Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 9

B SCANNER MAGNEDYNE, INC.

Tres de Mayo, Ward IV, Minglanilla, Cebu, 6046


Telefax (032) 236 – 0753 / Tel. No. (032) 490 – 0708
SEC Reg. No. CS200529237 / PCAB Lic. No. 32522
Email address: scannermagnedyne@yahoo.com.ph

Date : April 15, 2019

To : WT Construction, Inc.
11th Floor, PAG-IBIG Fund – WT Corporate Tower
Cebu Business Park, Cebu City

Attention : Mr. Willy Te


Vice President

Subject : TEST REPORT

Test Item Distribution Transformer Serial Number M98E15193


Code T04 Configuration -
MVA Rating 0.075 MVA Impedance Voltage 2.66
Voltage Rating 14400/24940Y – 240/480 Test Site Consolacion, Cebu
Phase 1 Date of Test April 12, 2019
Maker General Electric Weather Fair

Test Equipment Model Maker S/N


Transformer Turns Ratio ATRT – 01B Teldar Instruments 16298
Winding Resistance TRM – 10 Teldar Instrumentsl 0845
Insulation Resistance Teraohm 10kV Metrel 14220150
Dielectric Breakdown Voltage DBV – 60 Teldar Instruments 7616

Prepared by: Conducted by:

_________________________ _________________________
Engr. Carl Anthony Bequilla Engr. Wilfred Medil
Technical Services Engineer Trainee Technical Services Engineer

Checked by: Noted by:

_________________________ _________________________
Engr. Arnell Mahumot Engr. Mario Gabunilas
Engineering Manager Assistant General Manager

SCANNER MAGNEDYNE INC.


SUMMARY OF TEST DATA

Transformer Test Ratio


As - Found Computed % Deviation
Tap 3 13200/240 55.006 55 0.01

Turns-ratio test results should not deviate more than 0.5% from either the adjacent coils or the calculated ratio

Remarks: Satisfactory

Winding Resistance Test


Primary Side Secondary Side
H1 – H2 9.587 Ω X1 – X3 4.076 mΩ
H2 – H1 9.576 Ω X3 – X1 4.077 mΩ

Temperature-corrected winding-resistance values should compare within one percent of previously obtained results.

Remarks: Satisfactory

Insulation Resistance Test


30 sec. 1 min. 10 min. Polarization
Position Test Voltage
reading reading reading Index
Primary-Secondary 10kV 18.6 GΩ 22.1 GΩ 35.9 GΩ 1.62
Primary-Ground 10kV 22.7 GΩ 26.5 GΩ 35.5 GΩ 1.34
Secondary-Ground 0.5kV 7.04 GΩ 7.83 GΩ 10.9 GΩ 1.39

The polarization index shall be greater than 1.0

Recommended minimum Insulation Resistance based on ANSI/NETA standards:


Transformer coil rating type in volts
0-600 volts = 100MΩ
Greater than 5000 volts = 5000MΩ

Test results are dependent on the temperature of insulating material and the humidity of the surrounding environment at the
time of the test. Insulation-resistance test data may be used to establish a trending pattern. Deviation from the baseline
information permit evaluation of the insulation.

Remarks: Satisfactory

Oil Dielectric Breakdown


Voltage Test
Trial Result (kV)
1 56.7
2 45.2
3 51.6
4 52.9
5 51.1
Average 51.5

IEEE C57. 106-1991 Suggested Limits for Continued Use of Service-Aged Insulation Oil specified that the Dielectric
Breakdown Voltage (ASTM Method D877) should not be less than 26 kV.

Remarks: Satisfactory

SCANNER MAGNEDYNE INC.


SUMMARY OF TEST RESULTS

All electrical tests conducted on the transformer have satisfactory results. Retest in one (1) year.

SCANNER MAGNEDYNE INC.


