EB 9519 EN: Translation of Original Instructions
EB 9519 EN: Translation of Original Instructions
EB 9519 EN: Translation of Original Instructions
These mounting and operating instructions assist you in mounting and operating the device
safely. The instructions are binding for handling SAMSON devices.
ÎÎ For the safe and proper use of these instructions, read them carefully and keep them for
later reference.
ÎÎ If you have any questions about these instructions, contact SAMSON‘s After-sales Service
Department (aftersalesservice@samson.de).
The mounting and operating instructions for the devices are included in
the scope of delivery. The latest documentation is available on our website
at www.samson.de > Service & Support > Downloads > Documentation.
! DANGER ! NOTICE
Hazardous situations which, if not avoided, Property damage message or malfunction
will result in death or serious injury
Note
! WARNING Additional information
Hazardous situations which, if not avoided,
could result in death or serious injury
Tip
Recommended action
2 EB 9519 EN
Contents
EB 9519 EN 3
Contents
8.2 Settings........................................................................................................32
8.3 Nameplate...................................................................................................35
9 Dial faces.....................................................................................................36
9.1 Attachable dial plates....................................................................................36
10 Dimensions..................................................................................................38
4 EB 9519 EN
Safety instructions and measures
EB 9519 EN 5
Safety instructions and measures
These versions are cleaned and assembled under special conditions. When replacing parts
that come into contact with gaseous oxygen, e.g. range springs, wear suitable gloves and
make sure that the parts do not come into contact with oil or grease.
When returning devices for oxygen service for repair, the sender assumes full responsibility
that the devices are handled to meet all requirements stipulated by VBG 62 or similar regula-
tions until they are handed over to the manufacturer. Otherwise, SAMSON does not accept
any responsibility.
6 EB 9519 EN
Safety instructions and measures
Referenced documentation
The following documents apply in addition to these mounting and operating instructions:
−− Mounting and operating instructions for mounted pipeline valves (strainers, shut-off
valves etc.)
EB 9519 EN 7
Safety instructions and measures
! DANGER
Operating the Media 5 Differential Pressure and Flow Meter in combination with the op-
tion module with 4 to 20 mA current output in potentially explosive atmospheres is not
permissible.
Impermissible use in potentially explosive atmospheres may lead to ignition of the atmo-
sphere and cause death, even with a harmless supply voltage.
ÎÎ Do not operate the Media 5 Differential Pressure and Flow Meter in combination
with the option module with 4 to 20 mA current output in hazardous areas.
These versions are cleaned and assembled under special conditions. When replac-
ing parts that come into contact with gaseous oxygen, e.g. range springs, wear suit-
able gloves and make sure that the parts do not come into contact with oil or
grease.
ÎÎ When returning devices for oxygen service for repair, the sender assumes full
responsibility that the devices are handled to meet all requirements stipulated by
VBG 62 or similar regulations until they are handed over to the manufacturer.
Otherwise, SAMSON does not accept any responsibility.
8 EB 9519 EN
Safety instructions and measures
! NOTICE
Risk of damage to the differential pressure and flow meter due to impermissible
negative pressure (vacuum) in the measuring chambers.
A negative pressure in the measuring chambers is not permissible during operation.
ÎÎ The following applies: operating pressure ≥ atmospheric pressure.
A vacuum in both measuring chambers for a brief period of time, e.g. to clean tanks,
is permissible.
EB 9519 EN 9
Design and principle of operation
10 EB 9519 EN
Design and principle of operation
2.4
Housing of indicating unit
2.3
2.2
3.1 2.1
Limit switch 3.2
(option)
A1 A2
1.9
1.1
1.8
Differential pressure cell 1.3 1.2
1.7
1.4 1.6
1.5
_ +
Differential pressure cell Limit switch (option) Current output (option)
1.1 dp cell 3.1 Metal tag 4.1 Status indication (green)
1.2 High-pressure chamber 3.2 Proximity switches A1/A2 4.2 Error indication (red)
1.3 Low-pressure chamber 4.3 Execute/confirm key
1.4 Range springs 4.4 Select function/data key
1.5 Measuring diaphragm
1.6 Diaphragm plates
1.7 Diaphragm stem
1.8 Lever
1.9 Flexible disk
4.1
Housing of indicating unit
2.1 Transmission element 4.2
(span adjuster)
2.2 Gear segment
2.3 Pointer mechanism
2.4 Dial plate
4.4 4.3
EB 9519 EN 11
Technical data
3 Technical data
Table 1: Technical data · All pressure in bar (gauge) · All errors and deviations are specified in % of
the adjusted measuring span
Media 5 Differential Pressure and Flow Meter
Measuring range in 0 to 0 to 0 to 0 to 0 to 0 to 0 to 0 to 0 to 0 to
mbar 60 100 160 250 400 600 1000 1600 2500 3600
Measuring min. 40 to 50 to 80 to 125 to 200 to 300 to 500 to 800 to 1250 to 1800 to
span in mbarmax. 66 110 176 275 440 660 1100 1760 2750 3960
Accuracy class ±4.0 % ±2.5 % ±1.6 %
Pressure rating PN 50, overloadable on one side up to 50 bar
Indicator Ø160 mm
Characteristic Reading linear to the differential pressure
Deviation from terminal-
<±2.5 % <±1.6 % including hysteresis
based linearity
Sensitivity <±0.5 % <±0.25 %
Effect of static pressure <0.03 %/1 bar
Degree of protection acc.
