Elfospace Box3: Cassette-Type Indoor Installation

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

CFK 007.0÷041.

Water terminal unit


Cassette-type indoor installation
Capacity from 2,98 to 11,19 kW ELFOSpace BOX3

The ELFOSpace BOX3 terminal unit has been designed for installation in
suspended ceilings without requiring any extra part for operation.
The ELFOSpace BOX3 is therefore suited for use in environments such as shops,
restaurants, hotels and gyms, where the excellent outflowing air control makes
them ideal air-conditioning units:

versions for 2 and 4-pipe systems;

available with standard DC Brushless motor;

suited for installation in standard suspended ceilings with 600 x 600 mm
module;

high standards of efficiency and quiet operation for unit with 800 X 800 mm
module;

standard version with infrared electronics;
 unit comes with a condensate drain pump built-in.
the

ErP compliant

functions and features

H 2O

Cool & heat Cassette type Water DC Motor


TERMINAL Units - AHU

dimensions and clearances


Size – CFK 007.0 011.0 015.0 021.0 031.0 041.0
CC2 A - Length mm 575 575 575 840 840 840
CC2 B - Width mm 575 575 575 840 840 840
CC2 C - Height mm 261 261 261 230 300 300
CC2 D - Length mm 647 647 647 950 950 950
CC2 E - Width mm 647 647 647 950 950 950
B2 A1 CC2 F - Height mm 50 50 50 45 45 45
CC2 A1 mm >1000 >1000 >1000 >1000 >1000 >1000
B A
C CC2 A2 mm >1000 >1000 >1000 >1000 >1000 >1000
B1 A2 CC2 B1 mm >1000 >1000 >1000 >1000 >1000 >1000
CC2 B2 mm >1000 >1000 >1000 >1000 >1000 >1000
F
CC2 Operating weight kg 16,5+2,5 16,5+2,5 16,5+2,5 23+6 27+6 27+6
CC4 A - Length mm 575 575 575 840 840 840
CC4 B - Width mm 575 575 575 840 840 840
CC4 C - Height mm 261 261 261 300 300 300
D
CC4 D - Length mm 647 647 647 950 950 950
E CC4 E - Width mm 647 647 647 950 950 950
CC4 F - Height mm 50 50 50 45 45 45
CC4 A1 mm >1000 >1000 >1000 >1000 >1000 >1000
CC4 A2 mm >1000 >1000 >1000 >1000 >1000 >1000
CAUTION! For trouble-free operation of the unit it is essential to maintain the safety
CC4 B1 mm >1000 >1000 >1000 >1000 >1000 >1000
distances indicated by the green areas. CC4 B2 mm >1000 >1000 >1000 >1000 >1000 >1000
CC4 Operating weight kg 16,7+2,5 16,7+2,5 16,7+2,5 27,5+6 30+6 30+6
The above mentioned data are referred to standard units for the constructive configurations indicated. For all the other configurations, refer to
the relative Technical Bulletin.
CC2 2 pipes
CC4 4-pipe
versions and configurations
PLASTIC FRAME FOR AIR SUPPLY AND RETURN: STANDARD CONFIGURATION:
PLAX Plastic frame for air supply and return (Standard) IRPCB Electronics with infrared remote control (Standard)
R05 R05 infrared remote control (Standard)
COIL CONFIGURATION: VEC High efficiency EC fan (Standard)
CC2 Coil configuration for 2-pipe system (Standard) XYE XYE communication port (Standard)
CC4 Coil configuration for 4-pipe system

technical data
Size – CFK 007.0 011.0 015.0 021.0 031.0 041.0
2-pipe
HIGH SPEED
Airflow m3/h 535 719 781 1175 1581 1871

Cooling capacity (1) kW 2,98 3,96 4,20 5,93 7,87 11,19
Sensible capacity (1) kW 2,49 3,20 3,45 5,00 6,68 9,04
Water flow-rate (1) l/h 530 700 750 1050 1440 1960
Water pressure drop (1) kPa 10,00 11,48 12,32 19,20 22,30 36,60

Heating capacity (2) kW 2,61 4,63 4,95 6,606 9,16 10,07
Water flow-rate (2) l/h 640 830 870 1300 1730 2350
Water pressure drop (2) kPa 12,10 9,20 9,40 25,90 28,80 49,20
Total power input W 15 28 43 41 85 126
MEDIUM SPEED
Airflow m3/h 429 561 611 987 1371 1415

Cooling capacity (1) kW 2,53 3,26 3,48 5,30 7,12 8,82
Sensible capacity (1) kW 2,08 2,57 2,74 4,34 5,95 7,03
Water flow-rate (1) l/h 450 580 610 920 1280 1530
Water pressure drop (1) kPa 7,00 8,20 8,62 15,40 18,10 22,70

Heating capacity (2) kW 2,89 3,79 3,99 6,35 8,54 10,08
Water flow-rate (2) l/h 540 670 700 1140 1570 1860
Water pressure drop (2) kPa 8,50 8,60 8,23 20,10 24,00 31,20
Total power input W 9 15 28 27 59 58
LOW SPEED
Airflow m3/h 322 448 494 768 1236 1198

