Download as pdf or txt
Download as pdf or txt
You are on page 1of 172

SERIES FLOW FAN TERMINAL

VAV COOLING W/ ELECTRIC HEAT


APPLICATION DATA New Release 1000 Form: AD1T-SECT J

MODELS HLFSE, HVFSE, HFMLE & HFSLE

These matrixes and the accompanying control


diagrams are to be used in conjunction with the
general information found in Form AD1T-GEN

SELECTION MATRIX
MODELS HLFSE, HVFSE, HFMLE & HFSLE .............. J.M1 - H.M8

CONTROL DIAGRAMS
MODELS HLFSE, HVFSE, HFMLE & HFSLE .................. J1 - J160
Te m p m as t e r
R

SERIES FLOW FAN TERMINAL


MODEL: HLFSE, HVFSE, HFMLE & HFSLE
VAV COOLING W/ ELECTRIC HEAT

CONTROL TYPE

HEAT CONTROL
OF OPERATION

FAILURE MODE
STAT ACTION

PNEUMATIC
SEQUENCE

ELECTRIC

OPTIONS
1Ø LOAD BEARING P.E. W/ INTRLK

3Ø LOAD BEARING P.E. W/ INTRLK


PRESSURE INDEPENDENT W/ RVRC

PNEUMATIC SIGNAL-FAN START

POSITIVE DAMPER CLOSE OFF

1Ø LOAD BEARING P.E.

1Ø PILOT DUTY P.E.

3Ø PILOT DUTY P.E.


PRESSURE INDEPENDENT

SUPPLY AIR-FAN START

DAMPER FAIL - CLOSE

DAMPER FAIL - OPEN


UNOCCUPIED MODE

REVERSE ACTING

HEAT FAIL - OFF


DIRECT ACTING

HEAT FAIL - ON
FAN FAIL - OFF
FAN FAIL - ON
J-K-L-M

J-K-L-M
2-3-4-5

2-3-4-5
1

PAGE CONTROL CONTROL PAGE


NO. CODE CODE NO.

J1 5E0W0** 5E0W0** J1

J2 5F0W0** 5F0W0** J2

J3 5G0W0** 5G0W0** J3

J4 5H0W0** 5H0W0** J4

J5 5E0W0** 5E0W0** J5

J6 5F0W0** 5F0W0** J6

J7 5G0W0** 5G0W0** J7

J8 5H0W0** 5H0W0** J8

J9 5E0W0** 5E0W0** J9

J10 5F0W0** 5F0W0** J10

J11 5G0W0** 5G0W0** J11

J12 5H0W0** 5H0W0** J12

J13 5E0W0** 5E0W0** J13

J14 5F0W0** 5F0W0** J14

J15 5G0W0** 5G0W0** J15

J16 5H0W0** 5H0W0** J16

J17 5E0W0** 5E0W0** J17

J18 5F0W0** 5F0W0** J18

J19 5G0W0** 5G0W0** J19

J20 5H0W0** 5H0W0** J20

**SEE CONTROL DIAGRAM FOR SELECTION CHOICE.


MTX021

- J.M1 -

2 YORK INTERNATIONAL
FORM AD1T-SECT J

Te m p m as t e r
R

SERIES FLOW FAN TERMINAL


MODEL: HLFSE, HVFSE, HFMLE & HFSLE
VAV COOLING W/ ELECTRIC HEAT

CONTROL TYPE

HEAT CONTROL
OF OPERATION

FAILURE MODE
STAT ACTION

PNEUMATIC
SEQUENCE

ELECTRIC

OPTIONS
1Ø LOAD BEARING P.E. W/ INTRLK

3Ø LOAD BEARING P.E. W/ INTRLK


PRESSURE INDEPENDENT W/ RVRC

PNEUMATIC SIGNAL-FAN START

POSITIVE DAMPER CLOSE OFF

1Ø LOAD BEARING P.E.

1Ø PILOT DUTY P.E.

3Ø PILOT DUTY P.E.


PRESSURE INDEPENDENT

SUPPLY AIR-FAN START

DAMPER FAIL - CLOSE

DAMPER FAIL - OPEN


UNOCCUPIED MODE

REVERSE ACTING

HEAT FAIL - OFF


DIRECT ACTING

HEAT FAIL - ON
FAN FAIL - OFF
FAN FAIL - ON
J-K-L-M

J-K-L-M
2-3-4-5

2-3-4-5
1

PAGE CONTROL CONTROL PAGE


NO. CODE CODE NO.

J21 5E030** 5E030** J21

J22 5F030** 5F030** J22

J23 5G030** 5G030** J23

J24 5H030** 5H030** J24

J25 5E030** 5E030** J25

J26 5F030** 5F030** J26

J27 5G030** 5G030** J27

J28 5H030** 5H030** J28

J29 5E030** 5E030** J29

J30 5F030** 5F030** J30

J31 5G030** 5G030** J31

J32 5H030** 5H030** J32

J33 5E030** 5E030** J33

J34 5F030** 5F030** J34

J35 5G030** 5G030** J35

J36 5H030** 5H030** J36

J37 5E030** 5E030** J37

J38 5F030** 5F030** J38

J39 5G030** 5G030** J39

J40 5H030** 5H030** J40

**SEE CONTROL DIAGRAM FOR SELECTION CHOICE.


MTX022

- J.M2 -

YORK INTERNATIONAL 3
Te m p m as t e r
R

SERIES FLOW FAN TERMINAL


MODEL: HLFSE, HVFSE, HFMLE & HFSLE
VAV COOLING W/ ELECTRIC HEAT

CONTROL TYPE

HEAT CONTROL
OF OPERATION

FAILURE MODE
STAT ACTION

PNEUMATIC
SEQUENCE

ELECTRIC

OPTIONS
1Ø LOAD BEARING P.E. W/ INTRLK

3Ø LOAD BEARING P.E. W/ INTRLK


PRESSURE INDEPENDENT W/ RVRC

PNEUMATIC SIGNAL-FAN START

POSITIVE DAMPER CLOSE OFF

1Ø LOAD BEARING P.E.

1Ø PILOT DUTY P.E.

3Ø PILOT DUTY P.E.


PRESSURE INDEPENDENT

SUPPLY AIR-FAN START

DAMPER FAIL - CLOSE

DAMPER FAIL - OPEN


UNOCCUPIED MODE

REVERSE ACTING

HEAT FAIL - OFF


DIRECT ACTING

HEAT FAIL - ON
FAN FAIL - OFF
FAN FAIL - ON
J-K-L-M

J-K-L-M
2-3-4-5

2-3-4-5
1

PAGE CONTROL CONTROL PAGE


NO. CODE CODE NO.

J41 5E0X0** 5E0X0** J41

J42 5F0X0** 5F0X0** J42

J43 5G0X0** 5G0X0** J43

J44 5H0X0** 5H0X0** J44

J45 5E0X0** 5E0X0** J45

J46 5F0X0** 5F0X0** J46

J47 5G0X0** 5G0X0** J47

J48 5H0X0** 5H0X0** J48

J49 5E0X0** 5E0X0** J49

J50 5F0X0** 5F0X0** J50

J51 5G0X0** 5G0X0** J51

J52 5H0X0** 5H0X0** J52

J53 5E0X0** 5E0X0** J53

J54 5F0X0** 5F0X0** J54

J55 5G0X0** 5G0X0** J55

J56 5H0X0** 5H0X0** J56

J57 5E0X0** 5E0X0** J57

J58 5F0X0** 5F0X0** J58

J59 5G0X0** 5G0X0** J59

J60 5H0X0** 5H0X0** J60

**SEE CONTROL DIAGRAM FOR SELECTION CHOICE.


MTX023

- J.M3 -

4 YORK INTERNATIONAL
FORM AD1T-SECT J

Te m p m as t e r
R

SERIES FLOW FAN TERMINAL


MODEL: HLFSE, HVFSE, HFMLE & HFSLE
VAV COOLING W/ ELECTRIC HEAT

CONTROL TYPE

HEAT CONTROL
OF OPERATION

FAILURE MODE
STAT ACTION

PNEUMATIC
SEQUENCE

ELECTRIC

OPTIONS
1Ø LOAD BEARING P.E. W/ INTRLK

3Ø LOAD BEARING P.E. W/ INTRLK


PRESSURE INDEPENDENT W/ RVRC

PNEUMATIC SIGNAL-FAN START

POSITIVE DAMPER CLOSE OFF

1Ø LOAD BEARING P.E.

1Ø PILOT DUTY P.E.

3Ø PILOT DUTY P.E.


PRESSURE INDEPENDENT

SUPPLY AIR-FAN START

DAMPER FAIL - CLOSE

DAMPER FAIL - OPEN


UNOCCUPIED MODE

REVERSE ACTING

HEAT FAIL - OFF


DIRECT ACTING

HEAT FAIL - ON
FAN FAIL - OFF
FAN FAIL - ON
J-K-L-M

J-K-L-M
2-3-4-5

2-3-4-5
1

PAGE CONTROL CONTROL PAGE


NO. CODE CODE NO.

J61 5E070** 5E070** J61

J62 5F070** 5F070** J62

J63 5G070** 5G070** J63

J64 5H070** 5H070** J64

J65 5E070** 5E070** J65

J66 5F070** 5F070** J66

J67 5G070** 5G070** J67

J68 5H070** 5H070** J68

J69 5E070** 5E070** J69

J70 5F070** 5F070** J70

J71 5G070** 5G070** J71

J72 5H070** 5H070** J72

J73 5E070** 5E070** J73

J74 5F070** 5F070** J74

J75 5G070** 5G070** J75

J76 5H070** 5H070** J76

J77 5E070** 5E070** J77

J78 5F070** 5F070** J78

J79 5G070** 5G070** J79

J80 5H070** 5H070** J80

**SEE CONTROL DIAGRAM FOR SELECTION CHOICE.


MTX024

- J.M4 -

YORK INTERNATIONAL 5
Te m p m as t e r
R

SERIES FLOW FAN TERMINAL


MODEL: HLFSE, HVFSE, HFMLE & HFSLE
VAV COOLING W/ ELECTRIC HEAT

CONTROL TYPE

HEAT CONTROL
OF OPERATION

FAILURE MODE
STAT ACTION

PNEUMATIC
SEQUENCE

ELECTRIC

OPTIONS
1Ø LOAD BEARING P.E. W/ INTRLK

3Ø LOAD BEARING P.E. W/ INTRLK


PRESSURE INDEPENDENT W/ RVRC

PNEUMATIC SIGNAL-FAN START

POSITIVE DAMPER CLOSE OFF

1Ø LOAD BEARING P.E.

1Ø PILOT DUTY P.E.

3Ø PILOT DUTY P.E.


PRESSURE INDEPENDENT

SUPPLY AIR-FAN START

DAMPER FAIL - CLOSE

DAMPER FAIL - OPEN


UNOCCUPIED MODE

REVERSE ACTING

HEAT FAIL - OFF


DIRECT ACTING

HEAT FAIL - ON
FAN FAIL - OFF
FAN FAIL - ON
J-K-L-M

J-K-L-M
2-3-4-5

2-3-4-5
1

PAGE CONTROL CONTROL PAGE


NO. CODE CODE NO.

J81 5E020** 5E020** J81

J82 5F020** 5F020** J82

J83 5G020** 5G020** J83

J84 5H020** 5H020** J84

J85 5E020** 5E020** J85

J86 5F020** 5F020** J86

J87 5G020** 5G020** J87

J88 5H020** 5H020** J88

J89 5E020** 5E020** J89

J90 5F020** 5F020** J90

J91 5G020** 5G020** J91

J92 5H020** 5H020** J92

J93 5E020** 5E020** J93

J94 5F020** 5F020** J94

J95 5G020** 5G020** J95

J96 5H020** 5H020** J96

J97 5E020** 5E020** J97

J98 5F020** 5F020** J98

J99 5G020** 5G020** J99

J100 5H020** 5H020** J100

**SEE CONTROL DIAGRAM FOR SELECTION CHOICE.


MTX025

- J.M5 -

6 YORK INTERNATIONAL
FORM AD1T-SECT J

Te m p m as t e r
R

SERIES FLOW FAN TERMINAL


MODEL: HLFSE, HVFSE, HFMLE & HFSLE
VAV COOLING W/ ELECTRIC HEAT

CONTROL TYPE

HEAT CONTROL
OF OPERATION

FAILURE MODE
STAT ACTION

PNEUMATIC
SEQUENCE

ELECTRIC

OPTIONS
1Ø LOAD BEARING P.E. W/ INTRLK

3Ø LOAD BEARING P.E. W/ INTRLK


PRESSURE INDEPENDENT W/ RVRC

PNEUMATIC SIGNAL-FAN START

POSITIVE DAMPER CLOSE OFF

1Ø LOAD BEARING P.E.

1Ø PILOT DUTY P.E.

3Ø PILOT DUTY P.E.


PRESSURE INDEPENDENT

SUPPLY AIR-FAN START

DAMPER FAIL - CLOSE

DAMPER FAIL - OPEN


UNOCCUPIED MODE

REVERSE ACTING

HEAT FAIL - OFF


DIRECT ACTING

HEAT FAIL - ON
FAN FAIL - OFF
FAN FAIL - ON
J-K-L-M

J-K-L-M
2-3-4-5

2-3-4-5
1

PAGE CONTROL CONTROL PAGE


NO. CODE CODE NO.

J101 5E040** 5E040** J101

J102 5F040** 5F040** J102

J103 5G040** 5G040** J103

J104 5H040** 5H040** J104

J105 5E040** 5E040** J105

J106 5F040** 5F040** J106

J107 5G040** 5G040** J107

J108 5H040** 5H040** J108

J109 5E040** 5E040** J109

J110 5F040** 5F040** J110

J111 5G040** 5G040** J111

J112 5H040** 5H040** J112

J113 5E040** 5E040** J113

J114 5F040** 5F040** J114

J115 5G040** 5G040** J115

J116 5H040** 5H040** J116

J117 5E040** 5E040** J117

J118 5F040** 5F040** J118

J119 5G040** 5G040** J119

J120 5H040** 5H040** J120

**SEE CONTROL DIAGRAM FOR SELECTION CHOICE.


MTX026

- J.M6 -

YORK INTERNATIONAL 7
Te m p m as t e r
R

SERIES FLOW FAN TERMINAL


MODEL: HLFSE, HVFSE, HFMLE & HFSLE
VAV COOLING W/ ELECTRIC HEAT

CONTROL TYPE

HEAT CONTROL
OF OPERATION

FAILURE MODE
STAT ACTION

PNEUMATIC
SEQUENCE

ELECTRIC

OPTIONS
1Ø LOAD BEARING P.E. W/ INTRLK

3Ø LOAD BEARING P.E. W/ INTRLK


PRESSURE INDEPENDENT W/ RVRC

PNEUMATIC SIGNAL-FAN START

POSITIVE DAMPER CLOSE OFF

1Ø LOAD BEARING P.E.

1Ø PILOT DUTY P.E.

3Ø PILOT DUTY P.E.


PRESSURE INDEPENDENT

SUPPLY AIR-FAN START

DAMPER FAIL - CLOSE

DAMPER FAIL - OPEN


UNOCCUPIED MODE

REVERSE ACTING

HEAT FAIL - OFF


DIRECT ACTING

HEAT FAIL - ON
FAN FAIL - OFF
FAN FAIL - ON
J-K-L-M

J-K-L-M
2-3-4-5

2-3-4-5
1

PAGE CONTROL CONTROL PAGE


NO. CODE CODE NO.

J121 5E060** 5E060** J121

J122 5F060** 5F060** J122

J123 5G060** 5G060** J123

J124 5H060** 5H060** J124

J125 5E060** 5E060** J125

J126 5F060** 5F060** J126

J127 5G060** 5G060** J127

J128 5H060** 5H060** J128

J129 5E060** 5E060** J129

J130 5F060** 5F060** J130

J131 5G060** 5G060** J131

J132 5H060** 5H060** J132

J133 5E060** 5E060** J133

J134 5F060** 5F060** J134

J135 5G060** 5G060** J135

J136 5H060** 5H060** J136

J137 5E060** 5E060** J137

J138 5F060** 5F060** J138

J139 5G060** 5G060** J139

J140 5H060** 5H060** J140

**SEE CONTROL DIAGRAM FOR SELECTION CHOICE.


MTX027

- J.M7 -

8 YORK INTERNATIONAL
FORM AD1T-SECT J

Te m p m as t e r
R

SERIES FLOW FAN TERMINAL


MODEL: HLFSE, HVFSE, HFMLE & HFSLE
VAV COOLING W/ ELECTRIC HEAT

CONTROL TYPE

HEAT CONTROL
OF OPERATION

FAILURE MODE
STAT ACTION

PNEUMATIC
SEQUENCE

ELECTRIC

OPTIONS
1Ø LOAD BEARING P.E. W/ INTRLK

3Ø LOAD BEARING P.E. W/ INTRLK


PRESSURE INDEPENDENT W/ RVRC

PNEUMATIC SIGNAL-FAN START

POSITIVE DAMPER CLOSE OFF

1Ø LOAD BEARING P.E.

1Ø PILOT DUTY P.E.

3Ø PILOT DUTY P.E.


PRESSURE INDEPENDENT

SUPPLY AIR-FAN START

DAMPER FAIL - CLOSE

DAMPER FAIL - OPEN


UNOCCUPIED MODE

REVERSE ACTING

HEAT FAIL - OFF


DIRECT ACTING

HEAT FAIL - ON
FAN FAIL - OFF
FAN FAIL - ON
J-K-L-M

J-K-L-M
2-3-4-5

2-3-4-5
1

PAGE CONTROL CONTROL PAGE


NO. CODE CODE NO.

J141 5E080** 5E080** J141

J142 5F080** 5F080** J142

J143 5G080** 5G080** J143

J144 5H080** 5H080** J144

J145 5E080** 5E080** J145

J146 5F080** 5F080** J146

J147 5G080** 5G080** J147

J148 5H080** 5H080** J148

J149 5E080** 5E080** J149

J150 5F080** 5F080** J150

J151 5G080** 5G080** J151

J152 5H080** 5H080** J152

J153 5E080** 5E080** J153

J154 5F080** 5F080** J154

J155 5G080** 5G080** J155

J156 5H080** 5H080** J156

J157 5E080** 5E080** J157

J158 5F080** 5F080** J158

J159 5G080** 5G080** J159

J160 5H080** 5H080** J160

**SEE CONTROL DIAGRAM FOR SELECTION CHOICE.


MTX028

- J.M8 -

YORK INTERNATIONAL 9
SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT
PRESS. INDEPENDENT, N.O. DAMPER, A.F.S. FAN START, DIRECT ACTING STAT, 1 PHASE, LOAD BEARING P.E. SWITCH

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V
DISCONNECT OCCUPIED MODE:
SWITCH WHEN THE DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
SENSED BY THE S1 AIR FLOW SWITCH, THE FAN MOTOR
IS ENERGIZED.
FUSING SPACE TEMP WARM (STAT OUTPUT HI). AT A STAT
OUTPUT OF 13 PSI THE VEL. CNTRLR WILL BE CONTROLLING
OPTIONAL DISCONNECT SWITCH AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
AND OR FUSING WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
PANEL WIRING DIAGRAM STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
ON A FURTHER DROP IN SPACE TEMP., PE1 WILL CLOSE
L1 (N) = 120V & 277V ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
TERMINAL 1 2
BLOCK AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
BK WH

C UNOCCUPIED MODE:
NO
WHEN DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
BK C NO BK WH G NO LONGER SENSED BY THE S1 AIR FLOW SWITCH, THE FAN
S1 5 MOTOR IS DEENERGIZED.
NC STANDARD 1
PE-1
NC STAGE HEAT ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
RD C NO RD JOB SPECIFICATIONS.

PE-2 OPTIONAL 2 NOTE: S1 AIRFLOW SWITCH FACTORY SET TO START FAN AT


NC STAGE HEAT .10"WC TOTAL PRESSURE SENSED AT INLET FLOW PROBE.
BN C NO BN

PE-3 OPTIONAL 3
NC STAGE HEAT

BK BL/WH BK
SC FM

PNEUMATIC DIAGRAM
N.O. RECOMMENDED FIELD P.E. SWITCH SETTINGS:

ACT. PE-1 = 8 PSI


PE-2 = 6 PSI
VEL. CNTRLR PE-3 = 4 PSI
BAL. TAPS (RESET BAND=8-13 PSI)
B
FLOW LO Y
M 20 PSI MAIN CONSTANT
PROBE HI X
T VOLUME
TOTAL AIR
D.A.. STAT HEAT
FLOW

1 PIPE COLD AIR


S1 AIR
AIR

FLOW PLENUM AIR


RESTRICTOR
OR OR 20 PSI MAIN

D.A.. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
2 PIPE COLD HOT
PE3 PE2 PE1 T-STAT BRANCH PRESSURE (PSIG)
ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE 1 = LOAD BEARING P.E.
SWITCH

1 1.6 3.9 E = 120V/1PH/60HZ - 2 STAGE


LOAD BEARING
P.E.

PER STAGE 2 0.8 1.9 5 = 120V/1PH/60HZ - 3 STAGE


3 0.5 1.3
K = 277V/1PH/60HZ - 1 STAGE
DISCONNECT

L = 277V/1PH/60HZ - 2 STAGE
SIZE & TYPE

DNF-40 1.6 3.9 Y = 277V/1PH/60HZ - 3 STAGE


DOOR INTERLOCK
BLOCK
FUSE

30 AMP BLOCK 1.6 3.9

1. MAX. K.W. BASED ON A.F.S. MAX LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.008 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5E0W0

REV.1 5/6/00 PNEUMATIC


PSFH001
- J1 -

10 YORK INTERNATIONAL
FORM AD1T-SECT J

SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT


PRESS. INDEPENDENT, N.C. DAMPER, A.F.S. FAN START, REVERSE ACTING STAT, 1 PHASE, LOAD BEARING P.E. SWITCH

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V
DISCONNECT OCCUPIED MODE:
SWITCH WHEN THE DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
SENSED BY THE S1 AIR FLOW SWITCH, THE FAN MOTOR
IS ENERGIZED.
FUSING SPACE TEMP WARM (STAT OUTPUT LOW). AT A STAT
OUTPUT OF 3 PSI THE VEL. CNTRLR WILL BE CONTROLLING
OPTIONAL DISCONNECT SWITCH AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
AND OR FUSING WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
PANEL WIRING DIAGRAM STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
ON A FURTHER DROP IN SPACE TEMP., PE1 WILL CLOSE
L1 (N) = 120V & 277V ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
TERMINAL 1 2
BLOCK AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
BK WH

C UNOCCUPIED MODE:
NO
WHEN DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
BK C NO BK WH G NO LONGER SENSED BY THE S1 AIR FLOW SWITCH, THE FAN
S1 5 MOTOR IS DEENERGIZED.
NC STANDARD 1
PE-1
NC STAGE HEAT ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
RD C NO RD JOB SPECIFICATIONS.

PE-2 OPTIONAL 2 NOTE: S1 AIRFLOW SWITCH FACTORY SET TO START FAN AT


NC STAGE HEAT .10"WC TOTAL PRESSURE SENSED AT INLET FLOW PROBE.
BN C NO BN

PE-3 OPTIONAL 3
NC STAGE HEAT

BK BL/WH BK
SC FM

PNEUMATIC DIAGRAM
N.C. RECOMMENDED FIELD P.E. SWITCH SETTINGS:
ACT.
PE-1 = 8 PSI
PE-2 = 10 PSI
VEL. CNTRLR PE-3 = 12 PSI
BAL. TAPS (RESET BAND=3-8 PSI)
B
FLOW LO X CONSTANT
M 20 PSI MAIN
PROBE HI Y VOLUME
T TOTAL AIR
R.A.. STAT COLD AIR HEAT
FLOW

AIR
S1 1 PIPE
AIR

FLOW PLENUM AIR


RESTRICTOR
OR OR 20 PSI MAIN

R.A.. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE2 2 PIPE HOT T-STAT BRANCH PRESSURE (PSIG) COLD
PE3 PE1
ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE 1 = LOAD BEARING P.E.
SWITCH

1 1.6 3.9 E = 120V/1PH/60HZ - 2 STAGE


LOAD BEARING
P.E.

PER STAGE 2 0.8 1.9 5 = 120V/1PH/60HZ - 3 STAGE


3 0.5 1.3
K = 277V/1PH/60HZ - 1 STAGE
DISCONNECT

L = 277V/1PH/60HZ - 2 STAGE
SIZE & TYPE

DNF-40 1.6 3.9 Y = 277V/1PH/60HZ - 3 STAGE


DOOR INTERLOCK
BLOCK
FUSE

30 AMP BLOCK 1.6 3.9

1. MAX. K.W. BASED ON A.F.S. MAX LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.008 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5F0W0

REV.1 5/6/00 PNEUMATIC


PSFH002
- J2 -

YORK INTERNATIONAL 11
SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT
PRESS. INDEPENDENT, N.O. DAMPER, A.F.S. FAN START, REVERSE ACTING STAT, 1 PHASE, LOAD BEARING P.E. SWITCH

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V
DISCONNECT OCCUPIED MODE:
SWITCH WHEN THE DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
SENSED BY THE S1 AIR FLOW SWITCH, THE FAN MOTOR
IS ENERGIZED.
FUSING SPACE TEMP WARM (STAT OUTPUT LOW). AT A STAT
OUTPUT OF 3 PSI THE VEL. CNTRLR WILL BE CONTROLLING
OPTIONAL DISCONNECT SWITCH AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
AND OR FUSING WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
PANEL WIRING DIAGRAM STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
ON A FURTHER DROP IN SPACE TEMP., PE1 WILL CLOSE
L1 (N) = 120V & 277V ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
TERMINAL 1 2
BLOCK AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
BK WH

C UNOCCUPIED MODE:
NO
WHEN DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
BK C NO BK WH G NO LONGER SENSED BY THE S1 AIR FLOW SWITCH, THE FAN
S1 5 MOTOR IS DEENERGIZED.
NC STANDARD 1
PE-1
NC STAGE HEAT ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
RD C NO RD JOB SPECIFICATIONS.

PE-2 OPTIONAL 2 NOTE: S1 AIRFLOW SWITCH FACTORY SET TO START FAN AT


NC STAGE HEAT .10"WC TOTAL PRESSURE SENSED AT INLET FLOW PROBE.
BN C NO BN

PE-3 OPTIONAL 3
NC STAGE HEAT

BK BL/WH BK
SC FM

PNEUMATIC DIAGRAM
N.O.
ACT. RECOMMENDED FIELD P.E. SWITCH SETTINGS:

PE-1 = 8 PSI
VEL. CNTRLR
PE-2 = 10 PSI
BAL. TAPS (RESET BAND=8-13 PSI)
PE-3 = 12 PSI
B
FLOW LO Y
M 20 PSI MAIN CONSTANT
PROBE HI X
T VOLUME
TOTAL AIR
REV. R.A.. STAT
FLOW

COLD AIR HEAT


S1 RELAY 1 PIPE AIR
AIR

M FLOW PLENUM AIR


1 RESTRICTOR
3 OR OR 20 PSI MAIN

R.A.. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
2 PIPE HOT COLD
PE3 PE2 PE1 T-STAT BRANCH PRESSURE (PSIG)
ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE 1 = LOAD BEARING P.E.
SWITCH

1 1.6 3.9 E = 120V/1PH/60HZ - 2 STAGE


LOAD BEARING
P.E.

PER STAGE 2 0.8 1.9 5 = 120V/1PH/60HZ - 3 STAGE


3 0.5 1.3
K = 277V/1PH/60HZ - 1 STAGE
DISCONNECT

L = 277V/1PH/60HZ - 2 STAGE
SIZE & TYPE

DNF-40 1.6 3.9 Y = 277V/1PH/60HZ - 3 STAGE


DOOR INTERLOCK
BLOCK
FUSE

30 AMP BLOCK 1.6 3.9

1. MAX. K.W. BASED ON A.F.S. MAX LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.016 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5G0W0

REV.1 5/6/00 PNEUMATIC


PSFH003
- J3 -

12 YORK INTERNATIONAL
FORM AD1T-SECT J

SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT


PRESS. INDEPENDENT, N.C. DAMPER, A.F.S. FAN START, DIRECT ACTING STAT, 1 PHASE, LOAD BEARING P.E. SWITCH

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V
DISCONNECT OCCUPIED MODE:
SWITCH WHEN THE DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
SENSED BY THE S1 AIR FLOW SWITCH, THE FAN MOTOR
IS ENERGIZED.
FUSING SPACE TEMP WARM (STAT OUTPUT HI). AT A STAT
OUTPUT OF 13 PSI THE VEL. CNTRLR WILL BE CONTROLLING
OPTIONAL DISCONNECT SWITCH AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
AND OR FUSING WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
PANEL WIRING DIAGRAM STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
ON A FURTHER DROP IN SPACE TEMP., PE1 WILL CLOSE
L1 (N) = 120V & 277V ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
TERMINAL 1 2
BLOCK AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
BK WH

C UNOCCUPIED MODE:
NO
WHEN DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
BK C NO BK WH G NO LONGER SENSED BY THE S1 AIR FLOW SWITCH, THE FAN
S1 5 MOTOR IS DEENERGIZED.
NC STANDARD 1
PE-1
NC STAGE HEAT ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
RD C NO RD JOB SPECIFICATIONS.

PE-2 OPTIONAL 2 NOTE: S1 AIRFLOW SWITCH FACTORY SET TO START FAN AT


NC STAGE HEAT .10"WC TOTAL PRESSURE SENSED AT INLET FLOW PROBE.
BN C NO BN

PE-3 OPTIONAL 3
NC STAGE HEAT

BK BL/WH BK
SC FM

PNEUMATIC DIAGRAM
N.C.
RECOMMENDED FIELD P.E. SWITCH SETTINGS:
ACT.
PE-1 = 8 PSI
VEL. CNTRLR PE-2 = 6 PSI
BAL. TAPS (RESET BAND=3-8 PSI) PE-3 = 4 PSI
B
FLOW LO X
M 20 PSI MAIN CONSTANT
PROBE HI Y
T VOLUME
TOTAL AIR
REV. D.A.. STAT
FLOW

HEAT COLD AIR


S1 RELAY 1 PIPE
AIR

AIR
M FLOW PLENUM AIR
1 RESTRICTOR
3 OR OR 20 PSI MAIN

D.A.. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
2 PIPE
PE3 PE2 PE1 COLD T-STAT BRANCH PRESSURE (PSIG) HOT
ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE 1 = LOAD BEARING P.E.
SWITCH

1 1.6 3.9 E = 120V/1PH/60HZ - 2 STAGE


LOAD BEARING
P.E.

PER STAGE 2 0.8 1.9 5 = 120V/1PH/60HZ - 3 STAGE


3 0.5 1.3
K = 277V/1PH/60HZ - 1 STAGE
DISCONNECT

L = 277V/1PH/60HZ - 2 STAGE
SIZE & TYPE

DNF-40 1.6 3.9 Y = 277V/1PH/60HZ - 3 STAGE


DOOR INTERLOCK
BLOCK
FUSE

30 AMP BLOCK 1.6 3.9

1. MAX. K.W. BASED ON A.F.S. MAX LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.016 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5H0W0

REV.1 5/6/00 PNEUMATIC


PSFH004
- J4 -

YORK INTERNATIONAL 13
SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT
PRESS. INDEPENDENT, N.O. DAMPER, A.F.S. FAN START, DIRECT ACTING STAT, 1 PHASE, LOAD BEARING P.E. SWITCH W/ CONT. INTRLK.

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V
DISCONNECT OCCUPIED MODE:
SWITCH WHEN THE DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
SENSED BY THE S1 AIR FLOW SWITCH, THE FAN MOTOR
IS ENERGIZED.
FUSING SPACE TEMP WARM (STAT OUTPUT HI). AT A STAT
OUTPUT OF 13 PSI THE VEL. CNTRLR WILL BE CONTROLLING
OPTIONAL DISCONNECT SWITCH AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
AND OR FUSING WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
PANEL WIRING DIAGRAM STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
L1 (N) = 120V & 277V ON A FURTHER DROP IN SPACE TEMP., PE1 WILL CLOSE
TERMINAL 1 2 ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
BLOCK
BK WH AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.

BK BK WH UNOCCUPIED MODE:
WHEN DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
C1-1 STANDARD 1 G NO LONGER SENSED BY THE S1 AIR FLOW SWITCH, THE FAN
STAGE HEAT MOTOR IS DEENERGIZED.
RD C NO RD
ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
PE-2 OPTIONAL 2 JOB SPECIFICATIONS.
NC STAGE HEAT
BN C NO BN NOTE: S1 AIRFLOW SWITCH FACTORY SET TO START FAN AT
.10"WC TOTAL PRESSURE SENSED AT INLET FLOW PROBE.
PE-3 OPTIONAL 3
NC STAGE HEAT
(WHEN REQ.)
BK
TC BK C NO BK
C1
PE-1
NC
C N0 BK BL/WH BK
BK
5 SC FM
S1
NC

PNEUMATIC DIAGRAM
N.O. RECOMMENDED FIELD P.E. SWITCH SETTINGS:

ACT. PE-1 = 8 PSI


PE-2 = 6 PSI
VEL. CNTRLR PE-3 = 4 PSI
BAL. TAPS (RESET BAND=8-13 PSI)
B
FLOW LO Y
M 20 PSI MAIN CONSTANT
PROBE HI X
T VOLUME
TOTAL AIR
D.A.. STAT HEAT
FLOW

1 PIPE COLD AIR


S1 AIR
AIR

FLOW PLENUM AIR


RESTRICTOR
OR OR 20 PSI MAIN

D.A.. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
2 PIPE COLD HOT
PE3 PE2 PE1 T-STAT BRANCH PRESSURE (PSIG)
ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE J = LOAD BEARING P.E. W/ 30A
1 3.6 8.3 E = 120V/1PH/60HZ - 2 STAGE MAG. CONTACTOR INTERLOCK
30 AMP CONT.
LOAD BRG. PE

2 1.8 4.1 5 = 120V/1PH/60HZ - 3 STAGE K = LOAD BEARING P.E. W/ 50A


W/ INTRLK

PER STAGE 3 1.2 2.7


K = 277V/1PH/60HZ - 1 STAGE MAG. CONTACTOR INTERLOCK
1 5.7 13.2
50 AMP CONT. L = 277V/1PH/60HZ - 2 STAGE L = LOAD BEARING P.E. W/ 30A
2 2.8 6.6 MERC. CONTACTOR INTERLOCK
PER STAGE Y = 277V/1PH/60HZ - 3 STAGE
3 1.9 4.4
M = LOAD BEARING P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR INTERLOCK


SIZE & TYPE

DOOR INTERLOCK 4.8 11.0

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 5.7 13.2
BLOCK

30 AMP BLOCK
FUSE

2.8 6.6

60 AMP BLOCK 5.7 13.2

1. MAX. K.W. BASED ON 48A, P.E., OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.008 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5E0W0

REV.1 5/6/00 PNEUMATIC


PSFH005
- J5 -

14 YORK INTERNATIONAL
FORM AD1T-SECT J

SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT


PRESS. INDEPENDENT, N.C. DAMPER, A.F.S. FAN START, REVERSE ACTING STAT, 1 PHASE, LOAD BEARING P.E. SWITCH W/ CONT. INTRLK.

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V
DISCONNECT OCCUPIED MODE:
SWITCH WHEN THE DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
SENSED BY THE S1 AIR FLOW SWITCH, THE FAN MOTOR
IS ENERGIZED.
FUSING SPACE TEMP WARM (STAT OUTPUT LOW). AT A STAT
OUTPUT OF 3 PSI THE VEL. CNTRLR WILL BE CONTROLLING
OPTIONAL DISCONNECT SWITCH AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
AND OR FUSING WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
PANEL WIRING DIAGRAM STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
L1 (N) = 120V & 277V ON A FURTHER DROP IN SPACE TEMP., PE1 WILL CLOSE
TERMINAL 1 2 ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
BLOCK
BK WH AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.

BK BK WH UNOCCUPIED MODE:
WHEN DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
C1-1 STANDARD 1 G NO LONGER SENSED BY THE S1 AIR FLOW SWITCH, THE FAN
STAGE HEAT MOTOR IS DEENERGIZED.
RD C NO RD
ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
PE-2 OPTIONAL 2 JOB SPECIFICATIONS.
NC STAGE HEAT
BN C NO BN NOTE: S1 AIRFLOW SWITCH FACTORY SET TO START FAN AT
.10"WC TOTAL PRESSURE SENSED AT INLET FLOW PROBE.
PE-3 OPTIONAL 3
NC STAGE HEAT
(WHEN REQ.)
BK
TC BK C NO BK
C1
PE-1
NC
C N0 BK BL/WH BK
BK
5 SC FM
S1
NC

PNEUMATIC DIAGRAM
N.C. RECOMMENDED FIELD P.E. SWITCH SETTINGS:
ACT.
PE-1 = 8 PSI
PE-2 = 10 PSI
VEL. CNTRLR PE-3 = 12 PSI
BAL. TAPS (RESET BAND=3-8 PSI)
B
FLOW LO X CONSTANT
M 20 PSI MAIN
PROBE HI Y VOLUME
T TOTAL AIR
R.A.. STAT COLD AIR HEAT
FLOW

AIR
S1 1 PIPE
AIR

FLOW PLENUM AIR


RESTRICTOR
OR OR 20 PSI MAIN

R.A.. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE2 2 PIPE HOT T-STAT BRANCH PRESSURE (PSIG) COLD
PE3 PE1
ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE J = LOAD BEARING P.E. W/ 30A
1 3.6 8.3 E = 120V/1PH/60HZ - 2 STAGE MAG. CONTACTOR INTERLOCK
30 AMP CONT.
LOAD BRG. PE

2 1.8 4.1 5 = 120V/1PH/60HZ - 3 STAGE K = LOAD BEARING P.E. W/ 50A


W/ INTRLK

PER STAGE 3 1.2 2.7


K = 277V/1PH/60HZ - 1 STAGE MAG. CONTACTOR INTERLOCK
1 5.7 13.2
50 AMP CONT. L = 277V/1PH/60HZ - 2 STAGE L = LOAD BEARING P.E. W/ 30A
2 2.8 6.6 MERC. CONTACTOR INTERLOCK
PER STAGE Y = 277V/1PH/60HZ - 3 STAGE
3 1.9 4.4
M = LOAD BEARING P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR INTERLOCK


SIZE & TYPE

DOOR INTERLOCK 4.8 11.0

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 5.7 13.2
BLOCK

30 AMP BLOCK
FUSE

2.8 6.6

60 AMP BLOCK 5.7 13.2

1. MAX. K.W. BASED ON 48A, P.E., OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.008 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5F0W0

REV.1 5/6/00 PNEUMATIC


PSFH006
- J6 -

YORK INTERNATIONAL 15
SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT
PRESS. INDEPENDENT, N.O. DAMPER, A.F.S. FAN START, REVERSE ACTING STAT, 1 PHASE, LOAD BEARING P.E. SWITCH W/ CONT. INTRLK.

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V
DISCONNECT OCCUPIED MODE:
SWITCH WHEN THE DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
SENSED BY THE S1 AIR FLOW SWITCH, THE FAN MOTOR
IS ENERGIZED.
FUSING SPACE TEMP WARM (STAT OUTPUT LOW). AT A STAT
OUTPUT OF 3 PSI THE VEL. CNTRLR WILL BE CONTROLLING
OPTIONAL DISCONNECT SWITCH AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
AND OR FUSING WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
PANEL WIRING DIAGRAM STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
L1 (N) = 120V & 277V ON A FURTHER DROP IN SPACE TEMP., PE1 WILL CLOSE
TERMINAL 1 2 ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
BLOCK
BK WH
AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.

BK BK WH UNOCCUPIED MODE:
WHEN DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
C1-1 STANDARD 1 G NO LONGER SENSED BY THE S1 AIR FLOW SWITCH, THE FAN
STAGE HEAT MOTOR IS DEENERGIZED.
RD C NO RD
ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
PE-2 OPTIONAL 2 JOB SPECIFICATIONS.
NC STAGE HEAT
BN C NO BN NOTE: S1 AIRFLOW SWITCH FACTORY SET TO START FAN AT
.10"WC TOTAL PRESSURE SENSED AT INLET FLOW PROBE.
PE-3 OPTIONAL 3
NC STAGE HEAT
(WHEN REQ.)
BK
TC BK C NO BK
C1
PE-1
NC
C N0 BK BL/WH BK
BK
5 SC FM
S1
NC

PNEUMATIC DIAGRAM
N.O.
ACT. RECOMMENDED FIELD P.E. SWITCH SETTINGS:

PE-1 = 8 PSI
VEL. CNTRLR
PE-2 = 10 PSI
BAL. TAPS (RESET BAND=8-13 PSI)
PE-3 = 12 PSI
B
FLOW LO Y
M 20 PSI MAIN CONSTANT
PROBE HI X
T VOLUME
TOTAL AIR
REV. R.A.. STAT
FLOW

COLD AIR HEAT


S1 RELAY 1 PIPE AIR
AIR

M FLOW PLENUM AIR


1 RESTRICTOR
3 OR OR 20 PSI MAIN

R.A.. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
2 PIPE HOT COLD
PE3 PE2 PE1 T-STAT BRANCH PRESSURE (PSIG)
ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE J = LOAD BEARING P.E. W/ 30A
1 3.6 8.3 E = 120V/1PH/60HZ - 2 STAGE MAG. CONTACTOR INTERLOCK
30 AMP CONT.
LOAD BRG. PE

2 1.8 4.1 5 = 120V/1PH/60HZ - 3 STAGE K = LOAD BEARING P.E. W/ 50A


W/ INTRLK

PER STAGE 3 1.2 2.7


K = 277V/1PH/60HZ - 1 STAGE MAG. CONTACTOR INTERLOCK
1 5.7 13.2
50 AMP CONT. L = 277V/1PH/60HZ - 2 STAGE L = LOAD BEARING P.E. W/ 30A
2 2.8 6.6 MERC. CONTACTOR INTERLOCK
PER STAGE Y = 277V/1PH/60HZ - 3 STAGE
3 1.9 4.4
M = LOAD BEARING P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR INTERLOCK


SIZE & TYPE

DOOR INTERLOCK 4.8 11.0

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 5.7 13.2
BLOCK

30 AMP BLOCK
FUSE

2.8 6.6

60 AMP BLOCK 5.7 13.2

1. MAX. K.W. BASED ON 48A, P.E., OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.016 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5G0W0

REV.1 5/6/00 PNEUMATIC


PSFH007
- J7 -

16 YORK INTERNATIONAL
FORM AD1T-SECT J

SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT


PRESS. INDEPENDENT, N.C. DAMPER, A.F.S. FAN START, DIRECT ACTING STAT, 1 PHASE, LOAD BEARING P.E. SWITCH W/ CONT. INTRLK.

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V
DISCONNECT OCCUPIED MODE:
SWITCH WHEN THE DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
SENSED BY THE S1 AIR FLOW SWITCH, THE FAN MOTOR
IS ENERGIZED.
FUSING SPACE TEMP WARM (STAT OUTPUT HI). AT A STAT
OUTPUT OF 13 PSI THE VEL. CNTRLR WILL BE CONTROLLING
OPTIONAL DISCONNECT SWITCH AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
AND OR FUSING WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
PANEL WIRING DIAGRAM STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
L1 (N) = 120V & 277V ON A FURTHER DROP IN SPACE TEMP., PE1 WILL CLOSE
TERMINAL 1 2 ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
BLOCK
BK WH AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.

BK BK WH UNOCCUPIED MODE:
WHEN DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
C1-1 STANDARD 1 G NO LONGER SENSED BY THE S1 AIR FLOW SWITCH, THE FAN
STAGE HEAT MOTOR IS DEENERGIZED.
RD C NO RD
ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
PE-2 OPTIONAL 2 JOB SPECIFICATIONS.
NC STAGE HEAT
BN C NO BN NOTE: S1 AIRFLOW SWITCH FACTORY SET TO START FAN AT
.10"WC TOTAL PRESSURE SENSED AT INLET FLOW PROBE.
PE-3 OPTIONAL 3
NC STAGE HEAT
(WHEN REQ.)
BK
TC BK C NO BK
C1
PE-1
NC
C N0 BK BL/WH BK
BK
5 SC FM
S1
NC

PNEUMATIC DIAGRAM
N.C.
RECOMMENDED FIELD P.E. SWITCH SETTINGS:
ACT.
PE-1 = 8 PSI
VEL. CNTRLR PE-2 = 6 PSI
BAL. TAPS (RESET BAND=3-8 PSI) PE-3 = 4 PSI
B
FLOW LO X
M 20 PSI MAIN CONSTANT
PROBE HI Y
T VOLUME
TOTAL AIR
REV. D.A.. STAT
FLOW

HEAT COLD AIR


S1 RELAY 1 PIPE
AIR

AIR
M FLOW PLENUM AIR
1 RESTRICTOR
3 OR OR 20 PSI MAIN

D.A.. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
2 PIPE
PE3 PE2 PE1 COLD T-STAT BRANCH PRESSURE (PSIG) HOT
ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE J = LOAD BEARING P.E. W/ 30A
1 3.6 8.3 E = 120V/1PH/60HZ - 2 STAGE MAG. CONTACTOR INTERLOCK
30 AMP CONT.
LOAD BRG. PE

2 1.8 4.1 5 = 120V/1PH/60HZ - 3 STAGE K = LOAD BEARING P.E. W/ 50A


W/ INTRLK

PER STAGE 3 1.2 2.7


K = 277V/1PH/60HZ - 1 STAGE MAG. CONTACTOR INTERLOCK
1 5.7 13.2
50 AMP CONT. L = 277V/1PH/60HZ - 2 STAGE L = LOAD BEARING P.E. W/ 30A
2 2.8 6.6 MERC. CONTACTOR INTERLOCK
PER STAGE Y = 277V/1PH/60HZ - 3 STAGE
3 1.9 4.4
M = LOAD BEARING P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR INTERLOCK


SIZE & TYPE

DOOR INTERLOCK 4.8 11.0

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 5.7 13.2
BLOCK

30 AMP BLOCK
FUSE

2.8 6.6

60 AMP BLOCK 5.7 13.2

1. MAX. K.W. BASED ON 48A, P.E., OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.016 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5H0W0

REV.1 5/6/00 PNEUMATIC


PSFH008
- J8 -

YORK INTERNATIONAL 17
SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT
PRESS. INDEPENDENT, N.O. DAMPER, A.F.S. FAN START, DIRECT ACTING STAT, 1 PHASE, PILOT DUTY P.E. SWITCH

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V
DISCONNECT OCCUPIED MODE:
SWITCH WHEN THE DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
SENSED BY THE S1 AIR FLOW SWITCH, THE FAN MOTOR
IS ENERGIZED.
FUSING SPACE TEMP WARM (STAT OUTPUT HI). AT A STAT
OUTPUT OF 13 PSI THE VEL. CNTRLR WILL BE CONTROLLING
OPTIONAL DISCONNECT SWITCH AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
AND OR FUSING WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
PANEL WIRING DIAGRAM STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
L1 (N) = 120V & 277V ON A FURTHER DROP IN SPACE TEMP., PE1 WILL CLOSE
TERMINAL 1 2 ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
BLOCK
BK WH AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.

BK BK WH UNOCCUPIED MODE:
WHEN DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
C1-1 STANDARD 1 ST. HEAT G NO LONGER SENSED BY THE S1 AIR FLOW SWITCH, THE FAN
RD RD
MOTOR IS DEENERGIZED.
C2-1 OPTIONAL 2 ST. HEAT
BN BN ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
JOB SPECIFICATIONS.
C N0
(WHEN REQ.) C3-1 OPTIONAL 3 ST. HEAT
BK
TC C NO BK ST.1 NOTE: S1 AIRFLOW SWITCH FACTORY SET TO START FAN AT
BK BK
S1 5 C1 .10"WC TOTAL PRESSURE SENSED AT INLET FLOW PROBE.
NC
PE-1
NC
ST.2
RD C NO RD
C2
PE-2
NC
ST.3
BN C NO BN
C3
PE-3
NC
BK BL/WH BK
SC FM

PNEUMATIC DIAGRAM
N.O. RECOMMENDED FIELD P.E. SWITCH SETTINGS:

ACT. PE-1 = 8 PSI


PE-2 = 6 PSI
VEL. CNTRLR PE-3 = 4 PSI
BAL. TAPS (RESET BAND=8-13 PSI)
B
FLOW LO Y
M 20 PSI MAIN CONSTANT
PROBE HI X
T VOLUME
TOTAL AIR
D.A.. STAT HEAT
FLOW

1 PIPE COLD AIR


S1 AIR
AIR

FLOW PLENUM AIR


RESTRICTOR
OR OR 20 PSI MAIN

D.A.. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
2 PIPE COLD HOT
PE3 PE2 PE1 T-STAT BRANCH PRESSURE (PSIG)
ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE 2 = PILOT DUTY P.E. W/ 30A
1 3.6 8.3 E = 120V/1PH/60HZ - 2 STAGE MAG. CONTACTOR
DE-ENERGIZING
CONTACTOR

30 AMP 2 2.8 6.6 5 = 120V/1PH/60HZ - 3 STAGE 3 = PILOT DUTY P.E. W/ 50A


CONTACTOR 3 1.9 4.4
K = 277V/1PH/60HZ - 1 STAGE MAG. CONTACTOR
1 5.7 13.2
50 AMP L = 277V/1PH/60HZ - 2 STAGE 4 = PILOT DUTY P.E. W/ 30A
2 2.8 6.6 MERC. CONTACTOR
CONTACTOR Y = 277V/1PH/60HZ - 3 STAGE
3 1.9 4.4
5 = PILOT DUTY P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR


SIZE & TYPE

DOOR INTERLOCK 4.8 11.0

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 5.7 13.2
BLOCK

30 AMP BLOCK
FUSE

2.8 6.6

60 AMP BLOCK 5.7 13.2

1. MAX. K.W. BASED ON 48A, OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.008 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5E0W0

REV.1 5/6/00 PNEUMATIC


PSFH009
- J9 -

18 YORK INTERNATIONAL
FORM AD1T-SECT J

SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT


PRESS. INDEPENDENT, N.C. DAMPER, A.F.S. FAN START, REVERSE ACTING STAT, 1 PHASE, PILOT DUTY P.E. SWITCH

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V
DISCONNECT OCCUPIED MODE:
SWITCH WHEN THE DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
SENSED BY THE S1 AIR FLOW SWITCH, THE FAN MOTOR
IS ENERGIZED.
FUSING SPACE TEMP WARM (STAT OUTPUT LOW). AT A STAT
OUTPUT OF 3 PSI THE VEL. CNTRLR WILL BE CONTROLLING
OPTIONAL DISCONNECT SWITCH AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
AND OR FUSING WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
PANEL WIRING DIAGRAM STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
L1 (N) = 120V & 277V ON A FURTHER DROP IN SPACE TEMP., PE1 WILL CLOSE
TERMINAL 1 2 ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
BLOCK
BK WH AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.

BK BK WH UNOCCUPIED MODE:
WHEN DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
C1-1 STANDARD 1 ST. HEAT G NO LONGER SENSED BY THE S1 AIR FLOW SWITCH, THE FAN
RD RD
MOTOR IS DEENERGIZED.
C2-1 OPTIONAL 2 ST. HEAT
BN BN ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
JOB SPECIFICATIONS.
C N0
(WHEN REQ.) C3-1 OPTIONAL 3 ST. HEAT
BK
TC C NO BK ST.1 NOTE: S1 AIRFLOW SWITCH FACTORY SET TO START FAN AT
BK BK
S1 5 C1 .10"WC TOTAL PRESSURE SENSED AT INLET FLOW PROBE.
NC
PE-1
NC
ST.2
RD C NO RD
C2
PE-2
NC
ST.3
BN C NO BN
C3
PE-3
NC
BK BL/WH BK
SC FM

PNEUMATIC DIAGRAM
N.C. RECOMMENDED FIELD P.E. SWITCH SETTINGS:
ACT.
PE-1 = 8 PSI
PE-2 = 10 PSI
VEL. CNTRLR PE-3 = 12 PSI
BAL. TAPS (RESET BAND=3-8 PSI)
B
FLOW LO X CONSTANT
M 20 PSI MAIN
PROBE HI Y VOLUME
T TOTAL AIR
R.A.. STAT COLD AIR HEAT
FLOW

AIR
S1 1 PIPE
AIR

FLOW PLENUM AIR


RESTRICTOR
OR OR 20 PSI MAIN

R.A.. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE2 2 PIPE HOT T-STAT BRANCH PRESSURE (PSIG) COLD
PE3 PE1
ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE 2 = PILOT DUTY P.E. W/ 30A
1 3.6 8.3 E = 120V/1PH/60HZ - 2 STAGE MAG. CONTACTOR
DE-ENERGIZING
CONTACTOR

30 AMP 2 2.8 6.6 5 = 120V/1PH/60HZ - 3 STAGE 3 = PILOT DUTY P.E. W/ 50A


CONTACTOR 3 1.9 4.4
K = 277V/1PH/60HZ - 1 STAGE MAG. CONTACTOR
1 5.7 13.2
50 AMP L = 277V/1PH/60HZ - 2 STAGE 4 = PILOT DUTY P.E. W/ 30A
2 2.8 6.6 MERC. CONTACTOR
CONTACTOR Y = 277V/1PH/60HZ - 3 STAGE
3 1.9 4.4
5 = PILOT DUTY P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR


SIZE & TYPE

DOOR INTERLOCK 4.8 11.0

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 5.7 13.2
BLOCK

30 AMP BLOCK
FUSE

2.8 6.6

60 AMP BLOCK 5.7 13.2

1. MAX. K.W. BASED ON 48A, OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.008 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5F0W0

REV.1 5/6/00 PNEUMATIC


PSFH010
- J10 -

YORK INTERNATIONAL 19
SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT
PRESS. INDEPENDENT, N.O. DAMPER, A.F.S. FAN START, REVERSE ACTING STAT, 1 PHASE, PILOT DUTY P.E. SWITCH

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V
DISCONNECT OCCUPIED MODE:
SWITCH WHEN THE DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
SENSED BY THE S1 AIR FLOW SWITCH, THE FAN MOTOR
IS ENERGIZED.
FUSING SPACE TEMP WARM (STAT OUTPUT LOW). AT A STAT
OUTPUT OF 3 PSI THE VEL. CNTRLR WILL BE CONTROLLING
OPTIONAL DISCONNECT SWITCH AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
AND OR FUSING WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
PANEL WIRING DIAGRAM STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
L1 (N) = 120V & 277V ON A FURTHER DROP IN SPACE TEMP., PE1 WILL CLOSE
TERMINAL 1 2 ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
BLOCK
BK WH AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.

BK BK WH UNOCCUPIED MODE:
WHEN DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
C1-1 STANDARD 1 ST. HEAT G NO LONGER SENSED BY THE S1 AIR FLOW SWITCH, THE FAN
RD RD
MOTOR IS DEENERGIZED.
C2-1 OPTIONAL 2 ST. HEAT
BN BN ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
JOB SPECIFICATIONS.
C N0
(WHEN REQ.) C3-1 OPTIONAL 3 ST. HEAT
BK
TC C NO BK ST.1 NOTE: S1 AIRFLOW SWITCH FACTORY SET TO START FAN AT
BK BK
S1 5 C1 .10"WC TOTAL PRESSURE SENSED AT INLET FLOW PROBE.
NC
PE-1
NC
ST.2
RD C NO RD
C2
PE-2
NC
ST.3
BN C NO BN
C3
PE-3
NC
BK BL/WH BK
SC FM

PNEUMATIC DIAGRAM
N.O.
ACT. RECOMMENDED FIELD P.E. SWITCH SETTINGS:

PE-1 = 8 PSI
VEL. CNTRLR
PE-2 = 10 PSI
BAL. TAPS (RESET BAND=8-13 PSI)
PE-3 = 12 PSI
B
FLOW LO Y
M 20 PSI MAIN CONSTANT
PROBE HI X
T VOLUME
TOTAL AIR
REV. R.A.. STAT
FLOW

COLD AIR HEAT


S1 RELAY 1 PIPE AIR
AIR

M FLOW PLENUM AIR


1 RESTRICTOR
3 OR OR 20 PSI MAIN

R.A.. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
2 PIPE HOT COLD
PE3 PE2 PE1 T-STAT BRANCH PRESSURE (PSIG)
ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE 2 = PILOT DUTY P.E. W/ 30A
1 3.6 8.3 E = 120V/1PH/60HZ - 2 STAGE MAG. CONTACTOR
DE-ENERGIZING
CONTACTOR

30 AMP 2 2.8 6.6 5 = 120V/1PH/60HZ - 3 STAGE 3 = PILOT DUTY P.E. W/ 50A


CONTACTOR 3 1.9 4.4
K = 277V/1PH/60HZ - 1 STAGE MAG. CONTACTOR
1 5.7 13.2
50 AMP L = 277V/1PH/60HZ - 2 STAGE 4 = PILOT DUTY P.E. W/ 30A
2 2.8 6.6 MERC. CONTACTOR
CONTACTOR Y = 277V/1PH/60HZ - 3 STAGE
3 1.9 4.4
5 = PILOT DUTY P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR


SIZE & TYPE

DOOR INTERLOCK 4.8 11.0

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 5.7 13.2
BLOCK

30 AMP BLOCK
FUSE

2.8 6.6

60 AMP BLOCK 5.7 13.2

1. MAX. K.W. BASED ON 48A, OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.016 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5G0W0

REV.1 5/6/00 PNEUMATIC


PSFH011
- J11 -

20 YORK INTERNATIONAL
FORM AD1T-SECT J

SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT


PRESS. INDEPENDENT, N.C. DAMPER, A.F.S. FAN START, DIRECT ACTING STAT, 1 PHASE, PILOT DUTY P.E. SWITCH

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V
DISCONNECT OCCUPIED MODE:
SWITCH WHEN THE DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
SENSED BY THE S1 AIR FLOW SWITCH, THE FAN MOTOR
IS ENERGIZED.
FUSING SPACE TEMP WARM (STAT OUTPUT HI). AT A STAT
OUTPUT OF 13 PSI THE VEL. CNTRLR WILL BE CONTROLLING
OPTIONAL DISCONNECT SWITCH AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
AND OR FUSING WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
PANEL WIRING DIAGRAM STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
L1 (N) = 120V & 277V ON A FURTHER DROP IN SPACE TEMP., PE1 WILL CLOSE
TERMINAL 1 2 ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
BLOCK
BK WH AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.

BK BK WH UNOCCUPIED MODE:
WHEN DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
C1-1 STANDARD 1 ST. HEAT G NO LONGER SENSED BY THE S1 AIR FLOW SWITCH, THE FAN
RD RD
MOTOR IS DEENERGIZED.
C2-1 OPTIONAL 2 ST. HEAT
BN BN ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
JOB SPECIFICATIONS.
C N0
(WHEN REQ.) C3-1 OPTIONAL 3 ST. HEAT
BK
TC C NO BK ST.1 NOTE: S1 AIRFLOW SWITCH FACTORY SET TO START FAN AT
BK BK
S1 5 C1 .10"WC TOTAL PRESSURE SENSED AT INLET FLOW PROBE.
NC
PE-1
NC
ST.2
RD C NO RD
C2
PE-2
NC
ST.3
BN C NO BN
C3
PE-3
NC
BK BL/WH BK
SC FM

PNEUMATIC DIAGRAM
N.C.
RECOMMENDED FIELD P.E. SWITCH SETTINGS:
ACT.
PE-1 = 8 PSI
VEL. CNTRLR PE-2 = 6 PSI
BAL. TAPS (RESET BAND=3-8 PSI) PE-3 = 4 PSI
B
FLOW LO X
M 20 PSI MAIN CONSTANT
PROBE HI Y
T VOLUME
TOTAL AIR
REV. D.A.. STAT
FLOW

HEAT COLD AIR


S1 RELAY 1 PIPE
AIR

AIR
M FLOW PLENUM AIR
1 RESTRICTOR
3 OR OR 20 PSI MAIN

D.A.. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
2 PIPE
PE3 PE2 PE1 COLD T-STAT BRANCH PRESSURE (PSIG) HOT
ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE 2 = PILOT DUTY P.E. W/ 30A
1 3.6 8.3 E = 120V/1PH/60HZ - 2 STAGE MAG. CONTACTOR
DE-ENERGIZING
CONTACTOR

30 AMP 2 2.8 6.6 5 = 120V/1PH/60HZ - 3 STAGE 3 = PILOT DUTY P.E. W/ 50A


CONTACTOR 3 1.9 4.4
K = 277V/1PH/60HZ - 1 STAGE MAG. CONTACTOR
1 5.7 13.2
50 AMP L = 277V/1PH/60HZ - 2 STAGE 4 = PILOT DUTY P.E. W/ 30A
2 2.8 6.6 MERC. CONTACTOR
CONTACTOR Y = 277V/1PH/60HZ - 3 STAGE
3 1.9 4.4
5 = PILOT DUTY P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR


SIZE & TYPE

DOOR INTERLOCK 4.8 11.0

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 5.7 13.2
BLOCK

30 AMP BLOCK
FUSE

2.8 6.6

60 AMP BLOCK 5.7 13.2

1. MAX. K.W. BASED ON 48A, OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.016 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5H0W0

REV.1 5/6/00 PNEUMATIC


PSFH012
- J12 -

YORK INTERNATIONAL 21
SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT
PRESS. INDEPENDENT, N.O. DAMPER, A.F.S. FAN START, DIRECT ACTING STAT, 3 PHASE, LOAD BEARING P.E. SWITCH W/ CONT. INTRLK.

