AMPS-24/E: Intelligent Power Supply Manual
AMPS-24/E: Intelligent Power Supply Manual
AMPS-24/E
Manual
This system meets NFPA requirements for operation at 0-49º C/ This system contains static-sensitive components. Always
32-120º F and at a relative humidity 93% ± 2% RH (non-condens- ground yourself with a proper wrist strap before handling any cir-
ing) at 32°C ± 2°C (90°F ± 3°F). However, the useful life of the sys- cuits so that static charges are removed from the body. Use static
tem's standby batteries and the electronic components may be suppressive packaging to protect electronic assemblies removed
adversely affected by extreme temperature ranges and humidity. from the unit.
Therefore, it is recommended that this system and its peripherals Units with a touchscreen display should be cleaned with a dry,
be installed in an environment with a normal room temperature of clean, lint free/microfiber cloth. If additional cleaning is required,
15-27º C/60-80º F. apply a small amount of Isopropyl alcohol to the cloth and wipe
Verify that wire sizes are adequate for all initiating and indicating clean. Do not use detergents, solvents, or water for cleaning. Do
device loops. Most devices cannot tolerate more than a 10% I.R. not spray liquid directly onto the display.
drop from the specified device voltage. Follow the instructions in the installation, operating, and pro-
gramming manuals. These instructions must be followed to avoid
damage to the control panel and associated equipment. FACP
operation and reliability depend upon proper installation.
Precau-D2-11-2017
FCC Warning
WARNING: This equipment generates, uses, and can radi- Canadian Requirements
ate radio frequency energy and if not installed and used in This digital apparatus does not exceed the Class A limits for
accordance with the instruction manual may cause interfer- radiation noise emissions from digital apparatus set out in
ence to radio communications. It has been tested and found the Radio Interference Regulations of the Canadian Depart-
to comply with the limits for class A computing devices pur- ment of Communications.
suant to Subpart B of Part 15 of FCC Rules, which is
designed to provide reasonable protection against such Le present appareil numerique n'emet pas de bruits radio-
interference when devices are operated in a commercial electriques depassant les limites applicables aux appareils
environment. Operation of this equipment in a residential numeriques de la classe A prescrites dans le Reglement sur
area is likely to cause interference, in which case the user le brouillage radioelectrique edicte par le ministere des
will be required to correct the interference at his or her own Communications du Canada.
expense.
HARSH™, NIS™, NOTI•FIRE•NET™, and eVance™ are all trademarks; and Acclimate® Plus™, FlashScan®, FAAST Fire Alarm Aspiration Sensing Technology®,
Honeywell®, Intelligent FAAST®, NOTIFIER®, ONYX®, ONYXWorks®, SWIFT®, VeriFire®, and VIEW® are all registered trademarks of Honeywell International Inc.
Microsoft® and Windows® are registered trademarks of the Microsoft Corporation. Chrome™ and Google™ are trademarks of Google Inc.
©Thursday, November 07, 2019 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.
Documentation Feedback
Your feedback helps us keep our documentation up-to-date and accurate. If you have any comments or suggestions about our online
Help or printed manuals, you can email us.
Please include the following information:
• Product name and version number (if applicable)
• Printed manual or online Help
• Topic Title (for online Help)
• Page number (for printed manual)
• Brief description of content you think should be improved or corrected
• Your suggestion for how to correct/improve documentation
Send email messages to:
FireSystems.TechPubs@honeywell.com
Please note this email address is for documentation feedback only. If you have any technical issues, please contact Technical
Services.
1.1 Features
• SLC Addressable by any CLIP or FlashScan Fire Alarm Control Panel (FACP)
• Remote charger/general purpose power supply
• Charges 7 to 200 AH batteries
• Isolated Signaling Line Circuit (SLC) interface
• Brownout detection
• Battery/battery charger supervision
• Disconnect of deeply-discharged battery (low battery disconnect)
• Selectable charger current
• AC loss detection and AC loss delay reporting
• Five-point trouble reporting
• Two models available: AMPS-24 (120 VAC, 50/60 Hz) or AMPS-24E (220-240 VAC, 50/60 Hz)
1.2 Specifications
The AMPS-24 is comprised of two boards; the CPS-24 board (the smaller front board), and the AMPS-K2 (the larger rear board). See
Figure 1.1.
