SINGLE

Technical
Data Book
SINGLE for SAMCOL
(R410A, HP)
History

Version Modification Date Remark


Ver.1.0 Release Single TDB for SAMCOL ‘17. 10. 17
Ver.1.1 Added new line-up by each model type ‘17.12.22
Ver.1.2 Revised Outdoor Compressor Oil type ‘18.09.20

2
Features & Benefits

Maintain optimal comfort and control with energy Stabilize the atmosphere with broad temperature
and cost-efficient technologies allowance and control
Featuring a suite of energy-optimizing technologies, Samsung is dedicated to supporting comfortable living
Samsung CAC Single delivers top-class energy efficiency and working environments based on the strength of
to support business in saving costs and the environment. its technologies. With a single unit, CAC Single delivers
reliable comfort and control over multiple areas to
Small package, big performance ensure a pleasant atmosphere in any climate.
The Samsung Ceiling Type air conditioner boasts a Wide temperature performance
slim, compact design—half the size of conventional
products—with cooling power comparable to larger No matter how extreme the temperature, the high-
units. performing CAC Single can handle the condition-
without the need for an additional unit. Featuring a wide
Multi-unit operation temperature allowance, it can cool in heat of up to 50
Instead of connecting just one indoor unit, users can
ensure a constant and comfortable home environment.
connect two indoor units with a single outdoor unit for
more efficient cooling and heating. The indoor units
operate and are controlled simultaneously as one cycle Ideal comfort in minutes
within the same mode via one remote controller for up The CAC Single digital inverter air conditioner works
to four rooms. This system is ideal for spaces requiring at maximum capacity at startup. As soon as the
multiple indoor units, such as open-plan offices or shops. temperature reaches the desired or set temperature,
CAC Single performs fine adjustments to cope with any
Outdoor unit Capacity changes. This means less temperature fluctuation and
2 Rooms
(kBtu/h) ideal comfort in a matter of minutes.
48 24 + 24
Steady Temperature Fluctuation

Non-inverter
High Temperature Fluctuation
Uncomfortable 25 C
(Energy Loss)

24 C
Comfortable

Uncomfortable
(Energy Loss) 23 C

Versatile piping installation


CAC Single outdoor units offer a selection of pipe
directions. The internal pipe connection ports allow
four different pipe directions, supporting a neater, more
organized-looking unit upon installation.

3
Nomenclature
Indoor Unit

Model Name

AC 036 M N 4 P K H CB
(1) (2) (3) (4) (5) (6) (7) (8) Buyer

(1) Classification (5) Product Notation

AC CAC 1 1 Way Cassette


N 4 Way Cassette (600x600)
4 4 Way Cassette, 360 Cassette
L LSP Duct
(2) Capacity M MSP Duct
C Ceiling
X 1,000 Btu/h (3 digits) J Console
A A3050 (Wall Mounted)

(3) Version
(6) Feature
H 2014
J 2015 F Flagship
K 2016 S Standard
M 2017 D Deluxe
P Premium

(4) Product Type


(7) Rating Voltage
N Indoor Unit
X Outdoor Unit K

(8) Mode

4
Nomenclature
Outdoor Unit

Model Name

AC 036 M X A D K H CB
(1) (2) (3) (4) (5) (6) (7) (8) Buyer

(1) Classification (5) Product Notation


AC CAC A Inv+Side+General Temp

(6) Feature
(2) Capacity
F Flagship
X 1,000 Btu/h (3 digits) S Standard
D Deluxe
P Premium

(3) Version

H 2014
J 2015 (7) Rating Voltage
K 2016 K
M 2017 N

(4) Product Type (8) Mode


N Indoor Unit H
X Outdoor Unit

5
Line-up
Indoor unit

Capacity (kBtu/h)
Model
24.0 36.0 48.0

4Way CST

360 CST

Ceiling

Outdoor Unit

Capacity (kBtu/h)
Model
24.0 36.0 48.0

1Phase

6
Contents

4Way Cassette 8
360 Cassette 25
Big Ceiling 44
Outdoor Units 57
Installation 76
Accessory 98

7
4Way Cassette

1. Specification 10
2. Summary Table 13
3. Capacity Table 14
4. Dimensional Drawing 17
5. Center of Gravity 19
6. Electrical Wiring Diagram 20
7. Sound Data 21
8. Temperature and air flow distribution 22

8
Features & Benefits
4Way Cassette

Stage a beautiful yet comfortable environment The Samsung 4Way Cassette indoor air conditioning
system delivers polish, comfort and efficiency with
With its newly improved design, 4Way Cassette supports features such as:
a clean, aesthetically appealing atmosphere and adds
a sense of sophistication to work and living spaces. • Stylishly clean design. Add panache to interior
Not only is this unit attractively designed, but it also spaces with a choice of clean, streamlined panel
uses advanced technologies to optimize comfort in any patterns in a lightweight build.
environment. • Robust operation. Control the atmosphere
perfectly with an advanced design for superior air
flow and cooling/heating performance.
• Low maintenance and simple installation. Ease
installation and minimize maintenance with a
detachable, no-drip design.

4Way Cassette - Stylishly clean design

Complement any interior with a sleek, lightweight design Neat and clean design
The new Samsung 4Way Cassette indoor air conditioner The indoor 4Way Cassette boasts a smart design
comes in a choice of patterns with a simple panel that promotes a neat and clean look. The completely
to better match the interior design. Its uniquely hermetic blade structure keeps the indoor unit clean
lightweight frame makes installation easy, while clever by preventing dust or other foreign substances from
blade construction keeps the unit clean for a tidy entering it. The internal parts of the indoor unit
appearance. are also out of sight when the blade is shut, thus
improving the unit’s appearance.

Lightweight build
The Samsung 4Way Cassette indoor unit is now lighter
in weight at 18 kg. It is one of the lightest indoor
units in the industry, about 40 percent lighter than
conventional products.
4Way Casseette Conventional
Aesthetic panel and display
4Way Cassette offers two different pattern designs for
the panel. Users can select either the Waffle or Classic
pattern to create just the right look to suit their design
preference. Plus, the simple display design with rounded
corners adds a chic sophistication to the interior.

*Based on 10kW

9
1. Specification
4Way Cassette

Indoor Unit AC024MN4DKH/CB AC036MN4DKH/CB AC048MN4DKH/CB


Model Name
Outdoor Unit AC024MXADKH/CB AC036MXADKH/CB AC048MXADKH/CB
Mode - Heat pump Heat pump Heat pump
kW 2.20/7.03/8.35 3.00/9.96/12.00 3.51/12.30/16.41
Cooling
Capacity Btu/h 7,500/24,000/28,500 10,200/34,000/40,900 12,000/42,000/56,000
Performance
(Min/Std/Max) kW 1.90/7.91/9.38 2.20/11.14/15.50 3.51/15.50/18.75
Heating
Btu/h 6,500/27,000/32,000 7,500/38,000/52,900 12,000/52,900/64,000
Power Input Cooling 0.35/2.36/3.45 0.60/3.10/4.70 0.90/3.56/6.70
kW
(Min/Std/Max) Heating 0.35/2.35/3.50 0.46/3.08/5.40 0.90/4.79/7.30
Current Input Cooling 2.0/10.3/15.0 3.00/13.60/20.40 3.7/15.8/30.0
Power A
(Min/Std/Max) Heating 2.0/10.4/15.5 2.50/13.60/23.00 3.7/20.9/32.0
MCA 21.0 25.0 33.0
Current A
MFA 25.0 30.0 40.0
EER Cooling 2.98 3.23 3.46
Efficiency W/W
COP Heating 3.37 3.61 3.24
System Type Flare connection Flare connection Flare connection
Liquid Pipe
6.35 (1/4") 9.52 (3/8") 9.52 (3/8")
Type Flare connection Flare connection Flare connection
Gas Pipe
15.88 (5/8") 15.88 (5/8") 19.05 (3/4")
Piping
Heat Insulation - Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes
Connections
Standard m 5 5 5
Piping length Max. m 50 50 75
(ODU-IDU) Elevation m 30 30 30
Chargeless m 7.5 30 30
Wiring Min. mm2 0.75 0.75 0.75
Communication
connections Remark - F1, F2 F1, F2 F1, F2
Type - R410A R410A R410A
Refrigerant
Factory Charging kg 2.0 3.0 3.8

10
1. Specification
4Way Cassette

Indoor Unit AC024MN4DKH/CB AC036MN4DKH/CB AC048MN4DKH/CB


Model Name
Outdoor Unit AC024MXADKH/CB AC036MXADKH/CB AC048MXADKH/CB
Power Supply 1,2,220-240,60 1,2,220-240,60 1,2,220-240,60
Type - F&T F&T F&T
Heat Fin - Al Al Al
Material
Exchanger Tube - Cu Cu Cu
Fin Treatment - Green Hydrophile Green Hydrophile Green Hydrophile
Type - Turbo Fan Turbo Fan Turbo Fan
Quantity EA 1 1 1
m³/min 19.5/16.5/14.5 31.00/25.00/19.00 33.1/27.5/22.0
Fan Air Flow Rate High/Mid/Low
l/s 325.0/275.0/241.7 516.67/416.67/316.67 551.7/458.3/366.7
External mmAq - - -
Min/Std/Max
Static Pressure Pa - - -
Type - BLDC BLDC BLDC
Fan Motor
Output Wx n 65 x 1 97 X 1 97 x 1
Drain Drain Pipe VP25 (OD 32,ID 25) VP25 (OD 32,ID 25) VP25 (OD 32,ID 25)
Sound Pressure Level High/Mid/Low/(Silent) dB(A) 36/33/29 44 / 39 / 33 45/41/37
Sound
Sound Power Level dB(A) - - -
Net Weight kg 14.5 18.0 20.0
External Shipping Weight kg 18.0 22.0 23.5
Dimension Net Dimensions (WxHxD) mm 840 x 204 x 840 840 x 288 x 840 840 x 288 x 840
Shipping Dimensions (WxHxD) mm 898 x 275 x 898 898 x 357 x 898 898 x 357 x 898
Casing Material - Polypropylene Polypropylene Polypropylene
Model Name - PC4NUSKAN PC4NUSKAN PC4NUSKAN
Type - Waffle Type Waffle Type Waffle Type
Material - HIPS+ABS HIPS+ABS HIPS+ABS
Color - Victory gray Victory gray Victory gray
Panel (1)
Net Weight kg 5.9 5.9 5.9
Shipping Weight kg 8.0 8.0 8.0
Indoor Net Dimensions (WxHxD) mm 950 x 45 x 950 950 x 45 x 950 950 x 45 x 950
Unit Shipping Dimensions (WxHxD) mm 1,005 x 100 x 1,005 1005 x 100 x 1005 1,005 x 100 x 1,005
Model Name - PC4NUSKEN PC4NUSKEN PC4NUSKEN
Type - Stripe Type Stripe Type Stripe Type
Material - HIPS+ABS HIPS+ABS HIPS+ABS
Panel (2) Color - Victory gray Victory gray Victory gray
Net Weight kg 5.9 5.9 5.9
Shipping Weight kg 8.0 8.0 8.0
Net Dimensions (WxHxD) mm 950 x 45 x 950 950 x 45 x 950 950 x 45 x 950
Shipping Dimensions (WxHxD) mm 1,005 x 100 x 1,005 1005 x 100 x 1005 1,005 x 100 x 1,005
Model Name - PC4NBSKAN PC4NBSKAN PC4NBSKAN
Type - Waffle Type Waffle Type Waffle Type
Material - HIPS+ABS HIPS+ABS HIPS+ABS
Color - Black Black Black
Panel (3)
Net Weight kg 5.9 5.9 5.9
Shipping Weight kg 8.5 8.5 8.5
Net Dimensions (WxHxD) mm 950 x 45 x 950 950 x 45 x 950 950 x 45 x 950
Shipping Dimensions (WxHxD) mm 1,005 x 100 x 1,005 1005 x 100 x 1005 1,005 x 100 x 1,005
Infrared remote control - MR-EH00 MR-EH00 MR-EH00
Control System
Wired remote control - MWR-WE11N MWR-WE11N MWR-WE11N
Drain Pump - Included Included Included
Drain Pump
Max. lifting Height / Displacement mm / Liter/h 750/24 750/24 750/24
External Model - - - -
Internal Model - - - -
Drain Pump
Additional Max. lifting Height /
mm / Liter/h - - -
Accessories Displacement
Air Filter - Removable / Washable Removable / Washable Removable / Washable
- MSD-CAN1 MSD-CAN1 MSD-CAN1

11
1. Specification
4Way Cassette

Indoor Unit AC024MN4DKH/CB AC036MN4DKH/CB AC048MN4DKH/CB


Model Name
Outdoor Unit AC024MXADKH/CB AC036MXADKH/CB AC048MXADKH/CB
Power Supply 1,2,220-240,60 1,2,220-240,60 1,2,220-240,60
Type - F&T F&T F&T
Heat Fin - Al Al Al
Material
Exchanger Tube - Cu Cu Cu
Fin Treatment - Anti-Corrosion Anti-Corrosion Anti-Corrosion
Model Name UG4T200FUAE4 UG8T300FUBJU UG5TK5450FJX
Type Twin BLDC Rotary Twin BLDC Twin BLDC Rotary
Compressor Output kW 1.79 2.82 4.12
Type - POE PVE POE
Oil
Initial charge cc 650 1,200 1,700
Type - Propeller Propellar Propeller
Discharge direction - Front Front Front
Fan Quantity EA 1 1 2
Outdoor
Unit m³/min 51 78 112
Air Flow Rate
l/s 850 1,300 1,867
Type - BLDC BLDC BLDC
Fan Motor
Output Wx n 125 125 125 x 2
Sound Pressure Cooling dB(A) 49 52 56
Sound Level Heating dB(A) 51 54 56
Sound Power Level dB(A) - - -
Net Weight kg 54.0 72.0 98.0
External Shipping Weight kg 58.0 77.0 108.0
Dimension Net Dimensions (WxHxD) mm 880 x 798 x 310 940 x 998 x 330 940 x 1,420 x 330
Shipping Dimensions (WxHxD) mm 1,023 x 881 x 413 995 x 1096 x 426 995 x 1,598 x 426
Casing Material Body - STEEL STEEL STEEL
Operating Cooling -15~50 -15~50 -15~50
Temp. Range Heating -20~24 -20~24 -20~24

NOTE
• Specification may be subject to change without prior notice.
1) Capacities are based on (Equivalent refrigerant piping 5m, Level differences 0m);
- Cooling : Indoor temperature 27.0°C DB, 19.0°C WB / Outdoor temperature 35.0°C DB, 24.0°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Select wire size based on the value of MCA
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level based on T1 condition (Indoor temperature 27°C DB, 19°C WB /
Outdoor temperature : 35°C DB, 24°C WB)
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
• In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.

