GOVERNMENT OF INDIA
MINISTRY OF RAILWAYS
lR;eso t;rs
TECHNICAL SPECIFICATION
FOR
MANUFACTURE AND SUPPLY OF
SINGLE / MULTICORE 11 kV / 33 kV GRADE
XLPE INSULATED AND PVC SHEATHED
ARMOURED /UNARMOURED
POWER CABLES FOR ELECTRIC SUPPLY PURPOSES
IN INDIAN RAILWAYS
Specification No. RDSO/2009/EM/SPEC/0002, Rev. ‘1’
(January - 2010)
ISSUED BY
ELECTRICAL DIRECTORATE
RESEARCH DESIGNS & STANDARDS ORGANIZATION
MANAK NAGAR, LUCKNOW - 226 011
vuqeksfnr
Approved by
dk;Zdkjh funs’kd@bZ-,e-
Executive Director (EM)
Page 2 of 17 Effective From Jan. 2010 Specification No. RDSO/2009/EM/SPEC/0002, Rev. ‘1’
INDEX
0.0 Foreword 3
1.0 General 3
2.0 Scope 4
4.0 Standards 5
7.0 Drawings 15
9.0 Warranty 17
0.0 FOREWORD
1.0 GENERAL
1.3 Railways/RDSO shall witness the type tests on the first order to be
carried out by the successful tenderer. The purchaser reserves the
right to witness the entire type test or any of the type tests as
considered necessary.
1.4 Unless brought out clearly, the offer/tender shall be deemed to
conform to this specification scrupulously. All deviations from this
specification shall be brought out in the schedule of deviations. Any
Page 4 of 17 Effective From Jan. 2010 Specification No. RDSO/2009/EM/SPEC/0002, Rev. ‘1’
1.6 The tenderer shall bring out clearly any additional feature which he
deems fit to include to give a complete and comprehensive offer. He
shall, however, explain reasons for offering such additional
features/items in his proposal.
2.0 SCOPE
Wind speed High wind speed in certain areas, with wind pressure
reaching 150kg/m²
4.0 STANDARDS
The XLPE cable shall conform to the following Indian Standards as
amended/revised till date unless stated otherwise, as applicable:
5.2 CABLE
5.2.2 The cable shall be suitable for laying in an area likely to be flooded by
water and shall be designed to be protected against rodent and termite
attack.
5.2.5 STORAGE
(i) Cable drums should be stored on dry hard and solid concrete
surface.
(ii) Sufficient space should be in between the drums for air
circulation.
5.3 CONDUCTOR
The tenderer shall quote for single/multi- core XLPE cable with plain
copper/Aluminum conductors which shall comply with the
requirement specified in IS: 8130-1984.
In three core cables, the cores shall be laid together with a suitable
right hand lay. The interstices shall be filled with non hygroscopic
material.
5.6 INSULATION
a) Treatment :
Temperature 135 ± 3º C
Duration 168 hrs.
b) Variation from corresponding values before ageing:
v) Shrinkage
a) Treatment: Temperature 130 ± 3º C
Duration 1 hour
b) Shrinkage 4% max
vi) Water absorption (gravimetric):
a] Treatment Temperature 85 ± 2º C
Duration 14 days
b] Water absorbed 1 mg/cm2, max
vii] Volume Resistivity:
a] at 27 º C 1x1014 ohm-cm, min
b] at 90 º C 1x1012 ohm-cm, min
5.6.1 The insulation compound shall be of high quality. It shall also be heat,
moisture, ozone and corona resistant.
XLPE compound should be of following makes:
a. Borealis, Sweden
b. NUC, Japan
5.6.2 The Insulation shall be applied by extrusion and vulcanized using dry
curing process to form a compact homogenous body free from micro
voids and contaminants.
5.6.3 Thickness of the insulation and its tolerance shall be as per Clauses
11.2 & 11.3 of IS: 7098- Part- II, 1985.
compatible with the temperature ratings of the cable and shall have
no deleterious affect on any other component of the cable.
5.8.3 In case of single core cables where there are both metallic
screening & armouring, there shall be extruded inner sheath
between them.
5.9 ARMOURING
5.9.5 The round steel wire/formed wires taken from the cable shall
meet the following requirements:
a. The tensile strength of round steel wire/formed steel wire
shall be not less than 250 N/mm2 and not more than 580
N/mm2
b. The elongation at break of round steel wire/formed steel
wire shall be not less than 6 percent.
c. Round steel wire shall meet the requirements of torsion
test. The gauge length between Vices and the minimum
number of turns without break shall be as per Table 6 of
IS: 3975 : 1999.
d. The zinc coating shall not show any cracks and shall not
flake off on rubbing by the bare finger when the formed
wire is subjected to winding test.
Page 10 of 17 Effective From Jan. 2010 Specification No. RDSO/2009/EM/SPEC/0002, Rev. ‘1’
6.1.2 Only after all the designs and drawings have been approved and
clearance given to this effect by RDSO, the manufacturer shall take up
manufacture of the prototype for inspection/testing by RDSO. It is to
be clearly understood that any changes to be done on the prototype as
required by RDSO, the same shall be done expeditiously.
6.1.3 Prior to giving a call for inspection and testing of the prototype, the
successful tenderer/manufacturer shall submit a detailed test
schedule consisting of test procedures, schematic circuit diagrams,
items/parameters to be checked and values required as per
specification for each of the tests and the number of days required to
complete all the tests at one stretch. The schedule shall also indicate
the venue of each of the tests. Once the schedule is approved, the
tests shall invariably be done accordingly. However, during the
process of type testing or even later, the DG/EM/RDSO, Lucknow,
reserves the right to conduct any additional test(s), besides those
specified herein, on any equipment/item so as to test the
equipment/item to his satisfaction or for gaining additional
information and knowledge.
