SELF ASSESSMENT - RAN - E NODE B
SITE ID ZBGR_4528 SITE NAME KEDUNG HALANG SEVERITY PASS - - FAIL
SUBCON TMR REGION JABO CRITICAL
SUBMIT DATE 8/26/2020 SUBMIT BY ISKANDAR MAJOR
REVIEW DATE 8/26/2020 REVIEW BY Andi MINOR
Sno Item Check Item Code Severity Descriptions Result Remarks Actula Picture Actula Picture
1 CABINET INSTALLATION CHECK
Cabinet and/or Sub rack positioned as shown
Z.E.1.1.1 Major on Floor plan in Design Pack FAIL Photo geotag tidak ada site ID
Z.E.2.5.4 Minor GPS cable label must be clear and neat and
printed
Z.E.2.5.5 Major GPS Arrester is installed as per Guideline
Horizontal Cable runs are neat and straight perlu pasang klemp kabel power RRU di
Z.E.3.1.1 Major and layout conform to the design pack and FAIL horizontal tray,geotag tdk ada site ID
use metal conduit for optic cables
Sno Item Check Item Code Severity Descriptions Result Remarks Actula Picture Actula Picture
Laying cable Horizontal and Vertical
3.1 Installation
Grounding kit installed on Radio Remote Photo grounding kit tdk jelas dan tdk
Z.E.3.2.1 Major Unit DC Power cable/GPS Cable and FAIL ada geotag site ID
integrated to grounding bar
Sno Item Check Item Code Severity Descriptions Result Remarks Actula Picture Actula Picture
GPS Antenna is located at "As Planned"
Z.E.3.3.1 Major height
All RF Jumper Cable ½" laying cable not perbaiki laying kabel jumper dan
Z.E.3.6.4 Major routed on fix arm of Tower mounting FAIL reposisi penempatan spare optic ke
bracket belakang masing" RRU
Z.E.3.11.2
N/A N/A
3.5 TDD RADIO REMOTE UNIT INSTALLATION
Sno Item Check Item Code Severity Descriptions Result Remarks Actula Picture Actula Picture
Z.E.3.1.7 Major The excess power cables must be cut off and
coiling of remaining are not allowed
Z.E.3.9.3 Major Jumper connected to FDD Filter Unit as per FAIL perlu view full filter dgn koneksi kabel
Design Pack
Z.E.3.10.5
Major Grounding cable plugs are securely seated
Sno Item Check Item Code Severity Descriptions Result Remarks Actula Picture Actula Picture
Sno Item Check Item Code Severity Descriptions Result Remarks Reference Picture Actual Picture
1 RECTIFIER INSTALLATION CHECK
Z.R.1.1.1 Critical New Rectifier Cabinet Type and positioned as shown in Design Pack
Z.R.1.1.2 Minor Sub Rack is clean and not scratched or dented or damage
Sub Rack are screwed in firmly with all the proper bolts/No Missing
Z.R.1.1.3 Major Screw
Z.R.1.2.1 Critical Number and placement of module should be installed as per Design
Pack (including add new rectifier module on existing Rectifier)
Z.R.1.2.2 Critical Confirm full set of DC MCBs installed as per Design Pack
Z.R.1.2.4 Minor All empty slots must be closed with dummy panels
Z.R.2.2.2 Major DC Power cable plugs are securely seated at both end (Rectifier part
and Battery part)
Z.R.2.2.3 Minor All Power cable label must be clear and neat and printed at both end
1.1 Rectifier Sub Rack Installation
Check
Z.R.2.2.4 Major AT Rectier all battery cable connection is done properly
Verify that all power cable wiring and heat shrinkable uses correct
Z.R.2.2.5 Minor colors'
Internal grounding wire uses Green and yellow color and connect to
Z.R.2.3.2 Critical rack grounding bar
Z.R.2.3.3 Major All grounding connection must be terminated with cable lugs
Z.R.2.3.4 Minor Grounding cable lug is terminated using heat-shrink/ sealant tape
Z.R.2.3.5 Major Grounding cable plugs in cabinet bus bar are securely seated
