Professional Documents
Culture Documents
CSWIP 3.1 Course (2017) - Compressed-471-476
CSWIP 3.1 Course (2017) - Compressed-471-476
CSWIP 3.1 Course (2017) - Compressed-471-476
Calibration
22 Calibration
22.1 Introduction
BS EN 50504 - Code of practice for validation of arc welding equipment, is a
standard that gives guidance to:
22.2 Terminology
BS EN 50504 defines the terms it uses, such as:
When considering welding equipment, those with output meters for welding
parameters (current, voltage, travel speed, etc) can be calibrated by checking
the meter reading with a more accurate measuring device and adjusting the
readings appropriately.
Equipment that does not have output meters (some power sources for MMA,
MIG/MAG) cannot be calibrated but can be validated to see the controls are
functioning properly.
WIS5-90516b
Calibration 22-1 Copyright © TWI Ltd
22.4 Instruments for calibration
Instruments used for calibration should:
For the main welding parameters, recommendations from the Standard are as
follows:
Current
Details are given about the instrumentation requirements and how to measure
pulsed current but there are requirements given, specified, or recommendations
made, about where in the circuit current measurements should be made.
The implication is that current can be measured at any position in the circuit –
the value should be the same.
Voltage
The standard emphasises that for processes where voltage is pre-set (on
constant voltage the power sources) the connection points used for the voltage
meter incorporated into the power source may differ from the arc voltage,
which is the important parameter.
This is illustrated by Figure 22.1 which shows the power source voltage meter
connected across points 1 and 7.
WIS5-90516b
Calibration 22-2 Copyright © TWI Ltd
Power
source
2 3
77 1 Wire
feeder
4
Arc voltage
{ 5
5
6
6
However because there will be some voltage drops in sections 1-2, 3-4 and 6-7
due to connection points introducing extra resistance into the circuit, the
voltage meter reading on the power source will tend to give a higher reading
than the true arc voltage.
Even if the power source voltage meter is connected across points 3 and 7
(which it may be) the meter reading would not take account of any significant
voltage drops in the return cable, section 6-7.
WIS5-90516b
Calibration 22-3 Copyright © TWI Ltd
The magnitude of any voltage drops in the welding circuit will depend on cable
diameter, length and temperature and the Standard emphasises the following:
It is desirable to measure the true arc voltage between points 4-5 but for
some welding processes it is not practical to measure arc voltage so close to
the arc.
For MMA it is possible to take a voltage reading relatively close to the arc by
connecting one terminal of the voltmeter through the cable sheath as close
as ~2m from the arc and connect the other terminal to the workpiece (or to
earth).
For MIG/MAG the nearest practical connection points have to be 3-5 but a
change from an air to a water-cooled torch or vice versa may have a
significant effect on the measured voltage.
Voltage drops between points 5-6 will be insignificant if there is a good
connection of the return cable at point 6.
The Standard gives guidance about minimising any drop in line voltage by
ensuring that the:
The Standard gives data for line voltage drops (DC voltage) according to
current, cable cross-section and length (for both copper and aluminium cables).
Travel speed
Welding manipulators, such as rotators and robotic manipulators, as well as the
more conventional linear travel carriages, influence heat input and other
properties of a weld and should be checked at intervals. Most of the standard
devices can be checked using a stopwatch and measuring rule but more
sophisticated equipment, such as a tacho-generator, may be appropriate.
WIS5-90516b
Calibration 22-4 Copyright © TWI Ltd