Optimization of Air Conditioning System: D. Y. Patil College of Engg. & Tech., Kolhapur - Page 1 of 19

You might also like

Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 19

Optimization Of Air Conditioning System

ABSTRACT
Air conditioning is the largest source of energy consumption. The issue of global
warming has become a particular concern in the world of research. To reduce the
effects of global warming it has been developing of green building with the aim of
energy saving . We are finding cooling load in the room by considering the different
heat source and the number of occupancy. Energy cooling load is affected by
external and internal heat sources. External cooling load in this include convection
outdoor/exterior using the calculation of heat using Thermal Analysis Research
Program (TARP), and Conduction Transfer Function (CTF).[3] We use as the
reference the ASHRAE standard for building materials and the metabolic of
occupants while on the activity. The results show that the number of occupancies
have an influence of cooling load. A large number of occupancy will cause the
cooling load is great as well, also including study of nano particles which will be use
as the refrigerant which suitable for cooling environment. Nano refrigerant is
nothing but the combination of nano-particle with the refrigerant for the sake of
better refrigeration process. It has been observed that, as compared to alternative
refrigerant, there is better improvement in heat transfer capacity of the refrigerant
after addition of nanoparticles is this also research area. After the studying , we are
implementing the Air Conditioning process become more efficient and safe as
compare to previous in atmospheric prospective. By considering different coating
materials of glass & LED tube lights.

D. Y. Patil College of Engg. & Tech., Kolhapur.Page 1 of 19


Optimization Of Air Conditioning System

CHAPTER 1
INTRODUCTION
In present days the environmental problem is one of the most serious problems.
Energy consumption by industries and buildings are responsible for this problem.
About 72% of world energy is consumed by infrastructure, industry, commercial
buildings, residential houses, and markets. In a large building or complex, which is
air‐conditioned, about 60% of the total energy requirement in the building is
allocated for the air‐conditioning plant installed to use the cooling purpose. Exact
prediction of the cooling and heating load, proper sizing of the heat ventilation air-
conditioning (HVAC) system and optimal control of the HVAC systems are
important to minimize energy consumption. Root factors that affect cooling loads are
the external climates such as outdoor temperature, solar radiation and humidity.
Local climatic conditions are important parameters for the energy efficiency of
buildings. Because the energy consumption in buildings depends on the climatic
conditions and the performance of heating ventilating and air conditioning (HVAC)
systems changes with them as well, better design in building HVAC applications that
take account of the right climatic conditions will result in better comfort and more
energy efficient buildings. Calculation of thermal load of building is very essential to
find exact air-conditioning equipment and air handling unit, to achieve comfort
operation and good air distribution in the air-conditioned zone. This project Cooling
load estimation for an externally loaded Educational Institute Building is presented
by using CLTD method.

D. Y. Patil College of Engg. & Tech., Kolhapur.Page 2 of 19


Optimization Of Air Conditioning System

1.1 Importance of project


Ensuring that you install the right size air conditioner or complete HVAC system is
critical to providing consistent indoor comfort for you. It is also important to saving
energy which can be wasted by either a too large or too small system since energy
savings translate to monetary savings in today’s economy you simply can’t afford to
ignore system sizing when selecting your new HVAC equipment. The capacity of
your equipment needs to match the size of area being heated or cooled and it must
take other factors in consideration as well. If the system installed is too large it uses
unnecessary amount of energy simply because it takes a more amount of energy to
run a larger system. It wastes energy through ‘short-cycling’, turning itself on and off
repeatedly and running only for short time, it can create unnecessary noise as access
air moves through the duct work if the system is large. It creates more wear and tear
on the system thus it fails to remove sufficient humidity from the air since it doesn’t
run long enough to provide adequate humidity control. If too small system is
installed it runs continuously yet can sometimes fail to maintain the proper comfort
level especially during extreme weather. It might require a supplemental form of
heating or cooling to keep you comfortable. This rises cost and offset the savings
from the energy efficiency of the system because the system is switching on and off
too frequently. it can create unnecessary noise . It will require regular maintenance to
keep it running optimally and prevent breakdown since it will tend to be a bit over worked.
Cooling load calculations involve a systematic, stepwise procedure using which one can
arrive at the required system capacity by taking into account all the building energy flows.
Thus a system that is correctly matched to your heating or cooling requirements offers the
following advantages. It operates at optimal efficiency saving your money on energy cost. It
keeps your indoor temperature and overall comfort level more consistent. It provides proper
humidity control, increasing comfort and lowering the likely hood of mold or mildew
problems. It operates without excessive noise, according to its intended specification, rather
than over burdening the system and shortening its lifestyle

