Professional Documents
Culture Documents
CFVV - VFVV For Transformer PDF
CFVV - VFVV For Transformer PDF
*
Corresponding Author: Tatjana Šimović, Zagreb 10000, Croatia, +385989889304, Email: tatjana.simovic@siemens.com
www.astesj.com 1
T. Šimović et al. / Advances in Science, Technology and Engineering Systems Journal Vol. 4, No. 1, 01-07 (2019)
This means that for the DETC to operate, the transformer must be makes sense to standardize and automate the regulation unit
disconnected from the network for a short period of time. Due to selection process, which was the main motivation for this work.
the mentioned limitations, the DETC is used only when the
The introduction of OLTCs improved the operating efficiency
regulation capabilities are not a primary concern. This is why an
of electrical systems considerably and this technique found
OLTC regulation unit is more and more becoming a standard
acceptance worldwide. In general the percentage of transformers
customer request for power transformer regulation.
equipped with OLTCs is increasing with the increase of the load
density and interconnection of electrical networks. In addition,
OLTCs applied in industrial process transformers as regulating
units in the chemical and metallurgical industry is another
important field of application [6].
Basic connection diagrams for regulation are typically chosen
with regard to system conditions and size/weight limits during
transportation.
Linear regulation (Figure 2) is applied for a simple design
transformer and regulation unit, with regulating range up to 20
percent of nominal voltage. The taps are added or substracted in
the series with the main winding. This kind of regulation ensures
smallest ohmic losses.
www.astesj.com 2
T. Šimović et al. / Advances in Science, Technology and Engineering Systems Journal Vol. 4, No. 1, 01-07 (2019)
using the rated power as the product of current and voltage (one or
three-phase).
Coarse change over selector or coarse/fine switching requires For a three-phase autotransformer with regulation in neutral
more complicated winding layout – it is regulation with two end, variable induction (variable flux voltage variation, VFVV),.
windings, regulated winding and coarse winding insertion (Figure Sn=const., the rated through current depends on both regulated and
4). Arrangement of coarse/fine selector has the electrical length of non-regulated voltage levels:
the fine tap winding plus one step. This kind of regulation offers
the lower copper losses in the tap position with the mínimum
number of effective turns. Coarse/fine regulation offers for some
industrial applications possibility of large number of operations where:
using special design with up to 5 coarse taps (107 operations i.e.
operating positions) [7]. U1 is the rated line voltage of the non-regulated side in kV
U2min is the rated line voltage in the minimum tap position in kV
In case of one-phase transformer, the rated through current is
multiplied by a factor of 3 since the rated power is per phase and
the rated voltages are phase voltages.
Maximum rated through current is the current which the
regulation unit is transferring from one tap to the other at relevant
step voltage.
Step voltage Ustep [V] is the phase voltage between the taps
which depends on the required regulated voltage range and the
Figure 4: Basic connection diagram with coarse tap selector required number of positions. This value is constant in case of
CFVV (constant flux voltage variation), unlike in the case of
Regulation with coarse fine change over selector across tap
VFVV (variable flux voltage variation) where different regulating
winding:
positions have different volt/turn ratio and therefore different step
voltage values:
Voltage across coarse tap winding UCV=UTV
where:
where:
UTV is voltage across tap winding in kV;
U1max and U1min are the required maximum and minimum
UR is regulating range phase to phase in kV; regulated line voltage in [kV] (equivalent three-phase bank line
voltage in case of a single-phase transformer);
UCV is voltage across coarse winding in kV;
n is the required number of regulating positions (including the
m is number of steps of tap winding
rated position);
3. Manual Selection and Calculations
Uk-Uk-1 is the (phase) voltage difference in [V] in the regulating
The selection of appropriate OLTC should be made very position k and k-1 (for positions k = 2 to n).
carefully, because the OLTC is an important factor with respect to The required regulation unit external insulation level depends
the transformer's reliability and cost. Each type of regulation unit on the insulation level to ground of the side where the regulation
is available in a number of variants, with different values of unit is connected. The withstand voltages of the external insulation
maximum rated through-current, number of phases, highest are standardized by international standards and correspond to the
insulation level, tap selector size and basic connection diagrams. highest voltage for equipment [8]. In case of regulation in neutral
Therefore, the type designation of a regulation unit depends on end (common for full transformer or VFVV autotransformer), the
these features. A guideline for the OLTC selection is given in IEC insulation level is usually the same as the insulation level of the
60542, but some special applications as HVDC transformers or transformer neutral (unless otherwise specified). In case of
phase shifters are not described in detail. regulation in line (common for CFVV autotransformers), the
When selecting the appropriate type of OLTC or DETC insulation level is the same as the lower voltage side to which the
manually, a number of parameters and technical limits have to be regulation unit is connected. The insulation level has to be checked
considered. against the applicable technical guide.
