lubricant in use be attached to the bubbles. The product is then operated until lu-
too low, lubricant needs to be added up to the lubricant reservoir in order to prevent bricant without bubbles is discharged at all lu-
maximum mark. accidental mixing of lubricants. brication points.
KFGC
Observe the instructions from the The process of venting the centralized lubrica-
machine manufacturer regarding the tion system can be facilitated by:
lubricants that are to be used.
Opening the ends of the main pipes until
Warning! lubricant without bubbles is discharged.
Only ill using clean lubricant and an
appropriate device. Contaminated Filling long pipe sections before connect-
lubricants can result in severe system ing to the lubrication points.
malfunction. The lubricant reservoir
must be illed without introducing
bubbles.
9. Display and control unit Page 75 EN
9.1 KFGS series Display and control elements of the KFGS control screen
KFGS
1 = CS LED Monitors system function via an external
1 piston detector
CS = Cycle Switch, piston detector
Cycle Switch, piston Piston detector monitoring is The piston detector is monitored
detector active. for signals during the CONTACT
(progressive pump cycle.
systems)
9. Display and control unit Page 77 EN
Low Level fault: fill The minimum fill level has been
level too low. reached in the reservoir.
KFGS
Fault Cycle Switch No signal from piston detector The control unit is currently in
fault: Piston detector during pump cycle. FAULT mode. The operational
sequence has been stopped.
Block mode No signal from the piston detector. Unlike in normal mode, the
control unit is still the monitoring sequence. A fault notification is
issued if the fault remains for three pump cycles times.
EN Page 78 9. Display and control unit
Operating voltage is present on pump unit Value for PAUSE can be changed.
and control unit, system is currently in oper-
ating status PAUSE
Operating voltage is present on pump unit Value for CONTACT can be changed.
and control unit, system is currently in oper-
KFGS
A cycle switch (CS) is used for system Monitoring type can be switched off in pro-
CS monitoring. On progressive feeders, moni- gramming mode.
toring is performed during the pump cycle COP = CS monitoring is active
1 (CONTACT). COP = OFF monitoring is switched off
The LED lights up when a signal is received.
PS
2 A pressure switch (PS) is used for
system monitoring. On single-line systems,
Monitoring by pressure switch cannot be
activated on progressive systems.
monitoring is performed during the pump COP = CS monitoring is active
cycle. COP = OFF monitoring is switched off
Device display - LED display
The LED lights up when a change-over
signal is received.
The operating voltage is present on the pump unit and control unit. The control unit is in
operating status FAULT. The cause can be accessed via the LED display and shown as a fault
code by pressing the pushbutton.
The operational sequence has been stopped.
9. Display and control unit Page 79 EN
Key Function
KFGS
Switch on the display in display mode
Call up last parameter in programming mode
Reduce displayed value by 1
9.2 KFGC series (CAN bus) Display and control elements of the KFGC (CAN bus) control screen
Yellow CS/MC LED Lights up briefly when the control unit detects a signal
edge at an input from a piston detector (CS), pressure
switch or from the machine contact (MC).
KFGC
Red FAULT LED LED lights up:Indicates a fault that does not
immediately influence the lubrication program
(e.g., break in valve cable).
The lubrication program continues despite
the fault notification.
LED flashes:
Indicates a fault that influences the lubrication program
(e.g., break in piston detector cable).
The lubrication program is aborted.
KFGC (CAN bus) display (CAN bus)
9. Display and control unit Page 81 EN
Continuation of "Display and control elements of the KFGC (CAN bus) control screen" table
KFGC
KFGC (CAN bus) display (CAN bus)
EN Page 82 10. KFGS display mode
LED displays. The display does not lash. It is 1 The current operating status is shown
Example: Timer operation pause
used to query the current settings and operat- Press briefly
ing parameters.
Always start the display mode by briely 2 Display remaining interval time for current
pressing one of the two keys. lubrication cycle. Example: 1 h
KFGS
8
or or
KFGS
9 Display operating hours
10/11
+
Example: 1st part of 2nd part of total value
total value Total value: 00533.8 h
Write down. Maximum value: 99999.9 h
13/14
+
Example:1st part of 2nd part of total value
total value Total value: 00033.8 h
Write down. Maximum value: 99999.9 h
Display clears
Oh and Fh values are stored in EEPROM and cannot be deleted.