SEQUENCE OF OPERATION:
L1 L2 L3
DISCONNECT OCCUPIED MODE:
SWITCH WHEN THE DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
SENSED BY THE S1 AIR FLOW SWITCH, THE FAN MOTOR
IS ENERGIZED.
FUSING SPACE TEMP WARM (STAT OUTPUT HI). AT A STAT
OUTPUT OF 13 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
OPTIONAL DISCONNECT SWITCH WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
PANEL WIRING DIAGRAM AND OR FUSING STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
L1 L2 L3 N
ON A FURTHER DROP IN SPACE TEMP., PE1 WILL CLOSE
TERMINAL 1 2 3 4 ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
BLOCK
BK WH
AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
BK BL

UNOCCUPIED MODE:
BK STANDARD 1 STAGE HEAT WHEN DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
C1-1 G NO LONGER SENSED BY THE S1 AIR FLOW SWITCH, THE FAN
BK BK MOTOR IS DEENERGIZED.
C1-2 ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
C N0 BK JOB SPECIFICATIONS.
TC ST.1
BK BK C NO BK
S1 5 C1 NOTE: S1 AIRFLOW SWITCH FACTORY SET TO START FAN AT
NC .10"WC TOTAL PRESSURE SENSED AT INLET FLOW PROBE.
PE-1
NC
BK BL/WH BK
SC FM

BK BK
L1 1
C1-1
RD
C NO
L2 2
RD
PE-2
NC
BK BK C
L1 1 BN NO BN

C NO C1-1 BL
L2 2
RD 3 L3 PE-3
RD RD
NC
PE-2 BL BL
NC L3 3
C1-2 C1-2
PNEUMATIC DIAGRAM OPTIONAL 2 STAGE HEAT OPTIONAL 3 STAGE HEAT
N.O.
ACT. RECOMMENDED FIELD P.E. SWITCH SETTINGS:

VEL. CNTRLR PE-1 = 8 PSI


BAL. TAPS (RESET BAND=8-13 PSI) PE-2 = 6 PSI
B PE-3 = 4 PSI
FLOW LO Y
M 20 PSI MAIN CONSTANT
PROBE HI X
T VOLUME
TOTAL AIR
D.A.. STAT HEAT
FLOW

1 PIPE COLD AIR


S1 AIR
AIR

FLOW PLENUM AIR


RESTRICTOR
OR OR 20 PSI MAIN

D.A.. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
2 PIPE COLD HOT
PE3 PE2 PE1 T-STAT BRANCH PRESSURE (PSIG)
ROOM ROOM

HEATER COMPONENTS MAX. KW


3 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-3 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 208 V 480 V P = 208V/3PH/60HZ - 1 STAGE J = LOAD BEARING P.E. W/ 30A
1 10.7 24.9 R = 208V/3PH/60HZ - 2 STAGE MAG. CONTACTOR INTERLOCK
30 AMP CONT.
LOAD BRG. PE

2 4.4 9.1 1 = 208V/3PH/60HZ - 3 STAGE K = LOAD BEARING P.E. W/ 50A


W/ INTRLK

PER STAGE 3 2.9 6.0


U = 480V/3PH/60HZ - 1 STAGE MAG. CONTACTOR INTERLOCK
1 17.2 39.8
50 AMP CONT. W = 480V/3PH/60HZ - 2 STAGE L = LOAD BEARING P.E. W/ 30A
2 4.4 9.1 MERC. CONTACTOR INTERLOCK
PER STAGE 3 = 480V/3PH/60HZ - 3 STAGE
3 2.9 6.0
M = LOAD BEARING P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR INTERLOCK


SIZE & TYPE

DOOR INTERLOCK 14.3 33.2

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 17.2 39.8
BLOCK

30 AMP BLOCK
FUSE

8.6 19.9

60 AMP BLOCK 17.2 39.8

1. MAX. K.W. BASED ON 48A, P.E., OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.008 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5E0W0

REV.1 5/6/00 PNEUMATIC


PSFH013
- J13 -

22 YORK INTERNATIONAL
FORM AD1T-SECT J

SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT


PRESS. INDEPENDENT, N.C. DAMPER, A.F.S. FAN START, REVERSE ACTING STAT, 3 PHASE, LOAD BEARING P.E. SWITCH W/ CONT. INTRLK.

SEQUENCE OF OPERATION:
L1 L2 L3
DISCONNECT OCCUPIED MODE:
SWITCH WHEN THE DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
SENSED BY THE S1 AIR FLOW SWITCH, THE FAN MOTOR
IS ENERGIZED.
FUSING SPACE TEMP WARM (STAT OUTPUT LOW). AT A STAT
OUTPUT OF 3 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
OPTIONAL DISCONNECT SWITCH WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
PANEL WIRING DIAGRAM AND OR FUSING STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
L1 L2 L3 N
ON A FURTHER DROP IN SPACE TEMP., PE1 WILL CLOSE
TERMINAL 1 2 3 4 ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
BLOCK
BK WH
AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
BK BL

UNOCCUPIED MODE:
BK STANDARD 1 STAGE HEAT WHEN DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
C1-1 G NO LONGER SENSED BY THE S1 AIR FLOW SWITCH, THE FAN
BK BK MOTOR IS DEENERGIZED.
C1-2 ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
C N0 BK JOB SPECIFICATIONS.
TC ST.1
BK BK C NO BK
S1 5 C1 NOTE: S1 AIRFLOW SWITCH FACTORY SET TO START FAN AT
NC .10"WC TOTAL PRESSURE SENSED AT INLET FLOW PROBE.
PE-1
NC
BK BL/WH BK
SC FM

BK BK
L1 1
C1-1
RD
C NO
L2 2 RD

PE-2
NC
L1 1
BK BK
BN C NO BN

C NO C1-1 BL
L2 2
RD 3 L3 PE-3
RD NC
RD BL BL
PE-2
NC L3 3
C1-2 C1-2

PNEUMATIC DIAGRAM OPTIONAL 2 STAGE HEAT OPTIONAL 3 STAGE HEAT


N.C.
RECOMMENDED FIELD P.E. SWITCH SETTINGS:
ACT.
PE-1 = 8 PSI
VEL. CNTRLR PE-2 = 10 PSI
BAL. TAPS (RESET BAND=3-8 PSI) PE-3 = 12 PSI
B
FLOW LO X CONSTANT
M 20 PSI MAIN
PROBE HI Y VOLUME
T TOTAL AIR
R.A.. STAT COLD AIR HEAT
FLOW

AIR
S1 1 PIPE
AIR

FLOW PLENUM AIR


RESTRICTOR
OR OR 20 PSI MAIN

R.A.. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE2 2 PIPE HOT T-STAT BRANCH PRESSURE (PSIG) COLD
PE3 PE1
ROOM ROOM

HEATER COMPONENTS MAX. KW


3 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-3 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 208 V 480 V P = 208V/3PH/60HZ - 1 STAGE J = LOAD BEARING P.E. W/ 30A
1 10.7 24.9 R = 208V/3PH/60HZ - 2 STAGE MAG. CONTACTOR INTERLOCK
30 AMP CONT.
LOAD BRG. PE

2 4.4 9.1 1 = 208V/3PH/60HZ - 3 STAGE K = LOAD BEARING P.E. W/ 50A


W/ INTRLK

PER STAGE 3 2.9 6.0


U = 480V/3PH/60HZ - 1 STAGE MAG. CONTACTOR INTERLOCK
1 17.2 39.8
50 AMP CONT. W = 480V/3PH/60HZ - 2 STAGE L = LOAD BEARING P.E. W/ 30A
2 4.4 9.1 MERC. CONTACTOR INTERLOCK
PER STAGE 3 = 480V/3PH/60HZ - 3 STAGE
3 2.9 6.0
M = LOAD BEARING P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR INTERLOCK


SIZE & TYPE

DOOR INTERLOCK 14.3 33.2

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 17.2 39.8
BLOCK

30 AMP BLOCK
FUSE

8.6 19.9

60 AMP BLOCK 17.2 39.8

1. MAX. K.W. BASED ON 48A, P.E., OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.008 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5F0W0

REV.1 5/6/00 PNEUMATIC


PSFH014
- J14 -

YORK INTERNATIONAL 23
SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT
PRESS. INDEPENDENT, N.O. DAMPER, A.F.S. FAN START, REVERSE ACTING STAT, 3 PHASE, LOAD BEARING P.E. SWITCH W/ CONT. INTRLK.

SEQUENCE OF OPERATION:
L1 L2 L3
DISCONNECT OCCUPIED MODE:
SWITCH WHEN THE DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
SENSED BY THE S1 AIR FLOW SWITCH, THE FAN MOTOR
IS ENERGIZED.
FUSING SPACE TEMP WARM (STAT OUTPUT LOW). AT A STAT
OUTPUT OF 3 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
OPTIONAL DISCONNECT SWITCH WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
PANEL WIRING DIAGRAM AND OR FUSING STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
L1 L2 L3 N
ON A FURTHER DROP IN SPACE TEMP., PE1 WILL CLOSE
TERMINAL 1 2 3 4 ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
BLOCK
BK WH
AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
BK BL

UNOCCUPIED MODE:
BK STANDARD 1 STAGE HEAT WHEN DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
C1-1 G NO LONGER SENSED BY THE S1 AIR FLOW SWITCH, THE FAN
BK BK MOTOR IS DEENERGIZED.
C1-2 ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
C N0 BK JOB SPECIFICATIONS.
TC ST.1
BK BK C NO BK
S1 5 C1 NOTE: S1 AIRFLOW SWITCH FACTORY SET TO START FAN AT
NC .10"WC TOTAL PRESSURE SENSED AT INLET FLOW PROBE.
PE-1
NC
BK BL/WH BK
SC FM

BK BK
L1 1
C1-1
RD
C NO
L2 2 RD

PE-2
NC
BK BK C
L1 1 BN NO BN

C NO C1-1 BL
L2 2
RD 3 L3 PE-3
RD
RD
NC
PE-2 BL BL
NC L3 3
C1-2 C1-2
PNEUMATIC DIAGRAM OPTIONAL 2 STAGE HEAT OPTIONAL 3 STAGE HEAT
N.O.
ACT. RECOMMENDED FIELD P.E. SWITCH SETTINGS:

VEL. CNTRLR PE-1 = 8 PSI


BAL. TAPS (RESET BAND=8-13 PSI) PE-2 = 10 PSI
B PE-3 = 12 PSI
FLOW LO Y
M 20 PSI MAIN CONSTANT
PROBE HI X
T VOLUME
TOTAL AIR
REV. R.A.. STAT
FLOW

COLD AIR HEAT


S1 RELAY 1 PIPE AIR
AIR

M FLOW PLENUM AIR


1 RESTRICTOR
3 OR OR 20 PSI MAIN

R.A.. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
2 PIPE HOT COLD
PE3 PE2 PE1 T-STAT BRANCH PRESSURE (PSIG)
ROOM ROOM

HEATER COMPONENTS MAX. KW


3 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-3 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 208 V 480 V P = 208V/3PH/60HZ - 1 STAGE J = LOAD BEARING P.E. W/ 30A
1 10.7 24.9 R = 208V/3PH/60HZ - 2 STAGE MAG. CONTACTOR INTERLOCK
30 AMP CONT.
LOAD BRG. PE

2 4.4 9.1 1 = 208V/3PH/60HZ - 3 STAGE K = LOAD BEARING P.E. W/ 50A


W/ INTRLK

PER STAGE 3 2.9 6.0


U = 480V/3PH/60HZ - 1 STAGE MAG. CONTACTOR INTERLOCK
1 17.2 39.8
50 AMP CONT. W = 480V/3PH/60HZ - 2 STAGE L = LOAD BEARING P.E. W/ 30A
2 4.4 9.1 MERC. CONTACTOR INTERLOCK
PER STAGE 3 = 480V/3PH/60HZ - 3 STAGE
3 2.9 6.0
M = LOAD BEARING P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR INTERLOCK


SIZE & TYPE

DOOR INTERLOCK 14.3 33.2

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 17.2 39.8
BLOCK

30 AMP BLOCK
FUSE

8.6 19.9

60 AMP BLOCK 17.2 39.8

1. MAX. K.W. BASED ON 48A, P.E., OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.016 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5G0W0

REV.1 5/6/00 PNEUMATIC


PSFH015
- J15 -

24 YORK INTERNATIONAL
FORM AD1T-SECT J

SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT


PRESS. INDEPENDENT, N.C. DAMPER, A.F.S. FAN START, DIRECT ACTING STAT, 3 PHASE, LOAD BEARING P.E. SWITCH W/ CONT. INTRLK.

SEQUENCE OF OPERATION:
L1 L2 L3
DISCONNECT OCCUPIED MODE:
SWITCH WHEN THE DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
SENSED BY THE S1 AIR FLOW SWITCH, THE FAN MOTOR
IS ENERGIZED.
FUSING SPACE TEMP WARM (STAT OUTPUT HI). AT A STAT
OUTPUT OF 13 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
OPTIONAL DISCONNECT SWITCH WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
PANEL WIRING DIAGRAM AND OR FUSING STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
L1 L2 L3 N
ON A FURTHER DROP IN SPACE TEMP., PE1 WILL CLOSE
TERMINAL 1 2 3 4 ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
BLOCK
BK WH
AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
BK BL

UNOCCUPIED MODE:
BK STANDARD 1 STAGE HEAT WHEN DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
C1-1 G NO LONGER SENSED BY THE S1 AIR FLOW SWITCH, THE FAN
BK BK MOTOR IS DEENERGIZED.
C1-2 ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
C N0 BK JOB SPECIFICATIONS.
TC ST.1
BK BK C NO BK
S1 5 C1 NOTE: S1 AIRFLOW SWITCH FACTORY SET TO START FAN AT
NC .10"WC TOTAL PRESSURE SENSED AT INLET FLOW PROBE.
PE-1
NC
BK BL/WH BK
SC FM

BK BK
L1 1
C1-1
RD
C NO
L2 2
RD
PE-2
NC
L1 1
BK BK
BN C NO BN

C NO C1-1 BL
L2 2
RD 3 L3 PE-3
RD RD
NC
PE-2 BL BL
NC L3 3
C1-2 C1-2
PNEUMATIC DIAGRAM OPTIONAL 2 STAGE HEAT OPTIONAL 3 STAGE HEAT
N.C.
RECOMMENDED FIELD P.E. SWITCH SETTINGS:
ACT.
PE-1 = 8 PSI
VEL. CNTRLR PE-2 = 6 PSI
BAL. TAPS (RESET BAND=3-8 PSI) PE-3 = 4 PSI
B
FLOW LO X
M 20 PSI MAIN CONSTANT
PROBE HI Y
T VOLUME
TOTAL AIR
REV. D.A.. STAT
FLOW

HEAT COLD AIR


S1 RELAY 1 PIPE
AIR

AIR
M FLOW PLENUM AIR
1 RESTRICTOR
3 OR OR 20 PSI MAIN

D.A.. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
2 PIPE
PE3 PE2 PE1 COLD T-STAT BRANCH PRESSURE (PSIG) HOT
ROOM ROOM

HEATER COMPONENTS MAX. KW


3 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-3 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 208 V 480 V P = 208V/3PH/60HZ - 1 STAGE J = LOAD BEARING P.E. W/ 30A
1 10.7 24.9 R = 208V/3PH/60HZ - 2 STAGE MAG. CONTACTOR INTERLOCK
30 AMP CONT.
LOAD BRG. PE

2 4.4 9.1 1 = 208V/3PH/60HZ - 3 STAGE K = LOAD BEARING P.E. W/ 50A


W/ INTRLK

PER STAGE 3 2.9 6.0


U = 480V/3PH/60HZ - 1 STAGE MAG. CONTACTOR INTERLOCK
1 17.2 39.8
50 AMP CONT. W = 480V/3PH/60HZ - 2 STAGE L = LOAD BEARING P.E. W/ 30A
2 4.4 9.1 MERC. CONTACTOR INTERLOCK
PER STAGE 3 = 480V/3PH/60HZ - 3 STAGE
3 2.9 6.0
M = LOAD BEARING P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR INTERLOCK


SIZE & TYPE

DOOR INTERLOCK 14.3 33.2

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 17.2 39.8
BLOCK

30 AMP BLOCK
FUSE

8.6 19.9

60 AMP BLOCK 17.2 39.8

1. MAX. K.W. BASED ON 48A, P.E., OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.016 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5H0W0

REV.1 5/6/00 PNEUMATIC


PSFH016
- J16 -

YORK INTERNATIONAL 25
SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT
PRESS. INDEPENDENT, N.O. DAMPER, A.F.S. FAN START, DIRECT ACTING STAT, 3 PHASE, PILOT DUTY P.E. SWITCH

SEQUENCE OF OPERATION:
L1 L2 L3
DISCONNECT OCCUPIED MODE:
SWITCH WHEN THE DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
SENSED BY THE S1 AIR FLOW SWITCH, THE FAN MOTOR
IS ENERGIZED.
FUSING SPACE TEMP WARM (STAT OUTPUT HI). AT A STAT
OUTPUT OF 13 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
OPTIONAL DISCONNECT SWITCH WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
PANEL WIRING DIAGRAM AND OR FUSING STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
L1 L2 L3 N
ON A FURTHER DROP IN SPACE TEMP., PE1 WILL CLOSE
TERMINAL 1 2 3 4 ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
BLOCK
BK WH
AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
BK BL

UNOCCUPIED MODE:
BK STANDARD 1 STAGE HEAT WHEN DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
C1-1 G NO LONGER SENSED BY THE S1 AIR FLOW SWITCH, THE FAN
BK BK MOTOR IS DEENERGIZED.
C1-2 ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
C N0 BK JOB SPECIFICATIONS.
TC ST.1
BK BK C NO BK
S1 5 C1 NOTE: S1 AIRFLOW SWITCH FACTORY SET TO START FAN AT
NC .10"WC TOTAL PRESSURE SENSED AT INLET FLOW PROBE.
PE-1
NC
ST.2
RD C NO RD
C2 BK BK
L1 1
PE-2 BL
C1-1 3 L3
NC RD RD
ST.3 L2 2
BN C NO BN
C3 C2-1
PE-3 OPTIONAL 2 STAGE HEAT
NC
BK BL/WH BK
SC FM L1 1
BK BK

C1-1
RD RD
L2 2
C2-1
BN BN

C3-1
BL BL
PNEUMATIC DIAGRAM L3 3
C1-2
N.O.
OPTIONAL 3 STAGE HEAT
ACT.
RECOMMENDED FIELD P.E. SWITCH SETTINGS:
VEL. CNTRLR
BAL. TAPS (RESET BAND=8-13 PSI) PE-1 = 8 PSI
PE-2 = 6 PSI
B
FLOW LO Y PE-3 = 4 PSI
M 20 PSI MAIN
PROBE HI X
T CONSTANT
VOLUME
D.A.. STAT TOTAL AIR
FLOW

S1 1 PIPE HEAT
AIR

COLD AIR
AIR
RESTRICTOR PLENUM AIR
OR OR FLOW
20 PSI MAIN

D.A.. STAT
2 PIPE 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE3 PE2 PE1
COLD T-STAT BRANCH PRESSURE (PSIG) HOT
ROOM ROOM

HEATER COMPONENTS MAX. KW


3 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-3 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 208 V 480 V P = 208V/3PH/60HZ - 1 STAGE 2 = PILOT DUTY P.E. W/ 30A
1 10.7 24.9 R = 208V/3PH/60HZ - 2 STAGE MAG. CONTACTOR
DE-ENERGIZING
CONTACTOR

30 AMP 2 5.3 12.4 1 = 208V/3PH/60HZ - 3 STAGE 3 = PILOT DUTY P.E. W/ 50A


PER STAGE 3 3.5 8.3
U = 480V/3PH/60HZ - 1 STAGE MAG. CONTACTOR
1 17.2 39.8
50 AMP W = 480V/3PH/60HZ - 2 STAGE 4 = PILOT DUTY P.E. W/ 30A
2 8.6 19.9 MERC. CONTACTOR
PER STAGE 3 = 480V/3PH/60HZ - 3 STAGE
3 5.7 13.2
5 = PILOT DUTY P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR


SIZE & TYPE

DOOR INTERLOCK 14.3 33.2

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 17.2 39.8
BLOCK

30 AMP BLOCK 8.6 19.9


FUSE

60 AMP BLOCK 17.2 39.8

1. MAX. K.W. BASED ON 48A, OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.008 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5E0W0

REV.1 5/6/00 PNEUMATIC


PSFH017
- J17 -

26 YORK INTERNATIONAL
FORM AD1T-SECT J

SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT


PRESS. INDEPENDENT, N.C. DAMPER, A.F.S. FAN START, REVERSE ACTING STAT, 3 PHASE, PILOT DUTY P.E. SWITCH

SEQUENCE OF OPERATION:
L1 L2 L3 OCCUPIED MODE:
DISCONNECT WHEN THE DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
SWITCH SENSED BY THE S1 AIR FLOW SWITCH, THE FAN MOTOR
IS ENERGIZED.
SPACE TEMP WARM (STAT OUTPUT LOW). AT A STAT
FUSING OUTPUT OF 3 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
OPTIONAL DISCONNECT SWITCH WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
PANEL WIRING DIAGRAM AND OR FUSING STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
L1 L2 L3 N ON A FURTHER DROP IN SPACE TEMP., PE1 WILL CLOSE
TERMINAL ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
1 2 3 4
BLOCK
BK WH AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
BK BL
UNOCCUPIED MODE:
BK STANDARD 1 STAGE HEAT WHEN DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
NO LONGER SENSED BY THE S1 AIR FLOW SWITCH, THE FAN
C1-1 G
MOTOR IS DEENERGIZED.
BK BK

C1-2 ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY


C N0 BK
JOB SPECIFICATIONS.
TC ST.1
BK BK C NO BK NOTE: S1 AIRFLOW SWITCH FACTORY SET TO START FAN AT
S1 5 C1
NC .10"WC TOTAL PRESSURE SENSED AT INLET FLOW PROBE.
PE-1
NC
ST.2
RD C NO RD BK BK
C2 L1 1
BL
C1-1 3 L3
PE-2 RD RD
NC L2 2
ST.3
BN C NO BN C2-1
C3
OPTIONAL 2 STAGE HEAT
PE-3
NC
BK BL/WH BK
SC FM BK BK
L1 1
C1-1
RD RD
L2 2
C2-1
BN BN

C3-1
BL BL
L3 3
PNEUMATIC DIAGRAM C1-2
N.C. OPTIONAL 3 STAGE HEAT
ACT. RECOMMENDED FIELD P.E. SWITCH SETTINGS:

VEL. CNTRLR PE-1 = 8 PSI


BAL. TAPS (RESET BAND=3-8 PSI) PE-2 = 10 PSI
B PE-3 = 12 PSI
FLOW LO X
M 20 PSI MAIN
PROBE HI Y CONSTANT
T VOLUME
TOTAL AIR
R.A.. STAT
FLOW

S1 1 PIPE COLD AIR HEAT


AIR

AIR
RESTRICTOR FLOW PLENUM AIR
OR OR 20 PSI MAIN

R.A.. STAT
PE2 PE1 2 PIPE 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE3
HOT T-STAT BRANCH PRESSURE (PSIG) COLD
ROOM ROOM
HEATER COMPONENTS MAX. KW
3 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-3 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 208 V 480 V P = 208V/3PH/60HZ - 1 STAGE 2 = PILOT DUTY P.E. W/ 30A
1 10.7 24.9 R = 208V/3PH/60HZ - 2 STAGE MAG. CONTACTOR
DE-ENERGIZING
CONTACTOR

30 AMP 2 5.3 12.4 1 = 208V/3PH/60HZ - 3 STAGE 3 = PILOT DUTY P.E. W/ 50A


PER STAGE 3 3.5 8.3
U = 480V/3PH/60HZ - 1 STAGE MAG. CONTACTOR
1 17.2 39.8
50 AMP W = 480V/3PH/60HZ - 2 STAGE 4 = PILOT DUTY P.E. W/ 30A
2 8.6 19.9 MERC. CONTACTOR
PER STAGE 3 = 480V/3PH/60HZ - 3 STAGE
3 5.7 13.2
5 = PILOT DUTY P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR


SIZE & TYPE

DOOR INTERLOCK 14.3 33.2

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 17.2 39.8
BLOCK

30 AMP BLOCK 8.6 19.9


FUSE

60 AMP BLOCK 17.2 39.8

1. MAX. K.W. BASED ON 48A, OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.008 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5F0W0

REV.1 5/6/00 PNEUMATIC


PSFH018
- J18 -

YORK INTERNATIONAL 27
SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT
PRESS. INDEPENDENT, N.O. DAMPER, A.F.S. FAN START, REVERSE ACTING STAT, 3 PHASE, PILOT DUTY P.E. SWITCH

SEQUENCE OF OPERATION:
L1 L2 L3 OCCUPIED MODE:
DISCONNECT WHEN THE DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
SWITCH SENSED BY THE S1 AIR FLOW SWITCH, THE FAN MOTOR
IS ENERGIZED.
SPACE TEMP WARM (STAT OUTPUT LOW). AT A STAT
FUSING OUTPUT OF 3 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
OPTIONAL DISCONNECT SWITCH WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
PANEL WIRING DIAGRAM AND OR FUSING STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
L1 L2 L3 N ON A FURTHER DROP IN SPACE TEMP., PE1 WILL CLOSE
TERMINAL ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
1 2 3 4
BLOCK
BK WH AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
BK BL
UNOCCUPIED MODE:
BK STANDARD 1 STAGE HEAT WHEN DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
NO LONGER SENSED BY THE S1 AIR FLOW SWITCH, THE FAN
C1-1 G
MOTOR IS DEENERGIZED.
BK BK

C1-2 ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY


C N0 BK
JOB SPECIFICATIONS.
TC ST.1
BK BK C NO BK NOTE: S1 AIRFLOW SWITCH FACTORY SET TO START FAN AT
S1 5 C1
NC .10"WC TOTAL PRESSURE SENSED AT INLET FLOW PROBE.
PE-1
NC
ST.2
RD C NO RD BK BK
C2 L1 1
BL
PE-2 C1-1 3 L3
RD RD
NC L2 2
ST.3
BN C NO BN C2-1
C3
OPTIONAL 2 STAGE HEAT
PE-3
NC
BK BL/WH BK BK BK
SC FM L1 1
C1-1
RD RD
L2 2
C2-1
BN BN

C3-1
BL BL
L3 3
PNEUMATIC DIAGRAM C1-2
N.O. OPTIONAL 3 STAGE HEAT
ACT.
RECOMMENDED FIELD P.E. SWITCH SETTINGS:
VEL. CNTRLR
PE-1 = 8 PSI
BAL. TAPS (RESET BAND=8-13 PSI)
PE-2 = 10 PSI
B PE-3 = 12 PSI
FLOW LO Y
M 20 PSI MAIN
PROBE HI X CONSTANT
T
VOLUME
TOTAL AIR
REV. R.A.. STAT
FLOW

S1 RELAY 1 PIPE COLD AIR HEAT


AIR

AIR
M RESTRICTOR FLOW PLENUM AIR
1
3 OR OR 20 PSI MAIN

R.A.. STAT
2 PIPE 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE3 PE2 PE1 HOT T-STAT BRANCH PRESSURE (PSIG) COLD
ROOM ROOM

HEATER COMPONENTS MAX. KW


3 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-3 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 208 V 480 V P = 208V/3PH/60HZ - 1 STAGE 2 = PILOT DUTY P.E. W/ 30A
1 10.7 24.9 R = 208V/3PH/60HZ - 2 STAGE MAG. CONTACTOR
DE-ENERGIZING
CONTACTOR

30 AMP 2 5.3 12.4 1 = 208V/3PH/60HZ - 3 STAGE 3 = PILOT DUTY P.E. W/ 50A


PER STAGE 3 3.5 8.3
U = 480V/3PH/60HZ - 1 STAGE MAG. CONTACTOR
1 17.2 39.8
50 AMP W = 480V/3PH/60HZ - 2 STAGE 4 = PILOT DUTY P.E. W/ 30A
2 8.6 19.9 MERC. CONTACTOR
PER STAGE 3 = 480V/3PH/60HZ - 3 STAGE
3 5.7 13.2
5 = PILOT DUTY P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR


SIZE & TYPE

DOOR INTERLOCK 14.3 33.2

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 17.2 39.8
BLOCK

30 AMP BLOCK 8.6 19.9


FUSE

60 AMP BLOCK 17.2 39.8

1. MAX. K.W. BASED ON 48A, OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.016 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5G0W0

REV.1 5/6/00 PNEUMATIC


PSFH019
- J19 -

28 YORK INTERNATIONAL
FORM AD1T-SECT J

SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT


PRESS. INDEPENDENT, N.C. DAMPER, A.F.S. FAN START, DIRECT ACTING STAT, 3 PHASE, PILOT DUTY P.E. SWITCH

SEQUENCE OF OPERATION:
L1 L2 L3 OCCUPIED MODE:
DISCONNECT WHEN THE DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
SWITCH SENSED BY THE S1 AIR FLOW SWITCH, THE FAN MOTOR
IS ENERGIZED.
SPACE TEMP WARM (STAT OUTPUT HI). AT A STAT
FUSING OUTPUT OF 13 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
OPTIONAL DISCONNECT SWITCH WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
PANEL WIRING DIAGRAM AND OR FUSING STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
L1 L2 L3 N ON A FURTHER DROP IN SPACE TEMP., PE1 WILL CLOSE
TERMINAL ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
1 2 3 4
BLOCK
BK WH AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
BK BL
UNOCCUPIED MODE:
BK STANDARD 1 STAGE HEAT WHEN DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
NO LONGER SENSED BY THE S1 AIR FLOW SWITCH, THE FAN
C1-1 G
MOTOR IS DEENERGIZED.
BK BK

C1-2 ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY


C N0 BK
JOB SPECIFICATIONS.
TC ST.1
BK BK C NO BK NOTE: S1 AIRFLOW SWITCH FACTORY SET TO START FAN AT
S1 5 C1
NC .10"WC TOTAL PRESSURE SENSED AT INLET FLOW PROBE.
PE-1
NC
ST.2
RD C NO RD
C2 L1 1
BK BK

BL
PE-2 C1-1 3 L3
NC RD RD
ST.3 L2 2
BN C NO BN C2-1
C3
PE-3 OPTIONAL 2 STAGE HEAT
NC
BK BL/WH BK
SC FM BK BK
L1 1
C1-1
RD RD
L2 2
C2-1
BN BN

C3-1
BL BL
L3 3
PNEUMATIC DIAGRAM C1-2
N.C.
OPTIONAL 3 STAGE HEAT
ACT.
RECOMMENDED FIELD P.E. SWITCH SETTINGS:
VEL. CNTRLR
BAL. TAPS (RESET BAND=3-8 PSI) PE-1 = 8 PSI
PE-2 = 6 PSI
B PE-3 = 4 PSI
FLOW LO X
M 20 PSI MAIN
PROBE HI Y CONSTANT
T
VOLUME
REV. D.A.. STAT TOTAL AIR
FLOW

S1 RELAY 1 PIPE HEAT COLD AIR


AIR

AIR
M RESTRICTOR FLOW PLENUM AIR
1
3 OR OR 20 PSI MAIN

D.A.. STAT
2 PIPE 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE3 PE2 PE1
COLD T-STAT BRANCH PRESSURE (PSIG) HOT
ROOM ROOM
HEATER COMPONENTS MAX. KW
3 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-3 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 208 V 480 V P = 208V/3PH/60HZ - 1 STAGE 2 = PILOT DUTY P.E. W/ 30A
1 10.7 24.9 R = 208V/3PH/60HZ - 2 STAGE MAG. CONTACTOR
DE-ENERGIZING
CONTACTOR

30 AMP 2 5.3 12.4 1 = 208V/3PH/60HZ - 3 STAGE 3 = PILOT DUTY P.E. W/ 50A


PER STAGE 3 3.5 8.3
U = 480V/3PH/60HZ - 1 STAGE MAG. CONTACTOR
1 17.2 39.8
50 AMP W = 480V/3PH/60HZ - 2 STAGE 4 = PILOT DUTY P.E. W/ 30A
2 8.6 19.9 MERC. CONTACTOR
PER STAGE 3 = 480V/3PH/60HZ - 3 STAGE
3 5.7 13.2
5 = PILOT DUTY P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR


SIZE & TYPE

DOOR INTERLOCK 14.3 33.2

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 17.2 39.8
BLOCK

30 AMP BLOCK 8.6 19.9


FUSE

60 AMP BLOCK 17.2 39.8

1. MAX. K.W. BASED ON 48A, OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.016 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5H0W0

REV.1 5/6/00 PNEUMATIC


PSFH020
- J20 -

YORK INTERNATIONAL 29
SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT
PRESS. INDEPENDENT, N.O. DAMPER, A.F.S. FAN START, UNOCCUPIED MODE, DIRECT ACTING STAT, 1 PHASE, LOAD BEARING P.E. SWITCH

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V OCCUPIED MODE:
DISCONNECT WHEN THE DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
SWITCH SENSED BY THE S1 AIR FLOW SWITCH, THE FAN MOTOR
IS ENERGIZED.
SPACE TEMP WARM (STAT OUTPUT HI). AT A STAT
FUSING OUTPUT OF 13 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
OPTIONAL DISCONNECT SWITCH
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
AND OR FUSING
PANEL WIRING DIAGRAM CONTROLLING AT ITS MINIMUM.
ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
L1 (N) = 120V & 277V
TERMINAL AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
1 2
BLOCK UNOCCUPIED MODE:
BK WH
WHEN MAIN AIR HANDLER IS OFF, THE S1 AIR FLOW SWITCH
C N0 BK DEENERGIZES THE FAN. AS TEMP DROPS PE1 ENERGIZES
THE FAN.
BK C NO BK WH G
S1 5
NC ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
PE-2 STANDARD 1
C NO JOB SPECIFICATIONS.
NC STAGE HEAT
RD RD C NO RD
PE-1
NC OPTIONAL 2
PE-3 NOTE: S1 AIRFLOW SWITCH FACTORY SET TO START FAN AT
NC STAGE HEAT
.10"WC TOTAL PRESSURE SENSED AT INLET FLOW PROBE.
BN C NO BN

OPTIONAL 3
PE-4
NC STAGE HEAT

BK BL/WH BK
SC FM

N.O. PNEUMATIC DIAGRAM


ACT. RECOMMENDED FIELD P.E. SWITCH SETTINGS:

PE-1 = 8 PSI
PE-2 = 8 PSI
BAL. TAPS VEL. CNTRLR PE-3 = 6 PSI
B (RESET BAND=8-13 PSI) PE-4 = 4 PSI
FLOW LO Y CONSTANT
M 20 PSI MAIN
PROBE HI X VOLUME
T TOTAL AIR
D.A.. STAT HEAT COLD AIR
FLOW

S1 1 PIPE AIR
(UNOCCUPIED)
AIR

FLOW PLENUM AIR


FAN STARTS
RESTRICTOR
OR OR 20 PSI MAIN (FIELD CALIB.)

D.A.. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE4 PE3 PE2 PE1 2 PIPE COLD T-STAT BRANCH PRESSURE (PSIG) HOT
ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE 1 = LOAD BEARING P.E.
SWITCH

1 1.6 3.9 E = 120V/1PH/60HZ - 2 STAGE


LOAD BEARING
P.E.

PER STAGE 2 0.8 1.9 5 = 120V/1PH/60HZ - 3 STAGE


3 0.5 1.3
K = 277V/1PH/60HZ - 1 STAGE
DISCONNECT

L = 277V/1PH/60HZ - 2 STAGE
SIZE & TYPE

DNF-40 1.6 3.9 Y = 277V/1PH/60HZ - 3 STAGE


DOOR INTERLOCK
BLOCK
FUSE

30 AMP BLOCK 1.6 3.9

1. MAX. K.W. BASED ON A.F.S. MAX LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.008 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5E030

REV.1 5/6/00 PNEUMATIC


PSFH021
- J21 -

30 YORK INTERNATIONAL
FORM AD1T-SECT J

SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT


PRESS. INDEPENDENT, N.C. DAMPER, A.F.S. FAN START, UNOCCUPIED MODE, REVERSE ACTING STAT, 1 PHASE, LOAD BEARING P.E. SWITCH

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V OCCUPIED MODE:
DISCONNECT WHEN THE DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
SWITCH SENSED BY THE S1 AIR FLOW SWITCH, THE FAN MOTOR
IS ENERGIZED.
SPACE TEMP WARM (STAT OUTPUT LOW). AT A STAT
FUSING OUTPUT OF 3 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
OPTIONAL DISCONNECT SWITCH
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
AND OR FUSING
PANEL WIRING DIAGRAM CONTROLLING AT ITS MINIMUM.
ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
L1 (N) = 120V & 277V
TERMINAL AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
1 2
BLOCK UNOCCUPIED MODE:
BK WH
WHEN MAIN AIR HANDLER IS OFF, THE S1 AIR FLOW SWITCH
C N0 BK DEENERGIZES THE FAN. AS TEMP DROPS PE1 ENERGIZES
THE FAN.
BK C NO BK WH G
S1 5
NC ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
PE-2 STANDARD 1
C NO JOB SPECIFICATIONS.
RD NC STAGE HEAT
RD C NO RD
PE-1
NC OPTIONAL 2
PE-3 NOTE: S1 AIRFLOW SWITCH FACTORY SET TO START FAN AT
NC STAGE HEAT
.10"WC TOTAL PRESSURE SENSED AT INLET FLOW PROBE.
BN C NO BN

OPTIONAL 3
PE-4
NC STAGE HEAT

BK BL/WH BK
SC FM

N.C. PNEUMATIC DIAGRAM


ACT. RECOMMENDED FIELD P.E. SWITCH SETTINGS:

PE-1 = 8 PSI
PE-2 = 8 PSI
BAL. TAPS PE-3 = 10 PSI
VEL. CNTRLR
PE-4 = 12 PSI
B (RESET BAND=3-8 PSI)
FLOW LO X
M 20 PSI MAIN CONSTANT
PROBE HI Y
T VOLUME
TOTAL AIR
R.A.. STAT HEAT
FLOW

COLD AIR
S1 1 PIPE AIR (UNOCCUPIED)
AIR

FLOW PLENUM AIR


RESTRICTOR FAN STARTS
OR OR 20 PSI MAIN (FIELD CALIB.)

R.A.. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE4 PE3 PE2 PE1 2 PIPE HOT T-STAT BRANCH PRESSURE (PSIG) COLD
ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE 1 = LOAD BEARING P.E.
SWITCH

1 1.6 3.9 E = 120V/1PH/60HZ - 2 STAGE


LOAD BEARING
P.E.

PER STAGE 2 0.8 1.9 5 = 120V/1PH/60HZ - 3 STAGE


3 0.5 1.3
K = 277V/1PH/60HZ - 1 STAGE
DISCONNECT

L = 277V/1PH/60HZ - 2 STAGE
SIZE & TYPE

DNF-40 1.6 3.9 Y = 277V/1PH/60HZ - 3 STAGE


DOOR INTERLOCK
BLOCK
FUSE

30 AMP BLOCK 1.6 3.9

1. MAX. K.W. BASED ON A.F.S. MAX LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.008 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5F030

REV.1 5/6/00 PNEUMATIC


PSFH022
- J22 -

YORK INTERNATIONAL 31
SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT
PRESS. INDEPENDENT, N.O. DAMPER, A.F.S. FAN START, UNOCCUPIED MODE, REVERSE ACTING STAT, 1 PHASE, LOAD BEARING P.E. SWITCH

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V
OCCUPIED MODE:
DISCONNECT WHEN THE DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
SWITCH SENSED BY THE S1 AIR FLOW SWITCH, THE FAN MOTOR
IS ENERGIZED.
FUSING SPACE TEMP WARM (STAT OUTPUT LOW). AT A STAT
OUTPUT OF 3 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
OPTIONAL DISCONNECT SWITCH WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
AND OR FUSING STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
PANEL WIRING DIAGRAM CONTROLLING AT ITS MINIMUM.
ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
L1 (N) = 120V & 277V ENERGIZING THE FIRST STAGE OF ELELCTRIC HEAT.

TERMINAL 1 2 AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.


BLOCK
BK WH UNOCCUPIED MODE:
WHEN MAIN AIR HANDLER IS OFF, THE S1 AIR FLOW SWITCH
C N0 BK DEENERGIZES THE FAN. AS TEMP DROPS PE1 ENERGIZES
C NO THE FAN.
S1 BK BK WH G
5
NC ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
PE-2 STANDARD 1
C NO RD NC STAGE HEAT JOB SPECIFICATIONS.
RD C NO RD
PE-1
NC OPTIONAL 2
PE-3
NC STAGE HEAT NOTE: S1 AIRFLOW SWITCH FACTORY SET TO START FAN AT
BN C NO BN
.10"WC TOTAL PRESSURE SENSED AT INLET FLOW PROBE.

OPTIONAL 3
PE-4
NC STAGE HEAT

BK BL/WH BK
SC FM

N.O. PNEUMATIC DIAGRAM


ACT. RECOMMENDED FIELD P.E. SWITCH SETTINGS:

PE-1 = 8 PSI
PE-2 = 8 PSI
BAL. TAPS VEL. CNTRLR PE-3 = 10 PSI
B (RESET BAND=8-13 PSI) PE-4 = 12 PSI
FLOW LO Y
M 20 PSI MAIN
PROBE HI X CONSTANT
T
VOLUME
TOTAL AIR
REV. R.A.. STAT
FLOW

S1 RELAY 1 PIPE COLD AIR HEAT


AIR

AIR (UNOCCUPIED)
M RESTRICTOR FLOW PLENUM AIR
1 FAN STARTS
3 OR OR 20 PSI MAIN
(FIELD CALIB.)

R.A.. STAT
2 PIPE 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE4 PE3 PE2 PE1 HOT T-STAT BRANCH PRESSURE (PSIG) COLD
ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE 1 = LOAD BEARING P.E.
SWITCH

1 1.6 3.9 E = 120V/1PH/60HZ - 2 STAGE


LOAD BEARING
P.E.

PER STAGE 2 0.8 1.9 5 = 120V/1PH/60HZ - 3 STAGE


3 0.5 1.3
K = 277V/1PH/60HZ - 1 STAGE
DISCONNECT

L = 277V/1PH/60HZ - 2 STAGE
SIZE & TYPE

DNF-40 1.6 3.9 Y = 277V/1PH/60HZ - 3 STAGE


DOOR INTERLOCK
BLOCK
FUSE

30 AMP BLOCK 1.6 3.9

1. MAX. K.W. BASED ON A.F.S. MAX LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.016 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5G030

REV.1 5/6/00 PNEUMATIC


PSFH023
- J23 -

32 YORK INTERNATIONAL
FORM AD1T-SECT J

SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT


PRESS. INDEPENDENT, N.C. DAMPER, A.F.S. FAN START, UNOCCUPIED MODE, DIRECT ACTING STAT, 1 PHASE, LOAD BEARING P.E. SWITCH

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V OCCUPIED MODE:
DISCONNECT WHEN THE DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
SWITCH SENSED BY THE S1 AIR FLOW SWITCH, THE FAN MOTOR
IS ENERGIZED.
SPACE TEMP WARM (STAT OUTPUT HI). AT A STAT
FUSING OUTPUT OF 13 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
OPTIONAL DISCONNECT SWITCH
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
AND OR FUSING
PANEL WIRING DIAGRAM CONTROLLING AT ITS MINIMUM.
ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
L1 (N) = 120V & 277V
TERMINAL AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
1 2
BLOCK UNOCCUPIED MODE:
BK WH
WHEN MAIN AIR HANDLER IS OFF, THE S1 AIR FLOW SWITCH
C N0 BK DEENERGIZES THE FAN. AS TEMP DROPS PE1 ENERGIZES
THE FAN.
BK C NO BK WH G
S1 5
NC ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
PE-2 STANDARD 1
C NO JOB SPECIFICATIONS.
NC STAGE HEAT
RD RD C NO RD
PE-1
NC OPTIONAL 2
PE-3 NOTE: S1 AIRFLOW SWITCH FACTORY SET TO START FAN AT
NC STAGE HEAT
.10"WC TOTAL PRESSURE SENSED AT INLET FLOW PROBE.
BN C NO BN

OPTIONAL 3
PE-4
NC STAGE HEAT

BK BL/WH BK
SC FM

N.C. PNEUMATIC DIAGRAM


ACT.
RECOMMENDED FIELD P.E. SWITCH SETTINGS:

PE-1 = 8 PSI
PE-2 = 8 PSI
BAL. TAPS VEL. CNTRLR PE-3 = 6 PSI
B (RESET BAND=3-8 PSI)
PE-4 = 4 PSI
FLOW LO X
M 20 PSI MAIN
PROBE HI Y CONSTANT
T
VOLUME
REV. D.A.. STAT TOTAL AIR
FLOW

S1 RELAY 1 PIPE HEAT COLD AIR


AIR

AIR
M (UNOCCUPIED)
1 RESTRICTOR FLOW PLENUM AIR
3 OR OR 20 PSI MAIN FAN STARTS
(FIELD CALIB.)

D.A.. STAT
2 PIPE 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE2 PE1 COLD T-STAT BRANCH PRESSURE (PSIG) HOT
PE4 PE3
ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE 1 = LOAD BEARING P.E.
SWITCH

1 1.6 3.9 E = 120V/1PH/60HZ - 2 STAGE


LOAD BEARING
P.E.

PER STAGE 2 0.8 1.9 5 = 120V/1PH/60HZ - 3 STAGE


3 0.5 1.3
K = 277V/1PH/60HZ - 1 STAGE
DISCONNECT

L = 277V/1PH/60HZ - 2 STAGE
SIZE & TYPE

DNF-40 1.6 3.9 Y = 277V/1PH/60HZ - 3 STAGE


DOOR INTERLOCK
BLOCK
FUSE

30 AMP BLOCK 1.6 3.9

1. MAX. K.W. BASED ON A.F.S. MAX LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.016 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5H030

REV.1 5/6/00 PNEUMATIC


PSFH024
- J24 -

YORK INTERNATIONAL 33
SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT
PRESS. INDEPENDENT, N.O. DAMPER, A.F.S. FAN START, UNOCCUPIED MODE, DIRECT ACTING STAT, 1 PHASE, LOAD BEARING P.E. SWITCH W/ CONT. INTRLK.

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V OCCUPIED MODE:
DISCONNECT WHEN THE DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
SWITCH SENSED BY THE S1 AIR FLOW SWITCH, THE FAN MOTOR
IS ENERGIZED.
SPACE TEMP WARM (STAT OUTPUT HI). AT A STAT
FUSING OUTPUT OF 13 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
OPTIONAL DISCONNECT SWITCH
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
AND OR FUSING
PANEL WIRING DIAGRAM CONTROLLING AT ITS MINIMUM.
ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
L1 (N) = 120V & 277V ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
TERMINAL 1 2
BLOCK AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
BK WH
UNOCCUPIED MODE:
WHEN MAIN AIR HANDLER IS OFF, THE S1 AIR FLOW SWITCH
BK BK WH DEENERGIZES THE FAN. AS TEMP DROPS PE1 ENERGIZES
THE FAN.
C1-1 STANDARD 1 G
STAGE HEAT
ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
RD C NO RD JOB SPECIFICATIONS.

PE-3 OPTIONAL 2
NC STAGE HEAT
BN C NO BN
NOTE: S1 AIRFLOW SWITCH FACTORY SET TO START FAN AT
OPTIONAL 3 .10"WC TOTAL PRESSURE SENSED AT INLET FLOW PROBE.
PE-4
C N0 BK NC STAGE HEAT
(WHEN REQ.)
BK
TC BK C NO BK
S1 5 C1
NC
C PE-2
NO NC
RD BK BL/WH BK
PE-1 SC FM
NC

N.O. PNEUMATIC DIAGRAM


ACT. RECOMMENDED FIELD P.E. SWITCH SETTINGS:

PE-1 = 8 PSI
PE-2 = 8 PSI
BAL. TAPS VEL. CNTRLR PE-3 = 6 PSI
B (RESET BAND=8-13 PSI) PE-4 = 4 PSI
FLOW LO Y CONSTANT
M 20 PSI MAIN
PROBE HI X VOLUME
T TOTAL AIR
D.A.. STAT HEAT COLD AIR
FLOW

S1 1 PIPE AIR
(UNOCCUPIED)
AIR

FLOW PLENUM AIR


FAN STARTS
RESTRICTOR
OR OR 20 PSI MAIN (FIELD CALIB.)

D.A.. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE4 PE3 PE2 PE1 2 PIPE COLD T-STAT BRANCH PRESSURE (PSIG) HOT
ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE J = LOAD BEARING P.E. W/ 30A
1 3.6 8.3 E = 120V/1PH/60HZ - 2 STAGE MAG. CONTACTOR INTERLOCK
30 AMP CONT.
LOAD BRG. PE

2 1.8 4.1 5 = 120V/1PH/60HZ - 3 STAGE K = LOAD BEARING P.E. W/ 50A


W/ INTRLK

PER STAGE 3 1.2 2.7


K = 277V/1PH/60HZ - 1 STAGE MAG. CONTACTOR INTERLOCK
1 5.7 13.2
50 AMP CONT. L = 277V/1PH/60HZ - 2 STAGE L = LOAD BEARING P.E. W/ 30A
2 2.8 6.6 MERC. CONTACTOR INTERLOCK
PER STAGE Y = 277V/1PH/60HZ - 3 STAGE
3 1.9 4.4
M = LOAD BEARING P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR INTERLOCK


SIZE & TYPE

DOOR INTERLOCK 4.8 11.0

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 5.7 13.2
BLOCK

30 AMP BLOCK
FUSE

2.8 6.6

60 AMP BLOCK 5.7 13.2

1. MAX. K.W. BASED ON 48A, P.E., OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.016 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5E030

REV.1 5/6/00 PNEUMATIC


PSFH025
- J25 -

34 YORK INTERNATIONAL
FORM AD1T-SECT J

SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT


PRESS. INDEPENDENT, N.C. DAMPER, A.F.S. FAN START, UNOCCUPIED MODE, REVERSE ACTING STAT, 1 PHASE, LOAD BEARING P.E. SWITCH W/ CONT. INTRLK.

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V OCCUPIED MODE:
DISCONNECT WHEN THE DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
SWITCH SENSED BY THE S1 AIR FLOW SWITCH, THE FAN MOTOR
IS ENERGIZED.
SPACE TEMP WARM (STAT OUTPUT LOW). AT A STAT
FUSING OUTPUT OF 3 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
OPTIONAL DISCONNECT SWITCH
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
AND OR FUSING
PANEL WIRING DIAGRAM CONTROLLING AT ITS MINIMUM.
ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
L1 (N) = 120V & 277V ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
TERMINAL 1 2
BLOCK AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
BK WH
UNOCCUPIED MODE:
WHEN MAIN AIR HANDLER IS OFF, THE S1 AIR FLOW SWITCH
BK BK WH DEENERGIZES THE FAN. AS TEMP DROPS PE1 ENERGIZES
THE FAN.
C1-1 STANDARD 1 G
STAGE HEAT
ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
RD C NO RD JOB SPECIFICATIONS.

PE-3 OPTIONAL 2
NC STAGE HEAT
BN C NO BN
NOTE: S1 AIRFLOW SWITCH FACTORY SET TO START FAN AT
OPTIONAL 3 .10"WC TOTAL PRESSURE SENSED AT INLET FLOW PROBE.
PE-4
C N0 BK NC STAGE HEAT
(WHEN REQ.)
BK
TC BK C NO BK
S1 5 C1
NC
C PE-2
NO NC
RD BK BL/WH BK
PE-1 SC FM
NC

N.C. PNEUMATIC DIAGRAM


ACT. RECOMMENDED FIELD P.E. SWITCH SETTINGS:

PE-1 = 8 PSI
PE-2 = 8 PSI
BAL. TAPS PE-3 = 10 PSI
VEL. CNTRLR
PE-4 = 12 PSI
B (RESET BAND=3-8 PSI)
FLOW LO X
M 20 PSI MAIN CONSTANT
PROBE HI Y
T VOLUME
TOTAL AIR
R.A.. STAT HEAT
FLOW

COLD AIR
S1 1 PIPE AIR (UNOCCUPIED)
AIR

FLOW PLENUM AIR


RESTRICTOR FAN STARTS
OR OR 20 PSI MAIN (FIELD CALIB.)

R.A.. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE4 PE3 PE2 PE1 2 PIPE HOT T-STAT BRANCH PRESSURE (PSIG) COLD
ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE J = LOAD BEARING P.E. W/ 30A
1 3.6 8.3 E = 120V/1PH/60HZ - 2 STAGE MAG. CONTACTOR INTERLOCK
30 AMP CONT.
LOAD BRG. PE

2 1.8 4.1 5 = 120V/1PH/60HZ - 3 STAGE K = LOAD BEARING P.E. W/ 50A


W/ INTRLK

PER STAGE 3 1.2 2.7


K = 277V/1PH/60HZ - 1 STAGE MAG. CONTACTOR INTERLOCK
1 5.7 13.2
50 AMP CONT. L = 277V/1PH/60HZ - 2 STAGE L = LOAD BEARING P.E. W/ 30A
2 2.8 6.6 MERC. CONTACTOR INTERLOCK
PER STAGE Y = 277V/1PH/60HZ - 3 STAGE
3 1.9 4.4
M = LOAD BEARING P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR INTERLOCK


SIZE & TYPE

DOOR INTERLOCK 4.8 11.0

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 5.7 13.2
BLOCK

30 AMP BLOCK
FUSE

2.8 6.6

60 AMP BLOCK 5.7 13.2

1. MAX. K.W. BASED ON 48A, P.E., OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.008 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5F030

REV.1 5/6/00 PNEUMATIC


PSFH026
- J26 -

YORK INTERNATIONAL 35
SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT
PRESS. INDEPENDENT, N.O. DAMPER, A.F.S. FAN START, UNOCCUPIED MODE, REVERSE ACTING STAT, 1 PHASE, LOAD BEARING P.E. SWITCH W/ CONT. INTRLK.

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V
OCCUPIED MODE:
DISCONNECT WHEN THE DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
SWITCH SENSED BY THE S1 AIR FLOW SWITCH, THE FAN MOTOR
IS ENERGIZED.
FUSING SPACE TEMP WARM (STAT OUTPUT LOW). AT A STAT
OUTPUT OF 3 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
OPTIONAL DISCONNECT SWITCH WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
AND OR FUSING STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
PANEL WIRING DIAGRAM CONTROLLING AT ITS MINIMUM.
ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
L1 (N) = 120V & 277V
ENERGIZING THE FIRST STAGE OF ELELCTRIC HEAT.
TERMINAL 1 2
BLOCK AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
BK WH
UNOCCUPIED MODE:
WHEN MAIN AIR HANDLER IS OFF, THE S1 AIR FLOW SWITCH
BK BK WH
DEENERGIZES THE FAN. AS TEMP DROPS PE1 ENERGIZES
C1-1 STANDARD 1 THE FAN.
G
STAGE HEAT
C ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
RD NO RD
JOB SPECIFICATIONS.
PE-3 OPTIONAL 2
NC STAGE HEAT
BN C NO BN
NOTE: S1 AIRFLOW SWITCH FACTORY SET TO START FAN AT
PE-4 OPTIONAL 3 .10"WC TOTAL PRESSURE SENSED AT INLET FLOW PROBE.
C N0 BK NC STAGE HEAT
(WHEN REQ.)
BK
TC BK C NO BK
S1 5 C1
NC
C PE-2
NO NC
RD BK BL/WH BK
PE-1 SC FM
NC

N.O. PNEUMATIC DIAGRAM


ACT. RECOMMENDED FIELD P.E. SWITCH SETTINGS:

PE-1 = 8 PSI
PE-2 = 8 PSI
BAL. TAPS VEL. CNTRLR PE-3 = 10 PSI
B (RESET BAND=8-13 PSI) PE-4 = 12 PSI
FLOW LO Y
M 20 PSI MAIN
PROBE HI X CONSTANT
T
VOLUME
TOTAL AIR
REV. R.A.. STAT
FLOW

S1 RELAY 1 PIPE COLD AIR HEAT


AIR

AIR (UNOCCUPIED)
M RESTRICTOR FLOW PLENUM AIR
1 FAN STARTS
3 OR OR 20 PSI MAIN
(FIELD CALIB.)

R.A.. STAT
2 PIPE 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE4 PE3 PE2 PE1 HOT T-STAT BRANCH PRESSURE (PSIG) COLD
ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE J = LOAD BEARING P.E. W/ 30A
1 3.6 8.3 E = 120V/1PH/60HZ - 2 STAGE MAG. CONTACTOR INTERLOCK
30 AMP CONT.
LOAD BRG. PE

2 1.8 4.1 5 = 120V/1PH/60HZ - 3 STAGE K = LOAD BEARING P.E. W/ 50A


W/ INTRLK

PER STAGE 3 1.2 2.7


K = 277V/1PH/60HZ - 1 STAGE MAG. CONTACTOR INTERLOCK
1 5.7 13.2
50 AMP CONT. L = 277V/1PH/60HZ - 2 STAGE L = LOAD BEARING P.E. W/ 30A
2 2.8 6.6 MERC. CONTACTOR INTERLOCK
PER STAGE Y = 277V/1PH/60HZ - 3 STAGE
3 1.9 4.4
M = LOAD BEARING P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR INTERLOCK


SIZE & TYPE

DOOR INTERLOCK 4.8 11.0

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 5.7 13.2
BLOCK

30 AMP BLOCK
FUSE

2.8 6.6

60 AMP BLOCK 5.7 13.2

1. MAX. K.W. BASED ON 48A, P.E., OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.016 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5G030

REV.1 5/6/00 PNEUMATIC


PSFH027
- J27 -

36 YORK INTERNATIONAL
FORM AD1T-SECT J

SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT


PRESS. INDEPENDENT, N.C. DAMPER, A.F.S. FAN START, UNOCCUPIED MODE, DIRECT ACTING STAT, 1 PHASE, LOAD BEARING P.E. SWITCH W/ CONT. INTRLK.

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V OCCUPIED MODE:
DISCONNECT WHEN THE DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
SWITCH SENSED BY THE S1 AIR FLOW SWITCH, THE FAN MOTOR
IS ENERGIZED.
SPACE TEMP WARM (STAT OUTPUT HI). AT A STAT
FUSING OUTPUT OF 13 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
OPTIONAL DISCONNECT SWITCH
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
AND OR FUSING
PANEL WIRING DIAGRAM CONTROLLING AT ITS MINIMUM.
ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
L1 (N) = 120V & 277V ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
TERMINAL 1 2
BLOCK AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
BK WH
UNOCCUPIED MODE:
WHEN MAIN AIR HANDLER IS OFF, THE S1 AIR FLOW SWITCH
BK BK WH DEENERGIZES THE FAN. AS TEMP DROPS PE1 ENERGIZES
THE FAN.
C1-1 STANDARD 1 G
STAGE HEAT
ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
RD C NO RD JOB SPECIFICATIONS.

PE-3 OPTIONAL 2
NC STAGE HEAT
BN C NO BN
NOTE: S1 AIRFLOW SWITCH FACTORY SET TO START FAN AT
OPTIONAL 3 .10"WC TOTAL PRESSURE SENSED AT INLET FLOW PROBE.
PE-4
C N0 BK NC STAGE HEAT
(WHEN REQ.)
BK
TC BK C NO BK
S1 5 C1
NC
C PE-2
NO NC
RD BK BL/WH BK
PE-1 SC FM
NC

N.C. PNEUMATIC DIAGRAM


ACT.
RECOMMENDED FIELD P.E. SWITCH SETTINGS:

PE-1 = 8 PSI
PE-2 = 8 PSI
BAL. TAPS VEL. CNTRLR PE-3 = 6 PSI
B (RESET BAND=3-8 PSI)
PE-4 = 4 PSI
FLOW LO X
M 20 PSI MAIN
PROBE HI Y CONSTANT
T
VOLUME
REV. D.A.. STAT TOTAL AIR
FLOW

S1 RELAY 1 PIPE HEAT COLD AIR


AIR

AIR
M (UNOCCUPIED)
1 RESTRICTOR FLOW PLENUM AIR
3 OR OR 20 PSI MAIN FAN STARTS
(FIELD CALIB.)

D.A.. STAT
2 PIPE 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE2 PE1 COLD T-STAT BRANCH PRESSURE (PSIG) HOT
PE4 PE3
ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE J = LOAD BEARING P.E. W/ 30A
1 3.6 8.3 E = 120V/1PH/60HZ - 2 STAGE MAG. CONTACTOR INTERLOCK
30 AMP CONT.
LOAD BRG. PE

2 1.8 4.1 5 = 120V/1PH/60HZ - 3 STAGE K = LOAD BEARING P.E. W/ 50A


W/ INTRLK

PER STAGE 3 1.2 2.7


K = 277V/1PH/60HZ - 1 STAGE MAG. CONTACTOR INTERLOCK
1 5.7 13.2
50 AMP CONT. L = 277V/1PH/60HZ - 2 STAGE L = LOAD BEARING P.E. W/ 30A
2 2.8 6.6 MERC. CONTACTOR INTERLOCK
PER STAGE Y = 277V/1PH/60HZ - 3 STAGE
3 1.9 4.4
M = LOAD BEARING P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR INTERLOCK


SIZE & TYPE

DOOR INTERLOCK 4.8 11.0

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 5.7 13.2
BLOCK

30 AMP BLOCK
FUSE

2.8 6.6

60 AMP BLOCK 5.7 13.2

1. MAX. K.W. BASED ON 48A, P.E., OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.018 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5H030

REV.1 5/6/00 PNEUMATIC


PSFH028
- J28 -

YORK INTERNATIONAL 37
SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT
PRESS. INDEPENDENT, N.O. DAMPER, A.F.S. FAN START, UNOCCUPIED MODE, DIRECT ACTING STAT, 1 PHASE, PILOT DUTY P.E. SWITCH

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V OCCUPIED MODE:
DISCONNECT WHEN THE DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
SWITCH SENSED BY THE S1 AIR FLOW SWITCH, THE FAN MOTOR
IS ENERGIZED.
SPACE TEMP WARM (STAT OUTPUT HI). AT A STAT
FUSING OUTPUT OF 13 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
OPTIONAL DISCONNECT SWITCH
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
AND OR FUSING
PANEL WIRING DIAGRAM CONTROLLING AT ITS MINIMUM.
ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
L1 (N) = 120V & 277V ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
TERMINAL 1 2
BLOCK AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
BK WH
UNOCCUPIED MODE:
WHEN MAIN AIR HANDLER IS OFF, THE S1 AIR FLOW SWITCH
BK BK WH DEENERGIZES THE FAN. AS TEMP DROPS PE1 ENERGIZES
STANDARD 1 ST. HEAT THE FAN.
C1-1 G
RD RD
ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
OPTIONAL 2 ST. HEAT JOB SPECIFICATIONS.
C2-1
BN BN
C N0 BK OPTIONAL 3 ST. HEAT
C3-1
TC C NO ST.1
BK BK BK
S1 5 C1 NOTE: S1 AIRFLOW SWITCH FACTORY SET TO START FAN AT
NC .10"WC TOTAL PRESSURE SENSED AT INLET FLOW PROBE.
C PE-2
NO (WHEN REQ.) NC
RD
ST.2
RD C NO RD
PE-1 C2
NC
PE-3
NC
ST.3
BN C NO BN
C3
PE-4
NC
BK BL/WH BK
SC FM

N.O. PNEUMATIC DIAGRAM


ACT. RECOMMENDED FIELD P.E. SWITCH SETTINGS:

PE-1 = 8 PSI
PE-2 = 8 PSI
BAL. TAPS VEL. CNTRLR PE-3 = 6 PSI
B (RESET BAND=8-13 PSI) PE-4 = 4 PSI
FLOW LO Y CONSTANT
M 20 PSI MAIN
PROBE HI X VOLUME
T TOTAL AIR
D.A.. STAT HEAT COLD AIR
FLOW

S1 1 PIPE AIR
(UNOCCUPIED)
AIR

FLOW PLENUM AIR


FAN STARTS
RESTRICTOR
OR OR 20 PSI MAIN (FIELD CALIB.)