D. Y. Patil College of Engg. & Tech., Kolhapur.Page 3 of 19


Optimization Of Air Conditioning System

CHAPTER 2
LITERATURE REVIEW
1. Vikas Palliwal[2017] : explained Human comfortness is essential now a days
because of the improvement in life style and increasing atmospheric
temperature. Electrical air conditioning machines are not most suitable for
large buildings because of the higher power consumption and shorter
life. The effective design of central air conditioning can provide lower power
consumption, capital cost and improve aesthetics of a building.
2. Chairani [2017] : explained cooling load in the room by considering the different
heat source and the number of occupancy. Energy cooling load is affected by
external and internal heat sources. The internal cooling load is calculated based
on the activity of the occupants in the office, a number of occupants, heat gain
from lighting, and heat gain from electrics equipment.
3. K. T. Pawale[2017]: explained, It has been observed that, as compared to alternative
refrigerant, there is better improvement in heat transfer capacity of the refrigerant
after addition of nanoparticles. He obtained are found to have their improved
thermo-physical properties over the conventional refrigerants. Nano-particles can be
used along with refrigerant in order to improve the performance of vapour
compression refrigeration system.
4. S. A. Fadhilah[2014] : investigated thoroughly in many ways to reduce the energy
consumption. Hence, Nano refrigerant which is one kind of nanofluids has been
introduced as a superior properties refrigerant that increased the heat transfer rate in
the refrigeration system. Many types of materials could be used as the nanoparticles
to be suspended into the conventional refrigerants.
5. P. Dipika: studied in “Effect of Nanoparticles in Refrigeration System” to bring
out some of the important woks done in the field of Nano refrigerants as well as
Nano lubricants.
6. C.A. Balaras[1996]: explained that thermal mass can reduce peak cooling loads and
indoor air temperature swings in buildings. Experimental studies which demonstrate
the effectiveness of thermal mass as an energy conservation alternative and in
providing more comfortable indoor conditions, are also reviewed.

D. Y. Patil College of Engg. & Tech., Kolhapur.Page 4 of 19


Optimization Of Air Conditioning System

2.1 Problem Definition


Now a days increasing atmospheric temperature Electrical air conditioning
machines are not most suitable for large buildings because of the higher power
consumption and shorter life. Educational and research institutions also need
human comfortness, as the population of student community increase year
by year. The effective design of air conditioning can provide lower power
consumption, capital cost and which is based upon the calculating exact cooling
load . A survey say’s that use of the AC in many buildings, hotels, colleges etc. in
India which is on large scale in the sense of cooling environment. Thus,
development of exact capacity of air conditioning is best option to over-come these
problems.
2.2 Research findings / issues:
1. Cooling load is influenced by external factors and internal factors, also affected by
a number of occupancies.
2. Different factors associated with about material of glass .
3. Inside material used for wall .
4. Achieve an optimal state and maintain effective cooling with minimum power
5. consumptions .
2.3 Objective of proposed work:
1. The objective of this project is to calculate cooling load to find exact air-conditioning
equipment and air handling unit, to achieve comfort operation and good air distribution in
the air-conditioned zone.
2. To study the cooling load in the room by considering the different heat source
3. To study the different nano particles use as refrigerant for effective cooling
4. To implement nano particles in air conditioning system and checking the desired
properties which are within limits