12
2. Summary Table
4Way Cassette

Performance Characteristics

Capacity
Net Weight Airflow Sound Pressure Level
Model Code Cooling Heating Fan Speed
(kg) (CMM) (dBA)
(Btu/h) (Btu/h)
Max. 28,500 32,000 High 19.5 36
AC024MN4DKH/CB 15.0 Std. 24,000 27,000 Mid 16.5 33
Min. 7,500 6,500 Low 14.5 29
Max. 40,900 52,900 High 31.0 44
AC036MN4DKH/CB 18.0 Std. 34,000 38,000 Mid 25.0 39
Min. 10,200 7,500 Low 19.0 33
Max. 56,000 64,000 High 33.1 45
AC048MN4DKH/CB 20.0 Std. 42,000 52,900 Mid 27.5 41
Min. 12,000 12,000 Low 22.0 37

NOTE
• Sound data is based on cooling operation.

Electric Characteristics

Model Outdoor Unit Input Current (Amperes) Power Supply


Rated Outdoor Unit
Indoor Unit Outdoor Unit Indoor Unit Total MCA(A) MFA(A)
Min. Max. Cooling Heating
AC024MN4DKH/CB AC024MXADKH/CB 60 220-240 198 264 20.0 20.0 1.0 21.0 21.0 25.0
AC036MN4DKH/CB AC036MXADKH/CB 60 220-240 198 264 24.0 24.0 1.0 25.0 25.0 30.0
AC048MN4DKH/CB AC048MXADKH/CB 60 220-240 198 264 32.0 32.0 1.0 33.0 33.0 40.0

NOTE
• MCA : Minimum circuit amperes
• MFA : Maximum fuse amperes
• Select wire size based on the value of MCA

13
3. Capacity Table
4Way Cassette

AC024MN4DKH/CB+AC024MXADKH/CB

Cooling

TC : Total Capacity, SHC : Sensible Heat Capacity, PI : Power Input

Outdoor 20 / 14 22 / 16 25 / 18 27 / 19 28 / 20 30 / 22 32 / 24
Temperature
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
MBH MBH kW MBH MBH kW MBH MBH kW MBH MBH kW MBH MBH kW MBH MBH kW MBH MBH kW
-15 23.4 19.3 1.69 24.6 19.9 1.72 25.7 20.5 1.76 26.5 21.2 1.79 27.0 21.0 1.81 28.3 20.7 1.83 29.8 20.3 1.87
21 22.3 18.4 1.78 23.5 19.0 1.81 24.4 19.6 1.85 25.2 20.2 1.89 25.7 20.0 1.91 27.0 19.8 1.93 28.3 19.4 1.96
35 21.2 17.5 2.22 22.3 18.1 2.27 23.3 18.6 2.31 24.0 19.2 2.36 24.5 19.0 2.38 25.7 18.8 2.41 27.0 18.4 2.46
46 18.0 16.3 2.00 19.0 16.8 2.04 19.8 17.3 2.08 20.4 17.8 2.12 20.8 17.6 2.15 21.8 17.5 2.17 22.9 17.1 2.21
50 13.8 12.8 1.78 14.5 13.2 1.81 15.1 13.6 1.85 15.6 14.0 1.89 15.9 13.9 1.91 16.7 13.8 1.93 17.5 13.5 1.96

Heating

TC : Total Capacity, PI : Power Input

Outdoor Temperature 16 18 20 21 22 24
TC PI TC PI TC PI TC PI TC PI TC PI
MBH kW MBH kW MBH kW MBH kW MBH kW MBH kW
-20 19.0 3.12 18.8 3.09 18.6 3.06 18.4 3.02 18.3 2.99 18.1 2.96
-15 24.0 3.60 23.7 3.56 23.5 3.53 23.3 3.49 23.0 3.45 22.8 3.42
-5 27.0 3.36 26.7 3.32 26.5 3.29 26.2 3.26 25.9 3.22 25.7 3.19
0 28.1 2.88 27.8 2.85 27.5 2.82 27.3 2.79 27.0 2.76 26.7 2.74
7 27.5 2.40 27.3 2.37 27.0 2.35 26.7 2.33 26.5 2.30 26.2 2.28
24 35.8 2.76 35.5 2.73 35.1 2.70 34.7 2.68 34.4 2.65 34.1 2.62

NOTE
• The performance table shows the average value of each conditions.

14
3. Capacity Table
4Way Cassette

AC036MN4DKH/CB+AC036MXADKH/CB

Cooling

TC : Total Capacity, SHC : Sensible Heat Capacity, PI : Power Input

Outdoor 20 / 14 22 / 16 25 / 18 27 / 19 28 / 20 30 / 22 32 / 24
Temperature
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
MBH MBH kW MBH MBH kW MBH MBH kW MBH MBH kW MBH MBH kW MBH MBH kW MBH MBH kW
-15 33.3 27.5 2.23 35.0 28.3 2.28 36.5 29.2 2.32 37.6 30.1 2.37 38.4 29.8 2.39 40.3 29.5 2.42 42.3 28.9 2.47
21 31.7 26.2 2.35 33.4 27.0 2.40 34.8 27.8 2.45 35.8 28.7 2.50 36.5 28.4 2.52 38.4 28.1 2.55 40.3 27.5 2.60
35 30.2 24.9 2.94 31.8 25.7 3.00 33.1 26.5 3.06 34.0 27.3 3.10 34.8 27.0 3.15 36.5 26.8 3.18 38.4 26.2 3.25
46 25.7 24.1 2.64 27.0 24.8 2.70 28.1 25.6 2.75 29.0 26.4 2.81 29.6 26.1 2.84 31.1 25.9 2.86 32.6 25.3 2.92
50 19.6 19.2 2.35 20.7 19.8 2.40 21.5 20.4 2.45 22.2 21.1 2.50 22.6 20.9 2.52 23.8 20.6 2.55 24.9 20.2 2.60

Heating

TC : Total Capacity, PI : Power Input

Outdoor Temperature 16 18 20 21 22 24
TC PI TC PI TC PI TC PI TC PI TC PI
MBH kW MBH kW MBH kW MBH kW MBH kW MBH kW
-20 26.9 4.11 26.6 4.07 26.4 4.03 26.1 3.99 25.8 3.95 25.6 3.91
-15 33.9 4.74 33.6 4.70 33.2 4.65 32.9 4.60 32.6 4.56 32.3 4.51
-5 38.2 4.43 37.8 4.38 37.5 4.34 37.1 4.30 36.7 4.25 36.3 4.21
0 39.8 3.79 39.4 3.76 39.0 3.72 38.6 3.68 38.2 3.65 37.8 3.61
7 39.0 3.16 38.6 3.13 38.0 3.08 37.8 3.07 37.5 3.04 37.1 3.01
24 50.7 3.64 50.2 3.60 49.7 3.57 49.2 3.53 48.7 3.49 48.2 3.46

NOTE
• The performance table shows the average value of each conditions.

15
3. Capacity Table
4Way Cassette

AC048MN4DKH/CB+AC048MXADKH/CB

Cooling

TC : Total Capacity, SHC : Sensible Heat Capacity, PI : Power Input

Outdoor 20 / 14 22 / 16 25 / 18 27 / 19 28 / 20 30 / 22 32 / 24
Temperature
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
MBH MBH kW MBH MBH kW MBH MBH kW MBH MBH kW MBH MBH kW MBH MBH kW MBH MBH kW
-15 41.0 33.8 2.55 43.1 34.9 2.60 44.9 35.9 2.65 46.3 37.0 2.71 47.2 36.7 2.73 49.6 36.3 2.76 52.1 35.6 2.81
21 39.0 32.2 2.68 41.1 33.2 2.74 42.8 34.2 2.79 44.1 35.3 2.85 45.0 34.9 2.88 47.2 34.6 2.90 49.6 33.9 2.96
35 37.2 30.7 3.35 39.1 31.6 3.42 40.7 32.6 3.49 42.0 33.6 3.56 42.8 33.3 3.60 45.0 32.9 3.63 47.2 32.3 3.70
46 31.6 28.5 3.02 33.2 29.3 3.08 34.6 30.2 3.14 35.7 31.2 3.20 36.4 30.9 3.24 38.2 30.6 3.27 40.1 29.9 3.33
50 24.2 22.4 2.68 25.4 23.1 2.74 26.5 23.8 2.79 27.3 24.6 2.85 27.8 24.3 2.88 29.2 24.1 2.90 30.7 23.6 2.96

Heating

TC : Total Capacity, PI : Power Input

Outdoor Temperature 16 18 20 21 22 24
TC PI TC PI TC PI TC PI TC PI TC PI
MBH kW MBH kW MBH kW MBH kW MBH kW MBH kW
-20 37.2 6.35 36.9 6.29 36.5 6.23 36.1 6.16 35.8 6.10 35.4 6.04
-15 46.9 7.33 46.5 7.26 46.0 7.19 45.6 7.11 45.1 7.04 44.7 6.97
-5 52.9 6.84 52.4 6.77 51.8 6.71 51.3 6.64 50.8 6.57 50.3 6.51
0 55.0 5.86 54.5 5.81 54.0 5.75 53.4 5.69 52.9 5.63 52.4 5.58
7 54.0 4.89 53.4 4.84 52.9 4.79 52.4 4.74 51.8 4.69 51.3 4.65
24 70.2 5.62 69.5 5.56 68.8 5.51 68.1 5.45 67.4 5.40 66.7 5.34

NOTE
• The performance table shows the average value of each conditions.

16
4. Dimensional Drawing
4Way Cassette

AC024MN4DKH/CB
Units : mm [inches]

Description
No. Name
AC024MN4DKH/CB
1 Liquid pipe connection
2 Gas pipe connection
3 Drain pipe connection VP-25(OD32, ID25)
4 Power supply & Communication wiring conduit
5 Sub duct connection Use M4 Screw
6 Fresh air intake knockout hole

NOTE
• As for suspension bolt, please use M8 ~ M10.
(Procured at local site)

17
4. Dimensional Drawing
4Way Cassette

AC036/048MN4DKH/CB
Units : mm [inches]

No. Name Description


1 Liquid pipe connection
2 Gas pipe connection
3 Drain pipe connection VP-25(OD32, ID25)
4 Power supply & Communication wiring conduit
5 Sub duct connection Use M4 Screw
6 Fresh air intake knockout hole

NOTE
• As for suspension bolt, please use M8 ~ M10.
(Procured at local site)

18
5. Center of Gravity
4Way Cassette

Units : mm [inches]

A B C D
AC024MN4DKH/CB 204 [8] 70 [2-3/4] 410 [ 16-1/8] 360 [14-3/16]
AC036/048MN4DKH/CB 288 [11-3/8] 130[5] 420 [16-1/2] 420 [16-1/2]

19
6. Electrical Wiring Diagram
4Way Cassette

SUB PBA Printed Circuit Board(SUB) SPI S-Plasma ion ROOM(10K) Thermistor ROOM OUT(10K)
M-BLDC BLDC Motor Electronic Expansion Valve Thermistor EVA IN(10K)
EXT_CONTROL EXTERNAL_CONTROL Thermistor EVA OUT(10K)

NOTE
• This wiring diagram applies only to the Indoor unit.
• Symbols show as follow :
blk: black, red: red, blu: blue, wht: white, yel: yellow, brn: brown, sky: skyblue: grn: green
• For connection wiring indoor-outdoor transmission F1-F2, indoor-wired remote controller transmission F3-F4.
• Protective earth(screw), : connector, : The wire quantity

20
7. Sound Data
4Way Cassette

Sound Pressure level


Unit: dB(A)
Model HIGH MID LOW
AC024MN4DKH/CB 36 33 29
AC036MN4DKH/CB 44 39 33
1.5m AC048MN4DKH/CB 45 41 37

Microphone

• NC Curve
1) AC024MN4DKH/CB 2) AC036MN4DKH/CB

70 70 70 70
65 65 65 65
NC 70
60 60 60 NC 65 60
NC 60
55 55 55 55
Sound Pressure Level (dB)

NC 60
NC 55
50 50 50 NC 55 50
High
NC 50
45 45 45 NC 50 45
NC 45
40 40 40 Low 40
High NC 45
NC 40 35
35 35 35
Low NC 40
NC 35 30 30
30 30 NC 35
NC 30 25 25
25 25 NC 30
20 NC 25 20 20 20
NC 25
NC 20 15 15
15 15 NC 20
10 NC 15 10 10 10
NC 15
5 5 5 5

0 0 0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency(Hz) Octave Band Center Frequency(Hz)

3) AC048MN4DKH/CB

70 70
65 65
NC 70
60 60
NC 60
55 55
NC 55
50 High 50
NC 50
45 45
NC 45
40 Low 40
NC 40
35 35
NC 35
30 30
NC 30
25 25
20 NC 25 20
15 NC 20 15
10 NC 15 10
5 5
0 0
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency(Hz)

NOTE
• Specifications may be subject to change without prior notice.
- Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A weighted sound pressure level
-
21
8. Temperature and air flow distribution
4Way Cassette

AC024MN4DKH/CB

• Cooling Air Velocity distribution • Cooling temperature distribution


(Discharge angle : 45 degree) (Discharge angle : 45 degree)

• Heating Air Velocity distribution • Heating temperature distribution


(Discharge angle : 52 degree) (Discharge angle : 52 degree)

22
8. Temperature and air flow distribution
4Way Cassette

AC036MN4DKH/CB

• Cooling Air Velocity distribution • Cooling temperature distribution


(Discharge angle : 45 degree) (Discharge angle : 45 degree)

• Heating Air Velocity distribution • Heating temperature distribution


(Discharge angle : 52 degree) (Discharge angle : 52 degree)

23
8. Temperature and air flow distribution
4Way Cassette

AC048MN4DKH/CB

• Cooling Air Velocity distribution • Cooling temperature distribution


(Discharge angle : 45 degree) (Discharge angle : 45 degree)

• Heating Air Velocity distribution • Heating temperature distribution


(Discharge angle : 52 degree) (Discharge angle : 52 degree)

24
360 Cassette

1. Specification 27
2. Summary Table 30
3. Capacity Table 31
4. Dimensional Drawing 34
5. Center of Gravity 38
6. Electrical Wiring Diagram 39
7. Sound Data 40
8. Temperature and air flow distribution 41

25
Features & Benefits
360 Cassette

All round cooling and comfort


The Samsung 360 Cassette air conditioner offers a brand
new way of staying comfortably cool in every corner of
the room. Its innovative circular design not only means
it perfectly fits in everywhere, adding a sophisticated
look to many different sites, but it also blows cool air
in all directions, so that the whole room is the same
temperature*. And its bladeless outlet ensures that cool
air is gently dispersed, without creating a cold draft**,
and doesn’t block the air flow, even at low angles, so it Conventional 360 Cassette

expels 25% more air* and spreads it farther.

EVENLY CIRCULATES & COOLS EVERY CORNER


Unlike 4-way, cassette type air conditioners that create
areas of uneven airflow where cool air can't reach*, a
circular outlet blows cool air in all directions, so every
corner of a room is the same temperature**.
* Samsung testing compared to a general 4 way cassette type air * Within an 9.3m radius the temperature difference is less than 0.6°C.
conditioner.
** Within an 9.3m radius the temperature difference is less than 0.6°C.