Cooling capacity (1) kW 2,00 2,76 3,01 4,40 6,67 7,48
Sensible capacity (1) kW 1,59 2,10 2,31 3,52 5,50 5,97
Water flow-rate (1) l/h 350 510 540 770 1220 1280
Water pressure drop (1) kPa 5,00 6,54 7,40 11,00 16,30 16,40

Heating capacity (2) kW 2,24 3,10 3,26 5,32 7,90 8,68
Water flow-rate (2) l/h 420 560 580 1130 1460 1590
Water pressure drop (2) kPa 5,30 6,00 6,10 19,90 20,70 23,30
Total power input W 5 19 21 17 45 39
4-pipe
HIGH SPEED
Airflow m3/h 536 727 731 1287 1785 1857

Cooling capacity (1) kW 2,40 3,08 3,05 5,36 8,75 8,76
Sensible capacity (1) kW 2,08 2,69 2,61 4,66 7,51 7,70
Water flow-rate (1) l/h 420 560 540 990 1570 1580
Water pressure drop (1) kPa 17,40 13,15 16,80 14,80 33,90 33,00

Heating capacity (3) kW 4,24 5,52 5,97 7,38 11,70 12,29
Water flow-rate (3) l/h 320 360 390 610 960 990
Water pressure drop (3) kPa 23,50 24,14 26,80 25,30 42,40 48,70
Total power input W 14 37 32 50 107 125
MEDIUM SPEED
Airflow m3/h 429 569 572 1084 1545 1410

Cooling capacity (1) kW 2,08 2,64 2,62 4,81 7,97 7,29
Sensible capacity (1) kW 1,78 2,24 2,21 4,17 6,74 6,20

TERMINAL Units - AHU


Water flow-rate (1) l/h 360 480 470 870 1430 1300
Water pressure drop (1) kPa 13,50 9,40 13,10 11,50 30,00 22,60

Heating capacity (3) kW 2,86 3,53 3,66 6,06 9,88 9,17
Water flow-rate (3) l/h 270 310 330 550 890 830
Water pressure drop (3) kPa 17,10 17,90 19,20 20,50 36,60 32,50
Total power input W 9 24 17 33 71 58
LOW SPEED
Airflow m3/h 321 451 462 851 1397 1191

Cooling capacity (1) kW 1,65 2,28 2,30 4,00 7,40 6,45
Sensible capacity (1) kW 1,39 1,88 1,90 3,42 6,18 5,40
Water flow-rate (1) l/h 290 410 400 720 1310 1150
Water pressure drop (1) kPa 9,30 7,00 10,30 8,10 24,00 17,70

Heating capacity (3) kW 2,25 2,98 3,09 5,09 9,27 8,24
Water flow-rate (3) l/h 210 270 280 470 840 760
Water pressure drop (3) kPa 11.30 13,10 14,50 14,50 32,60 27,00
Total power input W 5 19 11 19 54 38
Standard power supply V 220-240/1/50
Type of supply fan (4) - RAD DC
No. of supply fans - 1
H Sound pressure level (5) dB(A) 39 42 43 43 48 49
M Sound pressure level (5) dB(A) 33 36 38 39 44 43
L Sound pressure level (5) dB(A) 27 30 32 33 41 39
H Sound power level (5) dB(A) 51 54 55 55 60 61
M Sound power level (5) dB(A) 45 48 50 51 56 55
L Sound power level (5) dB(A) 39 42 44 45 53 51
Notes
The Product is compliant with the Erp (Energy Related Products) European Directive. It includes the (3) Entering exchanger water 65°C (temperature differential 10°C) - Ambient air 20°C
Commission delegated Regulation (EU) No 2016/2281, also known as Ecodesign Lot21. (4) RAD DC = DC Brushless radial fan
(5) Sound levels tested in anechoic chamber and referring to units for 2-pipe systems. The sound
(1) Entering exchanger water 7°C (temperature differential 5°C) - Ambient air 27°C D.B. / 19°C W.B. pressure level refers to 1 m from the external surface of the unit operating in the open field.
(2) Entering exchanger water 45°C (temperature differential 5°C) - Ambient air 20°C
accessories
■• 3V2X Three-way valve kit for 2-pipe "on/off" system ■• CCM08XBacnet gateway
■• 3V4X Three-way valve kit for 4-pipe "on/off" system ■• LONGWXLonworks gateway
■• KJR90X KJR90 electronic room control for wall installation ■• CCM18UX Modbus gateway up to 16 indoor units

■• KJR150X Indoor units group controller ■• CCM18X Modbus gateway up to 64 indoor units
■• CCM30BX Centralized controller with case ■• DTX Auxiliary condensate collection tray
Key to symbols and notes
■•Accessories separately supplied
For compatibility between the various accessories, please refer to the dedicated Technical Bulletin or our website in the Systems and Products section.
TERMINAL Units - AHU
REF-DG19A002GB-00

Data contained in this document are not binding and may be changed by the Manufacturer without notice.