D.A.. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE4 PE3 PE2 PE1 2 PIPE COLD T-STAT BRANCH PRESSURE (PSIG) HOT
ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE 2 = PILOT DUTY P.E. W/ 30A
1 3.6 8.3 E = 120V/1PH/60HZ - 2 STAGE MAG. CONTACTOR
DE-ENERGIZING
CONTACTOR

30 AMP 2 2.8 6.6 5 = 120V/1PH/60HZ - 3 STAGE 3 = PILOT DUTY P.E. W/ 50A


CONTACTOR 3 1.9 4.4
K = 277V/1PH/60HZ - 1 STAGE MAG. CONTACTOR
1 5.7 13.2
50 AMP L = 277V/1PH/60HZ - 2 STAGE 4 = PILOT DUTY P.E. W/ 30A
2 2.8 6.6 MERC. CONTACTOR
CONTACTOR Y = 277V/1PH/60HZ - 3 STAGE
3 1.9 4.4
5 = PILOT DUTY P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR


SIZE & TYPE

DOOR INTERLOCK 4.8 11.0

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 5.7 13.2
BLOCK

30 AMP BLOCK
FUSE

2.8 6.6

60 AMP BLOCK 5.7 13.2

1. MAX. K.W. BASED ON 48A, OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.008 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5E030

REV.1 5/6/00 PNEUMATIC


PSFH029
- J29 -

38 YORK INTERNATIONAL
FORM AD1T-SECT J

SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT


PRESS. INDEPENDENT, N.C. DAMPER, A.F.S. FAN START, UNOCCUPIED MODE, REVERSE ACTING STAT, 1 PHASE, PILOT DUTY P.E. SWITCH

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V OCCUPIED MODE:
DISCONNECT WHEN THE DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
SWITCH SENSED BY THE S1 AIR FLOW SWITCH, THE FAN MOTOR
IS ENERGIZED.
SPACE TEMP WARM (STAT OUTPUT LOW). AT A STAT
FUSING OUTPUT OF 3 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
OPTIONAL DISCONNECT SWITCH
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
AND OR FUSING
PANEL WIRING DIAGRAM CONTROLLING AT ITS MINIMUM.
ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
L1 (N) = 120V & 277V ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
TERMINAL 1 2
BLOCK AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
BK WH
UNOCCUPIED MODE:
WHEN MAIN AIR HANDLER IS OFF, THE S1 AIR FLOW SWITCH
BK BK WH DEENERGIZES THE FAN. AS TEMP DROPS PE1 ENERGIZES
STANDARD 1 ST. HEAT THE FAN.
C1-1 G
RD RD
ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
OPTIONAL 2 ST. HEAT JOB SPECIFICATIONS.
C2-1
BN BN
C N0 BK OPTIONAL 3 ST. HEAT
C3-1
TC C NO ST.1
BK BK BK
S1 5 C1 NOTE: S1 AIRFLOW SWITCH FACTORY SET TO START FAN AT
NC .10"WC TOTAL PRESSURE SENSED AT INLET FLOW PROBE.
C PE-2
NO (WHEN REQ.) NC
RD
ST.2
RD C NO RD
PE-1 C2
NC
PE-3
NC
ST.3
BN C NO BN
C3
PE-4
NC
BK BL/WH BK
SC FM

N.C. PNEUMATIC DIAGRAM


ACT. RECOMMENDED FIELD P.E. SWITCH SETTINGS:

PE-1 = 8 PSI
PE-2 = 8 PSI
BAL. TAPS PE-3 = 10 PSI
VEL. CNTRLR
PE-4 = 12 PSI
B (RESET BAND=3-8 PSI)
FLOW LO X
M 20 PSI MAIN CONSTANT
PROBE HI Y
T VOLUME
TOTAL AIR
R.A.. STAT HEAT
FLOW

COLD AIR
S1 1 PIPE AIR (UNOCCUPIED)
AIR

FLOW PLENUM AIR


RESTRICTOR FAN STARTS
OR OR 20 PSI MAIN (FIELD CALIB.)

R.A.. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE4 PE3 PE2 PE1 2 PIPE HOT T-STAT BRANCH PRESSURE (PSIG) COLD
ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE 2 = PILOT DUTY P.E. W/ 30A
1 3.6 8.3 E = 120V/1PH/60HZ - 2 STAGE MAG. CONTACTOR
DE-ENERGIZING
CONTACTOR

30 AMP 2 2.8 6.6 5 = 120V/1PH/60HZ - 3 STAGE 3 = PILOT DUTY P.E. W/ 50A


CONTACTOR 3 1.9 4.4
K = 277V/1PH/60HZ - 1 STAGE MAG. CONTACTOR
1 5.7 13.2
50 AMP L = 277V/1PH/60HZ - 2 STAGE 4 = PILOT DUTY P.E. W/ 30A
2 2.8 6.6 MERC. CONTACTOR
CONTACTOR Y = 277V/1PH/60HZ - 3 STAGE
3 1.9 4.4
5 = PILOT DUTY P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR


SIZE & TYPE

DOOR INTERLOCK 4.8 11.0

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 5.7 13.2
BLOCK

30 AMP BLOCK
FUSE

2.8 6.6

60 AMP BLOCK 5.7 13.2

1. MAX. K.W. BASED ON 48A, OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.008 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5F030

REV.1 5/14/00 PNEUMATIC


PSFH030
- J30 -

YORK INTERNATIONAL 39
SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT
PRESS. INDEPENDENT, N.O. DAMPER, A.F.S. FAN START, UNOCCUPIED MODE, REVERSE ACTING STAT, 1 PHASE, PILOT DUTY P.E. SWITCH

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V
OCCUPIED MODE:
DISCONNECT WHEN THE DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
SWITCH SENSED BY THE S1 AIR FLOW SWITCH, THE FAN MOTOR
IS ENERGIZED.
FUSING SPACE TEMP WARM (STAT OUTPUT LOW). AT A STAT
OUTPUT OF 3 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
OPTIONAL DISCONNECT SWITCH WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
AND OR FUSING STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
PANEL WIRING DIAGRAM CONTROLLING AT ITS MINIMUM.
ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
L1 (N) = 120V & 277V
ENERGIZING THE FIRST STAGE OF ELELCTRIC HEAT.
TERMINAL 1 2
BLOCK AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
BK WH
UNOCCUPIED MODE:
WHEN MAIN AIR HANDLER IS OFF, THE S1 AIR FLOW SWITCH
BK BK WH
DEENERGIZES THE FAN. AS TEMP DROPS PE1 ENERGIZES
C1-1 STANDARD 1 ST. HEAT THE FAN.
G
RD RD

OPTIONAL 2 ST. HEAT ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY


C2-1 JOB SPECIFICATIONS.
BN BN
C N0 BK OPTIONAL 3 ST. HEAT
C3-1
TC C NO ST.1
BK BK BK
S1 5 C1
NC NOTE: S1 AIRFLOW SWITCH FACTORY SET TO START FAN AT
PE-2 .10"WC TOTAL PRESSURE SENSED AT INLET FLOW PROBE.
C NO NC
(WHEN REQ.) ST.2
RD
RD C NO RD
PE-1 C2
NC
PE-3
NC
ST.3
BN C NO BN
C3
PE-4
NC
BK BL/WH BK
SC FM

N.O. PNEUMATIC DIAGRAM


ACT. RECOMMENDED FIELD P.E. SWITCH SETTINGS:

PE-1 = 8 PSI
PE-2 = 8 PSI
BAL. TAPS VEL. CNTRLR PE-3 = 10 PSI
B (RESET BAND=8-13 PSI) PE-4 = 12 PSI
FLOW LO Y
M 20 PSI MAIN
PROBE HI X CONSTANT
T
VOLUME
TOTAL AIR
REV. R.A.. STAT
FLOW

S1 RELAY 1 PIPE COLD AIR HEAT


AIR

AIR (UNOCCUPIED)
M RESTRICTOR FLOW PLENUM AIR
1 FAN STARTS
3 OR OR 20 PSI MAIN
(FIELD CALIB.)

R.A.. STAT
2 PIPE 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE4 PE3 PE2 PE1 HOT T-STAT BRANCH PRESSURE (PSIG) COLD
ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE 2 = PILOT DUTY P.E. W/ 30A
1 3.6 8.3 E = 120V/1PH/60HZ - 2 STAGE MAG. CONTACTOR
DE-ENERGIZING
CONTACTOR

30 AMP 2 2.8 6.6 5 = 120V/1PH/60HZ - 3 STAGE 3 = PILOT DUTY P.E. W/ 50A


CONTACTOR 3 1.9 4.4
K = 277V/1PH/60HZ - 1 STAGE MAG. CONTACTOR
1 5.7 13.2
50 AMP L = 277V/1PH/60HZ - 2 STAGE 4 = PILOT DUTY P.E. W/ 30A
2 2.8 6.6 MERC. CONTACTOR
CONTACTOR Y = 277V/1PH/60HZ - 3 STAGE
3 1.9 4.4
5 = PILOT DUTY P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR


SIZE & TYPE

DOOR INTERLOCK 4.8 11.0

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 5.7 13.2
BLOCK

30 AMP BLOCK
FUSE

2.8 6.6

60 AMP BLOCK 5.7 13.2

1. MAX. K.W. BASED ON 48A, OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.016 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5G030

REV.1 5/14/00 PNEUMATIC


PSFH031
- J31 -

40 YORK INTERNATIONAL
FORM AD1T-SECT J

SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT


PRESS. INDEPENDENT, N.C. DAMPER, A.F.S. FAN START, UNOCCUPIED MODE, DIRECT ACTING STAT, 1 PHASE, PILOT DUTY P.E. SWITCH

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V OCCUPIED MODE:
DISCONNECT WHEN THE DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
SWITCH SENSED BY THE S1 AIR FLOW SWITCH, THE FAN MOTOR
IS ENERGIZED.
SPACE TEMP WARM (STAT OUTPUT HI). AT A STAT
FUSING OUTPUT OF 13 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
OPTIONAL DISCONNECT SWITCH
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
AND OR FUSING
PANEL WIRING DIAGRAM CONTROLLING AT ITS MINIMUM.
ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
L1 (N) = 120V & 277V ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
TERMINAL 1 2
BLOCK AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
BK WH
UNOCCUPIED MODE:
WHEN MAIN AIR HANDLER IS OFF, THE S1 AIR FLOW SWITCH
BK BK WH DEENERGIZES THE FAN. AS TEMP DROPS PE1 ENERGIZES
STANDARD 1 ST. HEAT THE FAN.
C1-1 G
RD RD
ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
OPTIONAL 2 ST. HEAT JOB SPECIFICATIONS.
C2-1
BN BN
C N0 BK OPTIONAL 3 ST. HEAT
C3-1
TC C NO ST.1
BK BK BK
S1 5 C1 NOTE: S1 AIRFLOW SWITCH FACTORY SET TO START FAN AT
NC .10"WC TOTAL PRESSURE SENSED AT INLET FLOW PROBE.
C PE-2
NO (WHEN REQ.) NC
RD
ST.2
RD C NO RD
PE-1 C2
NC
PE-3
NC
ST.3
BN C NO BN
C3
PE-4
NC
BK BL/WH BK
SC FM

N.C. PNEUMATIC DIAGRAM


ACT.
RECOMMENDED FIELD P.E. SWITCH SETTINGS:

PE-1 = 8 PSI
PE-2 = 8 PSI
BAL. TAPS VEL. CNTRLR PE-3 = 6 PSI
B (RESET BAND=3-8 PSI)
PE-4 = 4 PSI
FLOW LO X
M 20 PSI MAIN
PROBE HI Y CONSTANT
T
VOLUME
REV. D.A.. STAT TOTAL AIR
FLOW

S1 RELAY 1 PIPE HEAT COLD AIR


AIR

AIR
M (UNOCCUPIED)
1 RESTRICTOR FLOW PLENUM AIR
3 OR OR 20 PSI MAIN FAN STARTS
(FIELD CALIB.)

D.A.. STAT
2 PIPE 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE2 PE1 COLD T-STAT BRANCH PRESSURE (PSIG) HOT
PE4 PE3
ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE 2 = PILOT DUTY P.E. W/ 30A
1 3.6 8.3 E = 120V/1PH/60HZ - 2 STAGE MAG. CONTACTOR
DE-ENERGIZING
CONTACTOR

30 AMP 2 2.8 6.6 5 = 120V/1PH/60HZ - 3 STAGE 3 = PILOT DUTY P.E. W/ 50A


CONTACTOR 3 1.9 4.4
K = 277V/1PH/60HZ - 1 STAGE MAG. CONTACTOR
1 5.7 13.2
50 AMP L = 277V/1PH/60HZ - 2 STAGE 4 = PILOT DUTY P.E. W/ 30A
2 2.8 6.6 MERC. CONTACTOR
CONTACTOR Y = 277V/1PH/60HZ - 3 STAGE
3 1.9 4.4
5 = PILOT DUTY P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR


SIZE & TYPE

DOOR INTERLOCK 4.8 11.0

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 5.7 13.2
BLOCK

30 AMP BLOCK
FUSE

2.8 6.6

60 AMP BLOCK 5.7 13.2

1. MAX. K.W. BASED ON 48A, OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.016 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5H030

REV.1 5/14/00 PNEUMATIC


PSFH032
- J32 -

YORK INTERNATIONAL 41
SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT
PRESS. INDEPENDENT, N.O. DAMPER, A.F.S. FAN START, UNOCCUPIED MODE, DIRECT ACTING STAT, 3 PHASE, LOAD BEARING P.E. SWITCH W/ CONT. INTRLK.

SEQUENCE OF OPERATION:
L1 L2 L3 OCCUPIED MODE:
DISCONNECT WHEN THE DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
SWITCH SENSED BY THE S1 AIR FLOW SWITCH, THE FAN MOTOR
IS ENERGIZED.
SPACE TEMP WARM (STAT OUTPUT HI). AT A STAT
FUSING OUTPUT OF 13 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
OPTIONAL DISCONNECT SWITCH STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
PANEL WIRING DIAGRAM AND OR FUSING CONTROLLING AT ITS MINIMUM.
ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
L1 L2 L3 N ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
TERMINAL 1 2 3 4
BLOCK AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
BK WH

BK BL
UNOCCUPIED MODE:
WHEN MAIN AIR HANDLER IS OFF, THE S1 AIR FLOW SWITCH
BK
DEENERGIZES THE FAN. AS TEMP DROPS PE1 ENERGIZES
STANDARD 1 STAGE HEAT THE FAN.
C1-1 G
BK BK
ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
C1-2 JOB SPECIFICATIONS.
C N0 BK

BK
TC BK C NO BK
S1 5 C1
NC NOTE: S1 AIRFLOW SWITCH FACTORY SET TO START FAN AT
PE-2 .10"WC TOTAL PRESSURE SENSED AT INLET FLOW PROBE.
C NO NC
RD BK BL/WH BK
PE-1 SC FM
NC

BK BK
L1 1
C1-1
RD
C NO
L2 2
RD
PE-3
NC
L1 1
BK BK
BN C NO BN

C NO C1-1 BL
L2 2
RD 3 L3 PE-4
RD RD
NC
PE-3 BL BL
NC L3 3
C1-2 C1-2

N.O. PNEUMATIC DIAGRAM OPTIONAL 2 STAGE HEAT OPTIONAL 3 STAGE HEAT

ACT. RECOMMENDED FIELD P.E. SWITCH SETTINGS:

PE-1 = 8 PSI
PE-2 = 8 PSI
BAL. TAPS VEL. CNTRLR PE-3 = 6 PSI
B (RESET BAND=8-13 PSI) PE-4 = 4 PSI
FLOW LO Y CONSTANT
M 20 PSI MAIN
PROBE HI X VOLUME
T TOTAL AIR
D.A.. STAT HEAT COLD AIR
FLOW

S1 1 PIPE AIR
(UNOCCUPIED)
AIR

FLOW PLENUM AIR


FAN STARTS
RESTRICTOR
OR OR 20 PSI MAIN (FIELD CALIB.)

D.A.. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE4 PE3 PE2 PE1 2 PIPE COLD T-STAT BRANCH PRESSURE (PSIG) HOT
ROOM ROOM

HEATER COMPONENTS MAX. KW


3 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-3 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 208 V 480 V P = 208V/3PH/60HZ - 1 STAGE J = LOAD BEARING P.E. W/ 30A
1 10.7 24.9 R = 208V/3PH/60HZ - 2 STAGE MAG. CONTACTOR INTERLOCK
30 AMP CONT.
LOAD BRG. PE

2 4.4 9.1 1 = 208V/3PH/60HZ - 3 STAGE K = LOAD BEARING P.E. W/ 50A


W/ INTRLK

PER STAGE 3 2.9 6.0


U = 480V/3PH/60HZ - 1 STAGE MAG. CONTACTOR INTERLOCK
1 17.2 39.8
50 AMP CONT. W = 480V/3PH/60HZ - 2 STAGE L = LOAD BEARING P.E. W/ 30A
2 4.4 9.1 MERC. CONTACTOR INTERLOCK
PER STAGE 3 = 480V/3PH/60HZ - 3 STAGE
3 2.9 6.0
M = LOAD BEARING P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR INTERLOCK


SIZE & TYPE

DOOR INTERLOCK 14.3 33.2

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 17.2 39.8
BLOCK

30 AMP BLOCK
FUSE

8.6 19.9

60 AMP BLOCK 17.2 39.8

1. MAX. K.W. BASED ON 48A, P.E., OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.016 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5E030

REV.1 5/14/00 PNEUMATIC


PSFH033
- J33 -

42 YORK INTERNATIONAL
FORM AD1T-SECT J

SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT


PRESS. INDEPENDENT, N.C. DAMPER, A.F.S. FAN START, UNOCCUPIED MODE, REVERSE ACTING STAT, 3 PHASE, LOAD BEARING P.E. SWITCH W/ CONT. INTRLK.

SEQUENCE OF OPERATION:
L1 L2 L3 OCCUPIED MODE:
DISCONNECT WHEN THE DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
SWITCH SENSED BY THE S1 AIR FLOW SWITCH, THE FAN MOTOR
IS ENERGIZED.
SPACE TEMP WARM (STAT OUTPUT LOW). AT A STAT
FUSING OUTPUT OF 3 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
OPTIONAL DISCONNECT SWITCH STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
PANEL WIRING DIAGRAM AND OR FUSING CONTROLLING AT ITS MINIMUM.
ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
L1 L2 L3 N ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
TERMINAL 1 2 3 4
BLOCK AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
BK WH

BK BL
UNOCCUPIED MODE:
WHEN MAIN AIR HANDLER IS OFF, THE S1 AIR FLOW SWITCH
BK
DEENERGIZES THE FAN. AS TEMP DROPS PE1 ENERGIZES
STANDARD 1 STAGE HEAT THE FAN.
C1-1 G
BK BK
ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
C1-2 JOB SPECIFICATIONS.
C N0 BK

BK
TC BK C NO BK
S1 5 C1
NC NOTE: S1 AIRFLOW SWITCH FACTORY SET TO START FAN AT
PE-2 .10"WC TOTAL PRESSURE SENSED AT INLET FLOW PROBE.
C NO NC
RD BK BL/WH BK
PE-1 SC FM
NC

BK BK
L1 1
C1-1
RD
C NO
L2 2 RD

PE-3
NC
L1 1
BK BK
BN C NO BN

C NO C1-1 BL
L2 2
RD 3 L3 PE-4
RD NC
RD BL BL
PE-3
NC L3 3
C1-2 C1-2

N.C. PNEUMATIC DIAGRAM OPTIONAL 2 STAGE HEAT OPTIONAL 3 STAGE HEAT

ACT. RECOMMENDED FIELD P.E. SWITCH SETTINGS:

PE-1 = 8 PSI
PE-2 = 8 PSI
BAL. TAPS PE-3 = 10 PSI
VEL. CNTRLR
PE-4 = 12 PSI
B (RESET BAND=3-8 PSI)
FLOW LO X
M 20 PSI MAIN CONSTANT
PROBE HI Y
T VOLUME
TOTAL AIR
R.A.. STAT HEAT
FLOW

COLD AIR
S1 1 PIPE AIR (UNOCCUPIED)
AIR

FLOW PLENUM AIR


RESTRICTOR FAN STARTS
OR OR 20 PSI MAIN (FIELD CALIB.)

R.A.. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE4 PE3 PE2 PE1 2 PIPE HOT T-STAT BRANCH PRESSURE (PSIG) COLD
ROOM ROOM

HEATER COMPONENTS MAX. KW


3 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-3 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 208 V 480 V P = 208V/3PH/60HZ - 1 STAGE J = LOAD BEARING P.E. W/ 30A
1 10.7 24.9 R = 208V/3PH/60HZ - 2 STAGE MAG. CONTACTOR INTERLOCK
30 AMP CONT.
LOAD BRG. PE

2 4.4 9.1 1 = 208V/3PH/60HZ - 3 STAGE K = LOAD BEARING P.E. W/ 50A


W/ INTRLK

PER STAGE 3 2.9 6.0


U = 480V/3PH/60HZ - 1 STAGE MAG. CONTACTOR INTERLOCK
1 17.2 39.8
50 AMP CONT. W = 480V/3PH/60HZ - 2 STAGE L = LOAD BEARING P.E. W/ 30A
2 4.4 9.1 MERC. CONTACTOR INTERLOCK
PER STAGE 3 = 480V/3PH/60HZ - 3 STAGE
3 2.9 6.0
M = LOAD BEARING P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR INTERLOCK


SIZE & TYPE

DOOR INTERLOCK 14.3 33.2

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 17.2 39.8
BLOCK

30 AMP BLOCK
FUSE

8.6 19.9

60 AMP BLOCK 17.2 39.8

1. MAX. K.W. BASED ON 48A, P.E., OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.008 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5F030

REV.1 5/14/00 PNEUMATIC


PSFH034
- J34 -

YORK INTERNATIONAL 43
SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT
PRESS. INDEPENDENT, N.O. DAMPER, A.F.S. FAN START, UNOCCUPIED MODE, REVERSE ACTING STAT, 3 PHASE, LOAD BEARING P.E. SWITCH W/ CONT. INTRLK.

SEQUENCE OF OPERATION:
L1 L2 L3 OCCUPIED MODE:
DISCONNECT WHEN THE DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
SWITCH SENSED BY THE S1 AIR FLOW SWITCH, THE FAN MOTOR
IS ENERGIZED.
SPACE TEMP WARM (STAT OUTPUT LOW). AT A STAT
FUSING OUTPUT OF 3 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
OPTIONAL DISCONNECT SWITCH STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
PANEL WIRING DIAGRAM AND OR FUSING CONTROLLING AT ITS MINIMUM.
L1 L2 L3 N ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
ENERGIZING THE FIRST STAGE OF ELELCTRIC HEAT.
TERMINAL 1 2 3 4
BLOCK AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
BK WH

BK BL UNOCCUPIED MODE:
WHEN MAIN AIR HANDLER IS OFF, THE S1 AIR FLOW SWITCH
BK STANDARD 1 STAGE HEAT DEENERGIZES THE FAN. AS TEMP DROPS PE1 ENERGIZES
THE FAN.
C1-1 G
BK BK
ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
C1-2 JOB SPECIFICATIONS.
C N0 BK

BK
TC BK C NO BK
S1 5 C1
NC NOTE: S1 AIRFLOW SWITCH FACTORY SET TO START FAN AT
C PE-2 .10"WC TOTAL PRESSURE SENSED AT INLET FLOW PROBE.
NO NC
RD BK BL/WH BK
PE-1 SC FM
NC

BK BK
L1 1
C1-1
RD
C NO
L2 2 RD

PE-3
NC
L1 1
BK BK
BN C NO BN

C NO C1-1 BL
L2 2
RD 3 L3 PE-4
RD NC
RD BL BL
PE-3
NC L3 3
C1-2 C1-2
N.O. PNEUMATIC DIAGRAM OPTIONAL 2 STAGE HEAT OPTIONAL 3 STAGE HEAT
ACT. RECOMMENDED FIELD P.E. SWITCH SETTINGS:

PE-1 = 8 PSI
PE-2 = 8 PSI
BAL. TAPS VEL. CNTRLR PE-3 = 10 PSI
B (RESET BAND=8-13 PSI) PE-4 = 12 PSI
FLOW LO Y
M 20 PSI MAIN
PROBE HI X CONSTANT
T
VOLUME
TOTAL AIR
REV. R.A.. STAT
FLOW

S1 RELAY 1 PIPE COLD AIR HEAT


AIR

AIR (UNOCCUPIED)
M RESTRICTOR FLOW PLENUM AIR
1 FAN STARTS
3 OR OR 20 PSI MAIN
(FIELD CALIB.)

R.A.. STAT
2 PIPE 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE4 PE3 PE2 PE1 HOT T-STAT BRANCH PRESSURE (PSIG) COLD
ROOM ROOM

HEATER COMPONENTS MAX. KW


3 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-3 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 208 V 480 V P = 208V/3PH/60HZ - 1 STAGE J = LOAD BEARING P.E. W/ 30A
1 10.7 24.9 R = 208V/3PH/60HZ - 2 STAGE MAG. CONTACTOR INTERLOCK
30 AMP CONT.
LOAD BRG. PE

2 4.4 9.1 1 = 208V/3PH/60HZ - 3 STAGE K = LOAD BEARING P.E. W/ 50A


W/ INTRLK

PER STAGE 3 2.9 6.0


U = 480V/3PH/60HZ - 1 STAGE MAG. CONTACTOR INTERLOCK
1 17.2 39.8
50 AMP CONT. W = 480V/3PH/60HZ - 2 STAGE L = LOAD BEARING P.E. W/ 30A
2 4.4 9.1 MERC. CONTACTOR INTERLOCK
PER STAGE 3 = 480V/3PH/60HZ - 3 STAGE
3 2.9 6.0
M = LOAD BEARING P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR INTERLOCK


SIZE & TYPE

DOOR INTERLOCK 14.3 33.2

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 17.2 39.8
BLOCK

30 AMP BLOCK
FUSE

8.6 19.9

60 AMP BLOCK 17.2 39.8

1. MAX. K.W. BASED ON 48A, P.E., OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.016 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5G030

REV.1 5/14/00 PNEUMATIC


PSFH035
- J35 -

44 YORK INTERNATIONAL
FORM AD1T-SECT J

SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT


PRESS. INDEPENDENT, N.C. DAMPER, A.F.S. FAN START, UNOCCUPIED MODE, DIRECT ACTING STAT, 3 PHASE, LOAD BEARING P.E. SWITCH W/ CONT. INTRLK.

SEQUENCE OF OPERATION:
L1 L2 L3 OCCUPIED MODE:
DISCONNECT WHEN THE DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
SWITCH SENSED BY THE S1 AIR FLOW SWITCH, THE FAN MOTOR
IS ENERGIZED.
SPACE TEMP WARM (STAT OUTPUT HI). AT A STAT
FUSING OUTPUT OF 13 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
OPTIONAL DISCONNECT SWITCH STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
PANEL WIRING DIAGRAM AND OR FUSING CONTROLLING AT ITS MINIMUM.
ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
L1 L2 L3 N ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
TERMINAL 1 2 3 4
BLOCK AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
BK WH

BK BL
UNOCCUPIED MODE:
WHEN MAIN AIR HANDLER IS OFF, THE S1 AIR FLOW SWITCH
BK
DEENERGIZES THE FAN. AS TEMP DROPS PE1 ENERGIZES
STANDARD 1 STAGE HEAT THE FAN.
C1-1 G
BK BK
ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
C1-2 JOB SPECIFICATIONS.
C N0 BK

BK
TC BK C NO BK
S1 5 C1
NC NOTE: S1 AIRFLOW SWITCH FACTORY SET TO START FAN AT
PE-2 .10"WC TOTAL PRESSURE SENSED AT INLET FLOW PROBE.
C NO NC
RD BK BL/WH BK
PE-1 SC FM
NC

BK BK
L1 1
C1-1
RD
C NO
L2 2
RD
PE-3
NC
L1 1
BK BK
BN C NO BN

C NO C1-1 BL
L2 2
RD 3 L3 PE-4
RD RD
NC
PE-3 BL BL
NC L3 3
C1-2 C1-2
N.C. PNEUMATIC DIAGRAM
OPTIONAL 2 STAGE HEAT OPTIONAL 3 STAGE HEAT
ACT.
RECOMMENDED FIELD P.E. SWITCH SETTINGS:

PE-1 = 8 PSI
PE-2 = 8 PSI
BAL. TAPS VEL. CNTRLR PE-3 = 6 PSI
B (RESET BAND=3-8 PSI)
PE-4 = 4 PSI
FLOW LO X
M 20 PSI MAIN
PROBE HI Y CONSTANT
T
VOLUME
REV. D.A.. STAT TOTAL AIR
FLOW

S1 RELAY 1 PIPE HEAT COLD AIR


AIR

AIR
M (UNOCCUPIED)
1 RESTRICTOR FLOW PLENUM AIR
3 OR OR 20 PSI MAIN FAN STARTS
(FIELD CALIB.)

D.A.. STAT
2 PIPE 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE2 PE1 COLD T-STAT BRANCH PRESSURE (PSIG) HOT
PE4 PE3
ROOM ROOM

HEATER COMPONENTS MAX. KW


3 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-3 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 208 V 480 V P = 208V/3PH/60HZ - 1 STAGE J = LOAD BEARING P.E. W/ 30A
1 10.7 24.9 R = 208V/3PH/60HZ - 2 STAGE MAG. CONTACTOR INTERLOCK
30 AMP CONT.
LOAD BRG. PE

2 4.4 9.1 1 = 208V/3PH/60HZ - 3 STAGE K = LOAD BEARING P.E. W/ 50A


W/ INTRLK

PER STAGE 3 2.9 6.0


U = 480V/3PH/60HZ - 1 STAGE MAG. CONTACTOR INTERLOCK
1 17.2 39.8
50 AMP CONT. W = 480V/3PH/60HZ - 2 STAGE L = LOAD BEARING P.E. W/ 30A
2 4.4 9.1 MERC. CONTACTOR INTERLOCK
PER STAGE 3 = 480V/3PH/60HZ - 3 STAGE
3 2.9 6.0
M = LOAD BEARING P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR INTERLOCK


SIZE & TYPE

DOOR INTERLOCK 14.3 33.2

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 17.2 39.8
BLOCK

30 AMP BLOCK
FUSE

8.6 19.9

60 AMP BLOCK 17.2 39.8

1. MAX. K.W. BASED ON 48A, P.E., OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.018 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5H030

REV.1 5/14/00 PNEUMATIC


PSFH036
- J36 -

YORK INTERNATIONAL 45
SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT
PRESS. INDEPENDENT, N.O. DAMPER, A.F.S. FAN START, UNOCCUPIED MODE, DIRECT ACTING STAT, 3 PHASE, PILOT DUTY P.E. SWITCH

SEQUENCE OF OPERATION:
L1 L2 L3 OCCUPIED MODE:
DISCONNECT WHEN THE DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
SWITCH SENSED BY THE S1 AIR FLOW SWITCH, THE FAN MOTOR
IS ENERGIZED.
SPACE TEMP WARM (STAT OUTPUT HI). AT A STAT
FUSING OUTPUT OF 13 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
OPTIONAL DISCONNECT SWITCH STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
PANEL WIRING DIAGRAM AND OR FUSING CONTROLLING AT ITS MINIMUM.
ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
L1 L2 L3 N ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
TERMINAL 1 2 3 4
BLOCK AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
BK WH

BK BL
UNOCCUPIED MODE:
WHEN MAIN AIR HANDLER IS OFF, THE S1 AIR FLOW SWITCH
BK
DEENERGIZES THE FAN. AS TEMP DROPS PE1 ENERGIZES
STANDARD 1 STAGE HEAT THE FAN.
C1-1 G
BK BK
ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
C1-2 JOB SPECIFICATIONS.
C N0 BK NOTE: S1 AIRFLOW SWITCH FACTORY SET TO START FAN AT
TC ST.1 .10"WC TOTAL PRESSURE SENSED AT INLET FLOW PROBE.
BK BK C NO BK
S1 5 C1
NC
C PE-2
NO NC
ST.2 BK BK
RD RD C NO RD L1 1
PE-1 C2 C1-1 BL
3 L3
NC RD RD
PE-3 L2 2
NC C2-1
ST.3
BN C NO BN
C3 OPTIONAL 2 STAGE HEAT
PE-4
NC BK BK
BK BL/WH BK L1 1
SC FM C1-1
RD RD
L2 2
C2-1
BN BN

C3-1
BL BL
L3 3
C1-2
N.O. PNEUMATIC DIAGRAM OPTIONAL 3 STAGE HEAT
ACT.
RECOMMENDED FIELD P.E. SWITCH SETTINGS:

PE-1 = 8 PSI
PE-2 = 8 PSI
BAL. TAPS VEL. CNTRLR
PE-3 = 6 PSI
B (RESET BAND=8-13 PSI)
Y PE-4 = 4 PSI
FLOW LO M 20 PSI MAIN
PROBE HI X CONSTANT
T VOLUME
TOTAL AIR
D.A.. STAT
FLOW

S1 1 PIPE HEAT COLD AIR


AIR

AIR
(UNOCCUPIED)
RESTRICTOR FLOW PLENUM AIR
FAN STARTS
OR OR 20 PSI MAIN (FIELD CALIB.)

D.A.. STAT
PE4 PE3 PE2 PE1 2 PIPE 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
COLD T-STAT BRANCH PRESSURE (PSIG) HOT
ROOM ROOM

HEATER COMPONENTS MAX. KW


3 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-3 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 208 V 480 V P = 208V/3PH/60HZ - 1 STAGE 2 = PILOT DUTY P.E. W/ 30A
1 10.7 24.9 R = 208V/3PH/60HZ - 2 STAGE MAG. CONTACTOR
DE-ENERGIZING
CONTACTOR

30 AMP 2 5.3 12.4 1 = 208V/3PH/60HZ - 3 STAGE 3 = PILOT DUTY P.E. W/ 50A


PER STAGE 3 3.5 8.3
U = 480V/3PH/60HZ - 1 STAGE MAG. CONTACTOR
1 17.2 39.8
50 AMP W = 480V/3PH/60HZ - 2 STAGE 4 = PILOT DUTY P.E. W/ 30A
2 8.6 19.9 MERC. CONTACTOR
PER STAGE 3 = 480V/3PH/60HZ - 3 STAGE
3 5.7 13.2
5 = PILOT DUTY P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR


SIZE & TYPE

DOOR INTERLOCK 14.3 33.2

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 17.2 39.8
BLOCK

30 AMP BLOCK 8.6 19.9


FUSE

60 AMP BLOCK 17.2 39.8

1. MAX. K.W. BASED ON 48A, OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.008 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5E030

REV.1 5/14/00 PNEUMATIC


PSFH037
- J37 -

46 YORK INTERNATIONAL
FORM AD1T-SECT J

SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT


PRESS. INDEPENDENT, N.C. DAMPER, A.F.S. FAN START, UNOCCUPIED MODE, REVERSE ACTING STAT, 3 PHASE, PILOT DUTY P.E. SWITCH

SEQUENCE OF OPERATION:
L1 L2 L3 OCCUPIED MODE:
DISCONNECT WHEN THE DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
SWITCH SENSED BY THE S1 AIR FLOW SWITCH, THE FAN MOTOR
IS ENERGIZED.
SPACE TEMP WARM (STAT OUTPUT LOW). AT A STAT
FUSING OUTPUT OF 3 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
OPTIONAL DISCONNECT SWITCH STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
PANEL WIRING DIAGRAM AND OR FUSING CONTROLLING AT ITS MINIMUM.
ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
L1 L2 L3 N ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
TERMINAL 1 2 3 4
BLOCK AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
BK WH

BK BL
UNOCCUPIED MODE:
WHEN MAIN AIR HANDLER IS OFF, THE S1 AIR FLOW SWITCH
BK
DEENERGIZES THE FAN. AS TEMP DROPS PE1 ENERGIZES
STANDARD 1 STAGE HEAT THE FAN.
C1-1 G
BK BK
ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
C1-2 JOB SPECIFICATIONS.
C N0 BK
NOTE: S1 AIRFLOW SWITCH FACTORY SET TO START FAN AT
TC C NO ST.1 .10"WC TOTAL PRESSURE SENSED AT INLET FLOW PROBE.
BK BK BK
S1 5 C1
NC
C PE-2
NO NC
RD
ST.2 BK BK
RD C NO RD L1 1
PE-1 C2 C1-1 BL
3 L3
NC RD RD
PE-3 L2 2
NC C2-1
ST.3
BN C NO BN
C3 OPTIONAL 2 STAGE HEAT
PE-4
NC
BK BL/WH BK BK BK
SC FM L1 1
C1-1
RD RD
L2 2
C2-1
BN BN

C3-1
BL BL
L3 3
C1-2
N.C. PNEUMATIC DIAGRAM
OPTIONAL 3 STAGE HEAT
ACT.
RECOMMENDED FIELD P.E. SWITCH SETTINGS:

PE-1 = 8 PSI
PE-2 = 8 PSI
BAL. TAPS VEL. CNTRLR PE-3 = 10 PSI
B (RESET BAND=3-8 PSI) PE-4 = 12 PSI
FLOW LO X
M 20 PSI MAIN
PROBE HI Y CONSTANT
T VOLUME
TOTAL AIR
R.A.. STAT
FLOW

1 PIPE COLD AIR HEAT


S1
AIR

AIR (UNOCCUPIED)
RESTRICTOR FLOW PLENUM AIR
FAN STARTS
OR OR 20 PSI MAIN (FIELD CALIB.)

R.A.. STAT
PE2 2 PIPE 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE4 PE3 PE1
HOT T-STAT BRANCH PRESSURE (PSIG) COLD
ROOM ROOM

HEATER COMPONENTS MAX. KW


3 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-3 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 208 V 480 V P = 208V/3PH/60HZ - 1 STAGE 2 = PILOT DUTY P.E. W/ 30A
1 10.7 24.9 R = 208V/3PH/60HZ - 2 STAGE MAG. CONTACTOR
DE-ENERGIZING
CONTACTOR

30 AMP 2 5.3 12.4 1 = 208V/3PH/60HZ - 3 STAGE 3 = PILOT DUTY P.E. W/ 50A


PER STAGE 3 3.5 8.3
U = 480V/3PH/60HZ - 1 STAGE MAG. CONTACTOR
1 17.2 39.8
50 AMP W = 480V/3PH/60HZ - 2 STAGE 4 = PILOT DUTY P.E. W/ 30A
2 8.6 19.9 MERC. CONTACTOR
PER STAGE 3 = 480V/3PH/60HZ - 3 STAGE
3 5.7 13.2
5 = PILOT DUTY P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR


SIZE & TYPE

DOOR INTERLOCK 14.3 33.2

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 17.2 39.8
BLOCK

30 AMP BLOCK 8.6 19.9


FUSE

60 AMP BLOCK 17.2 39.8

1. MAX. K.W. BASED ON 48A, OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.008 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5F030

REV.1 5/14/00 PNEUMATIC


PSFH038
- J38 -

YORK INTERNATIONAL 47
SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT
PRESS. INDEPENDENT, N.O. DAMPER, A.F.S. FAN START, UNOCCUPIED MODE, REVERSE ACTING STAT, 3 PHASE, PILOT DUTY P.E. SWITCH

SEQUENCE OF OPERATION:
L1 L2 L3 OCCUPIED MODE:
DISCONNECT WHEN THE DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
SWITCH SENSED BY THE S1 AIR FLOW SWITCH, THE FAN MOTOR
IS ENERGIZED.
SPACE TEMP WARM (STAT OUTPUT LOW). AT A STAT
FUSING OUTPUT OF 3 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
OPTIONAL DISCONNECT SWITCH STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
PANEL WIRING DIAGRAM AND OR FUSING CONTROLLING AT ITS MINIMUM.
L1 L2 L3 N ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
ENERGIZING THE FIRST STAGE OF ELELCTRIC HEAT.
TERMINAL 1 2 3 4
BLOCK AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
BK WH

BK BL UNOCCUPIED MODE:
WHEN MAIN AIR HANDLER IS OFF, THE S1 AIR FLOW SWITCH
BK STANDARD 1 STAGE HEAT DEENERGIZES THE FAN. AS TEMP DROPS PE1 ENERGIZES
THE FAN.
C1-1 G
BK BK
ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
C1-2 JOB SPECIFICATIONS.
C N0 BK
NOTE: S1 AIRFLOW SWITCH FACTORY SET TO START FAN AT
TC C NO ST.1 .10"WC TOTAL PRESSURE SENSED AT INLET FLOW PROBE.
BK BK BK
S1 5 C1
NC
C PE-2
NO NC
RD
ST.2
RD C NO RD BK BK
PE-1 C2 L1 1
NC C1-1 BL
3 L3
PE-3 RD RD
NC
ST.3 L2 2
BN C NO BN C2-1
C3
OPTIONAL 2 STAGE HEAT
PE-4
NC
BK BL/WH BK
SC FM L1 1
BK BK

C1-1
RD RD
L2 2
C2-1
BN BN

C3-1
BL BL
L3 3
N.O. PNEUMATIC DIAGRAM C1-2
ACT. OPTIONAL 3 STAGE HEAT
RECOMMENDED FIELD P.E. SWITCH SETTINGS:

PE-1 = 8 PSI
BAL. TAPS VEL. CNTRLR PE-2 = 8 PSI
B (RESET BAND=8-13 PSI) PE-3 = 10 PSI
FLOW LO Y PE-4 = 12 PSI
M 20 PSI MAIN
PROBE HI X
T CONSTANT
REV. R.A.. STAT VOLUME
TOTAL AIR
FLOW

S1 RELAY 1 PIPE
AIR

COLD AIR HEAT


M RESTRICTOR AIR (UNOCCUPIED)
1 FLOW PLENUM AIR
3 OR OR 20 PSI MAIN FAN STARTS
(FIELD CALIB.)
R.A.. STAT
2 PIPE
PE4 PE3 PE2 PE1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
HOT T-STAT BRANCH PRESSURE (PSIG) COLD
ROOM ROOM
HEATER COMPONENTS MAX. KW
3 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-3 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 208 V 480 V P = 208V/3PH/60HZ - 1 STAGE 2 = PILOT DUTY P.E. W/ 30A
1 10.7 24.9 R = 208V/3PH/60HZ - 2 STAGE MAG. CONTACTOR
DE-ENERGIZING
CONTACTOR

30 AMP 2 5.3 12.4 1 = 208V/3PH/60HZ - 3 STAGE 3 = PILOT DUTY P.E. W/ 50A


PER STAGE 3 3.5 8.3
U = 480V/3PH/60HZ - 1 STAGE MAG. CONTACTOR
1 17.2 39.8
50 AMP W = 480V/3PH/60HZ - 2 STAGE 4 = PILOT DUTY P.E. W/ 30A
2 8.6 19.9 MERC. CONTACTOR
PER STAGE 3 = 480V/3PH/60HZ - 3 STAGE
3 5.7 13.2
5 = PILOT DUTY P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR


SIZE & TYPE

DOOR INTERLOCK 14.3 33.2

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 17.2 39.8
BLOCK

30 AMP BLOCK 8.6 19.9


FUSE

60 AMP BLOCK 17.2 39.8

1. MAX. K.W. BASED ON 48A, OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.016 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5G030

REV.1 5/14/00 PNEUMATIC


PSFH039
- J39 -

48 YORK INTERNATIONAL
FORM AD1T-SECT J

SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT


PRESS. INDEPENDENT, N.C. DAMPER, A.F.S. FAN START, UNOCCUPIED MODE, DIRECT ACTING STAT, 3 PHASE, PILOT DUTY P.E. SWITCH

SEQUENCE OF OPERATION:
L1 L2 L3 OCCUPIED MODE:
DISCONNECT WHEN THE DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
SWITCH SENSED BY THE S1 AIR FLOW SWITCH, THE FAN MOTOR
IS ENERGIZED.
SPACE TEMP WARM (STAT OUTPUT HI). AT A STAT
FUSING OUTPUT OF 13 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
OPTIONAL DISCONNECT SWITCH STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
PANEL WIRING DIAGRAM AND OR FUSING CONTROLLING AT ITS MINIMUM.
ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
L1 L2 L3 N ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
TERMINAL 1 2 3 4
BLOCK AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
BK WH

BK BL
UNOCCUPIED MODE:
WHEN MAIN AIR HANDLER IS OFF, THE S1 AIR FLOW SWITCH
BK
DEENERGIZES THE FAN. AS TEMP DROPS PE1 ENERGIZES
STANDARD 1 STAGE HEAT THE FAN.
C1-1 G
BK BK
ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
C1-2 JOB SPECIFICATIONS.
C N0 BK
NOTE: S1 AIRFLOW SWITCH FACTORY SET TO START FAN AT
TC C NO ST.1 .10"WC TOTAL PRESSURE SENSED AT INLET FLOW PROBE.
BK BK BK
S1 5 C1
NC
C PE-2
NO NC BK BK
ST.2 L1 1
RD RD C NO RD C1-1 BL
3 L3
PE-1 C2 RD RD
NC L2 2
PE-3 C2-1
NC
ST.3
BN C NO BN OPTIONAL 2 STAGE HEAT
C3
PE-4
NC BK BK
BK BL/WH BK
L1 1
SC FM C1-1
RD RD
L2 2
C2-1
BN BN

C3-1
BL BL
L3 3
C1-2
N.C. PNEUMATIC DIAGRAM
OPTIONAL 3 STAGE HEAT
ACT.
RECOMMENDED FIELD P.E. SWITCH SETTINGS:

PE-1 = 8 PSI
BAL. TAPS VEL. CNTRLR PE-2 = 8 PSI
B (RESET BAND=3-8 PSI) PE-3 = 6 PSI
FLOW LO X PE-4 = 4 PSI
M 20 PSI MAIN
PROBE HI Y
T CONSTANT
REV. D.A.. STAT VOLUME
TOTAL AIR
FLOW

S1 RELAY 1 PIPE
AIR

HEAT COLD AIR


M RESTRICTOR AIR
1 (UNOCCUPIED)
3 OR OR 20 PSI MAIN FLOW PLENUM AIR
FAN STARTS
(FIELD CALIB.)
D.A.. STAT
2 PIPE
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE4 PE3 PE2 PE1 COLD T-STAT BRANCH PRESSURE (PSIG) HOT
ROOM ROOM

HEATER COMPONENTS MAX. KW


3 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-3 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 208 V 480 V P = 208V/3PH/60HZ - 1 STAGE 2 = PILOT DUTY P.E. W/ 30A
1 10.7 24.9 R = 208V/3PH/60HZ - 2 STAGE MAG. CONTACTOR
DE-ENERGIZING
CONTACTOR

30 AMP 2 5.3 12.4 1 = 208V/3PH/60HZ - 3 STAGE 3 = PILOT DUTY P.E. W/ 50A


PER STAGE 3 3.5 8.3
U = 480V/3PH/60HZ - 1 STAGE MAG. CONTACTOR
1 17.2 39.8
50 AMP W = 480V/3PH/60HZ - 2 STAGE 4 = PILOT DUTY P.E. W/ 30A
2 8.6 19.9 MERC. CONTACTOR
PER STAGE 3 = 480V/3PH/60HZ - 3 STAGE
3 5.7 13.2
5 = PILOT DUTY P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR


SIZE & TYPE

DOOR INTERLOCK 14.3 33.2

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 17.2 39.8
BLOCK

30 AMP BLOCK 8.6 19.9


FUSE

60 AMP BLOCK 17.2 39.8

1. MAX. K.W. BASED ON 48A, OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.016 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5H030

REV.1 5/14/00 PNEUMATIC


PSFH040
- J40 -

YORK INTERNATIONAL 49
SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT
PRESS. INDEPENDENT, N.O. DAMPER, A.F.S. FAN START, POS. DAMPER CLOSE OFF, DIRECT ACTING STAT, 1 PHASE, LOAD BEARING P.E. SWITCH

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V
OCCUPIED MODE:
DISCONNECT WHEN THE DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
SWITCH SENSED BY THE S1 AIR FLOW SWITCH, THE FAN MOTOR
& EP SWITCH ARE ENERGIZED.
FUSING SPACE TEMP WARM (STAT OUTPUT HI). AT A STAT
OUTPUT OF 13 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
OPTIONAL DISCONNECT SWITCH WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
AND OR FUSING STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
PANEL WIRING DIAGRAM CONTROLLING AT ITS MINIMUM.
ON A FURTHER DROP IN SPACE TEMP., PE1 WILL CLOSE
L1 (N) = 120V & 277V ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
TERMINAL 1 2 AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
BLOCK
BK WH
UNOCCUPIED MODE:
C WHEN MAIN AIR HANDLER IS OFF, THE S1 AIR FLOW SWITCH
NO
DEENERGIZES THE FAN & EP SWITCH, CAUSING DAMPER TO
BK C NO BK WH G CLOSE.
S1 5
NC STANDARD 1
PE-1 ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
NC STAGE HEAT JOB SPECIFICATIONS.
RD C NO RD
NOTE: S1 AIRFLOW SWITCH FACTORY SET TO START FAN AT
PE-2 OPTIONAL 2 .10"WC TOTAL PRESSURE SENSED AT INLET FLOW PROBE.
NC STAGE HEAT
BN C NO BN

PE-3 OPTIONAL 3
NC STAGE HEAT

BK BL/WH BK
SC FM

EP

N.O. PNEUMATIC DIAGRAM


ACT. (3)C
(1)NC (2)NO RECOMMENDED FIELD P.E. SWITCH SETTINGS:
EP
PE-1 = 8 PSI
BAL. TAPS VEL. CNTRLR PE-2 = 6 PSI
B (RESET BAND=8-13 PSI) PE-3 = 4 PSI
FLOW LO Y
M 20 PSI MAIN
PROBE HI X
T CONSTANT
D.A.. STAT VOLUME
TOTAL AIR
FLOW

S1 1 PIPE HEAT
AIR

COLD AIR
AIR
RESTRICTOR
OR OR 20 PSI MAIN FLOW PLENUM AIR

D.A.. STAT
2 PIPE
PE2 PE1
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE3
COLD T-STAT BRANCH PRESSURE (PSIG) HOT
ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE 1 = LOAD BEARING P.E.
SWITCH

1 1.6 3.9 E = 120V/1PH/60HZ - 2 STAGE


LOAD BEARING
P.E.

PER STAGE 2 0.8 1.9 5 = 120V/1PH/60HZ - 3 STAGE


3 0.5 1.3
K = 277V/1PH/60HZ - 1 STAGE
DISCONNECT

L = 277V/1PH/60HZ - 2 STAGE
SIZE & TYPE

DNF-40 1.6 3.9 Y = 277V/1PH/60HZ - 3 STAGE


DOOR INTERLOCK
BLOCK
FUSE

30 AMP BLOCK 1.6 3.9

1. MAX. K.W. BASED ON A.F.S. MAX LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.008 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5E0X0

REV.1 5/14/00 PNEUMATIC


PSFH041
- J41 -

50 YORK INTERNATIONAL
FORM AD1T-SECT J

SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT


PRESS. INDEPENDENT, N.C. DAMPER, A.F.S. FAN START, POS. DAMPER CLOSE OFF, REVERSE ACTING STAT, 1 PHASE, LOAD BEARING P.E. SWITCH

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V
DISCONNECT OCCUPIED MODE:
SWITCH WHEN THE DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
SENSED BY THE S1 AIR FLOW SWITCH, THE FAN MOTOR
& EP SWITCH ARE ENERGIZED.
FUSING SPACE TEMP WARM (STAT OUTPUT LOW). AT A STAT
OUTPUT OF 3 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
OPTIONAL DISCONNECT SWITCH WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
AND OR FUSING
PANEL WIRING DIAGRAM STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
ON A FURTHER DROP IN SPACE TEMP., PE1 WILL CLOSE
L1 (N) = 120V & 277V ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
TERMINAL 1 2
BLOCK AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
BK WH
UNOCCUPIED MODE:
C NO WHEN MAIN AIR HANDLER IS OFF, THE S1 AIR FLOW SWITCH
DEENERGIZES THE FAN & EP SWITCH, CAUSING DAMPER TO
BK C NO WH G
S1 5 CLOSE.
NC STANDARD 1
PE-1 ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
NC STAGE HEAT
JOB SPECIFICATIONS.
RD C NO

OPTIONAL 2 NOTE: S1 AIRFLOW SWITCH FACTORY SET TO START FAN AT


PE-2 .10"WC TOTAL PRESSURE SENSED AT INLET FLOW PROBE.
NC STAGE HEAT
BN C NO

PE-3 OPTIONAL 3
NC STAGE HEAT

BK BL/WH BK
SC FM

EP

N.C. PNEUMATIC DIAGRAM


ACT. (3)C RECOMMENDED FIELD P.E. SWITCH SETTINGS:
(1)NC (2)NO
EP PE-1 = 8 PSI
PE-2 = 10 PSI
BAL. TAPS VEL. CNTRLR PE-3 = 12 PSI
B (RESET BAND=3-8 PSI)
FLOW LO X
M 20 PSI MAIN
PROBE HI Y CONSTANT
T
VOLUME
TOTAL AIR
R.A. STAT
FLOW

S1 1 PIPE COLD AIR HEAT


AIR

AIR
RESTRICTOR FLOW PLENUM AIR
OR OR 20 PSI MAIN

R.A. STAT
PE3 PE2 PE1 2 PIPE 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
HOT T-STAT BRANCH PRESSURE (PSIG) COLD
ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE 1 = LOAD BEARING P.E.
SWITCH

1 1.6 3.9 E = 120V/1PH/60HZ - 2 STAGE


LOAD BEARING
P.E.

PER STAGE 2 0.8 1.9 5 = 120V/1PH/60HZ - 3 STAGE


3 0.5 1.3
K = 277V/1PH/60HZ - 1 STAGE
DISCONNECT

L = 277V/1PH/60HZ - 2 STAGE
SIZE & TYPE

DNF-40 1.6 3.9 Y = 277V/1PH/60HZ - 3 STAGE


DOOR INTERLOCK
BLOCK
FUSE

30 AMP BLOCK 1.6 3.9

1. MAX. K.W. BASED ON A.F.S. MAX LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.008 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5F0X0

REV.1 5/14/00 PNEUMATIC


PSFH042
- J42 -

YORK INTERNATIONAL 51
52 YORK INTERNATIONAL
FORM AD1T-SECT J

YORK INTERNATIONAL 53
SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT
P.I., N.O. DAMPER, A.F.S. FAN START, POS. DAMPER CLOSE OFF, D.A. STAT, 1 PHASE, LOAD BEARING P.E. SWITCH W/ CONT. INTRLK.

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V
OCCUPIED MODE:
DISCONNECT WHEN THE DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
SWITCH SENSED BY THE S1 AIR FLOW SWITCH, THE FAN MOTOR
& EP SWITCH ARE ENERGIZED.
FUSING SPACE TEMP WARM (STAT OUTPUT HI). AT A STAT
OUTPUT OF 13 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
OPTIONAL DISCONNECT SWITCH WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
AND OR FUSING STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
PANEL WIRING DIAGRAM CONTROLLING AT ITS MINIMUM.
L1 (N) = 120V & 277V ON A FURTHER DROP IN SPACE TEMP., PE1 WILL CLOSE
ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
TERMINAL 1 2
BLOCK AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
BK WH

UNOCCUPIED MODE:
BK BK WH WHEN MAIN AIR HANDLER IS OFF, THE S1 AIR FLOW SWITCH
DEENERGIZES THE FAN & EP SWITCH, CAUSING DAMPER TO
C1-1 STANDARD 1 G CLOSE.
STAGE HEAT
RD C NO RD ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
JOB SPECIFICATIONS.
PE-2 OPTIONAL 2
NC STAGE HEAT NOTE: S1 AIRFLOW SWITCH FACTORY SET TO START FAN AT
BN C NO BN .10"WC TOTAL PRESSURE SENSED AT INLET FLOW PROBE.

PE-3 OPTIONAL 3
NC STAGE HEAT
(WHEN REQ.)
BK
TC BK C NO BK
C1
PE-1
NC
C N0 BK BL/WH BK
BK
5 SC FM
S1
NC
BK
EP

N.O. PNEUMATIC DIAGRAM


ACT. (3)C
(1)NC (2)NO RECOMMENDED FIELD P.E. SWITCH SETTINGS:
EP
PE-1 = 8 PSI
BAL. TAPS VEL. CNTRLR PE-2 = 6 PSI
B (RESET BAND=8-13 PSI) PE-3 = 4 PSI
FLOW LO Y
M 20 PSI MAIN
PROBE HI X
T CONSTANT
D.A.. STAT VOLUME
TOTAL AIR
FLOW

S1 1 PIPE HEAT
AIR

COLD AIR
AIR
RESTRICTOR
OR OR 20 PSI MAIN FLOW PLENUM AIR

D.A.. STAT
2 PIPE
PE2 PE1
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE3
COLD T-STAT BRANCH PRESSURE (PSIG) HOT
ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE J = LOAD BEARING P.E. W/ 30A
1 3.6 8.3 E = 120V/1PH/60HZ - 2 STAGE MAG. CONTACTOR INTERLOCK
30 AMP CONT.
LOAD BRG. PE

2 1.8 4.1 5 = 120V/1PH/60HZ - 3 STAGE K = LOAD BEARING P.E. W/ 50A


W/ INTRLK

PER STAGE 3 1.2 2.7


K = 277V/1PH/60HZ - 1 STAGE MAG. CONTACTOR INTERLOCK
1 5.7 13.2
50 AMP CONT. L = 277V/1PH/60HZ - 2 STAGE L = LOAD BEARING P.E. W/ 30A
2 2.8 6.6 MERC. CONTACTOR INTERLOCK
PER STAGE Y = 277V/1PH/60HZ - 3 STAGE
3 1.9 4.4
M = LOAD BEARING P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR INTERLOCK


SIZE & TYPE

DOOR INTERLOCK 4.8 11.0

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 5.7 13.2
BLOCK

30 AMP BLOCK
FUSE

2.8 6.6

60 AMP BLOCK 5.7 13.2

1. MAX. K.W. BASED ON 48A, P.E., OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.008 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5E0X0

REV.1 5/14/00 PNEUMATIC


PSFH045
- J45 -

54 YORK INTERNATIONAL
FORM AD1T-SECT J

SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT


P.I., N.C. DAMPER, A.F.S. FAN START, POS. DAMPER CLOSE OFF, R.A. STAT, 1 PHASE, LOAD BEARING P.E. SWITCH W/ CONT. INTRLK.

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V
DISCONNECT OCCUPIED MODE:
SWITCH WHEN THE DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
SENSED BY THE S1 AIR FLOW SWITCH, THE FAN MOTOR
& EP SWITCH ARE ENERGIZED.
FUSING SPACE TEMP WARM (STAT OUTPUT LOW). AT A STAT
OUTPUT OF 3 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
OPTIONAL DISCONNECT SWITCH WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
AND OR FUSING
PANEL WIRING DIAGRAM STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
L1 (N) = 120V & 277V ON A FURTHER DROP IN SPACE TEMP., PE1 WILL CLOSE
TERMINAL ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
1 2
BLOCK
BK WH
AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.

UNOCCUPIED MODE:
BK BK WH
WHEN MAIN AIR HANDLER IS OFF, THE S1 AIR FLOW SWITCH
C1-1 STANDARD 1 DEENERGIZES THE FAN & EP SWITCH, CAUSING DAMPER TO
G CLOSE.
STAGE HEAT
RD C NO RD
ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
OPTIONAL 2 JOB SPECIFICATIONS.
PE-2
NC STAGE HEAT
NOTE: S1 AIRFLOW SWITCH FACTORY SET TO START FAN AT
BN C NO BN .10"WC TOTAL PRESSURE SENSED AT INLET FLOW PROBE.

PE-3 OPTIONAL 3
NC STAGE HEAT
(WHEN REQ.)
BK
TC BK C NO BK
C1
PE-1
NC
C N0 BK BL/WH BK
BK
5 SC FM
S1
NC
BK
EP

N.C. PNEUMATIC DIAGRAM


ACT. (3)C RECOMMENDED FIELD P.E. SWITCH SETTINGS:
(1)NC (2)NO
EP PE-1 = 8 PSI
PE-2 = 10 PSI
BAL. TAPS VEL. CNTRLR PE-3 = 12 PSI
B (RESET BAND=3-8 PSI)
FLOW LO X
M 20 PSI MAIN
PROBE HI Y CONSTANT
T
VOLUME
TOTAL AIR
R.A. STAT
FLOW

S1 1 PIPE COLD AIR HEAT


AIR

AIR
RESTRICTOR FLOW PLENUM AIR
OR OR 20 PSI MAIN

R.A. STAT
PE3 PE2 PE1 2 PIPE 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
HOT T-STAT BRANCH PRESSURE (PSIG) COLD
ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE J = LOAD BEARING P.E. W/ 30A
1 3.6 8.3 E = 120V/1PH/60HZ - 2 STAGE MAG. CONTACTOR INTERLOCK
30 AMP CONT.
LOAD BRG. PE

2 1.8 4.1 5 = 120V/1PH/60HZ - 3 STAGE K = LOAD BEARING P.E. W/ 50A


W/ INTRLK

PER STAGE 3 1.2 2.7


K = 277V/1PH/60HZ - 1 STAGE MAG. CONTACTOR INTERLOCK
1 5.7 13.2
50 AMP CONT. L = 277V/1PH/60HZ - 2 STAGE L = LOAD BEARING P.E. W/ 30A
2 2.8 6.6 MERC. CONTACTOR INTERLOCK
PER STAGE Y = 277V/1PH/60HZ - 3 STAGE
3 1.9 4.4
M = LOAD BEARING P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR INTERLOCK


SIZE & TYPE

DOOR INTERLOCK 4.8 11.0

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 5.7 13.2
BLOCK

30 AMP BLOCK
FUSE

2.8 6.6

60 AMP BLOCK 5.7 13.2

1. MAX. K.W. BASED ON 48A, P.E., OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.008 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5F0X0

REV.1 5/14/00 PNEUMATIC


PSFH046
- J46 -

YORK INTERNATIONAL 55
SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT
P.I., N.O. DAMPER, A.F.S. FAN START, POS. DAMPER CLOSE OFF, R.A. STAT, 1 PHASE, LOAD BEARING P.E. SWITCH W/ CONT. INTRLK.

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V
DISCONNECT OCCUPIED MODE:
SWITCH WHEN THE DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
SENSED BY THE S1 AIR FLOW SWITCH, THE FAN MOTOR
& EP SWITCH ARE ENERGIZED.
FUSING SPACE TEMP WARM (STAT OUTPUT LOW). AT A STAT
OUTPUT OF 3 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
OPTIONAL DISCONNECT SWITCH WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
AND OR FUSING
PANEL WIRING DIAGRAM STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
L1 (N) = 120V & 277V ON A FURTHER DROP IN SPACE TEMP., PE1 WILL CLOSE
TERMINAL ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
1 2
BLOCK
BK WH
AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.

UNOCCUPIED MODE:
BK BK WH
WHEN MAIN AIR HANDLER IS OFF, THE S1 AIR FLOW SWITCH
C1-1 STANDARD 1 DEENERGIZES THE FAN & EP SWITCH, CAUSING DAMPER TO
G CLOSE.
STAGE HEAT
RD C NO RD
ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
OPTIONAL 2 JOB SPECIFICATIONS.
PE-2
NC STAGE HEAT
NOTE: S1 AIRFLOW SWITCH FACTORY SET TO START FAN AT
BN C NO BN .10"WC TOTAL PRESSURE SENSED AT INLET FLOW PROBE.