IP 54
to DIN EN 60529
Approx. 3 kg without valve block
Weight
Approx. 5 kg with valve block
Compliance
Limit switch (optional)
Max. 3 alarm contacts A1, A2 and A3 (limit switches) with inductive pick-up and LED
Version
according to EN 60947-5-6
Values corresponding to connected isolating switch amplifier acc. to EN 60947-5-6,
Control circuit
e.g. KFA6-SR2-Ex2.W
Proximity switch SJ3,5-N-LED, for hazardous areas according to PTB 99 ATEX 2219X
Switching accuracy <±2 %
Dead band, approx. <0.6 %
Current output (optional)
Version Magnetoresistive measuring system
Supply voltage UB 12 to 36 V (DC)
Output signal 4 to 20 mA, two-wire system
Perm. load RB in Ω RB = (UB – 12 V)/0.020 A (R ≤600 Ω at 24 V and 20 mA)
Power consumption 103 mW
Settings Zero calibration|Span calibration|Characteristic selection|Test function
12 EB 9519 EN
Technical data
Output and reading linear or square root extraction depending on installed flow
Characteristic characteristic
Characteristic set at the factory
Deviation from terminal-
<±0.2 %, related to 270° measuring span
based linearity
Sensitivity <±0.05 %, related to 270° measuring span
Effect of ambient
temperature in the range <0.1 %/10 K for zero and span
from –40 to +80 °C
Ambient conditions
Perm. ambient temperature range –40 to +80 °C
Perm. storage temperature range –40 to +100 °C
Use of Media 5 with gaseous oxygen
Max. oxygen pressure 50 bar
Perm. ambient temperature
–40 to +60 °C
range
Table 2: Materials
Media 5 Differential Pressure and Flow Meter
Version Standard version
dp cell CW617N (brass) CrNi steel
Measuring diaphragm and seals ECO 1)
Note
The standard version of the Media 5 Differential Pressure and Flow Meter can be used to
measure flammable gases and liquids in which hazardous area conditions of Zone 0 are to
be expected. The relevant regulations on the measurement of flammable gases and liquids of
Zone 0 must be observed.
Oxygen service: When the device is used for oxygen service, make sure that the dp cell and
any SAMSON accessories (e.g. valve block) only come into contact with gaseous oxygen.
EB 9519 EN 13
Installation
14 EB 9519 EN
Installation
H
h Y K
– + – + – +
1) 1) 1)
Separation chamber
Installation
Standard Reverse Standard Standard Reverse
1) SAMSON valve blocks can be mounted upside down to ensure the assignment of plus (+) to plus (+) and minus
(–) to minus (–) remains unchanged.
Fig. 2: Arrangement of devices
EB 9519 EN 15
Installation
4.5 Orifice flange (orifice plate during sizing as closely as possible. It is,
however, favorable to install equipment that
assembly) keep the operating state constant (e.g. pres-
The direction of flow must correspond to the sure regulators) upstream of the assembly.
arrow on the orifice plate. Unobstructed pipe
sections are required upstream and down- 4.5.1 Accessories
stream of the orifice plate assembly. For the
orifice tubes delivered by SAMSON, these We recommend installing a shut-off valve in
section are ensured by the weld-on calibra- the differential pressure lines as well as an
tion pipes. For orifice flanges, the unobstruct- equalizing valve. They can be used to shut
ed pipe section upstream of the orifice plate off both differential pressure lines and to by-
is specified in the order confirmation. Make pass the indicating unit when checking zero.
sure the orifice plate assembly as well as the
gaskets are properly aligned with the pipe-
line.
