Scope of Supply
Page 1 of 2
Controls
Qty Description
1 Duplex control panel for use with 35 hp, 460 volt, 3 phase pumps and including the
following features:
Type 4 floor mounted enclosure
Inner door interlocked main circuit breaker
Pump circuit breaker for each pump
Flygt SmartRun variable speed drives
3 phase surge arrestor
Control power transformer
Anti-condensation heater with thermostat
Current transformers for each pump
Inner door mounted components:
o High level indicator
o Overflow indicator
o Power OK indicator
o 15A GFCI duplex receptacle
Inner door mounted components for each pump:
o Run indicator
o Elapsed time meter
DC power supply and battery backup for controller
Red alarm beacon light
Audible alarm
Dry alarm output contacts for SCADA interfacing:
o High level
o Pump 1 fail
o Pump 2 fail
o Power fail
Space allowance for existing radio
Wires numbered
Terminal blocks, control relays and circuit breakers as required
UL508A listed
1 Pump disconnect panel including the following features:
Type 4X 304ss wall mounted enclosure
Anti-condensation heater with thermostat
Single channel analog barrier
Four channel intrinsically safe barrier
Three Flygt ENM-10 float sensors, 30’ cable
One level transducer, 0-5M range, 39’ cable
Terminal blocks as required
Wires numbered
UL698A listed
Page 2 of 2
TABLE OF CONTENTS
Section 1 Submersible Pumps
Pump Technical Data and Performance Curve
Dimensional Drawing
Power Cable Data
Performance Specification
** Included in Section 4
Section 1
Submersible Pumps
NP 3171 SH 3~ 278
Te chnical specification
Head
[f t]
200
190
180
170
160
150
140
130
120
110
100 61.2%
90
80
70
60
10
Impeller
0
Im peller m aterial H ard-Iron ™
0 100 200 300 400 500 600 700 [US g.p.m.] D ischarge F lange D iam eter 100 m m
Suction Flange D iam eter 100 m m
Water, pure Curve according to: ISO 9906 grade 2 annex 1 or 2 Im peller diam eter 168 m m
N um ber of blades 2
Power f actor
400
Z 70 Z
3/4 Load 0.89
MIN
84
Ef f ic iency
1046 (TO FURTHE S T P OINT) 1/1 Load 91.0 %
**770/820 3/4 Load 91.5 %
45° 209 1/2 Load 92.0 %
RE F.LINE
209
168
168
209
209
**72/22
200
V IE W Z Z
Ø20(4x)
100
B OLT
250
CL OF DISCH
[ft] Head
200
190
180
170
160
150
140
135 ft
130
120
110
100 61.2%
90
80
70
60
50
278 168mm
40
30
20
10
0
[%] Efficiency 53.8 %
50 Total efficiency
49.5 %
40 278
278 168mm
168mm
30
20
10
0
Shaft power P2 278 168mm (P1)
[hp] 20.9 hp
Power input P1 278 168mm (P2)
20
18 19.3 hp
16
14
[ft] NPSH-values 278 168mm
35
30
25
20
15 14 ft
10 304 US g.p.m.
0 50 100 150 200 250 300 350 400 450 500 550 600 650 700 750 800 [US g.p.m.]
Water, pure Curve according to: ISO 9906 grade 2 annex 1 or 2
[ft] Head
210
205
200
195
190
185
180
175
170
165
160
155
150
145
140
135 135 ft
130
125
120
115
110
105
61.2%
100
95
90
85
80
75
70
65
60
55
50
45 278 168mm
40
35 1
30
25
20
15
10
5
304 US g.p.m.
0
0 50 100 150 200 250 300 350 400 450 500 550 600 650 700 750 800 [US g.p.m.]
Water, pure Curve according to: ISO 9906 grade 2 annex 1 or 2
Indiv idual pump Total
Pumps
running Specific
/System Flow Head Shaft power Flow Head Shaft power Pump eff. energy NPSHre
1 304 US g.p.m. 135 ft 19.3 hp 304 US g.p.m. 135 ft 19.3 hp 53.8 % 856 kWh/US MG 14 ft
Head
[ft]
200
190
180
170
160
150
140
130
120
110
100 61.2%
90
61.2%
80
70 61.2%
60
61.2%
50
61.2% 278 168mm
40
55 Hz
30 50 Hz
45 Hz
20 40 Hz
10
0
[%] Efficiency
Total efficiency
50
40 40 Hz 45 Hz 50 Hz 55 Hz 278 168mm
45 Hz 50 Hz 55 Hz 278 168mm
40 Hz
30
20
10
0
[hp] Shaft power P2
278 168mm (P1)
20 Power input P1 278 168mm (P2)
55 Hz
16 55 Hz
12 50 Hz
50 Hz
45 Hz
8 45 Hz
40 Hz
40 Hz
4
0
[ft] NPSH-values 278 168mm
35 55 Hz
30 50 Hz
25 45 Hz
20 40 Hz
15
10
5
0 50 100 150 200 250 300 350 400 450 500 550 600 650 700 750 800 [US g.p.m.]
Water, pure Curve according to: ISO 9906 grade 2 annex 1 or 2
[ft] Head
210
205
200
195
190
185
180
175
170
165
160
155
150
145
140
135 135 ft
130
125
120
115
110
105
61.2%
100
95
90
85 61.2%
80
75
70 61.2%
65
60
55 61.2%
50
45 61.2% 278 168mm
40
35 1 55 Hz
30 50 Hz
25 45 Hz
20 40 Hz
15
10
5
304 US g.p.m.
0
0 50 100 150 200 250 300 350 400 450 500 550 600 650 700 750 800 [US g.p.m.]
Water, pure Curve according to: ISO 9906 grade 2 annex 1 or 2
**561/610
**85/135 476
REF.LINE
116
249
DN100
MIN LEVEL
995
400
292
*
Z 70 Z
MIN
**326/265
60
84
1046 (TO FURTHEST POINT)
**770/820
45° 209
REF.LINE
209
168
168
2" GUIDE BARS FOR NEWINSTALLATION 209
3" GUIDE BARS FOR RETROFIT
209
**72/22
200
VIEW Z Z
Ø20(4x)
100
BOLT
250
CL OF DISCH
Fly
ygt Su
ubmerrsible Motorr Cablles
2012‐10‐12
This bro
ochure conntains an ovverview of the Flygt motor
m cable assortme ent. The cables are
especia ed for submersible u se and ma
ally designe ade of careefully seleccted materials. The
assortm ns the following cable
ment contain ng applications:
es for varyin
Flygtt SUBCA
AB®
Why ch
hoose a Fly
ygt SUBCA
AB®?
Flygt SU
UBCAB® is a range off pump mo otor power cables esppecially devveloped by
y Xylem.
They arre made forr use with Flygt pumpss and mixerrs and make sure that the cable attached
a
to yourr product will
w never let you do own, whate ever your application
n is. Choosse Flygt
SUBCAB® for a low w life cycle cost, durab
bility and minimum
m do
own time.
1
Genera
al propertie
es for Flygt SUBCAB®
®
Flygt SUBCAB® is designed d for use with stand
dard and explosion
e p
proof subm
mersible
productts in applications where the amb
bient tempe
erature does not excee
ed 70°C.
For rem
mote pump control, Flygt provide es a simple
e and reliab ble solution
n through itts cables
with co
ontrol coress. You only y need on e cable instead of using the cconventiona al pump
control solution off a motor cable plus a separate control
c cable. The ran ge includes cables
with twisted pair of
o screened d control c ores speciffically adap
pted for thee use of Fly
ygt MAS
800 pummp superviision systemm.
2
Fig. 1 Fig. 2 Fig. 3
SUBCAB® ® SUBCAB® Scre ened SUBCAB®
10-35 mm m2 50-120 mm22 1,5 mm2
Fig. 4 Fig. 5 Fig. 6
SUBCAB®
S
Screened SUBBCAB® Sccreened SUBC
CAB®
control e lement design in fig.
2,5-50 mm
m2 70-120 mm22
1,2,3 and 5
Flygt SUBCA
AB® without control cores
** See p
page 9
3
Type Denomin
nation Part No. Nominal Outer Weightt Bendingg Fig.
m 2)
(mm (* EPR) current diameter kg/m radius No.
capacity (mm) (cm)
at 30°C
(Amp)**
Flygt SUBC
CAB® with co
ontrol coress
4G2.5 + 2x1.5 94
9 20 59* 32 17 - 18 0.43 17
4G4 + 2x1.5
2 94
9 20 60* 42 20 - 22 0.63 20
4G6 + 2x1.5
2 94
9 20 56* 54 24 - 26 0.83 24
4G10 + S(2x0.5)
S 94
9 19 81 75 24 - 26 0.85 26 1
4G16 + S(2x0.5)
S 94
9 19 82 100 26 - 28 1.30 26 1
4G25 + S(2x0.5)
S 94
9 19 83 127 32 - 34 1.70 32 1
4G35 + S(2x0.5)
S 94
9 19 84 157 35 - 37 2.24 35 1
3x50 + 2G
G35/2 +
94
9 19 85 192 35 - 37 2.60 35 2
S(2x0
0.5)
3x70 + 2G
G35/2 +
94
9 19 86 246 38 - 41 3.30 38 2
S(2x0
0.5)
3x95 + 2G
G50/2 +
94
9 19 87 298 47 - 50 4.50 47 2
S(2x0
0.5)
3x120 + 2G
G70/2 +
94
9 19 88 346 54 - 56 5.70 54 2
S(2x00.5)
7G4 + 2x1.5
2 94
9 20 80* 42 22 – 24 0.84 22
7G6 + S(2x0.5) 94
9 19 80 54 24 - 26 0,85 24
** See p
page 9
4
Temp e correcttion
perature
Temperature corrrection fac
ctors for Fly
ygt cables
The currrent capacities for Flygt cables a re designed for duty at
a 30°C am bient tempperature.
If the am mperature exceeds 30°°C, the maxximum current rating tthe conduc
mbient tem ctors can
handle has to be taken
t into consideratiion. The cu
urrent rating
g must be aadjusted (lo
owered)
according to the ta
able.
Examp le
• Sele
ect correctio
on factor fo
or 52°C in th
he table (0,76 ).
Calcculate "virtu
ual" currentt 33 / 0,76 = 44A
Cho m 2 at 52°C. rated 54
oose 4 G 6 mm 4A
Ambien
nt tempera
ature corre
ection facto
ors
According to IEC 60364-5-52
6 23 table 52--D1 and NE
EC table 310-16 (USA//Canada) in
n air.
Maximum mechanic
cal load
The maximum mechanical loa 1 kg/mm2 conductorr area.
ad on Flygtt cables is 1.5
Examp le
Flygt SU
UBCAB® 4 G 50 p/No.. 94 19 85 ccan take a max.
m load of 1.5 x 4 x 5 50 =300 kg. It
s the max.. length thaat can hang vertically iss 300 / 2.6 = 115m cable.
weighs 2.6 kg/m, so
Bend
ding radius
The min nding radiuss of Flygt caables is 10 x outer diameter.
nimum ben
9
Flygtt SUBCA
AB® standards a
and apprrovals
Flygt SU
UBCAB® caables comply with the following general
g stan
ndards:
Standard
d Typee Standaard Typ
pe
Flexible caable
IEC 602245 VDDE 0207 part 20 Material
in general
IEC 602
228 class 5 Conducto r VD
DE 0250 Material
IEC 608
811-1-1 CLA
AUSE 9 Oil resistan
nt VD
DE 0282 part 810 Material
IEC 608
811-2-1 CLA
AUSE 10 Oil resistan
nt VD
DE 0472 part 803-A Oil resista
ant
IEC 603
332-1 Flame retaardant VD
DE 0472 part 804-B Flame rettardant
IEC 603
332-2 Flame retaardant VD
DE 0295 Conducto
or
IEC 603
364-5-523 Current VD
DE 0298 Current
Flexible caable
CSA C2
22.2 No.49--1992 VD
DE 0472 Testing
in general
Flexible caable Flexible cable
c in
UL 1581
1 D 22.4
HD
in general general
Flexible caable Cables fo
or
CCC.GB
B5013/IEC6
60245 N 50525-2-2
EN 21
in general submersible use
Flexible caable
EN 50525-2-21 EN
N 50363-1:2
2005 Material
in general
Other cabless standards and
d approv
vals
Cable T
Type Sta
andard/Ap
pproval Type
Flygt HC
CR IEC
C 60287 Curren
nt rating
Flygt HC
CR IEC
C 60332-3 Cat A Flame retardant
Flygt HC
CR SS
S 424 02 46 Condu
uctor insulaation material
Flygt HC
CR NE
EMA WC 27
7500 Materiial
Silicone
e cable VD
DE 0207 Curren
nt rating
Silicone
e cable IEC
C 60332-1 Flame retardant
Medium
m voltage cable DIN VDE 250
0 Materiial
Medium
m voltage cable DIN VDE 298
8 part 4 Curren
nt rating
Medium
m voltage cable DIN VDE 207
7 Insulattion materiaal
10
NP3171.095 SPECIFICATIONS
REQUIREMENTS
Furnish and install 2 submersible non-clog wastewater pump(s). Each pump shall be
equipped with an 35 HP submersible electric motor, connected for operation on 460 volts,
phase, 60 hertz service, with 50 feet of submersible cable (SUBCAB) suitable for submersible
pump applications. The power cable shall be sized according to NEC and ICEA standards and
also meet with P-MSHA Approval. The pump shall be supplied with a mating cast iron 4 inch
discharge connection and be capable of delivering 300 GPM at 131 TDH. Each pump
shall be fitted with chain sling unit and Flygt grip eye. The working load of the lifting system shall
be 50% greater than the pump unit weight.
PUMP CONSTRUCTION
Major pump components shall be of grey cast iron, ASTM A-48, Class 35B, with smooth surfaces
devoid of blow holes or other irregularities. The lifting handle shall be of stainless steel. All
exposed nuts or bolts shall be of stainless steel construction. All metal surfaces coming into
contact with the pumpage, other than stainless steel or brass, shall be protected by a factory
applied spray coating of acrylic dispersion zinc phosphate primer with a polyester resin paint
finish on the exterior of the pump.
Sealing design shall incorporate metal-to-metal contact between machined surfaces. Critical
mating surfaces where watertight sealing is required shall be machined and fitted with Nitrile
rubber O-rings. Fittings will be the result of controlled compression of rubber O-rings in two
planes and O-ring contact of four sides without the requirement of a specific torque limit.
Rectangular cross sectioned gaskets requiring specific torque limits to achieve compression shall
not be considered as adequate or equal. No secondary sealing compounds, elliptical O-rings,
grease or other devices shall be used.
COOLING SYSTEM
Each unit shall be provided with an integral motor cooling system. A stainless steel motor cooling
jacket shall encircle the stator housing, providing for dissipation of motor heat regardless of the
type of pump installation. An impeller, integral to the cooling system and driven by the pump
shaft, shall provide the necessary circulation of the cooling liquid through the jacket. The cooling
liquid shall pass about the stator housing in the closed loop system in turbulent flow providing for
superior heat transfer. The cooling system shall have one fill port and one drain port integral to
the cooling jacket. The cooling system shall provide for continuous pump operation in liquid or
ambient temperatures of up to 104°F (40°C.). Operational restrictions at temperatures below
104°F are not acceptable. Fans, blowers or auxiliary cooling systems that are mounted external
to the pump motor are not acceptable.
MOTOR
The pump motor shall be a NEMA B design, induction type with a squirrel cage rotor, shell type
design, housed in an air filled, watertight chamber. The stator windings shall be insulated with
moisture resistant Class H insulation rated for 180°C (356°F). The stator shall be insulated by the
trickle impregnation method using Class H monomer-free polyester resin resulting in a winding fill
factor of at least 95%. The motor shall be inverter duty rated in accordance with NEMA MG1, Part
31.The stator shall be heat-shrink fitted into the cast iron stator housing. The use of multiple step
dip and bake-type stator insulation process is not acceptable. The use of pins, bolts, screws or
other fastening devices used to locate or hold the stator and that penetrate the stator housing are
not acceptable. The motor shall be designed for continuous duty while handling pumped media of
up to 104°F. The motor shall be capable of no less than 30 evenly spaced starts per hour. The
rotor bars and short circuit rings shall be made of aluminum. Three thermal switches shall be
embedded in the stator end coils, one per phase winding, to monitor the stator temperature.
These thermal switches shall be used in conjunction with and supplemental to external motor
overload protection and shall be connected to the motor control panel.
The junction chamber shall be sealed off from the stator housing and shall contain a terminal
board for connection of power and pilot sensor cables using threaded compression type
terminals. The use of wire nuts or crimp-type connectors is not acceptable. The motor and the
pump shall be produced by the same manufacturer.
The motor service factor (combined effect of voltage, frequency and specific gravity) shall be
1.15. The motor shall have a voltage tolerance of +/- 10%. The motor shall be designed for
continuous operation in up to a 40°C ambient and shall have a NEMA Class B maximum
operating temperature rise of 80°C. A motor performance chart shall be provided upon request
exhibiting curves for motor torque, current, power factor, input/output kW and efficiency. The
chart shall also include data on motor starting and no-load characteristics.
Motor horsepower shall be sufficient so that the pump is non-overloading throughout its entire
performance curve, from shut-off to run-out. The motor and cable shall be capable of continuous
submergence underwater without loss of watertight integrity to a depth of 65 feet or greater.
BEARINGS
The integral pump/motor shaft shall rotate on two bearings. The motor bearings shall be sealed
and permanently grease lubricated with high temperature grease. The upper motor bearing shall
be a two row angular contact ball bearing. The lower bearing shall be a two row angular contact
ball bearing to handle the thrust and radial forces. The minimum L10 bearing life shall be 50,000
hours at any usable portion of the pump curve.
MECHANICAL SEALS
Each pump shall be provided with a positively driven dual, tandem mechanical shaft seal system
consisting of two seal sets, each having an independent spring. The lower primary seal, located
between the pump and seal chamber, shall contain one stationary and one positively driven
rotating corrosion and abrasion resistant tungsten-carbide ring. The upper secondary seal,
located between the seal chamber and the seal inspection chamber shall be a leakage-free seal.
The upper seal shall contain one stationary and one positively driven rotating corrosion and
abrasion resistant tungsten-carbide seal ring. The rotating seal ring shall have small back-swept
grooves laser inscribed upon its face to act as a pump as it rotates, returning any fluid that should
enter the dry motor chamber back into the lubricant chamber. All seal rings shall be individual
solid sintered rings. Each seal interface shall be held in place by its own spring system. The seals
shall not depend upon direction of rotation for sealing. Mounting of the lower seal on the impeller
hub is not acceptable. Shaft seals without positively driven rotating members or conventional
double mechanical seals containing either a common single or double spring acting between the
upper and lower seal faces are not acceptable. The seal springs shall be isolated from the
pumped media to prevent materials from packing around them, limiting their performance.
Each pump shall be provided with a lubricant chamber for the shaft sealing system. The lubricant
chamber shall be designed to prevent overfilling and shall provide capacity for lubricant
expansion. The seal lubricant chamber shall have one drain and one inspection plug that are
accessible from the exterior of the motor unit. The seal system shall not rely upon the pumped
media for lubrication.
The area about the exterior of the lower mechanical seal in the cast iron housing shall have cast
in an integral concentric spiral groove. This groove shall protect the seals by causing abrasive
particulate entering the seal cavity to be forced out away from the seal due to centrifugal action.
A separate seal leakage chamber shall be provided so that any leakage that may occur past the
upper, secondary mechanical seal will be captured prior to entry into the motor stator housing.
Such seal leakage shall not contaminate the motor lower bearing. The leakage chamber shall be
equipped with a float type switch that will signal if the chamber should reach 50% capacity.
PUMP SHAFT
The pump and motor shaft shall be a single piece unit. The pump shaft is an extension of the
motor shaft. Shafts using mechanical couplings shall not be acceptable. The shaft shall be
stainless steel – ASTM A479 S43100-T. Shaft sleeves will not be acceptable.
IMPELLER
TM
The impeller shall be of Hard-Iron (ASTM A-532 (Alloy III A) 25% chrome cast iron),
dynamically balanced, semi-open, multi-vane, back swept, screw-shaped, non-clog design. The
impeller leading edges shall be mechanically self-cleaned automatically upon each rotation as
they pass across a spiral groove located on the volute suction. The leading edges of the impeller
shall be hardened to Rc 60 and shall be capable of handling solids, fibrous materials, heavy
sludge and other matter normally found in wastewater. The screw shape of the impeller inlet shall
provide an inducing effect for the handling of up to 5% sludge and rag-laden wastewater. The
impeller to volute clearance shall be readily adjustable by the means of a single trim screw. The
impeller shall be locked to the shaft, held by an impeller bolt and shall be coated with alkyd resin
primer.
PROTECTION
Each pump motor stator shall incorporate three thermal switches, one per stator phase winding
and be connected in series, to monitor the temperature of the motor. Should the thermal switches
open, the motor shall stop and activate an alarm. A float switch shall be installed in the seal
leakage chamber and will activate if leakage into the chamber reaches 50% chamber capacity,
signaling the need to schedule an inspection.
The thermal switches and float switch shall be connected to a Mini CAS control and status
monitoring unit. The Mini CAS unit shall be designed to be mounted in the pump control panel.
.
Section 2
Submersible Pumps Accessories
Issued: 4/14 Supersedes: 2/12
2 1/2" - DP/FP-3068. 493 17 06 2 1/2" 2 1/2" 11 5/8 7 7/8 4 3/4 7 7/8 11 7/16 9 7/8 6 1/2 4 9/16 45° 90° x 4 5 5/8
3" - 3045, 3057, 555 48 01 2" 3-8 NPT 6 3/4 5 1/2 4 1/8 5 1/2 10 3/4 6 3/4 3 15/16 7/8 --- --- ---
CP-3068.
3" - DP-3068, 3080, 444 68 05 3" 3" 14 9 7/8 8 10 5/8 15 3/8 15 3/4 7 7/8 4 9/16 45° 90° x 4 6
3085, 3102,
3127, 3153.
6" - 3102,
3127(MT), 444 70 06 5 1/2" 6" 15 9/16 11 10 12 3/16 15 3/8 17 3/4 9 7/8 4 9/16 22.5° 45° x 8 9 1/2
3153, 3171.