When AC power is lost, the deeply-discharged battery cutoff protection will be invoked at 17 volts. The power supply will be discon-
nected from the batteries. The power supply’s normal operation will be restored when AC power returns.
NOTE: The AMPS-24 can provide up to 3A for releasing applications, limited by the FCM-1-REL.
NOTE: Unless otherwise indicated, when used in this manual, NFS2-3030 refers to both the NFS-3030 and NFS2-3030E
and AMPS-24 refers to both the AMPS-24 and AMPS-24E.
SLC (TB2)
COM
A B +24V
+ – +–
TBL
Slide Switch SW3 BUS
Rotary Switch SW2 (TB4)
+–
USB Port J3
Type B
Outputs (TB2)
Accessories
+ 24V
COM
COM
+ 5V
Connections
BAT +
Battery
(TB3)
BAT –
Ground Fault
Switch SW1
amps24_CPS24andMaina.wmf
HOT
AC (TB1)
NEUT
EARTH
GROUND
AC Fuse F4
GEN TBL
LED 4
+24V AUX
LED 5
+5V AUX
LED 6
LOGIC POWER
LED 1
TROUBLE
LED 2
EARTH FAULT
LED 3
AC
LED 4
amps24_CPS24andMain.wmf
Figure 1.2 Locations of LED Indicators
There are eighteen LEDs that indicate various conditions and troubles. The following table lists and describes each.
5 TBL BUS Yellow Steady when external trouble bus signal received (trouble bus shorted)
2 TROUBLE Yellow Coded trouble indicator: 1 blink = AC failure; 2 blinks - high battery; 3
blinks = low battery; 4 blinks = charger failure
CPS-24 3 EARTH FAULT Yellow Ground fault detected
Board 4 AC Green AC is on
NOTE: A surge suppressor, model EDCO HSP121BT-1RU (for 120VAC operations) is required when using the FCM-1-REL for releasing
applications. The AMPS-24E power supply is not suitable for releasing applications.
amps24cab3b.wmf
CHS-6 Chassis
EQ Series Cabinet
Figure 2.2 EQ Series Backbox
BB100_AMPS24_2Batta.wmf
Figure 2.4 BB-100 Mounting
BB200_AMPS24_4Battb.wmf
Figure 2.5 BB-200 Mounting
The AMPS-24 mounts in a BB-200 cabinet with four 100 amp-hour batteries (two on the top shelf and two on the bottom). The power
supply is fastened directly to the unpainted section of the backbox with two keps nuts.
WARNING: Heavy Load!
! The total weight of a fully loaded BB-200 will exceed 300 pounds. Additional support may be required when mounting this
cabinet to a wall.
See BB-100/200 Cabinet Installation Instructions for more information.
amps24_BB25_pwrlmtdb.wmf
TB2: Accessories Output Wiring (5V,
24V) - Power-limited (Class 2) and
filtered. (See page 22.)
Figure 2.6 BB-25 Cabinet: Power-limited (Class 2) Wiring Example, with Two Battery Wiring
Side-View
Power-
limited
NFS2-3030 (Class 2)
circuits
TB1: AC Primary AC
Power Wiring -
Nonpower-limited
Grounding Wire and supervised
Figure 2.7 CAB-4 Series Cabinet: Power-limited (Class 2) Wiring Example
TB1 - Main 24V power to panel. Power- The BB-100 cabinet must be
limited (Class 2). located less than 20 feet (6.1
TB2 - Secondary Power 5V and
TB2 - SLC Circuit Wiring - Power-limited m) from the enclosure
24V Auxiliary outputs. Power-
(Class 2) and supervised. housing the control panel and
limited (Class 2).
TB4 - Trouble Bus Wiring - Power-limited all connections must be
(Class 2) and non-supervised. contained in conduit.
TB1 - AC Primary
Power Wiring -
Nonpower-limited and
supervised TB3 - 24V Auxiliary power.
Power-limited (Class 2).
TB3 - Nonpower-limited
and supervised
BB100_AMPS24_Power
Grounding
Wire
Figure 2.8 BB-100 Cabinet: Power-limited (Class 2) Wiring Example with Two Battery Wiring
TB1 - Main 24V power to panel. Power-limited (Class 2).