PE-3 OPTIONAL 3
NC STAGE HEAT
(WHEN REQ.)
BK
TC BK C NO BK
C1
PE-1
NC
C N0 BK BL/WH BK
BK
5 SC FM
S1
NC
BK
EP

N.O.
PNEUMATIC DIAGRAM
ACT. (3)C RECOMMENDED FIELD P.E. SWITCH SETTINGS:
(1)NC (2)NO
PE-1 = 8 PSI
EP
PE-2 = 10 PSI
BAL. TAPS VEL. CNTRLR PE-3 = 12 PSI
B (RESET BAND=8-13 PSI)
FLOW LO Y
M 20 PSI MAIN
PROBE HI X CONSTANT
T
VOLUME
REV. R.A.. STAT TOTAL AIR
FLOW

S1 RELAY 1 PIPE HEAT


AIR

COLD AIR
AIR
M RESTRICTOR PLENUM AIR
1 FLOW
3 OR OR 20 PSI MAIN

R.A.. STAT
2 PIPE 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE3 PE2 PE1 HOT T-STAT BRANCH PRESSURE (PSIG) COLD
ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE J = LOAD BEARING P.E. W/ 30A
1 3.6 8.3 E = 120V/1PH/60HZ - 2 STAGE MAG. CONTACTOR INTERLOCK
30 AMP CONT.
LOAD BRG. PE

2 1.8 4.1 5 = 120V/1PH/60HZ - 3 STAGE K = LOAD BEARING P.E. W/ 50A


W/ INTRLK

PER STAGE 3 1.2 2.7


K = 277V/1PH/60HZ - 1 STAGE MAG. CONTACTOR INTERLOCK
1 5.7 13.2
50 AMP CONT. L = 277V/1PH/60HZ - 2 STAGE L = LOAD BEARING P.E. W/ 30A
2 2.8 6.6 MERC. CONTACTOR INTERLOCK
PER STAGE Y = 277V/1PH/60HZ - 3 STAGE
3 1.9 4.4
M = LOAD BEARING P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR INTERLOCK


SIZE & TYPE

DOOR INTERLOCK 4.8 11.0

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 5.7 13.2
BLOCK

30 AMP BLOCK
FUSE

2.8 6.6

60 AMP BLOCK 5.7 13.2

1. MAX. K.W. BASED ON 48A, P.E., OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.016 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5G0X0

REV.1 5/14/00 PNEUMATIC


PSFH047
- J47 -

56 YORK INTERNATIONAL
FORM AD1T-SECT J

SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT


P.I., N.C. DAMPER, A.F.S. FAN START, POS. DAMPER CLOSE OFF, D.A. STAT, 1 PHASE, LOAD BEARING P.E. SWITCH W/ CONT. INTRLK.

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V
OCCUPIED MODE:
DISCONNECT WHEN THE DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
SWITCH SENSED BY THE S1 AIR FLOW SWITCH, THE FAN MOTOR
& EP SWITCH ARE ENERGIZED.
FUSING SPACE TEMP WARM (STAT OUTPUT HI). AT A STAT
OUTPUT OF 13 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
OPTIONAL DISCONNECT SWITCH WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
AND OR FUSING STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
PANEL WIRING DIAGRAM CONTROLLING AT ITS MINIMUM.
L1 (N) = 120V & 277V ON A FURTHER DROP IN SPACE TEMP., PE1 WILL CLOSE
ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
TERMINAL 1 2
BLOCK AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
BK WH

UNOCCUPIED MODE:
BK BK WH WHEN MAIN AIR HANDLER IS OFF, THE S1 AIR FLOW SWITCH
DEENERGIZES THE FAN & EP SWITCH, CAUSING DAMPER TO
C1-1 STANDARD 1 G CLOSE.
STAGE HEAT
RD C NO RD ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
JOB SPECIFICATIONS.
PE-2 OPTIONAL 2
NC STAGE HEAT NOTE: S1 AIRFLOW SWITCH FACTORY SET TO START FAN AT
BN C NO BN .10"WC TOTAL PRESSURE SENSED AT INLET FLOW PROBE.

PE-3 OPTIONAL 3
NC STAGE HEAT
(WHEN REQ.)
BK
TC BK C NO BK
C1
PE-1
NC
C N0 BK BL/WH BK
BK
5 SC FM
S1
NC
BK
EP

N.C.
PNEUMATIC DIAGRAM
ACT. (3)C
RECOMMENDED FIELD P.E. SWITCH SETTINGS:
(1)NC (2)NO
EP PE-1 = 8 PSI
BAL. TAPS VEL. CNTRLR PE-2 = 6 PSI
(RESET BAND=3-8 PSI) PE-3 = 4 PSI
B
FLOW LO X
M 20 PSI MAIN
PROBE HI Y CONSTANT
T
VOLUME
REV. D.A.. STAT TOTAL AIR
FLOW

S1 RELAY 1 PIPE HEAT


AIR

COLD AIR
AIR
M RESTRICTOR PLENUM AIR
1 FLOW
3 OR OR 20 PSI MAIN

D.A.. STAT
2 PIPE 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE3 PE2 PE1 COLD T-STAT BRANCH PRESSURE (PSIG) HOT
ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE J = LOAD BEARING P.E. W/ 30A
1 3.6 8.3 E = 120V/1PH/60HZ - 2 STAGE MAG. CONTACTOR INTERLOCK
30 AMP CONT.
LOAD BRG. PE

2 1.8 4.1 5 = 120V/1PH/60HZ - 3 STAGE K = LOAD BEARING P.E. W/ 50A


W/ INTRLK

PER STAGE 3 1.2 2.7


K = 277V/1PH/60HZ - 1 STAGE MAG. CONTACTOR INTERLOCK
1 5.7 13.2
50 AMP CONT. L = 277V/1PH/60HZ - 2 STAGE L = LOAD BEARING P.E. W/ 30A
2 2.8 6.6 MERC. CONTACTOR INTERLOCK
PER STAGE Y = 277V/1PH/60HZ - 3 STAGE
3 1.9 4.4
M = LOAD BEARING P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR INTERLOCK


SIZE & TYPE

DOOR INTERLOCK 4.8 11.0

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 5.7 13.2
BLOCK

30 AMP BLOCK
FUSE

2.8 6.6

60 AMP BLOCK 5.7 13.2

1. MAX. K.W. BASED ON 48A, P.E., OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.016 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5H0X0

REV.1 5/14/00 PNEUMATIC


PSDH048
- J48 -

YORK INTERNATIONAL 57
SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT
PRESS. INDEPENDENT, N.O. DAMPER, A.F.S. FAN START, POS. DAMPER CLOSE OFF, DIRECT ACTING STAT, 1 PHASE, PILOT DUTY P.E. SWITCH

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V OCCUPIED MODE:
DISCONNECT WHEN THE DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
SWITCH SENSED BY THE S1 AIR FLOW SWITCH, THE FAN MOTOR
& EP SWITCH ARE ENERGIZED.
SPACE TEMP WARM (STAT OUTPUT HI). AT A STAT
FUSING OUTPUT OF 13 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
OPTIONAL DISCONNECT SWITCH
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
AND OR FUSING
PANEL WIRING DIAGRAM CONTROLLING AT ITS MINIMUM.
ON A FURTHER DROP IN SPACE TEMP., PE1 WILL CLOSE
L1 (N) = 120V & 277V ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
TERMINAL 1 2
BLOCK AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
BK WH
UNOCCUPIED MODE:
WHEN MAIN AIR HANDLER IS OFF, THE S1 AIR FLOW SWITCH
BK BK WH DEENERGIZES THE FAN AND EP SWITCH, CAUSING DAMPER TO
STANDARD 1 ST. HEAT CLOSE.
C1-1 G
RD RD
ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
OPTIONAL 2 ST. HEAT JOB SPECIFICATIONS.
C2-1
BN BN
C N0 BK OPTIONAL 3 ST. HEAT
C3-1
TC C NO ST.1
BK BK BK
S1 5 C1 NOTE: S1 AIRFLOW SWITCH FACTORY SET TO START FAN AT
NC .10"WC TOTAL PRESSURE SENSED AT INLET FLOW PROBE.
PE-1
(WHEN REQ.) NC
ST.2
RD C NO RD
C2
PE-2
NC
ST.3
BN C NO BN
C3
PE-3
NC
BK BL/WH BK
SC FM

BK
EP

PNEUMATIC DIAGRAM
N.O.
ACT. (3)C RECOMMENDED FIELD P.E. SWITCH SETTINGS:
(1)NC (2)NO
PE-1 = 8 PSI
EP PE-2 = 6 PSI
BAL. TAPS VEL. CNTRLR PE-3 = 4 PSI
B (RESET BAND=8-13 PSI)
FLOW LO Y CONSTANT
M 20 PSI MAIN
PROBE HI X VOLUME
T TOTAL AIR
D.A.. STAT HEAT COLD AIR
FLOW

S1 1 PIPE AIR
(UNOCCUPIED)
AIR

FLOW PLENUM AIR


FAN STARTS
RESTRICTOR
OR OR 20 PSI MAIN (FIELD CALIB.)

D.A.. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE3 PE2 PE1 2 PIPE COLD T-STAT BRANCH PRESSURE (PSIG) HOT
ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE 2 = PILOT DUTY P.E. W/ 30A
1 3.6 8.3 E = 120V/1PH/60HZ - 2 STAGE MAG. CONTACTOR
DE-ENERGIZING
CONTACTOR

30 AMP 2 2.8 6.6 5 = 120V/1PH/60HZ - 3 STAGE 3 = PILOT DUTY P.E. W/ 50A


CONTACTOR 3 1.9 4.4
K = 277V/1PH/60HZ - 1 STAGE MAG. CONTACTOR
1 5.7 13.2
50 AMP L = 277V/1PH/60HZ - 2 STAGE 4 = PILOT DUTY P.E. W/ 30A
2 2.8 6.6 MERC. CONTACTOR
CONTACTOR Y = 277V/1PH/60HZ - 3 STAGE
3 1.9 4.4
5 = PILOT DUTY P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR


SIZE & TYPE

DOOR INTERLOCK 4.8 11.0

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 5.7 13.2
BLOCK

30 AMP BLOCK
FUSE

2.8 6.6

60 AMP BLOCK 5.7 13.2

1. MAX. K.W. BASED ON 48A, OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.008 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5E030

REV.1 5/6/00 PNEUMATIC


PSFH029
- J49 -

58 YORK INTERNATIONAL
FORM AD1T-SECT J

SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT


PRESS. INDEPENDENT, N.C. DAMPER, A.F.S. FAN START, POS. DAMPER CLOSE OFF, REVERSE ACTING STAT, 1 PHASE, PILOT DUTY P.E. SWITCH

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V
DISCONNECT OCCUPIED MODE:
SWITCH WHEN THE DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
SENSED BY THE S1 AIR FLOW SWITCH, THE FAN MOTOR
& EP SWITCH ARE ENERGIZED.
FUSING SPACE TEMP WARM (STAT OUTPUT LOW). AT A STAT
OUTPUT OF 3 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
OPTIONAL DISCONNECT SWITCH WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
AND OR FUSING
PANEL WIRING DIAGRAM STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
L1 (N) = 120V & 277V ON A FURTHER DROP IN SPACE TEMP., PE1 WILL CLOSE
TERMINAL ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
1 2
BLOCK
BK WH
AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.

UNOCCUPIED MODE:
BK BK WH
WHEN MAIN AIR HANDLER IS OFF, THE S1 AIR FLOW SWITCH
C1-1 STANDARD 1 ST. HEAT G
DEENERGIZES THE FAN & EP SWITCH, CAUSING DAMPER TO
RD RD CLOSE.
OPTIONAL 2 ST. HEAT
C2-1 ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
BN BN JOB SPECIFICATIONS.
C N0
(WHEN REQ.) C3-1 OPTIONAL 3 ST. HEAT
BK ST.1 NOTE: S1 AIRFLOW SWITCH FACTORY SET TO START FAN AT
BK TC BK C NO BK .10"WC TOTAL PRESSURE SENSED AT INLET FLOW PROBE.
S1 5 C1
NC
PE-1
NC
ST.2
RD C NO RD
C2
PE-2
NC
ST.3
BN C NO BN
C3
PE-3
NC
BK BL/WH BK
SC FM

BK
EP

RECOMMENDED FIELD P.E. SWITCH SETTINGS:


N.C. PNEUMATIC DIAGRAM
PE-1 = 8 PSI
ACT. (3)C PE-2 = 10 PSI
(1)NC (2)NO PE-3 = 12 PSI
EP
BAL. TAPS VEL. CNTRLR CONSTANT
B (RESET BAND=3-8 PSI) VOLUME
FLOW LO X TOTAL AIR
M 20 PSI MAIN
PROBE HI Y HEAT
T COLD AIR
AIR
R.A. STAT FLOW PLENUM AIR
FLOW

S1 1 PIPE
AIR

RESTRICTOR
OR OR 20 PSI MAIN
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
HOT T-STAT BRANCH PRESSURE (PSIG) COLD
R.A. STAT ROOM ROOM
PE3 PE2 PE1 2 PIPE

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE 2 = PILOT DUTY P.E. W/ 30A
1 3.6 8.3 E = 120V/1PH/60HZ - 2 STAGE MAG. CONTACTOR
DE-ENERGIZING
CONTACTOR

30 AMP 2 2.8 6.6 5 = 120V/1PH/60HZ - 3 STAGE 3 = PILOT DUTY P.E. W/ 50A


CONTACTOR 3 1.9 4.4
K = 277V/1PH/60HZ - 1 STAGE MAG. CONTACTOR
1 5.7 13.2
50 AMP L = 277V/1PH/60HZ - 2 STAGE 4 = PILOT DUTY P.E. W/ 30A
2 2.8 6.6 MERC. CONTACTOR
CONTACTOR Y = 277V/1PH/60HZ - 3 STAGE
3 1.9 4.4
5 = PILOT DUTY P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR


SIZE & TYPE

DOOR INTERLOCK 4.8 11.0

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 5.7 13.2
BLOCK

30 AMP BLOCK
FUSE

2.8 6.6

60 AMP BLOCK 5.7 13.2

1. MAX. K.W. BASED ON 48A, OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.008 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5F0X0

REV.1 5/14/00 PNEUMATIC


PSFH050
- J50 -

YORK INTERNATIONAL 59
SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT
PRESS. INDEPENDENT, N.O. DAMPER, A.F.S. FAN START, POS. DAMPER CLOSE OFF, REVERSE ACTING STAT, 1 PHASE, PILOT DUTY P.E. SWITCH

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V
DISCONNECT OCCUPIED MODE:
SWITCH WHEN THE DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
SENSED BY THE S1 AIR FLOW SWITCH, THE FAN MOTOR
& EP SWITCH ARE ENERGIZED.
FUSING SPACE TEMP WARM (STAT OUTPUT LOW). AT A STAT
OUTPUT OF 3 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
OPTIONAL DISCONNECT SWITCH WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
AND OR FUSING
PANEL WIRING DIAGRAM STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
L1 (N) = 120V & 277V ON A FURTHER DROP IN SPACE TEMP., PE1 WILL CLOSE
TERMINAL ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
1 2
BLOCK
BK WH
AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.

UNOCCUPIED MODE:
BK BK WH
WHEN MAIN AIR HANDLER IS OFF, THE S1 AIR FLOW SWITCH
C1-1 STANDARD 1 ST. HEAT G
DEENERGIZES THE FAN & EP SWITCH, CAUSING DAMPER TO
RD RD CLOSE.
OPTIONAL 2 ST. HEAT
C2-1 ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
BN BN JOB SPECIFICATIONS.
C N0
(WHEN REQ.) C3-1 OPTIONAL 3 ST. HEAT
BK ST.1 NOTE: S1 AIRFLOW SWITCH FACTORY SET TO START FAN AT
BK TC BK C NO BK .10"WC TOTAL PRESSURE SENSED AT INLET FLOW PROBE.
S1 5 C1
NC
PE-1
NC
ST.2
RD C NO RD
C2
PE-2
NC
ST.3
BN C NO BN
C3
PE-3
NC
BK BL/WH BK
SC FM

BK
EP

N.O.
PNEUMATIC DIAGRAM
ACT. (3)C RECOMMENDED FIELD P.E. SWITCH SETTINGS:
(1)NC (2)NO
PE-1 = 8 PSI
EP
PE-2 = 10 PSI
BAL. TAPS VEL. CNTRLR PE-3 = 12 PSI
B (RESET BAND=8-13 PSI)
FLOW LO Y
M 20 PSI MAIN
PROBE HI X CONSTANT
T
VOLUME
REV. R.A.. STAT TOTAL AIR
FLOW

S1 RELAY 1 PIPE HEAT


AIR

COLD AIR
AIR
M RESTRICTOR PLENUM AIR
1 FLOW
3 OR OR 20 PSI MAIN

R.A.. STAT
2 PIPE 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE3 PE2 PE1 HOT T-STAT BRANCH PRESSURE (PSIG) COLD
ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE 2 = PILOT DUTY P.E. W/ 30A
1 3.6 8.3 E = 120V/1PH/60HZ - 2 STAGE MAG. CONTACTOR
DE-ENERGIZING
CONTACTOR

30 AMP 2 2.8 6.6 5 = 120V/1PH/60HZ - 3 STAGE 3 = PILOT DUTY P.E. W/ 50A


CONTACTOR 3 1.9 4.4
K = 277V/1PH/60HZ - 1 STAGE MAG. CONTACTOR
1 5.7 13.2
50 AMP L = 277V/1PH/60HZ - 2 STAGE 4 = PILOT DUTY P.E. W/ 30A
2 2.8 6.6 MERC. CONTACTOR
CONTACTOR Y = 277V/1PH/60HZ - 3 STAGE
3 1.9 4.4
5 = PILOT DUTY P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR


SIZE & TYPE

DOOR INTERLOCK 4.8 11.0

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 5.7 13.2
BLOCK

30 AMP BLOCK
FUSE

2.8 6.6

60 AMP BLOCK 5.7 13.2

1. MAX. K.W. BASED ON 48A, OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.016 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5G0X0

REV.1 5/14/00 PNEUMATIC


PSFH051
- J51 -

60 YORK INTERNATIONAL
FORM AD1T-SECT J

SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT


PRESS. INDEPENDENT, N.C. DAMPER, A.F.S. FAN START, POS. DAMPER CLOSE OFF, DIRECT ACTING STAT, 1 PHASE, PILOT DUTY P.E. SWITCH

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V
OCCUPIED MODE:
DISCONNECT WHEN THE DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
SWITCH SENSED BY THE S1 AIR FLOW SWITCH, THE FAN MOTOR
& EP SWITCH ARE ENERGIZED.
FUSING SPACE TEMP WARM (STAT OUTPUT HI). AT A STAT
OUTPUT OF 13 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
OPTIONAL DISCONNECT SWITCH WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
AND OR FUSING STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
PANEL WIRING DIAGRAM CONTROLLING AT ITS MINIMUM.
L1 (N) = 120V & 277V ON A FURTHER DROP IN SPACE TEMP., PE1 WILL CLOSE
ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
TERMINAL 1 2
BLOCK AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
BK WH

UNOCCUPIED MODE:
BK BK WH WHEN MAIN AIR HANDLER IS OFF, THE S1 AIR FLOW SWITCH
DEENERGIZES THE FAN & EP SWITCH, CAUSING DAMPER TO
C1-1 STANDARD 1 ST. HEAT G CLOSE.
RD RD

OPTIONAL 2 ST. HEAT ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY


C2-1
BN BN JOB SPECIFICATIONS.
C N0
(WHEN REQ.) C3-1 OPTIONAL 3 ST. HEAT NOTE: S1 AIRFLOW SWITCH FACTORY SET TO START FAN AT
BK
TC C NO BK ST.1 .10"WC TOTAL PRESSURE SENSED AT INLET FLOW PROBE.
BK BK
S1 5 C1
NC
PE-1
NC
ST.2
RD C NO RD
C2
PE-2
NC
ST.3
BN C NO BN
C3
PE-3
NC
BK BL/WH BK
SC FM

BK
EP

N.C.
PNEUMATIC DIAGRAM
ACT. (3)C
RECOMMENDED FIELD P.E. SWITCH SETTINGS:
(1)NC (2)NO
EP PE-1 = 8 PSI
BAL. TAPS VEL. CNTRLR PE-2 = 6 PSI
(RESET BAND=3-8 PSI) PE-3 = 4 PSI
B
FLOW LO X
M 20 PSI MAIN
PROBE HI Y CONSTANT
T
VOLUME
REV. D.A.. STAT TOTAL AIR
FLOW

S1 RELAY 1 PIPE HEAT


AIR

COLD AIR
AIR
M RESTRICTOR PLENUM AIR
1 FLOW
3 OR OR 20 PSI MAIN

D.A.. STAT
2 PIPE 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE3 PE2 PE1 COLD T-STAT BRANCH PRESSURE (PSIG) HOT
ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE 2 = PILOT DUTY P.E. W/ 30A
1 3.6 8.3 E = 120V/1PH/60HZ - 2 STAGE MAG. CONTACTOR
DE-ENERGIZING
CONTACTOR

30 AMP 2 2.8 6.6 5 = 120V/1PH/60HZ - 3 STAGE 3 = PILOT DUTY P.E. W/ 50A


CONTACTOR 3 1.9 4.4
K = 277V/1PH/60HZ - 1 STAGE MAG. CONTACTOR
1 5.7 13.2
50 AMP L = 277V/1PH/60HZ - 2 STAGE 4 = PILOT DUTY P.E. W/ 30A
2 2.8 6.6 MERC. CONTACTOR
CONTACTOR Y = 277V/1PH/60HZ - 3 STAGE
3 1.9 4.4
5 = PILOT DUTY P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR


SIZE & TYPE

DOOR INTERLOCK 4.8 11.0

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 5.7 13.2
BLOCK

30 AMP BLOCK
FUSE

2.8 6.6

60 AMP BLOCK 5.7 13.2

1. MAX. K.W. BASED ON 48A, OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.016 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5H0X0

REV.1 5/14/00 PNEUMATIC


PSFH052
- J52 -

YORK INTERNATIONAL 61
SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT
P.I., N.O. DAMPER, A.F.S. FAN START, POS. DAMPER CLOSE OFF, D.A. STAT, 3 PHASE, LOAD BEARING P.E. SWITCH W/ CONT. INTRLK.

SEQUENCE OF OPERATION:

L1 L2 L3 OCCUPIED MODE:
DISCONNECT WHEN THE DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
SWITCH SENSED BY THE S1 AIR FLOW SWITCH, THE FAN MOTOR
& EP SWITCH ARE ENERGIZED.
SPACE TEMP WARM (STAT OUTPUT HI). AT A STAT
FUSING OUTPUT OF 13 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
OPTIONAL DISCONNECT SWITCH
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
PANEL WIRING DIAGRAM AND OR FUSING
CONTROLLING AT ITS MINIMUM.
L1 L2 L3 N ON A FURTHER DROP IN SPACE TEMP., PE1 WILL CLOSE
TERMINAL ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
1 2 3 4
BLOCK AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
BK WH

BK BL
UNOCCUPIED MODE:
WHEN MAIN AIR HANDLER IS OFF, THE S1 AIR FLOW SWITCH
BK STANDARD 1 STAGE HEAT DEENERGIZES THE FAN & EP SWITCH, CAUSING DAMPER TO
C1-1 G CLOSE.
BK BK
ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
C1-2
JOB SPECIFICATIONS.
C N0 BK

TC ST.1 NOTE: S1 AIRFLOW SWITCH FACTORY SET TO START FAN AT


BK BK C NO BK
S1 5 C1 .10"WC TOTAL PRESSURE SENSED AT INLET FLOW PROBE.
NC
PE-1
NC
BK BL/WH BK
SC FM

BK BK BK
EP L1 1
C1-1
RD
C NO
L2 2
RD
PE-2
NC
L1 1
BK BK
BN C NO BN

C NO C1-1 BL
L2 2
RD 3 L3 PE-3
RD RD
NC
PE-2 BL BL
NC L3 3
C1-2 C1-2
N.O. PNEUMATIC DIAGRAM
OPTIONAL 2 STAGE HEAT OPTIONAL 3 STAGE HEAT
ACT. (3)C
(1)NC (2)NO RECOMMENDED FIELD P.E. SWITCH SETTINGS:
EP
PE-1 = 8 PSI
BAL. TAPS VEL. CNTRLR PE-2 = 6 PSI
B (RESET BAND=8-13 PSI) PE-3 = 4 PSI
FLOW LO Y
M 20 PSI MAIN
PROBE HI X
T CONSTANT
D.A.. STAT VOLUME
TOTAL AIR
FLOW

S1 1 PIPE HEAT
AIR

COLD AIR
AIR
RESTRICTOR
OR OR 20 PSI MAIN FLOW PLENUM AIR

D.A.. STAT
2 PIPE
PE2 PE1
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE3
COLD T-STAT BRANCH PRESSURE (PSIG) HOT
ROOM ROOM

HEATER COMPONENTS MAX. KW


3 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-3 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 208 V 480 V P = 208V/3PH/60HZ - 1 STAGE J = LOAD BEARING P.E. W/ 30A
1 10.7 24.9 R = 208V/3PH/60HZ - 2 STAGE MAG. CONTACTOR INTERLOCK
30 AMP CONT.
LOAD BRG. PE

2 4.4 9.1 1 = 208V/3PH/60HZ - 3 STAGE K = LOAD BEARING P.E. W/ 50A


W/ INTRLK

PER STAGE 3 2.9 6.0


U = 480V/3PH/60HZ - 1 STAGE MAG. CONTACTOR INTERLOCK
1 17.2 39.8
50 AMP CONT. W = 480V/3PH/60HZ - 2 STAGE L = LOAD BEARING P.E. W/ 30A
2 4.4 9.1 MERC. CONTACTOR INTERLOCK
PER STAGE 3 = 480V/3PH/60HZ - 3 STAGE
3 2.9 6.0
M = LOAD BEARING P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR INTERLOCK


SIZE & TYPE

DOOR INTERLOCK 14.3 33.2

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 17.2 39.8
BLOCK

30 AMP BLOCK
FUSE

8.6 19.9

60 AMP BLOCK 17.2 39.8

1. MAX. K.W. BASED ON 48A, P.E., OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.008 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5E0X0

REV.1 5/14/00 PNEUMATIC


PSFH053
- J53 -

62 YORK INTERNATIONAL
FORM AD1T-SECT J

SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT


P.I., N.C. DAMPER, A.F.S. FAN START, POS. DAMPER CLOSE OFF, R.A. STAT, 3 PHASE, LOAD BEARING P.E. SWITCH W/ CONT. INTRLK.

SEQUENCE OF OPERATION:
L1 L2 L3
DISCONNECT OCCUPIED MODE:
WHEN THE DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
SWITCH
SENSED BY THE S1 AIR FLOW SWITCH, THE FAN MOTOR
& EP SWITCH ARE ENERGIZED.
FUSING SPACE TEMP WARM (STAT OUTPUT LOW). AT A STAT
OUTPUT OF 3 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
OPTIONAL DISCONNECT SWITCH WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
PANEL WIRING DIAGRAM AND OR FUSING STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
L1 L2 L3 N ON A FURTHER DROP IN SPACE TEMP., PE1 WILL CLOSE
TERMINAL 1 2 3 4 ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
BLOCK
BK WH AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
BK BL
UNOCCUPIED MODE:
BK WHEN MAIN AIR HANDLER IS OFF, THE S1 AIR FLOW SWITCH
STANDARD 1 STAGE HEAT
DEENERGIZES THE FAN & EP SWITCH, CAUSING DAMPER TO
C1-1 G CLOSE.
BK BK

C1-2 ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY


C N0 JOB SPECIFICATIONS.
BK

TC ST.1
BK BK C NO BK NOTE: S1 AIRFLOW SWITCH FACTORY SET TO START FAN AT
S1 5 C1
NC .10"WC TOTAL PRESSURE SENSED AT INLET FLOW PROBE.
PE-1
NC
BK BL/WH BK
SC FM
BK BK
BK
L1 1
EP C1-1
RD
C NO
L2 2 RD

PE-2
NC
BK BK
L1 1 BN C NO BN
C NO C1-1 BL
L2 2
RD 3 L3
RD PE-3
RD NC
PE-2 BL BL
NC C1-2 L3 3
C1-2
OPTIONAL 2 STAGE HEAT OPTIONAL 3 STAGE HEAT
N.C. PNEUMATIC DIAGRAM
ACT. (3)C RECOMMENDED FIELD P.E. SWITCH SETTINGS:
(1)NC (2)NO
EP PE-1 = 8 PSI
BAL. TAPS PE-2 = 10 PSI
VEL. CNTRLR
PE-3 = 12 PSI
B (RESET BAND=3-8 PSI)
FLOW LO X
M 20 PSI MAIN CONSTANT
PROBE HI Y
T VOLUME
TOTAL AIR
R.A. STAT
FLOW

COLD AIR HEAT


S1 1 PIPE AIR
AIR

FLOW PLENUM AIR


RESTRICTOR
OR OR 20 PSI MAIN

R.A. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE3 PE2 PE1 2 PIPE HOT COLD
T-STAT BRANCH PRESSURE (PSIG)
ROOM ROOM

HEATER COMPONENTS MAX. KW


3 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-3 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 208 V 480 V P = 208V/3PH/60HZ - 1 STAGE J = LOAD BEARING P.E. W/ 30A
1 10.7 24.9 R = 208V/3PH/60HZ - 2 STAGE MAG. CONTACTOR INTERLOCK
30 AMP CONT.
LOAD BRG. PE

2 4.4 9.1 1 = 208V/3PH/60HZ - 3 STAGE K = LOAD BEARING P.E. W/ 50A


W/ INTRLK

PER STAGE 3 2.9 6.0


U = 480V/3PH/60HZ - 1 STAGE MAG. CONTACTOR INTERLOCK
1 17.2 39.8
50 AMP CONT. W = 480V/3PH/60HZ - 2 STAGE L = LOAD BEARING P.E. W/ 30A
2 4.4 9.1 MERC. CONTACTOR INTERLOCK
PER STAGE 3 = 480V/3PH/60HZ - 3 STAGE
3 2.9 6.0
M = LOAD BEARING P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR INTERLOCK


SIZE & TYPE

DOOR INTERLOCK 14.3 33.2

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 17.2 39.8
BLOCK

30 AMP BLOCK
FUSE

8.6 19.9

60 AMP BLOCK 17.2 39.8

1. MAX. K.W. BASED ON 48A, P.E., OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.008 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5F0X0

REV.1 5/14/00 PNEUMATIC


PSFH054
- J54 -

YORK INTERNATIONAL 63
SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT
P.I., N.O. DAMPER, A.F.S. FAN START, POS. DAMPER CLOSE OFF, R.A. STAT, 3 PHASE, LOAD BEARING P.E. SWITCH W/ CONT. INTRLK.

SEQUENCE OF OPERATION:
L1 L2 L3
DISCONNECT OCCUPIED MODE:
WHEN THE DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
SWITCH
SENSED BY THE S1 AIR FLOW SWITCH, THE FAN MOTOR
& EP SWITCH ARE ENERGIZED.
FUSING SPACE TEMP WARM (STAT OUTPUT LOW). AT A STAT
OUTPUT OF 3 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
OPTIONAL DISCONNECT SWITCH WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
PANEL WIRING DIAGRAM AND OR FUSING STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
L1 L2 L3 N ON A FURTHER DROP IN SPACE TEMP., PE1 WILL CLOSE
TERMINAL 1 2 3 4 ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
BLOCK
BK WH AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
BK BL
UNOCCUPIED MODE:
BK WHEN MAIN AIR HANDLER IS OFF, THE S1 AIR FLOW SWITCH
STANDARD 1 STAGE HEAT
DEENERGIZES THE FAN & EP SWITCH, CAUSING DAMPER TO
C1-1 G CLOSE.
BK BK

C1-2 ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY


C N0 JOB SPECIFICATIONS.
BK

TC ST.1
BK BK C NO BK NOTE: S1 AIRFLOW SWITCH FACTORY SET TO START FAN AT
S1 5 C1
NC .10"WC TOTAL PRESSURE SENSED AT INLET FLOW PROBE.
PE-1
NC
BK BL/WH BK
SC FM

BK BK BK
EP L1 1
C1-1
RD
C NO
L2 2 RD

PE-2
NC
BK BK C
L1 1 BN NO BN

C NO C1-1 BL
L2 2
RD 3 L3 PE-3
RD
RD
NC
PE-2 BL BL
NC L3 3
C1-2 C1-2
N.O.
PNEUMATIC DIAGRAM
OPTIONAL 2 STAGE HEAT OPTIONAL 3 STAGE HEAT
ACT. (3)C
(1)NC (2)NO RECOMMENDED FIELD P.E. SWITCH SETTINGS:
EP
PE-1 = 8 PSI
BAL. TAPS VEL. CNTRLR PE-2 = 10 PSI
B (RESET BAND=8-13 PSI) PE-3 = 12 PSI
FLOW LO Y
M 20 PSI MAIN
PROBE HI X CONSTANT
T
VOLUME
REV. R.A.. STAT TOTAL AIR
FLOW

S1 RELAY 1 PIPE HEAT


AIR

COLD AIR
AIR
M RESTRICTOR PLENUM AIR
1 FLOW
3 OR OR 20 PSI MAIN

R.A.. STAT
2 PIPE 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE3 PE2 PE1 HOT T-STAT BRANCH PRESSURE (PSIG) COLD
ROOM ROOM

HEATER COMPONENTS MAX. KW


3 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-3 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 208 V 480 V P = 208V/3PH/60HZ - 1 STAGE J = LOAD BEARING P.E. W/ 30A
1 10.7 24.9 R = 208V/3PH/60HZ - 2 STAGE MAG. CONTACTOR INTERLOCK
30 AMP CONT.
LOAD BRG. PE

2 4.4 9.1 1 = 208V/3PH/60HZ - 3 STAGE K = LOAD BEARING P.E. W/ 50A


W/ INTRLK

PER STAGE 3 2.9 6.0


U = 480V/3PH/60HZ - 1 STAGE MAG. CONTACTOR INTERLOCK
1 17.2 39.8
50 AMP CONT. W = 480V/3PH/60HZ - 2 STAGE L = LOAD BEARING P.E. W/ 30A
2 4.4 9.1 MERC. CONTACTOR INTERLOCK
PER STAGE 3 = 480V/3PH/60HZ - 3 STAGE
3 2.9 6.0
M = LOAD BEARING P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR INTERLOCK


SIZE & TYPE

DOOR INTERLOCK 14.3 33.2

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 17.2 39.8
BLOCK

30 AMP BLOCK
FUSE

8.6 19.9

60 AMP BLOCK 17.2 39.8

1. MAX. K.W. BASED ON 48A, P.E., OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.016 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5G0X0

REV.1 5/14/00 PNEUMATIC


PSFH055
- J55 -

64 YORK INTERNATIONAL
FORM AD1T-SECT J

SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT


P.I., N.C. DAMPER, A.F.S. FAN START, POS. DAMPER CLOSE OFF, D.A. STAT, 3 PHASE, LOAD BEARING P.E. SWITCH W/ CONT. INTRLK.

SEQUENCE OF OPERATION:

L1 L2 L3 OCCUPIED MODE:
DISCONNECT WHEN THE DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
SWITCH SENSED BY THE S1 AIR FLOW SWITCH, THE FAN MOTOR
& EP SWITCH ARE ENERGIZED.
SPACE TEMP WARM (STAT OUTPUT HI). AT A STAT
FUSING OUTPUT OF 13 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
OPTIONAL DISCONNECT SWITCH
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
PANEL WIRING DIAGRAM AND OR FUSING
CONTROLLING AT ITS MINIMUM.
L1 L2 L3 N ON A FURTHER DROP IN SPACE TEMP., PE1 WILL CLOSE
TERMINAL ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
1 2 3 4
BLOCK AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
BK WH

BK BL
UNOCCUPIED MODE:
WHEN MAIN AIR HANDLER IS OFF, THE S1 AIR FLOW SWITCH
BK STANDARD 1 STAGE HEAT DEENERGIZES THE FAN & EP SWITCH, CAUSING DAMPER TO
C1-1 G CLOSE.
BK BK
ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
C1-2
JOB SPECIFICATIONS.
C N0 BK

TC ST.1 NOTE: S1 AIRFLOW SWITCH FACTORY SET TO START FAN AT


BK BK C NO BK
S1 5 C1 .10"WC TOTAL PRESSURE SENSED AT INLET FLOW PROBE.
NC
PE-1
NC
BK BL/WH BK
SC FM

BK BK BK
EP L1 1
C1-1
RD
C NO
L2 2
RD
PE-2
NC
L1 1
BK BK
BN C NO BN

C NO C1-1 BL
L2 2
RD 3 L3 PE-3
RD RD
NC
PE-2 BL BL
NC L3 3
C1-2 C1-2
N.C.
PNEUMATIC DIAGRAM
OPTIONAL 2 STAGE HEAT OPTIONAL 3 STAGE HEAT
ACT. (3)C
RECOMMENDED FIELD P.E. SWITCH SETTINGS:
(1)NC (2)NO
EP PE-1 = 8 PSI
BAL. TAPS VEL. CNTRLR PE-2 = 6 PSI
(RESET BAND=3-8 PSI) PE-3 = 4 PSI
B
FLOW LO X
M 20 PSI MAIN
PROBE HI Y CONSTANT
T
VOLUME
REV. D.A.. STAT TOTAL AIR
FLOW

S1 RELAY 1 PIPE HEAT


AIR

COLD AIR
AIR
M RESTRICTOR PLENUM AIR
1 FLOW
3 OR OR 20 PSI MAIN

D.A.. STAT
2 PIPE 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE3 PE2 PE1 COLD T-STAT BRANCH PRESSURE (PSIG) HOT
ROOM ROOM

HEATER COMPONENTS MAX. KW


3 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-3 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 208 V 480 V P = 208V/3PH/60HZ - 1 STAGE J = LOAD BEARING P.E. W/ 30A
1 10.7 24.9 R = 208V/3PH/60HZ - 2 STAGE MAG. CONTACTOR INTERLOCK
30 AMP CONT.
LOAD BRG. PE

2 4.4 9.1 1 = 208V/3PH/60HZ - 3 STAGE K = LOAD BEARING P.E. W/ 50A


W/ INTRLK

PER STAGE 3 2.9 6.0


U = 480V/3PH/60HZ - 1 STAGE MAG. CONTACTOR INTERLOCK
1 17.2 39.8
50 AMP CONT. W = 480V/3PH/60HZ - 2 STAGE L = LOAD BEARING P.E. W/ 30A
2 4.4 9.1 MERC. CONTACTOR INTERLOCK
PER STAGE 3 = 480V/3PH/60HZ - 3 STAGE
3 2.9 6.0
M = LOAD BEARING P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR INTERLOCK


SIZE & TYPE

DOOR INTERLOCK 14.3 33.2

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 17.2 39.8
BLOCK

30 AMP BLOCK
FUSE

8.6 19.9

60 AMP BLOCK 17.2 39.8

1. MAX. K.W. BASED ON 48A, P.E., OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.016 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5H0X0

REV.1 5/14/00 PNEUMATIC


PSFH056
- J56 -

YORK INTERNATIONAL 65
SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT
PRESS. INDEPENDENT, N.O. DAMPER, A.F.S. FAN START, POS. DAMPER CLOSE OFF, DIRECT ACTING STAT, 3 PHASE, PILOT DUTY P.E. SWITCH

SEQUENCE OF OPERATION:

L1 L2 L3 OCCUPIED MODE:
DISCONNECT WHEN THE DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
SWITCH SENSED BY THE S1 AIR FLOW SWITCH, THE FAN MOTOR
& EP SWITCH ARE ENERGIZED.
SPACE TEMP WARM (STAT OUTPUT HI). AT A STAT
FUSING OUTPUT OF 13 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
OPTIONAL DISCONNECT SWITCH
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
PANEL WIRING DIAGRAM AND OR FUSING
CONTROLLING AT ITS MINIMUM.
L1 L2 L3 N ON A FURTHER DROP IN SPACE TEMP., PE1 WILL CLOSE
TERMINAL ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
1 2 3 4
BLOCK AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
BK WH

BK BL
UNOCCUPIED MODE:
WHEN MAIN AIR HANDLER IS OFF, THE S1 AIR FLOW SWITCH
BK STANDARD 1 STAGE HEAT DEENERGIZES THE FAN & EP SWITCH, CAUSING DAMPER TO
C1-1 G CLOSE.
BK BK
ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
C1-2
JOB SPECIFICATIONS.
C N0 BK

TC ST.1 NOTE: S1 AIRFLOW SWITCH FACTORY SET TO START FAN AT


BK BK C NO BK
S1 5 C1 .10"WC TOTAL PRESSURE SENSED AT INLET FLOW PROBE.
NC
PE-1
NC
ST.2
RD C NO RD BK BK
C2 L1 1
BL
PE-2 C1-1 3 L3
RD RD
NC L2 2
ST.3
BN C NO BN C2-1
C3
OPTIONAL 2 STAGE HEAT
PE-3
NC
BK BL/WH BK
SC FM L1 1
BK BK

C1-1
RD RD
BK
L2 2
EP C2-1
BN BN

C3-1
BL BL
L3 3
N.O. PNEUMATIC DIAGRAM C1-2
OPTIONAL 3 STAGE HEAT
ACT. (3)C
(1)NC (2)NO RECOMMENDED FIELD P.E. SWITCH SETTINGS:
EP
PE-1 = 8 PSI
BAL. TAPS VEL. CNTRLR PE-2 = 6 PSI
B (RESET BAND=8-13 PSI) PE-3 = 4 PSI
FLOW LO Y
M 20 PSI MAIN
PROBE HI X CONSTANT
T
VOLUME
TOTAL AIR
D.A.. STAT
FLOW

S1 1 PIPE HEAT COLD AIR


AIR

AIR
RESTRICTOR FLOW PLENUM AIR
OR OR 20 PSI MAIN

D.A.. STAT
2 PIPE 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE3 PE2 PE1 COLD T-STAT BRANCH PRESSURE (PSIG) HOT
ROOM ROOM

HEATER COMPONENTS MAX. KW


3 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-3 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 208 V 480 V P = 208V/3PH/60HZ - 1 STAGE 2 = PILOT DUTY P.E. W/ 30A
1 10.7 24.9 R = 208V/3PH/60HZ - 2 STAGE MAG. CONTACTOR
DE-ENERGIZING
CONTACTOR

30 AMP 2 5.3 12.4 1 = 208V/3PH/60HZ - 3 STAGE 3 = PILOT DUTY P.E. W/ 50A


PER STAGE 3 3.5 8.3
U = 480V/3PH/60HZ - 1 STAGE MAG. CONTACTOR
1 17.2 39.8
50 AMP W = 480V/3PH/60HZ - 2 STAGE 4 = PILOT DUTY P.E. W/ 30A
2 8.6 19.9 MERC. CONTACTOR
PER STAGE 3 = 480V/3PH/60HZ - 3 STAGE
3 5.7 13.2
5 = PILOT DUTY P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR


SIZE & TYPE

DOOR INTERLOCK 14.3 33.2

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 17.2 39.8
BLOCK

30 AMP BLOCK 8.6 19.9


FUSE

60 AMP BLOCK 17.2 39.8

1. MAX. K.W. BASED ON 48A, OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.008 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5E0X0

REV.1 5/14/00 PNEUMATIC


PSFH057
- J57 -

66 YORK INTERNATIONAL
FORM AD1T-SECT J

SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT


PRESS. INDEPENDENT, N.C. DAMPER, A.F.S. FAN START, POS. DAMPER CLOSE OFF, REVERSE ACTING STAT, 3 PHASE, PILOT DUTY P.E. SWITCH

SEQUENCE OF OPERATION:
L1 L2 L3
DISCONNECT OCCUPIED MODE:
WHEN THE DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
SWITCH
SENSED BY THE S1 AIR FLOW SWITCH, THE FAN MOTOR
& EP SWITCH ARE ENERGIZED.
FUSING SPACE TEMP WARM (STAT OUTPUT LOW). AT A STAT
OUTPUT OF 3 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
OPTIONAL DISCONNECT SWITCH WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
PANEL WIRING DIAGRAM AND OR FUSING STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
L1 L2 L3 N ON A FURTHER DROP IN SPACE TEMP., PE1 WILL CLOSE
TERMINAL 1 2 3 4 ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
BLOCK
BK WH AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
BK BL
UNOCCUPIED MODE:
BK WHEN MAIN AIR HANDLER IS OFF, THE S1 AIR FLOW SWITCH
STANDARD 1 STAGE HEAT
DEENERGIZES THE FAN & EP SWITCH, CAUSING DAMPER TO
C1-1 G CLOSE.
BK BK

C1-2 ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY


C N0 JOB SPECIFICATIONS.
BK

TC ST.1
BK BK C NO BK NOTE: S1 AIRFLOW SWITCH FACTORY SET TO START FAN AT
S1 5 C1
NC .10"WC TOTAL PRESSURE SENSED AT INLET FLOW PROBE.
PE-1
NC
ST.2
RD C NO RD L1 1
BK BK
C2 BL
C1-1 3 L3
PE-2 RD RD
NC L2 2
ST.3 C2-1
BN C NO BN
C3
OPTIONAL 2 STAGE HEAT
PE-3
NC
BK BK
BK
SC
BL/WH BK L1 1
FM
C1-1
RD RD
L2 2
BK C2-1
EP BN BN

C3-1
BL BL
L3 3
C1-2
N.C. PNEUMATIC DIAGRAM OPTIONAL 3 STAGE HEAT

ACT. (3)C RECOMMENDED FIELD P.E. SWITCH SETTINGS:


(1)NC (2)NO
PE-1 = 8 PSI
EP PE-2 = 10 PSI
BAL. TAPS VEL. CNTRLR PE-3 = 12 PSI
B (RESET BAND=3-8 PSI)
FLOW LO X CONSTANT
M 20 PSI MAIN
PROBE HI Y VOLUME
T TOTAL AIR
R.A. STAT COLD AIR HEAT
FLOW

1 PIPE AIR
S1
AIR

FLOW PLENUM AIR


RESTRICTOR
OR OR 20 PSI MAIN

R.A. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE2 PE1 2 PIPE HOT T-STAT BRANCH PRESSURE (PSIG) COLD
PE3
ROOM ROOM

HEATER COMPONENTS MAX. KW


3 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-3 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 208 V 480 V P = 208V/3PH/60HZ - 1 STAGE 2 = PILOT DUTY P.E. W/ 30A
1 10.7 24.9 R = 208V/3PH/60HZ - 2 STAGE MAG. CONTACTOR
DE-ENERGIZING
CONTACTOR

30 AMP 2 5.3 12.4 1 = 208V/3PH/60HZ - 3 STAGE 3 = PILOT DUTY P.E. W/ 50A


PER STAGE 3 3.5 8.3
U = 480V/3PH/60HZ - 1 STAGE MAG. CONTACTOR
1 17.2 39.8
50 AMP W = 480V/3PH/60HZ - 2 STAGE 4 = PILOT DUTY P.E. W/ 30A
2 8.6 19.9 MERC. CONTACTOR
PER STAGE 3 = 480V/3PH/60HZ - 3 STAGE
3 5.7 13.2
5 = PILOT DUTY P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR


SIZE & TYPE

DOOR INTERLOCK 14.3 33.2

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 17.2 39.8
BLOCK

30 AMP BLOCK 8.6 19.9


FUSE

60 AMP BLOCK 17.2 39.8

1. MAX. K.W. BASED ON 48A, OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.008 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5F0X0

REV.1 5/14/00 PNEUMATIC


PSFH058
- J58 -

YORK INTERNATIONAL 67
SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT
PRESS. INDEPENDENT, N.O. DAMPER, A.F.S. FAN START, POS. DAMPER CLOSE OFF, REVERSE ACTING STAT, 3 PHASE, PILOT DUTY P.E. SWITCH

SEQUENCE OF OPERATION:
L1 L2 L3
DISCONNECT OCCUPIED MODE:
WHEN THE DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
SWITCH
SENSED BY THE S1 AIR FLOW SWITCH, THE FAN MOTOR
& EP SWITCH ARE ENERGIZED.
FUSING SPACE TEMP WARM (STAT OUTPUT LOW). AT A STAT
OUTPUT OF 3 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
OPTIONAL DISCONNECT SWITCH WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
PANEL WIRING DIAGRAM AND OR FUSING STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
L1 L2 L3 N ON A FURTHER DROP IN SPACE TEMP., PE1 WILL CLOSE
TERMINAL 1 2 3 4 ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
BLOCK
BK WH AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
BK BL
UNOCCUPIED MODE:
BK WHEN MAIN AIR HANDLER IS OFF, THE S1 AIR FLOW SWITCH
STANDARD 1 STAGE HEAT
DEENERGIZES THE FAN & EP SWITCH, CAUSING DAMPER TO
C1-1 G CLOSE.
BK BK

C1-2 ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY


C N0 JOB SPECIFICATIONS.
BK

TC ST.1
BK BK C NO BK NOTE: S1 AIRFLOW SWITCH FACTORY SET TO START FAN AT
S1 5 C1
NC .10"WC TOTAL PRESSURE SENSED AT INLET FLOW PROBE.
PE-1
NC
ST.2 BK BK
RD C NO RD L1 1
C2 BL
C1-1 3 L3
RD RD
PE-2 L2 2
NC
ST.3 C2-1
BN C NO BN
C3 OPTIONAL 2 STAGE HEAT
PE-3
NC
BK BK
BK
SC
BL/WH BK L1 1
FM
C1-1
RD RD
L2 2
BK C2-1
EP BN BN

C3-1
BL BL
L3 3
N.O.
PNEUMATIC DIAGRAM C1-2
OPTIONAL 3 STAGE HEAT
ACT. (3)C
(1)NC (2)NO
RECOMMENDED FIELD P.E. SWITCH SETTINGS:
EP
BAL. TAPS VEL. CNTRLR PE-1 = 8 PSI
B (RESET BAND=8-13 PSI) PE-2 = 10 PSI
FLOW LO Y PE-3 = 12 PSI
M 20 PSI MAIN
PROBE HI X
T
CONSTANT
REV. R.A.. STAT VOLUME
FLOW

1 PIPE TOTAL AIR


S1 RELAY
AIR

COLD AIR HEAT


M RESTRICTOR AIR
1
3 OR OR 20 PSI MAIN FLOW PLENUM AIR

R.A.. STAT
2 PIPE
PE3 PE2 PE1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
HOT T-STAT BRANCH PRESSURE (PSIG) COLD
ROOM ROOM

HEATER COMPONENTS MAX. KW


3 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-3 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 208 V 480 V P = 208V/3PH/60HZ - 1 STAGE 2 = PILOT DUTY P.E. W/ 30A
1 10.7 24.9 R = 208V/3PH/60HZ - 2 STAGE MAG. CONTACTOR
DE-ENERGIZING
CONTACTOR

30 AMP 2 5.3 12.4 1 = 208V/3PH/60HZ - 3 STAGE 3 = PILOT DUTY P.E. W/ 50A


PER STAGE 3 3.5 8.3
U = 480V/3PH/60HZ - 1 STAGE MAG. CONTACTOR
1 17.2 39.8
50 AMP W = 480V/3PH/60HZ - 2 STAGE 4 = PILOT DUTY P.E. W/ 30A
2 8.6 19.9 MERC. CONTACTOR
PER STAGE 3 = 480V/3PH/60HZ - 3 STAGE
3 5.7 13.2
5 = PILOT DUTY P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR


SIZE & TYPE

DOOR INTERLOCK 14.3 33.2

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 17.2 39.8
BLOCK

30 AMP BLOCK 8.6 19.9


FUSE

60 AMP BLOCK 17.2 39.8

1. MAX. K.W. BASED ON 48A, OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.016 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5G0X0

REV.1 5/14/00 PNEUMATIC


PSFH059
- J59 -

68 YORK INTERNATIONAL
FORM AD1T-SECT J

SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT


PRESS. INDEPENDENT, N.C. DAMPER, A.F.S. FAN START, POS. DAMPER CLOSE OFF, DIRECT ACTING STAT, 3 PHASE, PILOT DUTY P.E. SWITCH

SEQUENCE OF OPERATION:

L1 L2 L3 OCCUPIED MODE:
DISCONNECT WHEN THE DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
SWITCH SENSED BY THE S1 AIR FLOW SWITCH, THE FAN MOTOR
& EP SWITCH ARE ENERGIZED.
SPACE TEMP WARM (STAT OUTPUT HI). AT A STAT
FUSING OUTPUT OF 13 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
OPTIONAL DISCONNECT SWITCH
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
PANEL WIRING DIAGRAM AND OR FUSING
CONTROLLING AT ITS MINIMUM.
L1 L2 L3 N ON A FURTHER DROP IN SPACE TEMP., PE1 WILL CLOSE
TERMINAL ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
1 2 3 4
BLOCK AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
BK WH

BK BL
UNOCCUPIED MODE:
WHEN MAIN AIR HANDLER IS OFF, THE S1 AIR FLOW SWITCH
BK STANDARD 1 STAGE HEAT DEENERGIZES THE FAN & EP SWITCH, CAUSING DAMPER TO
C1-1 G CLOSE.
BK BK
ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
C1-2
JOB SPECIFICATIONS.
C N0 BK

TC ST.1 NOTE: S1 AIRFLOW SWITCH FACTORY SET TO START FAN AT


BK BK C NO BK
S1 5 C1 .10"WC TOTAL PRESSURE SENSED AT INLET FLOW PROBE.
NC
PE-1
NC
ST.2 BK BK
RD C NO RD L1 1
C2 BL
C1-1 3 L3
PE-2 L2 2
RD RD
NC
ST.3 C2-1
BN C NO BN
C3 OPTIONAL 2 STAGE HEAT
PE-3
NC
BK BL/WH BK
SC FM L1 1
BK BK

C1-1
RD RD
BK
L2 2
EP C2-1
BN BN

C3-1
BL BL
N.C.
PNEUMATIC DIAGRAM L3 3
C1-2
ACT. (3)C OPTIONAL 3 STAGE HEAT
(1)NC (2)NO
EP RECOMMENDED FIELD P.E. SWITCH SETTINGS:
BAL. TAPS VEL. CNTRLR PE-1 = 8 PSI
B (RESET BAND=3-8 PSI) PE-2 = 6 PSI
FLOW LO X PE-3 = 4 PSI
M 20 PSI MAIN
PROBE HI Y
T CONSTANT
REV. D.A.. STAT VOLUME
FLOW

TOTAL AIR
S1 RELAY 1 PIPE
AIR

HEAT COLD AIR


M RESTRICTOR AIR
1 FLOW PLENUM AIR
3 OR OR 20 PSI MAIN

D.A.. STAT
2 PIPE
PE3 PE2 PE1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
COLD T-STAT BRANCH PRESSURE (PSIG) HOT
ROOM ROOM

HEATER COMPONENTS MAX. KW


3 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-3 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 208 V 480 V P = 208V/3PH/60HZ - 1 STAGE 2 = PILOT DUTY P.E. W/ 30A
1 10.7 24.9 R = 208V/3PH/60HZ - 2 STAGE MAG. CONTACTOR
DE-ENERGIZING
CONTACTOR

30 AMP 2 5.3 12.4 1 = 208V/3PH/60HZ - 3 STAGE 3 = PILOT DUTY P.E. W/ 50A


PER STAGE 3 3.5 8.3
U = 480V/3PH/60HZ - 1 STAGE MAG. CONTACTOR
1 17.2 39.8
50 AMP W = 480V/3PH/60HZ - 2 STAGE 4 = PILOT DUTY P.E. W/ 30A
2 8.6 19.9 MERC. CONTACTOR
PER STAGE 3 = 480V/3PH/60HZ - 3 STAGE
3 5.7 13.2
5 = PILOT DUTY P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR


SIZE & TYPE

DOOR INTERLOCK 14.3 33.2

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 17.2 39.8
BLOCK

30 AMP BLOCK 8.6 19.9


FUSE

60 AMP BLOCK 17.2 39.8

1. MAX. K.W. BASED ON 48A, OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.016 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5H0X0

REV.1 5/14/00 PNEUMATIC


PSFH060
- J60 -

YORK INTERNATIONAL 69
SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT
P.I., N.O. DAMPER, A.F.S. FAN START, UNOCCUPIED MODE, POS. DAMPER CLOSE OFF, D.A. STAT, 1 PHASE, LOAD BEARING P.E. SWITCH

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V
OCCUPIED MODE:
DISCONNECT WHEN THE DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
SWITCH SENSED BY THE S1 AIR FLOW SWITCH, THE FAN MOTOR
AND EP SWITCH ARE ENERGIZED.
FUSING SPACE TEMP WARM (STAT OUTPUT HI). AT A STAT
OUTPUT OF 13 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
OPTIONAL DISCONNECT SWITCH WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
AND OR FUSING STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
PANEL WIRING DIAGRAM CONTROLLING AT ITS MINIMUM.
ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
L1 (N) = 120V & 277V ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
TERMINAL 1 2 AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
BLOCK
BK WH UNOCCUPIED MODE:
WHEN MAIN AIR HANDLER IS OFF, THE S1 AIR FLOW SWITCH
C N0 BK DEENERGIZES THE FAN & EP SWITCH, CAUSING DAMPER TO
C NO CLOSE. AS TEMP. DROPS PE1 ENERGIZES THE FAN.
S1 BK BK WH G
5
NC ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
PE-2 STANDARD 1
C JOB SPECIFICATIONS.
NO NC STAGE HEAT
RD RD C NO RD
PE-1
NC OPTIONAL 2
PE-3 NOTE: S1 AIRFLOW SWITCH FACTORY SET TO START FAN AT
NC STAGE HEAT
.10"WC TOTAL PRESSURE SENSED AT INLET FLOW PROBE.
BN C NO BN

OPTIONAL 3
PE-4
NC STAGE HEAT

BK BL/WH BK
SC FM

EP

N.O. PNEUMATIC DIAGRAM


RECOMMENDED FIELD P.E. SWITCH SETTINGS:
ACT. 3(C)
(NC)1 2(NO) PE-1 = 8 PSI
EP PE-2 = 8 PSI
PE-3 = 6 PSI
BAL. TAPS VEL. CNTRLR PE-4 = 4 PSI
B (RESET BAND=8-13 PSI)
FLOW LO Y CONSTANT
M 20 PSI MAIN
PROBE HI X VOLUME
T TOTAL AIR
D.A.. STAT HEAT COLD AIR
FLOW

S1 1 PIPE AIR (UNOCCUPIED)


AIR

FLOW PLENUM AIR


FAN STARTS
RESTRICTOR
OR OR (FIELD CALIB.)
20 PSI MAIN

D.A.. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE4 PE3 PE2 PE1 2 PIPE COLD T-STAT BRANCH PRESSURE (PSIG) HOT
ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE 1 = LOAD BEARING P.E.
SWITCH

1 1.6 3.9 E = 120V/1PH/60HZ - 2 STAGE


LOAD BEARING
P.E.

PER STAGE 2 0.8 1.9 5 = 120V/1PH/60HZ - 3 STAGE


3 0.5 1.3
K = 277V/1PH/60HZ - 1 STAGE
DISCONNECT

L = 277V/1PH/60HZ - 2 STAGE
SIZE & TYPE

DNF-40 1.6 3.9 Y = 277V/1PH/60HZ - 3 STAGE


DOOR INTERLOCK
BLOCK
FUSE

30 AMP BLOCK 1.6 3.9

1. MAX. K.W. BASED ON A.F.S. MAX LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.008 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5E070

REV.1 5/14/00 PNEUMATIC


PSFH061
- J61 -

70 YORK INTERNATIONAL
FORM AD1T-SECT J

SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT


P.I., N.C. DAMPER, A.F.S. FAN START, UNOCCUPIED MODE, POS. DAMPER CLOSE OFF, R.A. STAT, 1 PHASE, LOAD BEARING P.E. SWITCH

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V
OCCUPIED MODE:
DISCONNECT WHEN THE DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
SWITCH SENSED BY THE S1 AIR FLOW SWITCH, THE FAN MOTOR
AND EP SWITCH ARE ENERGIZED.
FUSING SPACE TEMP WARM (STAT OUTPUT LOW). AT A STAT
OUTPUT OF 3 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
OPTIONAL DISCONNECT SWITCH WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
AND OR FUSING STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
PANEL WIRING DIAGRAM CONTROLLING AT ITS MINIMUM.
ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
L1 (N) = 120V & 277V ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
TERMINAL 1 2 AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
BLOCK
BK WH UNOCCUPIED MODE:
WHEN MAIN AIR HANDLER IS OFF, THE S1 AIR FLOW SWITCH
C N0 BK DEENERGIZES THE FAN & EP SWITCH, CAUSING DAMPER TO
C NO CLOSE. AS TEMP. DROPS PE1 ENERGIZES THE FAN.
S1 BK BK WH G
5
NC ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
PE-2 STANDARD 1
C JOB SPECIFICATIONS.
NO RD NC STAGE HEAT
RD C NO RD
PE-1
NC OPTIONAL 2
PE-3 NOTE: S1 AIRFLOW SWITCH FACTORY SET TO START FAN AT
NC STAGE HEAT
.10"WC TOTAL PRESSURE SENSED AT INLET FLOW PROBE.
BN C NO BN

OPTIONAL 3
PE-4
NC STAGE HEAT

BK BL/WH BK
SC FM

EP

N.C. PNEUMATIC DIAGRAM RECOMMENDED FIELD P.E. SWITCH SETTINGS:


ACT. 3(C) PE-1 = 8 PSI
(NC)1 2(NO) PE-2 = 8 PSI
EP PE-3 = 10 PSI
PE-4 = 12 PSI
BAL. TAPS VEL. CNTRLR
B (RESET BAND=3-8 PSI) CONSTANT
FLOW LO X
M 20 PSI MAIN VOLUME
PROBE HI Y TOTAL AIR
T
COLD AIR HEAT
R.A. STAT AIR
FLOW

(UNOCCUPIED)
S1 1 PIPE FLOW PLENUM AIR
AIR

FAN STARTS
RESTRICTOR (FIELD CALIB.)
OR OR 20 PSI MAIN

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
R.A. STAT HOT T-STAT BRANCH PRESSURE (PSIG) COLD
PE4 PE3 PE2 PE1 2 PIPE ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE 1 = LOAD BEARING P.E.
SWITCH

1 1.6 3.9 E = 120V/1PH/60HZ - 2 STAGE


LOAD BEARING
P.E.

PER STAGE 2 0.8 1.9 5 = 120V/1PH/60HZ - 3 STAGE


3 0.5 1.3
K = 277V/1PH/60HZ - 1 STAGE
DISCONNECT

L = 277V/1PH/60HZ - 2 STAGE
SIZE & TYPE

DNF-40 1.6 3.9 Y = 277V/1PH/60HZ - 3 STAGE


DOOR INTERLOCK
BLOCK
FUSE

30 AMP BLOCK 1.6 3.9

1. MAX. K.W. BASED ON A.F.S. MAX LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.008 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5F070

REV.1 5/14/00 PNEUMATIC


PSFH062
- J62 -

YORK INTERNATIONAL 71
SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT
P.I., N.O. DAMPER, A.F.S. FAN START, UNOCCUPIED MODE, POS. DAMPER CLOSE OFF, R.A. STAT, 1 PHASE, LOAD BEARING P.E. SWITCH

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V
DISCONNECT OCCUPIED MODE:
SWITCH WHEN THE DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
SENSED BY THE S1 AIR FLOW SWITCH, THE FAN MOTOR
& EP SWITCH ARE ENERGIZED.
FUSING SPACE TEMP WARM (STAT OUTPUT LOW). AT A STAT
OUTPUT OF 3 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
OPTIONAL DISCONNECT SWITCH WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
AND OR FUSING
PANEL WIRING DIAGRAM STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
L1 (N) = 120V & 277V ON A FURTHER DROP IN SPACE TEMP., PE1 WILL CLOSE
TERMINAL ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
1 2
BLOCK
BK WH
AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.