Comfortably cool, not cold Spreads more air in more ways

A bladeless design softly disperses cool air across the An innovative Booster Fan enables cool air to be
room, making you comfortably cool without feeling a expelled at much lower angles. It creates a low pressure
cold draft**. With no blades to block the air flow, it also area around the outlet, so that cool air comes out
expels 25% more air* and spreads it farther. parallel to the ceiling and disperses across a wider area.

* Within a 5mradius, no cold draft between 0~1.5m in height (with 14.0kw).

Circular to perfectly fit in everywhere All round simpler & intuitive control

Its innovative circular design can match a multitude of Intuitively control its performance and see where the
interior designs, so it perfectly fits in everywhere. Its air is going. The Wireless Remote Controller's* Jog
minimalist modern styling creates a sophisticated look shuttle and button offer a fun way to adjust the air flow
and its circular shape stands out beautifully. and a Circular LED Display shows its direction.

*Optional
26
1. Specification
360 Cassette

Indoor Unit AC024MN4PKH/CB AC036MN4PKH/CB AC048MN4PKH/CB


Model Name
Outdoor Unit AC024MXADKH/CB AC036MXADKH/CB AC048MXADKH/CB
Mode - Heat pump Heat pump Heat pump
kW 2.20/7.03/8.35 3.00/9.96/12.00 3.51/12.30/16.41
Cooling
Capacity Btu/h 7,500/24,000/28,500 10,200/34,000/40,900 12,000/42,000/56,000
Performance
(Min/Std/Max) kW 1.90/7.91/9.38 2.20/11.14/15.50 3.51/15.50/18.75
Heating
Btu/h 6,500/27,000/32,000 7,500/38,000/52,900 12,000/52,900/64,000
Power Input Cooling 0.35/2.47/3.45 0.60/3.38/4.70 0.90/3.56/6.70
kW
(Min/Std/Max) Heating 0.35/2.40/3.5 0.46/3.12/5.40 0.90/4.79/7.30
Current Input Cooling 2.0/11.2/15.0 3.00/15.10/20.40 3.7/15.8/30.0
Power A
(Min/Std/Max) Heating 2.0/10.9/15.5 2.50/14.60/23.00 3.7/20.9/32.0
MCA 21.5 25.5 33.5
Current A
MFA 25.0 30.0 40.0
EER Cooling 2.85 2.96 3.46
Efficiency W/W
COP Heating 3.30 3.56 3.24
System Type Flare connection Flare connection Flare connection
Liquid Pipe
6.35 (1/4") 9.52 (3/8") 9.52 (3/8")
Type Flare connection Flare connection Flare connection
Gas Pipe
15.88 (5/8") 15.88 (5/8") 19.05 (3/4")
Piping
Heat Insulation - Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes
Connections
Standard m 5 5 5
Piping length Max. m 50 50 75
(ODU-IDU) Elevation m 30 30 30
Chargeless m 7.5 30 30
Wiring Min. mm2 0.75 0.75 0.75
Communication
connections Remark - F1, F2 F1, F2 F1, F2
Type - R410A R410A R410A
Refrigerant
Factory Charging kg 2.0 3.0 3.8
Power Supply 1,2,220-240,60 1,2,220-240,60 1,2,220-240,60
Type - F&T F&T F&T
Heat Fin - Al Al Al
Material
Exchanger Tube - Cu Cu Cu
Fin Treatment - Green Hydrophile Green Hydrophile Green Hydrophile
Type - Turbo Fan Turbo Fan Turbo Fan
Quantity EA 1 1 1
m³/min 17.5/15.9/14.3 31.20/25.50/19.80 32.4/27.1/22.8
Fan Air Flow Rate High/Mid/Low
l/s 291.7/265.0/238.3 520.00/425.00/330.00 540.0/451.7/380.0
Indoor External mmAq - - -
Min/Std/Max
Unit Static Pressure Pa - - -
Type - BLDC BLDC BLDC
Fan Motor
Output Wx n 65 x 1 97 X 1 97 x 1
Drain Drain Pipe VP25 (OD 32,ID 25) VP25 (OD 32,ID 25) VP25 (OD 32,ID 25)
Sound Pressure Level High/Mid/Low/(Silent) dB(A) 36/33/29 44 / 39 / 33 45/41/37
Sound
Sound Power Level dB(A) - - -
Net Weight kg 20.2 23.5 25.5
External Shipping Weight kg 24.0 28.3 30.3
Dimension Net Dimensions (WxHxD) mm 947 x 281 x 947 947 x 365 x 947 947 x 365 x 947
Shipping Dimensions (WxHxD) mm 990 x 330 x 990 990 x 414 x 990 990 x 414 x 990

27
1. Specification
360 Cassette

Indoor Unit AC024MN4PKH/CB AC036MN4PKH/CB AC048MN4PKH/CB


Model Name
Outdoor Unit AC024MXADKH/CB AC036MXADKH/CB AC048MXADKH/CB
Casing Material - HIPS HIPS HIPS
Model Name - PC4NUDMAN PC4NUDMAN PC4NUDMAN
Type - Ceiling Type(Sqare) Ceiling Type(Sqare) Ceiling Type(Sqare)
Material - HIPS HIPS HIPS
Color - White White White
Panel (1)
Net Weight kg 3.6 3.6 3.6
Shipping Weight kg 6.3 6.3 6.3
Net Dimensions (WxHxD) mm 1,000 x 66 x 1,000 1000 x 66 x 1000 1,000 x 66 x 1,000
Shipping Dimensions (WxHxD) mm 1,093 x 85 x 1,083 1093 x 85 x 1083 1,093 x 85 x 1,083
Model Name - PC4NUNMAN PC4NUNMAN PC4NUNMAN
Type - Open Type(Circle) Open Type(Circle) Open Type(Circle)
Material - HIPS HIPS HIPS
Panel (2) Color - White White White
Net Weight kg 2.7 2.7 2.7
Shipping Weight kg 5.3 5.3 5.3
Net Dimensions (WxHxD) mm 1,050 x 94 x 1,050 1050 x 94 x 1050 1,050 x 94 x 1,050
Shipping Dimensions (WxHxD) mm 1,093 x 85 x 1,083 1093 x 85 x 1083 1,093 x 85 x 1,083
Model Name - PC4NBDMAN PC4NBDMAN PC4NBDMAN
Type - HIPS HIPS HIPS
Material - Ceiling Type(Sqare) Ceiling Type(Sqare) Ceiling Type(Sqare)
Color - Black Black Black
Panel (3)
Indoor Net Weight kg 3.6 3.6 3.6
Unit Shipping Weight kg 6.3 6.3 6.3
Net Dimensions (WxHxD) mm 1,000 x 66 x 1,000 1000 x 66 x 1000 1,000 x 66 x 1,000
Shipping Dimensions (WxHxD) mm 1,093 x 85 x 1,083 1093 x 85 x 1083 1,093 x 85 x 1,083
Model Name - PC4NBNMAN PC4NBNMAN PC4NBNMAN
Type - Open Type(Circle) Open Type(Circle) Open Type(Circle)
Material - HIPS HIPS HIPS
Color - Black Black Black
Panel (4)
Net Weight kg 2.7 2.7 2.7
Shipping Weight kg 5.4 5.4 5.4
Net Dimensions (WxHxD) mm 1,050 x 94 x 1,050 1050 x 94 x 1050 1,050 x 94 x 1,050
Shipping Dimensions (WxHxD) mm 1,093 x 85 x 1,083 1093 x 85 x 1083 1,093 x 85 x 1,083
Infrared remote control - AR-KH00E MR-EH00 AR-KH00E
Control System
Wired remote control - MWR-WE11N MWR-WE11N MWR-WE11N
Drain Pump - - - -
Drain Pump
Max. lifting Height / Displacement mm / Liter/h Included Included Included
External Model - - - -
Internal Model - - - -
Drain Pump
Additional Max. lifting Height /
mm / Liter/h 750/24 750/24 750/24
Accessories Displacement
Air Filter - Removable / Washable Removable / Washable Removable / Washable
- MSD-CAN1 MSD-CAN1 MSD-CAN1

28
1. Specification
360 Cassette

Indoor Unit AC024MN4PKH/CB AC036MN4PKH/CB AC048MN4PKH/CB


Model Name
Outdoor Unit AC024MXADKH/CB AC036MXADKH/CB AC048MXADKH/CB
Power Supply 1,2,220-240,60 1,2,220-240,60 1,2,220-240,60
Type - F&T F&T F&T
Heat Fin - Al Al Al
Material
Exchanger Tube - Cu Cu Cu
Fin Treatment - Anti-Corrosion Anti-Corrosion Anti-Corrosion
Model Name UG4T200FUAE4 UG8T300FUBJU UG5TK5450FJX
Type Twin BLDC Rotary Twin BLDC Twin BLDC Rotary
Compressor Output kW 1.79 2.82 4.12
Type - POE PVE POE
Oil
Initial charge cc 650 1,200 1,700
Type - Propeller Propellar Propeller
Discharge direction - Front Front Front
Fan Quantity EA 1 1 2
Outdoor
Unit m³/min 51 78 112
Air Flow Rate
l/s 850 1,300 1,867
Type - BLDC BLDC BLDC
Fan Motor
Output Wx n 125 125 125 x 2
Sound Pressure Cooling dB(A) 49 52 56
Sound Level Heating dB(A) 51 54 56
Sound Power Level dB(A) - - -
Net Weight kg 54.0 72.0 98.0
External Shipping Weight kg 58.0 77.0 108.0
Dimension Net Dimensions (WxHxD) mm 880 x 798 x 310 940 x 998 x 330 940 x 1,420 x 330
Shipping Dimensions (WxHxD) mm 1,023 x 881 x 413 995 x 1096 x 426 995 x 1,598 x 426
Casing Material Body - STEEL STEEL STEEL
Operating Cooling -15~50 -15~50 -15~50
Temp. Range Heating -20~24 -20~24 -20~24

NOTE
• Specification may be subject to change without prior notice.
1) Capacities are based on (Equivalent refrigerant piping 5m, Level differences 0m);
- Cooling : Indoor temperature 27.0°C DB, 19.0°C WB / Outdoor temperature 35.0°C DB, 24.0°C WB
-
2) Select wire size based on the value of MCA
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level based on T1 condition (Indoor temperature 27°C DB, 19°C WB /
Outdoor temperature : 35°C DB, 24°C WB)
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
• In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.

29
2. Summary Table
360 Cassette

Performance Characteristics

Capacity
Net Weight Airflow Sound Pressure Level
Model Code Cooling Heating Fan Speed
(kg) (CMM) (dBA)
(Btu/h) (Btu/h)
Max. 28,500 32,000 High 17.5 36
AC024MN4PKH/CB 20.2 Std. 24,000 27,000 Mid 15.9 33
Min. 7,500 6,500 Low 14.3 29
Max. 40,900 52,900 High 31.2 44
AC036MN4PKH/CB 23.5 Std. 34,000 38,000 Mid 25.5 39
Min. 10,200 7,500 Low 19.8 33
Max. 56,000 64,000 High 32.4 45
AC048MN4PKH/CB 25.5 Std. 42,000 52,900 Mid 27.1 41
Min. 12,000 12,000 Low 22.8 37

NOTE
• Sound data is based on cooling operation.

Electric Characteristics

Model Outdoor Unit Input Current (Amperes) Power Supply


Rated Outdoor Unit
Indoor Unit Outdoor Unit Indoor Unit Total MCA(A) MFA(A)
Min. Max. Cooling Heating
AC024MN4PKH/CB AC024MXADKH/CB 60 220-240 198 264 20.0 20.0 1.5 21.5 21.5 25.0
AC036MN4PKH/CB AC036MXADKH/CB 60 220-240 198 264 24.0 24.0 1.5 25.5 25.5 30.0
AC048MN4PKH/CB AC048MXADKH/CB 60 220-240 198 264 32.0 32.0 1.5 33.5 33.5 40.0

NOTE
• MCA : Minimum circuit amperes
• MFA : Maximum fuse amperes
• Select wire size based on the value of MCA

30
3. Capacity Table
360 Cassette

AC024MN4PKH/CB+AC024MXADKH/CB

Cooling

TC : Total Capacity, SHC : Sensible Heat Capacity, PI : Power Input

Outdoor 20 / 14 22 / 16 25 / 18 27 / 19 28 / 20 30 / 22 32 / 24
Temperature
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
MBH MBH kW MBH MBH kW MBH MBH kW MBH MBH kW MBH MBH kW MBH MBH kW MBH MBH kW
-15 23.4 19.3 1.77 24.6 19.9 1.80 25.7 20.5 1.84 26.5 21.2 1.88 27.0 21.0 1.90 28.3 20.7 1.91 29.8 20.3 1.95
21 22.3 18.4 1.86 23.5 19.0 1.90 24.4 19.6 1.94 25.2 20.2 1.98 25.7 20.0 2.00 27.0 19.8 2.02 28.3 19.4 2.06
35 21.2 17.5 2.32 22.3 18.1 2.37 23.3 18.6 2.42 24.0 19.2 2.47 24.5 19.0 2.49 25.7 18.8 2.52 27.0 18.4 2.57
46 18.0 16.3 2.09 19.0 16.8 2.13 19.8 17.3 2.18 20.4 17.8 2.22 20.8 17.6 2.25 21.8 17.5 2.27 22.9 17.1 2.31
50 13.8 12.8 1.86 14.5 13.2 1.90 15.1 13.6 1.94 15.6 14.0 1.98 15.9 13.9 2.00 16.7 13.8 2.02 17.5 13.5 2.06

Heating

TC : Total Capacity, PI : Power Input

Outdoor Temperature 16 18 20 21 22 24
TC PI TC PI TC PI TC PI TC PI TC PI
MBH kW MBH kW MBH kW MBH kW MBH kW MBH kW
-20 19.0 3.18 18.8 3.15 18.6 3.12 18.4 3.09 18.3 3.06 18.1 3.03
-15 24.0 3.67 23.7 3.64 23.5 3.60 23.3 3.56 23.0 3.53 22.8 3.49
-5 27.0 3.43 26.7 3.39 26.5 3.36 26.2 3.33 25.9 3.29 25.7 3.26
0 28.1 2.94 27.8 2.91 27.5 2.88 27.3 2.85 27.0 2.82 26.7 2.79
7 27.5 2.45 27.3 2.42 27.0 2.40 26.7 2.38 26.5 2.35 26.2 2.33
24 35.8 2.82 35.5 2.79 35.1 2.76 34.7 2.73 34.4 2.71 34.1 2.68

NOTE
• The performance table shows the average value of each conditions.

