4.3.5 Function Code
4.3.5 Function Code
In the case with three parallel equipments, the center equipment shall not use any suffix. It is like street
numbering. The entry to the main street does not use a suffix letter, but an entry in the backyard do. If only two
units operate in parallel or serial, they shall use the suffix A and B unless there is one main line and one side
line.
Fig. 4.6
In case of a two-letter user defined code, the first letter shall not be A, B or C so that the code is not
confused with a suffix letter followed by a one-letter code!
All values may (also) be Boolean. This is for example used in case of limit switches and feedback from the
process. If for example the feedback signal for a motor comes directly from the motor starter, it should have the
function code G. If it comes from a current sensor, the function code should be I, and if it comes from a rotary
gauge, it should be R.
The function codes are very close to the equipment codes of the widely used ISO 3511 standard (used in for
example EIS, DEP, KKS and NORSOK) except for a few, minor modifications.
Group A, which was previously used for automatic initiated functions and alarms, is now used entirely
for alarms since there is no need for a group for automatic initiated functions.
Like ISO 3511, group B is used for process states like hand operation, auto operation, booting-up,
initializing, stopped, pre-operational, operational, startup, running etc.
Like ISO 3511, group C is used for Boolean commands like hand, auto, start, stop, right, left, open,
close, clockwise, counter-clockwise, up, down etc.
Group E, which is used for voltage in ISO 3511, is used for error codes.