ENI - IRAQ

ZUBAIR OIL FIELD DEVELOPMENT PROJECT

Zubair - LV Switchgear 400 V '920-0-EL-105' - Data Sheets

EX-DE 01 25/10/2013 Revision after Comments L.Piersigilli S. Zannini C.Carroni S. Premchandani E. Yacoub
EX-DE 00 13/06/2013 Issue for Approval L.Piersigilli S. Zannini C.Carroni S. Premchandani E. Yacoub
Validity Rev.
Prepared Checked Approved Contractor Company
Status Number Date Description
by by by Approval Approval
Revision index
Company logo and business name Project name Company Identification

ZUBAIR OIL FIELD 00250921DEGA69038


eni iraq b.v. DEVELOPMENT
Job N.
Contractor logo and business name Contractor Identification
P12-1050
Weatherford Oil Tools Middle East
Contract N.
Vendor logo and business name Vendor Identification
130084-E-201
TECNOSISTEMI FZ LLC Order N.

Facility Name Location Scale Sheet of Sheets


Zubair IPF ONSHORE N.A 1 of 6
Document Title Supersedes N.
Superseded by N.
Zubair - LV Switchgear 400 V '920-0-EL-105' - Data Sheets Plant area Plant unit
N.A. N.A.
File No. 00250921DEGA69038_EXDE01_06

This document is property of eni iraq bv.


It shall neither be shown to Third Parties not used for purposes other than those for which it has been sent.
Company Identification Owner Identification Revision Index Sheet of Sheets
Validity Rev.
status N.
00250921DEGA69038 130084-E-201 2 of 6
EX-DE 01

REVISION HISTORY
Rev. Date Nr. of sheets Description
00 13/06/2013 06 Issued for Approval
01 25/10/2013 06 Revision after Comments

This document is property of eni iraq bv.


It shall neither be shown to Third Parties not used for purposes other than those for which it has been sent.
Revision Index
Company Document Identification Sheet of sheets
00250921DEGA69038 Validity Staus Rev. No. 3 of 6
EX-DE 01
Datasheet for LV Switchgear and Control Gear (Switchgear Description)
Tag Nos: 2509-21-920-0-EL-105 Client: Eni Iraq b.v.
Service: LV Switchgear Plant Location: Zubair Oil Field (Zubair)
Manufacturer: IMESA SPA Country of Origin: ITALY
No. of Units: 1
ENVIROMENTAL CONDITIONS (Refer Note-3)
Installation Onshore Relative humidity Max. 70,5 %
Ambient temp Max. and Min. : +55 oC (Max.) and -5 oC (Min.) Siesmicity points UBC Zone - 1
Design Ambient Temperature: +40 ºC Location: Indoor (HVAC)
SYSTEM DATA
Standard IEC 61439 Rated continuous current 400 A
Rated voltage & variation 400 V ± 5% (Note-4) Rated S.C withstand current 10 kA Symmetrical RMS
Rated frequency & variation 50 Hz ± 2% (Note-4) Rated S.C withstand time 1 Second

Number of phase / wire 3 Phase-4 Wire Dynamic S.C current 22kA Peak Asymmetrical

System earthing Solid Power frequency withstand volt. 2,5kV


Lighting impulse withstand voltage 4kV
CONSTRUCTION DATA
Type of switchgear Single front Withdrawable O/G feeder Rated current ≤ NA
Internal wiring (sq.mm) General 1,5 ,CT Circuit 2,5
Switchboard mounting Floor mounted Design life 25 Years
Type of construction Form 2b Test facilities N.A.
Enclosure type Metal-enclosed Switchboard overall dimension
Enclosure Ingress protection min IP31 Length 896 mm
Ingress protection to internal live min IP21 Height 2250 mm
parts in metering compartment Depth 518 mm
Internal arc withstand to No Switchboard overall weight 400 kg per cabinet
IEC 61641 Cable alley width NA
Duration of internal arc
N.A. Switchboard shipping dimension
withstand
Pressure relief for arc No Length 950 mm
VSD/Soft starters modules
N.A. Height 2350 mm
installation
Main protective relays N.A. Depth 600 mm
Weight 420 kgs
Switchboard to be extendable N.A. Motor Starter/Power feeder module : Full width module size
Heat Loss / Heat load 100 W Permissible floor deflection over 2mm maximum
full length
Main Busbar Details
Busbar material Copper No. of phase busbars NA nos.
Grade of busbar material hard drawn, high conductivity Each phase busbar size NA
Plating of the main busbars Not Applicable No. of neutral busbars NA nos
Plating of the busbar joints Corrosive resistant plating on Each neutral busbar size NA mm (H) x NA mm (t)
both the sides of the busbar joint Busbar Insulation Type Sleeved

