Guaranteed Technical Particulars of Distribution Transformer

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

Energypac Engineering Ltd.

Guaranteed Technical Particulars of Distribution Transformer

A General

A01 Manufacturer’s Name Energypac Engineering Limited

A02 Country of Origin Bangladesh

A03 Power 2000 kVA

A04 Number of Phases 3 phases

A05 Frequency 50 Hz

A06 Primary Voltage 33 kV

A07 Secondary Voltage 433 V

A08 Primary Rated Current 34.99 A

A09 Secondary Rated Current 2666.70 A

A10 Primary Connection Delta

A11 Secondary Connection star+n

A12 Vector Group Dyn11

A13 Reference Standards IEC 60076

B HV Winding Copper

B1 Tap-change Operation

B1.1 Tap-changer DETC, Manual Operation

B1.2 Country of Origin Reputed Manufacturer from India/Europe/China

B1.3 Tapping Range 5 positions: + 1 x 2.5% , 0, -3 x 2.5%

B2 Bushings

B2.1 Country of Origin Reputed Manufacturer from India/Europe/China

B2.2 Insulation Class 36 kV

B2.3 Rated Current 630 A

B2.4 Creepage Length ≥ 576 mm

B2.5 BIL 170 kV

C LV Winding Copper

C1 Bushings

C1.1 Country of Origin Reputed Manufacturer from India/Europe/China

C1.2 Insulation Class 1.1 kV

C1.3 Rated Current 4000 A

C1.4 Creepage Length ≥ 17.6 mm


Energypac Engineering Ltd.

Guaranteed Technical Particulars of Distribution Transformer

D Guaranteed Losses, Impedance and Audible Sound

D1 No Load Losses at Vn 1900 W

D2 On Load Losses Ref. 75oC 20000 kW


o
D3 Total Losses Ref. 75 C 21900 W

D4 No Load Current at Vn ≤0.5 %


o
D5 Impedance Ref. 120 C 6 %

D6 Noise Level ≤99 dB

E Transformer Efficiency and Regulation

Load Power factor Efficiency Regulation

E1.1 100% 1 98.92 % 1.04 %

E1.2 75% 1 99.13 % 0.78 %

E1.3 50% 1 99.31 % 0.52 %

E1.4 25% 1 99.37 % 0.26 %

E2.1 100% 0.8 98.65 % 4.26 %

E2.2 75% 0.8 98.92 % 3.20 %

E2.3 50% 0.8 99.14 % 2.13 %

E2.4 25% 0.8 99.22 % 1.07 %

F Cooling

F1 Internal/External Cooling Medium Oil/Air (ONAN)

F2 Maximum Ambient Temperature 40 o


C
F3 Oil Temperature Rise 60 K

F4 Winding Temperature Rise 65 K

G Shipping and Packing

G1 Weights

G1.1 Weight of Active Part 2,400 kg

G1.2 Weight of Tank 955 kg

G1.3 Weight of Oil 910 kg

G1.4 Untanking Weight 2,575 kg

G1.5 Total Weight 4,485 kg

G2 Dimensions

G2.1 Length 2305± 10% mm

G2.2 Width 1455± 10% mm

G2.3 Height 2610± 10% mm


CONTRACTOR :
ENERGYPAC ENGINEERING LTD.
Energypac ENERGY CENTER
00 AS PER CUSTOMER COMMENTS. 30.05.2016 AAR MBK
25 TEJGAON I/A, DHAKA - 1208, BANGLADESH.
No REVISION MADE DATE DRN CHD PHONE: +88-02-8870669. FAX: +880-2-8879398. WWW.ENERGYPAC-BD.COM
SIGN. DATE
CUSTOMER :-
DRAWN 30.05.2016
CHECKED 30.05.2016
TITLE :- GENERAL ARRANGEMENT.
APPROVED 30.05.2016 REVISION SCALE
SHEET :- 01 OF 01 00 NTS