The document describes the characteristics of different types of voltage transformers for 24 kV. It provides a synthesis table that lists the functional units each transformer type belongs to. It then provides more detailed specifications for several transformer types, including their rated voltage, primary and secondary voltages, thermal power, accuracy class, and rated output.
The document describes the characteristics of different types of voltage transformers for 24 kV. It provides a synthesis table that lists the functional units each transformer type belongs to. It then provides more detailed specifications for several transformer types, including their rated voltage, primary and secondary voltages, thermal power, accuracy class, and rated output.
The document describes the characteristics of different types of voltage transformers for 24 kV. It provides a synthesis table that lists the functional units each transformer type belongs to. It then provides more detailed specifications for several transformer types, including their rated voltage, primary and secondary voltages, thermal power, accuracy class, and rated output.
Units CM CVM DM1-A DM1-D DM1-W DM2 GBC-A GBC-B DMVL-A DMV-A DMV-D CM2 TM VTs DMVL-D VRQ2-n/S1 b b b b b b b b VRFR-n/S1 b b b VRC2/S1 b b b VRM3-n/S2 b b VCT24 b VRC1/S1 b
Transformer VRQ2-n/S1 (phase-to-earth) 50 or 60 Hz
b characteristics according to IEC standard 60044-2. 61045N
Rated voltage (kV) 24
Primary voltage (kV) 10/3 15/3 15-20/3 20/3 Secondary voltage (V) 100/3 Thermal power (VA) 250 Accuracy class 0.5 Rated output for 30 30 30 single primary winding (VA) Rated output for 30-50 double primary winding (VA)
Transformer VRFR-n/S1 (phase-to-earth) 50 or 60 Hz
b characteristics according to IEC standard 60044-2. Rated voltage (kV) 17.5 Primary voltage (kV) 10/3 15/3 Secondary voltage (V) 100/3 Thermal power (VA) 250 Accuracy class 0.5 Rated output for 30 single primary winding (VA)
Transformer VRC2/S1 (phase-to-phase) 50 or 60 Hz
b characteristics according to IEC standard 60044-2. 61046N
Rated voltage (kV) 24
Primary voltage (kV) 10 15 20 Secondary voltage (V) 100 Thermal power (VA) 500 Accuracy class 0.5 Rated output for 50 single primary winding (VA)
Transformer VRM3-n/S2 (phase-to-earth and protected by fuses 0.3 A) 50 or 60 Hz
b characteristics according to IEC standard 60044-2. PE55648
Rated voltage (kV) 12 17.5 24
Primary voltage (kV) 10/3 15/3 20/3 Secondary voltage (V) 100/3 - 100/3 First secondary Thermal power (VA) 200 Accuracy class 0.5 Rated output for single primary (VA) 30-50 Second secondary Thermal power (VA) 100 Accuracy class 3P Rated output 50