D. Y. Patil College of Engg. & Tech., Kolhapur.Page 5 of 19


Optimization Of Air Conditioning System

CHAPTER 3
DESIGN AND ANALYSIS
3.1 Block diagram of vapour compression cycle

3.1.1 Fundamentals/basics
Commonly used terms relative to cooling load calculation and heat transfer of the
buildings according to the ASHRAE reference are given below.
a) Refrigeration: - the term ‘Refrigeration’ means process of removing heat from a
substance or space under the controlled conditions. It also include the process of
reducing and maintaining the temperature of a body below the surrounding
temperature
b) Unit of refrigeration: - the practical unit of refrigeration is expressed in terms of
‘tonne of refrigeration (TR)’. A tonne of refrigeration is defined as the amount of
refrigeration effects produced by the melting of 1 ton of ice from and at 0oC in 24
hours.
c) Coefficient of performance (COP): - the COP is defined as the ratio of heat
extracted in the refrigerator to the work done on the refrigerant.
d) Refrigerant: - refrigerant is the fluid used for heat transfer in a refrigerating
system that release heat during condensation at a region of higher temperature and

D. Y. Patil College of Engg. & Tech., Kolhapur.Page 6 of 19


Optimization Of Air Conditioning System

pressur e, and absorbs heat during evaporation at low temperature and pressure
region.
e) Air conditioning: - controlling and maintaining environmental parameters such as
temperature, humidity, cleanliness, air movement, sound level, pressure difference
between condition space and surrounding within prescribed limit.
f) CLTD: - cooling load temperature difference is an equivalent temperature
difference used for calculating the instantaneous external cooling load across the
walls and roofs.
g) Humidity: - it is the mass of water vapour present in 1 kg of dry air, and is
generally expressed in terms of gram per kg of dry air (g/kg of dry air). It is also
called specific humidity or humidity ratio.
h) Relative humidity (RH): - it is a ratio of actual mass of water vapour in a given
volume of moist air to the mass of water vapour in the same volume of saturated air
at the same temperature and pressure.
i) Dry bulb temperature (DBT): - it is the temperature of air recorded by
thermometer, when it is not affected by the moisture present in the air. The dry bulb
temperature is generally denoted by td or tdb
j) Wet bulb temperature (WBT): - it is the temperature of air recorded by a
thermometer, when its bulb is surrounded by a wet cloth exposed to the air. The wet
bulb temperature is generally denoted by tw or twb
k) Heat transfer coefficient: - it is the rate of heat transfer through a unit area of
building envelope material, including its boundary films, per unit temperature
difference between the outside and inside air.
l) infiltration: uncontrolled inward air leakage to conditioned spaces through
unintentional openings in ceilings, floors, and walls from unconditioned spaces or
the outdoors caused by the same pressure differences that induce exfiltration.
3.1.2 Basic Information
Before estimating cooling load of any building there are some basic
information’s are necessary to design an exact HVAC systems, like building
orientation, weather condition, building spacing, buildings materials etc. The more
exact the information the more accurate will be the load estimated.
3.1.3 Building Location

D. Y. Patil College of Engg. & Tech., Kolhapur.Page 7 of 19


Optimization Of Air Conditioning System

The Institute building of D.Y. Patil College of Engineering and Technology


considered in this study is situated in Kolhapur, located at 16.7321‫﮿‬N latitude and
74.2405‫﮿‬E longitude in Kolhapur District of Maharashtra, India at an elevation of
about 546 meters above mean sea level. 3.1.2 Climate condition Kolhapur
has a humid climate. During Southwest monsoon (June – September), it receives
high rainfall and retreats Northeast monsoon (December – January). Average annual
rainfall ranges 778mm.The minimum and maximum temperatures ranges are 10 to
40 with a mean minimum and maximum temperature range of 14.90 to 27.30 during
coldest and hottest months. Table 3.1.3 gives the average high and low temperature
of Kolhapur

Month Average temperature Average


(oC) Humidity(%RH)
January 23.7 62
February 26.4 68
March 29.7 70 Tabl
e April 32.4 71 no.