6" - 3153, 3171, 602 33 06 5 1/2" 6" 15 9/16 11 10 12 3/16 15 15/16 17 3/4 9 7/8 4 9/16 22.5° 45° x 8 9 7/16
3202.
6" - R3231 388 25 06 6" 6" 20 11/16 19 3/4 15 3/4 19 3/4 23 5/8 15 3/4 7 7/8 6 7/8 22.5° 45° x 8 9 7/16
6" - 3127(LT), 3301, 604 56 06 6" 6" 15 9/16 11 1/8 10 12 3/16 15 15/16 18 10 1/8 4 9/16 22.5° 45° x 8 9 7/16
3315.
Note: Alternative discharge connections may be available, contact Flygt Application Engineering.
Caution:
I D Contact Flygt applications engineering
J C
department when making a pump/
discharge connection combination other
than those paired in the chart above.
K
A
H
F
G Note:
The discharge connection shown here
is typical in appearence for most pumps.
E
Issued: 9/11 Supersedes: 8/10
Upper Guide Bar Bracket (for 3000, 5500 & 8000 Series Pumps)
2" UPPER GUIDE BAR BRACKET Standard for the
following pumps:
613 68 00 Galvanized Steel
613 68 04 316 Stainless Steel DP-3068
DP-3080
MOUNTING HARDWARE CP/DP/FP/NP-3085
14-59 00 00 (stainless steel) NP-3102
NP-3127
4-1/4"
NP/FP-3153
NP/FP-3171
3/8"-16 LATERAL NUT
14-46 37 05 HP-5520, 5530
DP-8050, 8053, 8056, 8058
11-11/16"
HEX. HEAD BOLT (2),
7-1/8" 3/8"-16 x 7/8"
14-46 20 25
3/8" LOCK
WASHER (2)
14-46 50 67
OPTIONAL:
NUT RAIL
Note: use with 2" nominal guide bars FEATURE
LATERAL NUT
3" UPPER GUIDE BAR BRACKET
661 54 00 Galvanized Steel NUT
RAIL
661 54 01 316 Stainless Steel BRACKET
Single Eye, Split Mesh, Rod Closing* Single Eye, Split Mesh, Lace Closing
For support when cable end is not available.
Cable Diameter Approx. Breaking E M Catalog
Range Inches (cm) Strength Lbs. (N) Inches (cm) Inches (cm) Numbers
.50”-.62” (1.27-1.57) 790 (3,514) 7” (17.78) 81 /2” (21.59) 02203013
.63”-.74” (1.60-1.88) 790 (3,514) 8” (20.32) 81 /2” (21.59) 02203014
.75”-.99” (1.90-2.51) 1,020 (4,537) 8” (20.32) 101 /2” (26.67) 02203015
1.00”-1.24” (2.54-3.15) 1,610 (7,161) 9” (22.86) 121 /2” (31.75) 02203017
1.25”-1.49” (3.17-3.78) 1,610 (7,161) 10” (25.40) 141 /2” (36.83) 02203018 E
1.50”-1.74” (3.81-4.42) 1,610 (7,161) 12” (30.48) 151 /2” (39.37) 02203019
1.75”-1.99” (4.44-5.05) 2,150 (9,563) 14” (35.56) 161 /2” (41.91) 02203020
2.00”-2.49” (5.08-6.32) 3,260 (14,500) 16” (40.64) 191 /2” (49.53) 02203021
Support?????
2.50”-2.99” (6.35-7.59) 3,260 (14,500) 18” (45.72) 211 /2” (54.61) 02203022 M
3.00”-3.49” (7.62-8.86) 5,750 (25,576) 21” (53.34) 231 /2” (59.69) 02203023
3.50”-3.99” (8.89-10.13) 5,750 (25,576) 24” (60.96) 251 /2” (64.77) 02203024
E-Eye length M-Mesh length at nominal diameter
Single Eye, Split Mesh, Rod Closing
Grips
* Change catalog number from 022 to 024 for stainless steel. Consult factory for
availability.
Cable Holder
CABLE HOLDER
304L Stainless Steel
653 31 00
Mounting Hardware
to be supplied by user.
10-1/4
8-1/2
1/4
1-3/16
3/8
3-3/4
3-7/16
Flygt Pump LiftTM Lifting System
Water & Wastewater
Accessories Issued: 11/09 Supersedes: 4/08
The normal method of lowering and raising a CP pump in and out of a lift station is
by use of a chain or cable attached to the pump. The length of the chain or cable
is dependent on the depth of the station. The average length would probably be
between 18 to 20 ft. and in certain cases may be much longer. In many cases,
depending on the lifting device (usually a hoist), the operator may have to take a
second or third bite on the pump chain in order to lift the pump clear of the station.
An added accessory to the Flygt line is the pattented Flygt Pump LiftTM System
which consists of 33 ft. of nylon line, a short length of high tensile strength stainless
steel chain and a forged “Grip-Eye” of wrought alloy steel.
1. Connect the small eye of the grip-eye to the end of the hoist cable.
2. Slip the end of the nylon line through the large eye of the grip-eye. The nylon
line simply acts as a guide for the grip-eye on its way down to the short
length of the pump lifting chain.
3. While keeping the nylon line (guide line) taut, proceed to lower the grip-eye
until it is well positioned over the pump lifting chain.
4. Release the tension on the nylon guide line. The lifting chain will now take
a position to become engaged in the grip-eye.
5. Gradually take up tension on the hoist cable and the grip-eye will make a
positive grip on the pump lifting chain. Continue hoisting until the pump is
clear of the station.
Caution: The Grip-Eyes may only be used with the corresponding special
Flygt Chain Sling Units.
Fig. 1 Fig. 2
C
C
A A
D
B
E
B
E
Chain Sling
442 18 00 *442 18 06 *442 18 05
Ass'y
Submersible pump shall be furnished with a pump lifting-chain positive-recovery system consisting of the
following components:
1. Minimum of 10 meters (33 ft.) of nylon line, of diameter matching weight of lifting chain required, connected
to a short length (approximately ten links long) of high tensile strength proof-tested chain of required
capacity, connected to the lifting eye or lifting bail of the submersible pump.
2. A forged “grip-eye” of wrought alloy steel, provided separately to connect to the end of the lifting cable or
chain of the pump lifting device.
1. Connect small eye of grip-eye to end of chain or cable of external mechanical of lifting device.
3. Lower grip-eye to top of pump while maintaining a taut nylon line, making sure short length of chain
fastened to pump is also taut.
4. Release tension on nylon line when grip-eye has reached pump top. Make certain upper end of nylon line
has been secured.
5. Take up tension on cable or chain of lifting device, grip-eye will engage links of short chain and lift pump.
Device shall be the same as the “Flygt Pump LiftTM” manufactured by ITT Water & Wastewater, Shelton,
Connecticut or approved equal.
Furnish with each submersible pump one complete Flygt Pump LiftTM system or approved equal. The system
shall consist of 10 meters (33 ft.) nylon line, short length of high tensile strength proof-tested chain and forged
steel Grip-Eye for use with mechanical lifting device (furnished by others). System shall be appropriately sized
for weight of pump to be lifted.
Section 4
Pump Control Panel and
Pump Disconnect Panel
PROJECT SUMMARY
ELECTRICAL SERVICE
VOLTAGE: 480VAC
PHASE: THREE PHASE, 3W
WIRES: L1, L2, L3, GND
CONTROL SYSTEM
101
102
103
104
105
AL1
106
107
108
109
FAN EXHAUST
FAN EXHAUST
112
113
114
116
117
CB2
CB3
CB4
CB5
CB6
118
HMI HMI
119
120
60.00
121
CR CR CR CR CR CR CR
122 1 2 3 4 5 6 7
123
124
SRC311 #1 SRC311 #2
125
(FRAME 5) (FRAME 5)
126
HT
127 (ELEVATED 3" OFF
BACK PANEL)
128 GFCI
RECEPT
129
130
131
FAN INTAKE
FAN INTAKE
SK3241
SK3241
132 9 10 12 13 N1 80 81 SLD 82 83 SLD 100 101 102 103 104 105 106 107 1 2 3 4
PUMP
AC PDP SIGNAL PDP SCADA
RADIO
SENSORS
133
134
PS BAT
135
(DOCUMENT SHELF)
136
137
NOTE:
138 RADIO TELEMETRY EQUIPMENT
SUPPLIED BY OTHERS
139
140
18.00
141
142
143
144
145
146
147
36.00
148
BACK PANEL LAYOUT - 57" x 33"
149
150
151
152
153
154
155
156
157
158
DESCRIPTION PROJECT
THIS DOCUMENT IS THE PROPRIETARY
DUPLEX SRC311, 35HP, 460V, TYPE 4 PROPERTY OF FLYGT. IT HAS BEEN FURNISHED MARION COUNTY - AURORA, OR
UPON THE CONDITION THAT IT SHALL NOT BE FARGO PUMP LIFT STATION
RELEASED, DUPLICATED, USED OR DISCLOSED IN
WHOLE OR IN PART FOR ANY PURPOSE WITHOUT DESIGN BY DATE REVISION
THE EXPRESS WRITTEN PERMISSION OF FLYGT SDM 11-3-2014 0
AND SHALL BE CONSIDERED CONFIDENTIAL
ORDER NO. / QUOTE NO. INFORMATION. DWG NO. SHEET NO.
/ 081514SM3,4 EDW-CD-XYL-105 1 OF 7
200
201
202
203 POWER
OK
OVERFLOW
ALARM
PUMP 1 PUMP 2 MAIN
I I I
W R
204
RADIO
TEST
HIGH LEVEL
ALARM
O O O
205 R
206
207
PUMP 1 PUMP 1
FAULT FAULT
R R
208 PUMP 1
RUNNING
PUMP 1
RUNNING
G G
209
210
211
HMI HMI
212
213
214
215
GFCI
216 RECEPT
217
218
219
220
221
222
223
224
225
226
227
228
229
INNER DOOR LAYOUT - 57" x 33"
230
231
232
233
234 24.00
235
237
238 10 11 12 13 14 15 N
239
24.00
240
ISR
ISB
241
242
PUMP 1 PUMP 2
243 1 2 G 3 4 G
90 91 92 93 96 97 G
245
246
BACKPANEL SIZE 21"H X 21"W.
247
TYPE 4X SS304 SINGLE DOOR ENCLOSURE.
248 ENCLOSURE SIZE 24"H X 24"W X 10"D WALL MOUNTED.
249
250
251
252
253
10.00
INTRINSICALLY
254
SAFE
AREA
255
256
257
FRONT
258
DESCRIPTION PROJECT
THIS DOCUMENT IS THE PROPRIETARY
DUPLEX SRC311, 35HP, 460V, TYPE 4 PROPERTY OF FLYGT. IT HAS BEEN FURNISHED MARION COUNTY - AURORA, OR
UPON THE CONDITION THAT IT SHALL NOT BE FARGO PUMP LIFT STATION
RELEASED, DUPLICATED, USED OR DISCLOSED IN
WHOLE OR IN PART FOR ANY PURPOSE WITHOUT DESIGN BY DATE REVISION
THE EXPRESS WRITTEN PERMISSION OF FLYGT SDM 11-3-2014 0
AND SHALL BE CONSIDERED CONFIDENTIAL
ORDER NO. / QUOTE NO. INFORMATION. DWG NO. SHEET NO.
/ 081514SM3,4 EDW-CD-XYL-105 2 OF 7
300
301
FROM DISTRIBUTION PANEL
302
480VAC, THREE PHASE, 60 HZ, 3 WIRE + GND
303
L1 L2 L3 GND
304
305
306
MCB
307 150A
308
309
310 PDB1 L1 L2 L3
311
312
Hazardous Area
313 Class I Groups A,B,C,D
Class II Groups E,F,G
314 Class III
315
PCB1 PDP
80A SRC311 #1
1L1 1T1
316 L1 U 1T1
PUMP 1
317 35 HP 460V
1L2 1T2 46 FLA
318 L2 V 1T2 PUMP 1
319
GND
1L3 1T3
320 L3 W 1T3
GND
321
322
T1
323 1
SHT.6 FLS SENSOR
T2
324 2
325 GND
326
PCB2
327 80A SRC311 #2
2L1 2T1
328 L1 U 2T1
PUMP 2
329 35 HP 460V
2L2 2T2 46 FLA
330 L2 V 2T2 PUMP 2
331
GND
2L3 2T3
332 L3 W 2T3
GND
333
334
T1
335 3
SHT.6 FLS SENSOR
CB1 T2
336 4
13A
337 GND
339
H1 H3 H2 H4
340
XFR
341
2KVA
342 120V
X1 X2 PANEL
343 GROUND
CB3
344 15A GFCI-15A
5 GFCI RECEPTACLE
345
GENERAL USE
346
347
348
CB4
349 5A
TS1
FAN
6 7
350 ENCLOSURE FAN#1
351
TS2
FAN
8
352 ENCLOSURE FAN#2
353
354
HT
ENCLOSURE HEATER
355
200W
FAN
356
357
1
2(WHT)
358
400
400
DESCRIPTION PROJECT
THIS DOCUMENT IS THE PROPRIETARY
DUPLEX SRC311, 35HP, 460V, TYPE 4 PROPERTY OF FLYGT. IT HAS BEEN FURNISHED MARION COUNTY - AURORA, OR
UPON THE CONDITION THAT IT SHALL NOT BE FARGO PUMP LIFT STATION
RELEASED, DUPLICATED, USED OR DISCLOSED IN
WHOLE OR IN PART FOR ANY PURPOSE WITHOUT DESIGN BY DATE REVISION
THE EXPRESS WRITTEN PERMISSION OF FLYGT SDM 11-3-2014 0
AND SHALL BE CONSIDERED CONFIDENTIAL
ORDER NO. / QUOTE NO. INFORMATION. DWG NO. SHEET NO.
/ 081514SM3,4 EDW-CD-XYL-105 3 OF 7
358 358
400
401 1 2(WHT)
402
CB5
403 2A
9
404 9
CB6
405 2A
10
406 10 N1
407
PUMP DISCONNECT PANEL - PDP
408 10 9 N1
409
HT
410
FAN
411
412
413
414 AL4
613
31 33
415 R OVERFLOW LEVEL IND
X1 X2
416
CH.1
42 12 OVERFLOW LEVEL RELAY
417 90 12 12
12
CR1 NO - 420,517,704
FSHH A1 A2
41 11
418 91
14
419 AL5
Hazardous Area 13
420 Class I Groups A,B,C,D R HIGH LEVEL INDICATOR
Class II Groups E,F,G X1 X2
Class III
421
CH.2
52 22 HIGH LEVEL RELAY
422 92 13 13
13
CR2 NO - 421,518,706
FSH A1 A2
51 21
423 93
24
424
23
425
426
ISR
427
428
613
429
430
431
432
433
434
435
CB2
436
10A
437
438
OVERFLOW ALARM
439 SILENCE
CR1
3 21
440
11 14
441 HIGH LEVEL
CR2 CR3 ALARM SILENCE RELAY
442
23
CR3 NO - 421
11 14 11 14 A1 A2 NC - 422
443 SRC 1 FAULT
CR4 CR3
24 AA
444 AUDIBLE ALARM
11 14 12
445 SRC 2 FAULT
AL3
CR5
R
21 25
446 ALARM BEACON
11 14 BLK RED X1 X2
447 FL
448
449
450
451
452
453
454
455
456
457 3 2
458
500 500
DESCRIPTION PROJECT
THIS DOCUMENT IS THE PROPRIETARY
DUPLEX SRC311, 35HP, 460V, TYPE 4 PROPERTY OF FLYGT. IT HAS BEEN FURNISHED MARION COUNTY - AURORA, OR
UPON THE CONDITION THAT IT SHALL NOT BE FARGO PUMP LIFT STATION
RELEASED, DUPLICATED, USED OR DISCLOSED IN
WHOLE OR IN PART FOR ANY PURPOSE WITHOUT DESIGN BY DATE REVISION
THE EXPRESS WRITTEN PERMISSION OF FLYGT SDM 11-3-2014 0
AND SHALL BE CONSIDERED CONFIDENTIAL
ORDER NO. / QUOTE NO. INFORMATION. DWG NO. SHEET NO.
/ 081514SM3,4 EDW-CD-XYL-105 4 OF 7
458 458
500
501 3 2
502
503
504
505
506
507 RUN
RL1
RL2
G
31
508 PUMP 1 RUN LIGHT
17 18 X1 X2
509
511
512
513 AL1
518
519
520
521 RUN
RL2
RL2
G
36
522 PUMP 2 RUN LIGHT
17 18 X1 X2
523
525
526
527 AL2
532
533 OVERFLOW
CR1
HIGH LEVEL RELAY
CR6
38
534
21 24 A1 A2 NO - 602,615
535 HIGH LEVEL
CR2
536
21 24
537
538
539 PL1
544
545
546
547
548
549
550
551
552
553
554
555
556
557 3 2
558
700 700
DESCRIPTION PROJECT
THIS DOCUMENT IS THE PROPRIETARY
DUPLEX SRC311, 35HP, 460V, TYPE 4 PROPERTY OF FLYGT. IT HAS BEEN FURNISHED MARION COUNTY - AURORA, OR
UPON THE CONDITION THAT IT SHALL NOT BE FARGO PUMP LIFT STATION
RELEASED, DUPLICATED, USED OR DISCLOSED IN
WHOLE OR IN PART FOR ANY PURPOSE WITHOUT DESIGN BY DATE REVISION
THE EXPRESS WRITTEN PERMISSION OF FLYGT SDM 11-3-2014 0
AND SHALL BE CONSIDERED CONFIDENTIAL
ORDER NO. / QUOTE NO. INFORMATION. DWG NO. SHEET NO.
/ 081514SM3,4 EDW-CD-XYL-105 5 OF 7
600
601
PUMP DISCONNECT PANEL
602
PDP
SRC311 #1
603 PUMP #1
FLS SENSOR RJ45
T1
604 RES 1 1 WHT 1 +24V
T2 BLK 85
605 2 2 2 EXT BLOCK
609 6 T2 SENSOR
610 7 GND
612 9 GND
428 414
613 10 LVL INPUT(4-20MA)
4-20MA
614 SRC#1
11 ACTIVE PUMP
BRN(-) 42 13 BLK
619 99 (IN+) (OUT+) 81 81 15 RL1-NO
627
628 SRC311 #2
629 PUMP #2
FLS SENSOR RJ45
T1
630 RES 3 3 WHT 1 +24V
T2 BLK 87
631 4 4 2 EXT BLOCK
635 6 T2 SENSOR
636 7 GND
638 9 GND
4-20MA
640 SRC#2
11 ACTIVE PUMP
642 13 STO-
643
644 14 RL1-C
645 15 RL1-NO
647 17 RL2-A
648 18 RL2-B
649
650
651
652
653
654
655
656
657
658
DESCRIPTION PROJECT
THIS DOCUMENT IS THE PROPRIETARY
DUPLEX SRC311, 35HP, 460V, TYPE 4 PROPERTY OF FLYGT. IT HAS BEEN FURNISHED MARION COUNTY - AURORA, OR
UPON THE CONDITION THAT IT SHALL NOT BE FARGO PUMP LIFT STATION
RELEASED, DUPLICATED, USED OR DISCLOSED IN
WHOLE OR IN PART FOR ANY PURPOSE WITHOUT DESIGN BY DATE REVISION
THE EXPRESS WRITTEN PERMISSION OF FLYGT SDM 11-3-2014 0
AND SHALL BE CONSIDERED CONFIDENTIAL
ORDER NO. / QUOTE NO. INFORMATION. DWG NO. SHEET NO.
/ 081514SM3,4 EDW-CD-XYL-105 6 OF 7
558 558
700
CB7
701 2A RADIO ONLY
GFCI RECEPTACLE
702
RADIO USE ONLY
DUPLEX
703 RECEPTACLE
GFI
704
705
706 RADIO
TEST
707
QUICK TALK RADIO
708 (EXISTING)
712
716
720
724
725
726 NOTE:
RADIO TELEMETRY EQUIPMENT
727
SUPPLIED BY OTHERS
728
729
730
731
732
733
734
735
736
737
738
739
740
741
742
743
744
745
746
747
748
749
750
751
752
753
754
755
756
757
758
DESCRIPTION PROJECT
THIS DOCUMENT IS THE PROPRIETARY
DUPLEX SRC311, 35HP, 460V, TYPE 4 PROPERTY OF FLYGT. IT HAS BEEN FURNISHED MARION COUNTY - AURORA, OR
UPON THE CONDITION THAT IT SHALL NOT BE FARGO PUMP LIFT STATION
RELEASED, DUPLICATED, USED OR DISCLOSED IN
WHOLE OR IN PART FOR ANY PURPOSE WITHOUT DESIGN BY DATE REVISION
THE EXPRESS WRITTEN PERMISSION OF FLYGT SDM 11-3-2014 0
AND SHALL BE CONSIDERED CONFIDENTIAL
ORDER NO. / QUOTE NO. INFORMATION. DWG NO. SHEET NO.