Do not install any control valves that con-
stantly change the operating state of the pro-
cess medium (e.g. manually operated control
valves or temperature regulators) upstream
of the orifice plate assembly. The operating
state must match the conditions calculated
! NOTICE
The maximum permissible operating pressure for Type 90
is 40 bar in the standard version.
Inlet 20 to 50 x d
Outlet 5 x d For gas For steam For liquids
Fig. 3: Orifice flange (orifice
plate assembly)
16 EB 9519 EN
Installation
1
Test connection Equalizing valve
1 Shut-off valves
Shut-off valve (+) 2 Equalizing valve
Shut-off valve (–) – +
Fig. 5: Arrangement of shut-off valves and
Pressure gauge connection equalizing valves for flow rate
Connection for
measuring lines measurement
Fig. 4: SAMSON valve block
EB 9519 EN 17
Installation
Tip
The screw fittings and SAMSON valve blocks
with their associated order numbers are list-
ed in Data Sheet u T 9555.
18 EB 9519 EN
Start-up
EB 9519 EN 19
Operation
20 EB 9519 EN
Operation
If this is not the case, readjust the zero screw Adjusting zero and checking the measuring
(see Fig. 6) until zero position is reached. range:
EB 9519 EN 21
Operation
Note
Be aware that the adjustment is performed
on a moving part and, therefore, do not ex-
ert any force to it. Do not apply any pressure
with the screwdriver in the axial direction. If
the spring is mispositioned while adjusting
the measuring range and is located on the
tag instead of the toothed segment, the
pointer goes beyond the 100 % scale range
and not to 0 % when there is an input pres-
sure of 0 mbar. In this case, reposition the
spring as shown in Fig. 7.
22 EB 9519 EN
Operation
! NOTICE
The test medium must free of oil and grease when the device is used to measure
oxygen.
Process medium: gaseous oxygen · Max. temperature: +60 °C, max. oxygen
pressure: 50 bar
When the device is used for oxygen service, make sure that the dp cell and any
SAMSON accessories only come into contact with gaseous oxygen.
– +
Test pres-
Supply air reducing station with oil sure
filter and test pressure gauge
Precision regulator with Class 0.1
pressure gauge
Pointer axis
Toothed segment
max. 60°
EB 9519 EN 23
Limit switch (optional)
LED1 LED2
LED1 LED2 LED3
41 42 51 52
41 42 51 52 45 46
+ – + –
A1 A2 + – + – + –
A1 A2 A3
Switching amplifier
Switching amplifier
acc. to EN 60947-5-6
acc. to EN 60947-5-6
Limit switch with two alarm contacts Limit switch with three alarm contacts
– Terminal assignment – – Terminal assignment –
Fig. 8: Terminal assignment
24 EB 9519 EN
Limit switch (optional)
7.2 Adjusting the alarm For a more accurate adjustment (test bench),
pressurize the measuring chamber to check
contacts if the alarm signal is released at the required
The alarm contacts A1, A2 and A3 can be scale value through the movement of the tag
shifted in the assigned adjustment ranges (check the LED of the proximity switch).
1.1 and 1.2 or 2.1 and 2.2 using a screw- If necessary, correct the position of the alarm
driver. contact accordingly.
Depending on the selected function as a
minimum or maximum contact, contact is
made when the tag moves into or out of the
proximity switch. See Overview of functions
for alarm contacts on page 26.
Alarm contact A2
LED
EB 9519 EN 25
Limit switch (optional)
Switching points
Min. contact with decreasing reading
Max. contact with increasing reading
26 EB 9519 EN
Limit switch (optional)
How to proceed:
Note
1. Unscrew the case cover.
Before mounting the contact unit, position the
2. Unscrew the two dial plate screws (2) alarm contacts A1 and A2 in such a way
and remove the cover plate. Retighten di- that one of them rests in the recess of the
al plate screws. metal tag and the other one to the side of the
tag.
1 PCB
2 Dial screws
3 Threaded holes
4 Capillary tube
5 Metal tag
6 Proximity switches
EB 9519 EN 27
4 to 20 mA current output (optional)
28 EB 9519 EN
4 to 20 mA current output (optional)
The angle of the pointer axis is measured by Installing the current output option module
the magnetoresistive measuring system and How to proceed:
converted into an electric signal.
Installing the printed circuit board, magneto-
To operate the unit, a transmitter supply volt- resistive measuring system and terminal
age of UB = 12 to 36 V is required for the 4 board
to 20 mA measuring circuit.
Dial screws
! WARNING
Use of the current output option module in
hazardous areas is not permissible.