May 33.7 69
June 30.5 82
July 27.9 90
August 27.8 91
September 27.5 83
October 27.1 80
November 24.7 70
December 22.9 61

3.1.3: Average temperatures and Humidity of Kolhapur

Buildings may be classified as externally loaded and internally loaded. In externally


loaded buildings the cooling load on the building is mainly due to heat transfer
between the surroundings and the internal conditioned space. Since the surrounding
conditions are highly variable in any given day, the cooling load of an externally
loaded building varies widely. In internally loaded buildings the cooling load is
mainly due to internal heat generating sources such as occupants or appliances or
processes. In general the heat generation due to internal heat sources may remain

D. Y. Patil College of Engg. & Tech., Kolhapur.Page 8 of 19


Optimization Of Air Conditioning System

fairly constant, and since the heat transfer from the variable surroundings is much
less compared to the internal heat sources, the cooling load of an internally loaded
building remains fairly constant. Obviously from energy efficiency and economics
points of view, the system design strategy for an externally loaded building should be
different from an internally loaded building. Hence, prior knowledge of whether the
building is externally loaded or internally loaded is essential for effective system
design. As mentioned before, the total cooling load on a building consists of external
as well as internal loads. The external loads consist of heat transfer by conduction
through the building walls, roof, floor, doors etc, heat transfer by radiation through
fenestration such as windows and skylights. All these are sensible heat transfers. In
addition to these the external load also consists of heat transfer due to infiltration,
which consists of both sensible as well as latent components. The heat transfer due to
ventilation is not a load on the building but a load on the system. The various internal
loads consist of sensible and latent heat transfer due to occupants, products,
processes and appliances, sensible heat transfer due to lighting and other equipment.
Figure 3.1.3 shows various components that constitute the cooling load on a
building. Infiltration Heat transfer from ground solar radiation through fenestration
solar radiation through opaque surfaces Internal heat sources

Fig.3.1.3: Various cooling load components

Estimation of cooling load involves estimation of each of the above components


from the given data. In the present chapter, the cooling load calculations are carried
out based on the CLTD/CLF method suggested by ASHRAE. For more advanced
methods such as TFM, the reader should refer to ASHRAE and other handbooks.

D. Y. Patil College of Engg. & Tech., Kolhapur.Page 9 of 19


Optimization Of Air Conditioning System

3.2 Analytical work


3.2.1 Design condition
The amount of cooling that has to be accomplished to keep buildings
comfortable in summer and winter depends on the desired indoor conditions and on
the outdoor conditions on a given day. These conditions are respectively called the
“indoor design condition” and the “outdoor design condition”. For most of the
comfort systems, the recommended indoor temperature and relative humidity are as
follows DBT – 22.78 oC to 26.11 oC and RH – 50% , for summer DBT – 22.11 oC to
22.22 oC and RH – 20 to 30% for winter. The cooling load of the building is based
on 25 oC dry bulb temperature and 50% relative humidity Indoor design conditions.
The outdoor design conditions are determined from published data for the specific
location, based on weather airport records.
3.2.2 Overall heat transfer coefficient (U)
Commonly the building walls may consist of non-homogeneous materials for
example hollow bricks, air gap and plaster. Heat transfer through these types of wall
is quite complicated as it involves simultaneous heat transfer by conduction,
convection and radiation. All material has different kinds of thermo physical
properties; the thermo-physical properties of common building materials have been
measured and presented in ASHRAE and other handbooks and are taken as follows
in our calculation: U-value for wall (brick) : 2.5 W/m 2.K U-value for wood :- 1.42
W/m2.K U-value for roof : 1.2 W/m2.K U-value for floor : 1.2 W/m2.K U-value for
glass :- 3.12 W/m2.K
3.2.3 Cooling Load Temperature Difference
The expose walls of the D.Y.P.C.E.T building are thermally heavier than the wall
due to added insulation and climatic conditions, then corrected CLTD for the walls
exposed is taken as 25 OC for all seasons as presented and measured in ASHRAE.
Effective Temp. Difference (CLTD) for wall : 25 OC (Exposed to sunlight)
Effective Temp. Difference (ETD) for wall: (To-Ti) (Shaded)
Effective Temp. Difference (ETD) for roof : (To-Ti)
Effective Temp. Difference (ETD) for floor : (To-Ti)