/ 081514SM3,4 EDW-CD-XYL-105 7 OF 7
BILL OF MATERIAL
Custom
A/R Din Rail; 1 Meter Connector C103PM
A/R Terminal Block; UK 5N, 30A, 600V Phoenix 3004362
A/R End Block; ENS 35N Phoenix 800886
A/R End Cover; D-UK 4/10 (UK 5 & 6) Phoenix 303020
POWER COMPONENTS
1 MCB Circuit Breaker; 3P, 150A, 18kAIC@480V Square D HDL36150
2 PCB1,2 Circuit Breaker; 3P, 80A, 18kAIC@480V Square D HDL36080
MCB,PCB1
3 ,2 Circuit Breaker; Handle, Door Interlock Square D S29338
CONTROL COMPONENTS
2 RL1,2 Pilot Light, 30mm, Nema 4X, Green, 120V LED, PTT Square D 9001SKT38LGG31
4 AL1,2,4,5 Pilot Light, 30mm, Nema 4X, Red, 120V LED, PTT Square D 9001SKT38LRR31
1 PL1 Pilot Light, 30mm, Nema 4X, White, 120V LED, PTT Square D 9001SKT38LWW31
Push Button, 30mm, Nema 4X, 1NO, Black, Full
2 Guard Square D 9001SKR1BH5
7 CR1-7 Relay, 4PDT, 8A, LED, PTT, 120VAC Coil Schneider RXM4AB2F7
7 CR1-7 Relay, Socket, DIN, Box Lug Schneider RXZE2M114M
Mild Steel
Spec-00290
F63.422.2211
7
763.422.2600
Wall-Mount Enclosures
Standard Product
Body Conductive Panel Size Panel Size Number Data
Catalog Number AxBxC in. AxBxC mm Gauge Panel Panel D x E (in.) D x E (mm) F (in.) F (mm) of Clamps Pocket
A16H12ALP 16.00 x 12.00 x 6.00 406 x 305 x 152 16 A16P12 A16P12G 13.00 x 9.00 330 x 229 1.25 32 4 Small
A16H16ALP 16.00 x 16.00 x 6.00 406 x 406 x 152 16 A16P16 A16P16G 13.00 x 13.00 330 x 330 3.00 76 4 Small
A16H20ALP 16.00 x 20.00 x 6.00 406 x 508 x 152 16 A20P16 A20P16G 17.00 x 13.00 432 x 330 3.00 76 4 Small
A20H16ALP 20.00 x 16.00 x 6.00 508 x 406 x 152 16 A20P16 A20P16G 17.00 x 13.00 432 x 330 3.00 76 4 Small
A20H20ALP 20.00 x 20.00 x 6.00 508 x 508 x 152 16 A20P20 A20P20G 17.00 x 17.00 432 x 432 3.00 76 4 Small
A24H12ALP 24.00 x 12.00 x 6.00 610 x 305 x 152 16 A12P24 A12P24G 9.00 x 21.00 229 x 533 1.25 32 5 Small
A24H16ALP 24.00 x 16.00 x 6.00 610 x 406 x 152 16 A24P16 A24P16G 21.00 x 13.00 533 x 330 3.00 76 5 Small
A24H20ALP 24.00 x 20.00 x 6.00 610 x 508 x 152 16 A24P20 A24P20G 21.00 x 17.00 533 x 432 3.00 76 5 Small
A24H24ALP 24.00 x 24.00 x 6.00 610 x 610 x 152 16 A24P24 A24P24G 21.00 x 21.00 533 x 533 3.00 76 5 Small
A30H20ALP 30.00 x 20.00 x 6.00 762 x 508 x 152 14 A30P20 A30P20G 27.00 x 17.00 686 x 432 3.00 76 5 Small
A30H24ALP 30.00 x 24.00 x 6.00 762 x 610 x 152 14 A30P24 A30P24G 27.00 x 21.00 686 x 533 3.00 76 5 Large
A36H24ALP 36.00 x 24.00 x 6.00 914 x 610 x 152 14 A36P24 A36P24G 33.00 x 21.00 838 x 533 3.00 76 5 Large
A16H12BLP 16.00 x 12.00 x 8.00 406 x 305 x 203 16 A16P12 A16P12G 13.00 x 9.00 330 x 229 1.25 32 4 Small
A20H16BLP 20.00 x 16.00 x 8.00 508 x 406 x 203 16 A20P16 A20P16G 17.00 x 13.00 432 x 330 3.00 76 4 Small
A20H20BLP 20.00 x 20.00 x 8.00 508 x 508 x 203 16 A20P20 A20P20G 17.00 x 17.00 432 x 432 3.00 76 4 Small
A20H24BLP 20.00 x 24.00 x 8.00 508 x 610 x 203 16 A24P20 A24P20G 21.00 x 17.00 533 x 432 3.00 76 4 Small
A24H20BLP 24.00 x 20.00 x 8.00 610 x 508 x 203 16 A24P20 A24P20G 21.00 x 17.00 533 x 432 3.00 76 5 Small
A24H24BLP 24.00 x 24.00 x 8.00 610 x 610 x 203 16 A24P24 A24P24G 21.00 x 21.00 533 x 533 3.00 76 5 Small
A24H30BLP 24.00 x 30.00 x 8.00 610 x 762 x 203 14 A30P24 A30P24G 27.00 x 21.00 686 x 533 3.00 76 7 Small
A30H20BLP 30.00 x 20.00 x 8.00 762 x 508 x 203 14 A30P20 A30P20G 27.00 x 17.00 686 x 432 3.00 76 5 Small
A30H24BLP 30.00 x 24.00 x 8.00 762 x 610 x 203 14 A30P24 A30P24G 27.00 x 21.00 686 x 533 3.00 76 5 Large
A30H30BLP 30.00 x 30.00 x 8.00 762 x 762 x 203 14 A30P30 A30P30G 27.00 x 27.00 686 x 686 3.00 76 7 Large
A36H24BLP 36.00 x 24.00 x 8.00 914 x 610 x 203 14 A36P24 A36P24G 33.00 x 21.00 838 x 533 3.00 76 5 Large
A36H30BLP 36.00 x 30.00 x 8.00 914 x 762 x 203 14 A36P30 A36P30G 33.00 x 27.00 838 x 686 3.00 76 7 Large
A42H30BLP 42.00 x 30.00 x 8.00 1067 x 762 x 203 14 A42P30 A42P30G 39.00 x 27.00 991 x 686 3.00 76 8 Small
A42H36BLP 42.00 x 36.00 x 8.00 1067 x 914 x 203 14 A42P36 A42P36G 39.00 x 33.00 991 x 838 3.00 76 8 Large
A48H36BLP 48.00 x 36.00 x 8.00 1219 x 914 x 203 14 A48P36 A48P36G 45.00 x 33.00 1143 x 838 3.00 76 8 Large
A60H36BLP 60.00 x 36.00 x 8.00 1524 x 914 x 203 14 A60P36 A60P36G 57.00 x 33.00 1448 x 838 3.00 76 9 Large
A20H16CLP 20.00 x 16.00 x 10.00 508 x 406 x 254 14 A20P16 A20P16G 17.00 x 13.00 432 x 330 3.00 76 4 Small
A24H20CLP 24.00 x 20.00 x 10.00 610 x 508 x 254 14 A24P20 A24P20G 21.00 x 17.00 533 x 432 3.00 76 5 Small
A30H24CLP 30.00 x 24.00 x 10.00 762 x 610 x 254 14 A30P24 A30P24G 27.00 x 21.00 686 x 533 3.00 76 5 Large
A36H30CLP 36.00 x 30.00 x 10.00 914 x 762 x 254 14 A36P30 A36P30G 33.00 x 27.00 838 x 686 3.00 76 7 Large
A48H30CLP 48.00 x 30.00 x 10.00 1219 x 762 x 254 14 A48P30 A48P30G 45.00 x 27.00 1143 x 686 3.00 76 8 Small
A48H36CLP 48.00 x 36.00 x 10.00 1219 x 914 x 254 14 A48P36 A48P36G 45.00 x 33.00 1143 x 838 3.00 76 8 Large
A60H36CLP 60.00 x 36.00 x 10.00 1524 x 914 x 254 14 A60P36 A60P36G 57.00 x 33.00 1448 x 838 3.00 76 9 Large
A30H24DLP 30.00 x 24.00 x 12.00 762 x 610 x 305 14 A30P24 A30P24G 27.00 x 21.00 686 x 533 3.00 76 5 Large
A36H30DLP 36.00 x 30.00 x 12.00 914 x 762 x 305 14 A36P30 A36P30G 33.00 x 27.00 838 x 686 3.00 76 7 Large
A48H36DLP 48.00 x 36.00 x 12.00 1219 x 914 x 305 14 A48P36 A48P36G 45.00 x 33.00 1143 x 838 3.00 76 8 Large
A36H30FLP 36.00 x 30.00 x 16.00 914 x 762 x 406 14 A36P30 A36P30G 33.00 x 27.00 838 x 686 3.00 76 7 Large
A48H36FLP 48.00 x 36.00 x 16.00 1219 x 914 x 406 14 48P36 A48P36G 45.00 x 33.00 1143 x 838 3.00 76 8 Large
A60H36FLP 60.00 x 36.00 x 16.00 1524 x 914 x 406 14 A60P36 A60P36G 57.00 x 33.00 1448 x 838 3.00 76 9 Large
Purchase panels separately. Optional stainless steel, conductive, composite and aluminum panels are available for most sizes.
A60H36FLP3PT
1 Mild Steel SUBJECT TO CHANGE WITHOUT NOTICE EQUIPMENT PROTECTION
Spec-00290 F
Wall-Mount Enclosures Type 4 Wall-Mount Enclosures
Popular Accessories
Enclosure Width (B Dimension) Hole Seals Window Kits
12 in. (305 mm) AS050 APWK53NF
16 in. (406 mm) AS050 APWK53NF
20 in. (508 mm) AS050 APWK53NF
24 in. (610 mm) AS050 APWK53NF
30 in. (762 mm) AS050 APWK53NF
36 in. (914 mm) AS050 APWK53NF
INDUSTRY STANDARDS
Product maintains UL/CSA Type 4, 4X (stainless steel only) and
Type 12 when properly installed on Hoffman Type 4 or Type 12
enclosures.
APPLICATION
Kits are easily installed on most wall-mount Hoffman enclosures.
Can also be used to elevate Hoffman free-stand enclosures.
To install, drill holes in the bottom of the enclosure and bolt the
floor stands to the enclosure.It is not necessary to remove the wall-
mount brackets from the enclosure.
SPECIFICATIONS
12 gauge steel floor stand has an ANSI 61 gray polyester powder
finish over pretreated surfaces. Stainless steel floor stand is
available in Type 316 and Type 304.
COMPONENTS
Each kit includes two stands. Two sets of floor stands are
recommended for enclosures larger than double door free-stand
enclosures.
Catalog Number Material Height, H (in.) Height, H (mm) Width, C (in.) Width, C (mm) L (in.) L (mm)
AFK0608 Steel 6.00 152 8.06 205 7.06 179
AFK0610 Steel 6.00 152 10.06 256 7.06 179
AFK0612 Steel 6.00 152 12.06 306 7.06 179
AFK0618 Steel 6.00 152 18.06 459 7.06 179
AFK1208 Steel 12.00 305 8.06 205 8.12 206
AFK1210 Steel 12.00 305 10.06 256 8.12 206
AFK1212 Steel 12.00 305 12.06 306 8.12 206
AFK1216 Steel 12.00 305 16.06 408 8.12 206
AFK1218 Steel 12.00 305 18.13 461 8.12 206
AFK1220 Steel 12.00 305 20.06 510 8.12 206
AFK1808 Steel 18.00 457 8.06 205 9.17 233
AFK1810 Steel 18.00 457 10.06 256 9.17 233
AFK1812 Steel 18.00 457 12.06 306 9.17 233
AFK1816 Steel 18.00 457 16.06 408 9.17 233
AFK2408 Steel 24.00 610 8.06 205 10.23 260
AFK2410 Steel 24.00 610 10.06 256 10.23 260
AFK2412 Steel 24.00 610 12.06 306 10.23 260
AFK2416 Steel 24.00 610 16.06 408 10.23 260
AFK0608SS Stainless Steel, 304 6.00 152 8.06 205 9.09 231
AFK0610SS Stainless Steel, 304 6.00 152 10.06 256 9.09 231
AFK0612SS Stainless Steel, 304 6.00 152 12.06 306 9.09 231
AFK0618SS Stainless Steel, 304 6.00 152 18.06 459 9.09 231
AFK0624SS Stainless Steel, 304 6.00 152 24.06 611 9.09 231
AFK1208SS Stainless Steel, 304 12.00 305 8.06 205 9.09 231
AFK1210SS Stainless Steel, 304 12.00 305 10.06 256 9.09 231
AFK1212SS Stainless Steel, 304 12.00 305 12.06 306 9.09 231
AFK1216SS Stainless Steel, 304 12.00 305 16.06 408 9.09 231
AFK1218SS Stainless Steel, 304 12.00 305 18.06 459 9.09 231
AFK1224SS Stainless Steel, 304 12.00 305 24.06 611 9.09 231
AFK1808SS Stainless Steel, 304 18.00 457 8.06 205 9.09 231
AFK1810SS Stainless Steel, 304 18.00 457 10.06 256 9.09 231
AFK1812SS Stainless Steel, 304 18.00 457 12.06 306 9.09 231
AFK1816SS Stainless Steel, 304 18.00 457 16.06 408 9.09 231
AFK1818SS Stainless Steel, 304 18.00 457 18.06 459 9.09 231
AFK1824SS Stainless Steel, 304 18.00 457 24.06 611 9.09 231
AFK2408SS Stainless Steel, 304 24.00 610 8.06 205 9.09 231
AFK2410SS Stainless Steel, 304 24.00 610 10.06 256 9.09 231
AFK2412SS Stainless Steel, 304 24.00 610 12.06 306 9.09 231
3 Accessories SUBJECT TO CHANGE WITHOUT NOTICE EQUIPMENT PROTECTION
Spec-00484 J
Mounting Accessories Mounting Kits
Catalog Number Material Height, H (in.) Height, H (mm) Width, C (in.) Width, C (mm) L (in.) L (mm)
AFK2416SS Stainless Steel, 304 24.00 610 16.06 408 9.09 231
AFK2418SS Stainless Steel, 304 24.00 610 18.06 459 9.09 231
AFK2424SS Stainless Steel, 334 24.00 610 24.06 611 9.09 231
AFK0608SS6 Stainless Steel, 316 6.00 152 8.06 205 9.09 231
AFK0610SS6 Stainless Steel, 316 6.00 152 10.06 256 9.09 231
AFK0612SS6 Stainless Steel, 316 6.00 152 12.06 306 9.09 231
AFK0618SS6 Stainless Steel, 316 6.00 152 18.06 459 9.09 231
AFK0624SS6 Stainless Steel, 316 6.00 152 24.06 611 9.09 231
AFK1208SS6 Stainless Steel, 316 12.00 305 8.06 205 9.09 231
AFK1210SS6 Stainless Steel, 316 12.00 305 10.06 256 9.09 231
AFK1212SS6 Stainless Steel, 316 12.00 305 12.06 306 9.09 231
AFK1216SS6 Stainless Steel, 316 12.00 305 16.06 408 9.09 231
AFK1218SS6 Stainless Steel, 316 12.00 305 18.06 459 9.09 231
AFK1224SS6 Stainless Steel, 316 12.00 305 24.06 611 9.09 231
AFK1808SS6 Stainless Steel, 316 18.00 457 8.06 205 9.09 231
AFK1810SS6 Stainless Steel, 316 18.00 457 10.06 256 9.09 231
AFK1812SS6 Stainless Steel, 316 18.00 457 12.06 306 9.09 231
AFK1816SS6 Stainless Steel, 316 18.00 457 16.06 408 9.09 231
AFK1818SS6 Stainless Steel, 316 18.00 457 18.06 459 9.09 231
AFK1824SS6 Stainless Steel, 316 18.00 457 24.06 611 9.09 231
AFK2408SS6 Stainless Steel, 316 24.00 610 8.06 205 9.09 231
AFK2410SS6 Stainless Steel, 316 24.00 610 10.06 256 9.09 231
AFK2412SS6 Stainless Steel, 316 24.00 610 12.06 306 9.09 231
AFK2416SS6 Stainless Steel, 316 24.00 610 16.06 408 9.09 231
AFK2418SS6 Stainless Steel, 316 24.00 610 18.06 459 9.09 231
AFK2424SS6 Stainless Steel, 316 24.00 610 24.06 611 9.09 231
C-103-PM Prepunched Aluminum DIN Rail (1 Meter Lengths) ES, GT, MT, OT, ST
(note: Other lengths available, consult factory)
39.370 [1000.00]
1.083[27.50] 1.378[35.00]
TYP. .287[7.29]
R.
1.378[35.00]
.943[23.95] 1.063[27.00]
.177[4.50]
.984[25.00]
C-104-PM Prepunched Steel DIN Rail (1 Meter Lengths) ES, GT, MT, OT, ST
(note: Other lengths available, consult factory)
39.370[1000.00]
.295[7.50]
.492[12.50] .984[25.00]
R.
1.378[35.00] 1.063[27.00]
.205[5.20]
.709[18.00]
C-105-PM Prepunched Steel DIN Rail (1 Meter Lengths) ES, GT, MT, OT, ST
(note: Other lengths available, consult factory)
39.370[1000.00] .590[15.00]
.039[1.00]
.492[12.50] .984[25.00]
R.
.709[18.00]
C-106-2PM Prepunched Steel DIN Rail (2 Meter Lengths) ES, GT, MT, OT, ST
(note: Other lengths available, consult factory)
78.740[2000.00]
.984[25.00] .295[7.50]
.492[12.50]
R.
.709[18.00]
Features/Benefits:
•• Finger-safe protection
Fully insulated block ensures touch safe isolation of live parts. Recessed
termination screws and wire openings provide IP20 grade protection and
qualify as “finger-safe” per IEC 529
•• Compact modularity
Ratings:
Single or multiple pole configurations in the most compact foot rint. Allows
Volts : 600V
users to build smaller or higher density panels.
Amps: : 175 to 840A
•• Snap on DIN-rail mounting
SCCR : 100kA with proper fuse.
Sizes 1 to 4 feature integral DIN rail adaptors allowing for quick and easy
installations on 35mm DIN rail yielding lower installed costs.
Contact Technical Services for
•• Captive termination screws
instruction sheet and/or DC
Unique channel design ensures captive metric wire termination screws.
Ratings.
Screws can never be lost.
•• Available accessories
For multi-pole panel mounting, simply snap in pins for rigid fi . Cap plugs
provide the ability to maintain touch safety on unused openings. Circuit
identification markers simply snap into blocks to ID circuits. nd anchors
provide rigid end stops.
•• Multiple wire ratings Approvals:
Provide users more versatility by offering capability of using multiple •• UL Recognized Component
conductors in #2 and 2/0 openings. Guide XCFR2, File E73571
•• AC & DC ratings •• CSA Certified: Class 6228, Fil
FSPDB1, 2, and 3 have been evaluated for use at 1000V (AC or DC) 69363
provided they are installed on DIN-rails only and with barriers between
poles of opposite polarity of sufficient size to maintain requi ed spacings.
I2
FSPDB Finger-Safe Power Distribution Blocks
Catalog Numbers
Catalog Number Ampere Line Load
Short
Aluminum Copper Rating Wire Range Wire Range
(Based on NEC
Circuit
Openings
(Connector (Connector Table 310-16 for AWG/ Current
rated for 90° C rated for 75° C 75° C Cu wire AWG/ mm2 Openings mm2 Per Pole
kcmil Rating
Cu/AL wire) Cu wire only) only)
Dimensions Accessories
FSPDB1A FSPDB2A FSPDB3A FSPDB4A FSPDB5A Catalog No. Description
FSPDB1C FSPDB2C FSPDB3C FSPDB4C FSPDB5C Accessory pin to form multiple pole
Dimension FSPIN1
block
I
Figure 1 Figure 1 Figure 2 Figure 1 Figure 2
mm in mm in mm in mm in mm in Circuit identification marker for 2/0 &
FSCIM1
#2 max. conductors (Qty of 100)
A 25.4 1.00 28.4 1.12 46.9 1.85 39 1.54 72 2.84
Circuit identification marker for 350,
B 43.3 1.70 57.8 2.28 64.3 2.53 108 4.25 91 3.58
FSCIM2 400 & 600 kcmil max. conductors (Qty
C 49.5 1.95 56.0 2.21 64.3 2.53 80 3.15 80 3.15
of 100)
D 45.1 1.78 51.6 2.03 59.8 2.36 75.5 2.97 - -
FSCAP1 Cap plug for spare 2/0 openings
E 39.4 1.55 39.4 1.55 51.5 2.03 50.1 1.97 50.1 1.97
FSCAP2 Cap plug for spare 350 kcmil openings
F 72.6 2.86 87.7 3.45 100.8 3.97 145.5 5.73 145 5.71
FSCP3 Cap plug for spare 600 kcmil opening
G 59.6 2.35 74.6 2.94 82.4 3.24 120.6 4.75 127.5 5.02
FSEA Pair of end anchors
H 5.3 0.21 5.1 0.20 6.5 0.26 7 0.28 3 0.12
I - - - - 31.5 1.24 - - 52 2.04
J 5.3 0.21 6.4 0.25 6.5 0.26 6.5 0.26 6.5 0.26
K 10 0.40 11.7 0.46 8.9 0.35 16 0.63 8.5 0.34
H
I
K H
Figure 1 Figure 2
K
G G
B
F B
F
E J
D E J
A
D
C A
C
For the most current product performance data visit us-ferrazshawmut.mersen.com and use catalog search. I3
Electric Heaters
Rev. A October 2004
Construction Installation
• Attractive and durable housing is anodized
aluminum
• Thermostat, standard on all units, is adjustable CAUTION
from 0°F to 100°F (-18°C to 38°C)
• Fan draws cool air from the bottom of the These electric heaters are not designed for
enclosure and passes this air across the use in dusty, dirty, corrosive, or hazardous
thermostat and heating elements before locations.
being released into enclosure cavity Portions of the heater can get hot. Adequate
• Heated air is discharged through the top of protection must be taken to protect people
the heater unit from potential burns, and to protect other
• Four 10-32 self-tapping screws are included components from this heat.
with each heater Hoffman recommends this heater only be
• Ball bearing fan runs continuously for even installed in a totally-enclosed metal
temperature distribution enclosure.
• Terminal strip with clamp connector that Do not install heaters on wood panels.
accepts both solid and stranded wire
Finish
Hoffman electric heaters should be centered as
Brushed aluminum. low as possible on an interior enclosure panel.
This permits the unit to heat the cool air
Application Industry Standards located at the bottom of the enclosure. For
maximum efficiency and longevity, the heater
Designed to protect sensitive mechanical, UL Component Recognized should be mounted in a vertical position with
electrical, and electronic equipment from the CSA Listed the terminal block to the bottom and the air
harmful effects of condensation, corrosion, and CE outlet openings at the top in a sealed
low temperatures.Thermostatically controlled enclosure free from dust or debris. However,
fan-driven heater units maintain a stable the unit will also effectively distribute heat if
temperature within enclosures so critical turned 90 degrees with the terminal block out
components can perform more reliably over the bottom and the air outlet at the side.
a longer period of time. Although enclosure panels are preferable,
heaters may be installed on any flat sheet metal
surface. Do not install heaters on wood panels.