EN Page 84 11. KFGS programming
KFGS
8
Press briefly
(confirm new value)
When system monitoring is active, you can se- 2 Automatic display of first
lect monitoring via piston detector on progres- parameter: "pause in timer operation"
KFGS
5
Press either until or
Monitoring via piston Monitoring via Pressure
detector "CS" LED flashes switch "PS" LED flashes
6
Press briefly Confirm new setting
KFGS
(confirm code) "PAUSE" LED flashes
(confirm code)
sent to the dealer or authorized SKF
branch ofice.
3 Display flashes
Press briefly
Warning! (confirm key) (000 = factory setting)
Do not enter the digits 321 as the
new code. 4
Press briefly Display flashes
(confirm code)
6
Press briefly Confirm new code
KFGS
1) For the permissible setting range for KFG(S) 90-264 VAC,
see Technical Data, Chapter 16.
EN Page 90 12. KFGS operating modes
The interval and pump cycle are time- The interval depends on the number of pulses; In this operating mode, the lubrication cycle
dependent. the pump cycle time is time-dependent. is controlled solely by the pre-set values for
An external pulse generator must be attached PAUSE and CONTACT.
The lubrication cycle is controlled by the pre- as described in Chapter 4 in the assembly
KFGS
set, time-dependent values for PAUSE and instructions. Monitoring must be switched off.
CONTACT. COP = OFF System malfunctions are
PAUSE: Values in pulses not automatically detected or displayed.
PAUSE: Values in hours CONTACT: Values in minutes
CONTACT: Values in minutes 12.4 With system monitoring
A switch opens and closes based on machine
Set tPA and tCO in programming movements, revolutions, etc. In this operating mode, system functions are
mode. A lubrication is triggered once the set number additionally monitored using external switches.
of pulses (cPA) is reached. The following can be monitored:
Fill level in the lubricant reservoir
Set cPA und tCO in programming Function of progressive feeder using a
mode. piston detector
Function of single-line system using a
pressure switch
12.5 Fill level monitoring 12.6 Monitoring via piston detector The piston detector monitors the movement
Only possible for centralized lubri- of pistons in the progressive feeder during
If ill level monitoring is installed, it is cation systems with progressive CONTACT time (pump cycle time). The fol-
always active. feeders. lowing monitoring setting must be activated in
For greases up to NLGI Grade 2. programming mode:
If the level in the lubricant reservoir falls below COP = CS see Chapter 11.3
the minimum ill level, the lubricant cycle is
stopped and a fault notiication is issued on the 8 8
KFGS
display. 1
9
4
3
2 6
5 5
5
FLL: Fault Low Level (fill level too low)
12.7 Monitoring via pressure switch The pressure switch monitors the pressure
For single-line centralized lubrication build-up at the end of the main line during 5
systems. CONTACT time (pump cycle time). A signal is
For greases up to NLGI Grade 2. sent to the KFGS control unit when the set 4
pressure is reached.
The following monitoring setting must be
activated in programming mode:
4
COP = PS
KFGS
1
3
1 KFG unit
2 Pump element with pressure
relief valve
3 Main line
4 Single-line distributor
5 Pressure switch
13. Shutdown Page 93 EN
13. Shutdown
The described product can be temporarily shut If the product will be permanently shut down,
down by disconnecting the electrical supply the local regulations and laws regarding the
connections. The instructions in the Chapter disposal of contaminated equipment must be
KFG
"General information" in these assembly in- observed.
structions must be observed when doing so.
Warning!
KFGS
If the product is to be shut down for an extend- Lubricants can contaminate soil and
ed period of time, follow the instructions in the bodies of water. Lubricants must be
Chapter "Transport, delivery, and storage" of properly used and disposed of. Observe
these assembly instructions. the local regulations and laws regarding
KFGC
the disposal of lubricants.