C N0 UNOCCUPIED MODE:
BK WHEN MAIN AIR HANDLER IS OFF, THE S1 AIR FLOW SWITCH
DEENERGIZES THE FAN & EP SWITCH, CAUSING DAMPER TO
S1 BK C NO WH G CLOSE.
NC 5
C NO STANDARD 1
PE-2 ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
NC STAGE HEAT
JOB SPECIFICATIONS.
PE-1 RD C NO RD
NC NOTE: S1 AIRFLOW SWITCH FACTORY SET TO START FAN AT
PE-3 OPTIONAL 2
.10"WC TOTAL PRESSURE SENSED AT INLET FLOW PROBE.
NC STAGE HEAT
BN C NO BN

PE-4 OPTIONAL 3
NC STAGE HEAT

BK BL/WH BK
SC FM

BK
EP

N.O.
PNEUMATIC DIAGRAM
ACT. (3)C RECOMMENDED FIELD P.E. SWITCH SETTINGS:
(1)NC (2)NO
PE-1 = 8 PSI
EP
PE-2 = 8 PSI
BAL. TAPS VEL. CNTRLR PE-3 = 10 PSI
B (RESET BAND=8-13 PSI) PE-4 = 12 PSI
FLOW LO Y
M 20 PSI MAIN
PROBE HI X CONSTANT
T
VOLUME
REV. R.A.. STAT TOTAL AIR
FLOW

S1 RELAY 1 PIPE HEAT


AIR

COLD AIR
AIR
M RESTRICTOR PLENUM AIR
1 FLOW
3 OR OR 20 PSI MAIN

R.A.. STAT
2 PIPE 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE4 PE3 PE2 PE1 HOT T-STAT BRANCH PRESSURE (PSIG) COLD
ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE 1 = LOAD BEARING P.E.
MAG. CONTACTOR INTERLOCK
SWITCH

1 1.6 3.9 E = 120V/1PH/60HZ - 2 STAGE


LOAD BEARING
P.E.

2 0.8 1.9 5 = 120V/1PH/60HZ - 3 STAGE


PER STAGE 3 0.5 1.3
K = 277V/1PH/60HZ - 1 STAGE
DISCONNECT

L = 277V/1PH/60HZ - 2 STAGE
SIZE & TYPE

DNF-40 Y = 277V/1PH/60HZ - 3 STAGE


DOOR INTERLOCK 4.8 11.0
BLOCK
FUSE

30 AMP BLOCK 1.6 3.9

1. MAX. K.W. BASED ON 48A, P.E., OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.016 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5G070

REV.1 5/14/00 PNEUMATIC


PSFH063
- J63 -

72 YORK INTERNATIONAL
FORM AD1T-SECT J

SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT


P.I., N.O. DAMPER, A.F.S. FAN START, UNOCCUPIED MODE, POS. DAMPER CLOSE OFF, R.A. STAT, 1 PHASE, LOAD BEARING P.E. SWITCH

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V
DISCONNECT OCCUPIED MODE:
SWITCH WHEN THE DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
SENSED BY THE S1 AIR FLOW SWITCH, THE FAN MOTOR
& EP SWITCH ARE ENERGIZED.
FUSING SPACE TEMP WARM (STAT OUTPUT HI). AT A STAT
OUTPUT OF 13 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
OPTIONAL DISCONNECT SWITCH WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
AND OR FUSING
PANEL WIRING DIAGRAM STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
L1 (N) = 120V & 277V ON A FURTHER DROP IN SPACE TEMP., PE1 WILL CLOSE
TERMINAL ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
1 2
BLOCK
BK WH
AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.

C N0 UNOCCUPIED MODE:
BK WHEN MAIN AIR HANDLER IS OFF, THE S1 AIR FLOW SWITCH
DEENERGIZES THE FAN & EP SWITCH, CAUSING DAMPER TO
S1 BK C NO BK WH G CLOSE.
NC 5
C NO STANDARD 1
PE-2 ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
NC STAGE HEAT
JOB SPECIFICATIONS.
PE-1 RD C NO RD
NC NOTE: S1 AIRFLOW SWITCH FACTORY SET TO START FAN AT
PE-3 OPTIONAL 2
.10"WC TOTAL PRESSURE SENSED AT INLET FLOW PROBE.
NC STAGE HEAT
BN C NO BN

PE-4 OPTIONAL 3
NC STAGE HEAT

BK BL/WH BK
SC FM

BK
EP

N.C.
PNEUMATIC DIAGRAM
ACT. (3)C RECOMMENDED FIELD P.E. SWITCH SETTINGS:
(1)NC (2)NO
PE-1 = 8 PSI
EP
PE-2 = 8 PSI
BAL. TAPS VEL. CNTRLR PE-3 = 6 PSI
B (RESET BAND=3-8 PSI) PE-4 = 4 PSI
FLOW LO X
M 20 PSI MAIN
PROBE HI Y CONSTANT
T
VOLUME
REV. D.A.. STAT TOTAL AIR
FLOW

S1 RELAY 1 PIPE HEAT


AIR

COLD AIR
AIR
M RESTRICTOR PLENUM AIR
1 FLOW
3 OR OR 20 PSI MAIN

D.A.. STAT
2 PIPE 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE4 PE3 PE2 PE1 COLD T-STAT BRANCH PRESSURE (PSIG) HOT
ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE 1 = LOAD BEARING P.E.
MAG. CONTACTOR INTERLOCK
SWITCH

1 1.6 3.9 E = 120V/1PH/60HZ - 2 STAGE


LOAD BEARING
P.E.

2 0.8 1.9 5 = 120V/1PH/60HZ - 3 STAGE


PER STAGE 3 0.5 1.3
K = 277V/1PH/60HZ - 1 STAGE
DISCONNECT

L = 277V/1PH/60HZ - 2 STAGE
SIZE & TYPE

DNF-40 Y = 277V/1PH/60HZ - 3 STAGE


DOOR INTERLOCK 4.8 11.0
BLOCK
FUSE

30 AMP BLOCK 1.6 3.9

1. MAX. K.W. BASED ON 48A, P.E., OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.016 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5H070

REV.1 5/14/00 PNEUMATIC


PSFH064
- J64 -

YORK INTERNATIONAL 73
SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT
P.I., N.O. DAMPER, A.F.S. FAN START, UNOCCUPIED MODE, POS. DAMPER CLOSE OFF, D.A. STAT, 1 PHASE, LOAD BEARING P.E. SWITCH W/ CONT. INTRLK.

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V
OCCUPIED MODE:
DISCONNECT WHEN THE DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
SWITCH SENSED BY THE S1 AIR FLOW SWITCH, THE FAN MOTOR
AND EP SWITCH ARE ENERGIZED.
FUSING SPACE TEMP WARM (STAT OUTPUT HI). AT A STAT
OUTPUT OF 13 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
OPTIONAL DISCONNECT SWITCH WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
AND OR FUSING STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
PANEL WIRING DIAGRAM CONTROLLING AT ITS MINIMUM.
ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
L1 (N) = 120V & 277V
ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
TERMINAL 1 2
BLOCK AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
BK WH
UNOCCUPIED MODE:
WHEN MAIN AIR HANDLER IS OFF, THE S1 AIR FLOW SWITCH
BK BK WH
DEENERGIZES THE FAN & EP SWITCH, CAUSING DAMPER TO
C1-1 STANDARD 1 CLOSE. AS TEMP. DROPS PE1 ENERGIZES THE FAN.
G
STAGE HEAT ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
RD C NO RD JOB SPECIFICATIONS.

PE-3 OPTIONAL 2
NC STAGE HEAT
BN C NO BN
NOTE: S1 AIRFLOW SWITCH FACTORY SET TO START FAN AT
OPTIONAL 3 .10"WC TOTAL PRESSURE SENSED AT INLET FLOW PROBE.
PE-4
C N0 BK NC STAGE HEAT
(WHEN REQ.)
BK
TC BK C NO BK
S1 5 C1
NC
C PE-2
NO NC
RD BK BL/WH BK
PE-1 SC FM
NC

BK
EP

N.O. PNEUMATIC DIAGRAM


RECOMMENDED FIELD P.E. SWITCH SETTINGS:
ACT. 3(C)
(NC)1 2(NO) PE-1 = 8 PSI
EP PE-2 = 8 PSI
PE-3 = 6 PSI
BAL. TAPS VEL. CNTRLR PE-4 = 4 PSI
B (RESET BAND=8-13 PSI)
FLOW LO Y CONSTANT
M 20 PSI MAIN
PROBE HI X VOLUME
T TOTAL AIR
D.A.. STAT HEAT COLD AIR
FLOW

S1 1 PIPE AIR (UNOCCUPIED)


AIR

FLOW PLENUM AIR


FAN STARTS
RESTRICTOR
OR OR (FIELD CALIB.)
20 PSI MAIN

D.A.. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE4 PE3 PE2 PE1 2 PIPE COLD T-STAT BRANCH PRESSURE (PSIG) HOT
ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE J = LOAD BEARING P.E. W/ 30A
1 3.6 8.3 E = 120V/1PH/60HZ - 2 STAGE MAG. CONTACTOR INTERLOCK
30 AMP CONT.
LOAD BRG. PE

2 1.8 4.1 5 = 120V/1PH/60HZ - 3 STAGE K = LOAD BEARING P.E. W/ 50A


W/ INTRLK

PER STAGE 3 1.2 2.7


K = 277V/1PH/60HZ - 1 STAGE MAG. CONTACTOR INTERLOCK
1 5.7 13.2
50 AMP CONT. L = 277V/1PH/60HZ - 2 STAGE L = LOAD BEARING P.E. W/ 30A
2 2.8 6.6 MERC. CONTACTOR INTERLOCK
PER STAGE Y = 277V/1PH/60HZ - 3 STAGE
3 1.9 4.4
M = LOAD BEARING P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR INTERLOCK


SIZE & TYPE

DOOR INTERLOCK 4.8 11.0

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 5.7 13.2
BLOCK

30 AMP BLOCK
FUSE

2.8 6.6

60 AMP BLOCK 5.7 13.2

1. MAX. K.W. BASED ON 48A, P.E., OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.008 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5E070

REV.1 5/14/00 PNEUMATIC


PSFH065
- J65 -

74 YORK INTERNATIONAL
FORM AD1T-SECT J

SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT


P.I., N.C. DAMPER, A.F.S. FAN START, UNOCCUPIED MODE, POS. DAMPER CLOSE OFF, R.A. STAT, 1 PHASE, LOAD BEARING P.E. SWITCH W/ CONT. INTRLK.

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V
OCCUPIED MODE:
DISCONNECT WHEN THE DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
SWITCH SENSED BY THE S1 AIR FLOW SWITCH, THE FAN MOTOR
AND EP SWITCH ARE ENERGIZED.
FUSING SPACE TEMP WARM (STAT OUTPUT LOW). AT A STAT
OUTPUT OF 3 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
OPTIONAL DISCONNECT SWITCH WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
AND OR FUSING STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
PANEL WIRING DIAGRAM CONTROLLING AT ITS MINIMUM.
ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
L1 (N) = 120V & 277V
ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
TERMINAL 1 2
BLOCK AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
BK WH
UNOCCUPIED MODE:
WHEN MAIN AIR HANDLER IS OFF, THE S1 AIR FLOW SWITCH
BK BK WH
DEENERGIZES THE FAN & EP SWITCH, CAUSING DAMPER TO
C1-1 STANDARD 1 CLOSE. AS TEMP. DROPS PE1 ENERGIZES THE FAN.
G
STAGE HEAT ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
RD C NO RD JOB SPECIFICATIONS.

PE-3 OPTIONAL 2
NC STAGE HEAT
BN C NO BN
NOTE: S1 AIRFLOW SWITCH FACTORY SET TO START FAN AT
OPTIONAL 3 .10"WC TOTAL PRESSURE SENSED AT INLET FLOW PROBE.
PE-4
C N0 BK NC STAGE HEAT
(WHEN REQ.)
BK
TC BK C NO BK
S1 5 C1
NC
C PE-2
NO NC
RD BK BL/WH BK
PE-1 SC FM
NC

BK
EP

N.C. PNEUMATIC DIAGRAM RECOMMENDED FIELD P.E. SWITCH SETTINGS:


ACT. 3(C) PE-1 = 8 PSI
(NC)1 2(NO) PE-2 = 8 PSI
EP PE-3 = 10 PSI
PE-4 = 12 PSI
BAL. TAPS VEL. CNTRLR
B (RESET BAND=3-8 PSI) CONSTANT
FLOW LO X
M 20 PSI MAIN VOLUME
PROBE HI Y TOTAL AIR
T
COLD AIR HEAT
R.A. STAT AIR
FLOW

(UNOCCUPIED)
S1 1 PIPE FLOW PLENUM AIR
AIR

FAN STARTS
RESTRICTOR (FIELD CALIB.)
OR OR 20 PSI MAIN

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
R.A. STAT HOT T-STAT BRANCH PRESSURE (PSIG) COLD
PE4 PE3 PE2 PE1 2 PIPE ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE J = LOAD BEARING P.E. W/ 30A
1 3.6 8.3 E = 120V/1PH/60HZ - 2 STAGE MAG. CONTACTOR INTERLOCK
30 AMP CONT.
LOAD BRG. PE

2 1.8 4.1 5 = 120V/1PH/60HZ - 3 STAGE K = LOAD BEARING P.E. W/ 50A


W/ INTRLK

PER STAGE 3 1.2 2.7


K = 277V/1PH/60HZ - 1 STAGE MAG. CONTACTOR INTERLOCK
1 5.7 13.2
50 AMP CONT. L = 277V/1PH/60HZ - 2 STAGE L = LOAD BEARING P.E. W/ 30A
2 2.8 6.6 MERC. CONTACTOR INTERLOCK
PER STAGE Y = 277V/1PH/60HZ - 3 STAGE
3 1.9 4.4
M = LOAD BEARING P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR INTERLOCK


SIZE & TYPE

DOOR INTERLOCK 4.8 11.0

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 5.7 13.2
BLOCK

30 AMP BLOCK
FUSE

2.8 6.6

60 AMP BLOCK 5.7 13.2

1. MAX. K.W. BASED ON 48A, P.E., OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.008 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5F070

REV.1 5/21/00 PNEUMATIC


PSFH066
- J66 -

YORK INTERNATIONAL 75
SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT
P.I., N.O. DAMPER, A.F.S. FAN START, UNOCCUPIED MODE, POS. DAMPER CLOSE OFF, R.A. STAT, 1 PHASE, LOAD BEARING P.E. SWITCH W/ CONT. INTRLK.

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V
OCCUPIED MODE:
DISCONNECT WHEN THE DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
SWITCH SENSED BY THE S1 AIR FLOW SWITCH, THE FAN MOTOR
AND EP SWITCH ARE ENERGIZED.
FUSING SPACE TEMP WARM (STAT OUTPUT LOW). AT A STAT
OUTPUT OF 3 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
OPTIONAL DISCONNECT SWITCH WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
AND OR FUSING STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
PANEL WIRING DIAGRAM CONTROLLING AT ITS MINIMUM.
ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
L1 (N) = 120V & 277V
ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
TERMINAL 1 2
BLOCK AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
BK WH
UNOCCUPIED MODE:
WHEN MAIN AIR HANDLER IS OFF, THE S1 AIR FLOW SWITCH
BK BK WH
DEENERGIZES THE FAN & EP SWITCH, CAUSING DAMPER TO
C1-1 STANDARD 1 CLOSE. AS TEMP. DROPS PE1 ENERGIZES THE FAN.
G
STAGE HEAT ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
RD C NO RD JOB SPECIFICATIONS.

PE-3 OPTIONAL 2
NC STAGE HEAT
BN C NO BN
NOTE: S1 AIRFLOW SWITCH FACTORY SET TO START FAN AT
OPTIONAL 3 .10"WC TOTAL PRESSURE SENSED AT INLET FLOW PROBE.
PE-4
C N0 BK NC STAGE HEAT
(WHEN REQ.)
BK
TC BK C NO BK
S1 5 C1
NC
C PE-2
NO NC
RD BK BL/WH BK
PE-1 SC FM
NC

BK
EP

N.O.
PNEUMATIC DIAGRAM
RECOMMENDED FIELD P.E. SWITCH SETTINGS:
ACT. 3(C)
(NC)1 2(NO) PE-1 = 8 PSI
EP PE-2 = 8 PSI
PE-3 = 10 PSI
BAL. TAPS VEL. CNTRLR PE-4 = 12 PSI
B (RESET BAND=8-13 PSI)
FLOW LO Y
M 20 PSI MAIN CONSTANT
PROBE HI X
T VOLUME
TOTAL AIR
REV. R.A.. STAT HEAT
FLOW

COLD AIR
S1 RELAY 1 PIPE AIR
AIR

(UNOCCUPIED)
FLOW PLENUM AIR
M RESTRICTOR FAN STARTS
1 (FIELD CALIB.)
3 OR OR 20 PSI MAIN

R.A.. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
2 PIPE HOT T-STAT BRANCH PRESSURE (PSIG) COLD
PE4 PE3 PE2 PE1
ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE J = LOAD BEARING P.E. W/ 30A
1 3.6 8.3 E = 120V/1PH/60HZ - 2 STAGE MAG. CONTACTOR INTERLOCK
30 AMP CONT.
LOAD BRG. PE

2 1.8 4.1 5 = 120V/1PH/60HZ - 3 STAGE K = LOAD BEARING P.E. W/ 50A


W/ INTRLK

PER STAGE 3 1.2 2.7


K = 277V/1PH/60HZ - 1 STAGE MAG. CONTACTOR INTERLOCK
1 5.7 13.2
50 AMP CONT. L = 277V/1PH/60HZ - 2 STAGE L = LOAD BEARING P.E. W/ 30A
2 2.8 6.6 MERC. CONTACTOR INTERLOCK
PER STAGE Y = 277V/1PH/60HZ - 3 STAGE
3 1.9 4.4
M = LOAD BEARING P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR INTERLOCK


SIZE & TYPE

DOOR INTERLOCK 4.8 11.0

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 5.7 13.2
BLOCK

30 AMP BLOCK
FUSE

2.8 6.6

60 AMP BLOCK 5.7 13.2

1. MAX. K.W. BASED ON 48A, P.E., OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.016 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5G070

REV.1 5/21/00 PNEUMATIC


PSFH067
- J67 -

76 YORK INTERNATIONAL
FORM AD1T-SECT J

SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT


P.I., N.C. DAMPER, A.F.S. FAN START, UNOCCUPIED MODE, POS. DAMPER CLOSE OFF, D.A. STAT, 1 PHASE, LOAD BEARING P.E. SWITCH W/ CONT. INTRLK.

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V
OCCUPIED MODE:
DISCONNECT WHEN THE DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
SWITCH SENSED BY THE S1 AIR FLOW SWITCH, THE FAN MOTOR
AND EP SWITCH ARE ENERGIZED.
FUSING SPACE TEMP WARM (STAT OUTPUT HI). AT A STAT
OUTPUT OF 13 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
OPTIONAL DISCONNECT SWITCH WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
AND OR FUSING STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
PANEL WIRING DIAGRAM CONTROLLING AT ITS MINIMUM.
ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
L1 (N) = 120V & 277V
ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
TERMINAL 1 2
BLOCK AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
BK WH
UNOCCUPIED MODE:
WHEN MAIN AIR HANDLER IS OFF, THE S1 AIR FLOW SWITCH
BK BK WH
DEENERGIZES THE FAN & EP SWITCH, CAUSING DAMPER TO
C1-1 STANDARD 1 CLOSE. AS TEMP. DROPS PE1 ENERGIZES THE FAN.
G
STAGE HEAT ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
RD C NO RD JOB SPECIFICATIONS.

PE-3 OPTIONAL 2
NC STAGE HEAT
BN C NO BN
NOTE: S1 AIRFLOW SWITCH FACTORY SET TO START FAN AT
OPTIONAL 3 .10"WC TOTAL PRESSURE SENSED AT INLET FLOW PROBE.
PE-4
C N0 BK NC STAGE HEAT
(WHEN REQ.)
BK
TC BK C NO BK
S1 5 C1
NC
C PE-2
NO NC
RD BK BL/WH BK
PE-1 SC FM
NC

BK
EP

N.C.
PNEUMATIC DIAGRAM
RECOMMENDED FIELD P.E. SWITCH SETTINGS:
ACT. 3(C)
(NC)1 2(NO) PE-1 = 8 PSI
EP PE-2 = 8 PSI
PE-3 = 6 PSI
BAL. TAPS VEL. CNTRLR PE-4 = 4 PSI
B (RESET BAND=3-8 PSI)
FLOW LO X CONSTANT
M 20 PSI MAIN
PROBE HI Y VOLUME
T TOTAL AIR
REV. D.A.. STAT HEAT COLD AIR
FLOW

S1 RELAY 1 PIPE AIR (UNOCCUPIED)


AIR

FLOW PLENUM AIR


M FAN STARTS
1 RESTRICTOR
3 OR OR (FIELD CALIB.)
20 PSI MAIN

D.A.. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
2 PIPE COLD T-STAT BRANCH PRESSURE (PSIG) HOT
PE4 PE3 PE2 PE1 ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE J = LOAD BEARING P.E. W/ 30A
1 3.6 8.3 E = 120V/1PH/60HZ - 2 STAGE MAG. CONTACTOR INTERLOCK
30 AMP CONT.
LOAD BRG. PE

2 1.8 4.1 5 = 120V/1PH/60HZ - 3 STAGE K = LOAD BEARING P.E. W/ 50A


W/ INTRLK

PER STAGE 3 1.2 2.7


K = 277V/1PH/60HZ - 1 STAGE MAG. CONTACTOR INTERLOCK
1 5.7 13.2
50 AMP CONT. L = 277V/1PH/60HZ - 2 STAGE L = LOAD BEARING P.E. W/ 30A
2 2.8 6.6 MERC. CONTACTOR INTERLOCK
PER STAGE Y = 277V/1PH/60HZ - 3 STAGE
3 1.9 4.4
M = LOAD BEARING P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR INTERLOCK


SIZE & TYPE

DOOR INTERLOCK 4.8 11.0

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 5.7 13.2
BLOCK

30 AMP BLOCK
FUSE

2.8 6.6

60 AMP BLOCK 5.7 13.2

1. MAX. K.W. BASED ON 48A, P.E., OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.016 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5H070

REV.1 5/21/00 PNEUMATIC


PSFH068
- J68 -

YORK INTERNATIONAL 77
SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT
P.I., N.O. DAMPER, A.F.S. FAN START, UNOCCUPIED MODE, POS. DAMPER CLOSE OFF, D.A. STAT, 1 PHASE, PILOT DUTY P.E. SWITCH

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V
OCCUPIED MODE:
DISCONNECT WHEN THE DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
SWITCH SENSED BY THE S1 AIR FLOW SWITCH, THE FAN MOTOR
AND EP SWITCH ARE ENERGIZED.
FUSING SPACE TEMP WARM (STAT OUTPUT HI). AT A STAT
OUTPUT OF 13 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
OPTIONAL DISCONNECT SWITCH WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
AND OR FUSING STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
PANEL WIRING DIAGRAM CONTROLLING AT ITS MINIMUM.
ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
L1 (N) = 120V & 277V
ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
TERMINAL 1 2
BLOCK AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
BK WH
UNOCCUPIED MODE:
WHEN MAIN AIR HANDLER IS OFF, THE S1 AIR FLOW SWITCH
BK BK WH
DEENERGIZES THE FAN & EP SWITCH, CAUSING DAMPER TO
C1-1 STANDARD 1 ST. HEAT CLOSE. AS TEMP. DROPS PE1 ENERGIZES THE FAN.
G
RD RD
ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
OPTIONAL 2 ST. HEAT JOB SPECIFICATIONS.
C2-1
BN BN
C N0 BK OPTIONAL 3 ST. HEAT
C3-1
TC C NO ST.1
BK BK BK
S1 5 C1 NOTE: S1 AIRFLOW SWITCH FACTORY SET TO START FAN AT
NC .10"WC TOTAL PRESSURE SENSED AT INLET FLOW PROBE.
C PE-2
NO (WHEN REQ.) NC
RD
ST.2
RD C NO RD
PE-1 C2
NC
PE-3
NC
ST.3
BN C NO BN
C3
PE-4
NC
BK BL/WH BK
SC FM

BK
EP

N.O. PNEUMATIC DIAGRAM


RECOMMENDED FIELD P.E. SWITCH SETTINGS:
ACT. 3(C)
(NC)1 2(NO) PE-1 = 8 PSI
EP PE-2 = 8 PSI
PE-3 = 6 PSI
BAL. TAPS VEL. CNTRLR PE-4 = 4 PSI
B (RESET BAND=8-13 PSI)
FLOW LO Y CONSTANT
M 20 PSI MAIN
PROBE HI X VOLUME
T TOTAL AIR
D.A.. STAT HEAT COLD AIR
FLOW

S1 1 PIPE AIR (UNOCCUPIED)


AIR

FLOW PLENUM AIR


FAN STARTS
RESTRICTOR
OR OR (FIELD CALIB.)
20 PSI MAIN

D.A.. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE4 PE3 PE2 PE1 2 PIPE COLD T-STAT BRANCH PRESSURE (PSIG) HOT
ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE 2 = PILOT DUTY P.E. W/ 30A
1 3.6 8.3 E = 120V/1PH/60HZ - 2 STAGE MAG. CONTACTOR
DE-ENERGIZING
CONTACTOR

30 AMP 2 2.8 6.6 5 = 120V/1PH/60HZ - 3 STAGE 3 = PILOT DUTY P.E. W/ 50A


CONTACTOR 3 1.9 4.4
K = 277V/1PH/60HZ - 1 STAGE MAG. CONTACTOR
1 5.7 13.2
50 AMP L = 277V/1PH/60HZ - 2 STAGE 4 = PILOT DUTY P.E. W/ 30A
2 2.8 6.6 MERC. CONTACTOR
CONTACTOR Y = 277V/1PH/60HZ - 3 STAGE
3 1.9 4.4
5 = PILOT DUTY P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR


SIZE & TYPE

DOOR INTERLOCK 4.8 11.0

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 5.7 13.2
BLOCK

30 AMP BLOCK
FUSE

2.8 6.6

60 AMP BLOCK 5.7 13.2

1. MAX. K.W. BASED ON 48A, OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.008 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5E070

REV.1 5/21/00 PNEUMATIC


PSFH069
- J69 -

78 YORK INTERNATIONAL
FORM AD1T-SECT J

SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT


P.I., N.C. DAMPER, A.F.S. FAN START, UNOCCUPIED MODE, POS. DAMPER CLOSE OFF, R.A. STAT, 1 PHASE, PILOT DUTY P.E. SWITCH

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V
OCCUPIED MODE:
DISCONNECT WHEN THE DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
SWITCH SENSED BY THE S1 AIR FLOW SWITCH, THE FAN MOTOR
AND EP SWITCH ARE ENERGIZED.
FUSING SPACE TEMP WARM (STAT OUTPUT LOW). AT A STAT
OUTPUT OF 3 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
OPTIONAL DISCONNECT SWITCH WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
AND OR FUSING STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
PANEL WIRING DIAGRAM CONTROLLING AT ITS MINIMUM.
ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
L1 (N) = 120V & 277V
ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
TERMINAL 1 2
BLOCK AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
BK WH
UNOCCUPIED MODE:
WHEN MAIN AIR HANDLER IS OFF, THE S1 AIR FLOW SWITCH
BK BK WH
DEENERGIZES THE FAN & EP SWITCH, CAUSING DAMPER TO
C1-1 STANDARD 1 ST. HEAT CLOSE. AS TEMP. DROPS PE1 ENERGIZES THE FAN.
G
RD RD
ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
OPTIONAL 2 ST. HEAT JOB SPECIFICATIONS.
C2-1
BN BN
C N0 BK OPTIONAL 3 ST. HEAT
C3-1
TC C NO ST.1
BK BK BK
S1 5 C1 NOTE: S1 AIRFLOW SWITCH FACTORY SET TO START FAN AT
NC .10"WC TOTAL PRESSURE SENSED AT INLET FLOW PROBE.
C PE-2
NO NC
(WHEN REQ.) ST.2
RD
RD C NO RD
PE-1 C2
NC
PE-3
NC
ST.3
BN C NO BN
C3
PE-4
NC
BK BL/WH BK
SC FM

BK
EP

N.C. PNEUMATIC DIAGRAM RECOMMENDED FIELD P.E. SWITCH SETTINGS:


ACT. 3(C) PE-1 = 8 PSI
(NC)1 2(NO) PE-2 = 8 PSI
EP PE-3 = 10 PSI
PE-4 = 12 PSI
BAL. TAPS VEL. CNTRLR
B (RESET BAND=3-8 PSI) CONSTANT
FLOW LO X
M 20 PSI MAIN VOLUME
PROBE HI Y TOTAL AIR
T
COLD AIR HEAT
R.A. STAT AIR
FLOW

(UNOCCUPIED)
S1 1 PIPE FLOW PLENUM AIR
AIR

FAN STARTS
RESTRICTOR (FIELD CALIB.)
OR OR 20 PSI MAIN

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
R.A. STAT HOT T-STAT BRANCH PRESSURE (PSIG) COLD
PE4 PE3 PE2 PE1 2 PIPE ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE 2 = PILOT DUTY P.E. W/ 30A
1 3.6 8.3 E = 120V/1PH/60HZ - 2 STAGE MAG. CONTACTOR
DE-ENERGIZING
CONTACTOR

30 AMP 2 2.8 6.6 5 = 120V/1PH/60HZ - 3 STAGE 3 = PILOT DUTY P.E. W/ 50A


CONTACTOR 3 1.9 4.4
K = 277V/1PH/60HZ - 1 STAGE MAG. CONTACTOR
1 5.7 13.2
50 AMP L = 277V/1PH/60HZ - 2 STAGE 4 = PILOT DUTY P.E. W/ 30A
2 2.8 6.6 MERC. CONTACTOR
CONTACTOR Y = 277V/1PH/60HZ - 3 STAGE
3 1.9 4.4
5 = PILOT DUTY P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR


SIZE & TYPE

DOOR INTERLOCK 4.8 11.0

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 5.7 13.2
BLOCK

30 AMP BLOCK
FUSE

2.8 6.6

60 AMP BLOCK 5.7 13.2

1. MAX. K.W. BASED ON 48A, OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.008 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5F070

REV.1 5/21/00 PNEUMATIC


PSFH070
- J70 -

YORK INTERNATIONAL 79
SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT
P.I., N.O. DAMPER, A.F.S. FAN START, UNOCCUPIED MODE, POS. DAMPER CLOSE OFF, R.A. STAT, 1 PHASE, PILOT DUTY P.E. SWITCH

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V
OCCUPIED MODE:
DISCONNECT WHEN THE DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
SWITCH SENSED BY THE S1 AIR FLOW SWITCH, THE FAN MOTOR
AND EP SWITCH ARE ENERGIZED.
FUSING SPACE TEMP WARM (STAT OUTPUT LOW). AT A STAT
OUTPUT OF 3 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
OPTIONAL DISCONNECT SWITCH WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
AND OR FUSING STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
PANEL WIRING DIAGRAM CONTROLLING AT ITS MINIMUM.
ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
L1 (N) = 120V & 277V
ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
TERMINAL 1 2
BLOCK AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
BK WH
UNOCCUPIED MODE:
WHEN MAIN AIR HANDLER IS OFF, THE S1 AIR FLOW SWITCH
BK BK WH
DEENERGIZES THE FAN & EP SWITCH, CAUSING DAMPER TO
C1-1 STANDARD 1 ST. HEAT CLOSE. AS TEMP. DROPS PE1 ENERGIZES THE FAN.
G
RD RD
ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
OPTIONAL 2 ST. HEAT JOB SPECIFICATIONS.
C2-1
BN BN
C N0 BK OPTIONAL 3 ST. HEAT
C3-1
TC C NO ST.1
BK BK BK
S1 5 C1 NOTE: S1 AIRFLOW SWITCH FACTORY SET TO START FAN AT
NC .10"WC TOTAL PRESSURE SENSED AT INLET FLOW PROBE.
C PE-2
NO NC
(WHEN REQ.) ST.2
RD
RD C NO RD
PE-1 C2
NC
PE-3
NC
ST.3
BN C NO BN
C3
PE-4
NC
BK BL/WH BK
SC FM

BK
EP

N.O.
PNEUMATIC DIAGRAM
RECOMMENDED FIELD P.E. SWITCH SETTINGS:
ACT. 3(C)
(NC)1 2(NO) PE-1 = 8 PSI
EP PE-2 = 8 PSI
PE-3 = 10 PSI
BAL. TAPS VEL. CNTRLR PE-4 = 12 PSI
B (RESET BAND=8-13 PSI)
FLOW LO Y
M 20 PSI MAIN CONSTANT
PROBE HI X
T VOLUME
TOTAL AIR
REV. R.A.. STAT HEAT
FLOW

COLD AIR
S1 RELAY 1 PIPE AIR
AIR

(UNOCCUPIED)
FLOW PLENUM AIR
M RESTRICTOR FAN STARTS
1 (FIELD CALIB.)
3 OR OR 20 PSI MAIN

R.A.. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
2 PIPE HOT T-STAT BRANCH PRESSURE (PSIG) COLD
PE4 PE3 PE2 PE1
ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE 2 = PILOT DUTY P.E. W/ 30A
1 3.6 8.3 E = 120V/1PH/60HZ - 2 STAGE MAG. CONTACTOR
DE-ENERGIZING
CONTACTOR

30 AMP 2 2.8 6.6 5 = 120V/1PH/60HZ - 3 STAGE 3 = PILOT DUTY P.E. W/ 50A


CONTACTOR 3 1.9 4.4
K = 277V/1PH/60HZ - 1 STAGE MAG. CONTACTOR
1 5.7 13.2
50 AMP L = 277V/1PH/60HZ - 2 STAGE 4 = PILOT DUTY P.E. W/ 30A
2 2.8 6.6 MERC. CONTACTOR
CONTACTOR Y = 277V/1PH/60HZ - 3 STAGE
3 1.9 4.4
5 = PILOT DUTY P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR


SIZE & TYPE

DOOR INTERLOCK 4.8 11.0

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 5.7 13.2
BLOCK

30 AMP BLOCK
FUSE

2.8 6.6

60 AMP BLOCK 5.7 13.2

1. MAX. K.W. BASED ON 48A, OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.016 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5G070

REV.1 5/21/00 PNEUMATIC


PSFH071
- J71 -

80 YORK INTERNATIONAL
FORM AD1T-SECT J

SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT


P.I., N.C. DAMPER, A.F.S. FAN START, UNOCCUPIED MODE, POS. DAMPER CLOSE OFF, D.A. STAT, 1 PHASE, PILOT DUTY P.E. SWITCH

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V
OCCUPIED MODE:
DISCONNECT WHEN THE DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
SWITCH SENSED BY THE S1 AIR FLOW SWITCH, THE FAN MOTOR
AND EP SWITCH ARE ENERGIZED.
FUSING SPACE TEMP WARM (STAT OUTPUT HI). AT A STAT
OUTPUT OF 13 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
OPTIONAL DISCONNECT SWITCH WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
AND OR FUSING STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
PANEL WIRING DIAGRAM CONTROLLING AT ITS MINIMUM.
ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
L1 (N) = 120V & 277V
ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
TERMINAL 1 2
BLOCK AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
BK WH
UNOCCUPIED MODE:
WHEN MAIN AIR HANDLER IS OFF, THE S1 AIR FLOW SWITCH
BK BK WH
DEENERGIZES THE FAN & EP SWITCH, CAUSING DAMPER TO
C1-1 STANDARD 1 ST. HEAT CLOSE. AS TEMP. DROPS PE1 ENERGIZES THE FAN.
G
RD RD
ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
OPTIONAL 2 ST. HEAT JOB SPECIFICATIONS.
C2-1
BN BN
C N0 BK OPTIONAL 3 ST. HEAT
C3-1
TC C NO ST.1
BK BK BK
S1 5 C1 NOTE: S1 AIRFLOW SWITCH FACTORY SET TO START FAN AT
NC .10"WC TOTAL PRESSURE SENSED AT INLET FLOW PROBE.
C PE-2
NO NC
(WHEN REQ.) ST.2
RD
RD C NO RD
PE-1 C2
NC
PE-3
NC
ST.3
BN C NO BN
C3
PE-4
NC
BK BL/WH BK
SC FM

BK
EP

N.C.
PNEUMATIC DIAGRAM
RECOMMENDED FIELD P.E. SWITCH SETTINGS:
ACT. 3(C)
(NC)1 2(NO) PE-1 = 8 PSI
EP PE-2 = 8 PSI
PE-3 = 6 PSI
BAL. TAPS VEL. CNTRLR PE-4 = 4 PSI
B (RESET BAND=3-8 PSI)
FLOW LO X CONSTANT
M 20 PSI MAIN
PROBE HI Y VOLUME
T TOTAL AIR
REV. D.A.. STAT HEAT COLD AIR
FLOW

S1 RELAY 1 PIPE AIR (UNOCCUPIED)


AIR

FLOW PLENUM AIR


M FAN STARTS
1 RESTRICTOR
3 OR OR (FIELD CALIB.)
20 PSI MAIN

D.A.. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
2 PIPE COLD T-STAT BRANCH PRESSURE (PSIG) HOT
PE4 PE3 PE2 PE1 ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE 2 = PILOT DUTY P.E. W/ 30A
1 3.6 8.3 E = 120V/1PH/60HZ - 2 STAGE MAG. CONTACTOR
DE-ENERGIZING
CONTACTOR

30 AMP 2 2.8 6.6 5 = 120V/1PH/60HZ - 3 STAGE 3 = PILOT DUTY P.E. W/ 50A


CONTACTOR 3 1.9 4.4
K = 277V/1PH/60HZ - 1 STAGE MAG. CONTACTOR
1 5.7 13.2
50 AMP L = 277V/1PH/60HZ - 2 STAGE 4 = PILOT DUTY P.E. W/ 30A
2 2.8 6.6 MERC. CONTACTOR
CONTACTOR Y = 277V/1PH/60HZ - 3 STAGE
3 1.9 4.4
5 = PILOT DUTY P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR


SIZE & TYPE

DOOR INTERLOCK 4.8 11.0

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 5.7 13.2
BLOCK

30 AMP BLOCK
FUSE

2.8 6.6

60 AMP BLOCK 5.7 13.2

1. MAX. K.W. BASED ON 48A, OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.016 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5H070

REV.1 5/21/00 PNEUMATIC


PSFH072
- J72 -

YORK INTERNATIONAL 81
SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT
P.I., N.O. DAMPER, A.F.S. FAN START, UNOCCUPIED MODE, POS. DAMPER CLOSE OFF, D.A. STAT, 3 PHASE, LOAD BEARING P.E. SWITCH W/ CONT. INTRLK.

SEQUENCE OF OPERATION:
L1 L2 L3 OCCUPIED MODE:
DISCONNECT WHEN THE DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
SWITCH SENSED BY THE S1 AIR FLOW SWITCH, THE FAN MOTOR
AND EP SWITCH ARE ENERGIZED.
SPACE TEMP WARM (STAT OUTPUT HI). AT A STAT
FUSING OUTPUT OF 13 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
OPTIONAL DISCONNECT SWITCH
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
PANEL WIRING DIAGRAM AND OR FUSING CONTROLLING AT ITS MINIMUM.
L1 L2 L3 N ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
TERMINAL 1 2 3 4
BLOCK AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
BK WH

BK BL UNOCCUPIED MODE:
WHEN MAIN AIR HANDLER IS OFF, THE S1 AIR FLOW SWITCH
BK STANDARD 1 STAGE HEAT DEENERGIZES THE FAN & EP SWITCH, CAUSING DAMPER TO
CLOSE. AS TEMP. DROPS PE1 ENERGIZES THE FAN.
C1-1 G
BK BK ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
C1-2 JOB SPECIFICATIONS.
C N0 BK

BK
TC BK C NO BK
S1 5 C1
NC NOTE: S1 AIRFLOW SWITCH FACTORY SET TO START FAN AT
PE-2 .10"WC TOTAL PRESSURE SENSED AT INLET FLOW PROBE.
C NO NC
RD BK BL/WH BK
PE-1 SC FM
NC

BK BK BK
EP L1 1
C1-1
RD
C NO
L2 2
RD
PE-3
NC
BK BK C
L1 1 BN NO BN

C NO C1-1 BL
L2 2
RD 3 L3 PE-4
RD RD
NC
PE-3 BL BL
NC L3 3
C1-2 C1-2
OPTIONAL 2 STAGE HEAT OPTIONAL 3 STAGE HEAT
N.O. PNEUMATIC DIAGRAM
RECOMMENDED FIELD P.E. SWITCH SETTINGS:
ACT. 3(C)
(NC)1 2(NO) PE-1 = 8 PSI
EP PE-2 = 8 PSI
PE-3 = 6 PSI
BAL. TAPS VEL. CNTRLR PE-4 = 4 PSI
B (RESET BAND=8-13 PSI)
FLOW LO Y CONSTANT
M 20 PSI MAIN
PROBE HI X VOLUME
T TOTAL AIR
D.A.. STAT HEAT COLD AIR
FLOW

S1 1 PIPE AIR (UNOCCUPIED)


AIR

FLOW PLENUM AIR


FAN STARTS
RESTRICTOR
OR OR (FIELD CALIB.)
20 PSI MAIN

D.A.. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE4 PE3 PE2 PE1 2 PIPE COLD T-STAT BRANCH PRESSURE (PSIG) HOT
ROOM ROOM

HEATER COMPONENTS MAX. KW


3 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-3 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 208 V 480 V P = 208V/3PH/60HZ - 1 STAGE J = LOAD BEARING P.E. W/ 30A
1 10.7 24.9 R = 208V/3PH/60HZ - 2 STAGE MAG. CONTACTOR INTERLOCK
30 AMP CONT.
LOAD BRG. PE

2 4.4 9.1 1 = 208V/3PH/60HZ - 3 STAGE K = LOAD BEARING P.E. W/ 50A


W/ INTRLK

PER STAGE 3 2.9 6.0


U = 480V/3PH/60HZ - 1 STAGE MAG. CONTACTOR INTERLOCK
1 17.2 39.8
50 AMP CONT. W = 480V/3PH/60HZ - 2 STAGE L = LOAD BEARING P.E. W/ 30A
2 4.4 9.1 MERC. CONTACTOR INTERLOCK
PER STAGE 3 = 480V/3PH/60HZ - 3 STAGE
3 2.9 6.0
M = LOAD BEARING P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR INTERLOCK


SIZE & TYPE

DOOR INTERLOCK 14.3 33.2

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 17.2 39.8
BLOCK

30 AMP BLOCK
FUSE

8.6 19.9

60 AMP BLOCK 17.2 39.8

1. MAX. K.W. BASED ON 48A, P.E., OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.008 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5E070

REV.1 5/21/00 PNEUMATIC


PSFH073
- J73 -

82 YORK INTERNATIONAL
FORM AD1T-SECT J

SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT


P.I., N.C. DAMPER, A.F.S. FAN START, UNOCCUPIED MODE, POS. DAMPER CLOSE OFF, R.A. STAT, 3 PHASE, LOAD BEARING P.E. SWITCH W/ CONT. INTRLK.

SEQUENCE OF OPERATION:
L1 L2 L3 OCCUPIED MODE:
DISCONNECT WHEN THE DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
SWITCH SENSED BY THE S1 AIR FLOW SWITCH, THE FAN MOTOR
AND EP SWITCH ARE ENERGIZED.
SPACE TEMP WARM (STAT OUTPUT LOW). AT A STAT
FUSING OUTPUT OF 3 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
OPTIONAL DISCONNECT SWITCH
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
PANEL WIRING DIAGRAM AND OR FUSING CONTROLLING AT ITS MINIMUM.
L1 L2 L3 N ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
TERMINAL 1 2 3 4
BLOCK AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
BK WH

BK BL UNOCCUPIED MODE:
WHEN MAIN AIR HANDLER IS OFF, THE S1 AIR FLOW SWITCH
BK STANDARD 1 STAGE HEAT DEENERGIZES THE FAN & EP SWITCH, CAUSING DAMPER TO
CLOSE. AS TEMP. DROPS PE1 ENERGIZES THE FAN.
C1-1 G
BK BK ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
C1-2 JOB SPECIFICATIONS.
C N0 BK

BK
TC BK C NO BK
S1 5 C1
NC NOTE: S1 AIRFLOW SWITCH FACTORY SET TO START FAN AT
PE-2 .10"WC TOTAL PRESSURE SENSED AT INLET FLOW PROBE.
C NO NC
RD BK BL/WH BK
PE-1 SC FM
NC

BK BK BK
EP L1 1
C1-1
RD
C NO
L2 2 RD

PE-3
NC
BK BK C
L1 1 BN NO BN

C NO C1-1 BL
L2 2
RD 3 L3 PE-4
RD
RD
NC
PE-3 BL BL
NC L3 3
C1-2 C1-2
OPTIONAL 2 STAGE HEAT OPTIONAL 3 STAGE HEAT
N.C. PNEUMATIC DIAGRAM RECOMMENDED FIELD P.E. SWITCH SETTINGS:
ACT. 3(C) PE-1 = 8 PSI
(NC)1 2(NO) PE-2 = 8 PSI
EP PE-3 = 10 PSI
PE-4 = 12 PSI
BAL. TAPS VEL. CNTRLR
B (RESET BAND=3-8 PSI) CONSTANT
FLOW LO X
M 20 PSI MAIN VOLUME
PROBE HI Y TOTAL AIR
T
COLD AIR HEAT
R.A. STAT AIR
FLOW

(UNOCCUPIED)
S1 1 PIPE FLOW PLENUM AIR
AIR

FAN STARTS
RESTRICTOR (FIELD CALIB.)
OR OR 20 PSI MAIN

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
R.A. STAT HOT T-STAT BRANCH PRESSURE (PSIG) COLD
PE4 PE3 PE2 PE1 2 PIPE ROOM ROOM

HEATER COMPONENTS MAX. KW


3 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-3 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 208 V 480 V P = 208V/3PH/60HZ - 1 STAGE J = LOAD BEARING P.E. W/ 30A
1 10.7 24.9 R = 208V/3PH/60HZ - 2 STAGE MAG. CONTACTOR INTERLOCK
30 AMP CONT.
LOAD BRG. PE

2 4.4 9.1 1 = 208V/3PH/60HZ - 3 STAGE K = LOAD BEARING P.E. W/ 50A


W/ INTRLK

PER STAGE 3 2.9 6.0


U = 480V/3PH/60HZ - 1 STAGE MAG. CONTACTOR INTERLOCK
1 17.2 39.8
50 AMP CONT. W = 480V/3PH/60HZ - 2 STAGE L = LOAD BEARING P.E. W/ 30A
2 4.4 9.1 MERC. CONTACTOR INTERLOCK
PER STAGE 3 = 480V/3PH/60HZ - 3 STAGE
3 2.9 6.0
M = LOAD BEARING P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR INTERLOCK


SIZE & TYPE

DOOR INTERLOCK 14.3 33.2

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 17.2 39.8
BLOCK

30 AMP BLOCK
FUSE

8.6 19.9

60 AMP BLOCK 17.2 39.8

1. MAX. K.W. BASED ON 48A, P.E., OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.008 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5F070

REV.1 5/21/00 PNEUMATIC


PSFH074
- J74 -

YORK INTERNATIONAL 83
SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT
P.I., N.O. DAMPER, A.F.S. FAN START, UNOCCUPIED MODE, POS. DAMPER CLOSE OFF, R.A. STAT, 3 PHASE, LOAD BEARING P.E. SWITCH W/ CONT. INTRLK.

SEQUENCE OF OPERATION:
L1 L2 L3 OCCUPIED MODE:
DISCONNECT WHEN THE DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
SWITCH SENSED BY THE S1 AIR FLOW SWITCH, THE FAN MOTOR
AND EP SWITCH ARE ENERGIZED.
SPACE TEMP WARM (STAT OUTPUT LOW). AT A STAT
FUSING OUTPUT OF 3 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
OPTIONAL DISCONNECT SWITCH
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
PANEL WIRING DIAGRAM AND OR FUSING CONTROLLING AT ITS MINIMUM.
L1 L2 L3 N ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
TERMINAL 1 2 3 4
BLOCK AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
BK WH

BK BL UNOCCUPIED MODE:
WHEN MAIN AIR HANDLER IS OFF, THE S1 AIR FLOW SWITCH
BK STANDARD 1 STAGE HEAT DEENERGIZES THE FAN & EP SWITCH, CAUSING DAMPER TO
CLOSE. AS TEMP. DROPS PE1 ENERGIZES THE FAN.
C1-1 G
BK BK ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
C1-2 JOB SPECIFICATIONS.
C N0 BK

BK
TC BK C NO BK
S1 5 C1
NC NOTE: S1 AIRFLOW SWITCH FACTORY SET TO START FAN AT
PE-2 .10"WC TOTAL PRESSURE SENSED AT INLET FLOW PROBE.
C NO NC
RD BK BL/WH BK
PE-1 SC FM
NC

BK BK BK
EP L1 1
C1-1
RD
C NO
L2 2 RD

PE-3
NC
BK BK C
L1 1 BN NO BN

C NO C1-1 BL
L2 2
RD 3 L3 PE-4
RD
RD
NC
PE-3 BL BL
NC L3 3
C1-2 C1-2

N.O.
PNEUMATIC DIAGRAM OPTIONAL 2 STAGE HEAT OPTIONAL 3 STAGE HEAT
RECOMMENDED FIELD P.E. SWITCH SETTINGS:
ACT. 3(C)
(NC)1 2(NO) PE-1 = 8 PSI
EP PE-2 = 8 PSI
PE-3 = 10 PSI
BAL. TAPS VEL. CNTRLR PE-4 = 12 PSI
B (RESET BAND=8-13 PSI)
FLOW LO Y
M 20 PSI MAIN CONSTANT
PROBE HI X
T VOLUME
TOTAL AIR
REV. R.A.. STAT HEAT
FLOW

COLD AIR
S1 RELAY 1 PIPE AIR
AIR

(UNOCCUPIED)
FLOW PLENUM AIR
M RESTRICTOR FAN STARTS
1 (FIELD CALIB.)
3 OR OR 20 PSI MAIN

R.A.. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
2 PIPE HOT T-STAT BRANCH PRESSURE (PSIG) COLD
PE4 PE3 PE2 PE1
ROOM ROOM

HEATER COMPONENTS MAX. KW


3 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-3 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 208 V 480 V P = 208V/3PH/60HZ - 1 STAGE J = LOAD BEARING P.E. W/ 30A
1 10.7 24.9 R = 208V/3PH/60HZ - 2 STAGE MAG. CONTACTOR INTERLOCK
30 AMP CONT.
LOAD BRG. PE

2 4.4 9.1 1 = 208V/3PH/60HZ - 3 STAGE K = LOAD BEARING P.E. W/ 50A


W/ INTRLK

PER STAGE 3 2.9 6.0


U = 480V/3PH/60HZ - 1 STAGE MAG. CONTACTOR INTERLOCK
1 17.2 39.8
50 AMP CONT. W = 480V/3PH/60HZ - 2 STAGE L = LOAD BEARING P.E. W/ 30A
2 4.4 9.1 MERC. CONTACTOR INTERLOCK
PER STAGE 3 = 480V/3PH/60HZ - 3 STAGE
3 2.9 6.0
M = LOAD BEARING P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR INTERLOCK


SIZE & TYPE

DOOR INTERLOCK 14.3 33.2

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 17.2 39.8
BLOCK

30 AMP BLOCK
FUSE

8.6 19.9

60 AMP BLOCK 17.2 39.8

1. MAX. K.W. BASED ON 48A, P.E., OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.016 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5G070

REV.1 5/21/00 PNEUMATIC


PSFH075
- J75 -

84 YORK INTERNATIONAL
FORM AD1T-SECT J

SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT


P.I., N.C. DAMPER, A.F.S. FAN START, UNOCCUPIED MODE, POS. DAMPER CLOSE OFF, D.A. STAT, 3 PHASE, LOAD BEARING P.E. SWITCH W/ CONT. INTRLK.

SEQUENCE OF OPERATION:
L1 L2 L3 OCCUPIED MODE:
DISCONNECT WHEN THE DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
SWITCH SENSED BY THE S1 AIR FLOW SWITCH, THE FAN MOTOR
AND EP SWITCH ARE ENERGIZED.
SPACE TEMP WARM (STAT OUTPUT HI). AT A STAT
FUSING OUTPUT OF 13 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
OPTIONAL DISCONNECT SWITCH
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
PANEL WIRING DIAGRAM AND OR FUSING CONTROLLING AT ITS MINIMUM.
L1 L2 L3 N ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
TERMINAL 1 2 3 4
BLOCK AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
BK WH

BK BL UNOCCUPIED MODE:
WHEN MAIN AIR HANDLER IS OFF, THE S1 AIR FLOW SWITCH
BK STANDARD 1 STAGE HEAT DEENERGIZES THE FAN & EP SWITCH, CAUSING DAMPER TO
CLOSE. AS TEMP. DROPS PE1 ENERGIZES THE FAN.
C1-1 G
BK BK ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
C1-2 JOB SPECIFICATIONS.
C N0 BK

BK
TC BK C NO BK
S1 5 C1
NC NOTE: S1 AIRFLOW SWITCH FACTORY SET TO START FAN AT
PE-2 .10"WC TOTAL PRESSURE SENSED AT INLET FLOW PROBE.
C NO NC
RD BK BL/WH BK
PE-1 SC FM
NC

BK BK BK
EP L1 1
C1-1
RD
C NO
L2 2
RD
PE-3
NC
BK BK C
L1 1 BN NO BN

C NO C1-1 BL
L2 2
RD 3 L3 PE-4
RD RD
NC
PE-3 BL BL
NC L3 3
C1-2 C1-2

N.C.
PNEUMATIC DIAGRAM OPTIONAL 2 STAGE HEAT OPTIONAL 3 STAGE HEAT

RECOMMENDED FIELD P.E. SWITCH SETTINGS:


ACT. 3(C)
(NC)1 2(NO) PE-1 = 8 PSI
EP PE-2 = 8 PSI
BAL. TAPS PE-3 = 6 PSI
VEL. CNTRLR
PE-4 = 4 PSI
B (RESET BAND=3-8 PSI)
FLOW LO X CONSTANT
M 20 PSI MAIN
PROBE HI Y VOLUME
T TOTAL AIR
REV. D.A.. STAT HEAT COLD AIR
FLOW

S1 RELAY 1 PIPE AIR (UNOCCUPIED)


AIR

FLOW PLENUM AIR


M FAN STARTS
1 RESTRICTOR
3 OR OR (FIELD CALIB.)
20 PSI MAIN

D.A.. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
2 PIPE COLD T-STAT BRANCH PRESSURE (PSIG) HOT
PE4 PE3 PE2 PE1 ROOM ROOM

HEATER COMPONENTS MAX. KW


3 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-3 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 208 V 480 V P = 208V/3PH/60HZ - 1 STAGE J = LOAD BEARING P.E. W/ 30A
1 10.7 24.9 R = 208V/3PH/60HZ - 2 STAGE MAG. CONTACTOR INTERLOCK
30 AMP CONT.
LOAD BRG. PE

2 4.4 9.1 1 = 208V/3PH/60HZ - 3 STAGE K = LOAD BEARING P.E. W/ 50A


W/ INTRLK

PER STAGE 3 2.9 6.0


U = 480V/3PH/60HZ - 1 STAGE MAG. CONTACTOR INTERLOCK
1 17.2 39.8
50 AMP CONT. W = 480V/3PH/60HZ - 2 STAGE L = LOAD BEARING P.E. W/ 30A
2 4.4 9.1 MERC. CONTACTOR INTERLOCK
PER STAGE 3 = 480V/3PH/60HZ - 3 STAGE
3 2.9 6.0
M = LOAD BEARING P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR INTERLOCK


SIZE & TYPE

DOOR INTERLOCK 14.3 33.2

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 17.2 39.8
BLOCK

30 AMP BLOCK
FUSE

8.6 19.9

60 AMP BLOCK 17.2 39.8

1. MAX. K.W. BASED ON 48A, P.E., OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.016 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5H070

REV.1 5/21/00 PNEUMATIC


PSFH076
- J76 -

YORK INTERNATIONAL 85
SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT
P.I., N.O. DAMPER, A.F.S. FAN START, UNOCCUPIED MODE, POS. DAMPER CLOSE OFF, D.A. STAT, 3 PHASE, PILOT DUTY P.E. SWITCH

SEQUENCE OF OPERATION:
L1 L2 L3 OCCUPIED MODE:
DISCONNECT WHEN THE DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
SWITCH SENSED BY THE S1 AIR FLOW SWITCH, THE FAN MOTOR
AND EP SWITCH ARE ENERGIZED.
SPACE TEMP WARM (STAT OUTPUT HI). AT A STAT
FUSING OUTPUT OF 13 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
OPTIONAL DISCONNECT SWITCH
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
PANEL WIRING DIAGRAM AND OR FUSING CONTROLLING AT ITS MINIMUM.
L1 L2 L3 N ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
TERMINAL 1 2 3 4
BLOCK AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
BK WH

BK BL UNOCCUPIED MODE:
WHEN MAIN AIR HANDLER IS OFF, THE S1 AIR FLOW SWITCH
BK STANDARD 1 STAGE HEAT DEENERGIZES THE FAN & EP SWITCH, CAUSING DAMPER TO
CLOSE. AS TEMP. DROPS PE1 ENERGIZES THE FAN.
C1-1 G
BK BK ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
C1-2 JOB SPECIFICATIONS.
C N0 BK NOTE: S1 AIRFLOW SWITCH FACTORY SET TO START FAN AT
TC ST.1 .10"WC TOTAL PRESSURE SENSED AT INLET FLOW PROBE.
BK BK C NO BK
S1 5 C1
NC
C PE-2
NO NC
ST.2 BK BK
C NO L1 1
RD RD RD BL
PE-1 C2 C1-1 3 L3
NC RD RD
PE-3 L2 2
NC C2-1
ST.3
BN C NO BN
C3 OPTIONAL 2 STAGE HEAT
PE-4
NC
BK BL/WH BK BK BK
SC FM L1 1
C1-1
RD RD
L2 2
BK
EP C2-1
BN BN

C3-1
BL BL
L3 3
C1-2
N.O. PNEUMATIC DIAGRAM OPTIONAL 3 STAGE HEAT
ACT. 3(C) RECOMMENDED FIELD P.E. SWITCH SETTINGS:
(NC)1 2(NO)
EP PE-1 = 8 PSI
PE-2 = 8 PSI
BAL. TAPS VEL. CNTRLR PE-3 = 6 PSI
B (RESET BAND=8-13 PSI) PE-4 = 4 PSI
FLOW LO Y
M 20 PSI MAIN CONSTANT
PROBE HI X
T VOLUME
TOTAL AIR
D.A.. STAT HEAT
FLOW

1 PIPE COLD AIR


S1 AIR
AIR

(UNOCCUPIED)
FLOW PLENUM AIR
RESTRICTOR FAN STARTS
OR OR 20 PSI MAIN (FIELD CALIB.)