Heat sensitive components should not be
placed near the heater discharge area since this
air can be quite warm.The clearance range
defines the space that must be kept free of
these components for proper and safe
operation of the heater.
9.46 Data subject to change without notice ☎ 763 422 2211 FAX 763 422 2600 ©2003 Hoffman Enclosures Inc.
Bulletin
D85
Heaters
■ Dimensions and Clearance Range for
DAH1001A, -2A and DAH2001A, -2A
Electric Heaters
■ Dimensions and Clearance Range for
DAH4001B, -2B and DAH8001B, -2B
Data subject to change without notice ☎ 763 422 2211 FAX 763 422 2600 ©2003 Hoffman Enclosures Inc. 9.47
KT 011 Small Thermostat
Compact design
Wide adjustment range
Color coded temperature dials
DIN rail mountable
Regulating
Thermostat opens on temperature rise - for regulating heaters or for switching signal devices.
Comes with red temperature dial.
|
Technical Data
KT 011 Thermostat Heater KT 011 Thermostat e.g. Fan KT 011 Thermostat e.g. Signal Device
Specifications are subject to change without notice. Suitability of this product for its intended use and any associated risks must be determined by the end customer/ buyer in its final application.
STEGO, Inc. · 1395 South Marietta Parkway · Building 800 · Marietta, GA 30067 · Tel: (770) 984-0858 · Fax: (770) 984-0615
Toll free: 1-888-783-4611 (US & Canada only) · www.stegousa.com
Filter Fan
Metric measurements for this product are exact, imperial measurements are rounded to the nearest whole number
Filter fan unit ready for installation, NEMA 12 / IP 54 standard German Registered Design T2
H2
additional fine filter mat and hose- CE - 3527009
H1
proof hood UL/cUL - 76083 B1
Industrial Buyers Guide For additional technical information visit www.rittal-corp.com 209
Accessories
Filter mats for air conditioners Material:
Rittal cooling units are low-maintenance and are Open-celled polyurethane foamed plastic with
supplied without filter mats. Filter mats may be excellent physical and mechanical properties.
used for extreme conditions. Temperature-resistant from -40 to 176° F
(-40 to +80° C).Thickness: 0.4" (10 mm)
272 Inch and pound measurements are rounded to the nearest whole number Industrial Buyers Guide
PowerPact™ H-, J-, and L-Frame Circuit Breakers
Catalog Numbering
The PowerPact™ H-, J-, and L-frame circuit breakers are designed to protect electrical systems from
damage caused by overloads and short circuits. H- and J-frame circuit breakers are available with
either thermal-magnetic or Micrologic™ electronic trip units. L-frame circuit breakers are available with
Micrologic electronic trip unit.
Catalog Numbering
– J L L 3 6 250 T – ––––
Accessory Suffix Code (See Table 2)
Frame Poles Amperage
I-Line™ Phasing
H H-Frame 2 2P 060 60 A
Trip Unit — ABC (3P)
J J-Frame 3 3P 100 100 A
6 CBA (3P)
L L-Frame 4 4P 150 150 A Micrologic Electronic Trip Units 1 AB (2P)
250 250 A
Terminations U31 LI Standard Protection 2 AC (2P)
400 400 A
Brand U33 LSI Standard Protection 3 BA (2P)
L Lugs Line/Load Side 600 600 A
_ Square D U43 LSI plus Ammeter 4 BC (2P)
M Lugs Line Side 000 Switch or
N Schneider Frame only U44 LSIG plus Ammeter 5 CA (2P)
P Lugs Load Side
Electric U53 LSI plus Energy Management 6 CB (2P)
F Bus Bar Voltage
A I-Line U54 LSIG plus Energy Management
S Rear Connected 6 600 Vac M37 Magnetic Only (L-Frame Only)
N Plug-in M38 Motor Protector Circuit Breaker Standard
D Drawout S40 400 A Molded Case Switch (L-Frame Automatic Switch)
K Reverse I-Line S60 600 A Molded Case Switch (L-Frame Automatic Switch)
F40 400 A L-Frame Only (No Trip Unit)
F60 600 A L-Frame Only (No Trip Unit)
Performance Level (kA) (See Table 1)
Thermal-Magnetic Trip Units
— Standard Fixed Trip Unit (Suitable for reverse connection)
F06 60 A H-Frame Only (No trip unit)
F15 150 A H-Frame Only (No trip unit)
F25 250 A J-Frame Only (No trip unit)
T Complete Circuit Breaker (Frame + removable trip unit)
S15 150 A Molded Case Switch (H-Frame automatic switch)
S17 175 A Molded Case Switch (J-Frame automatic switch)
S25 250 A Molded Case Switch (J-Frame automatic switch)
C 100% Rated Continuous Current Rating1
M71 30 A H-Frame Motor Circuit Protector (MCP)
M72 50 A H-Frame Motor Circuit Protector (MCP)
M73 100 A H-Frame Motor Circuit Protector (MCP)
M74 150 A H-Frame Motor Circuit Protector (MCP)
M75 250 A J-Frame Motor Circuit Protector (MCP)
D81 500 Vdc 150–175 A J-Frame Molded Case Circuit Breaker
D82 500 Vdc 200–250 A J-Frame Molded Case Circuit Breaker
R 100% Rated Continuous Current Rating Complete Circuit Breaker
(Frame + removable trip unit)
8
11/2011 ™ © 2011 Schneider Electric
All Rights Reserved
PowerPact™ H-, J-, and L-Frame Circuit Breakers
Circuit Breakers
Table 14: PowerPact H-Frame 150 A Unit-Mount Thermal-Magnetic Circuit Breakers (600 Vac, 250 Vdc) with Factory
Sealed Trip Unit (Suitable for Reverse Connection)
25
© 2011 Schneider Electric ™ 11/2011
All Rights Reserved
PowerPact™ H-, J-, and L-Frame Circuit Breakers
Accessories and Auxiliaries
Installation The directly mounted rotary operating handle replaces the circuit breaker front accessory cover (secured by screws).
O/OFF
trip
(Open)
• Standard with black handle
Models • VDE type with red handle and yellow bezel for machine tool control
Accessories transform the standard direct rotary handle for the following situations:
• Motor control centers (MCCs):
Directly Mounted Rotary – Opening of door prevented when circuit breaker is on
Variations – Closing of circuit breaker inhibited when door is open
Operating Handle
• Machine tool control; complies with CNOMO E03.81.501N; degree of protection IP54
• Early make or early break contacts may be installed into direct mount rotary handle
Standards The directly-mounted rotary operating handle is UL Listed under file E103955 and CSA Certified under file LR 69561
Standards The door-mounted rotary operating handle is UL Listed under file E103955 and CSA Certified under file LR 69561
104
11/2011 ™ © 2011 Schneider Electric
All Rights Reserved
PowerPact™ H-, J-, and L-Frame Circuit Breakers
Accessories and Auxiliaries
Installation • A mounting plate that provides a rotary actuator for a standard toggle circuit breaker
• Handle assemblies available for NEMA 3, 3R, 4, and 4X
• Available in standard or short (3 in.) handle assemblies
The door mounted operating handle makes it possible to operate circuit breakers installed in enclosure from the front.
Operation Provides ON (I) and OFF (O) indication
The circuit breaker may be locked in the off position
The shaft length is the distance between the back of the circuit breaker and the door:
105
© 2011 Schneider Electric ™ 11/2011
All Rights Reserved
Multi 9™ Miniature Circuit UL 489 C60 480 Vac and UL489A C60 Miniature Circuit Breakers
Breakers Class 860 / Refer to Catalog 0860CT0201
www.schneider-electric.us
CIRCUIT BREAKERS
6 MGN61372 168.00 MGN61383 357.00 MGN61394 519.00 MGN61405 168.00 MGN61416 357.00 MGN61427 519.00
8 MGN61373 168.00 MGN61384 357.00 MGN61395 519.00 MGN61406 168.00 MGN61417 357.00 MGN61428 519.00
10 MGN61374 168.00 MGN61385 357.00 MGN61396 519.00 MGN61407 168.00 MGN61418 357.00 MGN61429 519.00
15 MGN61375 168.00 MGN61386 357.00 MGN61397 519.00 MGN61408 168.00 MGN61419 357.00 MGN61430 519.00
20 MGN61376 168.00 MGN61387 357.00 MGN61398 519.00 MGN61409 168.00 MGN61420 357.00 MGN61431 519.00
Multi 9 C60 UL 489A Listed Miniature Circuit Breakers for DC Telecommunication Applications
A limited range of C60 products are UL Listed as UL 489A circuit breakers for protection of DC telecommunications circuits.
Table 7.29: UL 489A Circuit Breakers for DC Telecommunications Applications
(1P, 2 Modules, C curve)
7
Rating (A) Cat. No. $ Price Rating (A) Cat. No. $ Price
0.5 60406 120.00 10 60414 101.00
1 60407 101.00 13 60415 101.00
2 60408 101.00 15 60416 101.00
3 60409 101.00 20 60417 101.00
4 60410 101.00 30 60418 101.00
5 60411 101.00 40 60419 111.00
6 60412 101.00 50 60420 117.00
8 60413 101.00 60 60421 123.00
UL 489/CSA C22.2 No.5 Listed 240 Vac C60 Circuit Breakers (AC)
A selected range of Multi-9 circuit breakers rated 240 V are UL 489/CSA C22.2 No.5 Listed. Unlike UL
1077 Supplementary Protectors, these UL 489/CSA C22.2 No.5 circuit breakers can be used for
branch circuit protection as required by the National Electrical Code.
As shown in tables Table 5 and Table 6, the UL 489/CSA C22.2 No.5 Listed products are available in
C and D curves. They include devices ranging from 0.5 to 35 A.
1P 2P 3P
Table 4: Specifications for UL 489/CSA C22.2 No.5 240 V Listed C60 Circuit Breakers
High Voltage Withstand 6 kV
Rating UL 486A File No. E216919 (Use with Copper Wire Only)
0.5–25 A: 14–4 AWG (2–25 mm2) Cables
Connector: Box Lug Torque to 22 lb-in. (2.48 N•m)
Connection
30–35 A: 14–2 AWG (1–35 mm2) Cables
Torque to 31 lb-in. (3.52 N•m)
Use Single UL Listed or CSA Certified Screw dia. 0.2 in. (5 mm)
Connector: Ring Tongue Insulated Ring Tongue Only Torque to 18 lb-in. (2.03 N•m)
Max Ring Terminal Width 0.54 in. (14 mm)
Mounting 35 mm DIN rail
Case IP40 as per IEC 529
Degree of Protection
Terminals IP20
Calibration 25°C (77°F)
Temperatures Storage -40 to 80°C (-40 to 176°F)
Operating -30 to 70°C (-22 to 158°F)
MN Undervoltage Trip
Plug-On Auxiliary Modules with MX + OF Shunt Trip/Auxiliary Switch
Mechanical Linkage: OF Auxiliary Switch
SD Alarm Switch
Tropicalization Treatment 2 Relative Humidity: 95% at 131°F (55°C)
Number of Operating Cycles Electrical (O-C) 6,000 load, 4,000 no-load
See specifications Table 2 for dimensions, weights and interrupting ratings
Standard Features
• Fast closing: Allows increased withstand to the high inrush currents of some loads.
• Trip-free mechanism: Contacts cannot be held in the I-ON position when the C60 circuit breaker is
tripped automatically.
• Positive indication of contact disconnect. Green mechanical indication on front face of circuit
breaker shows that all poles are open.
• C curve: Overcurrent protection for all application types. Magnetic release operates from 7 to 10
times ampere rating (7 to 14 for DC applications).
16
07/2010 © 2002–2010 Schneider Electric
All Rights Reserved
Multi 9™ System Catalog
Section 2—UL and CSA Rated Protection Devices
• D curve: Overcurrent protection for loads with high inrush currents (motors, transformers).
Magnetic release operates between 10 and 14 times ampere rating (no dc rating for D curve).
• Suitable for reverse feeding.
• Allows locking in O-OFF position using padlock attachment.
Connections
Three versions of field wiring connectors are available for the 240 Vac UL 489/CSA C22.2 No.5 Listed
devices:
• Box lug, meeting UL 486A requirements
• Ring tongue terminal with 5 mm screw
• Ring Tongue terminals with Fingersafe (IP20) shrouds
The circuit breakers can be ordered with the following combinations of connectors:
• Line terminal box lug/load terminal box lug
• Line terminal ring tongue/load terminal ring tongue (for fingersafe version, add -F suffix to catalog
number)
Figure 5: Connection Options for 240 Vac UL 489/CSA C22.2 No.5 Listed Devices
Fingersafe
Ring
Box Lug Ring
Tongue
Tongue
Fingersafe
Ring
Box Lug Ring
Tongue
Tongue
Standards
17
© 2002–2010 Schneider Electric 07/2010
All Rights Reserved
Multi 9™ System Catalog
Section 2—UL and CSA Rated Protection Devices
Catalog Numbers
Table 5: Catalog Numbers for C Curve, UL 489/CSA C22.2 No.5 Listed 240 Vac C60
Miniature Circuit Breakers (Box Lug and Ring Tongue Terminal Combinations)
Rating 1P 2P 3P
Box/Box Ring/Ring1 Box/Box Ring/Ring1 Box/Box Ring/Ring1
0.5 A 60100 60200 60134 60234 — —
1A 60101 60201 60135 60235 60168 60268
1.5 A 60102 60202 60136 60236 60169 60269
2A 60103 60203 60137 60237 60170 60270
3A 60104 60204 60138 60238 60171 60271
4A 60105 60205 60139 60239 60172 60272
5A 60106 60206 60140 60240 60173 60273
6A 60107 60207 60141 60241 60174 60274
7A 60108 60208 60142 60242 60175 60275
8A 60109 60209 60143 60243 60176 60276
10 A 60110 60210 60144 60244 60177 60277
13 A 60111 60211 60145 60245 60178 60278
15 A 60112 60212 60146 60246 60179 60279
20 A 60113 60213 60147 60247 60180 60280
25 A 60114 60214 60148 60248 60181 60281
30 A 60115 60215 60149 60249 60182 60282
35 A 60116 60216 60150 60250 60183 60283
1
IP-20 Fingersafe ring tongue terminals may be ordered with an F suffix (example: 60210F)
Table 6: Catalog Numbers for D Curve, UL 489/CSA C22.2 No.5 Listed 240 Vac C60
Miniature Circuit Breakers (Line/Load as Box Lug or Ring Tongue Terminals)
Rating 1P 2P 3P
Box/Box Ring/Ring1 Box/Box Ring/Ring1 Box/Box Ring/Ring1
0.5 A 60117 60217 60151 60251 — —
1A 60118 60218 60152 60252 60184 60284
1.5 A 60119 60219 60153 60253 60185 60285
2A 60120 60220 60154 60254 60186 60286
3A 60121 60221 60155 60255 60187 60287
4A 60122 60222 60156 60256 60188 60288
5A 60123 60223 60157 60257 60189 60289
6A 60124 60224 60158 60258 60190 60290
7A 60125 60225 60159 60259 60191 60291
8A 60126 60226 60160 60260 60192 60292
10 A 60127 60227 60161 60261 60193 60293
13 A 60128 60228 60162 60262 60194 60294
15 A 60129 60229 60163 60263 60195 60295
20 A 60130 60230 60164 60264 60196 60296
25 A 60131 60231 60165 60265 60197 60297
30 A 60132 60232 60166 60266 60198 60298
35 A 60133 60233 60167 60267 60199 60299
1
IP-20 Fingersafe ring tongue terminals may be ordered with an F suffix (example: 60210F)
NOTE: UL 489/CSA C22.2 No.5 Listed Multi 9 circuit breakers are calibrated at 25°C (77°F). Please
refer to the rating tables (page 83) for applications at temperatures greater than 25°C (77°F).
NOTE: The NEC requires that the continuous load applied to the circuit breaker shall not exceed 80%
of the circuit breaker ampere rating.
18
07/2010 © 2002–2010 Schneider Electric
All Rights Reserved
F Section 4/27/05 2:08 PM Page 4
GFCI
®
Hospital & Commercial Grade GFCI Devices
LEVITON LEVITON
LEVITON LEVITON
CLASS A CLASS A
CLASS A CLASS A
AC ONLY
20 AMP
20 AMP
20 AMP
GFCI
GFCI
GFCI
GFCI
SWITCH
4.21 (106.93 mm)
4.21 (106.93 mm)
4.21 (106.93 mm)
O
2.7 (68.6 mm)
2.7 (68.6 mm)
125V 60HZ
TEST MONTHLY
TEST MENSUEL
TEST MONTHLY
TEST MONTHLY
TEST MENSUEL
TEST MENSUEL
FOLLOW DIRECTIONS
RESET
SUIVEZ INSTRUCTION
1000W 120V
FOLLOW DIRECTIONS
FOLLOW DIRECTIONS
RESET RESET
SUIVEZ INSTRUCTION
SUIVEZ INSTRUCTION
TEST MONTHLY
TEST MENSUEL
RESET
RESET
FOLLOW DIRECTIONS
SUIVEZ INSTRUCTION
RESET RESET
RESET
TEST
CLASS A
SWITCH
CLASS
CLASS
CLASS
OFF
125V
125V
125V
1.12 (28 mm) 1.12 (28 mm) 1.12 (28 mm) 1.12 (28 mm)
8590 SERIES
1.53 (38.9 mm) 1.7 (43.2 mm)
8299 SERIES
1.53 (38.9 mm)
3 To learn more about Leviton devices or for answers to technical questions call our Techline at 1-800-824-3005 or visit us at: www.leviton.com
Product Data Sheet 9070FSC2
TERM COVER (10 kits/package)
Technical
Characteristics
As standards, specifications, and designs change from time to time, please ask for confirmation of the information given in this document.
Dimensions
VA Catalog Acc. A B C E F Slots
Figure
UL CE Number Key IN mm IN mm IN mm IN mm IN mm IN mm
25 25 9070T25D1 1 I 3.09 79 3.00 76 2.58 66 2.00 51 2.50 64 0.20 x 0.38 5 x 10
50 50 9070T50D1 1 I 3.09 79 3.00 76 2.58 66 2.00 51 2.50 64 0.20 x 0.38 5 x 10
75 75 9070T75D1 1 I 3.34 85 3.38 86 2.89 73 2.38 61 2.81 71 0.20 x 0.48 5 x 12
100 100 9070T100D1 1 I 3.34 85 3.38 86 2.89 73 2.38 61 2.81 71 0.20 x 0.48 5 x 12
150 150 9070T150D1 1 I 3.59 91 3.75 95 3.20 81 2.88 73 3.13 80 0.20 x 0.38 5 x 10
200 200 9070T200D1 1 I 3.59 91 3.75 95 3.20 81 2.88 73 3.13 80 0.20 x 0.38 5 x 10
250 160 9070T250D1 2 I 5.30 135 3.75 95 3.21 82 2.88 73 3.13 80 0.20 x 0.38 5 x 10
300 200 9070T300D1 2 I 4.74 120 4.50 114 3.84 98 2.56 65 3.75 95 0.20 x 0.38 5 x 10
350 250 9070T350D1 2 I 5.11 130 4.50 114 3.84 98 3.00 76 3.75 95 0.20 x 0.38 5 x 10
500 300 9070T500D1 2 I 5.49 139 4.50 114 3.84 98 3.56 90 3.75 95 0.20 x 0.38 5 x 10
750 500 9070T750D1 2 I 5.61 143 5.25 133 4.51 115 3.43 87 4.38 111 0.28 x 0.56 7 x 14
1000 630 9070T1000D1 2 I 6.30 160 5.25 133 4.51 115 4.31 109 4.38 111 0.28 x 0.56 7 x 14
1500 1000 9070T1500D1 2 I 5.92 150 7.06 179 6.17 157 4.13 105 5.81 148 0.28 x 0.56 7 x 14
2000 1500 9070T2000D1 2 I 7.17 182 7.06 179 6.17 157 4.56 116 5.81 148 0.28 x 0.56 7 x 14
3000 2000 9070T3000D1 3 I 7.24 184 9.00 229 8.75 222 4.63 118 7.63 194 0.44 x 1.13 11 x 29
5000 3000 9070T5000D1 3 I 9.15 232 9.00 229 8.75 222 6.56 167 7.63 194 0.44 x 1.13 11 x 29
D B
D A D
A B A B
C C
C
F E F E
F E
8
© 1999–2005 Schneider Electric All Rights Reserved 08/2005
Technical Specification
SRC311 v.3.0TS
Technical Specification
Technical Specification
Product design
The SRC 311 is a pump drive with the SmartRun™ functionality, which is dedicated for
wastewater pump stations. The drive is one of the components that is included in a pump
system solution for pump stations. The system consists of a level sensor, a level switch,
and the drive that controls and monitors the pumps in the pump station. The system is
reliable, energy efficient, and does not need extra monitor or control devices. The system
can include up to three drives and pumps with alternation and full redundancy.
Approval
SRC 311 version Approvals
200–240V CE, cUL
380–480V CE, cUL
500–600V CE, cUL, CSA
Facility requirements
Check that the following requirements are met:
Environment
The drive must be protected from direct sunlight and from rainfall.
Altitude
Maximum altitude for non-de-rated operation is 1000 m (3281 ft).
Maximum altitude with UL approval is 2000 m (6562 ft).
Maximum altitude without UL approval is 4000 m (13 123 ft).
Ambient temperature
Activity °C (°F)
Operation –10 – 40 (14 – 104)
De-rated operation Maximum 50 (122)
Storage –40 – 60 (–40 – 140)
Humidity requirements
The relative humidity must not exceed 95% (non-condensing).
Air requirements
The air surrounding the unit must be free from:
• Excessive dust
• Acids
• Salt
Conformal coating is applied according to IEC standard 60721–3–2, Class 3C2.