6.1.5 The tests shall be conducted on the prototype of the cable at the works
of the manufacturer or at any NABL approved testing house or
laboratory in the presence of DG/EM/RDSO, Lucknow, or his
authorized representative. The prototype shall be complete in all
Page 12 of 17 Effective From Jan. 2010 Specification No. RDSO/2009/EM/SPEC/0002, Rev. ‘1’
6.1.9 Test certificates shall be completed with all the results. Purchaser’s
approval shall be obtained before dispatch of cables from the
works.
6.1.10 Manufacturer shall advise the purchaser one month in advance when
the cable shall be ready for inspection and tests, so that the latter’s
representatives may be deputed to witness the test(s). No material
shall be shipped or dispatched until inspection and tests upto the
satisfaction of the purchaser have been carried out. Such inspection
and approval shall not relieve the manufacturer from full
responsibility as defined in scope to the requirement of the
specification nor prejudice any claim, right or privilege which the
purchaser may have because of the use of defective or unsatisfactory
equipment.
6.2.0 TESTS
The tests shall be carried out as per the stipulations of IS: 7098
(Part II)-1985. The test plan shall be got approved by RDSO before
carrying out the test. Following tests shall be carried out on the cable
as a minimum:
Page 13 of 17 Effective From Jan. 2010 Specification No. RDSO/2009/EM/SPEC/0002, Rev. ‘1’
Clause 19.5
11. Impulse withstand test IS:7098 (Part-II) - - Part-47
Clause 19.6
12. High voltage test IS:7098 (Part-II) Part-45
Clause 19.7
13. Flammability test IS:7098 (Part-II) - - Part-53
Clause 19.7
14. Cold Impact test for outer IS: 5831-1984 - - Part- 21
sheath
NOTE :
1. Test Sl. Nos. 6, 7, 8, 10 and 11 are applicable only to screened
cables. It shall be permissible to carry out test 8 on different
sample.
2. If the test sample fails in high voltage test, one more test sample
shall be taken for a high voltage test preceded by bending test
followed by partial discharge test and heat cycle test followed by
partial discharge test.
3. The type test certificate approved by RDSO shall be valid for five
years. The type test may also be repeated within this five years
period if any change introduced in cable material or design.
4. If the test sample fails in high voltage test, one more test sample
shall be taken for a high voltage test preceded by bending test
followed by partial discharge test and heat cycle test followed by
partial discharge test.
7.0 DRAWINGS:
Page 15 of 17 Effective From Jan. 2010 Specification No. RDSO/2009/EM/SPEC/0002, Rev. ‘1’
8.2 The cut ends of the cable shall be sealed by means of non-hygroscopic
sealing materials so as to protect the cable from outside moisture
during transit and laying.
8.4 All wooden component of the drum shall be constructed from wood,
properly seasoned, sound and free from defects. Wood preservative
treatment shall be applied to the entire drum.
8.5 Drums or parts of drums made from ferrous metals shall be treated
with a suitable rust-preventive finish or coating to minimize rusting
during transit or storage.
8.6 Bolts, screws, nails etc. if used in the construction of drums shall be
counter sunk so that the heads are below the surface of the flange.
Page 16 of 17 Effective From Jan. 2010 Specification No. RDSO/2009/EM/SPEC/0002, Rev. ‘1’
8.7 The tenderer shall clearly indicate in the offer, the normal length of
cable in one drum. Normal single length should not be less than 500
meters per drum. Lesser length preferably not less than 40% of the
normal drum length as per site conditions shall also be accepted
subject to the approval of purchaser.
9.0 WARRANTY:
The cables and joints & termination must be guaranteed for
satisfactory operation for a period of 60 months from the date of
commissioning.
S. No. Description
1.0 Type of Cable
2.0 Conforming Standard
3.0 Rated voltage
4.0 Conductor
4.1 Nominal cross-sectional area of conductor
4.2 Conductor Material to IS:8130/84
4.3 Shape of conductor
4.4 DC resistance of the conductor at 20C (ohm per Km)
4.5 Maximum D.C. resistance of conductor at 90° C (ohm
per Km)
5.0 Conductor screen
a) Material
b) Minimum thickness in mm
6.0 Insulation
a) Material
Page 17 of 17 Effective From Jan. 2010 Specification No. RDSO/2009/EM/SPEC/0002, Rev. ‘1’
S. No. Description
b) Nominal thickness in mm
7.0 Insulation screen
a) Material
b) Minimum thickness in mm
8.0 Inner Sheath
a) Material
b) Minimum thickness in mm
9.0 Armouring
a) Material
b) Nominal dimension of wires / strips in
mm
10.0 Outer Sheath
a) Material to IS:5831/1984
b) Minimum thickness of outer sheath in mm
11.0 Nominal overall diameter of completed cable.
12.0 Nominal weight per meter of complete Cable.
(Single/multi core)
13.0 Standard drum length with tolerance in (meters)
14.0 Minimum permissible bending radius
15,0 Short circuit current carrying capacity of cable for one
second duration (KA)
16.0 Recommended continuous current ratings under
STD IS conditions:
16.1 In ground, at 30C ground temperature (Amps.)
16.2 In duct, at 30C ground temperature (Amps.)
16.3 In air, at 40C ambient temperature (Amps.)
17.0 Approximate reactance at 50 Hz (ohm per km)
18.0 Approximate impedance at 50 Hz (ohm per km)
19.0 Approximate capacitance at 50 Hz (micro farad per
km)