Material & Type of Busbar Track resistant, corrosion resistant Busbar colour coding N.A.

Support Insulator Flame retardant Vertical dropper busbar size 25x6mmq


Earth Busbar Details
Earth busbar material Copper Earth busbar size 40x8mmq
Earth busbar insulation Not Applicable Plating of the earth busbar Tinned
Earth fault current / time N.A.
Revision Index
Company Document Identification Sheet of sheets
00250921DEGA69038 Validity Staus Rev. No. 4 of 6
EX-DE 01
Datasheet for LV Switchgear and Control Gear (Switchgear Description)
Tag Nos: 2509-21-920-0-EL-105 Client: Eni Iraq b.v.
Service: LV Switchgear Plant Location: Zubair Oil Field (Zubair)
Circuit Breaker Details
Type (MCCB model reference) ABB CIRCUIT BREAKER T5 SERIES Mass of circuit breaker 6,9 kg
Application For Incomer, bus-coupler and for Closing coil burden NA watts (Inrush)
outgoing feeder rating 400Amp Tripping coil burden NA watts (Inrush)
Type of circuit breaker MCCB Electrical life 8000 Nos. operation (440V)
No. of poles 4 Poles Mechanical life 20000 Nos. operation
Type of mounting Withdrawable Power required by spring charging N.A.
Rated normal current 400 A motor
Minimum Symmetrical break current 36 kA for T5N Spring charging time N.A.
Min. Asymmetrical break current Power Factor 2.2 Circuit breaker aux. contacts Qty as per specification
Actual short time current rating 10kA for 1 sec Rating for Normally Open (NO) 250 V AC, 10 A
of circuit breaker Rating for Normally Closed (NC) 250 VAC, 10 A
DC component of circuit breaker 0 % CB truck position aux. contacts Qty as per specification
Rated insulation voltage 1 kV rms Rating for Service Position 230 V AC, 10 A
Power frequency withstand 3,5 kV Rating for Test Position 230 V AC, 10 A
Impulse voltage 8 kV Trip status Auxilliary Contacts Qty as per specification
Peak making rating 113 kA Rating 230 V AC, 10 A / 24 V DC, 10 A
Closing/tripping current 1 A Type of Control Service Test
Closing mechanism Manual Local close Yes Yes
Circuit breaker opening time N.A. (only manual Command) Local open Yes Yes
Circuit breaker closing time N.A. (only manual Command) Remote close/open Yes No
Operating duty O-3 sec-CO-3 sec-CO
Isolating Device Details
Type (MCCB model reference) NA Contactor auxiliary contacts NA
Application NA Normally Open (NO) NA
Type of power feeder NA Normally Closed (NC) NA
Type of motor feeder NA Starter/Feeder trolley position auxiliary contacts NA
No. of poles and rating NA Service NA
Type of mounting NA Test NA
Rated normal current NA Trip status Auxilliary Contacts NA
Minimum symmetrical break current NA
Minimum Asymmetrical break NA Type of control for motor starters NA
current Local start from switchboard NA
Actual SERVICE short time NA Local stop from switchboard NA
current rating of MCCB (Ics) Remote start/stop NA
Rated insulation voltage NA Process Trip NA
Power frequency withstand NA Motor Run/Trip status NA
Impulse voltage NA Local/Remote selection NA
Type -II co-ordination NA Type of control for power feeders NA
Local start from switchboard NA
Local stop from switchboard NA
Remote start/stop NA
CT Details
Name of manufacturer REVALCO SC withstand and duration Same as of main CB
Type Cast resin bar primary CBCT operated E/F protection NA
Details/Rating TAM3D - 400/1A cl.0,5 - 3VA CBCT location
Revision Index
Company Document Identification Sheet of sheets
00250921DEGA69038 Validity Staus Rev. No. 5 of 6
EX-DE 01
Datasheet for LV Switchgear and Control Gear (Switchgear Description)
Tag Nos: 2509-21-920-0-EL-105 Client: Eni Iraq b.v.
Service: LV Switchgear Plant Location: Zubair Oil Field (Zubair)
VT Details
Name of manufacturer N.A. Current limiting primary fuse N.A.
Type of installation N.A. VT fuses/MCB's rating N.A.
Details/rating N.A. Incomer primary/secondary NA /
Busbar primary/secondary NA /
Auxiliary Supplies
CB Closing, tripping & unlatch coils N.A. Spring charging motor NA
Protection relays & indication / 230V AC (internally derived) Anti-condensation heaters N.A
alarms (Auto switched) NA
Motor/feeder contactor coils N.A