B SCANNER MAGNEDYNE, INC.
Tres de Mayo, Ward IV, Minglanilla, Cebu, 6046
Telefax (032) 236 – 0753 / Tel. No. (032) 490 – 0708
SEC Reg. No. CS200529237 / PCAB Lic. No. 32522
Email address: scannermagnedyne@yahoo.com.ph

Date : April 15, 2019

To : WT Construction, Inc.
11th Floor, PAG-IBIG Fund – WT Corporate Tower
Cebu Business Park, Cebu City

Attention : Mr. Willy Te


Vice President

Subject : TEST REPORT

Test Item Distribution Transformer Serial Number


Code T05 Configuration -
MVA Rating 0.075 MVA Impedance Voltage -
Voltage Rating 14400/24940Y – 240/480 Test Site Consolacion, Cebu
Phase 1 Date of Test April 12, 2019
Maker General Electric Weather Fair

Test Equipment Model Maker S/N


Transformer Turns Ratio ATRT – 01B Teldar Instruments 16298
Winding Resistance TRM – 10 Teldar Instrumentsl 0845
Insulation Resistance Teraohm 10kV Metrel 14220150
Dielectric Breakdown Voltage DBV – 60 Teldar Instruments 7616

Prepared by: Conducted by:

_________________________ _________________________
Engr. Carl Anthony Bequilla Engr. Wilfred Medil
Technical Services Engineer Trainee Technical Services Engineer

Checked by: Noted by:

_________________________ _________________________
Engr. Arnell Mahumot Engr. Mario Gabunilas
Engineering Manager Assistant General Manager

SUMMARY OF TEST DATA

SCANNER MAGNEDYNE INC.


Transformer Test Ratio
As - Found Computed % Deviation
Tap 3 13200/240 55.011 55 0.02

Turns-ratio test results should not deviate more than 0.5% from either the adjacent coils or the calculated ratio

Remarks: Satisfactory

Winding Resistance Test


Primary Side Secondary Side
H1 – H2 9.560 Ω X1 – X3 4.033 mΩ
H2 – H1 9.617 Ω X3 – X1 4.038 mΩ

Temperature-corrected winding-resistance values should compare within one percent of previously obtained results.

Remarks: Satisfactory

Insulation Resistance Test


30 sec. 1 min. 10 min. Polarization
Position Test Voltage
reading reading reading Index
Primary-Secondary 10kV 781 MΩ 951 MΩ 1.53 GΩ 1.61
Primary-Ground 10kV 1.50 GΩ 1.70 GΩ 2.18 GΩ 1.28
Secondary-Ground 0.5kV 1.20 GΩ 1.26 GΩ 2.02 GΩ 1.60

The polarization index shall be greater than 1.0

Recommended minimum Insulation Resistance based on ANSI/NETA standards:


Transformer coil rating type in volts
0-600 volts = 100MΩ
Greater than 5000 volts = 5000MΩ

Test results are dependent on the temperature of insulating material and the humidity of the surrounding environment at the
time of the test. Insulation-resistance test data may be used to establish a trending pattern. Deviation from the baseline
information permit evaluation of the insulation.

Remarks: Satisfactory

Oil Dielectric Breakdown


Voltage Test
Trial Result (kV)
1 42.0
2 35.7
3 29.3
4 35.8
5 41.2
Average 36.8

IEEE C57. 106-1991 Suggested Limits for Continued Use of Service-Aged Insulation Oil specified that the Dielectric
Breakdown Voltage (ASTM Method D877) should not be less than 26 kV.

Remarks: Satisfactory

SCANNER MAGNEDYNE INC.


SUMMARY OF TEST RESULTS

All electrical tests conducted on the transformer have satisfactory results. Retest in one (1) year.

SCANNER MAGNEDYNE INC.