D.A.. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE4 PE3 PE2 PE1 2 PIPE COLD HOT
T-STAT BRANCH PRESSURE (PSIG)
ROOM ROOM
HEATER COMPONENTS MAX. KW
3 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-3 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 208 V 480 V P = 208V/3PH/60HZ - 1 STAGE 2 = PILOT DUTY P.E. W/ 30A
1 10.7 24.9 R = 208V/3PH/60HZ - 2 STAGE MAG. CONTACTOR
DE-ENERGIZING
CONTACTOR

30 AMP 2 5.3 12.4 1 = 208V/3PH/60HZ - 3 STAGE 3 = PILOT DUTY P.E. W/ 50A


PER STAGE 3 3.5 8.3
U = 480V/3PH/60HZ - 1 STAGE MAG. CONTACTOR
1 17.2 39.8
50 AMP W = 480V/3PH/60HZ - 2 STAGE 4 = PILOT DUTY P.E. W/ 30A
2 8.6 19.9 MERC. CONTACTOR
PER STAGE 3 = 480V/3PH/60HZ - 3 STAGE
3 5.7 13.2
5 = PILOT DUTY P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR


SIZE & TYPE

DOOR INTERLOCK 14.3 33.2

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 17.2 39.8
BLOCK

30 AMP BLOCK 8.6 19.9


FUSE

60 AMP BLOCK 17.2 39.8

1. MAX. K.W. BASED ON 48A, OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.008 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5E070

REV.1 5/21/00 PNEUMATIC


PSFH077
- J77 -

86 YORK INTERNATIONAL
FORM AD1T-SECT J

SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT


P.I., N.C. DAMPER, A.F.S. FAN START, UNOCCUPIED MODE, POS. DAMPER CLOSE OFF, R.A. STAT, 3 PHASE, PILOT DUTY P.E. SWITCH

SEQUENCE OF OPERATION:
L1 L2 L3 OCCUPIED MODE:
DISCONNECT WHEN THE DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
SWITCH SENSED BY THE S1 AIR FLOW SWITCH, THE FAN MOTOR
AND EP SWITCH ARE ENERGIZED.
SPACE TEMP WARM (STAT OUTPUT LOW). AT A STAT
FUSING OUTPUT OF 3 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
OPTIONAL DISCONNECT SWITCH
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
PANEL WIRING DIAGRAM AND OR FUSING CONTROLLING AT ITS MINIMUM.
L1 L2 L3 N ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
TERMINAL 1 2 3 4
BLOCK AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
BK WH

BK BL UNOCCUPIED MODE:
WHEN MAIN AIR HANDLER IS OFF, THE S1 AIR FLOW SWITCH
BK STANDARD 1 STAGE HEAT DEENERGIZES THE FAN & EP SWITCH, CAUSING DAMPER TO
CLOSE. AS TEMP. DROPS PE1 ENERGIZES THE FAN.
C1-1 G
BK BK ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
C1-2 JOB SPECIFICATIONS.
C N0 BK NOTE: S1 AIRFLOW SWITCH FACTORY SET TO START FAN AT
.10"WC TOTAL PRESSURE SENSED AT INLET FLOW PROBE.
TC C NO ST.1
BK BK BK
S1 5 C1
NC
C PE-2
NO NC BK BK
ST.2 L1 1
RD
RD C NO RD C1-1 BL
3 L3
PE-1 C2 RD RD
NC L2 2
PE-3 C2-1
NC
ST.3
BN C NO BN OPTIONAL 2 STAGE HEAT
C3
PE-4
NC BK BK
BK BL/WH BK L1 1
SC FM C1-1
RD RD
L2 2
BK
C2-1
EP BN BN

C3-1
BL BL
L3 3
C1-2
OPTIONAL 3 STAGE HEAT
N.C. PNEUMATIC DIAGRAM
RECOMMENDED FIELD P.E. SWITCH SETTINGS:
ACT. 3(C)
(NC)1 2(NO) PE-1 = 8 PSI
EP PE-2 = 8 PSI
PE-3 = 10 PSI
BAL. TAPS VEL. CNTRLR PE-4 = 12 PSI
B (RESET BAND=3-8 PSI)
FLOW LO X CONSTANT
M 20 PSI MAIN
PROBE HI Y VOLUME
T TOTAL AIR
R.A. STAT COLD AIR HEAT
FLOW

1 PIPE AIR (UNOCCUPIED)


S1
AIR

FLOW PLENUM AIR


FAN STARTS
RESTRICTOR (FIELD CALIB.)
OR OR 20 PSI MAIN

R.A. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE4 PE3 PE2 PE1 2 PIPE HOT T-STAT BRANCH PRESSURE (PSIG) COLD
ROOM ROOM

HEATER COMPONENTS MAX. KW


3 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-3 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 208 V 480 V P = 208V/3PH/60HZ - 1 STAGE 2 = PILOT DUTY P.E. W/ 30A
1 10.7 24.9 R = 208V/3PH/60HZ - 2 STAGE MAG. CONTACTOR
DE-ENERGIZING
CONTACTOR

30 AMP 2 5.3 12.4 1 = 208V/3PH/60HZ - 3 STAGE 3 = PILOT DUTY P.E. W/ 50A


PER STAGE 3 3.5 8.3
U = 480V/3PH/60HZ - 1 STAGE MAG. CONTACTOR
1 17.2 39.8
50 AMP W = 480V/3PH/60HZ - 2 STAGE 4 = PILOT DUTY P.E. W/ 30A
2 8.6 19.9 MERC. CONTACTOR
PER STAGE 3 = 480V/3PH/60HZ - 3 STAGE
3 5.7 13.2
5 = PILOT DUTY P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR


SIZE & TYPE

DOOR INTERLOCK 14.3 33.2

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 17.2 39.8
BLOCK

30 AMP BLOCK 8.6 19.9


FUSE

60 AMP BLOCK 17.2 39.8

1. MAX. K.W. BASED ON 48A, OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.008 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5F070

REV.1 5/21/00 PNEUMATIC


PSFH078
- J78 -

YORK INTERNATIONAL 87
SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT
P.I., N.O. DAMPER, A.F.S. FAN START, UNOCCUPIED MODE, POS. DAMPER CLOSE OFF, R.A. STAT, 3 PHASE, PILOT DUTY P.E. SWITCH

SEQUENCE OF OPERATION:
L1 L2 L3 OCCUPIED MODE:
DISCONNECT WHEN THE DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
SWITCH SENSED BY THE S1 AIR FLOW SWITCH, THE FAN MOTOR
AND EP SWITCH ARE ENERGIZED.
SPACE TEMP WARM (STAT OUTPUT LOW). AT A STAT
FUSING OUTPUT OF 3 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
OPTIONAL DISCONNECT SWITCH
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
PANEL WIRING DIAGRAM AND OR FUSING CONTROLLING AT ITS MINIMUM.
L1 L2 L3 N ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
TERMINAL 1 2 3 4
BLOCK AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
BK WH

BK BL UNOCCUPIED MODE:
WHEN MAIN AIR HANDLER IS OFF, THE S1 AIR FLOW SWITCH
BK STANDARD 1 STAGE HEAT DEENERGIZES THE FAN & EP SWITCH, CAUSING DAMPER TO
CLOSE. AS TEMP. DROPS PE1 ENERGIZES THE FAN.
C1-1 G
BK BK ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
C1-2 JOB SPECIFICATIONS.
C N0 BK NOTE: S1 AIRFLOW SWITCH FACTORY SET TO START FAN AT
ST.1 .10"WC TOTAL PRESSURE SENSED AT INLET FLOW PROBE.
BK TC BK C NO BK
S1 5 C1
NC
C PE-2
NO NC L1 1
BK BK

RD
ST.2 BL
RD C NO RD C1-1 3 L3
PE-1 C2 RD RD
NC L2 2
PE-3 C2-1
NC
ST.3
BN C NO BN OPTIONAL 2 STAGE HEAT
C3
PE-4
NC BK BK
BK BL/WH BK L1 1
SC FM C1-1
RD RD
L2 2
BK
C2-1
EP BN BN

C3-1
BL BL
L3 3
C1-2
N.O.
PNEUMATIC DIAGRAM OPTIONAL 3 STAGE HEAT

ACT. 3(C) RECOMMENDED FIELD P.E. SWITCH SETTINGS:


(NC)1 2(NO)
EP PE-1 = 8 PSI
PE-2 = 8 PSI
BAL. TAPS VEL. CNTRLR PE-3 = 10 PSI
B (RESET BAND=8-13 PSI) PE-4 = 12 PSI
FLOW LO Y
M 20 PSI MAIN
PROBE HI X CONSTANT
T VOLUME
TOTAL AIR
REV. R.A.. STAT
FLOW

S1 RELAY 1 PIPE COLD AIR HEAT


AIR

AIR (UNOCCUPIED)
M RESTRICTOR FLOW PLENUM AIR
1 FAN STARTS
3 OR OR 20 PSI MAIN (FIELD CALIB.)

R.A.. STAT
2 PIPE 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE4 PE3 PE2 PE1 HOT T-STAT BRANCH PRESSURE (PSIG) COLD
ROOM ROOM

HEATER COMPONENTS MAX. KW


3 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-3 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 208 V 480 V P = 208V/3PH/60HZ - 1 STAGE 2 = PILOT DUTY P.E. W/ 30A
1 10.7 24.9 R = 208V/3PH/60HZ - 2 STAGE MAG. CONTACTOR
DE-ENERGIZING
CONTACTOR

30 AMP 2 5.3 12.4 1 = 208V/3PH/60HZ - 3 STAGE 3 = PILOT DUTY P.E. W/ 50A


PER STAGE 3 3.5 8.3
U = 480V/3PH/60HZ - 1 STAGE MAG. CONTACTOR
1 17.2 39.8
50 AMP W = 480V/3PH/60HZ - 2 STAGE 4 = PILOT DUTY P.E. W/ 30A
2 8.6 19.9 MERC. CONTACTOR
PER STAGE 3 = 480V/3PH/60HZ - 3 STAGE
3 5.7 13.2
5 = PILOT DUTY P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR


SIZE & TYPE

DOOR INTERLOCK 14.3 33.2

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 17.2 39.8
BLOCK

30 AMP BLOCK 8.6 19.9


FUSE

60 AMP BLOCK 17.2 39.8

1. MAX. K.W. BASED ON 48A, OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.016 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5G070

REV.1 5/21/00 PNEUMATIC


PSFH079
- J79 -

88 YORK INTERNATIONAL
FORM AD1T-SECT J

SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT


P.I., N.C. DAMPER, A.F.S. FAN START, UNOCCUPIED MODE, POS. DAMPER CLOSE OFF, D.A. STAT, 3 PHASE, PILOT DUTY P.E. SWITCH

SEQUENCE OF OPERATION:
L1 L2 L3 OCCUPIED MODE:
DISCONNECT WHEN THE DUCT PRESSURE FROM THE CENTRAL SYSTEM IS
SWITCH SENSED BY THE S1 AIR FLOW SWITCH, THE FAN MOTOR
AND EP SWITCH ARE ENERGIZED.
SPACE TEMP WARM (STAT OUTPUT HI). AT A STAT
FUSING OUTPUT OF 13 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
OPTIONAL DISCONNECT SWITCH
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
PANEL WIRING DIAGRAM AND OR FUSING CONTROLLING AT ITS MINIMUM.
L1 L2 L3 N ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
TERMINAL 1 2 3 4
BLOCK AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
BK WH

BK BL UNOCCUPIED MODE:
WHEN MAIN AIR HANDLER IS OFF, THE S1 AIR FLOW SWITCH
BK STANDARD 1 STAGE HEAT DEENERGIZES THE FAN & EP SWITCH, CAUSING DAMPER TO
CLOSE. AS TEMP. DROPS PE1 ENERGIZES THE FAN.
C1-1 G
BK BK ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
C1-2 JOB SPECIFICATIONS.
C N0 BK NOTE: S1 AIRFLOW SWITCH FACTORY SET TO START FAN AT
.10"WC TOTAL PRESSURE SENSED AT INLET FLOW PROBE.
TC C NO ST.1
BK BK BK
S1 5 C1
NC
C PE-2
NO NC BK BK
ST.2 L1 1
RD RD C NO RD C1-1 BL
3 L3
PE-1 C2 RD RD
NC L2 2
PE-3 C2-1
NC
ST.3
BN C NO BN OPTIONAL 2 STAGE HEAT
C3
PE-4
NC BK BK
BK BL/WH BK L1 1
SC FM C1-1
RD RD
L2 2
BK
C2-1
EP BN BN

C3-1
BL BL
L3 3
C1-2
N.C.
PNEUMATIC DIAGRAM OPTIONAL 3 STAGE HEAT

ACT. 3(C) RECOMMENDED FIELD P.E. SWITCH SETTINGS:


(NC)1 2(NO)
EP PE-1 = 8 PSI
PE-2 = 8 PSI
BAL. TAPS VEL. CNTRLR PE-3 = 6 PSI
B (RESET BAND=3-8 PSI) PE-4 = 4 PSI
FLOW LO X
M 20 PSI MAIN CONSTANT
PROBE HI Y
T VOLUME
TOTAL AIR
REV. D.A.. STAT
FLOW

HEAT COLD AIR


S1 RELAY 1 PIPE AIR
AIR

(UNOCCUPIED)
M FLOW PLENUM AIR
1 RESTRICTOR FAN STARTS
3 OR OR 20 PSI MAIN (FIELD CALIB.)

D.A.. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
2 PIPE
PE4 PE3 PE2 PE1 COLD T-STAT BRANCH PRESSURE (PSIG) HOT
ROOM ROOM

HEATER COMPONENTS MAX. KW


3 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-3 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 208 V 480 V P = 208V/3PH/60HZ - 1 STAGE 2 = PILOT DUTY P.E. W/ 30A
1 10.7 24.9 R = 208V/3PH/60HZ - 2 STAGE MAG. CONTACTOR
DE-ENERGIZING
CONTACTOR

30 AMP 2 5.3 12.4 1 = 208V/3PH/60HZ - 3 STAGE 3 = PILOT DUTY P.E. W/ 50A


PER STAGE 3 3.5 8.3
U = 480V/3PH/60HZ - 1 STAGE MAG. CONTACTOR
1 17.2 39.8
50 AMP W = 480V/3PH/60HZ - 2 STAGE 4 = PILOT DUTY P.E. W/ 30A
2 8.6 19.9 MERC. CONTACTOR
PER STAGE 3 = 480V/3PH/60HZ - 3 STAGE
3 5.7 13.2
5 = PILOT DUTY P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR


SIZE & TYPE

DOOR INTERLOCK 14.3 33.2

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 17.2 39.8
BLOCK

30 AMP BLOCK 8.6 19.9


FUSE

60 AMP BLOCK 17.2 39.8

1. MAX. K.W. BASED ON 48A, OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.016 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5H070

REV.1 5/21/00 PNEUMATIC


PSFH080
- J80 -

YORK INTERNATIONAL 89
SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT
PRESS. INDEPENDENT, N.O. DAMPER, P.E. FAN START, DIRECT ACTING STAT, 1 PHASE, LOAD BEARING P.E. SWITCH

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V
SIGNAL TO PE1 ENERGIZES THE FAN.
DISCONNECT
SPACE TEMP WARM (STAT OUTPUT HI). AT A STAT
SWITCH
OUTPUT OF 13 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
FUSING WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
OPTIONAL DISCONNECT SWITCH
ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
AND OR FUSING
PANEL WIRING DIAGRAM ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.

AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.


L1 (N) = 120V & 277V
TERMINAL 1 2 NOTE: ON START UP, BLOWER FAN MOTOR MUST BE
BLOCK ENERGIZED BEFORE PRIMARY AIR FAN. FAN CONTROL
BK WH REQUIRES PROPER SETTING OF PE1 SWITCH BY TEMP.
CONTROL CONTRACTOR.
C NO
BK BK C NO BK WH G ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
PE-1 5 JOB SPECIFICATIONS.
NC
PE-2 STANDARD 1
NC STAGE HEAT
RD C NO RD

PE-3 OPTIONAL 2
NC STAGE HEAT
BN C NO BN

PE-4 OPTIONAL 3
NC STAGE HEAT

BK BL/WH BK
SC FM

PE1
P.E. SWITCH SUPPLIED BY FACTORY
(SIGNAL BY OTHERS)

PNEUMATIC DIAGRAM
N.O. RECOMMENDED FIELD P.E. SWITCH SETTINGS:

ACT. PE-2 = 8 PSI


PE-3 = 6 PSI
VEL. CNTRLR PE-4 = 4 PSI
BAL. TAPS (RESET BAND=8-13 PSI)
B
FLOW LO Y
M 20 PSI MAIN CONSTANT
PROBE HI X
T VOLUME
TOTAL AIR
D.A.. STAT HEAT
FLOW

1 PIPE COLD AIR


AIR
AIR

FLOW PLENUM AIR


RESTRICTOR
OR OR 20 PSI MAIN

D.A.. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
2 PIPE COLD HOT
PE4 PE3 PE2 T-STAT BRANCH PRESSURE (PSIG)
ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE 1 = LOAD BEARING P.E.
SWITCH

1 2.8 6.7 E = 120V/1PH/60HZ - 2 STAGE


LOAD BEARING
P.E.

PER STAGE 2 1.4 3.3 5 = 120V/1PH/60HZ - 3 STAGE


3 0.9 2.2
K = 277V/1PH/60HZ - 1 STAGE
DISCONNECT

L = 277V/1PH/60HZ - 2 STAGE
SIZE & TYPE

DNF-40 2.8 6.7 Y = 277V/1PH/60HZ - 3 STAGE


DOOR INTERLOCK
BLOCK
FUSE

30 AMP BLOCK 2.8 6.7

1. MAX. K.W. BASED ON P.E. MAX LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.008 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5E020

REV.1 8/5/00 PNEUMATIC


PSFH081
- J81 -

90 YORK INTERNATIONAL
FORM AD1T-SECT J

SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT


PRESS. INDEPENDENT, N.C. DAMPER, P.E. FAN START, REVERSE ACTING STAT, 1 PHASE, LOAD BEARING P.E. SWITCH

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V
SIGNAL TO PE1 ENERGIZES THE FAN.
DISCONNECT
SPACE TEMP WARM (STAT OUTPUT LOW). AT A STAT
SWITCH
OUTPUT OF 3 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
FUSING WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
OPTIONAL DISCONNECT SWITCH
ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
AND OR FUSING
PANEL WIRING DIAGRAM ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.

AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.


L1 (N) = 120V & 277V
TERMINAL 1 2 NOTE: ON START UP, BLOWER FAN MOTOR MUST BE
BLOCK ENERGIZED BEFORE PRIMARY AIR FAN. FAN CONTROL
BK WH
REQUIRES PROPER SETTING OF PE1 SWITCH BY TEMP.
CONTROL CONTRACTOR.
C NO
BK BK C NO BK WH G ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
PE-1 5 JOB SPECIFICATIONS.
NC
PE-2 STANDARD 1
NC STAGE HEAT
RD C NO RD

PE-3 OPTIONAL 2
NC STAGE HEAT
BN C NO BN

PE-4 OPTIONAL 3
NC STAGE HEAT

BK BL/WH BK
SC FM

PE1
P.E. SWITCH SUPPLIED BY FACTORY
(SIGNAL BY OTHERS)

PNEUMATIC DIAGRAM
N.C. RECOMMENDED FIELD P.E. SWITCH SETTINGS:
ACT.
PE-2 = 8 PSI
PE-3 = 10 PSI
VEL. CNTRLR PE-4 = 12 PSI
BAL. TAPS (RESET BAND=3-8 PSI)
B
FLOW LO X CONSTANT
M 20 PSI MAIN
PROBE HI Y VOLUME
T TOTAL AIR
R.A.. STAT COLD AIR HEAT
FLOW

AIR
1 PIPE
AIR

FLOW PLENUM AIR


RESTRICTOR
OR OR 20 PSI MAIN

R.A.. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE3 2 PIPE HOT T-STAT BRANCH PRESSURE (PSIG) COLD
PE4 PE2
ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE 1 = LOAD BEARING P.E.
SWITCH

1 2.8 6.7 E = 120V/1PH/60HZ - 2 STAGE


LOAD BEARING
P.E.

PER STAGE 2 1.4 3.3 5 = 120V/1PH/60HZ - 3 STAGE


3 0.9 2.2
K = 277V/1PH/60HZ - 1 STAGE
DISCONNECT

L = 277V/1PH/60HZ - 2 STAGE
SIZE & TYPE

DNF-40 2.8 6.7 Y = 277V/1PH/60HZ - 3 STAGE


DOOR INTERLOCK
BLOCK
FUSE

30 AMP BLOCK 2.8 6.7

1. MAX. K.W. BASED ON P.E. MAX LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.008 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5F020

REV.1 8/5/00 PNEUMATIC


PSFH082
- J82 -

YORK INTERNATIONAL 91
SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT
PRESS. INDEPENDENT, N.O. DAMPER, P.E. FAN START, REVERSE ACTING STAT, 1 PHASE, LOAD BEARING P.E. SWITCH

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V
SIGNAL TO PE1 ENERGIZES THE FAN.
DISCONNECT
SPACE TEMP WARM (STAT OUTPUT LOW). AT A STAT
SWITCH
OUTPUT OF 3 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
FUSING WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
OPTIONAL DISCONNECT SWITCH
ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
AND OR FUSING
PANEL WIRING DIAGRAM ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.

AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.


L1 (N) = 120V & 277V
TERMINAL 1 2 NOTE: ON START UP, BLOWER FAN MOTOR MUST BE
BLOCK ENERGIZED BEFORE PRIMARY AIR FAN. FAN CONTROL
BK WH
REQUIRES PROPER SETTING OF PE1 SWITCH BY TEMP.
CONTROL CONTRACTOR.
C NO
BK BK C NO BK WH G ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
PE-1 5 JOB SPECIFICATIONS.
NC
PE-2 STANDARD 1
NC STAGE HEAT
RD C NO RD

PE-3 OPTIONAL 2
NC STAGE HEAT
BN C NO BN

PE-4 OPTIONAL 3
NC STAGE HEAT

BK BL/WH BK
SC FM

PE1
P.E. SWITCH SUPPLIED BY FACTORY
(SIGNAL BY OTHERS)

PNEUMATIC DIAGRAM
N.O.
ACT. RECOMMENDED FIELD P.E. SWITCH SETTINGS:

PE-2 = 8 PSI
VEL. CNTRLR
PE-3 = 10 PSI
BAL. TAPS (RESET BAND=8-13 PSI)
PE-4 = 12 PSI
B
FLOW LO Y
M 20 PSI MAIN CONSTANT
PROBE HI X
T VOLUME
TOTAL AIR
REV. R.A.. STAT
FLOW

COLD AIR HEAT


RELAY 1 PIPE AIR
AIR

M FLOW PLENUM AIR


1 RESTRICTOR
3 OR OR 20 PSI MAIN

R.A.. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
2 PIPE HOT COLD
PE4 PE3 PE2 T-STAT BRANCH PRESSURE (PSIG)
ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE 1 = LOAD BEARING P.E.
SWITCH

1 2.8 6.7 E = 120V/1PH/60HZ - 2 STAGE


LOAD BEARING
P.E.

PER STAGE 2 1.4 3.3 5 = 120V/1PH/60HZ - 3 STAGE


3 0.9 2.2
K = 277V/1PH/60HZ - 1 STAGE
DISCONNECT

L = 277V/1PH/60HZ - 2 STAGE
SIZE & TYPE

DNF-40 2.8 6.7 Y = 277V/1PH/60HZ - 3 STAGE


DOOR INTERLOCK
BLOCK
FUSE

30 AMP BLOCK 2.8 6.7

1. MAX. K.W. BASED ON P.E. MAX LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.016 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5G020

REV.1 8/5/00 PNEUMATIC


PSFH083
- J83 -

92 YORK INTERNATIONAL
FORM AD1T-SECT J

SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT


PRESS. INDEPENDENT, N.C. DAMPER, P.E. FAN START, DIRECT ACTING STAT, 1 PHASE, LOAD BEARING P.E. SWITCH

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V
SIGNAL TO PE1 ENERGIZES THE FAN.
DISCONNECT
SPACE TEMP WARM (STAT OUTPUT HI). AT A STAT
SWITCH
OUTPUT OF 13 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
FUSING WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
OPTIONAL DISCONNECT SWITCH
ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
AND OR FUSING
PANEL WIRING DIAGRAM ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.

AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.


L1 (N) = 120V & 277V
TERMINAL 1 2 NOTE: ON START UP, BLOWER FAN MOTOR MUST BE
BLOCK ENERGIZED BEFORE PRIMARY AIR FAN. FAN CONTROL
BK WH REQUIRES PROPER SETTING OF PE1 SWITCH BY TEMP.
CONTROL CONTRACTOR.
C NO
BK BK C NO BK WH G ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
PE-1 5 JOB SPECIFICATIONS.
NC
PE-2 STANDARD 1
NC STAGE HEAT
RD C NO RD

PE-3 OPTIONAL 2
NC STAGE HEAT
BN C NO BN

PE-4 OPTIONAL 3
NC STAGE HEAT

BK BL/WH BK
SC FM

PE1
P.E. SWITCH SUPPLIED BY FACTORY
(SIGNAL BY OTHERS)

PNEUMATIC DIAGRAM
N.C.
RECOMMENDED FIELD P.E. SWITCH SETTINGS:
ACT.
PE-2 = 8 PSI
VEL. CNTRLR PE-3 = 6 PSI
BAL. TAPS (RESET BAND=3-8 PSI) PE-4 = 4 PSI
B
FLOW LO X
M 20 PSI MAIN CONSTANT
PROBE HI Y
T VOLUME
TOTAL AIR
REV. D.A.. STAT
FLOW

HEAT COLD AIR


RELAY 1 PIPE
AIR

AIR
M FLOW PLENUM AIR
1 RESTRICTOR
3 OR OR 20 PSI MAIN

D.A.. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
2 PIPE
PE4 PE3 PE2 COLD T-STAT BRANCH PRESSURE (PSIG) HOT
ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE 1 = LOAD BEARING P.E.
SWITCH

1 2.8 6.7 E = 120V/1PH/60HZ - 2 STAGE


LOAD BEARING
P.E.

PER STAGE 2 1.4 3.3 5 = 120V/1PH/60HZ - 3 STAGE


3 0.9 2.2
K = 277V/1PH/60HZ - 1 STAGE
DISCONNECT

L = 277V/1PH/60HZ - 2 STAGE
SIZE & TYPE

DNF-40 2.8 6.7 Y = 277V/1PH/60HZ - 3 STAGE


DOOR INTERLOCK
BLOCK
FUSE

30 AMP BLOCK 2.8 6.7

1. MAX. K.W. BASED ON P.E. MAX LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.016 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5H020

REV.1 8/5/00 PNEUMATIC


PSFH084
- J84 -

YORK INTERNATIONAL 93
SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT
PRESS. INDEPENDENT, N.O. DAMPER, P.E. FAN START, DIRECT ACTING STAT, 1 PHASE, LOAD BEARING P.E. SWITCH W/ CONT. INTRLK.

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V
SIGNAL TO PE1 ENERGIZES THE FAN.
DISCONNECT
SPACE TEMP WARM (STAT OUTPUT HI). AT A STAT
SWITCH
OUTPUT OF 13 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
FUSING WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
OPTIONAL DISCONNECT SWITCH
ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
AND OR FUSING
PANEL WIRING DIAGRAM ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.

L1 (N) = 120V & 277V AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
TERMINAL 1 2
BLOCK NOTE: ON START UP, BLOWER FAN MOTOR MUST BE
BK WH ENERGIZED BEFORE PRIMARY AIR FAN. FAN CONTROL
REQUIRES PROPER SETTING OF PE1 SWITCH BY TEMP.
BK BK WH CONTROL CONTRACTOR.

C1-1 STANDARD 1 G ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY


STAGE HEAT JOB SPECIFICATIONS.
RD C NO RD

PE-3 OPTIONAL 2
NC STAGE HEAT
BN C NO BN

PE-4 OPTIONAL 3
NC STAGE HEAT
(WHEN REQ.)
BK
TC BK C NO BK
C1
PE-2
NC
C NO BK BL/WH BK
BK
5 SC FM
PE-1
NC

PE1
P.E. SWITCH SUPPLIED BY FACTORY
(SIGNAL BY OTHERS)

PNEUMATIC DIAGRAM
N.O. RECOMMENDED FIELD P.E. SWITCH SETTINGS:

ACT. PE-2 = 8 PSI


PE-3 = 6 PSI
VEL. CNTRLR PE-4 = 4 PSI
BAL. TAPS (RESET BAND=8-13 PSI)
B
FLOW LO Y
M 20 PSI MAIN CONSTANT
PROBE HI X
T VOLUME
TOTAL AIR
D.A.. STAT HEAT
FLOW

1 PIPE COLD AIR


AIR
AIR

FLOW PLENUM AIR


RESTRICTOR
OR OR 20 PSI MAIN

D.A.. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
2 PIPE COLD HOT
PE4 PE3 PE2 T-STAT BRANCH PRESSURE (PSIG)
ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE J = LOAD BEARING P.E. W/ 30A
1 3.6 8.3 E = 120V/1PH/60HZ - 2 STAGE MAG. CONTACTOR INTERLOCK
30 AMP CONT.
LOAD BRG. PE

2 1.8 4.1 5 = 120V/1PH/60HZ - 3 STAGE K = LOAD BEARING P.E. W/ 50A


W/ INTRLK

PER STAGE 3 1.2 2.7


K = 277V/1PH/60HZ - 1 STAGE MAG. CONTACTOR INTERLOCK
1 5.7 13.2
50 AMP CONT. L = 277V/1PH/60HZ - 2 STAGE L = LOAD BEARING P.E. W/ 30A
2 2.8 6.6 MERC. CONTACTOR INTERLOCK
PER STAGE Y = 277V/1PH/60HZ - 3 STAGE
3 1.9 4.4
M = LOAD BEARING P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR INTERLOCK


SIZE & TYPE

DOOR INTERLOCK 4.8 11.0

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 5.7 13.2
BLOCK

30 AMP BLOCK
FUSE

2.8 6.6

60 AMP BLOCK 5.7 13.2

1. MAX. K.W. BASED ON 48A, P.E., OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.008 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5E020

REV.1 8/5/00 PNEUMATIC


PSFH085
- J85 -

94 YORK INTERNATIONAL
FORM AD1T-SECT J

SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT


PRESS. INDEPENDENT, N.C. DAMPER, P.E. FAN START, REVERSE ACTING STAT, 1 PHASE, LOAD BEARING P.E. SWITCH W/ CONT. INTRLK.

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V
SIGNAL TO PE1 ENERGIZES THE FAN.
DISCONNECT
SPACE TEMP WARM (STAT OUTPUT LOW). AT A STAT
SWITCH
OUTPUT OF 3 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
FUSING WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
OPTIONAL DISCONNECT SWITCH
ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
AND OR FUSING
PANEL WIRING DIAGRAM ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.

L1 (N) = 120V & 277V AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
TERMINAL 1 2
BLOCK NOTE: ON START UP, BLOWER FAN MOTOR MUST BE
BK WH ENERGIZED BEFORE PRIMARY AIR FAN. FAN CONTROL
REQUIRES PROPER SETTING OF PE1 SWITCH BY TEMP.
BK BK WH CONTROL CONTRACTOR.

C1-1 STANDARD 1 G ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY


STAGE HEAT JOB SPECIFICATIONS.
RD C NO RD

PE-3 OPTIONAL 2
NC STAGE HEAT
BN C NO BN

PE-4 OPTIONAL 3
NC STAGE HEAT
(WHEN REQ.)
BK
TC BK C NO BK
C1
PE-2
NC
C NO BK BL/WH BK
BK
5 SC FM
PE-1
NC

PE1
P.E. SWITCH SUPPLIED BY FACTORY
(SIGNAL BY OTHERS)

PNEUMATIC DIAGRAM
N.C. RECOMMENDED FIELD P.E. SWITCH SETTINGS:
ACT.
PE-2 = 8 PSI
PE-3 = 10 PSI
VEL. CNTRLR PE-4 = 12 PSI
BAL. TAPS (RESET BAND=3-8 PSI)
B
FLOW LO X CONSTANT
M 20 PSI MAIN
PROBE HI Y VOLUME
T TOTAL AIR
R.A.. STAT COLD AIR HEAT
FLOW

AIR
1 PIPE
AIR

FLOW PLENUM AIR


RESTRICTOR
OR OR 20 PSI MAIN

R.A.. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE3 2 PIPE HOT T-STAT BRANCH PRESSURE (PSIG) COLD
PE4 PE2
ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE J = LOAD BEARING P.E. W/ 30A
1 3.6 8.3 E = 120V/1PH/60HZ - 2 STAGE MAG. CONTACTOR INTERLOCK
30 AMP CONT.
LOAD BRG. PE

2 1.8 4.1 5 = 120V/1PH/60HZ - 3 STAGE K = LOAD BEARING P.E. W/ 50A


W/ INTRLK

PER STAGE 3 1.2 2.7


K = 277V/1PH/60HZ - 1 STAGE MAG. CONTACTOR INTERLOCK
1 5.7 13.2
50 AMP CONT. L = 277V/1PH/60HZ - 2 STAGE L = LOAD BEARING P.E. W/ 30A
2 2.8 6.6 MERC. CONTACTOR INTERLOCK
PER STAGE Y = 277V/1PH/60HZ - 3 STAGE
3 1.9 4.4
M = LOAD BEARING P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR INTERLOCK


SIZE & TYPE

DOOR INTERLOCK 4.8 11.0

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 5.7 13.2
BLOCK

30 AMP BLOCK
FUSE

2.8 6.6

60 AMP BLOCK 5.7 13.2

1. MAX. K.W. BASED ON 48A, P.E., OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.008 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5F020

REV.1 8/5/00 PNEUMATIC


PSFH086
- J86 -

YORK INTERNATIONAL 95
SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT
PRESS. INDEPENDENT, N.O. DAMPER, P.E. FAN START, REVERSE ACTING STAT, 1 PHASE, LOAD BEARING P.E. SWITCH W/ CONT. INTRLK.

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V
SIGNAL TO PE1 ENERGIZES THE FAN.
DISCONNECT
SPACE TEMP WARM (STAT OUTPUT LOW). AT A STAT
SWITCH
OUTPUT OF 3 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
FUSING WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
OPTIONAL DISCONNECT SWITCH
ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
AND OR FUSING
PANEL WIRING DIAGRAM ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.

L1 (N) = 120V & 277V AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
TERMINAL 1 2
BLOCK NOTE: ON START UP, BLOWER FAN MOTOR MUST BE
BK WH ENERGIZED BEFORE PRIMARY AIR FAN. FAN CONTROL
REQUIRES PROPER SETTING OF PE1 SWITCH BY TEMP.
BK BK WH CONTROL CONTRACTOR.

C1-1 STANDARD 1 G ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY


STAGE HEAT JOB SPECIFICATIONS.
RD C NO RD

PE-3 OPTIONAL 2
NC STAGE HEAT
BN C NO BN

PE-4 OPTIONAL 3
NC STAGE HEAT
(WHEN REQ.)
BK
TC BK C NO BK
C1
PE-2
NC
C NO BK BL/WH BK
BK
5 SC FM
PE-1
NC

PE1
P.E. SWITCH SUPPLIED BY FACTORY
(SIGNAL BY OTHERS)

PNEUMATIC DIAGRAM
N.O.
ACT. RECOMMENDED FIELD P.E. SWITCH SETTINGS:

PE-2 = 8 PSI
VEL. CNTRLR
PE-3 = 10 PSI
BAL. TAPS (RESET BAND=8-13 PSI)
PE-4 = 12 PSI
B
FLOW LO Y
M 20 PSI MAIN CONSTANT
PROBE HI X
T VOLUME
TOTAL AIR
REV. R.A.. STAT
FLOW

COLD AIR HEAT


RELAY 1 PIPE AIR
AIR

M FLOW PLENUM AIR


1 RESTRICTOR
3 OR OR 20 PSI MAIN

R.A.. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
2 PIPE HOT COLD
PE4 PE3 PE2 T-STAT BRANCH PRESSURE (PSIG)
ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE J = LOAD BEARING P.E. W/ 30A
1 3.6 8.3 E = 120V/1PH/60HZ - 2 STAGE MAG. CONTACTOR INTERLOCK
30 AMP CONT.
LOAD BRG. PE

2 1.8 4.1 5 = 120V/1PH/60HZ - 3 STAGE K = LOAD BEARING P.E. W/ 50A


W/ INTRLK

PER STAGE 3 1.2 2.7


K = 277V/1PH/60HZ - 1 STAGE MAG. CONTACTOR INTERLOCK
1 5.7 13.2
50 AMP CONT. L = 277V/1PH/60HZ - 2 STAGE L = LOAD BEARING P.E. W/ 30A
2 2.8 6.6 MERC. CONTACTOR INTERLOCK
PER STAGE Y = 277V/1PH/60HZ - 3 STAGE
3 1.9 4.4
M = LOAD BEARING P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR INTERLOCK


SIZE & TYPE

DOOR INTERLOCK 4.8 11.0

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 5.7 13.2
BLOCK

30 AMP BLOCK
FUSE

2.8 6.6

60 AMP BLOCK 5.7 13.2

1. MAX. K.W. BASED ON 48A, P.E., OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.016 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5G020

REV.1 8/5/00 PNEUMATIC


PSFH087
- J87 -

96 YORK INTERNATIONAL
FORM AD1T-SECT J

SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT


PRESS. INDEPENDENT, N.C. DAMPER, P.E. FAN START, DIRECT ACTING STAT, 1 PHASE, LOAD BEARING P.E. SWITCH W/ CONT. INTRLK.

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V
SIGNAL TO PE1 ENERGIZES THE FAN.
DISCONNECT
SPACE TEMP WARM (STAT OUTPUT HI). AT A STAT
SWITCH
OUTPUT OF 13 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
FUSING WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
OPTIONAL DISCONNECT SWITCH
ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
AND OR FUSING
PANEL WIRING DIAGRAM ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.

L1 (N) = 120V & 277V AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
TERMINAL 1 2
BLOCK NOTE: ON START UP, BLOWER FAN MOTOR MUST BE
BK WH ENERGIZED BEFORE PRIMARY AIR FAN. FAN CONTROL
REQUIRES PROPER SETTING OF PE1 SWITCH BY TEMP.
BK BK WH CONTROL CONTRACTOR.

C1-1 STANDARD 1 G ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY


STAGE HEAT JOB SPECIFICATIONS.
RD C NO RD

PE-3 OPTIONAL 2
NC STAGE HEAT
BN C NO BN

PE-4 OPTIONAL 3
NC STAGE HEAT
(WHEN REQ.)
BK
TC BK C NO BK
C1
PE-2
NC
C NO BK BL/WH BK
BK
5 SC FM
PE-1
NC

PE1
P.E. SWITCH SUPPLIED BY FACTORY
(SIGNAL BY OTHERS)

PNEUMATIC DIAGRAM
N.C.
RECOMMENDED FIELD P.E. SWITCH SETTINGS:
ACT.
PE-2 = 8 PSI
VEL. CNTRLR PE-3 = 6 PSI
BAL. TAPS (RESET BAND=3-8 PSI) PE-4 = 4 PSI
B
FLOW LO X
M 20 PSI MAIN CONSTANT
PROBE HI Y
T VOLUME
TOTAL AIR
REV. D.A.. STAT
FLOW

HEAT COLD AIR


RELAY 1 PIPE
AIR

AIR
M FLOW PLENUM AIR
1 RESTRICTOR
3 OR OR 20 PSI MAIN

D.A.. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
2 PIPE
PE4 PE3 PE2 COLD T-STAT BRANCH PRESSURE (PSIG) HOT
ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE J = LOAD BEARING P.E. W/ 30A
1 3.6 8.3 E = 120V/1PH/60HZ - 2 STAGE MAG. CONTACTOR INTERLOCK
30 AMP CONT.
LOAD BRG. PE

2 1.8 4.1 5 = 120V/1PH/60HZ - 3 STAGE K = LOAD BEARING P.E. W/ 50A


W/ INTRLK

PER STAGE 3 1.2 2.7


K = 277V/1PH/60HZ - 1 STAGE MAG. CONTACTOR INTERLOCK
1 5.7 13.2
50 AMP CONT. L = 277V/1PH/60HZ - 2 STAGE L = LOAD BEARING P.E. W/ 30A
2 2.8 6.6 MERC. CONTACTOR INTERLOCK
PER STAGE Y = 277V/1PH/60HZ - 3 STAGE
3 1.9 4.4
M = LOAD BEARING P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR INTERLOCK


SIZE & TYPE

DOOR INTERLOCK 4.8 11.0

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 5.7 13.2
BLOCK

30 AMP BLOCK
FUSE

2.8 6.6

60 AMP BLOCK 5.7 13.2

1. MAX. K.W. BASED ON 48A, P.E., OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.016 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5H020

REV.1 8/5/00 PNEUMATIC


PSFH088
- J88 -

YORK INTERNATIONAL 97
SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT
PRESS. INDEPENDENT, N.O. DAMPER, P.E. FAN START, DIRECT ACTING STAT, 1 PHASE, PILOT DUTY P.E. SWITCH

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V
SIGNAL TO PE1 ENERGIZES THE FAN.
DISCONNECT
SPACE TEMP WARM (STAT OUTPUT HI). AT A STAT
SWITCH
OUTPUT OF 13 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
FUSING WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
OPTIONAL DISCONNECT SWITCH
ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
AND OR FUSING
PANEL WIRING DIAGRAM ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.

L1 (N) = 120V & 277V AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
TERMINAL 1 2
BLOCK NOTE: ON START UP, BLOWER FAN MOTOR MUST BE
BK WH ENERGIZED BEFORE PRIMARY AIR FAN. FAN CONTROL
REQUIRES PROPER SETTING OF PE1 SWITCH BY TEMP.
BK BK WH CONTROL CONTRACTOR.

C1-1 STANDARD 1 ST. HEAT G ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
RD RD JOB SPECIFICATIONS.
OPTIONAL 2 ST. HEAT
C2-1
BN BN

C NO (WHEN REQ.) C3-1 OPTIONAL 3 ST. HEAT


BK
TC C NO BK ST.1
BK BK
PE-1 5 C1
NC
PE-2
NC
ST.2
RD C NO RD
C2
PE-3
NC
ST.3
BN C NO BN
C3
PE-4
NC
BK BL/WH BK
SC FM

PE1
P.E. SWITCH SUPPLIED BY FACTORY
(SIGNAL BY OTHERS)
PNEUMATIC DIAGRAM
N.O. RECOMMENDED FIELD P.E. SWITCH SETTINGS:

ACT. PE-2 = 8 PSI


PE-3 = 6 PSI
VEL. CNTRLR PE-4 = 4 PSI
BAL. TAPS (RESET BAND=8-13 PSI)
B
FLOW LO Y
M 20 PSI MAIN CONSTANT
PROBE HI X
T VOLUME
TOTAL AIR
D.A.. STAT HEAT
FLOW

1 PIPE COLD AIR


AIR
AIR

FLOW PLENUM AIR


RESTRICTOR
OR OR 20 PSI MAIN

D.A.. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
2 PIPE COLD HOT
PE4 PE3 PE2 T-STAT BRANCH PRESSURE (PSIG)
ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE 2 = PILOT DUTY P.E. W/ 30A
1 3.6 8.3 E = 120V/1PH/60HZ - 2 STAGE MAG. CONTACTOR
DE-ENERGIZING
CONTACTOR

30 AMP 2 2.8 6.6 5 = 120V/1PH/60HZ - 3 STAGE 3 = PILOT DUTY P.E. W/ 50A


CONTACTOR 3 1.9 4.4
K = 277V/1PH/60HZ - 1 STAGE MAG. CONTACTOR
1 5.7 13.2
50 AMP L = 277V/1PH/60HZ - 2 STAGE 4 = PILOT DUTY P.E. W/ 30A
2 2.8 6.6 MERC. CONTACTOR
CONTACTOR Y = 277V/1PH/60HZ - 3 STAGE
3 1.9 4.4
5 = PILOT DUTY P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR


SIZE & TYPE

DOOR INTERLOCK 4.8 11.0

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 5.7 13.2
BLOCK

30 AMP BLOCK
FUSE

2.8 6.6

60 AMP BLOCK 5.7 13.2

1. MAX. K.W. BASED ON 48A, OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.008 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5E020

REV.1 8/5/00 PNEUMATIC


PSFH089
- J89 -

98 YORK INTERNATIONAL
FORM AD1T-SECT J

SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT


PRESS. INDEPENDENT, N.C. DAMPER, P.E. FAN START, REVERSE ACTING STAT, 1 PHASE, PILOT DUTY P.E. SWITCH

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V
SIGNAL TO PE1 ENERGIZES THE FAN.
DISCONNECT
SPACE TEMP WARM (STAT OUTPUT LOW). AT A STAT
SWITCH
OUTPUT OF 3 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
FUSING WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
OPTIONAL DISCONNECT SWITCH
ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
AND OR FUSING
PANEL WIRING DIAGRAM ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.

L1 (N) = 120V & 277V AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
TERMINAL 1 2
BLOCK NOTE: ON START UP, BLOWER FAN MOTOR MUST BE
BK WH ENERGIZED BEFORE PRIMARY AIR FAN. FAN CONTROL
REQUIRES PROPER SETTING OF PE1 SWITCH BY TEMP.
BK BK WH CONTROL CONTRACTOR.

C1-1 STANDARD 1 ST. HEAT G ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
RD RD JOB SPECIFICATIONS.
OPTIONAL 2 ST. HEAT
C2-1
BN BN

C NO (WHEN REQ.) C3-1 OPTIONAL 3 ST. HEAT


BK
TC C NO BK ST.1
BK BK
PE-1 5 C1
NC
PE-2
NC
ST.2
RD C NO RD
C2
PE-3
NC
ST.3
BN C NO BN
C3
PE-4
NC
BK BL/WH BK
SC FM

PE1
P.E. SWITCH SUPPLIED BY FACTORY
(SIGNAL BY OTHERS)

PNEUMATIC DIAGRAM
N.C. RECOMMENDED FIELD P.E. SWITCH SETTINGS:
ACT.
PE-2 = 8 PSI
PE-3 = 10 PSI
VEL. CNTRLR PE-4 = 12 PSI
BAL. TAPS (RESET BAND=3-8 PSI)
B
FLOW LO X CONSTANT
M 20 PSI MAIN
PROBE HI Y VOLUME
T TOTAL AIR
R.A.. STAT COLD AIR HEAT
FLOW

AIR
1 PIPE
AIR

FLOW PLENUM AIR


RESTRICTOR
OR OR 20 PSI MAIN

R.A.. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE3 2 PIPE HOT T-STAT BRANCH PRESSURE (PSIG) COLD
PE4 PE2
ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE 2 = PILOT DUTY P.E. W/ 30A
1 3.6 8.3 E = 120V/1PH/60HZ - 2 STAGE MAG. CONTACTOR
DE-ENERGIZING
CONTACTOR

30 AMP 2 2.8 6.6 5 = 120V/1PH/60HZ - 3 STAGE 3 = PILOT DUTY P.E. W/ 50A


CONTACTOR 3 1.9 4.4
K = 277V/1PH/60HZ - 1 STAGE MAG. CONTACTOR
1 5.7 13.2
50 AMP L = 277V/1PH/60HZ - 2 STAGE 4 = PILOT DUTY P.E. W/ 30A
2 2.8 6.6 MERC. CONTACTOR
CONTACTOR Y = 277V/1PH/60HZ - 3 STAGE
3 1.9 4.4
5 = PILOT DUTY P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR


SIZE & TYPE

DOOR INTERLOCK 4.8 11.0

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 5.7 13.2
BLOCK

30 AMP BLOCK
FUSE

2.8 6.6

60 AMP BLOCK 5.7 13.2

1. MAX. K.W. BASED ON 48A, OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.008 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5F020

REV.1 8/5/00 PNEUMATIC


PSFH090
- J90 -

YORK INTERNATIONAL 99
SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT
PRESS. INDEPENDENT, N.O. DAMPER, P.E. FAN START, REVERSE ACTING STAT, 1 PHASE, PILOT DUTY P.E. SWITCH

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V
SIGNAL TO PE1 ENERGIZES THE FAN.
DISCONNECT
SPACE TEMP WARM (STAT OUTPUT LOW). AT A STAT
SWITCH
OUTPUT OF 3 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
FUSING WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
OPTIONAL DISCONNECT SWITCH
ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
AND OR FUSING
PANEL WIRING DIAGRAM ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.

L1 (N) = 120V & 277V AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
TERMINAL 1 2
BLOCK NOTE: ON START UP, BLOWER FAN MOTOR MUST BE
BK WH ENERGIZED BEFORE PRIMARY AIR FAN. FAN CONTROL
REQUIRES PROPER SETTING OF PE1 SWITCH BY TEMP.
BK BK WH CONTROL CONTRACTOR.

C1-1 STANDARD 1 ST. HEAT G ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
RD RD JOB SPECIFICATIONS.
OPTIONAL 2 ST. HEAT
C2-1
BN BN

C NO (WHEN REQ.) C3-1 OPTIONAL 3 ST. HEAT


BK
TC C NO BK ST.1
BK BK
PE-1 5 C1
NC
PE-2
NC
ST.2
RD C NO RD
C2
PE-3
NC
ST.3
BN C NO BN
C3
PE-4
NC
BK BL/WH BK
SC FM

PE1
P.E. SWITCH SUPPLIED BY FACTORY
(SIGNAL BY OTHERS)
PNEUMATIC DIAGRAM
N.O.
ACT. RECOMMENDED FIELD P.E. SWITCH SETTINGS:

PE-2 = 8 PSI
VEL. CNTRLR
PE-3 = 10 PSI
BAL. TAPS (RESET BAND=8-13 PSI)
PE-4 = 12 PSI
B
FLOW LO Y
M 20 PSI MAIN CONSTANT
PROBE HI X
T VOLUME
TOTAL AIR
REV. R.A.. STAT
FLOW

COLD AIR HEAT


RELAY 1 PIPE AIR
AIR

M FLOW PLENUM AIR


1 RESTRICTOR
3 OR OR 20 PSI MAIN

R.A.. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
2 PIPE HOT COLD
PE4 PE3 PE2 T-STAT BRANCH PRESSURE (PSIG)
ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE 2 = PILOT DUTY P.E. W/ 30A
1 3.6 8.3 E = 120V/1PH/60HZ - 2 STAGE MAG. CONTACTOR
DE-ENERGIZING
CONTACTOR

30 AMP 2 2.8 6.6 5 = 120V/1PH/60HZ - 3 STAGE 3 = PILOT DUTY P.E. W/ 50A


CONTACTOR 3 1.9 4.4
K = 277V/1PH/60HZ - 1 STAGE MAG. CONTACTOR
1 5.7 13.2
50 AMP L = 277V/1PH/60HZ - 2 STAGE 4 = PILOT DUTY P.E. W/ 30A
2 2.8 6.6 MERC. CONTACTOR
CONTACTOR Y = 277V/1PH/60HZ - 3 STAGE
3 1.9 4.4
5 = PILOT DUTY P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR


SIZE & TYPE

DOOR INTERLOCK 4.8 11.0

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 5.7 13.2
BLOCK

30 AMP BLOCK
FUSE

2.8 6.6

60 AMP BLOCK 5.7 13.2

1. MAX. K.W. BASED ON 48A, OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.016 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5G020

REV.1 8/5/00 PNEUMATIC


PSFH091
- J91 -

100 YORK INTERNATIONAL


FORM AD1T-SECT J

SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT


PRESS. INDEPENDENT, N.C. DAMPER, P.E. FAN START, DIRECT ACTING STAT, 1 PHASE, PILOT DUTY P.E. SWITCH

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V
SIGNAL TO PE1 ENERGIZES THE FAN.
DISCONNECT
SPACE TEMP WARM (STAT OUTPUT HI). AT A STAT
SWITCH
OUTPUT OF 13 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
FUSING WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
OPTIONAL DISCONNECT SWITCH
ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
AND OR FUSING
PANEL WIRING DIAGRAM ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.

L1 (N) = 120V & 277V AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
TERMINAL 1 2
BLOCK NOTE: ON START UP, BLOWER FAN MOTOR MUST BE
BK WH ENERGIZED BEFORE PRIMARY AIR FAN. FAN CONTROL
REQUIRES PROPER SETTING OF PE1 SWITCH BY TEMP.
BK BK WH CONTROL CONTRACTOR.

C1-1 STANDARD 1 ST. HEAT G ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
RD RD JOB SPECIFICATIONS.
OPTIONAL 2 ST. HEAT
C2-1
BN BN

C NO (WHEN REQ.) C3-1 OPTIONAL 3 ST. HEAT


BK
TC C NO BK ST.1
BK BK
PE-1 5 C1
NC
PE-2
NC
ST.2
RD C NO RD
C2
PE-3
NC
ST.3
BN C NO BN
C3
PE-4
NC
BK BL/WH BK
SC FM

PE1
P.E. SWITCH SUPPLIED BY FACTORY
(SIGNAL BY OTHERS)

PNEUMATIC DIAGRAM
N.C.
RECOMMENDED FIELD P.E. SWITCH SETTINGS:
ACT.
PE-2 = 8 PSI
VEL. CNTRLR PE-3 = 6 PSI
BAL. TAPS (RESET BAND=3-8 PSI) PE-4 = 4 PSI
B
FLOW LO X
M 20 PSI MAIN CONSTANT
PROBE HI Y
T VOLUME
TOTAL AIR
REV. D.A.. STAT
FLOW

HEAT COLD AIR


RELAY 1 PIPE
AIR

AIR
M FLOW PLENUM AIR
1 RESTRICTOR
3 OR OR 20 PSI MAIN

D.A.. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
2 PIPE
PE4 PE3 PE2 COLD T-STAT BRANCH PRESSURE (PSIG) HOT
ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE 2 = PILOT DUTY P.E. W/ 30A
1 3.6 8.3 E = 120V/1PH/60HZ - 2 STAGE MAG. CONTACTOR
DE-ENERGIZING
CONTACTOR

30 AMP 2 2.8 6.6 5 = 120V/1PH/60HZ - 3 STAGE 3 = PILOT DUTY P.E. W/ 50A


CONTACTOR 3 1.9 4.4
K = 277V/1PH/60HZ - 1 STAGE MAG. CONTACTOR
1 5.7 13.2
50 AMP L = 277V/1PH/60HZ - 2 STAGE 4 = PILOT DUTY P.E. W/ 30A
2 2.8 6.6 MERC. CONTACTOR
CONTACTOR Y = 277V/1PH/60HZ - 3 STAGE
3 1.9 4.4
5 = PILOT DUTY P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR


SIZE & TYPE

DOOR INTERLOCK 4.8 11.0

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 5.7 13.2
BLOCK

30 AMP BLOCK
FUSE

2.8 6.6

60 AMP BLOCK 5.7 13.2

1. MAX. K.W. BASED ON 48A, OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.016 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5H020

REV.1 8/5/00 PNEUMATIC


PSFH092
- J92 -

YORK INTERNATIONAL 101


SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT
PRESS. INDEPENDENT, N.O. DAMPER, P.E. FAN START, DIRECT ACTING STAT, 3 PHASE, LOAD BEARING P.E. SWITCH W/ CONT. INTRLK.

SEQUENCE OF OPERATION:
L1 L2 L3
SIGNAL TO PE1 ENERGIZES THE FAN.
DISCONNECT
SPACE TEMP WARM (STAT OUTPUT HI). AT A STAT
SWITCH
OUTPUT OF 13 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
FUSING WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
OPTIONAL DISCONNECT SWITCH ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
PANEL WIRING DIAGRAM AND OR FUSING ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
L1 L2 L3 N AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
TERMINAL 1 2 3 4
BLOCK NOTE: ON START UP, BLOWER FAN MOTOR MUST BE
BK WH
ENERGIZED BEFORE PRIMARY AIR FAN. FAN CONTROL
BK BL
REQUIRES PROPER SETTING OF PE1 SWITCH BY TEMP.
CONTROL CONTRACTOR.
BK STANDARD 1 STAGE HEAT
G ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
C1-1
BK BK JOB SPECIFICATIONS.
C1-2
C NO BK BK BK
ST.1 L1 1
BK TC BK C NO BK C1-1
PE-1 5 C1 C NO BL
NC L2 2
RD 3 L3
PE-2 RD RD
NC PE-3
NC C1-2
BK BL/WH BK
SC FM
OPTIONAL 2 STAGE HEAT

BK BK
L1 1
P.E. SWITCH SUPPLIED BY FACTORY C1-1
PE1 C NO
(SIGNAL BY OTHERS) L2 2
RD

RD
PE-3
NC
BN C NO BN

PE-4
NC
BL BL
L3 3
PNEUMATIC DIAGRAM C1-2
N.O. OPTIONAL 3 STAGE HEAT
ACT. RECOMMENDED FIELD P.E. SWITCH SETTINGS:

VEL. CNTRLR PE-2 = 8 PSI


BAL. TAPS (RESET BAND=8-13 PSI) PE-3 = 6 PSI
B PE-4 = 4 PSI
FLOW LO Y
M 20 PSI MAIN CONSTANT
PROBE HI X
T VOLUME
TOTAL AIR
D.A.. STAT HEAT
FLOW

1 PIPE COLD AIR


AIR
AIR

FLOW PLENUM AIR


RESTRICTOR
OR OR 20 PSI MAIN

D.A.. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
2 PIPE COLD HOT
PE4 PE3 PE2 T-STAT BRANCH PRESSURE (PSIG)
ROOM ROOM

HEATER COMPONENTS MAX. KW


3 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-3 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 208 V 480 V P = 208V/3PH/60HZ - 1 STAGE J = LOAD BEARING P.E. W/ 30A
1 10.7 24.9 R = 208V/3PH/60HZ - 2 STAGE MAG. CONTACTOR INTERLOCK
30 AMP CONT.
LOAD BRG. PE

2 4.4 9.1 1 = 208V/3PH/60HZ - 3 STAGE K = LOAD BEARING P.E. W/ 50A


W/ INTRLK

PER STAGE 3 2.9 6.0


U = 480V/3PH/60HZ - 1 STAGE MAG. CONTACTOR INTERLOCK
1 17.2 39.8
50 AMP CONT. W = 480V/3PH/60HZ - 2 STAGE L = LOAD BEARING P.E. W/ 30A
2 4.4 9.1 MERC. CONTACTOR INTERLOCK
PER STAGE 3 = 480V/3PH/60HZ - 3 STAGE
3 2.9 6.0
M = LOAD BEARING P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR INTERLOCK


SIZE & TYPE

DOOR INTERLOCK 14.3 33.2

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 17.2 39.8
BLOCK

30 AMP BLOCK
FUSE

8.6 19.9

60 AMP BLOCK 17.2 39.8

1. MAX. K.W. BASED ON 48A, P.E., OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.008 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5E020

REV.1 8/5/00 PNEUMATIC


PSFH093
- J93 -

102 YORK INTERNATIONAL


FORM AD1T-SECT J

SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT


PRESS. INDEPENDENT, N.C. DAMPER, P.E. FAN START, REVERSE ACTING STAT, 3 PHASE, LOAD BEARING P.E. SWITCH W/ CONT. INTRLK.

SEQUENCE OF OPERATION:
L1 L2 L3
SIGNAL TO PE1 ENERGIZES THE FAN.
DISCONNECT
SPACE TEMP WARM (STAT OUTPUT LOW). AT A STAT
SWITCH
OUTPUT OF 3 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
FUSING WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
OPTIONAL DISCONNECT SWITCH ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
PANEL WIRING DIAGRAM AND OR FUSING ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
L1 L2 L3 N AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
TERMINAL 1 2 3 4
BLOCK NOTE: ON START UP, BLOWER FAN MOTOR MUST BE
BK WH
ENERGIZED BEFORE PRIMARY AIR FAN. FAN CONTROL
BK BL
REQUIRES PROPER SETTING OF PE1 SWITCH BY TEMP.
CONTROL CONTRACTOR.
BK STANDARD 1 STAGE HEAT
G ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
C1-1
BK BK JOB SPECIFICATIONS.
C1-2
C NO BK
BK BK
TC ST.1 L1 1
BK BK C NO BK
PE-1 5 C1 C NO C1-1 BL
NC L2 2
RD 3 L3
RD
PE-2 RD
NC PE-3
NC C1-2
BK BL/WH BK
SC FM
OPTIONAL 2 STAGE HEAT

BK BK
L1 1
PE1
P.E. SWITCH SUPPLIED BY FACTORY C1-1
(SIGNAL BY OTHERS) RD
C NO
L2 2 RD

PE-3
NC
BN C NO BN

PE-4
NC
BL BL
L3 3
C1-2
PNEUMATIC DIAGRAM
N.C. OPTIONAL 3 STAGE HEAT

ACT. RECOMMENDED FIELD P.E. SWITCH SETTINGS:

PE-2 = 8 PSI
VEL. CNTRLR
PE-3 = 10 PSI
BAL. TAPS (RESET BAND=3-8 PSI)
PE-4 = 12 PSI
B
FLOW LO X
M 20 PSI MAIN CONSTANT
PROBE HI Y
T VOLUME
TOTAL AIR
R.A.. STAT HEAT
FLOW

COLD AIR
1 PIPE AIR
AIR

FLOW PLENUM AIR


RESTRICTOR
OR OR 20 PSI MAIN

R.A.. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE4 PE3 PE2 2 PIPE HOT COLD
T-STAT BRANCH PRESSURE (PSIG)
ROOM ROOM

HEATER COMPONENTS MAX. KW


3 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-3 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 208 V 480 V P = 208V/3PH/60HZ - 1 STAGE J = LOAD BEARING P.E. W/ 30A
1 10.7 24.9 R = 208V/3PH/60HZ - 2 STAGE MAG. CONTACTOR INTERLOCK
30 AMP CONT.
LOAD BRG. PE

2 4.4 9.1 1 = 208V/3PH/60HZ - 3 STAGE K = LOAD BEARING P.E. W/ 50A


W/ INTRLK

PER STAGE 3 2.9 6.0


U = 480V/3PH/60HZ - 1 STAGE MAG. CONTACTOR INTERLOCK
1 17.2 39.8
50 AMP CONT. W = 480V/3PH/60HZ - 2 STAGE L = LOAD BEARING P.E. W/ 30A
2 4.4 9.1 MERC. CONTACTOR INTERLOCK
PER STAGE 3 = 480V/3PH/60HZ - 3 STAGE
3 2.9 6.0
M = LOAD BEARING P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR INTERLOCK


SIZE & TYPE

DOOR INTERLOCK 14.3 33.2

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 17.2 39.8
BLOCK

30 AMP BLOCK
FUSE

8.6 19.9

60 AMP BLOCK 17.2 39.8

1. MAX. K.W. BASED ON 48A, P.E., OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.008 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5F020

REV.1 8/5/00 PNEUMATIC


PSFH094
- J94 -

YORK INTERNATIONAL 103


SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT
PRESS. INDEPENDENT, N.O. DAMPER, P.E. FAN START, REVERSE ACTING STAT, 3 PHASE, LOAD BEARING P.E. SWITCH W/ CONT. INTRLK.

SEQUENCE OF OPERATION:
L1 L2 L3
SIGNAL TO PE1 ENERGIZES THE FAN.
DISCONNECT
SPACE TEMP WARM (STAT OUTPUT LOW). AT A STAT
SWITCH
OUTPUT OF 3 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
FUSING WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
OPTIONAL DISCONNECT SWITCH ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
PANEL WIRING DIAGRAM AND OR FUSING ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
L1 L2 L3 N AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
TERMINAL 1 2 3 4
BLOCK NOTE: ON START UP, BLOWER FAN MOTOR MUST BE
BK WH
ENERGIZED BEFORE PRIMARY AIR FAN. FAN CONTROL
BK BL
REQUIRES PROPER SETTING OF PE1 SWITCH BY TEMP.
CONTROL CONTRACTOR.
BK STANDARD 1 STAGE HEAT
G ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
C1-1
BK BK JOB SPECIFICATIONS.
C1-2
C NO BK BK BK
ST.1 L1 1
BK TC BK C NO BK C1-1
PE-1 5 C1 C NO BL
NC L2 2
RD 3 L3
RD
PE-2 RD
NC PE-3
NC C1-2
BK BL/WH BK
SC FM
OPTIONAL 2 STAGE HEAT

BK BK
L1 1
P.E. SWITCH SUPPLIED BY FACTORY C1-1
PE1 RD
C NO
(SIGNAL BY OTHERS) L2 2 RD

PE-3
NC
BN C NO BN

PE-4
NC
BL BL
L3 3
PNEUMATIC DIAGRAM C1-2
N.O. OPTIONAL 3 STAGE HEAT
ACT. RECOMMENDED FIELD P.E. SWITCH SETTINGS:

VEL. CNTRLR PE-2 = 8 PSI


BAL. TAPS (RESET BAND=8-13 PSI) PE-3 = 10 PSI
B PE-4 = 12 PSI
FLOW LO Y
M 20 PSI MAIN
PROBE HI X CONSTANT
T
VOLUME
TOTAL AIR
REV. R.A.. STAT
FLOW

RELAY 1 PIPE COLD AIR HEAT


AIR

AIR
M RESTRICTOR FLOW PLENUM AIR
1
3 OR OR 20 PSI MAIN

R.A.. STAT
2 PIPE 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE4 PE3 PE2 HOT T-STAT BRANCH PRESSURE (PSIG) COLD
ROOM ROOM

HEATER COMPONENTS MAX. KW


3 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-3 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 208 V 480 V P = 208V/3PH/60HZ - 1 STAGE J = LOAD BEARING P.E. W/ 30A
1 10.7 24.9 R = 208V/3PH/60HZ - 2 STAGE MAG. CONTACTOR INTERLOCK
30 AMP CONT.
LOAD BRG. PE

2 4.4 9.1 1 = 208V/3PH/60HZ - 3 STAGE K = LOAD BEARING P.E. W/ 50A


W/ INTRLK

PER STAGE 3 2.9 6.0


U = 480V/3PH/60HZ - 1 STAGE MAG. CONTACTOR INTERLOCK
1 17.2 39.8
50 AMP CONT. W = 480V/3PH/60HZ - 2 STAGE L = LOAD BEARING P.E. W/ 30A
2 4.4 9.1 MERC. CONTACTOR INTERLOCK
PER STAGE 3 = 480V/3PH/60HZ - 3 STAGE
3 2.9 6.0
M = LOAD BEARING P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR INTERLOCK


SIZE & TYPE

DOOR INTERLOCK 14.3 33.2

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 17.2 39.8
BLOCK

30 AMP BLOCK
FUSE

8.6 19.9

60 AMP BLOCK 17.2 39.8

1. MAX. K.W. BASED ON 48A, P.E., OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.016 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5G020

REV.1 8/5/00 PNEUMATIC


PSFH095
- J95 -

104 YORK INTERNATIONAL


FORM AD1T-SECT J

SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT


PRESS. INDEPENDENT, N.C. DAMPER, P.E. FAN START, DIRECT ACTING STAT, 3 PHASE, LOAD BEARING P.E. SWITCH W/ CONT. INTRLK.