To recommission the product, follow the in- The product can also be returned to SKF
structions in the Chapter "Assembly". Lubrication Systems Germany GmbH for dis-
posal, in which case the customer is respon-
sible for reimbursing the costs incurred.
EN Page 94 14. Maintenance
14. Maintenance
Danger! Products from SKF Lubrication Systems Dismantling of the product or individual
Work on products that have not been Germany GmbH are low-maintenance. parts thereof within the statutory war-
de-energized may result in bodily injury. However, all connections and fittings must be ranty period is not permitted and voids
Assembly, maintenance and repair work regularly inspected for proper seating to en- any claims.
may only be performed on products sure proper function and to prevent hazards
KFG
that have been de-energized by quali- from arising. Only original spare parts from SKF
ied technical personnel. The supply Lubrication Systems Germany GmbH
voltage must be switched off before If necessary, the product can be cleaned using may be used. Arbitrary alterations to
KFGS
opening any of the product's compo- mild cleaning agents that are compatible with products and the use of non-original
nents. the product's materials (non-alkaline, non- spare parts and accessories are not
soap). For safety reasons, the product should permitted and nullify the statutory
Danger! be disconnected from the power supply and warranty.
KFGC
Centralized lubrication systems are the hydraulic and/or compressed air supply.
pressurized during operation. Central- SKF Lubrication Systems Germany GmbH shall
ized lubrication systems must there- It must be ensured that no cleaning agent en- not be held liable for damages resulting from
fore be depressurized before starting ters the interior of the product during cleaning. improperly performed assembly, maintenance
assembly, maintenance or repair work, and repair work on the product.
or any system modiications or system It is not necessary to clean the interior of the
repairs. product if the product is operated normally and
intercompatible lubricants are used.
Danger!
The described product is pressurized The interior of the product must be cleaned if
during operation. The product must incorrect or contaminated lubricant is acciden-
therefore be depressurized before tally filled into the product. If this occurs,
starting assembly, maintenance or re- please contact the Service department of SKF
pair work, or any system modiications Lubrication Systems Germany GmbH for
or system repairs. assistance.
14. Maintenance Page 95 EN
The following maintenance table contains an If you encounter problems or have any ques-
overview of the inspections and maintenance tions, please contact our sales and service
work that must be performed on a regular centers or our representatives abroad.
KFG
basis. A list with current addresses is available on the
The maintenance intervals depend on custom- Internet at: www.skf.com/lubrication
er-speciic settings and operating conditions.
KFGS
The customer is therefore responsible for
determining and observing the maintenance
intervals on its own.
KFGC
All work beyond this scope must be
performed by authorized SKF Service
establishments.
EN Page 96 14. Maintenance
Maintenance work
Check of fill level in lubricant Refill if necessary. Depends on planned lubricant consumption
reservoir
Inspection of system Parts that exhibit leaks must be replaced. After each refill of the lubricant reservoir or after
KFGS
components (lubricant Please contact an SKF service office. long operational pauses before commissioning the
lines, connection points, seals, machine/vehicle
etc.) for leaks
Visual inspection of bearings' In case of insufficient bearing lubrication, a fault in the In conjunction with lubrication reservoir filling
KFGC
KFGC
external pushbutton, if installed. sequence has been stopped.
If the reservoir has been emptied, the entire
system must be ventilated after reilling (see
Chapter 6, Assembly). Warning!
Determine and remedy the cause of
KFGS faults before deleting fault notiications.
All fault notiications are displayed by the LEDs The user is liable for damages resulting
as a centralized fault notiication. When from operating the machine without
a fault notiication is issued, the control unit lubrication.
stops the normal operational sequence and the
fault that has occurred is saved and displayed. The time during which the control unit
The cause of the fault can be read on the dis- and pump unit have been operated
play. This greatly simpliies failure diagnostics, without lubrication is stored as fault
though it requires system monitoring. hours Fh in the EEPROM and cannot be
deleted.
