Site Test Report Date: 29/5/2018 Contractor's Name: HADI HAIDER Customer: Sec-Eoa Jubail Commercial Port 115/13.8Kv Ss-2 Tapcon 260 Avr Relay

You might also like

Download as doc, pdf, or txt
Download as doc, pdf, or txt
You are on page 1of 4

SITE TEST REPORT Date : 29/5/2018

Customer:
Contractor’s name: HADI HAIDER
SEC-EOA
JUBAIL COMMERCIAL PORT 115/13.8kV SS-2 Contract No. : 071-C20R
Page 1 of 4
TAPCON 260 AVR RELAY
Panel NO.

1. GENERAL DATA AND INFORMATION.

Panel No: 6RTCC1 Designation 90


Make MR Rated current 1A
Serial No: 1620766 Aux: Voltage 88-265 VAC/DC
Model No: TAPCON 260 Setting Type Relay final setting
Application VOLTAGE CT Ratio 4000/1A
REGULATION
VT Ratio 115kV/115V

2. MECHANICAL CHECKS AND VISUAL INSPECTION.


ITEM DESCRIPTION REMARKS
1. Inspect for any physical damage or defects. OK
2. Verify connections as per approved drawing. OK
3. Check tightness of all connections. OK
4. Check Apparatus list. OK

3. ELECTRICAL TESTS:
3.1. FUNCTION TEST:

ITEM DESCRIPTION REMARKS


1. Check of LED Indications OK
2. Check of LCD Display OK
3. Watch dog contact checked OK
4. Binary inputs checked. OK

3.2. Check of Voltage Measurement : Limits: +/- 0.3%


Applied Voltage (V) Measured Voltage (kV) Error %
92
115
138

3.3 Check of Current Measurement: Limits: +/- 0.2%

Applied Current in Yellow Calculated Measured Error %


Phase (A) Primary (A) Primary (A)
0.25 1000
0.5 2000
0.75 3000

TESTING ENGINEER SEC CSD Engineer

Signature: ________________ Signature: ________________


Name : HAMED MEHMOOD (XER-029) Name : ALAA OSAMA
SITE TEST REPORT Date : 29/5/2018
Customer:
Contractor’s name: HADI HAIDER
SEC-EOA
JUBAIL COMMERCIAL PORT 115/13.8kV SS-2 Contract No. : 071-C20R
Page 2 of 4
TAPCON 260 AVR RELAY
Panel NO.

3.4 Check of Voltage Level:

Regulating Value: U Bal = U1+U2/2 BW% Set: 1.5% Limits: +/- 0.3%

Volts Calculated Values Measured Values Error % Balance


Raise Raise Raise Lower Raise Lower
115 113.275 116.725

3.5 Check of Bandwidth:

U BW = [{(U2-U1) /2}*100]/115 BW Volts= (U2 – U1) / 2 Limits: +/- 0.3%

Band Calculated Values Measured Value Error %


Band Band
Width % Raise Lower Raise Lower Raise Lower Width (V) % Width
set
2 113.275 116.725

3.6 Check of Time Linear: Bandwidth = +/- 1.5% & du = 5%

Voltage Actual Time T1


Selected Time T1
Raise Lower Raise Lower
109.25 120.75 60 sec

Limits: +/- 10% Calculated Time Value

3.7 Check of Delay Time 2:

Voltage Actual Time T2


Selected Time T2
Raise Lower Raise Lower
109.25 120.75 10 sec

TESTING ENGINEER SEC CSD Engineer

Signature: ________________ Signature: ________________


Name : HAMED MEHMOOD (XER-029) Name : ALAA OSAMA
SITE TEST REPORT Date : 29/5/2018
Customer:
Contractor’s name: HADI HAIDER
SEC-EOA
JUBAIL COMMERCIAL PORT 115/13.8kV SS-2 Contract No. : 071-C20R
Page 3 of 4
TAPCON 260 AVR RELAY
Panel NO.
Limits: +/- 10% Calculated Time value

3.8 Under Voltage Blocking: Set Un = 115 V Limits: +/- 0.3%

Scale Setting Voltage Measured Values


%Un Pick-up Error % Reset
80% 92

3.9 Over Voltage Monitoring: Set Un = 115V Limits: +/- 0.3%

Scale Setting Voltage Measured Values


%Un Pick-up Error % Reset
110% 126.5

3.10 Over Current Blocking: Set In = 1.3 A Limits: +/- 1.0%

Scale Setting In Current (A) Measured Values


% Pick-up Error % Reset
130% 1

Testing Instrument Used;

Instrument Calibration Valid up


Sl. No
Used to

FREJA 300 8501835 17-03-2021

TESTING ENGINEER SEC CSD Engineer

Signature: ________________ Signature: ________________


Name : HAMED MEHMOOD (XER-029) Name : ALAA OSAMA
SITE TEST REPORT Date : 29/5/2018
Customer:
Contractor’s name: HADI HAIDER
SEC-EOA
JUBAIL COMMERCIAL PORT 115/13.8kV SS-2 Contract No. : 071-C20R
Page 4 of 4
TAPCON 260 AVR RELAY
Panel NO.

TESTING ENGINEER SEC CSD Engineer

Signature: ________________ Signature: ________________


Name : HAMED MEHMOOD (XER-029) Name : ALAA OSAMA