Cover plate
8.1 Retrofitting
The retrofit kit (item no. 1402-1501) includes
the following parts: Housing screws
1 Printed circuit board with operating controls
Fig. 13: Standard version of Media 5 · Indicat-
2 Terminal board
ing unit with cover plate
3 Magnetoresistive measuring system with mating
plate
4 Self-adhesive dot on film 1. Undo the four housing screws. Remove
5 Cable gland the housing cover.
6 Nameplate (label)
2. Unscrew the two dial plate screws and
remove the cover plate. Retighten dial
4
plate screws.
3
3. Place the magnetoresistive measuring
1 system on the pointer.
5
Nameplate 6 Pointer axis before Pointer axis with self-
(label) attachment adhesive dot · Film pulled
off
EB 9519 EN 29
4 to 20 mA current output (optional)
Note
The mating plate must rest flat underneath
the pointer.
Pay particular attention to the counterweight
at the end of the pointer.
30 EB 9519 EN
4 to 20 mA current output (optional)
Connector
Three fastening
screws (Phillips 32–
32–
Z1)
31+ ~
31+
Fig. 17: Current output option module Fig. 19: Measuring signal connection in two-
Fastening screws wire system
EB 9519 EN 31
4 to 20 mA current output (optional)
Zero calibration
The electric zero is adapted to the mechani-
1 2
cal zero. As a result, a 4 mA signal is also
issued at Δp = 0 bar corresponding to the
pointer's zero point.
3 4
Zero can be calibrated in the scale range
between approx. –5° and 135° (see
Fig. 21: Current output option module · Operat- Fig. 22).
ing controls
Activate zero calibration level
32 EB 9519 EN
4 to 20 mA current output (optional)
Span calibration
The measuring span can be calibrated con-
tinuously without affecting zero or the mea-
suring accuracy (see Fig. 22). The pointer
135°
position corresponds to the end point with >95°
20 mA output signal.
As a result, the end points can easily be
adapted to the measured medium, especially
when attachable or multiple dial plates are 0° 270°
used.
≈ –5°
A measuring span calibration is possible in
the pointer range >95° (based on the point- Zero adjustment range
er's zero point, see Fig. 22). Span adjustment range
The red LED is permanently lit (error indica-
tion) if the calibration range is exceeded.
Fig. 22: Zero and span calibration ranges
Characteristic
Three characteristics are available.
−− Linear
−− Root-extracting
−− User-defined (factory
setting)
EB 9519 EN 33
4 to 20 mA current output (optional)
Blinking pattern
key Red
= 4 mA output.
Blinking pattern
key Red
= 20 mA output.
key Red Exit function.
Change to standard opera-
Green
tion
34 EB 9519 EN
4 to 20 mA current output (optional)
8.3 Nameplate
SAMSON 5005-0
4
Option module Output 4 ... 20 mA
Supply 12 ... 36 V DC
See technical data for ambient temperature 1 Firmware version
2 Model number
Firmware 1 3 Serial number
Model 2 4 QR code to go to
Serial no. 3 product
documentation
SAMSON AG Germany Made in Germany
Key technical data on the option module is written on the self-adhesive nameplate.
ÎÎ After installing the unit, stick the nameplate on the indicating unit (top view, left. See
photo).
The nameplate is already affixed when the device is delivered with the unit already installed.
EB 9519 EN 35
Dial faces
36 EB 9519 EN
Dial faces
Note
A cover plate (if mounted) must not be re-
moved.
For the version with limit switch or current
output, the contact unit must not be removed
as well.
EB 9519 EN 37
Dimensions
10 Dimensions
Ø191
297.5
2x G 3/8 ISO 228
31
60
38 EB 9519 EN
Dimensions
Ø168
5
147
200
Ø101
117
55
25
SW17
26
37 a
26 b
43
1 Valve block for upside down mounting
2 Mounting part
3 Vertical pipe
4 Clamp
5 Horizontal pipe
EB 9519 EN 39
Dimensions
Wall/panel mounting
Center of the
indicator unit
30
43.5
18
158.5
30
(M8 screws)
Panel mounting
+ 0.2
Ø180 – 0.3
Panel cut-out
30°
30°
Ø165 +5
40 EB 9519 EN
EB 9519 EN 41
42 EB 9519 EN
EB 9519 EN 43
EB 9519 EN
2019-10-25 · English
SAMSON AKTIENGESELLSCHAFT
Weismüllerstraße 3 · 60314 Frankfurt am Main, Germany
Phone: +49 69 4009-0 · Fax: +49 69 4009-1507
samson@samson.de · www.samson.de