Input voltage
Depending upon the model and power rating, the drives are designed for direct
connection to the following supplies
All SRC 311 monitor phase imbalance. A phase imbalance of > 3% results in SRC 311
tripping. For input supplies which have a supply imbalance greater than 3%, an input line
reactor is recommended. Alternatively, SRC 311 can be operated as a single-phase supply
drive with 50% de-rating.
kW HP Frame Size Nominal Input Fuse/MCB, type B) (A) Supply cable Nominal SUBCAB®
Current (A) None UL UL (mm2) Output cable (mm2)
Current (A)
4.0 5.0 3 17.3 20 20 6.0 18.0 2.5
kW HP Frame Size Nominal Input Fuse/MCB, type B) (A) Supply cable Nominal SUBCAB®
Current (A) (mm2) Output cable (mm2)
Current (A)
None UL UL
4.0 5.0 2 10.8 16 15 2.5 9.5 1.5
5.5 7.5 3 13.3 16 15 2.5 14.0 2.5
7.5 10.0 3 18.5 25 25 4.0 18.0 2.5
kW HP Frame Size Nominal Input Fuse/MCB, type B) (A) Supply cable Nominal SUBCAB®
Current (A) (mm2) Output cable (mm2)
Current (A)
None UL UL
4.0 – 2 7.1 10 10 2.5 6.5 1.5
5.5 – 2 14.4 25 20 2.5 9.0 2.5
7.5 – 3 14.4 25 20 2.5 12.0 2.5
11.0 – 3 23.6 40 35 2.5 17.0 2.5
IP55
kW HP Frame Size Nominal Input Fuse/MCB, type B) (A) Supply cable Nominal SUBCAB®
Current (A) (mm2) Output cable (mm2)
None UL UL Current (A)
kW HP Frame Size Nominal Input Fuse/MCB, type B) (A) Supply cable Nominal SUBCAB®
Current (A) (mm2) Output cable (mm2)
None UL UL Current (A)
kW HP Frame Size Nominal Input Fuse/MCB, type B) (A) Supply cable Nominal SUBCAB®
Current (A) None UL UL (mm2) Output cable (mm2)
Current (A)
11.0 15 4 26.5 32 30 6.0 24 6.0
15.0 20 4 32.9 40 40 6.0 30.0 6.0
18.5 25 4 46.6 63 60 16.0 39.0 10.0
22.0 30 4 54.1 63 60 16.0 46.0 10.0
30 40 5 69.6 80 80 35.0 61.0 16.0
37 50 5 76.9 100 100 35.0 70.0 25.0
45.0 60 6 92.3 125 125 50 .0 90.0 25.0
55.0 75 6 116.9 160 150 70.0 110.0 35.0
75.0 120 6 153.2 200 175 70.0 150.0 35.0
kW HP Frame Size Nominal Input Fuse/MCB, type B) (A) Supply cable Nominal SUBCAB®
Current (A) None UL UL (mm2) Output cable (mm2)
Current (A)
15.0 - 4 35.0 63 40 6.0 22.0 6.0
22.0 - 4 53.8 80 60 10.0 34.0 10.0
30.0 - 4 67.5 100 70 16.0 43.0 16.0
37.0 - 5 81.3 125 100 25.0 54.0 25.0
45.0 - 5 97.5 125 125 35 .0 65.0 35.0
55.0 - 6 131.3 200 150 35.0 78.0 35.0
75.0 - 6 162.5 250 200 50.0 105.0 50.0
90.0 - 6 187.5 250 250 70.0 130.0 70.0
110.0 - 6 187.5 250 250 70.0 150.0 70.0
Cable length
The maximum cable length is 100 m (328 ft). Screened cable must be used.
The PWM output switching from any inverter using a long motor cable can cause an
increase in the voltage at the motor terminals, depending on the cable length and
inductance. The rise time and peak voltage can affect the service life of the motor. Flygt
recommends using an output choke for motor cable lengths of 50 m or more to ensure
good motor service life.
For UL-compliant installation, use copper wire with a minimum insulation temperature
rating of 75°C (167°F). When using fuses, the type must be Class CC or Class J.
Dimensions
Frame size 2 – 3
C A
B
H
I
D
G E
F
Frame size 2 3
A mm (in) 257.0 (10.12) 310.0 (12.20)
B mm (in) 220.0 (8.67) 276.5 (10.89)
C mm (in) 200.0 (7.87) 251.5 (9.90)
D mm (in) 28.5 (1.12) 33.4 (1.31)
E mm (in) 238.0 (9.37) 256.0 (10.08)
F mm (in) 188.0 (7.40) 210.5 (8.29)
G mm (in) 176.0 (6.93) 197.5 (7.78)
H mm (in) 4.2 (0.17) 4.2 (0.17)
I mm (in) 8.5 (0.33) 8.5 (0.33)
Frame size 4 – 6
H
I
A C B
D
F G E
Frame size 4 5 6
A mm (in) 450.0 (17.72) 540.0 (21.26) 865.0 (34.06)
B mm (in) 428.0 (16.85) 515.0 (20.28) 830.0 (32.68)
Frame size 4 5 6
C mm (in) 433.0 (17.05) 520.0 (20.47) 840.0 (33.07)
D mm (in) 8.0 (0.315) 8.0 (0.315) 10.0 (0.394)
E mm (in) 252.0 (9.92) 270.0 (10.63) 330.0 (12.99)
F mm (in) 171.0 (6.73) 235.0 (9.25) 330.0 (12.99)
G mm (in) 110.0 (4.33) 175.0 (6.89) 200.0 (7.87)
H mm (in) 4.25 (0.167) 4.25 (0.167) 5.50 (0.217)
I mm (in) 7.5 (0.295) 7.5 (0.295) 11.0 (0.295)
Weight
Frame 2 3 4 5 6
Kg 4.8 7,3 11,5 22,5 50,0
Mounting clearance
X Minimum 200 mm (7.87 in)
X Y Minimum 10 mm (0.349 in)
Y Y
NOTICE:
The operating ambient temperature of the drive must be maintained.
Terminals
Power terminal Unit 1 and 2 Control Terminal Unit 1 Control Terminal Unit 2
1 2 3 4 5 6 1 2 3 4 5 6 7 8 9 101112 13 1 2 3 4 5 6 7 8 9 10111213
6
8
9 17
10 16 19 23 26
5 11
4 20
3 13 21 27
22 24
12 15 28
1 2
7 18
WS003610
M M 25
14
1. Incoming power
2. RFI-toroid core, for sizes 2 and 3
3. Brown lead
4. Black lead
5. Grey lead
6. Ground (earth)
7. Pump 1
8. T1, (pump 1)
9. T2, (pump 1)
10. T31 (pump 1)
11. T41 (pump 1)
12. Black lead
13. Control screen lead
14. Level switch
15. • EU: Grey
• US: Red
16. Screen lead of the shared communication cable
17. Signal leads of the shared communication cable
18. Pump 2
19. T1 (pump 2)
20. T2 (pump 2)
21. T31 (pump 1)
22. T41 (pump 1)
23. Screen lead of the shared communication cable
24. Screen lead of the level sensor cable
25. Level sensor signal lead
26. Level sensor lead –
27. Level sensor lead +
28. White
Figure 1: Two pump system
+24 V +24 V
1
1
Ext block Ext block
2
2
Alarm reset Alarm reset
3
3
M
High level in High level in
4
4
+ 10 V + 10 V
5
5
T2 in T2 in
6
6
Gnd Gnd
7
7
Lvl signal out Lvl signal out
8
8
Gnd Gnd
9
9
Lvl signal in Lvl signal in
10 11
10 11
Active pump Active pump
Inhibit in Inhibit in
12
12
+
Inhibit out Inhibit out
13
13
14 15 16 17 18
14 15 16 17 18
Relay1 NO Relay1 NO
Relay1 NC Relay1 NC
Relay2 com Relay2 com
Relay2 NO Relay2 NO
1
+24 V +24 V
1
1
M
2
2
3
3
+ 10 V + 10 V
5
5
T2 in T2 in
6
6
Gnd Gnd
7
7
8
8
Gnd Gnd
9
9
10 11
10 11
12
12
13
13
14 15 16 17 18
14 15 16 17 18
Relay1 NO Relay1 NO
Relay1 NC Relay1 NC
Relay2 com Relay2 com
Relay2 NO Relay2 NO
+24 V +24 V
1
1
M
+ 10 V + 10 V
5
5
T2 in T2 in
6
6
Gnd Gnd
7
7
Gnd Gnd
9
9
Relay1 NO Relay1 NO
Relay1 NC Relay1 NC
Relay2 com Relay2 com
WS007551
WS007550
Relay2 NO Relay2 NO
Figure 2: Three pump system Figure 3: Three pump I/O alternation system
Table 7: Power
Communication
The drive is equipped with an RJ45 connector. The connection is used to set up a network
via a wired connection. The connector contains two independent RS485 connections and
both can be used simultaneously.
NOTICE:
This RJ45 connector is not an Ethernet connection. Do not connect directly to an Ethernet
port. The voltage destroys the Ethernet device.
1 2 3 4 5 6 7 8 1. Not used
2. Not used
3. 0V
4. RS485- Optibus
5. RS485+ Optibus
6. +24 V, power supply
7. RS485- ModbusRTUx
WS003606
8. RS485+ ModbusRTU
All the drives parameters are read and written over the fieldbus communication. Process
parameters that are marked as configurable are also accessed and read, but process
parameters that are marked with a fixed value cannot be read or set over the fieldbus
communication.
Any external system that wants to read process data and alarms from the drive must be
configured with the correct parameter addresses for the drive.
Contact sales support for more information regarding communication.
Options
External Keypads and Optistick
• OLED External Keypad
• Optistick
Cables splitters, PC Kit
• RS485 Data cable Splitter
• RS485 Data cable w- RJ45
• USB to RS485 Connection kit
3 Extended digital input 3 needs to be activate for External digital input 1 and 2 to work.
Xylem Water Solutions Visit our Web site for the latest version of this document
and more information
Manufacturing AB
361 80 Emmaboda The original instruction is in English. All non-English
instructions are translations of the original instruction.
Sweden
Tel: +46-471-24 70 00 © 2012 Xylem Inc
Fax: +46-471-24 47 01
http://tpi.xyleminc.com
882877_3.0_en-US_2013-10_TS.SRC311
References (continued) Harmony™ 9001K/SK/KX
30 mm push buttons
9001SK – Pilot lights
Note: When ordering, add prefix “9001” to the reference.
4
For other voltages Full Voltage or SKTRaR31 SKTRaG31 SKTRab SKTRa
color cap
(1) Resistor (5)
shown)
9001SKTR38
(1) Replace a with the voltage assembly code as chosen from the tables on page 54.
Example: SKTaR31 with 208 Vac red LED voltage = SKT37LRR31.
(2) Replace b with the color code as chosen from the color code table below.
Example: SKP1b with a blue fresnel cap = SKP1L31.
5
(3) The cap must be the same color as the LED light module chosen, e.g., for a green LED, use a green color cap.
(4) On neon light modules, use clear color caps only.
(5) Use only full voltage or resistor voltage assembly codes on remote test pilot lights. Do not choose LED, neon or transformer codes.
For AC use only.
Color Caps
Color b Plastic Fresnel b Plastic Domed
L1 L2
START M O.L.
1 STOP 2 3
M
6
Amber A31 A9
L2
Blue L31 L9 M
Clear C31 C9
Green G31 G9 R
Red R31 R9
White W31 W9
7
C
Yellow Y31 Y9
Test
L1
TEST
L1 L2 L2
8
L1 BUTTON
START M (TEST) C L2
O.L.
1 STOP 2 3
M STOP START
L1 M1
(SIG)
(TEST) C L2
M L2
LSI
9
L1 M2
(SIG)
R
C
(TEST) C L2
Test
M3 L1 CR
L1 (SIG)
10
Push-to-test Pilot Light Remote Test Pilot Light
TEST
L1 L2
BUTTON L2 Blocks, Light Modules, Knobs, and Accessories, see pages 50 to 59.
To(TEST) C order Contact
select and
48
(TEST) C L2
References (continued) Harmony™ 9001K/SK/KX
30 mm push buttons
9001SK – Push buttons and mushroom operators
Note: When ordering, add prefix “9001” to the reference.
9001SKR2B
Universal (1)
Other (2)
SKR2UH13
SKR2b
SKR2UH5
SKR2bH5
SKR2UH6
SKR2bH6
SKR2U
SKR2b
4
Extended Guard
Snap-In Mushroom Button
Black SKR4BH13 SKR4BH5 SKR4BH6 SKR4B
Red SKR4RH13 SKR4RH5 SKR4RH6 SKR4R
5
Red (3) SKR4R05H13 SKR4R05H5 SKR4R05H6 SKR4R05
Green SKR4GH13 SKR4GH5 SKR4GH6 SKR4G
Other (4) SKR4dH13 SKR4dH5 SKR4dH6 SKR4d
Screw-On Mushroom Button with Set Screw Security
Color Codes 8
Color b SKR1, 2, 3 Place Color Code in Reference d SKR4, 5, 24, 25 Place Color Code in Reference
Blue L L
Yellow Y Y
White W —
Orange S S
Gray E —
(1) The universal push button operators contain one each of the following color inserts: black, red, green, yellow, orange, blue and white.
9
(2) Replace b with the color code as chosen from the color code table above.
(3) Knob has the words “Emergency Stop” in raised letters highlighted in white for readability.
(4) Replace d with the color code as chosen from the color code table above
(5) These operators can be ordered complete with contact blocks. For maximum block usage, see page 51. Add the “H” number chosen from
page 51 to the end of the operator reference number and add the cost of the “H” number to the operator cost.
To select and order Contact Blocks, Light Modules, Knobs, and Accessories, see pages 50 to 59.
10
41
Alarm Light INGRAM
P R O D U C T S, I N C.
1 3/8" 1 3/8"
4 T
0 W AT
2"
Ø 1/4"
3 1/4"
8-32 TAP
(2 REQ'D) 2"
1 1/4"
Ø 2"
or 1 1/2
Knock Out
8725 Youngerman Court, Ste 206, Jacksonville, FL 32244 888-875-2221 ph (904)733-2230 fax Website:www.ingramproducts.com e-mail: info@ingramproducts.com
Shatter Resistant
G.E. Lexan Globe
Gasket
Enclosure Wall
2 T
5W A T
#8 - 32 Mounting
Screw
2" Knock out
or 2" hole
Mounting Bracket
LX25 Assembly
Solid State Flasher INGRAM
P R O D U C T S, I N C.
Applied
Input Power
Off
Energized
E121431 Output On On On On
Time Time Time Time
De-energized
Off Off Off Off
Time Time Time Time
3KΩ RESISTOR
20 WATT
1/2"
120 VAC INPUT
Ø 15/16"
Ø 1/4"
MAX LOAD
1.000" TUNGSTEN 1.25 amps
PILOT DUTY 10 VA
FLASHER
1 1/2"
1.000"
Connection
8725 Youngerman Court, Ste 206, Jacksonville, FL 32244 888-875-2221 ph (904)778-2444 fax Website:www.ingramproducts.com e-mail: info@ingramproducts.com
MW-09-201-Q
Made in
USA
SPECIFICATIONS
100 20
PRESSURE dB(A), at 2 feet
90 15
300 hours with no decrease in sound output
Humidity- 95% relative humidity at +40°C continuously for 100 hours.
80 10 Vibration- Withstands vibration between 0 and 55 Hz. on all axes.
70 5
Life Expectancy: 10 years under normal operating conditions.
Warranty: For a period of two years from the date of manufacture under normal
40 60 80 100 120
operating conditions.
INPUT VOLTAGE Vac
PANEL MOUNTING
DIMENSIONS
MOUNTING HOLE
REAR VIEW SIDE VIEW RING FRONT VIEW 1.125 D
(28.6 D)
1.125 X 24
THREADS
FOR REFERENCE ONLY
0.43 0.89
(10.9) 1.41 D FITS PANELS UP-TO
(22.6) 0.315 (35.8 D)
(8.0) 0.25 (6.3) THICK
Copyright © 2004 Floyd Bell Inc. All specifications subject to change without notice.
Medium Loud Series - 95db(A) at 2 feet
Frequency 2900 + 500 Hz
**Terminations:
09/09/02
Model 34 Electronic LCD Hour Meter
Description
The Redington Model 34 LCD Hour Meter provides a large display, with 0.28” [7mm] high characters, in the industry size housings. The Hour Meters
are available in 5 different housings, including a surface mount inductive input model. All models are totally sealed and are capable of submersion in 6’
[2 meters] of water. A wide operating voltage, 10-300VDC and 20-300VAC, and inductive input make the Model 34 versatile for all indoor and outdoor
applications. All models are NEMA 4/4X, 12, & IP66 rated when used with the optional gasket and have a polarized lens which assures high visability in
an outdoor environment.
Maintenance Meters are offered with a maximum of 3 “Redi-Alerts” to alert users when service is due. Models are available with front panel field or fac-
tory programmable alerts. Not only does the display flash to get attention, but it displays a choice of 7 different .08”[2mm] maintenance icons. Models
are available as a Preset Timer with a MOSFET output for the actuation of external alarms or indicator lamps. Users can program or specify the service
interval and flash duration for each Redi-Alert. Flash duration is the amount of time in hours that the specific icon flashes before and after the service
interval. If a front panel manual reset of the Redi-Alert is required the front panel models with switches must be specified.
Features Options
• Totally sealed from moisture and dirt • A choice of 6 housings
• AC or DC voltage input in the same unit • A choice of reset modes
• Tachometer/Hour Meter versions • Front panel programmable
• Compact depth • Preset Timer with output
• Fits in existing panel openings • Can be programmed with starting time
• Always on display • Programmable output thresholds
• 15+ Year Battery Life • Preset Hour Meter/time up or down
• Up to 3 Redi-Alerts/7 icons
Specifications
Display: LCD with large 0.28” [7mm] high figures black on Maximum Withstanding voltage: 30VDC, reference to Common
light background Maximum Load current: 0.1Amp
8 www.trumeter.com
Model 34 Electronic LCD Hour Meter
Functions
Preset Hour Meter: The preset function is centered on the output signal. When the time reaches the preset value, the output signal is turned “on”.
The Preset function is time “up”.Upon reaching the preset value the preset can be automatically reset, or it can await an
external reset.
Inductive Models: The surface mount Inductive unit is designed with an inductive interface. The unit will sense the firing of a spark plug on most
small gasoline powered internal combustion engines. The wire lead from the unit is wrapped around the spark plug wire.
Inductive models are available with and without tachometers. Most small engines provide 1 spark per RPM, in which case the
maximum RPM is 30,000. Some small engines provide 2 sparks per RPM, the maximum RPM is then 15,000. Models are
available that can be field (front panel switches) or factory programmed for 1.0, 2.0, or 0.5 sparks/pulses per RPM.
Front Panel Switch Functions: Front panel switches can be used for reset, display selection and programming. The two front Panel switches
are used as follows:
SEL: During programming this switch is used to select options. The SEL switch is used during programming to move
horizontally in the programming flow chart.
RST: This is the reset switch during normal operation. During programming the RST switch is used to enter an option.
The RST switch is used during programming to move vertically in the programming flow chart.
Available Icons
Dimensions
Rectangular Flush Mount 2-Hole Mount
.34 [8.6] .34 [8.6]
1.60 [40.6] 1.75 [44.4]
.75 [19.0]
.75 [19.0]
.25 [6.3]
.25 [6.3]
.88 [22.3]
1.43 [36.3] .88 [22.3]
1.43 [36.3]
Panel Cutout: 1.45” [36.8mm] x 0.95” [24.1mm] Panel Cutout: 1.45” [36.8mm] x 0.95” [24.1mm]
Maximum Panel Thickness: 0.375” [9.5mm]
.34 [8.6]
.50 [12.7]
.28 [7.0]
.79 [20.0]
1.98 [50.3]
.75 [19.0]
.25 [6.3]
.88 [22.3]
1.43 [36.3]
www.trumeter.com 9
Model 34 Electronic LCD Hour Meter
3-Hole Mount Snap-In Mount
1.10 [27.9]
.34 [8.6]
1.29 [32.7]
.34 [8.6]
.28 [7.0]
.79 [20.0] .50 [12.7]
.50 [12.7]
1.29 [32.7]
.05 [1.3]
.79 .28 [7.0] 1.60 [40.6]
[20.0] .05 [1.3]
.75 [19.0]
.03 [0.7]
.05 [1.3]
.05 [1.3]
2.87 [72.9] .25 [6.3]
1.98 [50.3] .88 [22.3]
1.43 [36.3]
.75 [19.0]
Panel Cutout: 1.46” [37mm] x 0.95” [24.1mm]
Minimum Panel Thickness: 0.04” [1.0mm]
Maximum Panel Thickness: 0.125” [3.18mm]
.25 [6.3]
.88 [22.3]
1.43 [36.3]
Surface Mount
39.37 [1000.00]
.50 [12.7]
2.12 [54.0]
.28 [7.0]
1.10 [27.9]
.89 [22.6]
1.41 [35.8]
.55 [14.0]
Notes
1. When interfacing the Model 34 with a Solid State Relay or AC Sensor, the leakage current needs to be considered. Contact the factory or see the
application note at www.redingtoncounters.com
2. Exceeding the Absolute Voltage Range and the Absolute Maximum Limits may result in damage to the unit.
3. The open-drain MOSFET acts like an open-collector NPN trasistor. Care should be taken since there is no current limiting protection in the unit.
Applications
Medical Devices Generators Control Panels Production Equipment Garden Tractor Marine Equipment
10 www.trumeter.com
Part Number Description Gasket
3410-0000 AC/DC HOUR METER 2 HOLE 1/4" SPADE TERMINALS NON-RESET 5003-010
3410-0010 AC/DC HOUR METER 2 HOLE 1/4" SPADE TERMINALS REMOTE-RESET 5003-010
3410-0020 AC/DC HOUR METER 2 HOLE 1/4" SPADE TERMINALS PROGRAMMING 5003-010
AC/DC HOUR METER THREE HOLE CASE 1/4" SPADE TERMINALS NON-
3410-1000 5003-017
RESET
AC/DC HOUR METER THREE HOLE CASE 1/4" SPADE TERMINALS
3410-1010 5003-017
REMOTE-RESET
AC/DC HOUR METER FLUSH RECT CASE 1/4" SPADE TERMINALS NON-
3410-2000 5003-009
RESET
AC/DC HOUR METER FLUSH RECT CASE 1/4" SPADE TERMINALS
3410-2010 5003-009
REMOTE-RESET
AC/DC HOUR METER ROUND SAE CASE 1/4" SPADE TERMINALS NON-
3410-3000 5003-009
RESET
AC/DC HOUR METER ROUND SAE CASE 1/4" SPADE TERMINALS
3410-3010 5003-009
REMOTE-RESET **SPECIAL ORDER** MOQ = 50 PCS
AC/DC HOUR METER SNAP-IN CASE 1/4" SPADE TERMINALS NON-
3410-5000
RESET
AC/DC HOUR METER SNAP-IN CASE 1/4" SPADE TERMINALS REMOTE-
3410-5010
RESET
NOTE PART NUMBERS MUST END IN -XX20 TO BE PROGRAMMABLE
www.trumeter.com
Zelio® Plug-in Relays RXM Miniature Relays
Product Description
Product Description
7
8 Relay Description
1
2 1. Spring return push button for testing the contacts (green: DC, red: AC).