First of all, the rated through current of the regulation unit must The internal insulation level affects the regulation unit tap
not be less than the transformer highest current value of the selector size, whose price can vary significantly, meaning that the
regulating winding. For regulation at the neutral end with constant proper selection is of the essence in choosing the optimal
induction (constant flux voltage variation, CFVV), the rated regulation unit. Highest operating voltage across the regulating
through current in case of a three-phase full transformer is derived winding is the value that has to be compared with the highest
www.astesj.com 3
T. Šimović et al. / Advances in Science, Technology and Engineering Systems Journal Vol. 4, No. 1, 01-07 (2019)
permissible phase service voltage across the regulating winding number of positions may also increase the voltage stress of the
described in the technical guide, which defines several internal regulating winding, so this has to be taken into consideration (as
insulation distances to be checked, most important of which are described in the internal voltage calculations above). For rectifier
distances 'a' and 'b'. For insulating distance 'a' between start and or furnace transformers, wide tapping range should be considered.
end of the regulating winding and insulating distance 'b' between The predicted contact life of fixed and moving contacts is a
the fine tap selector contacts of different phases, a statistics-based function of the rated through current and has to be compared with
estimation is used. The logic behind the estimation is assuming the diagram for a specific regulation unit which can generally be
linear distribution, and additionally applying a „non-linearity“ found in the regulation unit manufacturer's technical guide.
factor depending on the regulation concept (reg.in main / coarse-
fine / reversing / linear) and transformer type (full / auto). The The recovery voltage occurs on the open change-over selector
mentioned factor is determined using statistical analysis derived contacts during switching sequence. It depends on the geometric
from experimental data. The differences in factors arise from the winding arrangement and the capacitances C1 and C2. Recovery
specifics of the distribution of electrical field in various power voltage can cause switching sparks or low-energy arcs, thereby
transformer types. producing unwanted gas which has a negative effect on the
characteristics of the insulation media (usually insulating oil). The
With some winding arrangements (neutral-end in autotransformers recovery voltage and breaking current values have to be checked
and line-end regulation in delta connected windings), very high in + and – selector switch positions:
voltages may occur. These voltages are significantly influenced by
the choice of the regulation concept (linear, coarse fine or
reversing regulation). In such cases, additional tools are used to
determine the electrical field distribution in the power transformer
(FEM analysis). Since the tap selector size price varies
significantly, this can also be subject to optimization.
The switching capacity PStN [kVA] determines the capability of the
regulation unit to switch between regulation steps. Since the worst
case has to be considered, the required switching capacity in the The breaking current IS+ and IS-:
regulation unit is the product of the relevant step voltage and
maximum rated through current (both described above):
The required switching capacity for a specific contact in an OLTC
is based on the relevant step voltage and current but is also
determined by the design and circuit of the OLTC. The switching
capacity itself is primarily a function of the contact design, contact
speed and arc-quenching agent [9].
The selected regulation unit must be within the switching UW+ and UW- are the recovery voltages in [kV];
capacity diagram (example in Figure 5). Limit values are given in IS+ and IS- are breaking currents in [mA];
the manufacturer's technical guide and may rectrict certain types
of tap changers in some cases. C1 and C2 are the capacitance values in [pF] of the regulating
winding (as shown in Figure 6) which can be approximated
assuming cylindrical winding system [10].
U1 is the rated regulated voltage in [kV];
Uf is the preselector voltage in [kV];
ω=2πf, where f is the power frequency in [Hz].