EN Page 98 15. Operational and pump faults
Fault types
KFGS
Warning A problem has occurred that does - LED Fill level in the reservoir The LED lights up.
not affect the operational sequence lights up sinks to the level of the A fault notification is generated.
but can lead to an operational and remains pre-warning sensor (only Operation continues as normal.
malfunction if not remedied. constant on systems equipped
and configured with this
functionality).
Mal- A fault has occurred that affects - LED flashes Insufficient number of piston 1. Block operation up to configured
function the proper functioning of the detector signals from a number of repetitions
lubrication system. lubrication zone during the 2. - If the piston detector signal
pump cycle has still not been received,
The lubrication points may the valve is closed and a
not be supplied with adequate fault notification is generated.
lubrication because a malfunc-
tion has affected the proper - The LED lights up.
functioning of the lubrication
system.
15.1.5 Recording fault times 15.1.6 Maintenance and repair All work beyond this scope must be
performed by authorized SKF Service
Fault-state counter The following maintenance and repair work establishments.
The amount of time that passes from issuance must be performed on a regular basis:
of a failure notiication to its acknowledgment The purity of the lubricants used is the decisive
is added up in hours. After acknowledgment, Inspect ill level in lubricant reservoir. factor in the service life of the pump elements.
this value is automatically transferred to the Regularly inspect system components
fault-hours counter. for leaks.
Visually inspect lubrication of bearings.
KFGS
Fault-hours counter Inspect electrical cables for damage.
The fault-hours counter adds up all fault-state Inspect electrical connections and
times occurring during the total running time contacts.
of the unit. The current counter reading can The basic function of the control unit
be read in display mode in two blocks of three and system components can be inspected
digits each by calling up the parameter Fh (see by triggering an interim lubrication.
Chapter 6). Inspect electrical connections in case of
The maximum reading that can be displayed is malfunction notiications.
99 999.9 hours. Replace defective fuses with new fuses
The smallest recordable interval is of the same performance and
0.1 hours = 6 minutes. characteristics.
The memory cannot be deleted.
EN Page 100 15. Operational and pump faults
15.1.7 Malfunctions on pump unit No signal from the piston detector Duration of block pause
in progressive system
Pause Normal operation blo
Block operation tPA block pause
Block operation is the reaction of the control C
S
0.1 h = 6 min 6 min
unit to the absence of signals from the piston
0.2 h = 12 min 12 min
detector. 0.3 h and longer 15 min
Possible causes:
Defective lubrication lines
KFGS
• Determine and remedy cause of fault.
Blocked progressive feeder Three pump cycles and two block pauses with-
Defective piston detector out signal from the piston detector:
Insuficient lubricant Block operation is aborted
No signal from piston detector Malfunction notiication is issued.
during pump cycle:
Normal operation is interrupted.
Block pause begins with query to
piston detector.
No signal from piston detector
during block pause:
Second lubrication cycle begins in
block operation.
As soon as a signal is received from the piston
detector, block operation is aborted and the
normal lubrication cycle starts with a pause. Fault notification on device display
KFG
Pump Agitator in Malfunction Mechanical damage, • Replace pump
grease reservoir does e.g., motor defective - Loosen main line at outlet of pressure regulating valve.
not rotate during the - Loosen electrical connection.
activated pump cycle - Loosen three fastening screws.
KFGS
(CONTACT mode). - Remove defective pump.
- Mount new pump and connect lubrication line
and electrical cable.
• Perform commissioning and functional inspection.
• Be sure the interval and contact times are correct.
• Check or replace fuse.
Electrical connection interrupted • Check electrical connections
• Check cable set for damage.
Pump does not Malfunction Electrical control has failed. • Check fuse
function when the Pump drive/motor is defective. • Replace pump
key is pressed,
although all electrical Lubricant level in reservoir is
connections are ok. below minimum. • Fill lubricant reservoir to "max."
although agitator is
rotating. pump element is worn out. • Replace pump element
(This is indicated when the outlet can be Note: metering is indicated by grooves.
closed with a finger once the main line is
removed.)