D. Y. Patil College of Engg. & Tech., Kolhapur.Page 10 of 19


Optimization Of Air Conditioning System

3.3 Case Study


3.3.1 Sample Cooling load calculation of Computer Lab (North Wing)
Cooling load calculation
 Inside conditions : 25 dry bulb, 50 percent RH
 Outside conditions : 40 OC dry bulb, 40% RH
 U-value for wall : 2.5 W/m2.K
 U-value for roof : 1.2 W/m2.K
 U-value for floor : 1.2 W/m2.K
 U-value for glass :- 3.12 W/m2.K
 CLTD for wall: 25 OC
 Effective Temp. Difference (ETD) for roof: 0 OC
 Effective Temp. Difference (ETD) for roof: 15 OC
 Solar Heat Gain (SHG) of glass : 300 W/m 2
 Internal Shading Coefficient (SC) of glass: 0.86
 Occupancy : 21 (90 W sensible heat/person) (40 W latent heat/person)
 Infiltration : 0.75 Air Changes per Hour
 Barometric pressure: 101 k pa
From psychrometric chart,
For the inside conditions of 25 OC dry bulb, 50% RH
Wi= 0.010 kg w/ kg
For the outside conditions of 40 OC dry bulb, 40% RH
Wo= 0.019 kg w/kg,
density of dry air = 1.095 kg/m 3
1) External loads:

a) Heat transfer rate through the walls (Exposed) :

Qwall = Uwall Awall CLTDwall

= 2.5 x (59.5- 16.8) x 25 = 2668 W (Sensible)

D. Y. Patil College of Engg. & Tech., Kolhapur.Page 11 of 19


Optimization Of Air Conditioning System

b) Heat transfer rate through roof:

Qroof = Uroof Aroof ETDroof

= 1.2 x 70 x 0 = 0 W (Sensible)

c) Heat transfer rate through floor: since the floor is not exposed to solar radiation, the
driving temperature difference for the roof is the temperature difference between the outdoor
and indoor, hence:

Qfloor = Ufloor Afloor ETDfloor

= 1.2 x 160 x 15 = 2880 W (Sensible)

d) Heat transfer rate through glass:

Hence the total heat transfer rate through the glass window is given by:

Qglass = Aglass [Uglass(To−Ti) + SHGFmax SC]

= 16.8 [3.12 x 15 + 300 x 0.86]

= 5120.64 W (Sensible)

e) Heat transfer due to infiltration:

The infiltration rate is 0.75 ACH, converting this into mass flow rate, the infiltration rate
in kg/s is given by:

Fmin = density of air x (ACH x volume of the room)/3600

= 1.095 x (0.75 x 576)/3600

Fmin = 0.1314 kg/s

f) Sensible heat transfer rate due to infiltration, Qsinf ;

Qsinf = Fmin cpm(To−Ti)

= 0.1314 x 1021.6 x (40 – 25)

= 2013.57 W (Sensible)

D. Y. Patil College of Engg. & Tech., Kolhapur.Page 12 of 19


Optimization Of Air Conditioning System

g) Latent heat transfer rate due to infiltration, Qlinf ;

Qlinf = fmin hfg(Wo−Wi)

= 0.1314 x 2501 x 1000 (0.019−0.010)

= 2957.68 W (latent)

2) Internal loads :

a) Load due to occupants:

The sensible and latent load due to occupants are:

Qsocc = no. of occupants x SHG

= 21x 90

= 1890W

Qlocc = no. of occupants x LHG

= 21 x 40

= 840W

b) Load due to lighting : Assuming a CLF value of 1.0 ,the load due to lighting is:

Qlights = 4 tube lights

= 28 x 4

= 112 W (Sensible)

c) Load due to appliance:

Qsapp= 4 fan + 21 computers

= 4 x 70 + 21 x 200

= 4480 W (Sensible)

D. Y. Patil College of Engg. & Tech., Kolhapur.Page 13 of 19


Optimization Of Air Conditioning System

Total sensible and latent loads are obtained by summing-up all the sensible and

latent load components (both external as well as internal) as :

Qstotal = 2668+2880+5120+2013+4480+112+14560 = 31834.5 W (sensible)

Qltotal = 2957.68+2800 = 5757.68 W (latent)

Total load on the building is:

Qtotal = Qstotal + Qltotal

= 31834.5 + 5757.68

= 37592.1 W

Ventilation may be neglected as the infiltration can take care of the small ventilation
requirement. Hence using a safety factor of 1.25, the required cooling capacity is:

Required cooling capacity = 37592.1 /3500 = 10.74TR

Required cooling capacity with Factor of Safety :

= 37592.1 x 1.25 =46990.12

= 46990.12/3500 = 13.4 TR

D. Y. Patil College of Engg. & Tech., Kolhapur.Page 14 of 19


Optimization Of Air Conditioning System

CHAPTER 4
FUTURE SCOPE
1. It should be developing a knowledge base on the rule for conservation energy
in the smart building.
2. The purpose of this research was to determine the required cooling load of
the building and to maintain an optimal state of the building considering with
the number of occupancy effect
3. To estimate capacity or size of plant/equipment.
4. To provide info for HVAC designs e.g. load profiles.
5. By using the nano particles enhancing the efficiency of refrigeration &Air
conditioning
6. Nano particles helps to improve the performance of compressor and also increasing
the heat transfer performance.

D. Y. Patil College of Engg. & Tech., Kolhapur.Page 15 of 19


Optimization Of Air Conditioning System

CHAPTER 5
COST ESTIMATION
5.1 Facilities available and requirements
1. Necessary technical, experimental, testing, computing, library and internet
facilities are available in the institute.
2. Necessary raw materials will be procured from vendors.

5.2 Expenditure table


Sr. no. Particulars Quantity Cost(Rs.)
1. Air conditioner 1 10000
2. Coating Material of 3 3000
Glass
3. Different Tube lights 4 2000
4 Nano particles(fluid) 1 7000
TOTAL - 22000/-

D. Y. Patil College of Engg. & Tech., Kolhapur.Page 16 of 19


Optimization Of Air Conditioning System

5.3 Work schedule for completion of project

Sr. Activity/ Jun Jan


Jul Aug Sep Oct Nov Dec Feb Mar
No. Month 2019 2020
Literature
1 Review and
survey
Brain storming
2

Study cooling
3
loads
Solving Case
4
study
Research study of
5
nano fluid
Experimental
6
Setup
Testing
7

Result Analysis
8

Draft of Report
9

Submission of
10
Report

REFERENCES

D. Y. Patil College of Engg. & Tech., Kolhapur.Page 17 of 19


Optimization Of Air Conditioning System

Research papers
1. C.A. Balaras, ”the role of thermal mass on the cooling load of buildings. An
overview of computational methods” ,1996
2. S. A. Fadhilah& R. S.Marhamah and A. H. M. Izzat , “Copper Oxide
Nanoparticles for Advanced Refrigerant”, Hindawi Publishing Corporation
Journal of Nanoparticles Volume 2014, Article ID 890751, 5 pages
3. Chairani S Sulistyo & Widyawan, “ Cooling Load Estimation in the Building
Based On Heat Sources” , International Conference on Environmental and Energy
Engineering ( 2017)
4. Vikas Palliwal, Pradeep Kumar Sharma ,” Cooling load For a Institutional
building” , International Journal of Interdisciplinary Research Volume 3, Issue 1,
March 2017 ISSN: 2455-1600
5. K. T. Pawale1&A. H. Dhumal & G. M. Kerkal ,” Performance Analysis of VCRS
with Nano-Refrigerant”, International Research Journal of Engineering and
Technology (IRJET) Volume: 04 Issue: 04 | Apr -2017
6. S. K. Gaadhe &.K. Chavda and R.D. Bandhiya , “Cooling Load Estimation of
College Reading Hall” , International Journal of Current Microbiology and
Applied Sciences ISSN: 2319-7706 Volume 8 Number 03 (2019)

D. Y. Patil College of Engg. & Tech., Kolhapur.Page 18 of 19


Optimization Of Air Conditioning System

Sign: Sign:

MR. SADANAND R. SHENDOLKAR MR.OMKAR C YADAV


Student Student

Sign: Sign:

MISS.SHIVANI P PARAB MISS.GANDHALI J KAMBLE


Student Student

Sign:-
Sign:-
Prof. (Dr) S. R. Todkar
Prof. P. A. Pandav Head,
Guide Department of Mechanical Engineering

Date:
Place: Kolhapur

D. Y. Patil College of Engg. & Tech., Kolhapur.Page 19 of 19

You might also like