SEQUENCE OF OPERATION:
L1 L2 L3
SIGNAL TO PE1 ENERGIZES THE FAN.
DISCONNECT
SPACE TEMP WARM (STAT OUTPUT HI). AT A STAT
SWITCH
OUTPUT OF 13 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
FUSING WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
OPTIONAL DISCONNECT SWITCH ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
PANEL WIRING DIAGRAM AND OR FUSING ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
L1 L2 L3 N AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
TERMINAL 1 2 3 4
BLOCK NOTE: ON START UP, BLOWER FAN MOTOR MUST BE
BK WH
ENERGIZED BEFORE PRIMARY AIR FAN. FAN CONTROL
BK BL
REQUIRES PROPER SETTING OF PE1 SWITCH BY TEMP.
CONTROL CONTRACTOR.
BK STANDARD 1 STAGE HEAT
G ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
C1-1
BK BK JOB SPECIFICATIONS.
C1-2
C NO BK

TC ST.1 BK BK
BK BK C NO BK L1 1
PE-1 5 C1 C1-1
NC C NO BL
L2 2
RD 3 L3
PE-2
NC RD RD
PE-3
BK BL/WH BK NC C1-2
SC FM
OPTIONAL 2 STAGE HEAT

BK BK
P.E. SWITCH SUPPLIED BY FACTORY L1 1
PE1 C1-1
(SIGNAL BY OTHERS) C NO
RD
L2 2
RD
PE-3
NC
BN C NO BN

PE-4
NC
BL BL
L3 3
PNEUMATIC DIAGRAM C1-2
N.C.
OPTIONAL 3 STAGE HEAT
ACT.
RECOMMENDED FIELD P.E. SWITCH SETTINGS:
VEL. CNTRLR PE-2 = 8 PSI
BAL. TAPS (RESET BAND=3-8 PSI) PE-3 = 6 PSI
B PE-4 = 4 PSI
FLOW LO X
M 20 PSI MAIN
PROBE HI Y CONSTANT
T VOLUME
TOTAL AIR
REV. D.A.. STAT
FLOW

RELAY 1 PIPE HEAT COLD AIR


AIR

AIR
M RESTRICTOR FLOW PLENUM AIR
1
3 OR OR 20 PSI MAIN

D.A.. STAT
2 PIPE 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE4 PE3 PE2 COLD T-STAT BRANCH PRESSURE (PSIG) HOT
ROOM ROOM

HEATER COMPONENTS MAX. KW


3 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-3 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 208 V 480 V P = 208V/3PH/60HZ - 1 STAGE J = LOAD BEARING P.E. W/ 30A
1 10.7 24.9 R = 208V/3PH/60HZ - 2 STAGE MAG. CONTACTOR INTERLOCK
30 AMP CONT.
LOAD BRG. PE

2 4.4 9.1 1 = 208V/3PH/60HZ - 3 STAGE K = LOAD BEARING P.E. W/ 50A


W/ INTRLK

PER STAGE 3 2.9 6.0


U = 480V/3PH/60HZ - 1 STAGE MAG. CONTACTOR INTERLOCK
1 17.2 39.8
50 AMP CONT. W = 480V/3PH/60HZ - 2 STAGE L = LOAD BEARING P.E. W/ 30A
2 4.4 9.1 MERC. CONTACTOR INTERLOCK
PER STAGE 3 = 480V/3PH/60HZ - 3 STAGE
3 2.9 6.0
M = LOAD BEARING P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR INTERLOCK


SIZE & TYPE

DOOR INTERLOCK 14.3 33.2

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 17.2 39.8
BLOCK

30 AMP BLOCK
FUSE

8.6 19.9

60 AMP BLOCK 17.2 39.8

1. MAX. K.W. BASED ON 48A, P.E., OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.016 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5H020

REV.1 8/5/00 PNEUMATIC


PSFH096
- J96 -

YORK INTERNATIONAL 105


SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT
PRESS. INDEPENDENT, N.O. DAMPER, P.E. FAN START, DIRECT ACTING STAT, 3 PHASE, PILOT DUTY P.E. SWITCH

SEQUENCE OF OPERATION:
L1 L2 L3
SIGNAL TO PE1 ENERGIZES THE FAN.
DISCONNECT
SPACE TEMP WARM (STAT OUTPUT HI). AT A STAT
SWITCH
OUTPUT OF 13 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
FUSING WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
OPTIONAL DISCONNECT SWITCH ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
PANEL WIRING DIAGRAM AND OR FUSING ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
L1 L2 L3 N AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
TERMINAL 1 2 3 4
BLOCK NOTE: ON START UP, BLOWER FAN MOTOR MUST BE
BK WH
ENERGIZED BEFORE PRIMARY AIR FAN. FAN CONTROL
BK BL
REQUIRES PROPER SETTING OF PE1 SWITCH BY TEMP.
CONTROL CONTRACTOR.
BK STANDARD 1 STAGE HEAT
G ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
C1-1
BK BK JOB SPECIFICATIONS.
C1-2
C NO BK

TC ST.1
BK BK C NO BK
PE-1 5 C1
NC BK BK
PE-2 L1 1
NC C1-1 BL
3 L3
ST.2
RD C NO RD RD RD
C2 L2 2
C2-1
PE-3
NC OPTIONAL 2 STAGE HEAT
ST.3
BN C NO BN
C3
PE-4 BK BK
NC L1 1
BK BL/WH BK C1-1
SC FM RD RD
L2 2
C2-1
BN BN

C3-1
PE1
P.E. SWITCH SUPPLIED BY FACTORY BL BL
(SIGNAL BY OTHERS) L3 3
C1-2
PNEUMATIC DIAGRAM OPTIONAL 3 STAGE HEAT
N.O.
ACT. RECOMMENDED FIELD P.E. SWITCH SETTINGS:

VEL. CNTRLR PE-2 = 8 PSI


BAL. TAPS (RESET BAND=8-13 PSI) PE-3 = 6 PSI
B PE-4 = 4 PSI
FLOW LO Y
M 20 PSI MAIN CONSTANT
PROBE HI X
T VOLUME
TOTAL AIR
D.A.. STAT HEAT
FLOW

1 PIPE COLD AIR


AIR
AIR

FLOW PLENUM AIR


RESTRICTOR
OR OR 20 PSI MAIN

D.A.. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
2 PIPE COLD HOT
PE4 PE3 PE2 T-STAT BRANCH PRESSURE (PSIG)
ROOM ROOM

HEATER COMPONENTS MAX. KW


3 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-3 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 208 V 480 V P = 208V/3PH/60HZ - 1 STAGE 2 = PILOT DUTY P.E. W/ 30A
1 10.7 24.9 R = 208V/3PH/60HZ - 2 STAGE MAG. CONTACTOR
DE-ENERGIZING
CONTACTOR

30 AMP 2 5.3 12.4 1 = 208V/3PH/60HZ - 3 STAGE 3 = PILOT DUTY P.E. W/ 50A


PER STAGE 3 3.5 8.3
U = 480V/3PH/60HZ - 1 STAGE MAG. CONTACTOR
1 17.2 39.8
50 AMP W = 480V/3PH/60HZ - 2 STAGE 4 = PILOT DUTY P.E. W/ 30A
2 8.6 19.9 MERC. CONTACTOR
PER STAGE 3 = 480V/3PH/60HZ - 3 STAGE
3 5.7 13.2
5 = PILOT DUTY P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR


SIZE & TYPE

DOOR INTERLOCK 14.3 33.2

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 17.2 39.8
BLOCK

30 AMP BLOCK 8.6 19.9


FUSE

60 AMP BLOCK 17.2 39.8

1. MAX. K.W. BASED ON 48A, OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.008 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5E020

REV.1 8/5/00 PNEUMATIC


PSFH097
- J97 -

106 YORK INTERNATIONAL


FORM AD1T-SECT J

SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT


PRESS. INDEPENDENT, N.C. DAMPER, P.E. FAN START, REVERSE ACTING STAT, 3 PHASE, PILOT DUTY P.E. SWITCH

SEQUENCE OF OPERATION:
L1 L2 L3
SIGNAL TO PE1 ENERGIZES THE FAN.
DISCONNECT
SPACE TEMP WARM (STAT OUTPUT LOW). AT A STAT
SWITCH
OUTPUT OF 3 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
FUSING WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
OPTIONAL DISCONNECT SWITCH ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
PANEL WIRING DIAGRAM AND OR FUSING ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
L1 L2 L3 N AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
TERMINAL 1 2 3 4
BLOCK NOTE: ON START UP, BLOWER FAN MOTOR MUST BE
BK WH
ENERGIZED BEFORE PRIMARY AIR FAN. FAN CONTROL
BK BL
REQUIRES PROPER SETTING OF PE1 SWITCH BY TEMP.
CONTROL CONTRACTOR.
BK STANDARD 1 STAGE HEAT
G ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
C1-1
BK BK JOB SPECIFICATIONS.
C1-2
C NO BK

TC ST.1
BK BK C NO BK
PE-1 5 C1
NC BK BK
PE-2 L1 1
NC C1-1 BL
3 L3
ST.2
RD C NO RD RD RD
C2 L2 2
C2-1
PE-3
NC OPTIONAL 2 STAGE HEAT
ST.3
BN C NO BN
C3
PE-4 BK BK
NC L1 1
BK BL/WH BK C1-1
SC FM RD RD
L2 2
C2-1
BN BN

C3-1
PE1
P.E. SWITCH SUPPLIED BY FACTORY BL BL
(SIGNAL BY OTHERS) L3 3
C1-2
OPTIONAL 3 STAGE HEAT
PNEUMATIC DIAGRAM
N.C. RECOMMENDED FIELD P.E. SWITCH SETTINGS:
ACT.
PE-2 = 8 PSI
PE-3 = 10 PSI
VEL. CNTRLR PE-4 = 12 PSI
BAL. TAPS (RESET BAND=3-8 PSI)
B
FLOW LO X CONSTANT
M 20 PSI MAIN
PROBE HI Y VOLUME
T TOTAL AIR
R.A.. STAT COLD AIR HEAT
FLOW

AIR
1 PIPE
AIR

FLOW PLENUM AIR


RESTRICTOR
OR OR 20 PSI MAIN

R.A.. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE3 2 PIPE HOT T-STAT BRANCH PRESSURE (PSIG) COLD
PE4 PE2
ROOM ROOM

HEATER COMPONENTS MAX. KW


3 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-3 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 208 V 480 V P = 208V/3PH/60HZ - 1 STAGE 2 = PILOT DUTY P.E. W/ 30A
1 10.7 24.9 R = 208V/3PH/60HZ - 2 STAGE MAG. CONTACTOR
DE-ENERGIZING
CONTACTOR

30 AMP 2 5.3 12.4 1 = 208V/3PH/60HZ - 3 STAGE 3 = PILOT DUTY P.E. W/ 50A


PER STAGE 3 3.5 8.3
U = 480V/3PH/60HZ - 1 STAGE MAG. CONTACTOR
1 17.2 39.8
50 AMP W = 480V/3PH/60HZ - 2 STAGE 4 = PILOT DUTY P.E. W/ 30A
2 8.6 19.9 MERC. CONTACTOR
PER STAGE 3 = 480V/3PH/60HZ - 3 STAGE
3 5.7 13.2
5 = PILOT DUTY P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR


SIZE & TYPE

DOOR INTERLOCK 14.3 33.2

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 17.2 39.8
BLOCK

30 AMP BLOCK 8.6 19.9


FUSE

60 AMP BLOCK 17.2 39.8

1. MAX. K.W. BASED ON 48A, OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.008 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5F020

REV.1 8/5/00 PNEUMATIC


PSFH098
- J98 -

YORK INTERNATIONAL 107


108 YORK INTERNATIONAL
FORM AD1T-SECT J

SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT


PRESS. INDEPENDENT, N.C. DAMPER, P.E. FAN START, DIRECT ACTING STAT, 3 PHASE, PILOT DUTY P.E. SWITCH

SEQUENCE OF OPERATION:
L1 L2 L3
SIGNAL TO PE1 ENERGIZES THE FAN.
DISCONNECT
SPACE TEMP WARM (STAT OUTPUT HI). AT A STAT
SWITCH
OUTPUT OF 13 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
FUSING WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
OPTIONAL DISCONNECT SWITCH ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
PANEL WIRING DIAGRAM AND OR FUSING ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
L1 L2 L3 N AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
TERMINAL 1 2 3 4
BLOCK NOTE: ON START UP, BLOWER FAN MOTOR MUST BE
BK WH ENERGIZED BEFORE PRIMARY AIR FAN. FAN CONTROL
BK BL REQUIRES PROPER SETTING OF PE1 SWITCH BY
TEMPERATURE CONTROL CONTRACTOR.
BK STANDARD 1 STAGE HEAT
ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
C1-1 G JOB SPECIFICATIONS.
BK BK

C1-2
C NO BK

TC ST.1
BK BK C NO BK
PE-1 5 C1
NC BK BK
PE-2 L1 1
NC C1-1 BL
3 L3
ST.2
RD C NO RD RD RD
C2 L2 2
C2-1
PE-3
NC OPTIONAL 2 STAGE HEAT
ST.3
BN C NO BN
C3
PE-4 BK BK
NC L1 1
BK BL/WH BK C1-1
SC FM RD RD
L2 2
C2-1
BN BN
BK
EP C3-1
BL BL
L3 3
C1-2
P.E. SWITCH SUPPLIED BY FACTORY
PNEUMATIC DIAGRAM PE1
(SIGNAL BY OTHERS) OPTIONAL 3 STAGE HEAT
N.C.
ACT. RECOMMENDED FIELD P.E. SWITCH SETTINGS:

PE-2 = 8 PSI
PE-3 = 6 PSI
BAL. TAPS VEL. CNTRLR PE-4 = 4 PSI
B (RESET BAND=3-8 PSI)
FLOW LO X CONSTANT
M 20 PSI MAIN
PROBE HI Y VOLUME
T TOTAL AIR
REV. D.A.. STAT HEAT COLD AIR
FLOW

RELAY 1 PIPE AIR


AIR

FLOW PLENUM AIR


M RESTRICTOR
1
3 OR OR 20 PSI MAIN

D.A.. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
2 PIPE COLD T-STAT BRANCH PRESSURE (PSIG) HOT
PE4 PE3 PE2 ROOM ROOM

HEATER COMPONENTS MAX. KW


3 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-3 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 208 V 480 V P = 208V/3PH/60HZ - 1 STAGE 2 = PILOT DUTY P.E. W/ 30A
1 10.7 24.9 R = 208V/3PH/60HZ - 2 STAGE MAG. CONTACTOR
DE-ENERGIZING
CONTACTOR

30 AMP 2 5.3 12.4 1 = 208V/3PH/60HZ - 3 STAGE 3 = PILOT DUTY P.E. W/ 50A


PER STAGE 3 3.5 8.3
U = 480V/3PH/60HZ - 1 STAGE MAG. CONTACTOR
1 17.2 39.8
50 AMP W = 480V/3PH/60HZ - 2 STAGE 4 = PILOT DUTY P.E. W/ 30A
2 8.6 19.9 MERC. CONTACTOR
PER STAGE 3 = 480V/3PH/60HZ - 3 STAGE
3 5.7 13.2
5 = PILOT DUTY P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR


SIZE & TYPE

DOOR INTERLOCK 14.3 33.2

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 17.2 39.8
BLOCK

30 AMP BLOCK 8.6 19.9


FUSE

60 AMP BLOCK 17.2 39.8

1. MAX. K.W. BASED ON 48A, OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.016 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5H020

REV.1 8/5/00 PNEUMATIC


PSFH100
- J100 -
YORK INTERNATIONAL 109
SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT
PRESS. INDEPENDENT, N.O. DAMPER, P.E. FAN START, UNOCCUPIED MODE, DIRECT ACTING STAT, 1 PHASE, LOAD BEARING P.E. SWITCH

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V OCCUPIED MODE:
SIGNAL TO PE1 ENERGIZES THE FAN.
DISCONNECT
SPACE TEMP WARM (STAT OUTPUT HI). AT A STAT
SWITCH OUTPUT OF 13 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
FUSING WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
OPTIONAL DISCONNECT SWITCH ON A FURTHER DROP IN SPACE TEMP., PE3 WILL CLOSE
AND OR FUSING
PANEL WIRING DIAGRAM ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
L1 (N) = 120V & 277V UNOCCUPIED MODE:
TERMINAL WHEN THE PRESSURE APPLIED TO PE1 (SET AND CONTROLLED
1 2
BLOCK BY OTHERS) IS DROPPED BELOW ITS SETPOINT IT MAKES
BK WH TO NC CONTACT ENABLING PE2, TURNING OFF FAN.
AS TEMP DROPS, STAT OUTPUT DROPS, STARTING FAN WHEN
C NO BK
PRESSURE DROPS BELOW PE2 SETPOINT.
BK C NO BK WH G
PE-1 5 NOTE: ON START UP, BLOWER FAN MOTOR MUST BE ENERGIZED
NC
STANDARD 1 BEFORE PRIMARY AIR FAN. FAN CONTROL REQUIRES PROPER
PE-3 SETTING OF PE1 SWITCH BY TEMP CONTROL CONTRACTOR.
C NO NC STAGE HEAT
RD RD C NO RD ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
PE-2 JOB SPECIFICATIONS.
NC
PE-4 OPTIONAL 2
NC STAGE HEAT ALL P.E. SWITCHES MUST BE SET IN THE FIELD PER JOB
C NO REQUIREMENTS.
BN BN

PE-5 OPTIONAL 3
NC STAGE HEAT

BK BL/WH BK
SC FM

PE1
P.E. SWITCH SUPPLIED BY FACTORY
(SIGNAL BY OTHERS)

N.O. PNEUMATIC DIAGRAM


ACT. RECOMMENDED FIELD P.E. SWITCH SETTINGS:

PE-2 = 8 PSI
PE-3 = 8 PSI
BAL. TAPS VEL. CNTRLR PE-4 = 6 PSI
B (RESET BAND=8-13 PSI) PE-5 = 4 PSI
FLOW LO Y CONSTANT
M 20 PSI MAIN
PROBE HI X VOLUME
T TOTAL AIR
D.A.. STAT HEAT COLD AIR
FLOW

1 PIPE AIR
(UNOCCUPIED)
AIR

FLOW PLENUM AIR


FAN STARTS
RESTRICTOR
OR OR 20 PSI MAIN (FIELD CALIB.)

D.A.. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE5 PE4 PE3 PE2 2 PIPE COLD T-STAT BRANCH PRESSURE (PSIG) HOT
ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE 1 = LOAD BEARING P.E.
SWITCH

1 2.8 6.7 E = 120V/1PH/60HZ - 2 STAGE


LOAD BEARING
P.E.

PER STAGE 2 1.4 3.3 5 = 120V/1PH/60HZ - 3 STAGE


3 0.9 2.2
K = 277V/1PH/60HZ - 1 STAGE
DISCONNECT

L = 277V/1PH/60HZ - 2 STAGE
SIZE & TYPE

DNF-40 2.8 6.7 Y = 277V/1PH/60HZ - 3 STAGE


DOOR INTERLOCK
BLOCK
FUSE

30 AMP BLOCK 2.8 6.7

1. MAX. K.W. BASED ON P.E. MAX LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.008 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5E040

REV.1 8/5/00 PNEUMATIC


PSFH101
- J101 -

110 YORK INTERNATIONAL


FORM AD1T-SECT J

SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT


PRESS. INDEPENDENT, N.C. DAMPER, P.E. FAN START, UNOCCUPIED MODE, REVERSE ACTING STAT, 1 PHASE, LOAD BEARING P.E. SWITCH

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V OCCUPIED MODE:
SIGNAL TO PE1 ENERGIZES THE FAN.
DISCONNECT
SPACE TEMP WARM (STAT OUTPUT LOW). AT A STAT
SWITCH OUTPUT OF 3 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
FUSING WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
OPTIONAL DISCONNECT SWITCH ON A FURTHER DROP IN SPACE TEMP., PE3 WILL CLOSE
AND OR FUSING
PANEL WIRING DIAGRAM ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
L1 (N) = 120V & 277V UNOCCUPIED MODE:
TERMINAL WHEN THE PRESSURE APPLIED TO PE1 (SET AND CONTROLLED
1 2
BLOCK BY OTHERS) IS DROPPED BELOW ITS SETPOINT IT MAKES
BK WH TO NC CONTACT ENABLING PE2, TURNING OFF FAN.
AS TEMP DROPS, STAT OUTPUT DROPS, STARTING FAN WHEN
C NO BK
PRESSURE DROPS BELOW PE2 SETPOINT.
BK C NO BK WH G
PE-1 5 NOTE: ON START UP, BLOWER FAN MOTOR MUST BE ENERGIZED
NC
STANDARD 1 BEFORE PRIMARY AIR FAN. FAN CONTROL REQUIRES PROPER
PE-3 SETTING OF PE1 SWITCH BY TEMP CONTROL CONTRACTOR.
C NO NC STAGE HEAT
RD RD C NO RD ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
PE-2 JOB SPECIFICATIONS.
NC
PE-4 OPTIONAL 2
NC STAGE HEAT ALL P.E. SWITCHES MUST BE SET IN THE FIELD PER JOB
C NO REQUIREMENTS.
BN BN

PE-5 OPTIONAL 3
NC STAGE HEAT

BK BL/WH BK
SC FM

PE1
P.E. SWITCH SUPPLIED BY FACTORY
(SIGNAL BY OTHERS)

N.C. PNEUMATIC DIAGRAM


ACT. RECOMMENDED FIELD P.E. SWITCH SETTINGS:

PE-2 = 8 PSI
PE-3 = 8 PSI
BAL. TAPS PE-4 = 10 PSI
VEL. CNTRLR
PE-5 = 12 PSI
B (RESET BAND=3-8 PSI)
FLOW LO X
M 20 PSI MAIN CONSTANT
PROBE HI Y
T VOLUME
TOTAL AIR
R.A.. STAT HEAT
FLOW

COLD AIR
1 PIPE AIR (UNOCCUPIED)
AIR

FLOW PLENUM AIR


RESTRICTOR FAN STARTS
OR OR 20 PSI MAIN (FIELD CALIB.)

R.A.. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE5 PE4 PE3 PE2 2 PIPE HOT T-STAT BRANCH PRESSURE (PSIG) COLD
ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE 1 = LOAD BEARING P.E.
SWITCH

1 2.8 6.7 E = 120V/1PH/60HZ - 2 STAGE


LOAD BEARING
P.E.

PER STAGE 2 1.4 3.3 5 = 120V/1PH/60HZ - 3 STAGE


3 0.9 2.2
K = 277V/1PH/60HZ - 1 STAGE
DISCONNECT

L = 277V/1PH/60HZ - 2 STAGE
SIZE & TYPE

DNF-40 2.8 6.7 Y = 277V/1PH/60HZ - 3 STAGE


DOOR INTERLOCK
BLOCK
FUSE

30 AMP BLOCK 2.8 6.7

1. MAX. K.W. BASED ON P.E. MAX LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.008 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5F040

REV.1 8/5/00 PNEUMATIC


PSFH102
- J102 -

YORK INTERNATIONAL 111


SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT
PRESS. INDEPENDENT, N.O. DAMPER, P.E. FAN START, UNOCCUPIED MODE, REVERSE ACTING STAT, 1 PHASE, LOAD BEARING P.E. SWITCH

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V OCCUPIED MODE:
SIGNAL TO PE1 ENERGIZES THE FAN.
DISCONNECT
SPACE TEMP WARM (STAT OUTPUT LOW). AT A STAT
SWITCH OUTPUT OF 3 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
FUSING WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
OPTIONAL DISCONNECT SWITCH ON A FURTHER DROP IN SPACE TEMP., PE3 WILL CLOSE
AND OR FUSING
PANEL WIRING DIAGRAM ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
L1 (N) = 120V & 277V UNOCCUPIED MODE:
TERMINAL WHEN THE PRESSURE APPLIED TO PE1 (SET AND CONTROLLED
1 2
BLOCK BY OTHERS) IS DROPPED BELOW ITS SETPOINT IT MAKES
BK WH TO NC CONTACT ENABLING PE2, TURNING OFF FAN.
AS TEMP DROPS, STAT OUTPUT DROPS, STARTING FAN WHEN
C NO BK
PRESSURE DROPS BELOW PE2 SETPOINT.
BK C NO BK WH G
PE-1 5 NOTE: ON START UP, BLOWER FAN MOTOR MUST BE ENERGIZED
NC
STANDARD 1 BEFORE PRIMARY AIR FAN. FAN CONTROL REQUIRES PROPER
PE-3 SETTING OF PE1 SWITCH BY TEMP CONTROL CONTRACTOR.
C NO NC STAGE HEAT
RD
RD C NO RD ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
PE-2 JOB SPECIFICATIONS.
NC
PE-4 OPTIONAL 2
NC STAGE HEAT ALL P.E. SWITCHES MUST BE SET IN THE FIELD PER JOB
C NO REQUIREMENTS.
BN BN

PE-5 OPTIONAL 3
NC STAGE HEAT

BK BL/WH BK
SC FM

PE1
P.E. SWITCH SUPPLIED BY FACTORY
(SIGNAL BY OTHERS)

N.O. PNEUMATIC DIAGRAM


ACT. RECOMMENDED FIELD P.E. SWITCH SETTINGS:

PE-2 = 8 PSI
PE-3 = 8 PSI
BAL. TAPS VEL. CNTRLR PE-4 = 10 PSI
B (RESET BAND=8-13 PSI) PE-5 = 12 PSI
FLOW LO Y
M 20 PSI MAIN
PROBE HI X CONSTANT
T
VOLUME
TOTAL AIR
REV. R.A.. STAT
FLOW

RELAY 1 PIPE COLD AIR HEAT


AIR

AIR (UNOCCUPIED)
M RESTRICTOR FLOW PLENUM AIR
1 FAN STARTS
3 OR OR 20 PSI MAIN
(FIELD CALIB.)

R.A.. STAT
2 PIPE 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE5 PE4 PE3 PE2 HOT T-STAT BRANCH PRESSURE (PSIG) COLD
ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE 1 = LOAD BEARING P.E.
SWITCH

1 2.8 6.7 E = 120V/1PH/60HZ - 2 STAGE


LOAD BEARING
P.E.

PER STAGE 2 1.4 3.3 5 = 120V/1PH/60HZ - 3 STAGE


3 0.9 2.2
K = 277V/1PH/60HZ - 1 STAGE
DISCONNECT

L = 277V/1PH/60HZ - 2 STAGE
SIZE & TYPE

DNF-40 2.8 6.7 Y = 277V/1PH/60HZ - 3 STAGE


DOOR INTERLOCK
BLOCK
FUSE

30 AMP BLOCK 2.8 6.7

1. MAX. K.W. BASED ON P.E. MAX LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.016 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5G040

REV.1 8/5/00 PNEUMATIC


PSFH103
- J103 -

112 YORK INTERNATIONAL


FORM AD1T-SECT J

SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT


PRESS. INDEPENDENT, N.C. DAMPER, P.E. FAN START, UNOCCUPIED MODE, DIRECT ACTING STAT, 1 PHASE, LOAD BEARING P.E. SWITCH

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V OCCUPIED MODE:
SIGNAL TO PE1 ENERGIZES THE FAN.
DISCONNECT
SPACE TEMP WARM (STAT OUTPUT HI). AT A STAT
SWITCH OUTPUT OF 13 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
FUSING WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
OPTIONAL DISCONNECT SWITCH ON A FURTHER DROP IN SPACE TEMP., PE3 WILL CLOSE
AND OR FUSING
PANEL WIRING DIAGRAM ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
L1 (N) = 120V & 277V UNOCCUPIED MODE:
TERMINAL WHEN THE PRESSURE APPLIED TO PE1 (SET AND CONTROLLED
1 2
BLOCK BY OTHERS) IS DROPPED BELOW ITS SETPOINT IT MAKES
BK WH TO NC CONTACT ENABLING PE2, TURNING OFF FAN.
AS TEMP DROPS, STAT OUTPUT DROPS, STARTING FAN WHEN
C NO BK
PRESSURE DROPS BELOW PE2 SETPOINT.
BK C NO BK WH G
PE-1 5 NOTE: ON START UP, BLOWER FAN MOTOR MUST BE ENERGIZED
NC
STANDARD 1 BEFORE PRIMARY AIR FAN. FAN CONTROL REQUIRES PROPER
PE-3 SETTING OF PE1 SWITCH BY TEMP CONTROL CONTRACTOR.
C NO NC STAGE HEAT
RD RD C NO RD ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
PE-2 JOB SPECIFICATIONS.
NC
PE-4 OPTIONAL 2
NC STAGE HEAT ALL P.E. SWITCHES MUST BE SET IN THE FIELD PER JOB
C NO REQUIREMENTS.
BN BN

PE-5 OPTIONAL 3
NC STAGE HEAT

BK BL/WH BK
SC FM

PE1
P.E. SWITCH SUPPLIED BY FACTORY
(SIGNAL BY OTHERS)

PNEUMATIC
N.C. PNEUMATIC DIAGRAM
ACT.
RECOMMENDED FIELD P.E. SWITCH SETTINGS:

PE-2 = 8 PSI
PE-3 = 8 PSI
BAL. TAPS VEL. CNTRLR PE-4 = 6 PSI
B (RESET BAND=3-8 PSI)
PE-5 = 4 PSI
FLOW LO X
M 20 PSI MAIN
PROBE HI Y CONSTANT
T
VOLUME
REV. D.A.. STAT TOTAL AIR
FLOW

RELAY 1 PIPE HEAT COLD AIR


AIR

AIR
M (UNOCCUPIED)
1 RESTRICTOR FLOW PLENUM AIR
3 OR OR 20 PSI MAIN FAN STARTS
(FIELD CALIB.)

D.A.. STAT
2 PIPE 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE3 PE2 COLD T-STAT BRANCH PRESSURE (PSIG) HOT
PE5 PE4
ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE 1 = LOAD BEARING P.E.
SWITCH

1 2.8 6.7 E = 120V/1PH/60HZ - 2 STAGE


LOAD BEARING
P.E.

PER STAGE 2 1.4 3.3 5 = 120V/1PH/60HZ - 3 STAGE


3 0.9 2.2
K = 277V/1PH/60HZ - 1 STAGE
DISCONNECT

L = 277V/1PH/60HZ - 2 STAGE
SIZE & TYPE

DNF-40 2.8 6.7 Y = 277V/1PH/60HZ - 3 STAGE


DOOR INTERLOCK
BLOCK
FUSE

30 AMP BLOCK 2.8 6.7

1. MAX. K.W. BASED ON P.E. MAX LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.016 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5H040

REV.1 8/5/00 PNEUMATIC


PSFH104
- J104 -

YORK INTERNATIONAL 113


SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT
PRESS. INDEPENDENT, N.O. DAMPER, P.E. FAN START, UNOCCUPIED MODE, DIRECT ACTING STAT, 1 PHASE, LOAD BEARING P.E. SWITCH W/ CONT. INTRLK.

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V OCCUPIED MODE:
SIGNAL TO PE1 ENERGIZES THE FAN.
DISCONNECT
SPACE TEMP WARM (STAT OUTPUT HI). AT A STAT
SWITCH OUTPUT OF 13 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
FUSING WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
OPTIONAL DISCONNECT SWITCH ON A FURTHER DROP IN SPACE TEMP., PE3 WILL CLOSE
AND OR FUSING
PANEL WIRING DIAGRAM ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
L1 (N) = 120V & 277V
TERMINAL UNOCCUPIED MODE:
1 2 WHEN THE PRESSURE APPLIED TO PE1 (SET AND CONTROLLED
BLOCK
BK WH BY OTHERS) IS DROPPED BELOW ITS SETPOINT IT MAKES
TO NC CONTACT ENABLING PE2, TURNING OFF FAN.
WH
AS TEMP DROPS, STAT OUTPUT DROPS, STARTING FAN WHEN
BK BK
PRESSURE DROPS BELOW PE2 SETPOINT.
C1-1 STANDARD 1 G
STAGE HEAT NOTE: ON START UP, BLOWER FAN MOTOR MUST BE ENERGIZED
BEFORE PRIMARY AIR FAN. FAN CONTROL REQUIRES PROPER
RD C NO RD
SETTING OF PE1 SWITCH BY TEMP CONTROL CONTRACTOR.
PE-4 OPTIONAL 2 ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
NC STAGE HEAT JOB SPECIFICATIONS.
BN C NO BN
ALL P.E. SWITCHES MUST BE SET IN THE FIELD PER JOB
OPTIONAL 3 REQUIREMENTS.
PE-5
C NO BK NC STAGE HEAT
(WHEN REQ.)
BK
TC BK C NO BK
PE-1 5 C1
NC
C PE-3
NO NC
RD BK BL/WH BK
PE-2 SC FM
NC

PE1
P.E. SWITCH SUPPLIED BY FACTORY
(SIGNAL BY OTHERS)

N.O. PNEUMATIC DIAGRAM


ACT. RECOMMENDED FIELD P.E. SWITCH SETTINGS:

PE-2 = 8 PSI
PE-3 = 8 PSI
BAL. TAPS VEL. CNTRLR PE-4 = 6 PSI
B (RESET BAND=8-13 PSI) PE-5 = 4 PSI
FLOW LO Y CONSTANT
M 20 PSI MAIN
PROBE HI X VOLUME
T TOTAL AIR
D.A.. STAT HEAT COLD AIR
FLOW

1 PIPE AIR
(UNOCCUPIED)
AIR

FLOW PLENUM AIR


FAN STARTS
RESTRICTOR
OR OR 20 PSI MAIN (FIELD CALIB.)

D.A.. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE5 PE4 PE3 PE2 2 PIPE COLD T-STAT BRANCH PRESSURE (PSIG) HOT
ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE J = LOAD BEARING P.E. W/ 30A
1 3.6 8.3 E = 120V/1PH/60HZ - 2 STAGE MAG. CONTACTOR INTERLOCK
30 AMP CONT.
LOAD BRG. PE

2 1.8 4.1 5 = 120V/1PH/60HZ - 3 STAGE K = LOAD BEARING P.E. W/ 50A


W/ INTRLK

PER STAGE 3 1.2 2.7


K = 277V/1PH/60HZ - 1 STAGE MAG. CONTACTOR INTERLOCK
1 5.7 13.2
50 AMP CONT. L = 277V/1PH/60HZ - 2 STAGE L = LOAD BEARING P.E. W/ 30A
2 2.8 6.6 MERC. CONTACTOR INTERLOCK
PER STAGE Y = 277V/1PH/60HZ - 3 STAGE
3 1.9 4.4
M = LOAD BEARING P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR INTERLOCK


SIZE & TYPE

DOOR INTERLOCK 4.8 11.0

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 5.7 13.2
BLOCK

30 AMP BLOCK
FUSE

2.8 6.6

60 AMP BLOCK 5.7 13.2

1. MAX. K.W. BASED ON 48A, P.E., OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.008 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5E040

REV.1 8/5/00 PNEUMATIC


PSFH105
- J105 -

114 YORK INTERNATIONAL


FORM AD1T-SECT J

SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT


PRESS. INDEPENDENT, N.C. DAMPER, P.E. FAN START, UNOCCUPIED MODE, REVERSE ACTING STAT, 1 PHASE, LOAD BEARING P.E. SWITCH W/ CONT. INTRLK.

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V OCCUPIED MODE:
SIGNAL TO PE1 ENERGIZES THE FAN.
DISCONNECT
SPACE TEMP WARM (STAT OUTPUT LOW). AT A STAT
SWITCH OUTPUT OF 3 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
FUSING WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
OPTIONAL DISCONNECT SWITCH ON A FURTHER DROP IN SPACE TEMP., PE3 WILL CLOSE
AND OR FUSING
PANEL WIRING DIAGRAM ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
L1 (N) = 120V & 277V
TERMINAL UNOCCUPIED MODE:
1 2 WHEN THE PRESSURE APPLIED TO PE1 (SET AND CONTROLLED
BLOCK
BK WH BY OTHERS) IS DROPPED BELOW ITS SETPOINT IT MAKES
TO NC CONTACT ENABLING PE2, TURNING OFF FAN.
WH
AS TEMP DROPS, STAT OUTPUT DROPS, STARTING FAN WHEN
BK BK
PRESSURE DROPS BELOW PE2 SETPOINT.
C1-1 STANDARD 1 G
STAGE HEAT NOTE: ON START UP, BLOWER FAN MOTOR MUST BE ENERGIZED
BEFORE PRIMARY AIR FAN. FAN CONTROL REQUIRES PROPER
RD C NO RD
SETTING OF PE1 SWITCH BY TEMP CONTROL CONTRACTOR.
PE-4 OPTIONAL 2 ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
NC STAGE HEAT JOB SPECIFICATIONS.
BN C NO BN
ALL P.E. SWITCHES MUST BE SET IN THE FIELD PER JOB
OPTIONAL 3 REQUIREMENTS.
PE-5
C NO BK NC STAGE HEAT
(WHEN REQ.)
BK
TC BK C NO BK
PE-1 5 C1
NC
C PE-3
NO NC
RD BK BL/WH BK
PE-2 SC FM
NC

PE1
P.E. SWITCH SUPPLIED BY FACTORY
(SIGNAL BY OTHERS)

N.C. PNEUMATIC DIAGRAM


ACT. RECOMMENDED FIELD P.E. SWITCH SETTINGS:

PE-2 = 8 PSI
PE-3 = 8 PSI
BAL. TAPS PE-4 = 10 PSI
VEL. CNTRLR
PE-5 = 12 PSI
B (RESET BAND=3-8 PSI)
FLOW LO X
M 20 PSI MAIN CONSTANT
PROBE HI Y
T VOLUME
TOTAL AIR
R.A.. STAT HEAT
FLOW

COLD AIR
1 PIPE AIR (UNOCCUPIED)
AIR

FLOW PLENUM AIR


RESTRICTOR FAN STARTS
OR OR 20 PSI MAIN (FIELD CALIB.)

R.A.. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE5 PE4 PE3 PE2 2 PIPE HOT T-STAT BRANCH PRESSURE (PSIG) COLD
ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE J = LOAD BEARING P.E. W/ 30A
1 3.6 8.3 E = 120V/1PH/60HZ - 2 STAGE MAG. CONTACTOR INTERLOCK
30 AMP CONT.
LOAD BRG. PE

2 1.8 4.1 5 = 120V/1PH/60HZ - 3 STAGE K = LOAD BEARING P.E. W/ 50A


W/ INTRLK

PER STAGE 3 1.2 2.7


K = 277V/1PH/60HZ - 1 STAGE MAG. CONTACTOR INTERLOCK
1 5.7 13.2
50 AMP CONT. L = 277V/1PH/60HZ - 2 STAGE L = LOAD BEARING P.E. W/ 30A
2 2.8 6.6 MERC. CONTACTOR INTERLOCK
PER STAGE Y = 277V/1PH/60HZ - 3 STAGE
3 1.9 4.4
M = LOAD BEARING P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR INTERLOCK


SIZE & TYPE

DOOR INTERLOCK 4.8 11.0

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 5.7 13.2
BLOCK

30 AMP BLOCK
FUSE

2.8 6.6

60 AMP BLOCK 5.7 13.2

1. MAX. K.W. BASED ON 48A, P.E., OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.008 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5F040

REV.1 8/5/00 PNEUMATIC


PSFH106
- J106 -

YORK INTERNATIONAL 115


SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT
PRESS. INDEPENDENT, N.O. DAMPER, P.E. FAN START, UNOCCUPIED MODE, REVERSE ACTING STAT, 1 PHASE, LOAD BEARING P.E. SWITCH W/ CONT. INTRLK.

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V OCCUPIED MODE:
SIGNAL TO PE1 ENERGIZES THE FAN.
DISCONNECT
SPACE TEMP WARM (STAT OUTPUT LOW). AT A STAT
SWITCH OUTPUT OF 3 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
FUSING WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
OPTIONAL DISCONNECT SWITCH ON A FURTHER DROP IN SPACE TEMP., PE3 WILL CLOSE
AND OR FUSING
PANEL WIRING DIAGRAM ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
L1 (N) = 120V & 277V
TERMINAL UNOCCUPIED MODE:
1 2 WHEN THE PRESSURE APPLIED TO PE1 (SET AND CONTROLLED
BLOCK
BK WH BY OTHERS) IS DROPPED BELOW ITS SETPOINT IT MAKES
TO NC CONTACT ENABLING PE2, TURNING OFF FAN.
WH
AS TEMP DROPS, STAT OUTPUT DROPS, STARTING FAN WHEN
BK BK
PRESSURE DROPS BELOW PE2 SETPOINT.
C1-1 STANDARD 1 G
STAGE HEAT NOTE: ON START UP, BLOWER FAN MOTOR MUST BE ENERGIZED
BEFORE PRIMARY AIR FAN. FAN CONTROL REQUIRES PROPER
RD C NO RD
SETTING OF PE1 SWITCH BY TEMP CONTROL CONTRACTOR.
PE-4 OPTIONAL 2 ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
NC STAGE HEAT JOB SPECIFICATIONS.
BN C NO BN
ALL P.E. SWITCHES MUST BE SET IN THE FIELD PER JOB
OPTIONAL 3 REQUIREMENTS.
PE-5
C NO BK NC STAGE HEAT
(WHEN REQ.)
BK
TC BK C NO BK
PE-1 5 C1
NC
C PE-3
NO NC
RD BK BL/WH BK
PE-2 SC FM
NC

PE1
P.E. SWITCH SUPPLIED BY FACTORY
(SIGNAL BY OTHERS)

N.O. PNEUMATIC DIAGRAM


ACT. RECOMMENDED FIELD P.E. SWITCH SETTINGS:

PE-2 = 8 PSI
PE-3 = 8 PSI
BAL. TAPS VEL. CNTRLR PE-4 = 10 PSI
B (RESET BAND=8-13 PSI) PE-5 = 12 PSI
FLOW LO Y
M 20 PSI MAIN
PROBE HI X CONSTANT
T
VOLUME
TOTAL AIR
REV. R.A.. STAT
FLOW

RELAY 1 PIPE COLD AIR HEAT


AIR

AIR (UNOCCUPIED)
M RESTRICTOR FLOW PLENUM AIR
1 FAN STARTS
3 OR OR 20 PSI MAIN
(FIELD CALIB.)

R.A.. STAT
2 PIPE 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE5 PE4 PE3 PE2 HOT T-STAT BRANCH PRESSURE (PSIG) COLD
ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE J = LOAD BEARING P.E. W/ 30A
1 3.6 8.3 E = 120V/1PH/60HZ - 2 STAGE MAG. CONTACTOR INTERLOCK
30 AMP CONT.
LOAD BRG. PE

2 1.8 4.1 5 = 120V/1PH/60HZ - 3 STAGE K = LOAD BEARING P.E. W/ 50A


W/ INTRLK

PER STAGE 3 1.2 2.7


K = 277V/1PH/60HZ - 1 STAGE MAG. CONTACTOR INTERLOCK
1 5.7 13.2
50 AMP CONT. L = 277V/1PH/60HZ - 2 STAGE L = LOAD BEARING P.E. W/ 30A
2 2.8 6.6 MERC. CONTACTOR INTERLOCK
PER STAGE Y = 277V/1PH/60HZ - 3 STAGE
3 1.9 4.4
M = LOAD BEARING P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR INTERLOCK


SIZE & TYPE

DOOR INTERLOCK 4.8 11.0

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 5.7 13.2
BLOCK

30 AMP BLOCK
FUSE

2.8 6.6

60 AMP BLOCK 5.7 13.2

1. MAX. K.W. BASED ON 48A, P.E., OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.016 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5G040

REV.1 8/5/00 PNEUMATIC


PSFH107
- J107 -

116 YORK INTERNATIONAL


FORM AD1T-SECT J

SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT


PRESS. INDEPENDENT, N.C. DAMPER, P.E. FAN START, UNOCCUPIED MODE, DIRECT ACTING STAT, 1 PHASE, LOAD BEARING P.E. SWITCH W/ CONT. INTRLK.

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V OCCUPIED MODE:
SIGNAL TO PE1 ENERGIZES THE FAN.
DISCONNECT
SPACE TEMP WARM (STAT OUTPUT HI). AT A STAT
SWITCH OUTPUT OF 13 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
FUSING WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
OPTIONAL DISCONNECT SWITCH ON A FURTHER DROP IN SPACE TEMP., PE3 WILL CLOSE
AND OR FUSING
PANEL WIRING DIAGRAM ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
L1 (N) = 120V & 277V
TERMINAL UNOCCUPIED MODE:
1 2 WHEN THE PRESSURE APPLIED TO PE1 (SET AND CONTROLLED
BLOCK
BK WH BY OTHERS) IS DROPPED BELOW ITS SETPOINT IT MAKES
TO NC CONTACT ENABLING PE2, TURNING OFF FAN.
WH
AS TEMP DROPS, STAT OUTPUT DROPS, STARTING FAN WHEN
BK BK
PRESSURE DROPS BELOW PE2 SETPOINT.
C1-1 STANDARD 1 G
STAGE HEAT NOTE: ON START UP, BLOWER FAN MOTOR MUST BE ENERGIZED
BEFORE PRIMARY AIR FAN. FAN CONTROL REQUIRES PROPER
RD C NO RD
SETTING OF PE1 SWITCH BY TEMP CONTROL CONTRACTOR.
PE-4 OPTIONAL 2 ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
NC STAGE HEAT JOB SPECIFICATIONS.
BN C NO BN
ALL P.E. SWITCHES MUST BE SET IN THE FIELD PER JOB
OPTIONAL 3 REQUIREMENTS.
PE-5
C NO BK NC STAGE HEAT
(WHEN REQ.)
BK
TC BK C NO BK
PE-1 5 C1
NC
C PE-3
NO NC
RD BK BL/WH BK
PE-2 SC FM
NC

PE1
P.E. SWITCH SUPPLIED BY FACTORY
(SIGNAL BY OTHERS)

N.C. PNEUMATIC DIAGRAM


ACT.
RECOMMENDED FIELD P.E. SWITCH SETTINGS:

PE-2 = 8 PSI
PE-3 = 8 PSI
BAL. TAPS VEL. CNTRLR PE-4 = 6 PSI
B (RESET BAND=3-8 PSI)
PE-5 = 4 PSI
FLOW LO X
M 20 PSI MAIN
PROBE HI Y CONSTANT
T
VOLUME
REV. D.A.. STAT TOTAL AIR
FLOW

RELAY 1 PIPE HEAT COLD AIR


AIR

AIR
M (UNOCCUPIED)
1 RESTRICTOR FLOW PLENUM AIR
3 OR OR 20 PSI MAIN FAN STARTS
(FIELD CALIB.)

D.A.. STAT
2 PIPE 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE3 PE2 COLD T-STAT BRANCH PRESSURE (PSIG) HOT
PE5 PE4
ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE J = LOAD BEARING P.E. W/ 30A
1 3.6 8.3 E = 120V/1PH/60HZ - 2 STAGE MAG. CONTACTOR INTERLOCK
30 AMP CONT.
LOAD BRG. PE

2 1.8 4.1 5 = 120V/1PH/60HZ - 3 STAGE K = LOAD BEARING P.E. W/ 50A


W/ INTRLK

PER STAGE 3 1.2 2.7


K = 277V/1PH/60HZ - 1 STAGE MAG. CONTACTOR INTERLOCK
1 5.7 13.2
50 AMP CONT. L = 277V/1PH/60HZ - 2 STAGE L = LOAD BEARING P.E. W/ 30A
2 2.8 6.6 MERC. CONTACTOR INTERLOCK
PER STAGE Y = 277V/1PH/60HZ - 3 STAGE
3 1.9 4.4
M = LOAD BEARING P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR INTERLOCK


SIZE & TYPE

DOOR INTERLOCK 4.8 11.0

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 5.7 13.2
BLOCK

30 AMP BLOCK
FUSE

2.8 6.6

60 AMP BLOCK 5.7 13.2

1. MAX. K.W. BASED ON 48A, P.E., OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.016 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5H040

REV.1 8/5/00 PNEUMATIC


PSFH108
- J108 -

YORK INTERNATIONAL 117


SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT
PRESS. INDEPENDENT, N.O. DAMPER, P.E. FAN START, UNOCCUPIED MODE, DIRECT ACTING STAT, 1 PHASE, PILOT DUTY P.E. SWITCH

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V OCCUPIED MODE:
SIGNAL TO PE1 ENERGIZES THE FAN.
DISCONNECT
SPACE TEMP WARM (STAT OUTPUT HI). AT A STAT
SWITCH OUTPUT OF 13 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
FUSING WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
OPTIONAL DISCONNECT SWITCH ON A FURTHER DROP IN SPACE TEMP., PE3 WILL CLOSE
AND OR FUSING
PANEL WIRING DIAGRAM ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
L1 (N) = 120V & 277V
TERMINAL UNOCCUPIED MODE:
1 2 WHEN THE PRESSURE APPLIED TO PE1 (SET AND CONTROLLED
BLOCK
BK WH BY OTHERS) IS DROPPED BELOW ITS SETPOINT IT MAKES
TO NC CONTACT ENABLING PE2, TURNING OFF FAN.
WH
AS TEMP DROPS, STAT OUTPUT DROPS, STARTING FAN WHEN
BK BK
PRESSURE DROPS BELOW PE2 SETPOINT.
C1-1 STANDARD 1 ST. HEAT
G
RD RD NOTE: ON START UP, BLOWER FAN MOTOR MUST BE ENERGIZED
OPTIONAL 2 ST. HEAT BEFORE PRIMARY AIR FAN. FAN CONTROL REQUIRES PROPER
C2-1 SETTING OF PE1 SWITCH BY TEMP CONTROL CONTRACTOR.
BN BN

C NO BK OPTIONAL 3 ST. HEAT ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY


C3-1 JOB SPECIFICATIONS.
TC C NO ST.1
BK BK BK
PE-1 5 C1 ALL P.E. SWITCHES MUST BE SET IN THE FIELD PER JOB
NC
REQUIREMENTS.
C PE-3
NO NC
(WHEN REQ.) ST.2
RD
RD C NO RD
PE-2 C2
NC
PE-4
NC
ST.3
BN C NO BN
C3
PE-5
NC
BK BL/WH BK
SC FM

PE1
P.E. SWITCH SUPPLIED BY FACTORY
(SIGNAL BY OTHERS)

N.O. PNEUMATIC DIAGRAM


ACT. RECOMMENDED FIELD P.E. SWITCH SETTINGS:

PE-2 = 8 PSI
PE-3 = 8 PSI
BAL. TAPS VEL. CNTRLR PE-4 = 6 PSI
B (RESET BAND=8-13 PSI) PE-5 = 4 PSI
FLOW LO Y CONSTANT
M 20 PSI MAIN
PROBE HI X VOLUME
T TOTAL AIR
D.A.. STAT HEAT COLD AIR
FLOW

1 PIPE AIR
(UNOCCUPIED)
AIR

FLOW PLENUM AIR


FAN STARTS
RESTRICTOR
OR OR 20 PSI MAIN (FIELD CALIB.)

D.A.. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE5 PE4 PE3 PE2 2 PIPE COLD T-STAT BRANCH PRESSURE (PSIG) HOT
ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE 2 = PILOT DUTY P.E. W/ 30A
1 3.6 8.3 E = 120V/1PH/60HZ - 2 STAGE MAG. CONTACTOR
DE-ENERGIZING
CONTACTOR

30 AMP 2 2.8 6.6 5 = 120V/1PH/60HZ - 3 STAGE 3 = PILOT DUTY P.E. W/ 50A


CONTACTOR 3 1.9 4.4
K = 277V/1PH/60HZ - 1 STAGE MAG. CONTACTOR
1 5.7 13.2
50 AMP L = 277V/1PH/60HZ - 2 STAGE 4 = PILOT DUTY P.E. W/ 30A
2 2.8 6.6 MERC. CONTACTOR
CONTACTOR Y = 277V/1PH/60HZ - 3 STAGE
3 1.9 4.4
5 = PILOT DUTY P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR


SIZE & TYPE

DOOR INTERLOCK 4.8 11.0

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 5.7 13.2
BLOCK

30 AMP BLOCK
FUSE

2.8 6.6

60 AMP BLOCK 5.7 13.2

1. MAX. K.W. BASED ON 48A, OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.008 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5E040

REV.1 8/5/00 PNEUMATIC


PSFH109
- J109 -

118 YORK INTERNATIONAL


FORM AD1T-SECT J

SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT


PRESS. INDEPENDENT, N.C. DAMPER, P.E. FAN START, UNOCCUPIED MODE, REVERSE ACTING STAT, 1 PHASE, PILOT DUTY P.E. SWITCH

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V OCCUPIED MODE:
SIGNAL TO PE1 ENERGIZES THE FAN.
DISCONNECT
SPACE TEMP WARM (STAT OUTPUT LOW). AT A STAT
SWITCH OUTPUT OF 3 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
FUSING WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
OPTIONAL DISCONNECT SWITCH ON A FURTHER DROP IN SPACE TEMP., PE3 WILL CLOSE
AND OR FUSING
PANEL WIRING DIAGRAM ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
L1 (N) = 120V & 277V
TERMINAL UNOCCUPIED MODE:
1 2 WHEN THE PRESSURE APPLIED TO PE1 (SET AND CONTROLLED
BLOCK
BK WH BY OTHERS) IS DROPPED BELOW ITS SETPOINT IT MAKES
TO NC CONTACT ENABLING PE2, TURNING OFF FAN.
WH
AS TEMP DROPS, STAT OUTPUT DROPS, STARTING FAN WHEN
BK BK
PRESSURE DROPS BELOW PE2 SETPOINT.
C1-1 STANDARD 1 ST. HEAT
G
RD RD NOTE: ON START UP, BLOWER FAN MOTOR MUST BE ENERGIZED
OPTIONAL 2 ST. HEAT BEFORE PRIMARY AIR FAN. FAN CONTROL REQUIRES PROPER
C2-1 SETTING OF PE1 SWITCH BY TEMP CONTROL CONTRACTOR.
BN BN

C NO BK OPTIONAL 3 ST. HEAT ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY


C3-1 JOB SPECIFICATIONS.
TC C NO ST.1
BK BK BK
PE-1 5 C1 ALL P.E. SWITCHES MUST BE SET IN THE FIELD PER JOB
NC
REQUIREMENTS.
C PE-3
NO NC
(WHEN REQ.) ST.2
RD
RD C NO RD
PE-2 C2
NC
PE-4
NC
ST.3
BN C NO BN
C3
PE-5
NC
BK BL/WH BK
SC FM

PE1
P.E. SWITCH SUPPLIED BY FACTORY
(SIGNAL BY OTHERS)

N.C. PNEUMATIC DIAGRAM


ACT. RECOMMENDED FIELD P.E. SWITCH SETTINGS:

PE-2 = 8 PSI
PE-3 = 8 PSI
BAL. TAPS PE-4 = 10 PSI
VEL. CNTRLR
PE-5 = 12 PSI
B (RESET BAND=3-8 PSI)
FLOW LO X
M 20 PSI MAIN CONSTANT
PROBE HI Y
T VOLUME
TOTAL AIR
R.A.. STAT HEAT
FLOW

COLD AIR
1 PIPE AIR (UNOCCUPIED)
AIR

FLOW PLENUM AIR


RESTRICTOR FAN STARTS
OR OR 20 PSI MAIN (FIELD CALIB.)

R.A.. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE5 PE4 PE3 PE2 2 PIPE HOT T-STAT BRANCH PRESSURE (PSIG) COLD
ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE 2 = PILOT DUTY P.E. W/ 30A
1 3.6 8.3 E = 120V/1PH/60HZ - 2 STAGE MAG. CONTACTOR
DE-ENERGIZING
CONTACTOR

30 AMP 2 2.8 6.6 5 = 120V/1PH/60HZ - 3 STAGE 3 = PILOT DUTY P.E. W/ 50A


CONTACTOR 3 1.9 4.4
K = 277V/1PH/60HZ - 1 STAGE MAG. CONTACTOR
1 5.7 13.2
50 AMP L = 277V/1PH/60HZ - 2 STAGE 4 = PILOT DUTY P.E. W/ 30A
2 2.8 6.6 MERC. CONTACTOR
CONTACTOR Y = 277V/1PH/60HZ - 3 STAGE
3 1.9 4.4
5 = PILOT DUTY P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR


SIZE & TYPE

DOOR INTERLOCK 4.8 11.0

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 5.7 13.2
BLOCK

30 AMP BLOCK
FUSE

2.8 6.6

60 AMP BLOCK 5.7 13.2

1. MAX. K.W. BASED ON 48A, OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.008 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5F040

REV.1 8/5/00 PNEUMATIC


PSFH110
- J110 -

YORK INTERNATIONAL 119


SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT
PRESS. INDEPENDENT, N.O. DAMPER, P.E. FAN START, UNOCCUPIED MODE, REVERSE ACTING STAT, 1 PHASE, PILOT DUTY P.E. SWITCH

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V OCCUPIED MODE:
SIGNAL TO PE1 ENERGIZES THE FAN.
DISCONNECT
SPACE TEMP WARM (STAT OUTPUT LOW). AT A STAT
SWITCH OUTPUT OF 3 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
FUSING WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
OPTIONAL DISCONNECT SWITCH ON A FURTHER DROP IN SPACE TEMP., PE3 WILL CLOSE
AND OR FUSING
PANEL WIRING DIAGRAM ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
L1 (N) = 120V & 277V
TERMINAL UNOCCUPIED MODE:
1 2 WHEN THE PRESSURE APPLIED TO PE1 (SET AND CONTROLLED
BLOCK
BK WH BY OTHERS) IS DROPPED BELOW ITS SETPOINT IT MAKES
TO NC CONTACT ENABLING PE2, TURNING OFF FAN.
WH
AS TEMP DROPS, STAT OUTPUT DROPS, STARTING FAN WHEN
BK BK
PRESSURE DROPS BELOW PE2 SETPOINT.
C1-1 STANDARD 1 ST. HEAT
G
RD RD NOTE: ON START UP, BLOWER FAN MOTOR MUST BE ENERGIZED
OPTIONAL 2 ST. HEAT BEFORE PRIMARY AIR FAN. FAN CONTROL REQUIRES PROPER
C2-1 SETTING OF PE1 SWITCH BY TEMP CONTROL CONTRACTOR.
BN BN

C NO BK OPTIONAL 3 ST. HEAT ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY


C3-1 JOB SPECIFICATIONS.
TC C NO ST.1
BK BK BK
PE-1 5 C1 ALL P.E. SWITCHES MUST BE SET IN THE FIELD PER JOB
NC
REQUIREMENTS.
C PE-3
NO NC
(WHEN REQ.) ST.2
RD
RD C NO RD
PE-2 C2
NC
PE-4
NC
ST.3
BN C NO BN
C3
PE-5
NC
BK BL/WH BK
SC FM

PE1
P.E. SWITCH SUPPLIED BY FACTORY
(SIGNAL BY OTHERS)

N.O. PNEUMATIC DIAGRAM


ACT. RECOMMENDED FIELD P.E. SWITCH SETTINGS:

PE-2 = 8 PSI
PE-3 = 8 PSI
BAL. TAPS VEL. CNTRLR PE-4 = 10 PSI
B (RESET BAND=8-13 PSI) PE-5 = 12 PSI
FLOW LO Y
M 20 PSI MAIN
PROBE HI X CONSTANT
T
VOLUME
TOTAL AIR
REV. R.A.. STAT
FLOW

RELAY 1 PIPE COLD AIR HEAT


AIR

AIR (UNOCCUPIED)
M RESTRICTOR FLOW PLENUM AIR
1 FAN STARTS
3 OR OR 20 PSI MAIN
(FIELD CALIB.)

R.A.. STAT
2 PIPE 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE5 PE4 PE3 PE2 HOT T-STAT BRANCH PRESSURE (PSIG) COLD
ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE 2 = PILOT DUTY P.E. W/ 30A
1 3.6 8.3 E = 120V/1PH/60HZ - 2 STAGE MAG. CONTACTOR
DE-ENERGIZING
CONTACTOR

30 AMP 2 2.8 6.6 5 = 120V/1PH/60HZ - 3 STAGE 3 = PILOT DUTY P.E. W/ 50A


CONTACTOR 3 1.9 4.4
K = 277V/1PH/60HZ - 1 STAGE MAG. CONTACTOR
1 5.7 13.2
50 AMP L = 277V/1PH/60HZ - 2 STAGE 4 = PILOT DUTY P.E. W/ 30A
2 2.8 6.6 MERC. CONTACTOR
CONTACTOR Y = 277V/1PH/60HZ - 3 STAGE
3 1.9 4.4
5 = PILOT DUTY P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR


SIZE & TYPE

DOOR INTERLOCK 4.8 11.0

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 5.7 13.2
BLOCK

30 AMP BLOCK
FUSE

2.8 6.6

60 AMP BLOCK 5.7 13.2

1. MAX. K.W. BASED ON 48A, OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.016 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5G040

REV.1 8/5/00 PNEUMATIC


PSFH111
- J111 -

120 YORK INTERNATIONAL


FORM AD1T-SECT J

SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT


PRESS. INDEPENDENT, N.C. DAMPER, P.E. FAN START, UNOCCUPIED MODE, DIRECT ACTING STAT, 1 PHASE, PILOT DUTY P.E. SWITCH

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V OCCUPIED MODE:
SIGNAL TO PE1 ENERGIZES THE FAN.
DISCONNECT
SPACE TEMP WARM (STAT OUTPUT HI). AT A STAT
SWITCH OUTPUT OF 13 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
FUSING WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
OPTIONAL DISCONNECT SWITCH ON A FURTHER DROP IN SPACE TEMP., PE3 WILL CLOSE
AND OR FUSING
PANEL WIRING DIAGRAM ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
L1 (N) = 120V & 277V
TERMINAL UNOCCUPIED MODE:
1 2 WHEN THE PRESSURE APPLIED TO PE1 (SET AND CONTROLLED
BLOCK
BK WH BY OTHERS) IS DROPPED BELOW ITS SETPOINT IT MAKES
TO NC CONTACT ENABLING PE2, TURNING OFF FAN.
WH
AS TEMP DROPS, STAT OUTPUT DROPS, STARTING FAN WHEN
BK BK
PRESSURE DROPS BELOW PE2 SETPOINT.
C1-1 STANDARD 1 ST. HEAT
G
RD RD NOTE: ON START UP, BLOWER FAN MOTOR MUST BE ENERGIZED
OPTIONAL 2 ST. HEAT BEFORE PRIMARY AIR FAN. FAN CONTROL REQUIRES PROPER
C2-1 SETTING OF PE1 SWITCH BY TEMP CONTROL CONTRACTOR.
BN BN

C NO BK OPTIONAL 3 ST. HEAT ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY


C3-1 JOB SPECIFICATIONS.
TC C NO ST.1
BK BK BK
PE-1 5 C1 ALL P.E. SWITCHES MUST BE SET IN THE FIELD PER JOB
NC
REQUIREMENTS.
C PE-3
NO NC
(WHEN REQ.) ST.2
RD
RD C NO RD
PE-2 C2
NC
PE-4
NC
ST.3
BN C NO BN
C3
PE-5
NC
BK BL/WH BK
SC FM

PE1
P.E. SWITCH SUPPLIED BY FACTORY
(SIGNAL BY OTHERS)

N.C. PNEUMATIC DIAGRAM


ACT. RECOMMENDED FIELD P.E. SWITCH SETTINGS:

PE-2 = 8 PSI
PE-3 = 8 PSI
BAL. TAPS VEL. CNTRLR PE-4 = 6 PSI
B (RESET BAND=3-8 PSI) PE-5 = 4 PSI
FLOW LO X
M 20 PSI MAIN CONSTANT
PROBE HI Y
T VOLUME
TOTAL AIR
REV. D.A.. STAT
FLOW

HEAT COLD AIR


RELAY 1 PIPE AIR
AIR

(UNOCCUPIED)
M FLOW PLENUM AIR
1 RESTRICTOR FAN STARTS
3 OR OR 20 PSI MAIN (FIELD CALIB.)