3 2. Mechanical “relay status” indicator.
3. Optional removable lock-down door and push button, enabling forced
4
maintaining of the contacts for test or maintenance purposes. During
5 operation, this lock-down door must always be in the closed position.
7 6
10 4. Bipolar LED (depending on version) indicating the relay status.
9 9 5. Removable marker for relay identification.
6. Four notches for DIN rail mounting adapter or panel mounting adapter.
7. Eight, eleven, or fourteen pins.
8. Area by which the product can be easily gripped.
9. Mounting adapter enabling direct mounting of the relay on a panel.
10. Mounting adapter enabling direct mounting of the relay on a DIN rail.
6
Socket Description
1 Sockets with Mixed Contact Terminals
Inputs NOTE: The inputs are mixed with the relay coil terminals, with the outputs
being located on the opposite side of the socket.
5 Coil Terminals
4
© 2005–2008 Schneider Electric All Rights Reserved 01/2008
RXM Miniature Relays Zelio® Plug-in Relays
Specifications and Characteristics
5 7 Coil Terminals
General characteristics
Conforming to standards IEC/EN 61810-1 (iss. 2), UL 508, CSA C22-2 n° 14
cULus File E164862 CCN NLDX, NLDX7; cURus File E164862 CCN NLDX2, NLDX8;
Product certifications
CSA pending; CE; RoHS compliant
Insulation characteristics
Rated insulation voltage (Ui) 250 V (IEC), 300 V (UL, CSA)
Rated impulse withstand voltage (Uimp) 3.6 kV (1.2/50 µs)
Between coil and contact 2,500 Vac
Dielectric strength
Between poles 2,500 Vac
(rms voltage)
Between contacts 1,500 Vac
Contact characteristics
Relay type RXM2ABppp RXM3ABppp RXM4ABppp RXM4GBppp
Number and type of contacts (see page 12) DPDT 3PDT 4PDT 4PDT
Contact materials AgNi AgAu–Bifurcated
Conventional thermal For ambient
12 A 10 A 6A 3A
current (Ith) temperature y 131 °F (55 °C)
Conforming to IEC N.O. 12 A 10 A 6A 2A
in utilization category
AC-1 N.C. 6A 5A 3A 1A
Rated operational current
Conforming to UL
12 A, 1/2 hp 10 A, 1/3 hp 8 A, 1/3 hp 3 A, 1/16 hp
Resistive @277 Vac, hp @120 Vac
5
01/2008 © 2005–2008 Schneider Electric All Rights Reserved
Zelio® Plug-in Relays RXM Miniature Relays
Specifications and Characteristics
107
106
D A B
C
105
0 1 2 3
Switching capacity (kVA)
Coil characteristics
AC 1.2 VA
Average consumption
DC 0.9 W
AC u 0.15 Uc
Drop-out voltage threshold
DC u 0.1 Uc
Socket characteristics
Socket type RXZE2S108M RXZE2S111M RXZE2S114M RXZE2M114 RXZE2M114M
RXM2ppppp1 RXM2ppppp1
Relay types used RXM2ppppp RXM3ppppp RXM4ppppp
RXM4ppppp RXM4ppppp
Product certifications cURus File E172326 CCN SWIV2, SWIV8; CSA (pending); CE; RoHS compliant
Conventional thermal current (Ith) 12 A 10 A
Degree of protection Conforming to IEC/EN 60529 IP 20
1 conductor: AWG 20–12 (0.5–2.5 mm2)
Solid wire without cable end
2 conductors: AWG 20–14 (0.5–1.5 mm2)
1 conductor: AWG 24–14 (0.2–2.5 mm2)
Connection Flexible wire with cable end
2 conductors: AWG 24–16 (0.2–1.5 mm2)
1 conductor: AWG 24–14 (0.2–2.5 mm2)
Flexible wire without cable end
2 conductors: AWG 24–16 (0.2–1.5 mm2)
Maximum tightening torque 5.3 lbf-in (0.6 Npm) (M3 screw)
Contact terminal arrangement Separate Mixed
Bus jumper Ith: 5 A Yes No
1
When mounting relay RXM2ppppp on socket RXZE2Mpppp, the thermal current must not exceed 10 A.
6
© 2005–2008 Schneider Electric All Rights Reserved 01/2008
RXM Miniature Relays Zelio® Plug-in Relays
Ordering Information
Miniature relays with lockable test button, without LED (sold in lots of 10)
Number and type of contacts - Thermal current (Ith)
DPDT - 12 A 3PDT - 10 A 4PDT - 6 A
Weight Weight Weight
Coil Voltage Catalog Number Catalog Number Catalog Number
lb. kg lb. kg lb. kg
12 Vdc RXM2AB1JD 0.082 0.037 RXM3AB1JD 0.084 0.038 RXM4AB1JD 0.080 0.036
RXMpAB2F7
24 Vdc RXM2AB1BD 0.082 0.037 RXM3AB1BD 0.084 0.038 RXM4AB1BD 0.080 0.036
48 Vdc RXM2AB1ED 0.082 0.037 RXM3AB1ED 0.084 0.038 RXM4AB1ED 0.080 0.036
110 Vdc RXM2AB1FD 0.082 0.037 RXM3AB1FD 0.084 0.038 RXM4AB1FD 0.080 0.036
220 Vdc — — — — — — RXM4AB1MD 0.080 0.036
24 Vac RXM2AB1B7 0.082 0.037 RXM3AB1B7 0.084 0.038 RXM4AB1B7 0.080 0.036
48 Vac RXM2AB1E7 0.082 0.037 RXM3AB1E7 0.084 0.038 RXM4AB1E7 0.080 0.036
120 Vac RXM2AB1F7 0.082 0.037 RXM3AB1F7 0.084 0.038 RXM4AB1F7 0.080 0.036
230 Vac RXM2AB1P7 0.082 0.037 RXM3AB1P7 0.084 0.038 RXM4AB1P7 0.080 0.036
240 Vac — — — — — — RXM4AB1U7 0.080 0.036
Miniature relays with lockable test button, with LED (sold in lots of 10)
12 Vdc RXM2AB2JD 0.082 0.037 RXM3AB2JD 0.084 0.038 RXM4AB2JD 0.080 0.036
24 Vdc RXM2AB2BD 0.082 0.037 RXM3AB2BD 0.084 0.038 RXM4AB2BD 0.080 0.036
48 Vdc RXM2AB2ED 0.082 0.037 RXM3AB2ED 0.084 0.038 RXM4AB2ED 0.080 0.036
110 Vdc RXM2AB2FD 0.082 0.037 RXM3AB2FD 0.084 0.038 RXM4AB2FD 0.080 0.036
125 Vdc — — — — — — RXM4AB2GD 0.080 0.036
24 Vac RXM2AB2B7 0.082 0.037 RXM3AB2B7 0.084 0.038 RXM4AB2B7 0.080 0.036
48 Vac RXM2AB2E7 0.082 0.037 RXM3AB2E7 0.084 0.038 RXM4AB2E7 0.080 0.036
120 Vac RXM2AB2F7 0.082 0.037 RXM3AB2F7 0.084 0.038 RXM4AB2F7 0.080 0.036
230 Vac RXM2AB2P7 0.082 0.037 RXM3AB2P7 0.084 0.038 RXM4AB2P7 0.080 0.036
Miniature relays with low level contacts, Miniature relays with low level contacts,
without LED (sold in lots of 10) with LED (sold in lots of 10)
Number and type of contacts - Thermal current (Ith) Number and type of contacts - Thermal current (Ith)
4PDT - 3 A 4PDT - 3 A
Weight Weight
Coil Voltage Catalog Number Coil Voltage Catalog Number
lb. kg lb. kg
RXM4GB2F7
12 Vdc RXM4GB1JD 0.080 0.036 12 Vdc RXM4GB2JD 0.080 0.036
24 Vdc RXM4GB1BD 0.080 0.036 24 Vdc RXM4GB2BD 0.080 0.036
48 Vdc RXM4GB1ED 0.080 0.036 48 Vdc RXM4GB2ED 0.080 0.036
110 Vdc RXM4GB1FD 0.080 0.036 110 Vdc RXM4GB2FD 0.080 0.036
24 Vac RXM4GB1B7 0.080 0.036 24 Vac RXM4GB2B7 0.080 0.036
48 Vac RXM4GB1E7 0.080 0.036 48 Vac RXM4GB2E7 0.080 0.036
120 Vac RXM4GB1F7 0.080 0.036 120 Vac RXM4GB2F7 0.080 0.036
230 Vac RXM4GB1P7 0.080 0.036 230 Vac RXM4GB2P7 0.080 0.036
240 Vac RXM4GB2U7 0.080 0.036
7
01/2008 © 2005–2008 Schneider Electric All Rights Reserved
RXM Miniature Relays Zelio® Plug-in Relays
Ordering Information
Miniature relays with lockable test button, without LED (sold in lots of 100)
Number and type of contacts - Thermal current (Ith)
DPDT - 12 A 4PDT - 6 A
Weight Weight
Coil Voltage Catalog Number Catalog Number
lb. kg lb. kg
12 Vdc — — — RXM4AB1JDTQ 0.080 0.036
24 Vdc RXM2AB1BDTQ 0.082 0.037 RXM4AB1BDTQ 0.080 0.036
48 Vdc — — — RXM4AB1EDTQ 0.080 0.036
110 Vdc — — — RXM4AB1FDTQ 0.080 0.036
220 Vdc — — — RXM4AB1MDTQ 0.080 0.036
24 Vac RXM2AB1B7TQ 0.082 0.037 RXM4AB1B7TQ 0.080 0.036
48 Vac — — — RXM4AB1E7TQ 0.080 0.036
RXZ E2M114M with
120 Vac RXM2AB1F7TQ 0.082 0.037 RXM4AB1F7TQ 0.080 0.036
relay RXM4AB2P7TQ
230 Vac RXM2AB1P7TQ 0.082 0.037 RXM4AB1P7TQ 0.080 0.036
Miniature relays with LED (sold in lots of 100)
24 Vdc — — — RXM4AB2BDTQ 0.080 0.036
24 Vac RXM2AB2B7TQ 0.082 0.037 RXM4AB2B7TQ 0.080 0.036
230 Vac RXM2AB2P7TQ 0.082 0.037 RXM4AB2P7TQ 0.080 0.036
Timing relays
Weight
Description For use with Catalog Number
lb. kg
2 timed DPDT contacts
REXL2pp 4 0.09 0.042
(function A—On-delay)
Sockets RXZ Eppppp
4 timed 4PDT contacts 4
REXL4pp 0.09 0.042
(function A—On-delay)
REXL4pp 4 ®
Please refer to the Zelio Time - Timers catalog (9050CT0001R2/05).
Relays
RXMpppppp RXM2 RXM3 RXM4
Common view Pin side view
0.16 = = = = =
(4)
1.06
(27)
0.26 21 21
0.28 1.57 (40) 0.24 (6.5) 0.83 0.10 0.10 0.10 0.10 0.18
(7) (6) (21) (2.5) (2.5) (2.5) (2.5) 0.10 (4.5) 0.10
0.24 0.53 0.53
(2.5 0.53 (2.5)
(6) (13.5) (13.5)
(13.5)
Sockets
RXZE2M114 RXZE2M114M
1.57 1.69
(40) 0.75 1.00 (43) 0.67
(19) (4) (25.5) (17)
34 24
44 34 24 14
7 6
8 7 6 5
44 14
8 5 42 32 22 12
42 32 22 12 4 3 2 1
4 3 2 1
0.14 0.14
3.11
(79)
(3.5) (3.5)
(1)
3.15
(1)
(80)
2.40
(61)
(39.5)
1.56
1.57
(40)
11
(2) A2 A1
(2) A2 A1
9
14 13
(3) (3) 14 13
41 31 21 41 31 21 11
12 11 10 12 11 10 9
1.97 0.93
(3.5)
0.83
0.14
0.35
(9) 0.28
2.64 (50) (23.5)
0.91 1.18 (21) 1.06
(7) (67)
(23) 2.72 (30) 1.18 (27)
0.28 (30)
(7) (69)
2.40
(61) 0.75
(19)
41 11 31 21 11 41 31 21 11
12 9 9 8 7 12 11 10 9
44 14 34 24 14 44 34 24 14
8 5 6 5 4 8 7 6 5
42 12 32 22 12 42 32 22 12
4 1 3 2 1 4 3 2 1
0.14
3.11
0.14 0.14
(79)
1.50
(38)
(38)
(38)
(2)
(3) A2 A1 A2 A1 A2 A1
14 13 14 13 14 13
(5)
(3.5)
0.14
1.04
2.24 (26.5)
(57)
(14.2)
0.47
(12)
0.56
(1)
1.06
(27)
(94.5)
3.72
3.19
(81)
0.98
(25)
1.02
(26)
(2.2)
0.09
0.87
(1) (1)
(22) 0.09
(7.3)
0.29
(2.3) 1.46
0.05 (37)
(2) (2) (1.2)
1.69
(43)
1.50
(38)
1.89
(48)
0.24 0.16
0.91 (6) (4) (48) (49) (24)
(23) 0.94
2.01
(24)
(51)
1
Test button becomes inaccessible
Dimensions = Inches
(mm)
11
01/2008 © 2005–2008 Schneider Electric All Rights Reserved
Zelio® Plug-in Relays RXM Miniature Relays
Wiring Diagrams
Miniature relays
RXM2ppppp RXM3ppppp RXM4ppppp
A2
A2
A2
12
14
42
44
12
14
22
24
32
34
12
14
22
24
32
34
42
44
A1
A1
A1
11
41
11
21
31
11
21
31
41
1 4 1 2 3 1 2 3 4
12 42 12 22 32 12 22 32 42
5 8 4 5 6 5 6 7 8
14 44 14 24 34 14 24 34 44
9 12 9 10 11 12
7 8 9
11 41 11 21 31 41
11 21 31
13 14 13 14
13 14
A1 A2 A1 A2
A1 A2
Numbers shown in italics correspond to NEMA marking. Viewed from pin end.
12
© 2005–2008 Schneider Electric All Rights Reserved 01/2008
BILL OF MATERIAL
Custom
A/R Din Rail; 1 Meter Connector C103PM
A/R Terminal Block; UK 5N, 30A, 600V Phoenix 3004362
A/R End Block; ENS 35N Phoenix 800886
A/R End Cover; D-UK 4/10 (UK 5 & 6) Phoenix 303020
6 Distribution Block; 175A, 1IN/1OUT Mersen FSPDB1A
CONTROL COMPONENTS
Barrier, Pulse, Two Channel, Isolated, 24-
1 ISR 230VAC/DC PR Electronics 5202B4
Barrier, Analog, Single Channel, Isolated, 24-
1 ISB 230VAC/DC PR Electronics 5104B-B2A
EXTERNAL EQUIPMENT
2 FSHH,FSH Float; ENM-10 Level Regulator, 40 Ft Xylem 5828830
Level Transducer, 3400 Series Hydro-Static, 0-30
1 LXDCR Ft Range, 39 Ft Cable (Std) MJK 209925
Wall-Mount Enclosures Wall-Mount Enclosures and Accessories
Stainless Steel
Spec-00090
G
763.422.2211
763.422.2600
Wall-Mount Enclosures
APPLICATION
These enclosures feature Hoffman’s exclusive POWERGLIDE™
Handle with 3-point latching, ideal for indoor or outdoor
applications that require corrosion protection, convenient access,
and padlocking security.
SPECIFICATIONS
• 4 gauge Type 304 or 316L stainless steel bodies and doors
1
• S eams continuously welded and ground smooth
• S eamless foam-in-place gasket
• Rolled lip around three sides of door
• Internal 3-point latch and Type 316L stainless steel padlocking
POWERGLIDE Handle
• Remove door by pulling stainless steel continuous hinge pin
• Data pocket is high-impact thermoplastic
• Collar studs provided for mounting optional panels
• E xterior hardware on Type 316L stainless steel enclosures
matches enclosure material
• Bonding provision on door; grounding stud on body
Standard Product
Panel Size
Stainless F Steel Conductive Stainless DxE Data
Catalog Number AxBxC in./mm Steel Type in./mm Panel Panel Steel Panel in./mm Pocket
A24H2006SSLP3PT 24.00 x 20.00 x 6.00 304 3.00 A24P20 A24P20G A24P20SS6 21.00 x 17.00 Small
610 x 508 x 152 76 533 x 432
A24H2006SS6LP3PT 24.00 x 20.00 x 6.00 316L 3.00 A24P20 A24P20G A24P20SS6 21.00 x 17.00 Small
610 x 508 x 152 76 533 x 432
A24H2008SSLP3PT 24.00 x 20.00 x 8.00 304 3.00 A24P20 A24P20G A24P20SS6 21.00 x 17.00 Small
610 x 508 x 203 76 533 x 432
A24H2008SS6LP3PT 24.00 x 20.00 x 8.00 316L 3.00 A24P20 A24P20G A24P20SS6 21.00 x 17.00 Small
610 x 508 x 203 76 533 x 432
A24H2408SSLP3PT 24.00 x 24.00 x 8.00 304 3.00 A24P24 A24P24G A24P24SS6 21.00 x 21.00 Small
610 x 610 x 203 76 533 x 533
A24H2408SS6LP3PT 24.00 x 24.00 x 8.00 316L 3.00 A24P24 A24P24G A24P24SS6 21.00 x 21.00 Small
610 x 610 x 203 76 533 x 533
A30H2408SSLP3PT 30.00 x 24.00 x 8.00 304 3.00 A30P24 A30P24G A30P24SS6 27.00 x 21.00 Large
762 x 610 x 203 76 686 x 533
A30H2408SS6LP3PT 30.00 x 24.00 x 8.00 316L 3.00 A30P24 A30P24G A30P24SS6 27.00 x 21.00 Large
762 x 610 x 203 76 686 x 533
A30H3008SSLP3PT 30.00 x 30.00 x 8.00 304 3.00 A30P30 A30P30G A30P30SS6 27.00 x 27.00 Large
762 x 762 x 203 76 686 x 686
A30H3008SS6LP3PT 30.00 x 30.00 x 8.00 316L 3.00 A30P30 A30P30G A30P30SS6 27.00 x 27.00 Large
762 x 762 x 203 76 686 x 686
A36H2408SSLP3PT 36.00 x 24.00 x 8.00 304 3.00 A36P24 A36P24G A36P24SS6 33.00 x 21.00 Large
914 x 610 x 203 76 838 x 533
A36H2408SS6LP3PT 36.00 x 24.00 x 8.00 316L 3.00 A36P24 A36P24G A36P24SS6 33.00 x 21.00 Large
914 x 610 x 203 76 838 x 533
A36H3008SSLP3PT 36.00 x 30.00 x 8.00 304 3.00 A36P30 A36P30G A36P30SS6 33.00 x 27.00 Large
914 x 762 x 203 76 838 x 686
A36H3008SS6LP3PT 36.00 x 30.00 x 8.00 316L 3.00 A36P30 A36P30G A36P30SS6 33.00 x 27.00 Large
914 x 762 x 203 76 838 x 686
A48H3608SSLP3PT 48.00 x 36.00 x 8.00 304 3.00 A48P36 A48P36G A48P36SS6 45.00 x 33.00 Large
1219 x 914 x 203 76 1143 x 838
A48H3608SS6LP3PT 48.00 x 36.00 x 8.00 316L 3.00 A48P36 A48P36G A48P36SS6 45.00 x 33.00 Large
1219 x 914 x 203 76 1143 x 838
A24H2010SSLP3PT 24.00 x 20.00 x 10.00 304 3.00 A24P20 A24P20G A24P20SS6 21.00 x 17.00 Small
610 x 508 x 254 76 533 x 432
Panel Size
Stainless F Steel Conductive Stainless DxE Data
Catalog Number AxBxC in./mm Steel Type in./mm Panel Panel Steel Panel in./mm Pocket
A24H2010SS6LP3PT 24.00 x 20.00 x 10.00 316L 3.00 A24P20 A24P20G A24P20SS6 21.00 x 17.00 Small
610 x 508 x 254 76 533 x 432
A36H3010SSLP3PT 36.00 x 30.00 x 10.00 304 3.00 A36P30 A36P30G A36P30SS6 33.00 x 27.00 Large
914 x 762 x 254 76 838 x 686
A36H3010SS6LP3PT 36.00 x 30.00 x 10.00 316L 3.00 A36P30 A36P30G A36P30SS6 33.00 x 27.00 Large
914 x 762 x 254 76 838 x 686
A42H3010SSLP3PT 42.00 x 30.00 x 10.00 304 3.00 A42P30 A42P30G A42P30SS6 39.00 x 27.00 Large
1067 x 762 x 254 76 991 x 686
A48H3610SSLP3PT 48.00 x 36.00 x 10.00 304 3.00 A48P36 A48P36G A48P36SS6 45.00 x 33.00 Large
1219 x 914 x 254 76 1143 x 838
A48H3610SS6LP3PT 48.00 x 36.00 x 10.00 316L 3.00 A48P36 A48P36G A48P36SS6 45.00 x 33.00 Large
1219 x 914 x 254 76 1143 x 838
A24H2412SSLP3PT 24.00 x 24.00 x 12.00 304 3.00 A24P24 A24P24G A24P24SS6 21.00 x 21.00 Small
610 x 610 x 305 76 533 x 533
A24H2412SS6LP3PT 24.00 x 24.00 x 12.00 316L 3.00 A24P24 A24P24G A24P24SS6 21.00 x 21.00 Small
610 x 610 x 305 76 533 x 533
A30H2412SSLP3PT 30.00 x 24.00 x 12.00 304 3.00 A30P24 A30P24G A30P24SS6 27.00 x 21.00 Large
760 x 610 x 305 76 686 x 533
A30H2412SS6LP3PT 30.00 x 24.00 x 12.00 316L 3.00 A30P24 A30P24G A30P24SS6 27.00 x 21.00 Large
762 x 610 x 305 76 686 x 533
A36H3012SSLP3PT 36.00 x 30.00 x 12.00 304 3.00 A36P30 A36P30G A36P30SS6 33.00 X 27.00 Large
914 x 762 x 305 76 838 x 686
A36H3012SS6LP3PT 36.00 x 30.00 x 12.00 316L 3.00 A36P30 A36P30G A36P30SS6 33.00 X 27.00 Large
914 x 762 x 305 76 838 x 686
A36H3612SSLP3PT 36.00 x 36.00 x 12.00 304 3.00 A36P36 A36P36G A36P36SS6 33.00 x 33.00 Large
914 x 914 x 305 76 838 x 838
A36H3612SS6LP3PT 36.00 x 36.00 x 12.00 316L 3.00 A36P36 A36P36G A36P36SS6 33.00 x 33.00 Large
914 x 914 x 305 76 838 x 838
A42H3612SSLP3PT 42.00 x 36.00 x 12.00 304 3.00 A42P36 A42P36G A42P36SS6 39.00 x 33.00 Large
1067 x 914 x 305 76 991 x 838
A48H3612SSLP3PT 48.00 x 36.00 x 12.00 304 3.00 A48P36 A48P36G A48P36SS6 45.00 x 33.00 Large
1219 x 914 x 305 76 1143 x 838
A48H3612SS6LP3PT 48.00 x 36.00 x 12.00 316L 3.00 A48P36 A48P36G A48P36SS6 45.00 x 33.00 Large
1219 x 914 x 305 76 1143 x 838
A60H3612SSLP3PT 60.00 x 36.00 x 12.00 304 3.00 A60P36 A60P36G A60P36SS6 57.00 x 33.00 Large
1524 x 914 x 305 76 1448 x 838
A60H3612SS6LP3PT 60.00 x 36.00 x 12.00 316L 3.00 A60P36 A60P36G A60P36SS6 57.00 x 33.00 Large
1524 x 914 x 305 76 1448 x 838
A48H3616SSLP3PT 48.00 x 36.00 x 16.00 304 3.00 A48P36 A48P36G A48P36SS6 45.00 x 33.00 Large
1219 x 914 x 406 76 1143 x 838
A48H3616SS6LP3PT 48.00 x 36.00 x 16.00 316L 3.00 A48P36 A48P36G A48P36SS6 45.00 x 33.00 Large
1219 x 914 x 406 76 1143 x 838
A60H3616SSLP3PT 60.00 x 36.00 x 16.00 304 3.00 A60P36 A60P36G A60P36SS6 57.00 x 33.00 Large
1524 x 914 x 406 76 1448 x 838
A60H3616SS6LP3PT 60.00 x 36.00 x 16.00 316L 3.00 A60P36 A60P36G A60P36SS6 57.00 x 33.00 Large
1524 x 914 x 406 76 1448 x 838
Purchase panels separately. Optional stainless steel, composite and aluminum panels are available for most sizes.