KFGS
Pressure regulating Malfunction System pressure is over 200/300 bar, e.g., • Check system and repair/rework the system so the
valve on pump due to feeder blockage or blocked lubrication maximum system pressure at 20 °C is 200 bar.
opens and lubricant point.
discharges.
Valve is damaged or contaminated, so it does • Replace pressure regulating valve .
not close properly.
15. Operational and pump faults Page 103 EN
15.2 Operational malfunctions on KFGC 15.2.3 Fault types 15.2.6 Remedy faults
(CAN bus)
Depending on the severity of the fault, the Always check cables irst when a fault
15.2.1 Pump malfunctions control unit issues either a warning or a mal- occurs. Most signal cables are moni-
function notiication (see following table). tored for breakage, so a defective cable
The possible causes of malfunctions listed in or loose contact can cause a fault
Chapter 11.1.8, "Malfunctions on KFG/KFGC 15.2.4 Fault notiication notiication.
pump units," also apply for the KFGC CAN bus
version. Warnings are indicated by a constant When a warning occurs, it is recom-
LED light. At the same time, the fault notiica- mended that the system be stopped
15.2.2 Faults detected by control unit tion is stored in the FRAM. and the fault be remedied.
Malfunctions are indicated by a lashing
KFGC
The comprehensive monitoring functions of LED light. At the same time, the fault When a malfunction occurs, the fault
the LC-CAN 5000 control unit allow faults in notiication is stored in the FRAM. must be remedied immediately in order
the operational process to be detected, regis- to prevent damage to the machine and
tered and displayed. 15.2.5 Read faults the associated risk of accidents.
Several faults, e.g., due to insuficient All fault notiications generated during op- After the fault has been remedied and
ill level or the absence of a signal from eration are stored in the control unit's FRAM before operation is resumed, the key
the piston detector, are only displayed together with further system parameters and must be pressed or the equivalent CAN
when system monitoring is active (see a timestamp. They can then be read from the command sent to reset the system's
Chapter 6.3.3.1, page 61). FRAM. This allows each failure to be uniquely fault status and delete the fault notiica-
identiied by its code. Refer to the "LC- tions.
CAN5000 - Coniguration and Control Inter-
face Protocol" manual for more information.
EN Page 104 15. Operational and pump faults
Fault types
Malfunction A fault has occurred that affects LED flashes Insufficient number of piston 1. Block operation up to configured
the proper functioning of the detector signals from a number of repetitions
lubrication system. lubrication zone during the 2. - If the piston detector signal
pump cycle has still not been received,
The lubrication points the valve is closed and a
KFGC
15.2.7 Warning and malfunction indicator on KFGC (CAN bus) pump unit
Fill level Warning Fill level in lubricant reservoir • Immediately refill with lubricant (see Chapter 4.4, page 22),
warning falls to warning sensor change pump element if necessary.
Break in sensor cable • Replace cable
Lubricant too soft • Replace lubricant
Fill level fault Malfunction Fill level in lubricant reservoir reaches • Immediately refill with lubricant (see Chapter 4.4, page 22)
"min" mark • Replace the cable.
Break in sensor cable
Cycle fault Malfunction Lubrication line defective • Replace the defective line.
Progressive feeder blocked or • Clean the feeder or replace it.
KFGC
defective
Piston detector defective • Replace the piston detector.
Insufficient lubricant • Immediately refill with lubricant (see Chapter 4.4, page 22),
change pump element if necessary.
Break in sensor cable • Replace the cable.
Pressure Malfunction Lubrication line defective • Replace the defective line.
build-up fault Pressure switch defective • Replace the pressure switch.
Pressure relief valve blocked • Clean the valve or replace it.
or defective • Immediately refill with lubricant (see Chapter 4.4, page 22),
Insufficient lubricant change pump element if necessary.
• Replace the cable.
Break in sensor cable • Replace lubricant
Lubricant too stiff • Increase main line cross-section.
Main line cross-section too small
Pressure Malfunction Pressure relief valve blocked or • Clean the valve or replace it.
reduction fault defective • Replace the pressure switch.
Pressure switch defective • Replace the cable.
Break in sensor cable • Fill lubricant at suitable flow pressure, clean system.