B SCANNER MAGNEDYNE, INC.
Tres de Mayo, Ward IV, Minglanilla, Cebu, 6046
Telefax (032) 236 – 0753 / Tel. No. (032) 490 – 0708
SEC Reg. No. CS200529237 / PCAB Lic. No. 32522
Email address: scannermagnedyne@yahoo.com.ph

Date : April 15, 2019

To : WT Construction, Inc.
11th Floor, PAG-IBIG Fund – WT Corporate Tower
Cebu Business Park, Cebu City

Attention : Mr. Willy Te


Vice President

Subject : TEST REPORT

Test Item Distribution Transformer Serial Number M98E15195


Code T06 Configuration -
MVA Rating 0.075 MVA Impedance Voltage 2.66
Voltage Rating 14400/24940Y – 240/480 Test Site Consolacion, Cebu
Phase 1 Date of Test April 12, 2019
Maker General Electric Weather Fair

Test Equipment Model Maker S/N


Transformer Turns Ratio ATRT – 01B Teldar Instruments 16298
Winding Resistance TRM – 10 Teldar Instrumentsl 0845
Insulation Resistance Teraohm 10kV Metrel 14220150
Dielectric Breakdown Voltage DBV – 60 Teldar Instruments 7616

Prepared by: Conducted by:

_________________________ _________________________
Engr. Carl Anthony Bequilla Engr. Wilfred Medil
Technical Services Engineer Trainee Technical Services Engineer

Checked by: Noted by:

_________________________ _________________________
Engr. Arnell Mahumot Engr. Mario Gabunilas
Engineering Manager Assistant General Manager

SCANNER MAGNEDYNE INC.


SUMMARY OF TEST DATA

Transformer Test Ratio


As - Found Computed % Deviation
Tap 3 13200/240 55.003 55 0.01

Turns-ratio test results should not deviate more than 0.5% from either the adjacent coils or the calculated ratio

Remarks: Satisfactory

Winding Resistance Test


Primary Side Secondary Side
H1 – H2 9.757 Ω X1 – X3 4.030 mΩ
H2 – H1 9.693 Ω X3 – X1 4.027 mΩ

Temperature-corrected winding-resistance values should compare within one percent of previously obtained results.

Remarks: Satisfactory

Insulation Resistance Test


30 sec. 1 min. 10 min. Polarization
Position Test Voltage
reading reading reading Index
Primary-Secondary 10kV 364 MΩ 397 MΩ 439 MΩ 1.11
Primary-Ground 10kV 500 MΩ 525 MΩ 540 MΩ 1.03
Secondary-Ground 0.5kV 192 MΩ 193 MΩ 188 MΩ 0.97

The polarization index shall be greater than 1.0

Recommended minimum Insulation Resistance based on ANSI/NETA standards:


Transformer coil rating type in volts
0-600 volts = 100MΩ
Greater than 5000 volts = 5000MΩ

Test results are dependent on the temperature of insulating material and the humidity of the surrounding environment at the
time of the test. Insulation-resistance test data may be used to establish a trending pattern. Deviation from the baseline
information permit evaluation of the insulation.

Remarks: Investigative

Oil Dielectric Breakdown


Voltage Test
Trial Result (kV)
1 25.2
2 20.4
3 23.3
4 20.5
5 22.6
Average 22.4

IEEE C57. 106-1991 Suggested Limits for Continued Use of Service-Aged Insulation Oil specified that the Dielectric
Breakdown Voltage (ASTM Method D877) should not be less than 26 kV.

Remarks: Investigative

SCANNER MAGNEDYNE INC.


SUMMARY OF TEST RESULTS

Insulation Resistance test result shows that the unit is investigative due its polarization index (PI) at the secondary
winding, with a value of 0.97, being less than 1.0 which is the standard set as per ANSI/NETA ATS 2017.
Oil Dielectric Breakdown Voltage test have investigative results as the average result with a value of 22.4 kV is
below the minimum standard as per IEEE C57.106-1991 Suggested Limits for Continued Use of Service-Aged
Insulation Oil which is 26 kV.
All other electrical tests have satisfactory results.
Due to the investigative test results, the unit is therefore recommended for reconditioning and oil replacement.

SCANNER MAGNEDYNE INC.

You might also like