Accessories
Spec-00480
E63.422.2211
7
763.422.2600
Fits
Enclosure
Catalog Size B
Number For in./mm
ADK12A Single-Door Wall-Mount Enclosures 12.00
305
ADK16A Single-Door Wall-Mount Enclosures 16.00
406
ADK20A Single-Door Wall-Mount Enclosures 20.00
508
ADK24A Single-Door Wall-Mount/Floor-Mount Enclosures with Continuous Hinge 24.00
610
ADK30A Single-Door Wall-Mount/Floor-Mount Enclosures with Continuous Hinge 30.00
762
ADK36A Single-Door Wall-Mount/Floor-Mount Enclosures with Continuous Hinge 36.00
914
ADK42A Two-Door Floor-Mount, Continuous Hinge Enclosures 42.00
1067
ADK48A Two-Door Floor-Mount, Continuous Hinge Enclosures-Door Floor-Mount 48.00
Enclosures 1219
ADK60A Two-Door Floor-Mount, Continuous Hinge Enclosuresoor Floor-Mount 60.00
Enclosures 1524
ADK72A Two-Door Floor-Mount, Continuous Hinge Enclosuresoor Floor-Mount 72.00
Protects door hardware from dripping water and settling dust. Enclosures 1829
Attaches quickly and easily to the enclosure with stainless steel Two-Door Drip Shield kits are not designed for use on 48.00-in. (1219-mm) wide and 60.00-in. (1524-mm)
screws and sealing washers (hardware is furnished). Stainless wide Two-Door Type 12 Wall-Mount Enclosures.
steel hinge pin and stainless steel door clamping assemblies are
furnished to replace the standard hinge pin and door clamping
assemblies. A tube of sealing compound is also supplied with
each kit. Manufactured from 14 gauge steel with an ANSI 61 gray
polyester powder paint finish over pretreated surfaces.
Bulletin: A80
Drip Shield Kit for Type 12 Free-Standing and Fits Enclosure Size B
Floor-Mount Enclosures With Concealed Catalog Number For in./mm
Hinges ADK24HH Single-Door Free-Stand/Floor-Mount Enclosures 24.00
610
Protects door hardware from dripping water and settling dust. ADK30HH Single-Door Free-Stand/Floor-Mount Enclosures 30.00
Attaches quickly and easily to the enclosure with stainless steel 762
screws and sealing washers (hardware is furnished). A tube of ADK36HH Single-Door Free-Stand/Floor-Mount Enclosures 36.00
sealing compound is also supplied with each kit. Manufactured from 914
14 gauge steel with an ANSI 61 gray polyester powder paint finish ADK42HH Two-Door Free-Stand/Floor-Mount Enclosures 42.00
over pretreated surfaces. 1067
ADK48HH Two-Door Free-Stand/Floor-Mount Enclosures 48.00
1067
Bulletin: A80
ADK60HH Two-Door Free-Stand/Floor-Mount Enclosures 60.00
1524
ADK72HH Two-Door Free-Stand/Floor-Mount Enclosures 72.00
1829
Stainless Steel Drip Shield Kit for Type 4 and 4X Easily installed on Type 4 and 4X wall-mount enclosures (excluding
Wall-Mount Enclosures quick-release latch models). Protects door from dripping water
and settling dust. Attaches quickly and easily to the enclosure with
stainless steel screws and sealing washers (furnished). A tube of
sealing compound is supplied with each kit. Manufactured from 14
gauge Type 316 stainless steel. Kits can be special ordered for other
Hoffman enclosures. Consult factory for more information. Product
maintains UL/CSA Type 4, 4X and 12 rating when properly installed
on a Hoffman enclosure.
Bulletin: A4SY
Fits Enclosure Size B
Catalog Number in./mm
ADK12SS6 12.00
305
ADK16SS6 16.00
406
ADK20SS6 20.00
508
ADK24SS6 24.00
610
ADK30SS6 30.00
762
ADK36SS6 36.00
914
C-103-PM Prepunched Aluminum DIN Rail (1 Meter Lengths) ES, GT, MT, OT, ST
(note: Other lengths available, consult factory)
39.370 [1000.00]
1.083[27.50] 1.378[35.00]
TYP. .287[7.29]
R.
1.378[35.00]
.943[23.95] 1.063[27.00]
.177[4.50]
.984[25.00]
C-104-PM Prepunched Steel DIN Rail (1 Meter Lengths) ES, GT, MT, OT, ST
(note: Other lengths available, consult factory)
39.370[1000.00]
.295[7.50]
.492[12.50] .984[25.00]
R.
1.378[35.00] 1.063[27.00]
.205[5.20]
.709[18.00]
C-105-PM Prepunched Steel DIN Rail (1 Meter Lengths) ES, GT, MT, OT, ST
(note: Other lengths available, consult factory)
39.370[1000.00] .590[15.00]
.039[1.00]
.492[12.50] .984[25.00]
R.
.709[18.00]
C-106-2PM Prepunched Steel DIN Rail (2 Meter Lengths) ES, GT, MT, OT, ST
(note: Other lengths available, consult factory)
78.740[2000.00]
.984[25.00] .295[7.50]
.492[12.50]
R.
.709[18.00]
Features/Benefits:
•• Finger-safe protection
Fully insulated block ensures touch safe isolation of live parts. Recessed
termination screws and wire openings provide IP20 grade protection and
qualify as “finger-safe” per IEC 529
•• Compact modularity
Ratings:
Single or multiple pole configurations in the most compact foot rint. Allows
Volts : 600V
users to build smaller or higher density panels.
Amps: : 175 to 840A
•• Snap on DIN-rail mounting
SCCR : 100kA with proper fuse.
Sizes 1 to 4 feature integral DIN rail adaptors allowing for quick and easy
installations on 35mm DIN rail yielding lower installed costs.
Contact Technical Services for
•• Captive termination screws
instruction sheet and/or DC
Unique channel design ensures captive metric wire termination screws.
Ratings.
Screws can never be lost.
•• Available accessories
For multi-pole panel mounting, simply snap in pins for rigid fi . Cap plugs
provide the ability to maintain touch safety on unused openings. Circuit
identification markers simply snap into blocks to ID circuits. nd anchors
provide rigid end stops.
•• Multiple wire ratings Approvals:
Provide users more versatility by offering capability of using multiple •• UL Recognized Component
conductors in #2 and 2/0 openings. Guide XCFR2, File E73571
•• AC & DC ratings •• CSA Certified: Class 6228, Fil
FSPDB1, 2, and 3 have been evaluated for use at 1000V (AC or DC) 69363
provided they are installed on DIN-rails only and with barriers between
poles of opposite polarity of sufficient size to maintain requi ed spacings.
I2
FSPDB Finger-Safe Power Distribution Blocks
Catalog Numbers
Catalog Number Ampere Line Load
Short
Aluminum Copper Rating Wire Range Wire Range
(Based on NEC
Circuit
Openings
(Connector (Connector Table 310-16 for AWG/ Current
rated for 90° C rated for 75° C 75° C Cu wire AWG/ mm2 Openings mm2 Per Pole
kcmil Rating
Cu/AL wire) Cu wire only) only)
Dimensions Accessories
FSPDB1A FSPDB2A FSPDB3A FSPDB4A FSPDB5A Catalog No. Description
FSPDB1C FSPDB2C FSPDB3C FSPDB4C FSPDB5C Accessory pin to form multiple pole
Dimension FSPIN1
block
I
Figure 1 Figure 1 Figure 2 Figure 1 Figure 2
mm in mm in mm in mm in mm in Circuit identification marker for 2/0 &
FSCIM1
#2 max. conductors (Qty of 100)
A 25.4 1.00 28.4 1.12 46.9 1.85 39 1.54 72 2.84
Circuit identification marker for 350,
B 43.3 1.70 57.8 2.28 64.3 2.53 108 4.25 91 3.58
FSCIM2 400 & 600 kcmil max. conductors (Qty
C 49.5 1.95 56.0 2.21 64.3 2.53 80 3.15 80 3.15
of 100)
D 45.1 1.78 51.6 2.03 59.8 2.36 75.5 2.97 - -
FSCAP1 Cap plug for spare 2/0 openings
E 39.4 1.55 39.4 1.55 51.5 2.03 50.1 1.97 50.1 1.97
FSCAP2 Cap plug for spare 350 kcmil openings
F 72.6 2.86 87.7 3.45 100.8 3.97 145.5 5.73 145 5.71
FSCP3 Cap plug for spare 600 kcmil opening
G 59.6 2.35 74.6 2.94 82.4 3.24 120.6 4.75 127.5 5.02
FSEA Pair of end anchors
H 5.3 0.21 5.1 0.20 6.5 0.26 7 0.28 3 0.12
I - - - - 31.5 1.24 - - 52 2.04
J 5.3 0.21 6.4 0.25 6.5 0.26 6.5 0.26 6.5 0.26
K 10 0.40 11.7 0.46 8.9 0.35 16 0.63 8.5 0.34
H
I
K H
Figure 1 Figure 2
K
G G
B
F B
F
E J
D E J
A
D
C A
C
For the most current product performance data visit us-ferrazshawmut.mersen.com and use catalog search. I3
Electric Heaters
Rev. A October 2004
Construction Installation
• Attractive and durable housing is anodized
aluminum
• Thermostat, standard on all units, is adjustable CAUTION
from 0°F to 100°F (-18°C to 38°C)
• Fan draws cool air from the bottom of the These electric heaters are not designed for
enclosure and passes this air across the use in dusty, dirty, corrosive, or hazardous
thermostat and heating elements before locations.
being released into enclosure cavity Portions of the heater can get hot. Adequate
• Heated air is discharged through the top of protection must be taken to protect people
the heater unit from potential burns, and to protect other
• Four 10-32 self-tapping screws are included components from this heat.
with each heater Hoffman recommends this heater only be
• Ball bearing fan runs continuously for even installed in a totally-enclosed metal
temperature distribution enclosure.
• Terminal strip with clamp connector that Do not install heaters on wood panels.
accepts both solid and stranded wire
Finish
Hoffman electric heaters should be centered as
Brushed aluminum. low as possible on an interior enclosure panel.
This permits the unit to heat the cool air
Application Industry Standards located at the bottom of the enclosure. For
maximum efficiency and longevity, the heater
Designed to protect sensitive mechanical, UL Component Recognized should be mounted in a vertical position with
electrical, and electronic equipment from the CSA Listed the terminal block to the bottom and the air
harmful effects of condensation, corrosion, and CE outlet openings at the top in a sealed
low temperatures.Thermostatically controlled enclosure free from dust or debris. However,
fan-driven heater units maintain a stable the unit will also effectively distribute heat if
temperature within enclosures so critical turned 90 degrees with the terminal block out
components can perform more reliably over the bottom and the air outlet at the side.
a longer period of time. Although enclosure panels are preferable,
heaters may be installed on any flat sheet metal
surface. Do not install heaters on wood panels.
Heat sensitive components should not be
placed near the heater discharge area since this
air can be quite warm.The clearance range
defines the space that must be kept free of
these components for proper and safe
operation of the heater.
9.46 Data subject to change without notice ☎ 763 422 2211 FAX 763 422 2600 ©2003 Hoffman Enclosures Inc.
Bulletin
D85
Heaters
■ Dimensions and Clearance Range for
DAH1001A, -2A and DAH2001A, -2A
Electric Heaters
■ Dimensions and Clearance Range for
DAH4001B, -2B and DAH8001B, -2B
Data subject to change without notice ☎ 763 422 2211 FAX 763 422 2600 ©2003 Hoffman Enclosures Inc. 9.47
Pulse isolator
5202B 5202B4
– 2 channels - 2 or 4 outputs
– Dual output
– 5-port 3.75 kVAC galvanic isolation
– Cable error detection
– Universal supply by AC or DC
Application
Connection
• Pulse isolator with safety barrier for the supply of NAMUR
sensors installed in the hazardous area.
• Pulse isolator with safety barrier for the detection of
mechanical contacts installed in the hazardous area.
• One input signal can be used on two separate outputs.
• A cable error alarm can be detected on a separate output.
Technical characteristics
• PR5202B1 and 5202B2 have relays with change-over
contacts or open NPN collectors available in the safe area.
• PR5202B4 has 4 SPST relays, which are activated
simultaneously two and two, available in the safe area. Each
relay can be programmed to the function N.O. or N.C.
• Inputs, outputs and supply are floating and galvanically
separated.
• 5202B is designed according to strict safety requirements and
is therefore suitable for application in SIL 2 installations.
Mounting / installation
• Mounted vertically or horizontally on a DIN rail. Up to 84
channels per meter can be mounted.
This page is automatically generated on the basis of information provided on www.prelectronics.com and affiliated websites. It is provided to you as a service and for information
purpose only. While we have attempted to maintain the information as accurately as possible, the page may contain errors or omissions for which we disclaim any and all liability
Environmental Conditions Output specifications
Specifications range....................................... -20°C to +60°C Relay output: Max. switching
Calibration temperature................................. 20...28°C frequency....................................................... 20 Hz
Relative humidity............................................ < 95% RH (non-cond.) Max. voltage................................................... 250 VRMS
Protection degree........................................... IP20 Max. current................................................... 2 AAC
Max. AC power.............................................. 100 VA
Mechanical specifications Max. load at 24 VDC...................................... 1 A
Opto, NPN outputs: Max. switching
Dimensions (HxWxD)..................................... 109 x 23.5 x 130 mm frequency....................................................... 5 kHz
Weight approx................................................ 230 g Min. pulse length, NPN output....................... > 0.1 ms
Wire size........................................................ 1 x 2.5 mm2 stranded wire Max. load, current / voltage............................ 80 mA / 30 VDC
Screw terminal torque.................................... 0.5 Nm Voltage drop at 25 mA / 80
mA.................................................................. < 0.75 VDC / < 2.5 VDC
Common specifications
Supply voltage, universal............................... 21.6...253 VAC, 50...60 Hz or Approvals
19.2...300 VDC EMC............................................................... EN 61326-1
Fuse............................................................... 400 mA SB / 250 VAC LVD................................................................ EN 61010-1
Max. power consumption............................... ≤ 1.5 W (2 channels), 5202B1 PELV/SELV.................................................... IEC 364-4-41 and EN 60742
and 5202B2
ATEX.............................................................. DEMKO 99ATEX127186
Max. power consumption............................... ≤ 2.0 W (2 channels), 5202B4
UL................................................................... UL 913, UL 508
Internal consumption...................................... ≤ 1.5 W (2 channels), 5202B1
and 5202B2 GOST R......................................................... Yes
Internal consumption...................................... ≤ 2.0 W (2 channels), 5202B4 GOST Ex........................................................ Yes
Isolation voltage, test /
working........................................................... 3.75 kVAC / 250 VAC
Auxiliary supplies: NAMUR
supply............................................................. 8 VDC / 8 mA
EMC immunity influence................................ < ±0.5%
Extended EMC immunity: NAMUR
NE 21, A criterion, burst................................. < ±1%
Input specifications
Sensor types.................................................. NAMUR according to EN
60947-5-6 / Mechanical
contact
Frequency range............................................ 0...5 kHz
Pulse length................................................... > 0.1 ms
Input resistance.............................................. 1 kΩ
Trig level, signal............................................. < 1.2 mA, > 2.1 mA
Trig level, cable fault...................................... < 0.1 mA, > 6.5 mA
5202B-091013
PRetrans 5104B
1- or 2-channel version
Universal supply by AC or DC
Application:
• Supply voltage and safety barrier for 2-wire 2-wire transmitter
transmitters mounted in a hazardous area. Output
• Safety barrier for analogue current / voltage
signals from a hazardous area.
Supply
• 1 : 1 or signal conversion of analogue current /
voltage signals.
Technical characteristics:
Current, mA
• The 20 factory-calibrated measurement
ranges in the 5104B can be selected by the Output
internal DIP-switches without the need for
recalibration. Special measurement ranges
can be delivered. Supply
• PR5104B is based on microprocessor
technology for gain and offset. The analogue
signal is transmitted at a response time of less
Voltage
than 25 ms.
• Inputs, outputs, and supply are floating and Output
galvanically separated.
• The output can be connected either as an Supply
active current / voltage transmitter or as a 2-
wire transmitter.
Mounting / installation:
3-wire transmitter
• Mounted vertically or horizontally on a DIN
rail. By way of the 2-channel version up to 84 Output
channels per metre can be mounted.
• NB: 5104B is recommended as Ex barrier for Supply
5331D, 5333D, 5334B, 5343B, 6331B, 6333B,
and 6334B.
When the level drops, pumping stops and When it reaches the and pumping
the micro switch is the level begins to highest permissible resumes.
activated.... rise.... point, the second
regulator reacts....
In Figure 1, liquid level is below the lowest level sensor #4. When sensor #4 tilts, it will send a signal to an alarm
(FLS 1). All sensors are hanging straight in the wet well, system, normally an alarm bell or red alarm light. There
therefore, the circuits in the sensor are not complete are other options for alarm conditions such as alert by
and no signal is being sent to the control. Both pumps telephone, etc. The alarm system issues a warning
are OFF. that something has happened in the station that could
result in an overflow condition. This could be a control
In Figure 2, as the liquid level rises, FLS-1 tilts and the problem, one or both pumps not operating, pumps not
sensors mechanical micro-switch completes the circuit operating up to capacity, etc. Regardless of the cause,
sending a signal to energize the control. At this point an alarm calls for immediate action.
both pumps are still in the OFF mode.
For most installations, the low level shut-off sensor should
In Figure 3, the liquid level has risen to a level that tilts be located approximately at the top of the pump volute.
level sensor #2, completing its circuit. However, there are certain situations where maximum
cooling may be required such as when pumping warm
a) This signal to the control activates the liquids; in certain cases with pumps that do not have
contactor in the control which, in turn, starts cooling jackets; some large horsepower units, etc. Also
the lead pump. in situations where the NPSH requires a liquid level that
is above the pump volute. When in doubt, contact Flygt
b) Level sensor #2 also at this time activates Application Engineering.
the alternator in the control which
automatically selects the other pump to
become the lead pump on the next start-up
cycle. The alternation of the pumps as the
"lead" pump serves two purposes:
Fig. 1 Fig. 2
FLS-4
FLS-3
FLS-2
FLS-1
Fig. 3 Fig. 4
Fig. 5
Issued: 6/94 Supersedes: 6/90
The Flygt ENM-10 Liquid Level Sensor can be utilized ENM-10 will operate in the "Pump Down" mode, activating
to monitor a "Pump Down" operation (as in a lift station the pumps at a selected high liquid level and shut off at a
application) or a "Pump UP" (filling) operation as may be selected low liquid level. Using the Red and White wires
required in certain industrial applications. The ENM-10 as the pilot circuit will activate the pumps in a "Pump
sensor cable contains three wires; Red, Black and White. UP" mode controlling the filling of a sump, tank etc. In
The Red wire is common to both sequences. Using the this case the pumps are activated at a selected low level
Red and Black wires as the liquid level pilot circuit, the and shut off at a selected high level.