31
2. Summary Table
360 Cassette

AC036MN4PKH/CB+AC036MXADKH/CB

Cooling

TC : Total Capacity, SHC : Sensible Heat Capacity, PI : Power Input

Outdoor 20 / 14 22 / 16 25 / 18 27 / 19 28 / 20 30 / 22 32 / 24
Temperature
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
MBH MBH kW MBH MBH kW MBH MBH kW MBH MBH kW MBH MBH kW MBH MBH kW MBH MBH kW
-15 33.3 27.8 2.43 35.0 28.7 2.48 36.5 29.6 2.53 37.6 30.5 2.58 38.4 30.2 2.61 40.3 29.9 2.64 42.3 29.3 2.69
21 31.7 26.5 2.56 33.4 27.3 2.61 34.8 28.1 2.67 35.8 29.0 2.72 36.5 28.7 2.75 38.4 28.4 2.77 40.3 27.9 2.83
35 30.2 25.2 3.20 31.8 26.0 3.27 33.1 26.8 3.33 34.0 27.6 3.38 34.8 27.4 3.43 36.5 27.1 3.47 38.4 26.5 3.54
46 25.7 24.4 2.88 27.0 25.1 2.94 28.1 25.9 3.00 29.0 26.7 3.06 29.6 26.4 3.09 31.1 26.2 3.12 32.6 25.6 3.18
50 19.6 19.4 2.56 20.7 20.0 2.61 21.5 20.7 2.67 22.2 21.3 2.72 22.6 21.1 2.75 23.8 20.9 2.77 24.9 20.4 2.83

Heating

TC : Total Capacity, PI : Power Input

Outdoor Temperature 16 18 20 21 22 24
TC PI TC PI TC PI TC PI TC PI TC PI
MBH kW MBH kW MBH kW MBH kW MBH kW MBH kW
-20 26.9 4.18 26.6 4.14 26.4 4.10 26.1 4.05 25.8 4.01 25.6 3.97
-15 33.9 4.82 33.6 4.77 33.2 4.73 32.9 4.68 32.6 4.63 32.3 4.58
-5 38.2 4.50 37.8 4.45 37.5 4.41 37.1 4.37 36.7 4.32 36.3 4.28
0 39.8 3.86 39.4 3.82 39.0 3.78 38.6 3.74 38.2 3.70 37.8 3.67
7 39.0 3.21 38.6 3.18 38.0 3.12 37.8 3.12 37.5 3.09 37.1 3.06
24 50.7 3.70 50.2 3.66 49.7 3.62 49.2 3.59 48.7 3.55 48.2 3.51

NOTE
• The performance table shows the average value of each conditions.

32
2. Summary Table
360 Cassette

AC048MN4PKH/CB+AC048MXADKH/CB

Cooling

TC : Total Capacity, SHC : Sensible Heat Capacity, PI : Power Input

Outdoor 20 / 14 22 / 16 25 / 18 27 / 19 28 / 20 30 / 22 32 / 24
Temperature
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
MBH MBH kW MBH MBH kW MBH MBH kW MBH MBH kW MBH MBH kW MBH MBH kW MBH MBH kW
-15 41.0 33.8 2.55 43.1 34.9 2.60 44.9 35.9 2.65 46.3 37.0 2.71 47.2 36.7 2.73 49.6 36.3 2.76 52.1 35.6 2.81
21 39.0 32.2 2.68 41.1 33.2 2.74 42.8 34.2 2.79 44.1 35.3 2.85 45.0 34.9 2.88 47.2 34.6 2.90 49.6 33.9 2.96
35 37.2 30.7 3.35 39.1 31.6 3.42 40.7 32.6 3.49 42.0 33.6 3.56 42.8 33.3 3.60 45.0 32.9 3.63 47.2 32.3 3.70
46 31.6 28.5 3.02 33.2 29.3 3.08 34.6 30.2 3.14 35.7 31.2 3.20 36.4 30.9 3.24 38.2 30.6 3.27 40.1 29.9 3.33
50 24.2 22.4 2.68 25.4 23.1 2.74 26.5 23.8 2.79 27.3 24.6 2.85 27.8 24.3 2.88 29.2 24.1 2.90 30.7 23.6 2.96

Heating

TC : Total Capacity, PI : Power Input

Outdoor Temperature 16 18 20 21 22 24
TC PI TC PI TC PI TC PI TC PI TC PI
MBH kW MBH kW MBH kW MBH kW MBH kW MBH kW
-20 37.2 6.35 36.9 6.29 36.5 6.23 36.1 6.16 35.8 6.10 35.4 6.04
-15 46.9 7.33 46.5 7.26 46.0 7.19 45.6 7.11 45.1 7.04 44.7 6.97
-5 52.9 6.84 52.4 6.77 51.8 6.71 51.3 6.64 50.8 6.57 50.3 6.51
0 55.0 5.86 54.5 5.81 54.0 5.75 53.4 5.69 52.9 5.63 52.4 5.58
7 54.0 4.89 53.4 4.84 52.9 4.79 52.4 4.74 51.8 4.69 51.3 4.65
24 70.2 5.62 69.5 5.56 68.8 5.51 68.1 5.45 67.4 5.40 66.7 5.34

NOTE
• The performance table shows the average value of each conditions.

33
4. Dimensional Drawing
360 Cassette

AC024MN4PKH/CB
Units : mm [inches]

No. Name Description No. Name Description


1 Liquid pipe connection 7 Suction rim for Booster fan
2 Gas pipe connection 8 Decoration cover
3 Drain pipe connection VP-25(OD32, ID25) 9 Drain hose(Accessory)
4 Power supply & Communication wiring conduit 10 Fresh air intake knockout hole Use M4 Screw
5 Air Discharge opening 11 Display window
6 Air suction grille 12 Remote controller receiver

NOTE
• As for suspension bolt, please use M8 ~ M10. (Procured at local site)
• Make sure the spacing between the ceiling and the cassette is more than 29mm[1-1/4].
Max ceiling opening : 960mm[37-13/16].

and additional insulation is required (polyethylene foam , thickness 10mm[3/8] or more)

34
4. Dimensional Drawing
360 Cassette

AC024MN4PKH/CB
Units : mm [inches]

No. Name Description No. Name Description


1 Liquid pipe connection 7 Suction rim for Booster fan
2 Gas pipe connection 8 Decoration cover
3 Drain pipe connection VP-25(OD32, ID25) 9 Drain hose(Accessory)
4 Power supply & Communication wiring conduit 10 Fresh air intake knockout hole Use M4 Screw
5 Air Discharge opening 11 Display window
6 Air suction grille 12 Remote controller receiver

NOTE
• As for suspension bolt, please use M8 ~ M10. (Procured at local site)
• Make sure the spacing between the ceiling and the cassette is more than 29mm[1-1/4].
Max ceiling opening : 960mm[37-13/16].

and additional insulation is required (polyethylene foam , thickness 10mm[3/8] or more)
• The circular panel is by default available in exposed installation.
Make inspection holes on the ceiling for easier installation and maintenance, as shown in the following table.
(The size of an inspection hole must be at least 450 mm x 450 mm.)
• A suspended ceiling structure can substitute for the inspection holes.

35
4. Dimensional Drawing
360 Cassette

AC036MN4PKH/CB
Units : mm [inches]

No. Name Description No. Name Description


1 Liquid pipe connection 7 Suction rim for Booster fan
2 Gas pipe connection 8 Decoration cover
3 Drain pipe connection VP-25(OD32, ID25) 9 Drain hose(Accessory)
4 Power supply & Communication wiring conduit 10 Fresh air intake knockout hole Use M4 Screw
5 Air Discharge opening 11 Display window
6 Air suction grille 12 Remote controller receiver

NOTE
• As for suspension bolt, please use M8 ~ M10. (Procured at local site)
• Make sure the spacing between the ceiling and the cassette is more than 29mm[1-1/4].
Max ceiling opening : 960mm[37-13/16].

and additional insulation is required (polyethylene foam , thickness 10mm[3/8] or more)

36
4. Dimensional Drawing
360 Cassette

AC048MN4PKH/CB
Units : mm [inches]

No. Name Description No. Name Description


1 Liquid pipe connection 7 Suction rim for Booster fan
2 Gas pipe connection 8 Decoration cover
3 Drain pipe connection VP-25(OD32, ID25) 9 Drain hose(Accessory)
4 Power supply & Communication wiring conduit 10 Fresh air intake knockout hole Use M4 Screw
5 Air Discharge opening 11 Display window
6 Air suction grille 12 Remote controller receiver

NOTE
• As for suspension bolt, please use M8 ~ M10. (Procured at local site)
• Make sure the spacing between the ceiling and the cassette is more than 29mm[1-1/4].
Max ceiling opening : 960mm[37-13/16].

and additional insulation is required (polyethylene foam , thickness 10mm[3/8] or more)
• The circular panel is by default available in exposed installation.
Make inspection holes on the ceiling for easier installation and maintenance, as shown in the following table.
(The size of an inspection hole must be at least 450 mm x 450 mm.)
• A suspended ceiling structure can substitute for the inspection holes.
37
5. Center of Gravity
360 Cassette

Units : mm [inches]

A B
AC024MN4PKH/CB 233 [9-3/16] 165 [6-1/2]
AC036/048MN4PKH/CB 317 [12-1/2] 220 [8-5/8]

38
6. Electrical Wiring Diagram
360 Cassette

2-LINE SUB PBA Printed Circuit Board(2-LINE SUB) SPI S-Plasma ion ROOM(10K) Thermistor ROOM OUT(10K)
M-BLDC BLDC Motor Electronic Expansion Valve Thermistor EVA IN(10K)
EXT CONTROL EXTERNAL_CONTROL Thermistor EVA OUT(10K)
Ventilator

NOTE
• This wiring diagram applies only to the Indoor unit.
• Symbols show as follow :
blk: black, red: red, blu: blue, wht: white, yel: yellow, brn: brown, sky: skyblue: grn: green
• For connection wiring indoor-outdoor transmission F1-F2, indoor-wired remote controller transmission F3-F4.
• Protective earth(screw), : connector, : The wire quantity

39
7. Sound Data
360 Cassette

Sound Pressure level


Unit: dB(A)
Model HIGH MID LOW
AC024MN4PKH/CB 36 33 29
AC036MN4PKH/CB 44 39 33
AC048MN4PKH/CB 45 41 37
1.5m

Microphone

• NC Curve
1) AC024MN4PKH/CB 2) AC036MN4PKH/CB

70 70 70 70
65 65 65 65
NC 70
60 60 60 NC 65 60
NC 60
55 55 55 55
Sound Pressure Level (dB)

NC 60
NC 55 High
50 50 50 NC 55 50
NC 50 Low
45 45 45 NC 50 45
NC 45
40 40 40 40
NC 45
High NC 40
35 35 35 35
Low NC 40
NC 35
30 30 30 30
NC 35
NC 30
25 25 25 25
NC 30
20 NC 25 20 20 20
NC 25
NC 20 15 15
15 15 NC 20
NC 15 10 10
10 10
NC 15
5 5 5 5
0 0 0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency(Hz) Octave Band Center Frequency(Hz)

3) AC048MN4PKH/CB
70 70
65 65
NC 70
60 60
NC 60
55 55
NC 55
50 High 50
NC 50
45 45
Low NC 45
40 40
NC 40
35 35
NC 35
30 30
NC 30
25 25
20 NC 25 20
15 NC 20 15
NC 15
10 10
5 5
0 0
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency(Hz)

NOTE
• Specifications may be subject to change without prior notice.
- Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A weighted sound pressure level
-
40
8. Temperature and air flow distribution
360 Cassette

AC024MN4PKH/CB

• Cooling Air Velocity distribution • Cooling temperature distribution


(Discharge angle : 60 degree) (Discharge angle : 60 degree)

• Heating Air Velocity distribution • Heating temperature distribution


(Discharge angle : 60 degree) (Discharge angle : 60 degree)

41
8. Temperature and air flow distribution
360 Cassette

AC036MN4PKH/CB

• Cooling Air Velocity distribution • Cooling temperature distribution


(Discharge angle : 60 degree) (Discharge angle : 60 degree)

• Heating Air Velocity distribution • Heating temperature distribution


(Discharge angle : 60 degree) (Discharge angle : 60 degree)

42
8. Temperature and air flow distribution
360 Cassette

AC048MN4PKH/CB

• Cooling Air Velocity distribution • Cooling temperature distribution


(Discharge angle : 60 degree) (Discharge angle : 60 degree)

• Heating Air Velocity distribution • Heating temperature distribution


(Discharge angle : 60 degree) (Discharge angle : 60 degree)

43
Big Ceiling

1. Specification 46
2. Summary Table 48
3. Capacity Table 49
4. Dimensional Drawing 51
5. Center of Gravity 52
6. Electrical Wiring Diagram 53
7. Sound Data 54
8. Temperature and air flow distribution 55

44
Features & Benefits
Ceiling Type (large capacity) - Powerful cooling with a long distance wind

Combine simple neat and innovated technologies to Simple display


experience superior performance and easy operation
The simple display design with its rounded corners adds
Samsung has been rewriting product descriptions a neat and tidy feeling to your interior.
beyond the industry standards. As one of such
company's product, Samsung Ceiling focused on sending
"sufficient" amount of conditioned air to "distant" places - Ice Blue : Operating
to cover huge area. For convenient installations and - Yellow Green : Schedule
maintenances, the Ceiling concentrated service direction - Red : Error
on one side. Do not get stressed with air conditioning. - Orange : Filter Alarm
Tim e Limit + Operating Pattern
Just leave it to Samsung Ceiling.

Single side installation


Due to difficulties in accessing their installed locations,
easiness to maintain ceiling indoor units should be
considered seriously. Relatively thin width of the product
makes locating all service ports at one side difficult.
However, for better customer experience, Samsung
challenged to this difficulty.
Fast cooling, 15m air flow
When users need air conditioning, they really need it
quickly. While the ceiling applied latest flow-efficient
blowers to increase amount of air it discharges, it also
mounted single BLDC motor to reduce noises and
possibilities of abrupt changes of modes. With increased
size of inlet area and fluid dynamically designed inner
passages, customers can experience incomparable
cooling power.
Also, with the advanced blade, which can move from
40 to 450, Samsung ceiling type can refreshingly cool
air that reaches every corner of the room with no blind
spots.