Example for recovery voltage calculation for single phase
autotransformer with regulation of common winding (Figure 7) in
wye connection (fine regulation), input data:
Rated power: 200MVA
Rated voltages and relevant tapping range: 400 / 230
+10 x 1,5%, -10 x 1,5% / 24 kV
Step voltage: 1992 V
Max. tapping current: 1772 A
Figure 5: Step capacities diagram
Test Voltages:
The number of tap positions and the number of contacts have a...340 kV (1,2/50μs); 65 kV (50 Hz)
to be considered as well - different types have different maximum Um... 950 kV (1,2/50μs); 395 kV (50 Hz)
regulation range, depending on the regulation concept. A higher
www.astesj.com 4
T. Šimović et al. / Advances in Science, Technology and Engineering Systems Journal Vol. 4, No. 1, 01-07 (2019)
select a different tap selector. The installation of the tie-in
resistors affects the regulation unit price as well as overall
transformer dimensions, so a solution with bigger tap selector size
and therefore higher permisible values of recovery voltage should
be considered in such cases. Furthermore, the tie-in resistor
dimensions are defined by the regulation unit manufacturer
specifically for each design, which can cause an additional
unwanted time delay in the transformer final design process. For
phase shifting transformers, using regulation unit with two-way
change-over selector, one can overcome problems during the
change-over selector operation and change of winding
connections between phases of the system voltage [11].
4. Tap Changer Selection Application and Database
Due to the complexity of the regulation unit technical limits
and cross-dependencies between different types, a relational
database is developed in such an architecture that an algorithm can
quickly go though all of the possible permutations and compare the
actual calculated values with every combination of regulation
Figure 6: Recovery voltage – capacitances per phase unit's limits. Also, the database management user interface (UI) is
developed in MS Access environment. Within the database, SQL
is used for querying data and sending it to the application for
further analysis in the TCS algorithm (Tap Changer Selection).
The algorithm then compares the queried data with the calculation
results which are calculated in the background as thoroughly
described in chapter III. The algorithm also takes into account
different possibilities of transformer regulation: for example, a
three phase transformer can either be regulated with a single three-
phase regulation unit or three single-phase regulation units.
Furthermore, autotransformer can be designed with regulation in
main winding, meaning that the regulation unit does not have a
common neutral end. Therefore, autotransformers with such
regulation can only be regulated with three single-phase regulation
units (three-phase regulation unit requires a neutral end common
Figure 7: Autotransformer winding arrangement wye connection
point). Also, different regulation concepts have different
According to input data (capacitances C1=4696pF and possibilities for number of positions and number of contacts.
C2=3366pF), following recovery voltages and breaking current All of the mentioned above is automatically checked for every
are calculated: single regulation unit combination queried from the database. This
UW+=8,3kV; UW-=28,2kV is achieved using a foreach loop which (in each step) calls for
IS+=21mA; IS-=71,3mA different modules used for this purpose. All of the modules and
functions are developed in C#, following object-oriented software
According to Figure 8., the potential measure is not needed. development principles (Model-View-Controller, MVC pattern).
The input for the algorithm that is expected from the application
user is the same data that the electrical designer uses in power
transformer design (MVA rating, rated voltages and required
regulation range, regulation concept, connection of regulating
winding, LI and AC voltage levels i.e. external insulation levels to
ground and number of tap positions), making the application very
user-friendly for any power transformer designer. This data model
also makes automatic data import from transformer design
software very simple. The algorithm output is the list of all the
possible solutions for regulation units (tap changers) that satisfy
the given input.
Figure 8: Recovery voltage and breaking current diagram
The results are finally sorted according to the expected total
The recovery voltage permisible value is the function of the cost, as shown in Figure 9. Therefore, the application user can
calculated breaking current value. The mentioned UW(IS) function simply choose the first regulation unit from the generated list
for each tap selector type and size can be found in the technical knowing that this is the optimal solution. Other regulation units
data of the regulation unit. If the calculated values of recovery from the list are not optimal but are also technically acceptable.
voltages are exceeded, it is necessary to install tie-in resistors or These can be selected in case of a specific request (e.g. higher
www.astesj.com 5
T. Šimović et al. / Advances in Science, Technology and Engineering Systems Journal Vol. 4, No. 1, 01-07 (2019)
external insulation level requested by the customer). Finally, a (depending on the regulation concept, linear distribution and
report containing all the calculations together with the technical nonlinear factor were applied) which are still acurate enough to
limits can be generated automatically. select an OLTC properly. There is room for expansion in the
application in order to better cover some special transformer's
designs, such as HVDC, limit cases or arrangement with enforced
current splitting. However, the results are already visible in the
offering phase, by reducing the time of OLTC selection up to 90%
compared to the manual selection. This means a lot of working
hours in the design office have been saved. Further improvements
are reflected in the pooling data from application database itself
and from the web application that is related to the OLTC and
motor drive unit equipment ordering data in one general database.
Figure 9: TCS results
www.astesj.com 7