TB2 - SLC Circuit Wiring - Power-limited (Class 2) and
TB2 - Secondary Power supervised.
5V and 24V Auxiliary TB4:Trouble Bus Wiring - Power-limited (Class 2), non-
outputs. Power-limited supervised.
(Class 2).
TB1 - AC Primary
Power Wiring -
Nonpower-limited
TB3 - 24V Auxiliary
and supervised.
power. Power-limited
(Class 2).
TB3 -
Nonpower-
limited and
supervised.
Grounding
Wire
Figure 2.9 BB-200 Cabinet: Power-limited (Class 2) Wiring Example with Four Battery Wiring
2.7.1 Overview
Complete all mounting procedures and check all wiring before applying power. Electrical connections are listed below and are detailed
in the following paragraphs:
AMPS-K2 (rear board)
TB1 - MAIN 24V
Main output, 5 A, 24VDC (nominal), output.
• 5A
1) with 5A charger and AUX 24V output disabled, or
2) with 1A charger and 3A AUX 24V, or
3) with 2A charger and 3A AUX 24V,
OR
• 3A (with 5A charger and 1A AUX 24V)
These values are described in table format in Table 1.1 on page 8.
TB3 - AUX 24V
Auxiliary 24V output provides filtered power-limited (Class 2) power for additional components.
• 5A (charger disabled)
• 3A (1A/2A charger)
• 1A (5A charger and 3A Main 24V output)
These values are described in table format in Table 1.1 on page 8.
TB2 - SLC Wiring
Connect to panel Signaling Line Circuit. This terminal is not used when the AMPS-24 is connected to a panel or DS-DB via the EIA-485
connection.
TB4 - TBL BUS
Trouble bus input is designed to receive trouble signals from any normally open dry contacts or open collector circuit.
J3 - USB
USB Type B connector for Power Supply configuration using a PC.
CPS-24 (front board)
TB1 - AC
Primary AC Power Source - 120 VAC, 50/60 Hz, 5A (AMPS-24E uses 220-240 VAC, 50/60 Hz, 2.5 A) from line voltage source.
TB2 - Accessories Output
Power-limited (Class 2); 24V @ 0.5A, 5V @ 0.15A.
TB3 - Secondary Output Source (Batteries)
24VDC from batteries installed in the appropriate enclosure. Secondary (battery) power is required to support the system during loss of
primary power.
TB1
+24V COM +485 - 485 COM +24V
MAIN 24V
+24V
COM
COM
+24V
TB1
+24V COM +485 - 485 COM +24V
MAIN 24V
Figure 2.12 is a block diagram representing an application where an AMPS-24 is used as a general purpose remote power supply and
battery charger.
AC power Non-charging
device such as
SLC DAA-75 or AA-
ONYX Series amplifier
Panel
24 VDC
General
AMPS-
AC power Purpose
Power
Battery Battery
+24V
COM
COM
+24V
TB3
+24V COM COM +24V
AUX 24V
NOTE: Do not connect the AMPS-24 to the SLC if the AMPS-24 is communicating via 485 trouble reporting. (Refer to
“Trouble Reporting” on page 32.)
See “SLC Addressing” on page 27.
SLC A SLC B
TB2
A+ A- B+ B-
SLC
5V — Red Wire
Certain system designs may require connecting two or four batteries to the power supply, connecting multiple power supplies to each
other, or connecting one set of batteries to multiple power supplies. Always use wire size 12-18 AWG (3.25 mm2– 0.75 mm2), and install
the power supply and the batteries in the appropriate enclosures, as described in Sections 2.4 and 2.5.
cps24_2batt.wmf
TB3
cps24_4Batt.wmf
TB3
NOTE: Use a ring terminal to attach two cables to one battery terminal.
To Batteries To Batteries
acps-610_MultiPS.wmf
AMPS-24 Compatible UL/ULC–Listed
Power Supply/Product
Figure 2.21 Connecting Multiple Power Supplies/Products with Common Bond Wire
Compatible AMPS24_MultiPS-BAT.wmf
UL/ULC–Listed
Power
Supply/Product
Internal Charger disabled
Compatible
UL/ULC–Listed AMPS-24
Power Internal Charger enabled
Supply/Product Refer to “Outputs Current Settings”
on page 31.
Internal Charger disabled
NOTE: The lowest base address for the AMPS-24 is 05. Do not use FACP addresses 00 through 04 for the AMPS-24.