45
1. Specification
Big Ceiling

Indoor Unit AC036MNCDKH/CB AC048MNCDKH/CB


Model Name
Outdoor Unit AC036MXADKH/CB AC048MXADKH/CB
Mode - Heat pump Heat pump
kW 3.00/10.00/12.00 4.30/12.89/17.30
Cooling
Capacity Btu/h 10,200/34,100/40,900 14,700/44,000/59,000
Performance
(Min/Std/Max) kW 2.20/11.20/15.50 4.69/15.50/19.93
Heating
Btu/h 7,500/38,200/52,900 16,000/52,900/68,000
Power Input Cooling 0.60/3.40/4.70 0.95/3.73/6.80
kW
(Min/Std/Max) Heating 0.46/3.20/5.40 0.95/4.45/7.35
Current Input Cooling 3.00/14.60/20.40 4.0/16.6/30.0
Power A
(Min/Std/Max) Heating 2.50/14.20/23.00 4.0/19.6/32.0
MCA 26.0 34.0
Current A
MFA 30.0 40.0
EER Cooling 2.97 3.46
Efficiency W/W
COP Heating 3.5 3.48
System Type Flare connection Flare connection
Liquid Pipe
9.52 (3/8") 9.52 (3/8")
Type Flare connection Flare connection
Gas Pipe
15.88 (5/8") 19.05 (3/4")
Piping
Heat Insulation - Both liquid and gas pipes Both liquid and gas pipes
Connections
Standard m 5 5
Piping length Max. m 50 75
(ODU-IDU) Elevation m 30 30
Chargeless m 30 30
Wiring Min. mm2 0.75 0.75
Communication
connections Remark - F1, F2 F1, F2
Type - R410A R410A
Refrigerant
Factory Charging kg 3.0 3.8
Power Supply 1,2,220-240,60 1,2,220-240,60
Type - F&T F&T
Heat Fin - Al Al
Material
Exchanger Tube - Cu Cu
Fin Treatment - Green Hydrophile Green Hydrophile
Type - Sirroco Sirroco
Quantity EA 4 4
m³/min 26.00/23.00/19.00 37.0/31.0/26.0
Fan Air Flow Rate High/Mid/Low
l/s 433.33/383.33/316.67 616.7/516.7/433.3
External mmAq - -
Min/Std/Max
Static Pressure Pa - -
Type - BLDC BLDC
Fan Motor
Output Wx n 244 X 1 244 x 1
Drain Drain Pipe VP25 (OD 32,ID 25) VP25 (OD 32,ID 25)
Sound Pressure Level High/Mid/Low/(Silent) dB(A) 42 / 38 / 34 50/47/43
Indoor Sound
Sound Power Level dB(A) - -
Unit
Net Weight kg 41.4 42.5
External Shipping Weight kg 48.0 48.0
Dimension Net Dimensions (WxHxD) mm 1,650 x 235 x 675 1,650 x 235 x 675
Shipping Dimensions (WxHxD) mm 1,739x 321 x 758 1,739 x 321 x 758
Casing Material - STEEL STEEL
Infrared remote control - MR-EH00 MR-EH00
Control System
Wired remote control - MWR-WE11N MWR-WE11N
Drain Pump - - -
Drain Pump
Max. lifting Height / Displacement mm / Liter/h - -
External Model - - -
Internal Model - - -
Drain Pump
Additional Max. lifting Height /
mm / Liter/h 750/24 -
Accessories Displacement
Air Filter - Removable / Washable Removable / Washable
- MSD-CAN1 MSD-CAN1

46
1. Specification
Big Ceiling

Indoor Unit AC036MNCDKH/CB AC048MNCDKH/CB


Model Name
Outdoor Unit AC036MXADKH/CB AC048MXADKH/CB
Power Supply 1,2,220-240,60 1,2,220-240,60
Type - F&T F&T
Heat Fin - Al Al
Material
Exchanger Tube - Cu Cu
Fin Treatment - Anti-Corrosion Anti-Corrosion
Model Name UG8T300FUBJU UG5TK5450FJX
Type Twin BLDC Twin BLDC Rotary
Compressor Output kW 2.82 4.12
Type - PVE POE
Oil
Initial charge cc 1,200 1,700
Type - Propellar Propeller
Discharge direction - Front Front
Fan Quantity EA 1 2
Outdoor
Unit m³/min 78 112
Air Flow Rate
l/s 1,300 1,867
Type - BLDC BLDC
Fan Motor
Output Wx n 125 125 x 2
Sound Pressure Cooling dB(A) 52 56
Sound Level Heating dB(A) 54 56
Sound Power Level dB(A) - -
Net Weight kg 72.0 98.0
External Shipping Weight kg 77.0 108.0
Dimension Net Dimensions (WxHxD) mm 940 x 998 x 330 940 x 1,420 x 330
Shipping Dimensions (WxHxD) mm 995 x 1096 x 426 995 x 1,598 x 426
Casing Material Body - STEEL STEEL
Operating Cooling -15~50 -15~50
Temp. Range Heating -20~24 -20~24

NOTE
• Specification may be subject to change without prior notice.
1) Capacities are based on (Equivalent refrigerant piping 5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35.0°C DB, 24°C WB
-
2) Select wire size based on the value of MCA
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level based on T1 condition (Indoor temperature 27°C DB, 19°C WB /
Outdoor temperature : 35°C DB, 24°C WB)
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
• In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.

47
2. Summary Table
Big Ceiling

Performance Characteristics

Capacity
Net Weight Airflow Sound Pressure Level
Model Code Cooling Heating Fan Speed
(kg) (CMM) (dBA)
(Btu/h) (Btu/h)
Max. 40,900 52,900 High 26.0 42
AC036MNCDKH/CB 41.4 Std. 34,100 38,200 Mid 23.0 38
Min. 10,200 7,500 Low 19.0 34
Max. 59,000 68,000 High 37.0 50
AC048MNCDKH/CB 41.4 Std. 44,000 52,900 Mid 31.0 47
Min. 14,700 16,000 Low 26.0 43

NOTE
• Sound data is based on cooling operation.

Electric Characteristics

Model Outdoor Unit Input Current (Amperes) Power Supply


Rated Outdoor Unit
Indoor Unit Outdoor Unit Indoor Unit Total MCA(A) MFA(A)
Min. Max. Cooling Heating
AC036MNCDKH/CB AC036MXADKH/CB 60 220-240 198 264 24.0 24.0 2.0 26.0 26.0 30.0
AC048MNCDKH/CB AC048MXADKH/CB 60 220-240 198 264 32.0 32.0 2.0 34.0 34.0 40.0

NOTE
• MCA : Minimum circuit amperes
• MFA : Maximum fuse amperes
• Select wire size based on the value of MCA

48
3. Capacity Table
Big Ceiling

AC036MNCDKH/CB+AC036MXADKH/CB

Cooling

TC : Total Capacity, SHC : Sensible Heat Capacity, PI : Power Input

Outdoor 20 / 14 22 / 16 25 / 18 27 / 19 28 / 20 30 / 22 32 / 24
Temperature
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
MBH MBH kW MBH MBH kW MBH MBH kW MBH MBH kW MBH MBH kW MBH MBH kW MBH MBH kW
-15 33.3 25.7 2.43 35.0 26.5 2.48 36.5 27.4 2.53 37.6 28.2 2.58 38.4 27.9 2.61 40.3 27.7 2.64 42.3 27.1 2.69
21 31.7 24.5 2.56 33.4 25.3 2.61 34.8 26.1 2.67 35.8 26.9 2.72 36.5 26.6 2.75 38.4 26.3 2.77 40.3 25.8 2.83
35 30.2 23.4 3.20 31.8 24.1 3.27 33.1 24.8 3.33 34.1 25.6 3.40 34.8 25.3 3.43 36.5 25.1 3.47 38.4 24.6 3.54
46 25.7 22.8 2.88 27.0 23.5 2.94 28.1 24.2 3.00 29.0 24.9 3.06 29.6 24.7 3.09 31.1 24.4 3.12 32.6 24.0 3.18
50 19.6 18.2 2.56 20.7 18.8 2.61 21.5 19.4 2.67 22.2 20.0 2.72 22.6 19.8 2.75 23.8 19.6 2.77 24.9 19.2 2.83

Heating

TC : Total Capacity, PI : Power Input

Outdoor Temperature 16 18 20 21 22 24
TC PI TC PI TC PI TC PI TC PI TC PI
MBH kW MBH kW MBH kW MBH kW MBH kW MBH kW
-20 26.9 4.24 26.6 4.20 26.4 4.16 26.1 4.12 25.8 4.08 25.6 4.04
-15 33.9 4.90 33.6 4.85 33.2 4.80 32.9 4.75 32.6 4.70 32.3 4.66
-5 38.2 4.57 37.8 4.52 37.5 4.48 37.1 4.44 36.7 4.39 36.3 4.35
0 39.8 3.92 39.4 3.88 39.0 3.84 38.6 3.80 38.2 3.76 37.8 3.73
7 39.0 3.26 38.6 3.23 38.2 3.20 37.8 3.17 37.5 3.14 37.1 3.10
24 50.7 3.75 50.2 3.72 49.7 3.68 49.2 3.64 48.7 3.61 48.2 3.57

NOTE
• The performance table shows the average value of each conditions.

49
3. Capacity Table
Big Ceiling

AC048MNCDKH/CB+AC048MXADKH/CB

Cooling

TC : Total Capacity, SHC : Sensible Heat Capacity, PI : Power Input

Outdoor 20 / 14 22 / 16 25 / 18 27 / 19 28 / 20 30 / 22 32 / 24
Temperature
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
MBH MBH kW MBH MBH kW MBH MBH kW MBH MBH kW MBH MBH kW MBH MBH kW MBH MBH kW
-15 42.9 35.4 2.67 45.2 36.5 2.72 47.1 37.6 2.78 48.5 38.8 2.83 49.5 38.4 2.86 52.0 38.0 2.89 54.6 37.3 2.95
21 40.9 33.7 2.81 43.0 34.8 2.87 44.8 35.9 2.92 46.2 37.0 2.98 47.1 36.6 3.01 49.5 36.2 3.04 52.0 35.5 3.10
35 38.9 32.1 3.51 41.0 33.1 3.58 42.7 34.1 3.66 44.0 35.2 3.73 44.9 34.8 3.77 47.1 34.5 3.80 49.5 33.8 3.88
46 33.1 29.8 3.16 34.8 30.7 3.22 36.3 31.7 3.29 37.4 32.7 3.36 38.1 32.3 3.39 40.1 32.0 3.42 42.1 31.4 3.49
50 25.3 23.5 2.81 26.6 24.2 2.87 27.7 25.0 2.92 28.6 25.7 2.98 29.2 25.5 3.01 30.6 25.2 3.04 32.2 24.7 3.10

Heating

TC : Total Capacity, PI : Power Input

Outdoor Temperature 16 18 20 21 22 24
TC PI TC PI TC PI TC PI TC PI TC PI
MBH kW MBH kW MBH kW MBH kW MBH kW MBH kW
-20 37.2 5.90 36.9 5.84 36.5 5.79 36.1 5.73 35.8 5.67 35.4 5.61
-15 46.9 6.81 46.5 6.74 46.0 6.68 45.6 6.61 45.1 6.54 44.7 6.48
-5 52.9 6.36 52.4 6.29 51.8 6.23 51.3 6.17 50.8 6.11 50.3 6.04
0 55.0 5.45 54.5 5.39 54.0 5.34 53.4 5.29 52.9 5.23 52.4 5.18
7 54.0 4.54 53.4 4.49 52.9 4.45 52.4 4.41 51.8 4.36 51.3 4.32
24 70.2 5.22 69.5 5.17 68.8 5.12 68.1 5.07 67.4 5.02 66.7 4.97

NOTE
• The performance table shows the average value of each conditions.

50
4. Dimensional Drawing
Big Ceiling

AC036/048MNCDKH/CB
Units : mm [inches]

No. Name Description


1 Gas pipe connection
2 Liquid pipe connection
3 Drain pipe connection VP-25(OD32, ID25)
4 Air filter
5 Air suction grille
6 Knockout hole for piping (upper)
7 Knockout hole for piping (rear)
8 Conduit Hole
9 Knockout hole for drain hose
10 Knockout hole for Fresh air intake
11 Cover side
12 Knockout hole for piping (side)

NOTE
• As for suspension bolt, please use M8 ~ M10.
(Procured at local site)

51
5. Center of Gravity
Big Ceiling

Units : mm [inches]

52
6. Electrical Wiring Diagram
Big Ceiling

MAIN PBA Printed Circuit Board(MAIN) SPI S-Plasma ion ROOM(10K) Thermistor ROOM OUT(10K)
Printed Circuit Board(BLDC DRIVER) Electronic Expansion Valve Thermistor EVA IN(10K)
SUB PBA Printed Circuit Board(SUB) EXT_CONTROL EXTERNAL_CONTROL Thermistor EVA OUT(10K)
M-BLDC BLDC Motor DISCHARGE(10K) Thermistor DISCHARGE(10K)

NOTE
• This wiring diagram applies only to the Indoor unit.
• Symbols show as follow :
blk: black, red: red, blu: blue, wht: white, yel: yellow, brn: brown, sky: skyblue: grn: green
• For connection wiring indoor-outdoor transmission F1-F2, indoor-wired remote controller transmission F3-F4.
• Protective earth(screw), : connector, : The wire quantity

53
7. Sound Data
Big Ceiling

Sound Pressure level


Unit: dB(A)

1m
Model HIGH MID LOW
AC036MNCDKH/CB 42 38 34
AC048MNCDKH/CB 50 47 43
1m

Microphone

• NC Curve
1) AC036MNCDKH/CB 2) AC048MNCDKH/CB
70 70 70 70
65 65 65 65
NC 70
60 NC 65 60 60 60
High NC 60
55 55 55 55
Sound Pressure Level (dB)

NC 60
NC 55
50 NC 55 50 50 50
Hig h
NC 50
45 NC 50 45 45 Low 45
NC 45
40 40 40 40
Low NC 45 NC 40
35 35 35 35
NC 40 NC 35
30 30 30 30
NC 35 NC 30
25 25 25 25
NC 30
NC 25
20 20 20 20
NC 25
15 15 NC 20
15 15
NC 20
NC 15
10 10 10 10
NC 15
5 5 5 5
0 0 0 0
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency(Hz) Octave Band Center Frequency(Hz)

NOTE
• Specifications may be subject to change without prior notice.
- Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A weighted sound pressure level
-

54
8. Temperature and air flow distribution
Big Ceiling (Ceiling Installation Only)

AC036MNCDKH/CB

• Cooling Air Velocity distribution


(Discharge angle : 32 degree)

• Cooling temperature distribution


(Discharge angle : 32 degree)

• Heating Air Velocity distribution


(Discharge angle : 32 degree)

• Heating temperature distribution


(Discharge angle : 32 degree)

55
8. Temperature and air flow distribution
Big Ceiling (Ceiling Installation Only)

AC048MNCDKH/CB

• Cooling Air Velocity distribution


(Discharge angle : 32 degree)

• Cooling temperature distribution


(Discharge angle : 32 degree)

• Heating Air Velocity distribution


(Discharge angle : 32 degree)

• Heating temperature distribution


(Discharge angle : 32 degree)

56
Outdoor Units

1. Summary Table 58
2. Dimensional Drawing 59
3. Center of Gravity 62
4. Electrical Wiring Diagram 64
5. Sound Data 66
6. Capacity Correction 67
7. Operation Range 70
8. Piping Diagram 71