Glanding and Termination


Connection to incoming feeders Cable Gland-plate mat. for 1-Core cables Aluminum NA / 3 mm

No of cables and Size As per cable schedule Gland plate Un-drilled

Outgoing feeder cable type Cu,XLPE,PVC,SWA/(AWA),PVC Cable glands & termination kit By Contractor
Cable entry Bottom Space for termination Min. 250mm clear from gland plate
Gland-plate material & thickness Mild steel NA / 3 mm
Painting Details
Exterior Paint shade RAL 7032 Interior Paint shade As per Manufacturer standard
As per Proj spec.
Exterior thickness >50 microns Painting procedure
00250621DGSC00025
Name Plates and Labels
Rating plate material Stainless steel Other name/label plate material 3-ply Trafolite
Languages for rating plates / English lettering Black in white background
name plates Label fixing for components self adhesive
(Inside compartment & for devices)
Name plate fixing Fixed using stainless steel screws
Anti Condensation Heaters
Required in each vertical section No Thermostat required N.A
Supply voltage / rating N.A
Recommended Clearances
Minimum clearance from front 1380 mm Minimum clearance from rear N.A.
Minimum clearance from top 500 mm
PROTECTION, CONTROL, METERING & COMMUNICATION DEVICES
Protection Device Details
Protection functions Proj. spec.00250621DESH00001 Lock-out relay Part of main relay

Trip circuit supervision Part of main relay Metering Part of main relay

Metering Make and Model Number


Main incoming circuit ERI725A2T - 400/5A REVALCO Outgoing circuits ABB CL-523R - RED
Bus section ERI 72500VDT - 500V REVALCO
Earth Fault Protection Criteria
For motor starters Rated ≥ NA For distribution feeders Rated current ≥ NA
Revision Index
Company Document Identification Sheet of sheets
00250921DEGA69038 Validity Staus Rev. No. 6 of 6
EX-DE 01
Datasheet for LV Switchgear and Control Gear (Switchgear Description)
Tag Nos: 2509-21-920-0-EL-105 Client: Eni Iraq b.v.
Service: LV Switchgear Plant Location: Zubair Oil Field (Zubair)
Control Function
Remote trip control By Potential free contact from Auto-transfer/synchronizing Yes
(Refer Note-6) ESD system through IRP. Manual option to ATS Yes
Other

Indicating lamps Cluster LED (As per specification) Other control & auxiliary devices T154 TECHSYSTEM

Colour code As per Spec. 00250621DGSC00025


INSPECTION AND TESTS
Refer to the Project specification for details Reqd. Witness
Routine tests per IEC (Refer Note-5) YES YES
Type Test Certificates (Refer Note-5) N.A. N.A.
Notes:
1. For Detail Environmental Site condition Ref.0220262506ZAE09005 Rev-3- Site and Climatic Conditions)
2. Under normal conditions the variations is system voltage and frequency shall be ±5% & ±2% respectively however, under transient conditions
the variations will be ±10% & ±5% respectively. Switchgear shall be designed to cater for the variations under both, steady state and transient conditions.
3. Tests shall be carried out in accordance with IEC standards.
4. Vendor to submit complete filled data sheet for each switchgear with dedicated Tag numbers issued by CONTRACTOR.