For example:
Pointing the arrow at the 1 selects the “one” address decade, beginning at 10.
Pointing the arrow at the 12 selects the “twelve” address decade, beginning at 120.
rotarysw.CDR
Figure 3.1 below gives two examples of setting the base address with both rotary and slider switch settings.
5 5-9
acps610_sw31.wmf
acpsaddrot3.CDR
120 120-124
Connect a standard USB cable from the PC’s USB port to the AMPS-
24’s USB interface (J3). When the download is complete, the unit auto-
matically reboots and returns to normal operation.
AMPS24_USBa.
Select AMPS-24
from drop-down
menu.
In addition to creating and opening databases on the PC’s local drive, modifications may be made to any AMPS-24 that is directly con-
nected to the PC with the PK-PPS programming utility. When PK-PPS is open and the PC is connected via the USB to a power supply,
that power supply is represented by the icon in the left window. Click on this icon to see the power supply’s current configuration and
version information.
Right-clicking on the AMPS-24 icon provides three work options:
SAVE Select this option to save the power supply’s current configuration as a database file (*.pdb) on the PC’s local drive.
MODIFY Select this option to edit the power supply’s current configuration. When all changes are made, the new database will
overwrite the one in the AMPS-24. The new database can also be saved to the local drive.
DOWNLOAD Select this option to download a database, application, or bootloader file to the power supply. See Section 3.2.5.
PKPPS Label.bmp
Label
For greater ease of identification, you may create a label for each power supply. Labels may have a maximum of 40 characters.
PKPPS Charger.bmp
NOTE: The charger current option “1A CHARGE” is not approved for ULC applications.
PKPPS Interface.bmp
Figure 3.6 PK-PPS: Interface Type
Interface Type
Select the interface type.
SLC: This must be selected when the AMPS-24 is used as the power supply for a CPU2-3030 or as a remote power supply.
EIA-485: This must be selected when the AMPS-24 is used with an NCA-2.
PKPPS Trouble.bmp
Trouble Reporting
Select the trouble reporting option.
Five Point Monitoring: When the power supply is configured for Five Point Monitoring (trouble reporting over the SLC), the panel
will report a trouble message beginning at the base SLC address. This selection must be made if the power supply is being used to
power a CPU2-3030 or as a remote power supply. Reporting at the base address (“Monitor General”) includes current limit,
hardware failure, trouble bus active, and CPS communication trouble. Refer to “SLC Addressing” on page 27.
When the power supply is configured for Five Point Monitoring, the panel displays a specific trouble message for AC Fail, Battery,
Earth Fault, and Charger Fail addresses (See Table 3.1).
In CLIP mode, the labels for the “Base + x” addresses must be entered manually. In FlashScan mode, device labeling is automatic.
US AC Fail Delay time: Make a selection (0, 2 HOURS, 8 HOURS, or 16 HOURS) from the drop-down menu.
PK-PPS Summary.jpg
Summary
The Summary screen displays all of your previous selections and the resulting SLC address consumption. Review this summary
screen before downloading and ensure that the proper number of consecutive addresses are reserved. You may use the BACK button
to edit any of your selections. Click the FINISH button to save your changes to the database.
3.3.2 Display
When the power supply is configured for 485 Trouble Reporting, the NCA-2 displays a system trouble for each specific trouble message
for each AMPS-24.
NOTE: AMPS-24/E revisions previous to the AMPS-K2 revision do not have the extra monitor point for Charger Fault. When
replacing a previous revision AMPS-24 with an AMPS-K2 version, remember to program the monitor point.
AMPS-24 [ ] x [0.13]=
Accessories Output (TB2 on CPS-24).
Enter 0.5 A in all white boxes if TB2 is in
use. Leave blank if not in use.
Local Energy Municipal Box [ ]x [ ]=
Sum each column for totals Primary, Primary, Secondary,
non-alarm: alarm: non-alarm:
4.1.3 Calculating the Maximum Secondary Power Non-Fire Alarm Current Draw
Use the table below to determine the maximum current requirements of the secondary power source during non-fire alarm conditions.
The result obtained is the amount of current that the batteries must be able to supply to the fire alarm system. Use the result in Table 4.4
to determine the size of the batteries needed for the fire alarm system.