57
1. Summary Table
Outdoor Units

Performance Characteristics

Capacity Net Size Net Weight Airflow Sound Pressure Level (dBA)
Model Code
(Btu/h) (WxHxD mm) (kg) (CMM) Cooling Heating
24,000 AC024MXADKH/CB 880 x 798 x 310 54.0 51.0 49.0 51.0
36,000 AC036MXADKH/CB 940 x 998 x 330 72.0 78.0 52.0 54.0
48,000 AC048MXADKH/CB 940 x 1420 x 330 98.0 112.0 56.0 56.0

58
2. Dimensional Drawing
Outdoor Units

AC024MXADKH/CB
Units : mm [inches]

No. Name Description


1 Refrigerant liquid pipe
2 Refrigerant gas pipe
3 Drain Hole

59
1. Summary Table
Outdoor Units

AC036MXADKH/CB
Units : mm [inches]

No. Name Description


1 Refrigerant liquid pipe
2 Refrigerant gas pipe
3 Piping intake knockout hole Front / Side / Rear / Bottom
4 Power wiring conduit
5 Communication wiring conduit
6 Drain Hole Connect with the provided drain plug

60
1. Summary Table
Outdoor Units

AC048MXADKH/CB
Units : mm [inches]

No. Name Description


1 Refrigerant liquid pipe
2 Refrigerant gas pipe
3 Piping intake knockout hole Front / Side / Rear / Bottom
4 Power wiring conduit
5 Communication wiring conduit
6 Drain Hole Connect with the provided drain plug

61
3. Center of Gravity
Outdoor Units

AC024MXADKH/CB
Units : mm [inches]

AC036MXADKH/CB
Units : mm [inches]

62
3. Center of Gravity
Outdoor Units

AC048MXADKH/CB
Units : mm [inches]

63
4. Electrical Wiring Diagram
Outdoor Units

AC024MXADKH/CB

MAIN PCB EEV Electronic Expansion Valve DIS-TEMP


INVERTER PCB M-BLDC BLDC Motor OUT-TEMP
EMI PCB OLP-TEMP Thermistor OLP COND-TEMP

NOTE
• This wiring diagram applies only to the outdoor unit.
• Colors blk: black, red: red, blu: blue, wht: white, yel: yellow, brn: brown, sky: skyblue


the installation manual.
• : connector, : The wire quantity

64
4. Electrical Wiring Diagram

AC036/048MXADKH/CB

MAIN PCB EEV Electronic Expansion Valve DIS-TEMP


INVERTER PCB M-BLDC BLDC Motor OUT-TEMP
EMI PCB OLP-TEMP Thermistor OLP COND-TEMP

NOTE
• This wiring diagram applies only to the outdoor unit.
• Colors blk: black, red: red, blu: blue, wht: white, yel: yellow, brn: brown, sky: skyblue


the installation manual.
• : connector, : The wire quantity

65
5. Sound Data
Outdoor Units

Sound Pressure level

Model Cooling Heating


Microphone 1m Microphone 1m
AC024MXADKH/CB 49 51
AC036MXADKH/CB 52 54
AC048MXADKH/CB 56 56
1.5m 1.5m

Front Front


AC024MXADKH/CB AC036MXADKH/CB
90 90 90 90
85 85 85 NC 90 85
80 80 80 NC 85 80
75 75 75 NC 8 0 75
70 70 70 70
Sound Pressure Level (dB)

NC 75
65 65 65 NC 70 65
NC 70 60 Cooling
Heating 60
60 60 NC 65
Heating NC 60 55 55
55 55 NC 60
Cool ing NC 55 50 NC 55 50
50 50
NC 50 45 NC 50 45
45 45
NC 45 40 40
40 40 NC 4 5
NC 40 35 35
35 35 NC 40
NC 35 30 NC 35
30
30 30 25 25
NC 30 NC 30
25 25 20 20
20 NC 25 20 Hearing NC 25
15 15
15 Hearing NC 20 15 threshold NC 20
threshold 10 10
10 NC 15 10 NC 15
5 5
5 5 0 0
0 0 63 125 250 500 1000 2000 4000 8000
63 125 250 500 1000 2000 4000 8000 Octave Band Center Frequency(Hz)
Octave Band Center Frequency(Hz)

AC048MXADKH/CB
90 90
85 85
80 80
75 75
70 70
65 65
NC 70
60 Heating 60
Cooling NC 60
55 55
NC 55
50 50
NC 50
45 45
NC 45
40 40
NC 40
35 35
NC 35
30 30
NC 30
25 25
20 NC 25 20
15 Hearing NC 20 15
threshold NC 15
10 10
5 5
0 0
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency(Hz)

NOTE
• Specifications may be subject to change without prior notice.
Sound pressure level is obtained in an anechoic room.
Sound pressure level is a relative value, depending on the distance and acoustic environment.
Sound pressure level may differ depending on operation condition.
dBA = A weighted sound pressure level

66
6. Capacity Correction
Outdoor Units

AC024MXADKH/CB

Cooling

Pipe Length (m)


5 10 15 20 25 30 35 40 45 50
30 93 92 91 90
25 94 93 92 91 90
20 96 94 93 92 91 90
15 97 96 94 93 92 91 90
Level Difference (m)

10 98 97 96 94 93 92 91 90
5 99 98 97 96 94 93 92 91 90
0 100 99 98 97 96 94 93 92 91 90
-5 98 97 96 95 94 93 92 91 89
-10 97 96 95 94 92 91 90 88
-15 95 95 93 92 91 89 88
-20 94 93 92 90 89 87
-25 92 91 90 88 86
-30 91 89 88 85

Heating

Pipe Length (m)


5 10 15 20 25 30 35 40 45 50
30 95 94 93 92
25 96 95 94 93 92
20 96 96 95 94 93 92
15 97 96 96 95 94 93 92
Level Difference (m)

10 98 97 96 96 95 94 93 92
5 99 98 97 96 96 95 94 93 92
0 100 99 98 97 96 96 95 94 93 92
-5 99 98 97 96 96 95 94 93 92
-10 98 97 96 96 95 94 93 92
-15 97 96 96 95 94 93 92
-20 96 96 95 94 93 92
-25 96 95 94 93 92
-30 95 94 93 92

67
5. Sound Data
Outdoor Units

AC036MXADKH/CB

Cooling

Pipe Length (m)


5 10 15 20 25 30 35 40 45 50
30 93 92 91 90
25 94 93 92 91 90
20 96 94 93 92 91 90
15 97 96 94 93 92 91 90
Level Difference (m)

10 98 97 96 94 93 92 91 90
5 99 98 97 96 94 93 92 91 90
0 100 99 98 97 96 94 93 92 91 90
-5 98 97 96 95 94 93 92 91 89
-10 97 96 95 94 92 91 90 88
-15 95 95 93 92 91 89 88
-20 94 93 92 90 89 87
-25 92 91 90 88 86
-30 91 89 88 85

Heating

Pipe Length (m)


5 10 15 20 25 30 35 40 45 50
30 95 94 93 92
25 96 95 94 93 92
20 96 96 95 94 93 92
15 97 96 96 95 94 93 92
Level Difference (m)

10 98 97 96 96 95 94 93 92
5 99 98 97 96 96 95 94 93 92
0 100 99 98 97 96 96 95 94 93 92
-5 99 98 97 96 96 95 94 93 92
-10 98 97 96 96 95 94 93 92
-15 97 96 96 95 94 93 92
-20 96 96 95 94 93 92
-25 96 95 94 93 92
-30 95 94 93 92

68
5. Sound Data
Outdoor Units

AC048MXADKH/CB

Cooling

Pipe Length (m)


5 10 15 20 25 30 35 40 45 50 55 60 65 70 75
30 95 94 93 92 91 91 90 89 88
25 96 95 94 93 92 91 91 90 89 88
20 97 96 95 94 93 92 91 91 90 89 88
15 97 97 96 95 94 93 92 91 91 90 89 88
Level Difference (m)

10 98 97 97 96 95 94 93 92 91 91 90 89 88
5 99 98 97 97 96 95 94 93 92 91 91 90 89 88
0 100 99 98 97 97 96 95 94 93 92 91 91 90 89 88
-5 99 98 97 96 95 95 94 93 92 91 90 89 88 87
-10 98 97 96 95 94 93 93 92 91 90 89 88 86
-15 97 96 95 94 93 92 91 90 89 88 87 85
-20 95 95 94 93 92 91 90 89 88 86 84
-25 94 93 93 92 91 90 89 87 86 83
-30 93 92 91 90 89 88 87 85 82

Heating

Pipe Length (m)


5 10 15 20 25 30 35 40 45 50 55 60 65 70 75
30 96 95 94 94 93 92 91 91 90
25 96 96 95 94 94 93 92 91 91 90
20 97 96 96 95 94 94 93 92 91 91 90
15 98 97 96 96 95 94 94 93 92 91 91 90
Level Difference (m)

10 99 98 97 96 96 95 94 94 93 92 91 91 90
5 99 99 98 97 96 96 95 94 94 93 92 91 91 90
0 100 99 99 98 97 96 96 95 94 94 93 92 91 91 90
-5 99 99 98 97 96 96 95 94 94 93 92 91 91 90
-10 99 98 97 96 96 95 94 94 93 92 91 91 90
-15 98 97 96 96 95 94 94 93 92 91 91 90
-20 97 96 96 95 94 94 93 92 91 91 90
-25 96 96 95 94 94 93 92 91 91 90
-30 96 95 94 94 93 92 91 91 90

69
7. Operation Range
Outdoor Units

Outdoor Unit Indoor Unit Indoor Unit


Mode
Temperature(DB) Temperature(DB) Humidity(RH)
Cooling 80% or less
Heating
Drying 80% or less

NOTE
• The assumed installation conditions are follows

The level difference is 0 m.

70
8. Piping Diagram
Outdoor Units

AC024MN4PKH/CB + AC024MXADKH/CB, AC024MN4DKH/CB + AC024MXADKH/CB

OUTDOOR UNIT INDOOR UNIT

Thermistor-
IDU Heat Thermistor-
Exchanger Mid IDU
(T_IM) Heat
Exchanger
IN
(T_II)
Service
Valve-
Gas Pipe Heat Exchanger -
(SV_G) Indoor unit
(HX_ID)

Indoor
Fan Motor
(IFM)
Outdoor Fan Motor1 (OFM1)
Electronic Thermistor-
Expansion Valve- Indoor Room
Main1 (T_IR)
(E_M1)

Thermistor-
Ambient Heat Exchanger -
(T_A) Thermistor- Service
Main(Outdoor unit) Cond Out Valve-
(HX_M) (T_A) Liquid Pipe
(SV_L)

Solenoid valve -
4Way
(V_4W)

Accumulator
(AC)
Thermistor-
Thermistor- Discharge
Compressor pipe
Top (T_D)
(T_CT)

Compressor
(COMP)

71
7. Operation Range
Outdoor Units

AC036MN4DKH/CB + AC036MXADKH/CB, AC036MN4PKH/CB + AC036MXADKH/CB

OUTDOOR UNIT INDOOR UNIT

Thermistor-
IDU Heat Thermistor-
Exchanger Mid IDU
(T_IM) Heat
Exchanger
IN
(T_II)
Service
Valve-
Gas Pipe Heat Exchanger -
(SV_G) Indoor unit
(HX_ID)

Indoor
Fan Motor
(IFM)
Outdoor Fan Motor1 (OFM1)
Electronic Thermistor-
Expansion Valve- Indoor Room
Main1 (T_IR)
(E_M1)

Thermistor-
Ambient Heat Exchanger -
(T_A) Thermistor- Service
Main(Outdoor unit) Cond Out Valve-
(HX_M) (T_A) Liquid Pipe
(SV_L)

Solenoid valve -
4Way
(V_4W)

Accumulator
(AC)
Thermistor-
Thermistor- Discharge
Compressor pipe
Top (T_D)
(T_CT)

Compressor
(COMP)

72
7. Operation Range
Outdoor Units

AC036MNCDKH/CB + AC036MXADKH/CB

OUTDOOR UNIT INDOOR UNIT

Thermistor-
IDU Heat Thermistor-
Exchanger Mid IDU
(T_IM) Heat
Exchanger
IN
(T_II)
Service
Valve-
Gas Pipe Heat Exchanger -
(SV_G) Indoor unit
(HX_ID)

Thermistor-
Indoor Room
(T_IR)
Outdoor Fan Motor1 (OFM1)
Electronic
Expansion Valve-
Main1 Indoor Fan Motor
(E_M1) (IFM)

Thermistor-
Ambient Heat Exchanger -
(T_A) Thermistor- Service
Main(Outdoor unit) Cond Out Valve-
(HX_M) (T_A) Liquid Pipe
(SV_L)

Solenoid valve -
4Way
(V_4W)

Accumulator
(AC)
Thermistor-
Thermistor- Discharge
Compressor pipe
Top (T_D)
(T_CT)

Compressor
(COMP)

73
7. Operation Range

AC048MN4PKH/CB + AC048MXADKH/CB, AC048MN4DKH/CB + AC048MXADKH/CB

OUTDOOR UNIT INDOOR UNIT

Thermistor-
IDU Heat Thermistor-
Exchanger Mid IDU
(T_IM) Heat
Exchanger
IN
(T_II)
Service
Valve-
Gas Pipe Heat Exchanger -
(SV_G) Indoor unit
(HX_ID)

Indoor
Fan Motor
(IFM)
OutdoorFanMotor1 (OFM1) OutdoorFanMotor2 (OFM2)
Thermistor-
Electronic Indoor Room
Expansion Valve- (T_IR)
Main1 (E_M1)

Thermistor-
Ambient Heat Exchanger -
(T_A) Thermistor- Service
Main(Outdoor unit) Cond Out Valve-
(HX_M) (T_A) Liquid Pipe
(SV_L)

Solenoid valve -
4Way
(V_4W)

Accumulator
(AC)
Thermistor-
Thermistor- Discharge
Compressor pipe
Top (T_D)
(T_CT)

Compressor
(COMP)

74
7. Operation Range

AC048MNCDKH/CB + AC048MXADKH/CB

OUTDOOR UNIT INDOOR UNIT

Thermistor-
IDU Heat Thermistor-
Exchanger Mid IDU
(T_IM) Heat
Exchanger
IN
(T_II)
Service
Valve-
Gas Pipe Heat Exchanger -
(SV_G) Indoor unit
(HX_ID)

Thermistor-
Indoor Room
(T_IR)
OutdoorFanMotor1 (OFM1) OutdoorFanMotor2 (OFM2)

Electronic
Expansion Valve- Indoor Fan Motor
Main1 (E_M1) (IFM)

Thermistor-
Ambient Heat Exchanger -
(T_A) Thermistor- Service
Main(Outdoor unit) Cond Out Valve-
(HX_M) (T_A) Liquid Pipe
(SV_L)

Solenoid valve -
4Way
(V_4W)

Accumulator
(AC)
Thermistor-
Thermistor- Discharge
Compressor pipe
Top (T_D)
(T_CT)

Compressor
(COMP)

75
Installation
1. 4 Way Cassette

Installing the indoor unit CAUTION


When deciding on the location of the air conditioner the following • Make sure that the ceiling is strong enough to support the weight of the
restrictions must be taken into account. indoor unit. Before hanging the unit, test the strength of each attached
suspension bolt.
1 Place the pattern sheet on the ceiling at the spot where you want to
install the indoor unit. • If the length of the suspension bolt is more than 1.5 m, you are required
to prevent vibration.
4 Screw eight pairs of nuts and washers to the suspension bolts, making
space for hanging the indoor unit.