Lubricant too consistent
EN Page 106 15. Operational and pump faults
Temperature fault Malfunction Ambient temperature too high • Check system for line blockage and lubricant for feedability.
Output power too high • Let pump unit cool down.
Motor current fault Malfunction Partial or total blockage of motor shaft • Check the agitator for freedom of movement.
and/or agitator • Check whether objects in the grease reservoir
are impeding the agitator.
• Check the lubricant for feedability.
Input/output was configured but the
KFGC
KFG
"Functional Extra Low Voltage,"
"Protective Extra Low Voltage“ (PELV)
KFGS
Disconnect the unit for insulation and
voltage inspection according to
EN 60204-1 1992.
KFGC
EN Page 108 16. Technical data
Technical data
Description Value
KFG(S) 1-5 KFG(S) 3-5 KFG(S) 5-5
KFG
Lubricant NLGI Grade 1 to 2 greases with EP additives, compatible with plastics, NBR elastomers, copper and copper
alloys, and NLGI Grade 000 to 0 fluid greases
Flow pressure Up to max. 700 mbar
16. Technical data Page 109 EN
KFG
Rated voltage 12 VDC 24 VDC
Power consumption (load-dependent) 2.4 A 1) 1.25 A 1)
Power consumption (maximum) <5A < 2.5 A
Pump starting current (approx. 20 ms) 9A 4.5 A
KFGS
Max. pre-connected fuse 10 A 2) 3) 7.5 A 2) 3)
Fill level switch W1 NLGI 2 Fault notification via pulse
Fill level switch W1_smooth NLGI 2 Fault notification via energized contact
NLGI ≤ 1 Fault notification via capacitive proximity switch
KFGC
Fill level switch W2
Electrically controlled 12/24 VDC or 230 VAC
pressure relief valve
17. Accessories
Accessories
KFG
with cable for connecting to pis-
ton detector and an external fault Two-way distributor (for connecting to the M12x1 plug on the pump with 2x M12x1 outputs 179-990-700
indicator for piston detector and separate indicator lamp)
KFGS
M12x1 plug without cable, with 4 pins, protection class IP 67 (mounted) 179-990-371
M12x1 angle plug without cable, with 4 pins, protection class IP 67 (mounted) 179-990-372
M12x1 plug, straight with 5 m cable, 4x 0.25 mm2, protection class IP 68 (mounted) 179-990-600
KFGC
M12x1 angle plug with 5 m cable, 4x 0.25 mm , protection class IP 68 (mounted)
2
179-990-601
Cable socket Type A (ISO 4400), pivoted, without LED, 1.5 mm , line diameter 6 mm to 9 mm
2
179-990-034
according to DIN 43 650
Cable socket Type A (ISO 4400), pivoted, without LED, 1.5 mm2, line diameter 4.5 mm to 7 mm 179-990-034
according to DIN 43 650
Cable socket Type A (ISO 4400), pivoted, with red LED, 1.5 mm2, line diameter 6 mm to 9 mm 179-990-121
according to DIN 43 650
Additional data and electrical plug-in connections are available in brochure No. 1-1730,
"Electric Plug-and-Socket Connectors."
EN Page 112 17. Accessories
2
3
4
X2 1
light
BN 1 1 2
X3 2 2 X4 3 SL2 “Fault” indicator light (-)
A double-pin plug with a special cable CS/PS
BU 3 3 BU 4 SL2 "Fault" indicator light (+)
adapter is required for this application.