BLACK BLACK
CONDUCTOR CONDUCTOR
TIED OFF & TIED OFF &
TAPED. TAPED.
POSITION 2
CHEMICAL RESISTANCE LIST
Issued: 3/11 Supersedes: 6/94
The liquid in which level regulation is practiced most The classification is broken down into the following
Flygt
frequently Monitoring
is, of course, water. OfDevices
the millions of regu- categories:
lators in use
ENM-10 all overLevel
Liquid the world today, it is estimated
Sensors 0 = No effect, 1 = Minor to moderate and 2 = Severe
that nine out of ten work in water. effect. The sign — means that information is not avai-
However, with a float body of polypropylene, a cable lable.
The
of PVCliquid in which level
or NBR/PVC regulation
nitrile/PVC orand
rubber NBR/PVC
a ben-nitrile/PVC rubber and 0 = No affect, 1= Minor to Moderate
is practiced Keep in mind also that the density
andof2 the liquid deter-
ding relief ofmost
EPDM frequently
rubber,isthe
water.
ENM-10 a protective
is virtuallysleeve mines
of EPDM
the
rubber.
bouyancy
Resistance = Non-Resistant.
Of the millions
insensitive of regulators
to many in useliquids.
aggressive all The density of a liquidENM-10
of the regulator. The is
determines
made for seven different densities.
over the world today, it is estimated The table shows how resistant the the bouyancy of the regulator. The See page 2.
The tableout
that nine shows
of tenhow resistant
work the ENM-10
in water. equipped
material is to different chemicals ENM-10 is made for seven different
with either PVC or NBR/PVC nitrile/PVC rubber Always
cable, temperatures. observe local regulations:
at two different Take The note
particular densities.
of:
is
Theto ENM-10
different chemicals
is virtually at two differentclassification
insensitive temperatures. is broken
• riskdown into
of fire/explosio
to many aggressive liquids with its three categories: • hygiene requirements
body of polypropylene, a cord of PVC
20°C 60°C 20°C 60°C 20°C 60°C 20°C 60°C 20°C 60°C 20°C 60°C
(68°F) (140°F) (68°F) (140°F) (68°F) (140°F) (68°F) (140°F) (68°F) (140°F) (68°F) (140°F)
209921 Expert™ 3400, range 0 - 1 ft. WG 209928 Expert™ 3400, range 0 - 1000 ft. WG
209922 Expert™ 3400, range 0 - 3 ft. WG 209991 Expert™ 3400, range 0 - 1 ft. 1" NPT top
209923 Expert™ 3400, range 0 - 10 ft. WG 209992 Expert™ 3400, range 0 - 3 ft. 1" NPT top
209925 Expert™ 3400, range 0 - 30 ft. WG 209993 Expert™ 3400, range 0 - 10 ft. 1" NPT top
209926 Expert™ 3400, range 0 - 100 ft. WG 209996 Expert™ 3400, range 0 - 100 ft. 1" NPT top
209927 Expert™ 3400, range 0 - 300 ft. WG 202925 Expert™ 3400 w/ special meas. range
Dimensions and
Dia.1.97
Level Transmitter
Dia.1.97
5.31 1.42
2.4 in.
Applications
• For use in branch circuit wiring
in wet, damp, or dry locations
• May be used as a weatherproof
junction box, or as a housing for
receptacles, switches, and GFCI’s
Product Features 5320-0 TO 5320-7 5321-0 TO
• Reinforced connector outlets 5324-0 TO 5324-5 5321-7, 5330-0 5322-0, 5331-0
• State-of-the-art powder coat finish
• Eight box mounting options with
detachable lugs provided
• Two closure plugs included 5385-0 TO 5387-0
5323-0, 5332-0
• Ground screw installed
• Multi-lingual instructions O R D E R I N G I N F O R M AT I O N - D I M E N S I O N S
in each package
Compliances
2 " D E E P, W I T H L U G S – T H R E E T H R E A D E D O U T L E T S – 4 - 1 / 2 " x 2 - 3 / 4 "
• – Standard 514A
®
WEATHERPROOF BOXES,
COVERS AND LIGHTING
5322-0 16.5 Gray 5–1/2" Shrink 20
5331-0 16.0 Gray 5–3/4" Shrink 20
5323-0 17.0 Gray 5–1/2" Shrink 20
5332-0 16.5 Gray 5–3/4" Shrink 20
& !
&
!
& %
+ = or + =
& ( GFCI
Adapter
(Included) Duplex
Adapter
(Included)
Without
Adaptor
Switch 1 1/4" 1 3/8" 1 9/16" & 1 5/8" 1 11/16" 2 1/8" 2 1/4"
or
Without
# "!
Adapter Adapter Adaptor
GFCI (Included) Duplex (Included) Switch 1 1/4" 1 3/8" 1 9/16" 1 11/16" 2 1/8" 2 1/4"
& 1 5/8"
# "!
&
!
+ = + + + + =
& !
or # "!
Without
Adapter Adapter Adaptor
GFCI (Included) Duplex (Included) Switch 1 1/4" 1 3/8" 1 9/16" 1 11/16" 2 1/8" 2 1/4"
& 1 5/8"
www.taymac.com 12
Section 5
Warranty and Service
WARRANTY
XYLEM WATER SOLUTIONS USA, INC.
For the period defined, XYLEM WATER SOLUTIONS USA, INC. offers a commercial warranty to the original End Purchaser
against defects in workmanship and material on Flygt Products. Warranty covers Flygt parts and labor as outlined in
ADDENDUM – A.
COVERAGE:
XYLEM WATER SOLUTIONS USA, INC. will pay the cost of parts and labor during the warranty period, provided that the
Flygt product, with cable attached, is returned prepaid to an XYLEM WATER SOLUTIONS USA, INC. Authorized Service
Facility for Flygt Product repairs. Coverage for Flygt parts and labor will be provided for the period shown in ADDENDUM
- A. The warranty period will begin from date of shipment or date of a valid Start-up (For permanently installed pumps
only). In cases where the Start-up date is used as the beginning of the warranty on a permanently installed Flygt pump, a
Start-up Report completed by an approved service technician from an XYLEM WATER SOLUTIONS USA, INC. Authorized
Service Facility for Flygt products must be received by the XYLEM WATER SOLUTIONS USA, INC. Area Service Manager
for Flygt Products within thirty (30) days of the initial onset of the unit placed into service. If not received, the beginning
of the warranty coverage will default to the Flygt product ship date. A Start-up for a permanently installed Flygt pump
must occur within one (1) year from the date of shipment from an XYLEM WATER SOLUTIONS USA, INC. authorized
facility for Flygt Products or warranty will automatically default to ship date as start of warranty. (See STORAGE section)
When using the start-up date as the beginning of the warranty, a copy of the Start-up Report will be required to support
any Warranty Claims. Warranty on Flygt Dewatering pumps will begin with ship date only. No other date on Flygt
Dewatering pumps will be considered.
XYLEM WATER SOLUTIONS USA, INC.’S sole obligation under this Warranty for Flygt Products shall be to replace, repair
or grant credit for Flygt Products upon XYLEM WATER SOLUTIONS USA, INC.’S exclusive determination that the Flygt
Product does not conform to the above warranty. In the event that the Flygt product is replaced, warranty on the
replacement product will be equal to the balance remaining on the original product or ninety (90) days, whichever is
greater.
MISUSE:
This Warranty shall not apply to any Flygt product or part of Flygt product which (i) has been subjected to misuse,
misapplication, accident, alteration, neglect, or physical damage (ii) has been installed, operated, used and/or maintained
in a manner which is in an application that is contrary to XYLEM WATER SOLUTIONS USA, INC.’S printed instructions as it
pertains to installation, operation and maintenance of Flygt Products, including but without limitation to (iii) operation of
equipment without being connected to monitoring devices supplied with specific products for protection; or (iv) damaged
due to a defective power supply, improper electrical protection, faulty installation or repair, ordinary wear and tear,
corrosion or chemical attack, an act of God, an act of war or by an act of terrorism; or (v) has been damaged resulting
from the use of accessory equipment not sold by XYLEM WATER SOLUTIONS USA, INC. or not approved by XYLEM
WATER SOLUTIONS USA, INC. in connection with Flygt products.
WEAR PARTS:
This warranty does not cover costs for standard and/or scheduled maintenance performed, nor does it cover Flygt parts
that, by virtue of their operation, require replacement through normal wear (aka: Wear Parts), unless a defect in material
or workmanship can be determined by XYLEM WATER SOLUTIONS USA, INC.. Wear Parts are defined as Cutters, Cutting
Plates, Impellers, Agitators, Diffusers, Wear Rings (Stationary or Rotating), Volutes (when used in an abrasive
environment), oil, grease, cooling fluids and/or any items deemed necessary to perform and meet the requirements of
normal maintenance on all Flygt equipment.
WARRANTY
XYLEM WATER SOLUTIONS USA, INC.
DISCLAIMERS:
(i) XYLEM WATER SOLUTIONS USA, INC.’S warranties are null and void when Flygt Products are exported outside of the
United States of America without the knowledge and written consent of XYLEM WATER SOLUTIONS USA, INC. U.S.A.,
INC.; (ii) XYLEM WATER SOLUTIONS USA, INC. makes no independent warranty or representation with respect to parts
or products manufactured by others and provided by XYLEM WATER SOLUTIONS USA, INC. (however, XYLEM WATER
SOLUTIONS USA, INC. will extend to the Purchaser any warranty received from XYLEM WATER SOLUTIONS USA, INC.’S
supplier for such parts or products).
LIMITATIONS:
XYLEM WATER SOLUTIONS USA, INC. NEITHER ASSUMES, NOR AUTHORIZES ANY PERSON OR COMPANY TO ASSUME
FOR XYLEM WATER SOLUTIONS USA, INC., ANY OTHER OBLIGATION IN CONNECTION WITH THE SALE OF ITS FLYGT
EQUIPMENT. ANY ENLARGEMENT OR MODIFICATION OF THIS WARRANTY BY A FLYGT PRODUCT DISTRIBUTOR, OR
OTHER SELLING AGENT SHALL BECOME THE EXCLUSIVE RESPONSIBILITY OF SUCH ENTITY. THE FOREGOING
WARRANTY IS EXCLUSIVE AND IN LIEU OF ANY AND ALL OTHER EXPRESS OR IMPLIED WARRANTIES, GUARANTEES,
CONDITIONS OR TERMS OF WHATEVER NATURE RELATING TO FLYGT PRODUCT(S), INCLUDING AND WITHOUT
LIMITATION ANY IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE WHICH
ARE HEREBY EXPRESSLY DISCLAIMED AND EXCLUDED. PURCHASER’S EXCLUSIVE REMEDY AND XYLEM WATER
SOLUTIONS USA, INC.’S AGGREGATE LIABILITY FOR BREACH OF ANY OF THE FOREGOING WARRANTIES IS LIMITED
TO REPAIRING OR REPLACING FLYGT PRODUCTS AND SHALL IN ALL CASES BE LIMITED TO THE AMOUNT PAID BY THE
PURCHASER HEREUNDER. IN NO EVENT IS XYLEM WATER SOLUTIONS USA, INC. LIABLE FOR ANY OTHER FORM OF
DAMAGES, WHETHER DIRECT, INDIRECT, LIQUIDATED, INCIDENTAL, CONSEQUENTIAL, PUNITIVE, EXEMPLARY OR
SPECIAL DAMAGES, INCLUDING BUT NOT LIMITED TO LOSS OF USE, LOSS OF PROFIT, LOSS OF ANTICIPATED
SAVINGS OR REVENUE, LOSS OF INCOME, LOSS OF BUSINESS, LOSS OF PRODUCTION, LOSS OF OPPORTUNITY OR
LOSS OF REPUTATION.
XYLEM WATER SOLUTIONS USA, INC. WILL NOT BE HELD RESPONSIBLE FOR TRAVEL EXPENSES, RENTED EQUIPMENT,
OUTSIDE CONTRACTOR'S FEES, OR ANY EXPENSES ASSOCIATED WITH A FLYGT PRODUCT REPAIR SHOP NOT
AUTHORIZED BY XYLEM WATER SOLUTIONS USA, INC. U.S.A., INC. REIMBURSEMENT COSTS FOR CRANES AND/OR ANY
SPECIAL EQUIPMENT USED IN CONJUNCTION FOR THE REMOVAL AND/OR REINSTALLATION OF ANY FLYGT
EQUIPMENT IS NOT COVERED UNDER THIS WARRANTY.
ANY UNAUTHORIZED ALTERATIONS TO SUPPLIED FLYGT EQUIPMENT USED WITHOUT XYLEM WATER SOLUTIONS USA,
INC. SUPPLIED FLYGT BRAND CABLE OR CONTROLS WILL NOT BE COVERED UNDER THIS WARRANTY, UNLESS IT CAN
BE PROVEN SUCH ANCILLARY EQUIPMENT IS SUITABLE FOR THE PURPOSE AND EQUAL TO XYLEM WATER SOLUTIONS
USA, INC. SUPPLIED FLYGT BRAND CABLES OR CONTROLS THAT WOULD ORIGINALLY HAVE BEEN SUPPLIED WITH THE
TYPE OF EQUIPMENT IN USE.
REQUIREMENTS:
A copy of Electrical System Schematics of the Control used (including a Control’s Bill of Material) could be required to
support a Warranty Claim when a non Flygt Brand Control is used. In addition, a written record, hereby known as “the
log”, will be associated with each unit serial number and must be maintained by the organization having product
maintenance responsibility. The log must record each preventative maintenance activity and any repair activity during the
life of the warranty or verification that an XYLEM WATER SOLUTIONS USA, INC. authorized Service Contract for Flygt
Products is in force and must be available for review and/or auditing. Failure to meet these conditions could render this
warrant null and void. Such logs could be required to determine warranty coverage.
WARRANTY
XYLEM WATER SOLUTIONS USA, INC.
STORAGE:
Should a delay occur between ship date and the date of start-up, maintenance as outlined in XYLEM WATER SOLUTIONS
USA, INC.’S Care & Maintenance Manual for Flygt Products must be performed by the “CONTRACTOR” and/or “OWNER”
during any such period of storage. Documentation providing proof and outlining what maintenance was performed must
be provided to XYLEM WATER SOLUTIONS USA, INC. or its Flygt Products representative within thirty (30) days of said
maintenance, or the XYLEM WATER SOLUTIONS USA, INC. warranty for Flygt Products could be considered void.
CONTROLS:
Warranty coverage for permanently installed controls will start for the end purchaser on the date of shipment.. This
warranty does not apply to controls that have been damaged due to a defective and/or improper input power supply,
improper electrical protection, accidental damage, improper or unauthorized installation and/or repair, unauthorized
alteration, negligence, environmental corrosion or chemical attack, improper maintenance or storage of control, any act of
God, an act of war, an act of terrorism or damage resulting from the use of accessory equipment not approved by XYLEM
WATER SOLUTIONS USA, INC.. Further, this warranty does not apply in the event an adjustment is found to correct the
alleged defect.
Solid state devices will be covered for a period of one (1) year. Electrical control panels containing controllers, PLC’s,
drives, soft starts, and other computerized equipment will require Transient Voltage Surge Suppression (TVSS) protection
in order to satisfy the requirements of this warranty. The protection equipment associated with the control must be kept
in working condition during the life of the warranty. Auxiliary equipment supplied with the control (air-conditioners etc.) is
limited by the respective original equipment manufacturer’s warranty offered. Consumable items such as: light bulbs,
fuses, and relays are covered under normal operating conditions. Electrical surges experienced during startups and/or
during normal operating use of the control panel will cause the consumable items not to be covered under this warranty
policy. Components not supplied by XYLEM WATER SOLUTIONS USA, INC. will not covered by this warranty.
Flygt Products contained within a TOP pre-engineered fiberglass pump station will carry the standard XYLEM WATER
SOLUTIONS USA, INC. warranty for Flygt products and/or accessories installed in the TOP pre-engineered fiberglass
pump station.
All Flygt Product restrictions and/or limitations as outlined and described within the context of this warranty are germane
to all sections of this XYLEM WATER SOLUTIONS USA, INC. Warranty document.
Electrical Control Panels (permanently installed) Xylem Manufactured Control Panels - 3 - Years 100% - 1 YR LIMITED - 2 - YR
100%
Accessories Permanent / Portable (From Ship
Date)
Ver 8 -120909
Xylem Water Solutions USA, Inc.
http://www.xyleminc.com
Corporate Headquarters
Xylem Water Solutions USA, Inc.
Flygt/WEDECO Products
14125 South Bridge Circle
Charlotte, NC 28273
Tel. (704) 409-9700
Fax.(704) 295-9080
flygt_nc@xyleminc.com
http://www.xyleminc.com
Flygt Product Direct Sales Offices
Xylem Water Solutions USA, Inc. Xylem Water Solutions USA, Inc. Xylem Water Solutions USA, Inc.
11161 Harrel Street 90 Horizon Drive
North Carolina: 204 Industrial Boulevard
Mira Loma, CA 91752 Suwanee, GA 30024 Cedar Park, TX 78613
Xylem Water Solutions USA, Inc.
Tel: (951) 332-3668 Tel: (770) 932-4320 Tel: (512) 260-0281
14125 South Bridge Circle
Fax: (951) 332-3679 Fax: (770) 932-4321 Fax: (512) 260-0286
Charlotte, NC 28273
flygt_ca2@xyleminc.com flygt_ga@xyleminc.com flygt_tx1@xyleminc.com
Tel: (704) 504-8804
http://xyleminc.com http://xyleminc.com http://xyleminc.com
Fax: (704) 504 8773
flygt_nc@xyleminc.com
Xylem Water Solutions USA, Inc. Xylem Water Solutions USA, Inc.
http://xyleminc.com
13350 Gregg Street Suite 108 Illinois: 1959 Saratoga Blvd, Bldg. 29
Poway, CA 92064 Corpus Christi, TX 78417
Tel: (858) 679 9344 Xylem Water Solutions USA, Inc. Ohio: Tel: (361) 808-7867
Fax: (858) 679 9480 8402 West 183rd Street Suite A Fax: (361) 225-2965
flygt_ca3@xyleminc.com Tinley Park, IL 60477 Xylem Water Solutions USA, Inc. flygt_tx2@~xyleminc.com
http://xyleminc.com Tel: (708) 342-0484 1615 State Route 131 http://xyleminc.com
Fax: (708) 342-0491 Milford, OH 45150
flygt_il@xyleminc.com Tel: (513) 831-7867 Xylem Water Solutions USA, Inc.
Connecticut: http://xyleminc.com Fax: (513) 831-7868 17352 Bell North Drive
flygt_oh1@xyleminc.com Schertz, TX 78154
Xylem Water Solutions USA, Inc. Tel: (210) 946-7867
http://xyleminc.com
1000 Bridgeport Ave., Suite 402 Indiana: Fax: (210) 651-3057
Shelton, CT 06484 flygt_tx3@xyleminc.com
Xylem Water Solutions USA, Inc.
Tel: (203) 712-8999 Xylem Water Solutions USA, Inc. http://xyleminc.com
121 Commerce Park Drive
Fax: (203) 712-8998 Indiana, LLC
Westerville, OH 43082
flygt_info@xyleminc.com 7615 West New York St.
http://xyleminc.com Indianapolis, IN 46214
Tel: (513) 831-7867 Wisconsin:
Fax: (614) 895-2646
Tel: (317) 273-4470
flygt_oh2@xyleminc.com Xylem Water Solutions USA, Inc.
Fax: (317) 273-4480
Florida: flygt_in@xyleminc.com
http://xyleminc.com N27 W23291 Roundy Drive
http://xyleminc.com Pewaukee, WI 53072
Xylem Water Solutions USA, Inc.
Florida, LLC
Oregon: Tel: (262) 544-1922
Xylem Water Solutions USA, Inc. Fax: (262) 544-1399
2152 Sprint Blvd flygt_wi@.xyleminc.com
Indiana, LLC Xylem Water Solutions USA, Inc.
Apopka, FL 32703 http://xylemwin.com
950 Maxwell Avenue 2630 North Marine Drive
Tel: (407) 880-2900
Evansville, IN 47711 Portland, OR 97217
Fax: (407) 880-2962
Tel: (812) 421-2486 Tel: (503) 240-1980
flygt_fl@xleminc.com
Fax: (812) 421-4612 Fax: (503) 240-3445
http://xyleminc..com
flygt_in1@xyleminc.com flygt_or@xyleminc.com
http://xyleminc.com http://xyleminc.com
Xylem Water Solutions USA, Inc.
Florida, LLC Kentucky: Pennsylvania:
1730 Tenth Street W
Riviera Beach, FL 33404 Xylem Water Solutions USA, Inc. Xylem Water Solutions USA, Inc.
Tel: (561) 848-1200 3865 Produce Road Suite 225 2330 Yellow Springs Road
Fax: (561) 848-1299 Louisville, KY 40218 Malvern, PA 19355
flygt_fl12@xylem.com Tel: (502) 969-0186 Tel: (610) 647-6620
http://xyleminc.com Fax: (502) 969-0576 Fax: (610) 647-5563
flygt_ky@xyleminc.com flygt_pa@xyleminc.com
http://xyleminc.com http://xyleminc.com
Xylem Water Solutions USA, Inc.
Florida, LLC
5771 Country Lakes Drive
Massachusetts:
Ft. Myers, FL 33905
Xylem Water Solutions USA, Inc.
Tel: (239) 693-5226
78K Olympia Avenue
Fax: (239) 693-1485
Woburn, MA 01801
flygt_fl2@xyleminc.com
Tel: (781) 935-6516
http://xyleminc.com
Fax: (781) 938-0364
flygt_ma@xyleminc.com
http://xyleminc.com
SUBMERSIBLE PUMPS & MIXERS
Authorized Service & Sales Facility
for
Warranty & Non-Warranty Repair Work
To order service or parts or answer any questions, contact your local branch office:
XYLEM / FLYGT PRODUCTS
2630 North Marine Drive
Portland, OR 97217
PHONE: 503-240-1980
FAX: 503-240-3445
Replacement Parts Sales and Service: Dave Olson (Ext. 2902175)
David.Olson2@xyleminc.com