CAUTION
• You must install all of the suspension rods.
• It is important to leave sufficient space in the false ceiling to allow
access for maintenance or repairs to the drainage pipe connection, the
refrigerant pipe connection, or to remove the unit if necessary.

5 Hang the indoor unit to the suspension bolts between two nuts. Cut a
NOTE pad stopper and place it on the suspension bolts to hold the washers.
• Since the diagram is made of paper, it may shrink or stretch slightly due Remove the stopper and screw the nuts to fix the unit.
to temperature or humidity. For this reason, before drilling the holes, be
sure to maintain the correct dimensions between the markings.

2 Insert bolt anchors, use existing ceiling supports or construct a suitable


support as shown in figure.

6 Adjust the unit to the appropriate position, taking into account the
installation area for the front panel.

• Place the pattern sheet on the indoor unit.


• Adjust the space between the ceiling and the indoor unit by using a
dimension gauge.
3 Install the suspension bolts, depending on the ceiling type.
• Fix the indoor unit securely after adjusting the level of the unit by
using a leveller.
• Remove the pattern sheet, connect the other cables. and install the
front panel.

76
Installation
1. 4 Way Cassette

Installing the drain hose and drain pipe CAUTION


1 Push the supplied drain hose as far as possible over the drain socket. Check that the indoor unit is level with the ceiling by using the leveller.
• Install air ventilation to drain condensation smoothly.
2 Tighten the metal clamp as shown in the picture.

3 Wrap the supplied large sealing pad over the metal clamp and drain • If it is necessary to increase the height of the drain pipe, install the drain
hose to insulate and fix it with clamps. pipe straight within 300 mm from the drain hose port. If it is raised
higher than 550 mm, there may be water leaks.
4 Insulate the complete drain piping inside the building (field supply).
If the drain hose cannot be sufficiently set on a slope, fit the hose with
drain raising piping (field supply).

5 Push the drain hose up to insulation when connecting the drain hose to
drain socket.

• Do not give the hose an upward gradient beyond the connection port.
This will cause water to flow backwards when the unit is stopped,
resulting in water leaks.

77
Installation
1. 4 Way Cassette

• Do not apply force to the piping on the unit side when connecting the • Max. allowable axis gap.
drain hose. The hose should not be allowed to hang loose from its
connection to the unit. Fasten the hose to a wall, frame or other support
as close to the unit as possible.

• Max. allowable bending angle.

• Install horizontally.

NOTE
• If a concentrated drain pipe is installed, refer to the figure below.

78
Installation
1. 4 Way Cassette

Connecting the power and communication Indoor power supply

cables Power supply Max/Min(V) Indoor power cable

220 to 240V, 50/60Hz ±10%


CAUTION
Communication cable
• Always remember to connect the refrigerant pipes before performing
the electric connections.
When disconnecting the system, always disconnect the electric cables
before disconnecting the refrigerant pipes.
• Always remember to connect the air conditioner to the grounding system
before performing the electric connections. Use a crimp ring terminal at
the end of each wire.
The indoor unit is powered through the outdoor unit by means of a H07
RN-F connection cable (or a more power model), with insulation in synthetic
rubber and a jacket in polychloroprene (neoprene), in accordance with the
requirements specified in the standard EN 60335-2-40.

1 Remove the screw on the electrical component box and remove the cover
plate.
Tightening torque (kgf • cm)
2 Route the connection cord through the side of the indoor unit and
connect the cable to the terminals refer to the figure below. M3.5 8.0 to 12.0

3 Route the other end of the cable to the outdoor unit through the ceiling & M4 12.0 to 18.0
the hole on the wall.
• 1 N·m = 10 kgf·cm
4 Reassemble the electrical component box cover, carefully tightening the
screw. • Power supply cords of parts of appliances for outdoor use shall not be
lighter than polychloroprene sheathed flexible cord. (Code designation
IEC:60245 IEC 57 / CENELEC: H05RN-F or IEC:60245 IEC 66 / CENELEC:
1 phase H07RN-F)
• Since it has the external power supply, refer to the outdoor unit
installation manual for MAIN POWER.

CAUTION
• When installing the indoor unit in a computer room or network room,
use the double shielded communication cable (tape aluminum /
polyester braid + copper) of FROHH2R type.

79
Installation
2. 360 Cassette

Installing the indoor unit b For recessed installation of the circular panel
• Install inspection holes to both directions of the connection part
When deciding on the location of the air conditioner the following of the refrigerant pipe and the drain hose and of the indoor unit
restrictions must be taken into account. display.
(2 points)
1 Determine the positions of the pipe and the drain hose hole as shown in
the pattern sheet, and drill the hole with an inner diameter of 14 mm.

3 Insert bolt anchors, use existing ceiling supports or construct a suitable


support as shown in figure.

NOTE
• Since the diagram is made of paper, it may shrink or stretch slightly due
to temperature or humidity. For this reason, before drilling the holes, be
sure to maintain the correct dimensions between the markings.
2 Perform the following steps to install inspection holes in accordance
with the panel type.

a For the recessed installation of the square panel.


• Install an inspection hole to the direction of connection parts of the
refrigerant pipe and the drain hose. (1 point)
4 Install the suspension bolts, depending on the ceiling type.

CAUTION
• Make sure that the ceiling is strong enough to support the weight of the
indoor unit. Before hanging the unit, test the strength of each attached
suspension bolt.
• If the length of the suspension bolt is more than 1.5 m, you are required
to prevent vibration.
5 Screw eight pairs of nuts and washers to the suspension bolts, making
space for hanging the indoor unit.

80
Installation
2. 360 Cassette

CAUTION Installing the drain hose and drain pipe


• You must install all of the suspension rods. 1 Push the supplied drain hose as far as possible over the drain socket.
• It is important to leave sufficient space in the false ceiling to allow
2 Tighten the metal clamp as shown in the picture.
access for maintenance or repairs to the drainage pipe connection, the
refrigerant pipe connection, or to remove the unit if necessary.
6 Hang the indoor unit to the suspension bolts between two nuts. Cut a pad
stopper and place it on the suspension bolts to hold the washers. Remove
the stopper and screw the nuts to fix the unit.

3 Wrap the supplied large sealing pad over the metal clamp and drain hose
to insulate and fix it with clamps.

4 Insulate the complete drain piping inside the building (field supply).
If the drain hose cannot be sufficiently set on a slope, fit the hose with
drain raising piping (field supply).
7 Adjust the unit to the appropriate position, taking into account the 5 Push the drain hose up to insulation when connecting the drain hose to
installation area for the front panel. drain socket.
• Place the pattern sheet on the indoor unit.
• Adjust the space between the ceiling and the indoor unit by using a
dimension gauge.
• Fix the indoor unit securely after adjusting the level of the unit by
using a leveller.
• Remove the pattern sheet, connect the other cables. and install the
front panel.

CAUTION
Check that the indoor unit is level with the ceiling by using the leveller.
• Install air ventilation to drain condensation smoothly.

81
Installation
2. 360 Cassette

• Install horizontally.

• If it is necessary to increase the height of the drain pipe, install the drain
pipe straight within 300 mm from the drain hose port. If it is raised
higher than 550 mm, there may be water leaks.

• Max. allowable axis gap.

• Do not give the hose an upward gradient beyond the connection port.
This will cause water to flow backwards when the unit is stopped,
resulting in water leaks.

• Max. allowable bending angle.

• Do not apply force to the piping on the unit side when connecting the
drain hose. The hose should not be allowed to hang loose from its
connection to the unit. Fasten the hose to a wall, frame or other support
as close to the unit as possible. NOTE
• If a concentrated drain pipe is installed, refer to the figure below.

82
Installation
2. 360 Cassette

Connecting the power and communication NOTE

cables • Insert the power and the communication cables to the cable insert hole,
then arrange and connect the cables, as shown in the figure:

CAUTION
• Always remember to connect the refrigerant pipes before performing the
electric connections.
When disconnecting the system, always disconnect the electric cables
before disconnecting the refrigerant pipes.
• Always remember to connect the air conditioner to the grounding system
before performing the electric connections. Use a crimp ring terminal at
the end of each wire.
The indoor unit is powered through the outdoor unit by means of a H07
RN-F connection cable (or a more power model), with insulation in synthetic
rubber and a jacket in polychloroprene (neoprene), in accordance with the
requirements specified in the standard EN 60335-2-40.

1 Remove the screw on the electrical component box and remove the cover
plate.

2 Route the connection cord through the side of the indoor unit and
connect the cable to the terminals refer to the figure below.

3 Route the other end of the cable to the outdoor unit through the ceiling &
the hole on the wall.

4 Reassemble the electrical component box cover, carefully tightening the


screw.

Wiring terminals) 1 phase

Indoor power supply

Power supply Max/Min(V) Indoor power cable

220 to 240V, 50/60 Hz ±10%

Communication cable

83
Installation
2. 360 Cassette

Tightening torque (kgf • cm)

M3.5 8.0 to 12.0

M4 12.0 to 18.0

• 1 N·m = 10 kgf·cm

• Power supply cords of parts of appliances for outdoor use shall not be
lighter than polychloroprene sheathed flexible cord. (Code designation
IEC:60245 IEC 57 / CENELEC: H05RN-F or IEC:60245 IEC 66 / CENELEC:
H07RN-F)
• Since it has the external power supply, refer to the outdoor unit
installation manual for MAIN POWER.

CAUTION
• When installing the indoor unit in a computer room or network room, use
the double shielded communication cable (tape aluminum / polyester
braid + copper) of FROHH2R type.

84
Installation
3. Big Ceiling

Ceiling installation
CAUTION
1 Select pipe directions. • Ensure that the ceiling is strong enough to support the weight of the
indoor unit.
When the directions are selected, drill 3-1/8''-(100mm, for pipe and
cables) and 1-3/4''-(40mm, for drain hose) diameter holes on the wall so • Before hanging the unit, test the strength of each attached suspension
that it slants slightly downwards toward the outdoor for smooth water bolt.
flow. • Install the drain hose from the rear of the unit.

NOTE NOTE
• Use the template to select pipe directions. • The gap between the lower end of the indoor unit and the ceiling should
2 Drill holes for anchor bolts according to the distance and mount them.
4 When Hanging the set, firstly unscrew the screws from the both of
NOTE sides, and then disassemble the Case-sides, or else the case-side will be
damaged by disassembling it directly.
• Use the template.
3 Install the unit onto the ceiling. Be sure to arrange the drain hose so that
it is leveled lower than the drain hose connecting port of the indoor unit.

NOTE
• For proper drainage of condensate, give a 2° (The gap between the lower Unscrew two screws from the both of sides.

the side of the unit which will be connected with the drain hose as shown 5 Reassemble the Case-sides, tightening the screws after hanging the set.
in the figure.

Connection pipe

Drain hose

Connection pipe
Remove the Case-sides from the both of sides.
Drain hose

85
Installation
3. Big Ceiling

Installing the drain hose and drain pipe wall

Care must be taken when installing the drain hose for the indoor unit to hole

ensure that any condensation water is correctly drained outside.

NOTE
• Installing the drain hose should be the shorter, the better.
• In order to discharge condensate water, a downward gradient should be No grade
maintained.
• Fix the drain hose with Cable-Tie, so that it will not separate from the
machine.

1 Insert the drain hose to bottom of the outfall of water basin.

2 Lock flexible hose clamp of the drain hose according to the figure.
3 Wind and wrap flexible hose clamp and drain hose fully with thermal
insulation sponge; fix both ends of external layer with ribbon for thermal
insulation.
No slack No in the water water
4 After being installed, drain hose must be insulated fully by heat
insulating material. (To be provided at site.)

• Be sure to tighten the flexible hose clamp of the drain hose.


• Wrap the insulation after attaching the flexible hose clamp.
Connecting the power and communication
cables
Flexible hose clamp of drain hose

Joint of drain hose Fix with Cable-Tie


CAUTION
A • Always remember to connect the refrigerant pipes before performing
Drain hose the electric connections.
Indoor unit
When disconnecting the system, always disconnect the electric cables
before disconnecting the refrigerant pipes.

A A-A’ CAUTION
Drain hose
Wrap thermal sleeve hose • Always remember to connect the air conditioner to the grounding system
before performing the electric connections. Use a crimp ring terminal at
the end of each wire.
The indoor unit is powered through the outdoor unit by means of a H07
RN-F connection cable (or a more power model), with insulation in synthetic
rubber and a jacket in polychloroprene (neoprene), in accordance with the
requirements specified in the standard EN 60335-2-40.

1 Remove the screw on the electrical component box and remove the
cover plate.

2 Route the connection cord through the side of the indoor unit and
connect the cable to the terminals refer to the figure below.

3 Route the other end of the cable to the outdoor unit through the ceiling &
the hole on the wall.

4 Reassemble the electrical component box cover, carefully tightening the


screw.

86
Installation
3. Big Ceiling

1 phase
Tightening torque (kgf • cm)

M3.5 8.0 to 12.0

Indoor Unit M4 12.0 to 18.0

• 1 N·m = 10 kgf·cm

1(L) 2(N) 1 2 F1 F2 V1 V2 F3 F4 • Power supply cords of parts of appliances for outdoor use shall not be
lighter than polychloroprene sheathed flexible cord. (Code designation
IEC:60245 IEC 57 / CENELEC: H05RN-F or IEC:60245 IEC 66 / CENELEC:
H07RN-F)

1(L) 2(N) L N F1 F2 • Since it has the external power supply, refer to the outdoor unit
installation manual for MAIN POWER.

Cable
clamp

CAUTION
Indoor Power Main power cable Communication • When installing the indoor unit in a computer room or a server room,
cable use the double shielded communication cable (tape aluminum /
polyester braid + copper) of FROHH2R type.