Z.R.1.3.2 Critical DRY CONTACT are screwed in firmly with all the proper bolts/No
Missing Screw
Z.R.2.3.1 Major Grounding cable connected to Cabinet door, Sub rack and/or
modules and integrated to Grounding bar
1.2
2 CABLE INSTALLATION AND LABELLING CHECK
Z.R.2.1.2 Major AC Power cable plugs are securely seated at ACPDB & SPD sensor FAIL koneksi kabel alarm kurang phase F/ arres
installed properly
Z.R.2.1.4 Minor All Power cable label must be clear and neat and printed at both end
2.1.2
Z.R.2.3.6 Major Sub rack is Grounded to the main bus bar as per site specifications
Z.R.2.3.7 Minor Grounding cable lug is terminated using heat-shrink/ sealant tape
2.2
3 CABINET SERIAL NUMBER
3.1
4 BATTERY TEST CAPACITY WAREHOUSE LABEL ( Applied only to AGM battery)
SITE ID ZBGR_4528 SITE NAME KEDUNG HALANG SEVERITY PASS - - FAIL TOTAL N/A
SUBCON TMR REGION JABO CRITICAL
SUBMIT DATE 8/26/2020 SUBMIT BY ISKANDAR MAJOR
REVIEW DATE 8/26/2020 REVIEW BY Andi MINOR
Sno Item Check Item Code Severity Descriptions Result Remarks Reference Picture Actual Picture
4.1 Block 1.1 Z.R.4.1.1 Major Battery Performent test from warehouse must available on Battery
4.1
4.2 Block 1.2 Z.R.4.1.1 Major Battery Performent test from warehouse must available on Battery FAIL perlu photo sticker battery test dr WH 2
4.2
4.3 Block 1.3 Z.R.4.1.1 Major Battery Performent test from warehouse must available on Battery N/A N/A
4.3
4.4 Block 1.4 Z.R.4.1.1 Major Battery Performent test from warehouse must available on Battery N/A N/A
4.4
4.5 Block 1.5 Z.R.4.1.1 Major Battery Performent test from warehouse must available on Battery N/A N/A
4.5
4.6 Block 1.6 Z.R.4.1.1 Major Battery Performent test from warehouse must available on Battery N/A N/A
4.6
4.7 Block 1.7 Z.R.4.1.1 Major Battery Performent test from warehouse must available on Battery N/A N/A
4.7
4.8 Block 1.8 Z.R.4.1.1 Major Battery Performent test from warehouse must available on Battery N/A N/A
4.8
4.9 Block 1.9 Z.R.4.1.1 Major Battery Performent test from warehouse must available on Battery N/A N/A
4.9
4.10 Block 1.10 Z.R.4.1.1 Major Battery Performent test from warehouse must available on Battery N/A N/A
4.10
4.11 Block 1.11 Z.R.4.1.1 Major Battery Performent test from warehouse must available on Battery N/A N/A
4.11
SITE ID ZBGR_4528 SITE NAME KEDUNG HALANG SEVERITY PASS - - FAIL TOTAL N/A
SUBCON TMR REGION JABO CRITICAL
SUBMIT DATE 8/26/2020 SUBMIT BY ISKANDAR MAJOR
REVIEW DATE 8/26/2020 REVIEW BY Andi MINOR
Sno Item Check Item Code Severity Descriptions Result Remarks Reference Picture Actual Picture
4.12 Block 1.12 Z.R.4.1.1 Major Battery Performent test from warehouse must available on Battery N/A N/A
4.12
SITE ID ZBGR_4528 SITE NAME KEDUNG HALANG SEVERITY PASS - - FAIL TOTAL N/A
SUBCON TMR REGION JABO CRITICAL
SUBMIT DATE 8/26/2020 SUBMIT BY ISKANDAR MAJOR
REVIEW DATE 8/26/2020 REVIEW BY Andi MINOR
Sno Item Check Item Code Severity Descriptions Result Remarks Reference Picture Actual Picture
5 SETTING PARAMETER CHECK
5.1 Floating Voltage Z.R.4.5.1 Major Check the paramater of Floating voltage
N/A
5.2 Equal Voltage Z.R.4.5.2 Major Check the paramater of equal voltage
5.1
5.3 Charge current limit Z.R.4.5.3 Major Check the paramater of charge current limit
5.2
5.4 Battery Cap#1 Z.R.4.5.4 Major Check the paramater of battery cap#1
5.5 Battery Cap#2 Z.R.4.5.5 Major Check the paramater of battery cap#2
N/A
5.6 Battery Cap#3 Z.R.4.5.6 Major Check the paramater of battery cap#3
5.3