Professional Documents
Culture Documents
Transformer 1
Transformer 1
Transformer 1
33
Transformer (Construction and Operation)
Transformer Connections
The (delta – delta), the (delta – y), and the (Y – Y) connections are the most generally
used. They are illustrated in figure 8.
The Y - delta and the delta - delta connections may be used as step up transformers for
moderate voltages/ The Y - delta has the advantage of providing a good grounding point
on the Y connected side.
Delta connections are not the best for transmission at very high voltage; they may however
be associated with other connections which provide means for properly grounding the high
voltage system.
• The step up delta - Y and step down Y - delta connections are the best for high
voltage transmission systems. They are economical in cost, and they provide a stable
neutral where the high voltage system may be directly grounded.
•
• The Y - Y connection may be used to interconnect two delta systems and provide
suitable neutrals for grounding both of them
34
Transformer (Construction and Operation)
Transformer Connections
35
Transformer (Construction and Operation)
36
Transformer (Construction and Operation)
Transformer Ratings
Power kW = kVA x PF
The efficiency of the transformer is the ratio of power output to the power
input,
37
Transformer (Construction and Operation)
38
Transformer (Construction and Operation)
Fig. 1-12 -
Transformer ratings
39
Transformer (Construction and Operation)
40
Transformer (Construction and Operation)
Winding Construction
• The high voltage (HV) and low voltage (LV) windings of a
large transformer. Note that they are wound on cylinders
which are made from Bakelised or varnished paper.
• Fig. 2-4 shows the construction of the core and coils for a three
phase transformer with cylindrical windings.
Bushing
• Bushings are made of porcelain and are constructed to provide
ample current carrying capacity. The high voltage bushings are
generally of the clamp type, hollow and oil filled.
43
Transformer (Construction and Operation)
44
Transformer (Construction and Operation)
Breathers
• This device removes dirt and moisture from external air
drawn into the tank by the breathing action of the transformer.
45
Transformer (Construction and Operation)
46
Transformer (Construction and Operation)
Thermometer
• Dial type thermometer permits direct reading of the oil
temperature with a sensor positioned near the top of the oil.
47
Transformer (Construction and Operation)
Terminal Boxes
• In highly polluted or contaminated areas such as around
factories and in coastal districts, the bushings may be affected
by dirt or salt resulting in a flashover. For this reason, such
transformers are equipped with terminal boxes so constructed
that the bushing ends are not exposed.
48
Transformer (Construction and Operation)
Buchholtz Relay
• Buchholtz relays have long served as mechanical protectors
against internal troubles. This type of relay is designed to give
an alarm when the transformer develops an internal fault, and
is actuated by the gas produced in the transformer and the
rushing flow of the oil.
49
Transformer (Construction and Operation)
Buchholtz Relay
50
Transformer (Construction and Operation)
51
Transformer (Construction and Operation)
52
Transformer (Construction and Operation)
53
Transformer (Construction and Operation)
54
Transformer (Construction and Operation)
56
Transformer (Construction and Operation)
Cooling
• It should be noted that although the losses in transformers are small
compared to their input or output power, that do produce a significant
amount of heat which can damage the transformer.
• Transformers are generally cooled by air (forced or natural circulation- AF
or AN) or by oil (OFF or ON). Most indoor transformers are cooled by air.
The windings and core are cooled by natural circulation of air.
• A typical mineral oil cooled transformer is shown in Fig. 7-2-9. This type
of transformer is designed to be used outdoors. It uses a highly refined and
purified oil of low viscosity to cool the windings and core.
• Another method of cooling is to use water. A coil of pipe, usually copper,
is placed inside the tank just below the surface of the oil. The cooling water
passes through the pipe coil helping in heat removal process.
57
Transformer (Construction and Operation)
Cooling
Cooling
Mineral oil has two advantages:
• Excellent insulating properties
• Good heat transfer properties
Unfortunately, it has two disadvantages:
• Fire risk
• Pollution potential in case of leaks.
59
Transformer (Construction and Operation)
Special Transformers
Distribution Transformers
• Distribution transformers are generally considered a transformers 500 kVA
and smaller, 67 kV and below, both single phase and three phase. Although
majority of the units are designed for pole mounting, some of the larger
sizes are build for station use.
60
Transformer (Construction and Operation)
61
Transformer (Construction and Operation)
Grounding Transformer
62
Transformer (Construction and Operation)
Instrument Transformers
Current and voltage measuring
instruments are designed to operate at low
current and voltage. Also from a safety
standpoint, instruments are not connected
to high voltage. Instrument transformers
reduce high voltage and current to a safe,
usable value for operation.
63
Transformer (Construction and Operation)
64
Transformer (Construction and Operation)
Instrument Transformers
65
Transformer (Construction and Operation)
66
Transformer (Construction and Operation)
Instrument Transformers
Figure 1.4. An elevation and corresponding single-line diagram illustrates the basic components
of a distribution substation. This substation has a single source, a single transformer and four
feeders.
68
Transformer (Construction and Operation)
69
Transformer (Construction and Operation)
Insulation Deterioration
70
Transformer (Construction and Operation)
71
Transformer (Construction and Operation)
72
Transformer (Construction and Operation)
Transformer faults
I. winding and terminal faults
II. core faults
III. tank and transformer accessory faults
IV. on–load tap changer faults
V. abnormal operating conditions
VI. sustained or uncleared external faults
73
Transformer (Construction and Operation)
Transformer Protection
74