Indoor power supply

Power supply Max/Min(V) Indoor power cable

220 to 240V, 50/60 Hz ±10% 2.5mm2

Communication cable

0.75mm2

AC power: M4 screw Communication: M3.5 screw

11 13 7.5 9.0

87
Installation
4. Outdoor Unit

Choosing the installation location CAUTION


• You have just purchased a system air conditioner and it has been
installed by your installation specialist.
Installation location requirements
• This device must be installed according to the national electrical
• Do not place the outdoor unit on its side or upside down. Failing to do so rules.
may cause the compressor lubrication oil to run into the cooling circuit
• If your outdoor unit exceeds a net weight of 60 kg, do not install it on
and lead to a serious damage to the unit.
a suspended wall, but stand it on a floor.
• Install the unit in a well-ventilated location away from direct sunlight or
• When installing the outdoor unit at the seaside, make sure that it is not
strong winds.
directly exposed to sea breeze. If you cannot find an adequate place free
• Install the unit in a location that would not obstruct any passageways or from direct sea breeze, construct a protection wall or a protective fence.
thoroughfares.
Install the outdoor unit in a place (such as near buildings etc.) where
• Install the unit in a location that would not inconvenience or disturb your it can be prevented from sea breeze. Failure to do so may cause a
neighbors, as they could be affected by the noise or the airflow coming damage to the outdoor unit.
from the unit.
• Install the unit in a location where the pipes and the cables can be easily
connected to the indoor unit.
• Install the unit on a flat, stable surface that can withstand the weight
of the unit. Otherwise, the unit can generate noise and vibration during
operation.
• Install the unit so that the air flow is directed towards the open area.
• Maintain sufficient clearance around the outdoor unit, especially from a • If you cannot avoid installing the outdoor unit at the seaside, construct a
radio, computer, stereo system, etc. protection wall around to block the sea breeze.
• Construct a protection wall with a solid material such as concrete to
block the sea breeze. Make sure that the height and the width of the wall
are 1.5 times larger than the size of the outdoor unit. Also, secure a space
larger than 700 mm between the protection wall and the outdoor unit for
exhausted air to ventilate.

CAUTION
• Depending on the condition of power supply, unstable power or voltage
may cause malfunction of the parts or control system. (At the ship or
places using power supply from electric generator...etc)
• Install the unit in a place where water can drain smoothly.
• If you have any difficulty finding installation location as prescribed above,
• Install the unit at a height where its base can be firmly fixed in place.
contact your manufacturer for details.
• Make sure that the water dripping from the drain hose runs away
correctly and safely. • Be sure to clean the sea water and the dust on the heat exchanger of the
outdoor unit and apply a corrosion inhibitor on it. (At least once in a year.)

88
Installation
4. Outdoor Unit

Outdoor unit dimensions Minimum clearances for the outdoor unit

A Type When installing 1 outdoor unit


AC024MXADKH
(Unit: mm)

B Type
AC036MXADKH

C Type
AC048MXADKH

89
Installation
4. Outdoor Unit

When installing more than 1 outdoor unit


WARNING
(Unit: mm) • Should adopt bar type louver. Don’t use a type of rain resistance louver.

• Louver specifications.
Angle criteria : less than 20°
Opening ratio criteria : greater than 80%

Moving the outdoor unit with wire rope

1 Before carrying the outdoor unit, fasten two wire ropes of 8 m or longer,
as shown in the figure.

2 To prevent damages or scratches effectively, insert a piece of cloth


between the outdoor unit and the ropes.

3 Move the outdoor unit.

CAUTION
• The outdoor unit must be installed according to the specified distances
in order to permit accessibility from each side, to guarantee correct
operation, maintenance, and repair of the unit.
The components of the outdoor unit must be reachable and removable
under safe conditions for people and the unit.

90
Installation
4. Outdoor Unit

Fixing the outdoor unit in place Optional: Fixing the outdoor unit to a wall with a rack

Install the outdoor unit on a rigid and stable base to prevent disturbance
from any noise caused by vibration. When installing the unit at a height or in
a location exposed to strong winds, fix the unit securely to a support (i.e., a
wall or a ground).
Fix the outdoor unit with anchor bolts. Make sure that the anchor bolts are
20 mm or higher from the base surface.

• Install a proper grommet in order to reduce noise and residual vibration


transferred by the outdoor unit towards the wall.

CAUTION
• When installing an air guide duct, be sure to check the following:
The screws do not damage the copper pipe.
The air guide duct is fixed firmly on the guard fan.

CAUTION
• Install a drain outlet at the lowest end around the base for outdoor unit
drainage
• When installing the outdoor unit on the roof, waterproof the unit and
check the ceiling strength.

• Make sure that the wall can support the weights of the rack and the
outdoor unit.
• Install the rack close to the column as much as possible.

91
Installation
4. Outdoor Unit

Connecting the power cables, communication Air conditioning system examples


cable, and controllers When using earth leakage circuit breaker (ELCB) for a single phase

You must connect the following three electrical cables to the outdoor unit:
• The main power cable between the auxiliary circuit breaker and the
outdoor unit.
• The outdoor-to-indoor power cable between the outdoor unit and the
indoor unit.
• The communication cable between the outdoor unit and the indoor unit.

CAUTION
• During installation, make first the refrigerant connections and then
the electrical connections. If the unit is uninstalled, first disconnect the
electrical cables and then the refrigerant connections.
• Connect the air conditioner to the earthing system before making the
electrical connections.
ELCB
1
NOTE
• Especially, if your outdoor unit is the one designed for Russian and
European markets, consult the supply authority, if necessary, to estimate
and reduce the supply system impedance before installation.

CAUTION
• If the outdoor unit is installed in a location vulnerable to an electric leak
or submergence, make sure to install an ELCB.

92
Installation
4. Outdoor Unit

Connecting the main power cable

When using ELB for 1 phase

1(L) 2(N) L N

• Devices disconnected from the power supply should be completely


CAUTION disconnected in the condition of overvoltage category.
• You should connect the power cable into the power cable terminal and
• Keep distances of 50 mm or more between power cable and
fasten it with a clamp.
communication cable.
• The unbalanced power must be maintained within 2% of supply rating.
If the power is unbalanced greatly, it may shorten the life of the Main power terminal block specifications
condenser. If the unbalanced power is exceeded over 4% of supply
rating, the indoor unit is protected, stopped and the error mode
indicates.
• To protect the product from water and possible shock, you should keep
the power cable and the connection cord of the indoor and outdoor units
within ducts. (with appropriate IP rating and material selection for your
application)
• Ensure that main supply connection is made through a switch that
disconnects all poles, with contact gap of a least 3 mm.

93
Installation
4. Outdoor Unit

Connecting the main power cable

When using ELB for 1 phase

Main power terminal block specifications


CAUTION
• 1-phase terminal block specifications
• You should connect the power cable into the power cable terminal and
fasten it with a clamp.
• The unbalanced power must be maintained within 2% of supply rating.
If the power is unbalanced greatly, it may shorten the life of the
condenser. If the unbalanced power is exceeded over 4% of supply
rating, the indoor unit is protected, stopped and the error mode
indicates.
• To protect the product from water and possible shock, you should keep
the power cable and the connection cord of the indoor and outdoor units
within ducts. (with appropriate IP rating and material selection for your
application)
• Ensure that main supply connection is made through a switch that
disconnects all poles, with contact gap of a least 3 mm.
• Devices disconnected from the power supply should be completely
disconnected in the condition of overvoltage category.
• Keep distances of 50 mm or more between power cable and
communication cable.

94
Installation
4. Outdoor Unit

Main power cable specifications


The power cable is not supplied with air conditioner.
• Select the power supply cable in accordance with relevant local and national regulations.
• Wire size must comply with the applicable local and national code.
• Specifications for local wiring power cord and branch wiring are in compliance with local cord.

Single phase

Indoor unit Outdoor unit Hz Volts Min. Max. Cooling Heating Indoor unit Total MCA MFA
AC024MN4DKH/CB 60 220-240 198 264 20 20 1.0 21.0 21.0 25.0
AC024MXADKH/CB
AC024MN4PKH/CB 60 220-240 198 264 20 20 1.5 21.5 21.5 25.0
AC036MN4PKH/CB 60 220-240 198 264 24 24 1.5 25.5 25.5 30.0
AC036MN4DKH/CB AC036MXADKH/CB 60 220-240 198 264 24 24 1.0 25.0 25.0 30.0
AC036MNCDKH/CB 60 220-240 198 264 24 24 2.0 26.0 26.0 30.0
AC048MN4PKH/CB 60 220-240 198 264 32 32 1.5 33.5 33.5 40.0
AC048MN4DKH/CB AC048MXADKH/CB 60 220-240 198 264 32 32 1.0 33.0 33.0 40.0
AC048MNCDKH/CB 60 220-240 198 264 32 32 2.0 34.0 34.0 40.0

NOTE

1 Voltage range 4 MFA is used to select the circuit breaker and the ground fault circuit
• Units are suitable for use on electrical systems where voltage interrupter (earth leakage circuit breaker).
supplied to unit terminal is not below or above listed range limits 5 MCA represents maximum input current.
2 Maximum allowable voltage variation between phases is 2%.
• MFA represents capacity which may accept MCA
3 Wire size & type must comply with the applicable local and national code. • Abbreviations
• Wire size: Based on the value of MCA. MCA: Min. Circuit Amps. (A)
• Wire type: 60245 IEC57(IEC) or H05RN-F(CENELEC) grade or more. MFA: Max. Fuse Amps. (A)

95
Installation
4. Outdoor Unit

Connecting the refrigerant pipe

L1

L0

Pipe length or height


Refrigerant piping system table
AC024MXADKH

Max. allowable length Actual pipe length L0 + H + L1 50m or less

Allowable height length Actual pipe length H 30m or lesss

• Temper grade and minimum thickness of the refrigerant pipe

Minimum thickness
Outer diameter [mm] Temper grade
[mm]
ø6.35 0.7
ø9.52 0.7
C1220T-O
ø12.70 0.8
ø15.88 1.0
• The appearance of the unit may be different from the diagram depending
ø15.88 0.8 on the model.
C1220T-1/2H OR
ø19.05 0.9
C1220T-H
ø22.23 0.9 CAUTION
• After connecting the pipes with knock-out treatment, plug the space
CAUTION around the pipes.
• Be sure to use C1220T-1/2H (Semi-hard) pipe for more than Ø19.05 mm. • After connecting the pipes, proceed exactly as directed in the guide to
If you use C1220T-O (Soft) pipe for Ø19.05 mm, the pipe may be broken, prevent interference with the internal parts.
which can result in an injury.

96
Installation
4. Outdoor Unit

Connecting the refrigerant pipe

Maximum allowable length


Items
Single installation DPM installation
Applicable outdoor unit models AC036MXADKH AC048MXADKH AC036MXADKH AC048MXADKH
Total pipe length (L1+…+Ln+1+a+b) - - 50 m 75 m
Main pipe (L1) 50 m 75 m 30 m 50 m
Max. distance among indoor units (D) - - 10 m 10 m
Max. length after branch - - 15 m 15 m
Max. height difference between
30 m 30 m 30 m 30 m
outdoor and indoor units (h1)
Max. height difference among
- - 0.5 m 0.5 m
indoor units(h2)
Max Pipe length difference among indoor units after branch
- - 5m 5m
[L2-L3 or L2-L4 or L2-L5 or a-b or (a+L2)-(b+L4) or (a+L3)-(b+L5)]

• "n" means the number of indoor unit connection of DPM.

n=1 n=3 L2
indoor indoor
L1
L1 L3 D
h1 indoor h2 h1
D
L4
outdoor indoor
outdoor
L2 L2
indoor indoor
n=2 L1 n=4 a
h2 L 3
D L1 indoor D
h1 L4 h2 h1
indoor indoor D
L3
b L5 indoor
outdoor outdoor

• Use a joint kit that is only for DPM.


• Temper grade and minimum thickness of the refrigerant pipe

Outer diameter [mm] Minimum thickness [mm] Temper grade


ø6.35 0.7
ø9.52 0.7
C1220T-O
ø12.70 0.8
ø15.88 1.0
ø15.88 0.8
ø19.05 0.9 C1220T-1/2H OR C1220T-H
ø22.23 0.9

97
Accessory
Controller

Classification Product Image Model Remark

DMS 2.0 MIM-D00AN

Intergrated
Management MIM-D01AN
DMS 2.5
System MIM-D01AUN

S-NET 3 MST-P3P

MIM-B17BN
BACnet G/W
MIM-B17BUN

MIM-B18BN
LONWORKS G/W
MIM-B18BUN
Buiding
Management
System
PIM
MIM-B16N
(Pulse Interface Module)

SIM
MIM-B12N
(Signal Interface Module)

On/Off Controller MCM-A202DN

Centralized Touch Controller MCM-A300N


Control System

MIM-H03N
Wi-Fi Kit
MIM-H03UN

98
Accessory
Controller

Classification Product Image Model Remark


MR-EH00/EH00M
MR-EC00/EC00M Except for 360 Cassette
Wireless remote Controller MR-EH00U
AR-KH00E
360 Cassette Only
AR-KH00U

MWR-WE10N

Individual Include 360 Cassette Airflow


Control System MWR-WE11N
Control function

Wired remote Controller


MWR-SH00N Simple Type

MWR-SH10N Touch Simple Type

External room sensor MRW-TA

Compatible interface module MIM-N01

Others External contact MIM-B14


interface module MIM-B14A

S-Converter MIM-C02N

Wireless signal receiver MRK-A10N Duct type only

• In case you want more information about the accessories, please refer to the control and accessories TDB on
pvi.samsung.com site.

99
Accessory
Indoor Unit’s Accessory

Product Image Model Remark

PC1NUSMAN Slim 1Way Cassette

PC1NUPMAN Slim 1Way Cassette (Z-sliding)

PC1MWSKAN Slim 1Way Cassette

PC4SUSMBN 4 Way Cassette(600 x 600) (Waffle)

PC4SUSMFN 4 Way Cassette(600 x 600) (Classic)

PC4NUSKAN 4 Way Cassette (Waffle)

PC4NUSKEN 4 Way Cassette (Classic)


Panel

PC4NBSKAN 4 Way Cassette (Waffle / Black)

PC4NUDMAN 360 Cassette Square (White)

PC4NUNMAN 360 Cassette Circle (White)

PC4NBDMAN 360 Cassette Square (Black)

PC4NBNMAN 360 Cassette Circle (Black)

[Option] 4Way, 4Way(600x600), 360, Ceiling


MSD-CAN1
[Included] Console
S-Plasma Ion KIT
MSD-EAN1 [Option] Duct S, Big Duct, ERV, ERV Plus

100
Accessory
Indoor Unit’s Accessory

Product Image Model Remark

Motion detect
MCR-SMA 4 Way Cassette(600 x 600)
Sensor

MDP-E075SEE3D Slim Duct

Drain Pump
MDP-G075SP Duct S (External)

MDP-G075SQ Duct S (Internal)

MXJ-2D2509K 2 indoor units connection

MXJ-3D2509K 3 indoor units connection


Joint

MXJ-4D2509K 4 indoor units connection

• In case you want more information about the accessories, please refer to the control and accessories TDB on
pvi.samsung.com site.

101
2018. 09
Ver.1.2
Samsung Electronics Co., LTD.
B2B PM / SE
Head Office (Suwon Korea) 129, Samsung-Ro, Yeongtong-Gu, Suwon City, Gyeonggi-Do, Korea 16677
Website : www.samsung.com, http://btsp.samsunggsbn.com Email : airconditioner@samsung.com
Images and data in this book may subject to change without prior notice.