Results taken from the table below assume that, while in a non-fire alarm condition, batteries must feed the AMPS-24 (and any addi-
tional supplies) with the maximum rated power each supply can provide.
Alarm Current
Device Quantity Total Current/Type
(in amps)
Alarm Current, from Table 4.1, col 3 =
Additional Load [ ] X =
Sum Column for Secondary Non-Fire Alarm Load =
Table 4.2 Maximum Secondary Power Non-Fire Alarm Current Draw
4.1.4 Calculating the Maximum Secondary Power Fire Alarm Current Draw
Use the table below to determine the maximum current requirements of the secondary power source during fire alarm conditions. The
result obtained is the amount of current that the batteries must be able to supply to the fire alarm system. Use the result in Table 4.4 to
determine the size of the batteries needed for the fire alarm system.
Results taken from the table below assume that, while in a fire alarm condition, batteries must feed the AMPS-24 (and any additional
supplies) with the maximum rated power each supply can provide.
Alarm Current
Device Quantity Total Current/Type
(in amps)
Alarm Current, from Table 4.1, col 2 =
Additional Load [ ] X =
Sum Column for Secondary Fire Alarm Load =
Table 4.3 Maximum Secondary Power Fire Alarm Current Draw
________________
________________ X = _________AH
Sum Column for Total Secondary Amp Hours calculated = _________AH
Multiply by the derating factor x 1.2 (See Note 7) = _________AH
Battery Size – Total Secondary Amp Hours Required = __________AH
3. Batteries installed in a system powered by an automatic starting engine generator need to provide at least 4 hours of standby power.
4. Factory Mutual requires 90 hours of standby for deluge-preaction systems.
5. Emergency voice/alarm communications systems require 2 hours of operation in the alarm condition. Due to the sporadic nature of
voice operation, however, NFPA 72 permits 15 minutes of operation at a maximum connected load to equal 2 hours of normal use.
6. If the total exceeds 200 AH, an Uninterruptable Power Supply with sufficient amp-hour capacity is needed. The Uninterruptable
Power Supply must be UL-listed for Fire-Protective Signaling.
7. The following battery derating factors must be used for Canadian installations using an AMPS-24 charger:
• For 7 AH capacity, use derating factor of 1.1
• For 12 AH capacity, use derating factor of 1.2
• For 26 AH capacity, use derating factor of 1.2
• For 55 AH capacity, use derating factor of 1.8
• For 100 – 200 AH capacity, use derating factor of 2.5
4.2.2 Calculating the Battery Size
Use this table to choose the battery size, in amp-hours, needed to support the fire alarm system. The AMPS-24 can charge batteries from
7 to 200 AH. Select batteries that meet or exceed the Total Amp-Hours calculated in Table 4.4 and that are within the acceptable battery
charger range. Write the amp-hours requirements on the Protected Premises label.
Voltage Number Required Our Part Backbox†
Battery Size
Rating Number* (Order Part Number)
7 AH 12 volts two BAT-1270 CABS-PS1, SBB-A4, SBB-B4,
SBB-C4, SBB-D4, EQBB-B4,
EQBB-C4, EQBB-D4, BB-25
12 AH 12 volts two BAT-12120 CABS-PS1, SBB-A4, SBB-B4,
SBB-C4, SBB-D4, EQBB-B4,
EQBB-C4, EQBB-D4, BB-25
26 AH 12 volts two BAT-12260 SBB-A4, SBB-B4,
SBB-C4, SBB-D4, EQBB-B4,
EQBB-C4, EQBB-D4, BB-25
55 AH 12 volts two for 55 AH BAT-12550 BB-55, NFS-LBB
four for 110 AH BB-100
100 AH 12 volts two for 100 AH BAT-121000 BB-100
four for 200 AH BB-200
NOTE: Battery size is limited to 7 AH minimum and 200 AH maximum using the internal AMPS-24 battery charger.
[ ]x
AMPS-24
[0.13]=
Accessories Output (TB2 on CPS-24).
Enter 0.5 A in all white boxes if TB2 is in use. Leave blank if not in
use.
[ ]x [
Local Energy Municipal Box
]=
Sum each column for totals Primary, Primary, Secondary
non-alarm: alarm: , non-
alarm:
Warn-HL-08-2009.fm