BK 4 179-990-700 4 BK SL2
KFGS
2,4W
BN 1
Connection for piston detector/pressure
WH 2
CS/PS switch CS
BU 3
PIN Code Assignment
1 Voltage ( + )
2 CS/PS Pressure/piston detector (signal)
3 (-)
4 CS/PS Pressure/piston detector (signal)
Accessories
KFG
Application Type designation Features
Order number
Piston distributor for single-line EXZT2A02-E Pulse generator/counter with adjustable interval time, interval time extension,
systems monitoring of pressure build-up and reduction, and fill level monitoring
Piston distributor for single-line EXZT2A03-E Pulse generator/counter with selectable monitoring time, monitoring of fill level and
systems pump cycle time (stroke monitoring), adjustable delay time, and interval time extension
Progressive systems EXZT2A05-E Pulse generator/counter with adjustable interval time, interval time extension,
pressure build-up monitoring, pulse monitoring, and fill level monitoring
Progressive systems EXZT2A06-E Pulse generator/counter with selectable monitoring time, monitoring of fill level and
pump cycle time (stroke monitoring), adjustable delay time, interval time extension, and
pulse monitoring
Piston distributor for EXZT2A07-E Pulse generator/counter with adjustable interval time, interval time extension,
single-line systems pressure build-up monitoring, fill level monitoring, and fill level pre-warning
Electronic timer for centralized IG351-10-E Pulse generator with adjustable interval time, adjustable pump cycle time, and fill level
lubrication systems monitoring with NO-contact
Piston distributor for single-line IGZ38-30-E Pulse generator/counter with adjustable interval time and pressure build-up monitoring,
systems and fill level monitoring with NC contact (wire breakage monitoring)
Piston distributor for single-line IGZ36-20-E Pulse generator/counter with adjustable interval time, monitoring of pressure build-up
systems and reduction, and adjustable delay time
Piston distributor for single-line IGZ36-20-S6-E Same as IGZ36-20-E, but with full level monitoring with NC contact
systems (wire breakage monitoring)
EN Page 114 17. Accessories
adjustable stroke rate, selectable interval time and monitoring time, and
monitoring of fill level and pump cycle time
Progressive systems IGZ51-20-S2-E Same as IGT51-20, but with non-volatile memory in case of power failure
Piston distributor for single-line IGZ51-20-S3-E Pulse generator/counter with adjustable interval time, interval time extension,
systems monitoring of pressure build-up and reduction, adjustable delay time and connectable
non-volatile memory in case of power failure
Progressive systems IGZ51-20-S7-E Same as IGZ51-20-S2, but with fill level switch as NC contact,
pump cycle time = set monitoring time
Progressive systems IGZ51-20-S8-E Pulse generator/counter with selectable intermittent or continuous pump operation, pre-
lubrication, selectable interval time and monitoring time, monitoring of fill level, pump
cycle time and pulses, and non-volatile memory in case of power failure
951-170-203-EN
The contents of this publication are the copyright of the publisher and may not be repro-
duced in whole or in part without permission of SKF Lubrication Systems Germany
GmbH. Every care has been taken to ensure the accuracy of the information contained in
this publication. However, no liability can be accepted for any loss or damage, whether di-
rect, indirect or consequential arising out of use of the information contained herein.
All SKF products may be used only for their intended purpose as described in these as-
sembly instructions with associated operating instructions. If assembly/operating instruc-
tions are supplied together with the products, they must be read and followed. Not all lu-
bricants can be fed using centralized lubrication systems. SKF can, on request, inspect
the feedability of the lubricant selected by the user in centralized lubrication systems.
Lubrication systems and their components manufactured by SKF are not approved for
use in conjunction with gases, liquefied gases, pressurized gases in solution, vapors or
such fluids whose vapor pressure exceeds normal atmospheric pressure (1013 mbar) by
more than 0.5 bar at their maximum permissible temperature.
Particular attention is called to the fact that hazardous materials of any kind, especially
the materials classified as hazardous by CLP Regulation EC 1272/2008 may only be used
to fill SKF centralized lubrication systems and components and delivered and/or distrib-
uted with the same after consulting with and receiving written approval from SKF.
SKF Lubrication Systems Germany GmbH SKF Lubrication Systems Germany GmbH
Motzener Strasse 35/37 ·12277 Berlin · Germany 2. Industriestrasse 4 ·68766 Hockenheim · Germany
PO Box 970444 · 12704 Berlin · Germany
Tel. +49 (0)30 72002-0 · Fax +49 (0)30 72002-111 Tel. +49 (0)62 05 27-0 · Fax +49 (0)62 05 27-101
www.skf.com/lubrication www.skf.com/lubrication