D.A.. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
2 PIPE
COLD T-STAT BRANCH PRESSURE (PSIG) HOT
PE5 PE4 PE3 PE2 ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE 2 = PILOT DUTY P.E. W/ 30A
1 3.6 8.3 E = 120V/1PH/60HZ - 2 STAGE MAG. CONTACTOR
DE-ENERGIZING
CONTACTOR

30 AMP 2 2.8 6.6 5 = 120V/1PH/60HZ - 3 STAGE 3 = PILOT DUTY P.E. W/ 50A


CONTACTOR 3 1.9 4.4
K = 277V/1PH/60HZ - 1 STAGE MAG. CONTACTOR
1 5.7 13.2
50 AMP L = 277V/1PH/60HZ - 2 STAGE 4 = PILOT DUTY P.E. W/ 30A
2 2.8 6.6 MERC. CONTACTOR
CONTACTOR Y = 277V/1PH/60HZ - 3 STAGE
3 1.9 4.4
5 = PILOT DUTY P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR


SIZE & TYPE

DOOR INTERLOCK 4.8 11.0

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 5.7 13.2
BLOCK

30 AMP BLOCK
FUSE

2.8 6.6

60 AMP BLOCK 5.7 13.2

1. MAX. K.W. BASED ON 48A, OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.016 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5H040

REV.1 8/5/00 PNEUMATIC


PSFH112
- J112 -

YORK INTERNATIONAL 121


SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT
PRESS. INDEPENDENT, N.O. DAMPER, P.E. FAN START, UNOCCUPIED MODE, DIRECT ACTING STAT, 3 PHASE, LOAD BEARING P.E. SWITCH W/ CONT. INTRLK.

SEQUENCE OF OPERATION:
OCCUPIED MODE:
L1 L2 L3
SIGNAL TO PE1 ENERGIZES THE FAN.
DISCONNECT SPACE TEMP WARM (STAT OUTPUT HI). AT A STAT
SWITCH OUTPUT OF 13 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
FUSING
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
OPTIONAL DISCONNECT SWITCH ON A FURTHER DROP IN SPACE TEMP., PE3 WILL CLOSE
PANEL WIRING DIAGRAM AND OR FUSING ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.

L1 L2 L3 N AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.


TERMINAL UNOCCUPIED MODE:
1 2 3 4
BLOCK WHEN THE PRESSURE APPLIED TO PE1 (SET AND CONTROLLED
BK WH
BY OTHERS) IS DROPPED BELOW ITS SETPOINT IT MAKES
BK BL TO NC CONTACT ENABLING PE2, TURNING OFF FAN.
AS TEMP DROPS, STAT OUTPUT DROPS, STARTING FAN WHEN
BK STANDARD 1 STAGE HEAT PRESSURE DROPS BELOW PE2 SETPOINT.
C1-1 G
NOTE: ON START UP, BLOWER FAN MOTOR MUST BE ENERGIZED
BK BK
BEFORE PRIMARY AIR FAN. FAN CONTROL REQUIRES PROPER
C1-2 SETTING OF PE1 SWITCH BY TEMP CONTROL CONTRACTOR.
C NO BK ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
TC C NO JOB SPECIFICATIONS.
PE-1 BK BK BK
NC 5 C1
ALL P.E. SWITCHES MUST BE SET IN THE FIELD PER JOB
C PE-3 REQUIREMENTS.
NO NC
RD BK BL/WH BK
PE-2 SC FM
NC

BK BK
L1 1
C1-1
P.E. SWITCH SUPPLIED BY FACTORY RD
C NO
PE1 L2 2
(SIGNAL BY OTHERS)
RD
PE-4
NC
L1 1
BK BK
BN C NO BN

C NO C1-1 BL
L2 2
RD 3 L3 PE-5
RD RD
NC
PE-4 BL BL
NC L3 3
C1-2 C1-2

N.O. PNEUMATIC DIAGRAM OPTIONAL 2 STAGE HEAT OPTIONAL 3 STAGE HEAT

ACT. RECOMMENDED FIELD P.E. SWITCH SETTINGS:

PE-2 = 8 PSI
PE-3 = 8 PSI
BAL. TAPS VEL. CNTRLR PE-4 = 6 PSI
B (RESET BAND=8-13 PSI) PE-5 = 4 PSI
FLOW LO Y CONSTANT
M 20 PSI MAIN
PROBE HI X VOLUME
T TOTAL AIR
D.A.. STAT HEAT COLD AIR
FLOW

1 PIPE AIR
(UNOCCUPIED)
AIR

FLOW PLENUM AIR


FAN STARTS
RESTRICTOR
OR OR 20 PSI MAIN (FIELD CALIB.)

D.A.. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE5 PE4 PE3 PE2 2 PIPE COLD T-STAT BRANCH PRESSURE (PSIG) HOT
ROOM ROOM

HEATER COMPONENTS MAX. KW


3 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-3 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 208 V 480 V P = 208V/3PH/60HZ - 1 STAGE J = LOAD BEARING P.E. W/ 30A
1 10.7 24.9 R = 208V/3PH/60HZ - 2 STAGE MAG. CONTACTOR INTERLOCK
30 AMP CONT.
LOAD BRG. PE

2 4.4 9.1 1 = 208V/3PH/60HZ - 3 STAGE K = LOAD BEARING P.E. W/ 50A


W/ INTRLK

PER STAGE 3 2.9 6.0


U = 480V/3PH/60HZ - 1 STAGE MAG. CONTACTOR INTERLOCK
1 17.2 39.8
50 AMP CONT. W = 480V/3PH/60HZ - 2 STAGE L = LOAD BEARING P.E. W/ 30A
2 4.4 9.1 MERC. CONTACTOR INTERLOCK
PER STAGE 3 = 480V/3PH/60HZ - 3 STAGE
3 2.9 6.0
M = LOAD BEARING P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR INTERLOCK


SIZE & TYPE

DOOR INTERLOCK 14.3 33.2

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 17.2 39.8
BLOCK

30 AMP BLOCK
FUSE

8.6 19.9

60 AMP BLOCK 17.2 39.8

1. MAX. K.W. BASED ON 48A, P.E., OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.008 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5E040

REV.1 8/5/00 PNEUMATIC


PSFH113
- J113 -

122 YORK INTERNATIONAL


FORM AD1T-SECT J

SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT


PRESS. INDEPENDENT, N.C. DAMPER, P.E. FAN START, UNOCCUPIED MODE, REVERSE ACTING STAT, 3 PHASE, LOAD BEARING P.E. SWITCH W/ CONT. INTRLK.

SEQUENCE OF OPERATION:
OCCUPIED MODE:
L1 L2 L3
SIGNAL TO PE1 ENERGIZES THE FAN.
DISCONNECT SPACE TEMP WARM (STAT OUTPUT LOW). AT A STAT
SWITCH OUTPUT OF 3 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
FUSING
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
OPTIONAL DISCONNECT SWITCH ON A FURTHER DROP IN SPACE TEMP., PE3 WILL CLOSE
PANEL WIRING DIAGRAM AND OR FUSING ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.

L1 L2 L3 N AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.


TERMINAL UNOCCUPIED MODE:
1 2 3 4
BLOCK WHEN THE PRESSURE APPLIED TO PE1 (SET AND CONTROLLED
BK WH
BY OTHERS) IS DROPPED BELOW ITS SETPOINT IT MAKES
BK BL TO NC CONTACT ENABLING PE2, TURNING OFF FAN.
AS TEMP DROPS, STAT OUTPUT DROPS, STARTING FAN WHEN
BK STANDARD 1 STAGE HEAT PRESSURE DROPS BELOW PE2 SETPOINT.
C1-1 G
NOTE: ON START UP, BLOWER FAN MOTOR MUST BE ENERGIZED
BK BK
BEFORE PRIMARY AIR FAN. FAN CONTROL REQUIRES PROPER
C1-2 SETTING OF PE1 SWITCH BY TEMP CONTROL CONTRACTOR.
C NO BK ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
TC C NO JOB SPECIFICATIONS.
PE-1 BK BK BK
NC 5 C1
ALL P.E. SWITCHES MUST BE SET IN THE FIELD PER JOB
C PE-3 REQUIREMENTS.
NO NC
RD BK BL/WH BK
PE-2 SC FM
NC

BK BK
L1 1
C1-1
P.E. SWITCH SUPPLIED BY FACTORY RD
C NO
PE1 L2 2
(SIGNAL BY OTHERS) RD

PE-4
NC
L1 1
BK BK
BN C NO BN

C NO C1-1 BL
L2 2
RD 3 L3 PE-5
RD NC
RD BL BL
PE-4
NC L3 3
C1-2 C1-2

N.C. PNEUMATIC DIAGRAM OPTIONAL 2 STAGE HEAT OPTIONAL 3 STAGE HEAT

ACT. RECOMMENDED FIELD P.E. SWITCH SETTINGS:

PE-2 = 8 PSI
PE-3 = 8 PSI
BAL. TAPS PE-4 = 10 PSI
VEL. CNTRLR
PE-5 = 12 PSI
B (RESET BAND=3-8 PSI)
FLOW LO X
M 20 PSI MAIN CONSTANT
PROBE HI Y
T VOLUME
TOTAL AIR
R.A.. STAT HEAT
FLOW

COLD AIR
1 PIPE AIR (UNOCCUPIED)
AIR

FLOW PLENUM AIR


RESTRICTOR FAN STARTS
OR OR 20 PSI MAIN (FIELD CALIB.)

R.A.. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE5 PE4 PE3 PE2 2 PIPE HOT T-STAT BRANCH PRESSURE (PSIG) COLD
ROOM ROOM

HEATER COMPONENTS MAX. KW


3 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-3 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 208 V 480 V P = 208V/3PH/60HZ - 1 STAGE J = LOAD BEARING P.E. W/ 30A
1 10.7 24.9 R = 208V/3PH/60HZ - 2 STAGE MAG. CONTACTOR INTERLOCK
30 AMP CONT.
LOAD BRG. PE

2 4.4 9.1 1 = 208V/3PH/60HZ - 3 STAGE K = LOAD BEARING P.E. W/ 50A


W/ INTRLK

PER STAGE 3 2.9 6.0


U = 480V/3PH/60HZ - 1 STAGE MAG. CONTACTOR INTERLOCK
1 17.2 39.8
50 AMP CONT. W = 480V/3PH/60HZ - 2 STAGE L = LOAD BEARING P.E. W/ 30A
2 4.4 9.1 MERC. CONTACTOR INTERLOCK
PER STAGE 3 = 480V/3PH/60HZ - 3 STAGE
3 2.9 6.0
M = LOAD BEARING P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR INTERLOCK


SIZE & TYPE

DOOR INTERLOCK 14.3 33.2

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 17.2 39.8
BLOCK

30 AMP BLOCK
FUSE

8.6 19.9

60 AMP BLOCK 17.2 39.8

1. MAX. K.W. BASED ON 48A, P.E., OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.008 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5F040

REV.1 8/5/00 PNEUMATIC


PSFH114
- J114 -

YORK INTERNATIONAL 123


SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT
PRESS. INDEPENDENT, N.O. DAMPER, P.E. FAN START, UNOCCUPIED MODE, REVERSE ACTING STAT, 3 PHASE, LOAD BEARING P.E. SWITCH W/ CONT. INTRLK.

SEQUENCE OF OPERATION:
OCCUPIED MODE:
L1 L2 L3
SIGNAL TO PE1 ENERGIZES THE FAN.
DISCONNECT SPACE TEMP WARM (STAT OUTPUT LOW). AT A STAT
SWITCH OUTPUT OF 3 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
FUSING
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
OPTIONAL DISCONNECT SWITCH ON A FURTHER DROP IN SPACE TEMP., PE3 WILL CLOSE
PANEL WIRING DIAGRAM AND OR FUSING ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.

L1 L2 L3 N AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.


TERMINAL UNOCCUPIED MODE:
1 2 3 4
BLOCK WHEN THE PRESSURE APPLIED TO PE1 (SET AND CONTROLLED
BK WH
BY OTHERS) IS DROPPED BELOW ITS SETPOINT IT MAKES
BK BL TO NC CONTACT ENABLING PE2, TURNING OFF FAN.
AS TEMP DROPS, STAT OUTPUT DROPS, STARTING FAN WHEN
BK STANDARD 1 STAGE HEAT PRESSURE DROPS BELOW PE2 SETPOINT.
C1-1 G
NOTE: ON START UP, BLOWER FAN MOTOR MUST BE ENERGIZED
BK BK
BEFORE PRIMARY AIR FAN. FAN CONTROL REQUIRES PROPER
C1-2 SETTING OF PE1 SWITCH BY TEMP CONTROL CONTRACTOR.
C NO BK ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
TC C NO JOB SPECIFICATIONS.
PE-1 BK BK BK
NC 5 C1
ALL P.E. SWITCHES MUST BE SET IN THE FIELD PER JOB
C PE-3 REQUIREMENTS.
NO NC
RD BK BL/WH BK
PE-2 SC FM
NC

BK BK
L1 1
C1-1
PE1
P.E. SWITCH SUPPLIED BY FACTORY RD
C NO
(SIGNAL BY OTHERS) L2 2 RD

PE-4
NC
L1 1
BK BK
BN C NO BN

C NO C1-1 BL
L2 2
RD 3 L3 PE-5
RD NC
RD BL BL
PE-4
NC L3 3
C1-2 C1-2
N.O. PNEUMATIC DIAGRAM OPTIONAL 2 STAGE HEAT OPTIONAL 3 STAGE HEAT
ACT. RECOMMENDED FIELD P.E. SWITCH SETTINGS:

PE-2 = 8 PSI
PE-3 = 8 PSI
BAL. TAPS VEL. CNTRLR PE-4 = 10 PSI
B (RESET BAND=8-13 PSI) PE-5 = 12 PSI
FLOW LO Y
M 20 PSI MAIN
PROBE HI X CONSTANT
T
VOLUME
TOTAL AIR
REV. R.A.. STAT
FLOW

RELAY 1 PIPE COLD AIR HEAT


AIR

AIR (UNOCCUPIED)
M RESTRICTOR FLOW PLENUM AIR
1 FAN STARTS
3 OR OR 20 PSI MAIN
(FIELD CALIB.)

R.A.. STAT
2 PIPE 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE5 PE4 PE3 PE2 HOT T-STAT BRANCH PRESSURE (PSIG) COLD
ROOM ROOM

HEATER COMPONENTS MAX. KW


3 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-3 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 208 V 480 V P = 208V/3PH/60HZ - 1 STAGE J = LOAD BEARING P.E. W/ 30A
1 10.7 24.9 R = 208V/3PH/60HZ - 2 STAGE MAG. CONTACTOR INTERLOCK
30 AMP CONT.
LOAD BRG. PE

2 4.4 9.1 1 = 208V/3PH/60HZ - 3 STAGE K = LOAD BEARING P.E. W/ 50A


W/ INTRLK

PER STAGE 3 2.9 6.0


U = 480V/3PH/60HZ - 1 STAGE MAG. CONTACTOR INTERLOCK
1 17.2 39.8
50 AMP CONT. W = 480V/3PH/60HZ - 2 STAGE L = LOAD BEARING P.E. W/ 30A
2 4.4 9.1 MERC. CONTACTOR INTERLOCK
PER STAGE 3 = 480V/3PH/60HZ - 3 STAGE
3 2.9 6.0
M = LOAD BEARING P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR INTERLOCK


SIZE & TYPE

DOOR INTERLOCK 14.3 33.2

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 17.2 39.8
BLOCK

30 AMP BLOCK
FUSE

8.6 19.9

60 AMP BLOCK 17.2 39.8

1. MAX. K.W. BASED ON 48A, P.E., OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.016 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5G040

REV.1 8/5/00 PNEUMATIC


PSFH115
- J115 -

124 YORK INTERNATIONAL


FORM AD1T-SECT J

SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT


PRESS. INDEPENDENT, N.C. DAMPER, P.E. FAN START, UNOCCUPIED MODE, DIRECT ACTING STAT, 3 PHASE, LOAD BEARING P.E. SWITCH W/ CONT. INTRLK.

SEQUENCE OF OPERATION:
OCCUPIED MODE:
L1 L2 L3
SIGNAL TO PE1 ENERGIZES THE FAN.
DISCONNECT SPACE TEMP WARM (STAT OUTPUT HI). AT A STAT
SWITCH OUTPUT OF 13 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
FUSING
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
OPTIONAL DISCONNECT SWITCH ON A FURTHER DROP IN SPACE TEMP., PE3 WILL CLOSE
PANEL WIRING DIAGRAM AND OR FUSING ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.

L1 L2 L3 N AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.


TERMINAL UNOCCUPIED MODE:
1 2 3 4
BLOCK WHEN THE PRESSURE APPLIED TO PE1 (SET AND CONTROLLED
BK WH
BY OTHERS) IS DROPPED BELOW ITS SETPOINT IT MAKES
BK BL TO NC CONTACT ENABLING PE2, TURNING OFF FAN.
AS TEMP DROPS, STAT OUTPUT DROPS, STARTING FAN WHEN
BK STANDARD 1 STAGE HEAT PRESSURE DROPS BELOW PE2 SETPOINT.
C1-1 G
NOTE: ON START UP, BLOWER FAN MOTOR MUST BE ENERGIZED
BK BK
BEFORE PRIMARY AIR FAN. FAN CONTROL REQUIRES PROPER
C1-2 SETTING OF PE1 SWITCH BY TEMP CONTROL CONTRACTOR.
C NO BK ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
TC C NO JOB SPECIFICATIONS.
PE-1 BK BK BK
NC 5 C1
ALL P.E. SWITCHES MUST BE SET IN THE FIELD PER JOB
C PE-3 REQUIREMENTS.
NO NC
RD BK BL/WH BK
PE-2 SC FM
NC

BK BK
L1 1
C1-1
C NO
PE1
P.E. SWITCH SUPPLIED BY FACTORY L2 2
RD

(SIGNAL BY OTHERS) RD
PE-4
NC
L1 1
BK BK
BN C NO BN

C NO C1-1 BL
L2 2
RD 3 L3 PE-5
RD RD
NC
PE-4 BL BL
NC L3 3
C1-2 C1-2
N.C. PNEUMATIC DIAGRAM
OPTIONAL 2 STAGE HEAT OPTIONAL 3 STAGE HEAT
ACT.
RECOMMENDED FIELD P.E. SWITCH SETTINGS:

PE-2 = 8 PSI
PE-3 = 8 PSI
BAL. TAPS VEL. CNTRLR PE-4 = 6 PSI
B (RESET BAND=3-8 PSI)
PE-5 = 4 PSI
FLOW LO X
M 20 PSI MAIN
PROBE HI Y CONSTANT
T
VOLUME
REV. D.A.. STAT TOTAL AIR
FLOW

RELAY 1 PIPE HEAT COLD AIR


AIR

AIR
M (UNOCCUPIED)
1 RESTRICTOR FLOW PLENUM AIR
3 OR OR 20 PSI MAIN FAN STARTS
(FIELD CALIB.)

D.A.. STAT
2 PIPE 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE3 PE2 COLD T-STAT BRANCH PRESSURE (PSIG) HOT
PE5 PE4
ROOM ROOM

HEATER COMPONENTS MAX. KW


3 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-3 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 208 V 480 V P = 208V/3PH/60HZ - 1 STAGE J = LOAD BEARING P.E. W/ 30A
1 10.7 24.9 R = 208V/3PH/60HZ - 2 STAGE MAG. CONTACTOR INTERLOCK
30 AMP CONT.
LOAD BRG. PE

2 4.4 9.1 1 = 208V/3PH/60HZ - 3 STAGE K = LOAD BEARING P.E. W/ 50A


W/ INTRLK

PER STAGE 3 2.9 6.0


U = 480V/3PH/60HZ - 1 STAGE MAG. CONTACTOR INTERLOCK
1 17.2 39.8
50 AMP CONT. W = 480V/3PH/60HZ - 2 STAGE L = LOAD BEARING P.E. W/ 30A
2 4.4 9.1 MERC. CONTACTOR INTERLOCK
PER STAGE 3 = 480V/3PH/60HZ - 3 STAGE
3 2.9 6.0
M = LOAD BEARING P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR INTERLOCK


SIZE & TYPE

DOOR INTERLOCK 14.3 33.2

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 17.2 39.8
BLOCK

30 AMP BLOCK
FUSE

8.6 19.9

60 AMP BLOCK 17.2 39.8

1. MAX. K.W. BASED ON 48A, P.E., OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.016 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5H040

REV.1 8/5/00 PNEUMATIC


PSFH116
- J116 -

YORK INTERNATIONAL 125


SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT
PRESS. INDEPENDENT, N.O. DAMPER, P.E. FAN START, UNOCCUPIED MODE, DIRECT ACTING STAT, 3 PHASE, PILOT DUTY P.E. SWITCH

SEQUENCE OF OPERATION:
OCCUPIED MODE:
L1 L2 L3
SIGNAL TO PE1 ENERGIZES THE FAN.
DISCONNECT SPACE TEMP WARM (STAT OUTPUT HI). AT A STAT
SWITCH OUTPUT OF 13 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
FUSING
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
OPTIONAL DISCONNECT SWITCH ON A FURTHER DROP IN SPACE TEMP., PE3 WILL CLOSE
PANEL WIRING DIAGRAM AND OR FUSING ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.

L1 L2 L3 N AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.


TERMINAL UNOCCUPIED MODE:
1 2 3 4
BLOCK WHEN THE PRESSURE APPLIED TO PE1 (SET AND CONTROLLED
BK WH
BY OTHERS) IS DROPPED BELOW ITS SETPOINT IT MAKES
BK BL TO NC CONTACT ENABLING PE2, TURNING OFF FAN.
AS TEMP DROPS, STAT OUTPUT DROPS, STARTING FAN WHEN
BK STANDARD 1 STAGE HEAT PRESSURE DROPS BELOW PE2 SETPOINT.
C1-1 G
NOTE: ON START UP, BLOWER FAN MOTOR MUST BE ENERGIZED
BK BK
BEFORE PRIMARY AIR FAN. FAN CONTROL REQUIRES PROPER
C1-2 SETTING OF PE1 SWITCH BY TEMP CONTROL CONTRACTOR.
C NO BK ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
TC C NO ST.1 JOB SPECIFICATIONS.
BK BK BK
PE-1 5 C1
NC ALL P.E. SWITCHES MUST BE SET IN THE FIELD PER JOB
C PE-3 REQUIREMENTS.
NO NC
ST.2
RD RD C NO RD
PE-2 C2 BK BK
NC L1 1
PE-4 C1-1 BL
3 L3
NC
ST.3 RD RD
BN C NO BN L2 2
C3 C2-1
PE-5 OPTIONAL 2 STAGE HEAT
NC
BK BL/WH BK
SC FM
BK BK
L1 1
C1-1
RD RD
L2 2
PE1
P.E. SWITCH SUPPLIED BY FACTORY C2-1
(SIGNAL BY OTHERS) BN BN

C3-1
BL BL
PNEUMATIC DIAGRAM L3 3
N.O. C1-2
ACT. OPTIONAL 3 STAGE HEAT
RECOMMENDED FIELD P.E. SWITCH SETTINGS:
PE-2 = 8 PSI
BAL. TAPS VEL. CNTRLR PE-3 = 8 PSI
(RESET BAND=8-13 PSI) PE-4 = 6 PSI
B
FLOW LO Y PE-5 = 4 PSI
M 20 PSI MAIN
PROBE HI X CONSTANT
T VOLUME
TOTAL AIR
D.A.. STAT
FLOW

1 PIPE HEAT COLD AIR


AIR

AIR
(UNOCCUPIED)
RESTRICTOR FLOW PLENUM AIR
FAN STARTS
OR OR 20 PSI MAIN (FIELD CALIB.)

D.A.. STAT
PE5 PE4 PE3 PE2 2 PIPE 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
COLD T-STAT BRANCH PRESSURE (PSIG) HOT
ROOM ROOM

HEATER COMPONENTS MAX. KW


3 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-3 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 208 V 480 V P = 208V/3PH/60HZ - 1 STAGE 2 = PILOT DUTY P.E. W/ 30A
1 10.7 24.9 R = 208V/3PH/60HZ - 2 STAGE MAG. CONTACTOR
DE-ENERGIZING
CONTACTOR

30 AMP 2 5.3 12.4 1 = 208V/3PH/60HZ - 3 STAGE 3 = PILOT DUTY P.E. W/ 50A


PER STAGE 3 3.5 8.3
U = 480V/3PH/60HZ - 1 STAGE MAG. CONTACTOR
1 17.2 39.8
50 AMP W = 480V/3PH/60HZ - 2 STAGE 4 = PILOT DUTY P.E. W/ 30A
2 8.6 19.9 MERC. CONTACTOR
PER STAGE 3 = 480V/3PH/60HZ - 3 STAGE
3 5.7 13.2
5 = PILOT DUTY P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR


SIZE & TYPE

DOOR INTERLOCK 14.3 33.2

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 17.2 39.8
BLOCK

30 AMP BLOCK 8.6 19.9


FUSE

60 AMP BLOCK 17.2 39.8

1. MAX. K.W. BASED ON 48A, OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.008 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5E040

REV.1 8/5/00 PNEUMATIC


PSFH117
- J117 -

126 YORK INTERNATIONAL


FORM AD1T-SECT J

SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT


PRESS. INDEPENDENT, N.C. DAMPER, P.E. FAN START, UNOCCUPIED MODE, REVERSE ACTING STAT, 3 PHASE, PILOT DUTY P.E. SWITCH

SEQUENCE OF OPERATION:
OCCUPIED MODE:
L1 L2 L3
SIGNAL TO PE1 ENERGIZES THE FAN.
DISCONNECT SPACE TEMP WARM (STAT OUTPUT LOW). AT A STAT
SWITCH OUTPUT OF 3 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
FUSING
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
OPTIONAL DISCONNECT SWITCH ON A FURTHER DROP IN SPACE TEMP., PE3 WILL CLOSE
PANEL WIRING DIAGRAM AND OR FUSING ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.

L1 L2 L3 N AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.


TERMINAL UNOCCUPIED MODE:
1 2 3 4
BLOCK WHEN THE PRESSURE APPLIED TO PE1 (SET AND CONTROLLED
BK WH
BY OTHERS) IS DROPPED BELOW ITS SETPOINT IT MAKES
BK BL TO NC CONTACT ENABLING PE2, TURNING OFF FAN.
AS TEMP DROPS, STAT OUTPUT DROPS, STARTING FAN WHEN
BK STANDARD 1 STAGE HEAT PRESSURE DROPS BELOW PE2 SETPOINT.
C1-1 G
NOTE: ON START UP, BLOWER FAN MOTOR MUST BE ENERGIZED
BK BK
BEFORE PRIMARY AIR FAN. FAN CONTROL REQUIRES PROPER
C1-2 SETTING OF PE1 SWITCH BY TEMP CONTROL CONTRACTOR.
C NO BK ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
TC C NO ST.1 JOB SPECIFICATIONS.
BK BK BK
PE-1 5 C1
NC ALL P.E. SWITCHES MUST BE SET IN THE FIELD PER JOB
C PE-3 REQUIREMENTS.
NO NC
RD
ST.2
RD C NO RD
PE-2 C2 BK BK
NC L1 1
PE-4 C1-1 BL
3 L3
NC RD RD
ST.3 L2 2
BN C NO BN
C3 C2-1
PE-5 OPTIONAL 2 STAGE HEAT
NC
BK BL/WH BK
SC FM
BK BK
L1 1
C1-1
RD RD
L2 2
P.E. SWITCH SUPPLIED BY FACTORY C2-1
PE1 BN BN
(SIGNAL BY OTHERS)
C3-1
BL BL
L3 3
N.C. PNEUMATIC DIAGRAM C1-2
ACT. OPTIONAL 3 STAGE HEAT
RECOMMENDED FIELD P.E. SWITCH SETTINGS:
PE-2 = 8 PSI
BAL. TAPS VEL. CNTRLR PE-3 = 8 PSI
(RESET BAND=3-8 PSI) PE-4 = 10 PSI
B
FLOW LO X PE-5 = 12 PSI
M 20 PSI MAIN
PROBE HI Y CONSTANT
T
VOLUME
TOTAL AIR
R.A.. STAT
FLOW

1 PIPE COLD AIR HEAT


AIR

AIR (UNOCCUPIED)
RESTRICTOR FLOW PLENUM AIR
FAN STARTS
OR OR 20 PSI MAIN
(FIELD CALIB.)

R.A.. STAT
PE5 PE4 PE3 PE2 2 PIPE 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
HOT T-STAT BRANCH PRESSURE (PSIG) COLD
ROOM ROOM
HEATER COMPONENTS MAX. KW
3 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-3 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 208 V 480 V P = 208V/3PH/60HZ - 1 STAGE 2 = PILOT DUTY P.E. W/ 30A
1 10.7 24.9 R = 208V/3PH/60HZ - 2 STAGE MAG. CONTACTOR
DE-ENERGIZING
CONTACTOR

30 AMP 2 5.3 12.4 1 = 208V/3PH/60HZ - 3 STAGE 3 = PILOT DUTY P.E. W/ 50A


PER STAGE 3 3.5 8.3
U = 480V/3PH/60HZ - 1 STAGE MAG. CONTACTOR
1 17.2 39.8
50 AMP W = 480V/3PH/60HZ - 2 STAGE 4 = PILOT DUTY P.E. W/ 30A
2 8.6 19.9 MERC. CONTACTOR
PER STAGE 3 = 480V/3PH/60HZ - 3 STAGE
3 5.7 13.2
5 = PILOT DUTY P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR


SIZE & TYPE

DOOR INTERLOCK 14.3 33.2

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 17.2 39.8
BLOCK

30 AMP BLOCK 8.6 19.9


FUSE

60 AMP BLOCK 17.2 39.8

1. MAX. K.W. BASED ON 48A, OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.008 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5F040

REV.1 8/5/00 PNEUMATIC


PSFH118
- J118 -

YORK INTERNATIONAL 127


SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT
PRESS. INDEPENDENT, N.O. DAMPER, P.E. FAN START, UNOCCUPIED MODE, REVERSE ACTING STAT, 3 PHASE, PILOT DUTY P.E. SWITCH

SEQUENCE OF OPERATION:
OCCUPIED MODE:
L1 L2 L3
SIGNAL TO PE1 ENERGIZES THE FAN.
DISCONNECT SPACE TEMP WARM (STAT OUTPUT LOW). AT A STAT
SWITCH OUTPUT OF 3 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
FUSING
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
OPTIONAL DISCONNECT SWITCH ON A FURTHER DROP IN SPACE TEMP., PE3 WILL CLOSE
PANEL WIRING DIAGRAM AND OR FUSING ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.

L1 L2 L3 N AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.


TERMINAL UNOCCUPIED MODE:
1 2 3 4
BLOCK WHEN THE PRESSURE APPLIED TO PE1 (SET AND CONTROLLED
BK WH
BY OTHERS) IS DROPPED BELOW ITS SETPOINT IT MAKES
BK BL TO NC CONTACT ENABLING PE2, TURNING OFF FAN.
AS TEMP DROPS, STAT OUTPUT DROPS, STARTING FAN WHEN
BK STANDARD 1 STAGE HEAT PRESSURE DROPS BELOW PE2 SETPOINT.
C1-1 G
NOTE: ON START UP, BLOWER FAN MOTOR MUST BE ENERGIZED
BK BK
BEFORE PRIMARY AIR FAN. FAN CONTROL REQUIRES PROPER
C1-2 SETTING OF PE1 SWITCH BY TEMP CONTROL CONTRACTOR.
C NO BK ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
TC C NO ST.1 JOB SPECIFICATIONS.
BK BK BK
PE-1 5 C1
NC ALL P.E. SWITCHES MUST BE SET IN THE FIELD PER JOB
C PE-3 REQUIREMENTS.
NO NC
RD
ST.2
RD C NO RD
PE-2 C2 BK BK
NC L1 1
PE-4 BL
C1-1 3 L3
NC RD RD
ST.3 L2 2
BN C NO BN
C3 C2-1
PE-5 OPTIONAL 2 STAGE HEAT
NC
BK BL/WH BK
SC FM BK BK
L1 1
C1-1
RD RD
L2 2
P.E. SWITCH SUPPLIED BY FACTORY C2-1
PE1 BN BN
(SIGNAL BY OTHERS)
C3-1
BL BL
N.O. PNEUMATIC DIAGRAM L3 3
C1-2
ACT. OPTIONAL 3 STAGE HEAT
RECOMMENDED FIELD P.E. SWITCH SETTINGS:
PE-2 = 8 PSI
BAL. TAPS VEL. CNTRLR PE-3 = 8 PSI
B (RESET BAND=8-13 PSI) PE-4 = 10 PSI
FLOW LO Y PE-5 = 12 PSI
M 20 PSI MAIN
PROBE HI X
T CONSTANT
VOLUME
REV. R.A.. STAT TOTAL AIR
FLOW

RELAY 1 PIPE HEAT


AIR

COLD AIR
M AIR (UNOCCUPIED)
1 RESTRICTOR PLENUM AIR
3 OR OR 20 PSI MAIN FLOW FAN STARTS
(FIELD CALIB.)

R.A.. STAT
2 PIPE 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE5 PE4 PE3 PE2
HOT T-STAT BRANCH PRESSURE (PSIG) COLD
ROOM ROOM

HEATER COMPONENTS MAX. KW


3 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-3 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 208 V 480 V P = 208V/3PH/60HZ - 1 STAGE 2 = PILOT DUTY P.E. W/ 30A
1 10.7 24.9 R = 208V/3PH/60HZ - 2 STAGE MAG. CONTACTOR
DE-ENERGIZING
CONTACTOR

30 AMP 2 5.3 12.4 1 = 208V/3PH/60HZ - 3 STAGE 3 = PILOT DUTY P.E. W/ 50A


PER STAGE 3 3.5 8.3
U = 480V/3PH/60HZ - 1 STAGE MAG. CONTACTOR
1 17.2 39.8
50 AMP W = 480V/3PH/60HZ - 2 STAGE 4 = PILOT DUTY P.E. W/ 30A
2 8.6 19.9 MERC. CONTACTOR
PER STAGE 3 = 480V/3PH/60HZ - 3 STAGE
3 5.7 13.2
5 = PILOT DUTY P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR


SIZE & TYPE

DOOR INTERLOCK 14.3 33.2

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 17.2 39.8
BLOCK

30 AMP BLOCK 8.6 19.9


FUSE

60 AMP BLOCK 17.2 39.8

1. MAX. K.W. BASED ON 48A, OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.016 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5G040

REV.1 8/5/00 PNEUMATIC


PSFH119
- J119 -

128 YORK INTERNATIONAL


FORM AD1T-SECT J

SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT


PRESS. INDEPENDENT, N.C. DAMPER, P.E. FAN START, UNOCCUPIED MODE, DIRECT ACTING STAT, 3 PHASE, PILOT DUTY P.E. SWITCH

SEQUENCE OF OPERATION:
OCCUPIED MODE:
L1 L2 L3
SIGNAL TO PE1 ENERGIZES THE FAN.
DISCONNECT SPACE TEMP WARM (STAT OUTPUT HI). AT A STAT
SWITCH OUTPUT OF 13 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
FUSING
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
OPTIONAL DISCONNECT SWITCH ON A FURTHER DROP IN SPACE TEMP., PE3 WILL CLOSE
PANEL WIRING DIAGRAM AND OR FUSING ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.

L1 L2 L3 N AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.


TERMINAL UNOCCUPIED MODE:
1 2 3 4
BLOCK WHEN THE PRESSURE APPLIED TO PE1 (SET AND CONTROLLED
BK WH
BY OTHERS) IS DROPPED BELOW ITS SETPOINT IT MAKES
BK BL TO NC CONTACT ENABLING PE2, TURNING OFF FAN.
AS TEMP DROPS, STAT OUTPUT DROPS, STARTING FAN WHEN
BK STANDARD 1 STAGE HEAT PRESSURE DROPS BELOW PE2 SETPOINT.
C1-1 G
NOTE: ON START UP, BLOWER FAN MOTOR MUST BE ENERGIZED
BK BK
BEFORE PRIMARY AIR FAN. FAN CONTROL REQUIRES PROPER
C1-2 SETTING OF PE1 SWITCH BY TEMP CONTROL CONTRACTOR.
C NO BK ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
TC C NO ST.1 JOB SPECIFICATIONS.
BK BK BK
PE-1 5 C1
NC ALL P.E. SWITCHES MUST BE SET IN THE FIELD PER JOB
C PE-3 REQUIREMENTS.
NO NC
ST.2
RD RD C NO RD
PE-2 C2 L1 1
BK BK
NC BL
PE-4 C1-1 3 L3
NC RD RD
ST.3 L2 2
BN C NO BN
C2-1
C3
PE-5 OPTIONAL 2 STAGE HEAT
NC
BK BL/WH BK
SC FM BK BK
L1 1
C1-1
RD RD
L2 2
P.E. SWITCH SUPPLIED BY FACTORY C2-1
PE1 BN BN
(SIGNAL BY OTHERS)
C3-1
BL BL
L3 3
N.C. PNEUMATIC DIAGRAM C1-2
ACT. OPTIONAL 3 STAGE HEAT
RECOMMENDED FIELD P.E. SWITCH SETTINGS:
PE-2 = 8 PSI
BAL. TAPS VEL. CNTRLR PE-3 = 8 PSI
B (RESET BAND=3-8 PSI) PE-4 = 6 PSI
FLOW LO X PE-5 = 4 PSI
M 20 PSI MAIN
PROBE HI Y
T CONSTANT
VOLUME
REV. D.A.. STAT TOTAL AIR
FLOW

RELAY 1 PIPE HEAT


AIR

COLD AIR
M AIR
RESTRICTOR (UNOCCUPIED)
1 FLOW PLENUM AIR
3 OR OR 20 PSI MAIN FAN STARTS
(FIELD CALIB.)

D.A.. STAT
2 PIPE 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE5 PE4 PE3 PE2 COLD T-STAT BRANCH PRESSURE (PSIG) HOT
ROOM ROOM

HEATER COMPONENTS MAX. KW


3 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-3 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 208 V 480 V P = 208V/3PH/60HZ - 1 STAGE 2 = PILOT DUTY P.E. W/ 30A
1 10.7 24.9 R = 208V/3PH/60HZ - 2 STAGE MAG. CONTACTOR
DE-ENERGIZING
CONTACTOR

30 AMP 2 5.3 12.4 1 = 208V/3PH/60HZ - 3 STAGE 3 = PILOT DUTY P.E. W/ 50A


PER STAGE 3 3.5 8.3
U = 480V/3PH/60HZ - 1 STAGE MAG. CONTACTOR
1 17.2 39.8
50 AMP W = 480V/3PH/60HZ - 2 STAGE 4 = PILOT DUTY P.E. W/ 30A
2 8.6 19.9 MERC. CONTACTOR
PER STAGE 3 = 480V/3PH/60HZ - 3 STAGE
3 5.7 13.2
5 = PILOT DUTY P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR


SIZE & TYPE

DOOR INTERLOCK 14.3 33.2

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 17.2 39.8
BLOCK

30 AMP BLOCK 8.6 19.9


FUSE

60 AMP BLOCK 17.2 39.8

1. MAX. K.W. BASED ON 48A, OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.016 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5H040

REV.1 8/5/00 PNEUMATIC


PSFH120
- J120 -

YORK INTERNATIONAL 129


SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT
PRESS. INDEPENDENT, N.O. DAMPER, P.E. FAN START, POS. DAMPER CLOSE OFF, DIRECT ACTING STAT, 1 PHASE, LOAD BEARING P.E. SWITCH

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V
OCCUPIED MODE:
DISCONNECT SIGNAL TO PE1 ENERGIZES THE FAN & EP SWITCH.
SWITCH SPACE TEMP WARM (STAT OUTPUT HI). AT A STAT
OUTPUT OF 13 PSI THE VEL. CNTRLR WILL BE CONTROLLING
FUSING AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
OPTIONAL DISCONNECT SWITCH CONTROLLING AT ITS MINIMUM.
AND OR FUSING ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
PANEL WIRING DIAGRAM ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.

AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.


L1 (N) = 120V & 277V
TERMINAL UNOCCUPIED MODE:
1 2
BLOCK WHEN SIGNAL TO PE1 FALLS BELOW ITS SETPOINT
BK WH IT DE-ENERGIZES THE FAN & EP SWITCH, CAUSING THE
DAMPER TO CLOSE.
C NO BK
ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
BK C NO BK WH G JOB SPECIFICATIONS.
PE-1 5
NC
PE-2 STANDARD 1
NC STAGE HEAT
RD C NO RD

OPTIONAL 2
PE-3 NOTE: S1 AIRFLOW SWITCH FACTORY SET TO START FAN AT
NC STAGE HEAT
.10"WC TOTAL PRESSURE SENSED AT INLET FLOW PROBE.
BN C NO BN

OPTIONAL 3
PE-4
NC STAGE HEAT

BK BL/WH BK
SC FM

EP

P.E. SWITCH SUPPLIED BY FACTORY


PE1
(SIGNAL BY OTHERS)

N.O. PNEUMATIC DIAGRAM


RECOMMENDED FIELD P.E. SWITCH SETTINGS:
ACT. 3(C)
PE-2 = 8 PSI
(NC)1 2(NO)
PE-3 = 6 PSI
EP
PE-4 = 4 PSI
BAL. TAPS VEL. CNTRLR
B (RESET BAND=8-13 PSI)
FLOW LO Y CONSTANT
M 20 PSI MAIN
PROBE HI X VOLUME
T TOTAL AIR
D.A.. STAT HEAT COLD AIR
FLOW

1 PIPE AIR
AIR

FLOW PLENUM AIR


RESTRICTOR
OR OR 20 PSI MAIN

D.A.. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE4 PE3 PE2 2 PIPE COLD T-STAT BRANCH PRESSURE (PSIG) HOT
ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE 1 = LOAD BEARING P.E.
SWITCH

1 2.8 6.7 E = 120V/1PH/60HZ - 2 STAGE


LOAD BEARING
P.E.

PER STAGE 2 1.4 3.3 5 = 120V/1PH/60HZ - 3 STAGE


3 0.9 2.2
K = 277V/1PH/60HZ - 1 STAGE
DISCONNECT

L = 277V/1PH/60HZ - 2 STAGE
SIZE & TYPE

DNF-40 2.8 6.7 Y = 277V/1PH/60HZ - 3 STAGE


DOOR INTERLOCK
BLOCK
FUSE

30 AMP BLOCK 2.8 6.7

1. MAX. K.W. BASED ON A.F.S. MAX LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.008 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5E060

REV.1 5/14/00 PNEUMATIC


PSFH121
- J121 -

130 YORK INTERNATIONAL


FORM AD1T-SECT J

SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT


PRESS. INDEPENDENT, N.C. DAMPER, P.E. FAN START, POS. DAMPER CLOSE OFF, REVERSE ACTING STAT, 1 PHASE, LOAD BEARING P.E. SWITCH

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V
OCCUPIED MODE:
DISCONNECT SIGNAL TO PE1 ENERGIZES THE FAN & EP SWITCH.
SWITCH SPACE TEMP WARM (STAT OUTPUT LOW). AT A STAT
OUTPUT OF 3 PSI THE VEL. CNTRLR WILL BE CONTROLLING
FUSING AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
OPTIONAL DISCONNECT SWITCH CONTROLLING AT ITS MINIMUM.
AND OR FUSING ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
PANEL WIRING DIAGRAM ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.

L1 (N) = 120V & 277V AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.

TERMINAL UNOCCUPIED MODE:


1 2
BLOCK WHEN SIGNAL TO PE1 FALLS BELOW ITS SETPOINT IT
BK WH DEENERGIZES THE FAN & EP SWITCH, CAUSING DAMPER TO
C CLOSE.
NO BK
ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
BK C NO BK WH G
PE-1 5 JOB SPECIFICATIONS.
NC
PE-2 STANDARD 1
NC STAGE HEAT
RD C NO RD

OPTIONAL 2
PE-3 NOTE: S1 AIRFLOW SWITCH FACTORY SET TO START FAN AT
NC STAGE HEAT
.10"WC TOTAL PRESSURE SENSED AT INLET FLOW PROBE.
BN C NO BN

OPTIONAL 3
PE-4
NC STAGE HEAT

BK BL/WH BK
SC FM

EP

P.E. SWITCH SUPPLIED BY FACTORY


PE1
(SIGNAL BY OTHERS)

N.C. PNEUMATIC DIAGRAM


RECOMMENDED FIELD P.E. SWITCH SETTINGS:
ACT. 3(C)
PE-2 = 8 PSI
(NC)1 2(NO)
ACTPNEU PE-3 = 6 PSI
EP
PE-4 = 4 PSI
BAL. TAPS VEL. CNTRLR
B (RESET BAND=3-8 PSI)
FLOW LO Y CONSTANT
M 20 PSI MAIN
PROBE HI X VOLUME
T TOTAL AIR
R.A.. STAT HEAT COLD AIR
FLOW

1 PIPE AIR
AIR

FLOW PLENUM AIR


RESTRICTOR
OR OR 20 PSI MAIN

R.A.. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE4 PE3 PE2 2 PIPE COLD T-STAT BRANCH PRESSURE (PSIG) HOT
ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE 1 = LOAD BEARING P.E.
SWITCH

1 2.8 6.7 E = 120V/1PH/60HZ - 2 STAGE


LOAD BEARING
P.E.

PER STAGE 2 1.4 3.3 5 = 120V/1PH/60HZ - 3 STAGE


3 0.9 2.2
K = 277V/1PH/60HZ - 1 STAGE
DISCONNECT

L = 277V/1PH/60HZ - 2 STAGE
SIZE & TYPE

DNF-40 2.8 6.7 Y = 277V/1PH/60HZ - 3 STAGE


DOOR INTERLOCK
BLOCK
FUSE

30 AMP BLOCK 2.8 6.7

1. MAX. K.W. BASED ON A.F.S. MAX LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.008 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5F060

REV.1 5/14/00 PNEUMATIC


PSFH122
- J122 -

YORK INTERNATIONAL 131


SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT
PRESS. INDEPENDENT, N.O. DAMPER, P.E. FAN START, POS. DAMPER CLOSE OFF, REVERSE ACTING STAT, 1 PHASE, LOAD BEARING P.E. SWITCH

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V
DISCONNECT SIGNAL TO PE1 ENERGIZES THE FAN & EP SWITCH.
SWITCH SPACE TEMP WARM (STAT OUTPUT LOW). AT A STAT
OUTPUT OF 3 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
FUSING WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
OPTIONAL DISCONNECT SWITCH
ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
AND OR FUSING
PANEL WIRING DIAGRAM ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.

AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.


L1 (N) = 120V & 277V
TERMINAL UNOCCUPIED MODE:
1 2 WHEN SIGNAL TO PE1 FALLS BELOW ITS SETPOINT
BLOCK
BK WH IT DE-ENERGIZES THE FAN & EP SWITCH, CAUSING THE
DAMPER TO CLOSE.
C NO
ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
BK BK C NO BK WH G
PE-1 5 JOB SPECIFICATIONS.
NC
PE-2 STANDARD 1
NC STAGE HEAT
RD C NO RD

PE-3 OPTIONAL 2
NC STAGE HEAT
BN C NO BN

PE-4 OPTIONAL 3
NC STAGE HEAT

BK BL/WH BK
SC FM

EP

PE1
P.E. SWITCH SUPPLIED BY FACTORY
(SIGNAL BY OTHERS)

N.O.
PNEUMATIC DIAGRAM
ACT. (3)C RECOMMENDED FIELD P.E. SWITCH SETTINGS:
(1)NC (2)NO
PE-2 = 8 PSI
EP
PE-3 = 10 PSI
BAL. TAPS VEL. CNTRLR PE-4 = 12 PSI
B (RESET BAND=8-13 PSI)
FLOW LO Y
M 20 PSI MAIN
PROBE HI X CONSTANT
T
VOLUME
REV. R.A.. STAT TOTAL AIR
FLOW

RELAY 1 PIPE HEAT


AIR

COLD AIR
AIR
M RESTRICTOR PLENUM AIR
1 FLOW
3 OR OR 20 PSI MAIN

R.A.. STAT
2 PIPE 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE4 PE3 PE2 HOT T-STAT BRANCH PRESSURE (PSIG) COLD
ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE 1 = LOAD BEARING P.E.
SWITCH

1 2.8 6.7 E = 120V/1PH/60HZ - 2 STAGE


LOAD BEARING
P.E.

PER STAGE 2 1.4 3.3 5 = 120V/1PH/60HZ - 3 STAGE


3 0.9 2.2
K = 277V/1PH/60HZ - 1 STAGE
DISCONNECT

L = 277V/1PH/60HZ - 2 STAGE
SIZE & TYPE

DNF-40 2.8 6.7 Y = 277V/1PH/60HZ - 3 STAGE


DOOR INTERLOCK
BLOCK
FUSE

30 AMP BLOCK 2.8 6.7

1. MAX. K.W. BASED ON P.E. MAX LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.016 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5G060

REV.1 8/5/00 PNEUMATIC


PSFH123
- J123 -

132 YORK INTERNATIONAL


FORM AD1T-SECT J

SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT


PRESS. INDEPENDENT, N.C. DAMPER, P.E. FAN START, POS. DAMPER CLOSE OFF, DIRECT ACTING STAT, 1 PHASE, LOAD BEARING P.E. SWITCH

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V
DISCONNECT SIGNAL TO PE1 ENERGIZES THE FAN & EP SWITCH.
SWITCH SPACE TEMP WARM (STAT OUTPUT HI). AT A STAT
OUTPUT OF 13 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
FUSING WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
OPTIONAL DISCONNECT SWITCH
ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
AND OR FUSING
PANEL WIRING DIAGRAM ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.

AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.


L1 (N) = 120V & 277V
TERMINAL UNOCCUPIED MODE:
1 2 WHEN SIGNAL TO PE1 FALLS BELOW ITS SETPOINT
BLOCK
BK WH IT DE-ENERGIZES THE FAN & EP SWITCH, CAUSING THE
DAMPER TO CLOSE.
C NO
ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
BK BK C NO BK WH G
PE-1 5 JOB SPECIFICATIONS.
NC
PE-2 STANDARD 1
NC STAGE HEAT
RD C NO RD

PE-3 OPTIONAL 2
NC STAGE HEAT
BN C NO BN

PE-4 OPTIONAL 3
NC STAGE HEAT

BK BL/WH BK
SC FM

EP

PE1
P.E. SWITCH SUPPLIED BY FACTORY
(SIGNAL BY OTHERS)

N.C.
PNEUMATIC DIAGRAM
ACT. (3)C
RECOMMENDED FIELD P.E. SWITCH SETTINGS:
(1)NC (2)NO
EP PE-2 = 8 PSI
BAL. TAPS VEL. CNTRLR PE-3 = 6 PSI
(RESET BAND=3-8 PSI) PE-4 = 4 PSI
B
FLOW LO X
M 20 PSI MAIN
PROBE HI Y CONSTANT
T
VOLUME
REV. D.A.. STAT TOTAL AIR
FLOW

RELAY 1 PIPE HEAT


AIR

COLD AIR
AIR
M RESTRICTOR PLENUM AIR
1 FLOW
3 OR OR 20 PSI MAIN

D.A.. STAT
2 PIPE 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE4 PE3 PE2 COLD T-STAT BRANCH PRESSURE (PSIG) HOT
ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE 1 = LOAD BEARING P.E.
SWITCH

1 2.8 6.7 E = 120V/1PH/60HZ - 2 STAGE


LOAD BEARING
P.E.

PER STAGE 2 1.4 3.3 5 = 120V/1PH/60HZ - 3 STAGE


3 0.9 2.2
K = 277V/1PH/60HZ - 1 STAGE
DISCONNECT

L = 277V/1PH/60HZ - 2 STAGE
SIZE & TYPE

DNF-40 2.8 6.7 Y = 277V/1PH/60HZ - 3 STAGE


DOOR INTERLOCK
BLOCK
FUSE

30 AMP BLOCK 2.8 6.7

1. MAX. K.W. BASED ON P.E. MAX LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.016 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5H060

REV.1 8/5/00 PNEUMATIC


PSFH124
- J124 -

YORK INTERNATIONAL 133


SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT
P.I., N.O. DAMPER, P.E. FAN START, POS. DAMPER CLOSE OFF, D.A. STAT, 1 PHASE, LOAD BEARING P.E. SWITCH W/ CONT. INTRLK.

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V
DISCONNECT SIGNAL TO PE1 ENERGIZES THE FAN & EP SWITCH.
SWITCH SPACE TEMP WARM (STAT OUTPUT HI). AT A STAT
OUTPUT OF 13 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
FUSING WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
OPTIONAL DISCONNECT SWITCH
ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
AND OR FUSING
PANEL WIRING DIAGRAM ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.

L1 (N) = 120V & 277V AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
TERMINAL 1 2
BLOCK UNOCCUPIED MODE:
BK WH
WHEN SIGNAL TO PE1 FALLS BELOW ITS SETPOINT
IT DE-ENERGIZES THE FAN & EP SWITCH, CAUSING THE
DAMPER TO CLOSE.
BK BK WH

C1-1 STANDARD 1 ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY


G JOB SPECIFICATIONS.
STAGE HEAT
RD C NO RD

PE-3 OPTIONAL 2
NC STAGE HEAT
BN C NO BN

PE-4 OPTIONAL 3
NC STAGE HEAT
(WHEN REQ.)
BK
TC BK C NO BK
C1
PE-2
NC
C NO BK BL/WH BK
BK
5 SC FM
PE-1
NC
BK
EP

PE1
P.E. SWITCH SUPPLIED BY FACTORY
(SIGNAL BY OTHERS)

N.O. PNEUMATIC DIAGRAM


ACT. (3)C
(1)NC (2)NO RECOMMENDED FIELD P.E. SWITCH SETTINGS:
EP
PE-2 = 8 PSI
BAL. TAPS VEL. CNTRLR PE-3 = 6 PSI
B (RESET BAND=8-13 PSI) PE-4 = 4 PSI
FLOW LO Y
M 20 PSI MAIN
PROBE HI X
T CONSTANT
D.A.. STAT VOLUME
TOTAL AIR
FLOW

1 PIPE HEAT
AIR

COLD AIR
AIR
RESTRICTOR
OR OR 20 PSI MAIN FLOW PLENUM AIR

D.A.. STAT
2 PIPE
PE3 PE2
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE4
COLD T-STAT BRANCH PRESSURE (PSIG) HOT
ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE J = LOAD BEARING P.E. W/ 30A
1 3.6 8.3 E = 120V/1PH/60HZ - 2 STAGE MAG. CONTACTOR INTERLOCK
30 AMP CONT.
LOAD BRG. PE

2 1.8 4.1 5 = 120V/1PH/60HZ - 3 STAGE K = LOAD BEARING P.E. W/ 50A


W/ INTRLK

PER STAGE 3 1.2 2.7


K = 277V/1PH/60HZ - 1 STAGE MAG. CONTACTOR INTERLOCK
1 5.7 13.2
50 AMP CONT. L = 277V/1PH/60HZ - 2 STAGE L = LOAD BEARING P.E. W/ 30A
2 2.8 6.6 MERC. CONTACTOR INTERLOCK
PER STAGE Y = 277V/1PH/60HZ - 3 STAGE
3 1.9 4.4
M = LOAD BEARING P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR INTERLOCK


SIZE & TYPE

DOOR INTERLOCK 4.8 11.0

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 5.7 13.2
BLOCK

30 AMP BLOCK
FUSE

2.8 6.6

60 AMP BLOCK 5.7 13.2

1. MAX. K.W. BASED ON 48A, P.E., OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.008 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5E060

REV.1 8/5/00 PNEUMATIC


PSFH125
- J125 -

134 YORK INTERNATIONAL


FORM AD1T-SECT J

SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT


P.I., N.C. DAMPER, P.E. FAN START, POS. DAMPER CLOSE OFF, R.A. STAT, 1 PHASE, LOAD BEARING P.E. SWITCH W/ CONT. INTRLK.

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V
DISCONNECT SIGNAL TO PE1 ENERGIZES THE FAN & EP SWITCH.
SWITCH SPACE TEMP WARM (STAT OUTPUT LOW). AT A STAT
OUTPUT OF 3 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
FUSING WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
OPTIONAL DISCONNECT SWITCH
ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
AND OR FUSING
PANEL WIRING DIAGRAM ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.

L1 (N) = 120V & 277V AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
TERMINAL 1 2
BLOCK UNOCCUPIED MODE:
BK WH
WHEN SIGNAL TO PE1 FALLS BELOW ITS SETPOINT
IT DE-ENERGIZES THE FAN & EP SWITCH, CAUSING THE
DAMPER TO CLOSE.
BK BK WH

C1-1 STANDARD 1 ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY


G JOB SPECIFICATIONS.
STAGE HEAT
RD C NO RD

PE-3 OPTIONAL 2
NC STAGE HEAT
BN C NO BN

PE-4 OPTIONAL 3
NC STAGE HEAT
(WHEN REQ.)
BK
TC BK C NO BK
C1
PE-2
NC
C NO BK BL/WH BK
BK
5 SC FM
PE-1
NC
BK
EP

PE1
P.E. SWITCH SUPPLIED BY FACTORY
(SIGNAL BY OTHERS)

N.C. PNEUMATIC DIAGRAM


ACT. RECOMMENDED FIELD P.E. SWITCH SETTINGS:
(3)C
(1)NC (2)NO
PE-2 = 8 PSI
EP PE-3 = 10 PSI
BAL. TAPS PE-4 = 12 PSI
VEL. CNTRLR
B (RESET BAND=3-8 PSI)
FLOW LO X CONSTANT
M 20 PSI MAIN VOLUME
PROBE HI Y TOTAL AIR
T
COLD AIR HEAT
R.A. STAT
FLOW

AIR
1 PIPE PLENUM AIR
AIR

FLOW
RESTRICTOR
OR OR 20 PSI MAIN

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
R.A. STAT
2 PIPE HOT T-STAT BRANCH PRESSURE (PSIG) COLD
PE4 PE3 PE2 ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE J = LOAD BEARING P.E. W/ 30A
1 3.6 8.3 E = 120V/1PH/60HZ - 2 STAGE MAG. CONTACTOR INTERLOCK
30 AMP CONT.
LOAD BRG. PE

2 1.8 4.1 5 = 120V/1PH/60HZ - 3 STAGE K = LOAD BEARING P.E. W/ 50A


W/ INTRLK

PER STAGE 3 1.2 2.7


K = 277V/1PH/60HZ - 1 STAGE MAG. CONTACTOR INTERLOCK
1 5.7 13.2
50 AMP CONT. L = 277V/1PH/60HZ - 2 STAGE L = LOAD BEARING P.E. W/ 30A
2 2.8 6.6 MERC. CONTACTOR INTERLOCK
PER STAGE Y = 277V/1PH/60HZ - 3 STAGE
3 1.9 4.4
M = LOAD BEARING P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR INTERLOCK


SIZE & TYPE

DOOR INTERLOCK 4.8 11.0

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 5.7 13.2
BLOCK

30 AMP BLOCK
FUSE

2.8 6.6

60 AMP BLOCK 5.7 13.2

1. MAX. K.W. BASED ON 48A, P.E., OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.008 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5F060

REV.1 8/5/00 PNEUMATIC


PSFH126
- J126 -

YORK INTERNATIONAL 135


SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT
P.I., N.O. DAMPER, P.E. FAN START, POS. DAMPER CLOSE OFF, R.A. STAT, 1 PHASE, LOAD BEARING P.E. SWITCH W/ CONT. INTRLK.

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V
DISCONNECT SIGNAL TO PE1 ENERGIZES THE FAN & EP SWITCH.
SWITCH SPACE TEMP WARM (STAT OUTPUT LOW). AT A STAT
OUTPUT OF 3 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
FUSING WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
OPTIONAL DISCONNECT SWITCH
ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
AND OR FUSING
PANEL WIRING DIAGRAM ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.

L1 (N) = 120V & 277V AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
TERMINAL 1 2
BLOCK UNOCCUPIED MODE:
BK WH
WHEN SIGNAL TO PE1 FALLS BELOW ITS SETPOINT
IT DE-ENERGIZES THE FAN & EP SWITCH, CAUSING THE
DAMPER TO CLOSE.
BK BK WH

C1-1 STANDARD 1 ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY


G JOB SPECIFICATIONS.
STAGE HEAT
RD C NO RD

PE-3 OPTIONAL 2
NC STAGE HEAT
BN C NO BN

PE-4 OPTIONAL 3
NC STAGE HEAT
(WHEN REQ.)
BK
TC BK C NO BK
C1
PE-2
NC
C NO BK BL/WH BK
BK
5 SC FM
PE-1
NC
BK
EP

PE1
P.E. SWITCH SUPPLIED BY FACTORY
(SIGNAL BY OTHERS)

N.O.
PNEUMATIC DIAGRAM
ACT. (3)C RECOMMENDED FIELD P.E. SWITCH SETTINGS:
(1)NC (2)NO
PE-2 = 8 PSI
EP
PE-3 = 10 PSI
BAL. TAPS VEL. CNTRLR PE-4 = 12 PSI
B (RESET BAND=8-13 PSI)
FLOW LO Y
M 20 PSI MAIN
PROBE HI X CONSTANT
T
VOLUME
REV. R.A.. STAT TOTAL AIR
FLOW

RELAY 1 PIPE HEAT


AIR

COLD AIR
AIR
M RESTRICTOR PLENUM AIR
1 FLOW
3 OR OR 20 PSI MAIN

R.A.. STAT
2 PIPE 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE4 PE3 PE2 HOT T-STAT BRANCH PRESSURE (PSIG) COLD
ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE J = LOAD BEARING P.E. W/ 30A
1 3.6 8.3 E = 120V/1PH/60HZ - 2 STAGE MAG. CONTACTOR INTERLOCK
30 AMP CONT.
LOAD BRG. PE

2 1.8 4.1 5 = 120V/1PH/60HZ - 3 STAGE K = LOAD BEARING P.E. W/ 50A


W/ INTRLK

PER STAGE 3 1.2 2.7


K = 277V/1PH/60HZ - 1 STAGE MAG. CONTACTOR INTERLOCK
1 5.7 13.2
50 AMP CONT. L = 277V/1PH/60HZ - 2 STAGE L = LOAD BEARING P.E. W/ 30A
2 2.8 6.6 MERC. CONTACTOR INTERLOCK
PER STAGE Y = 277V/1PH/60HZ - 3 STAGE
3 1.9 4.4
M = LOAD BEARING P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR INTERLOCK


SIZE & TYPE

DOOR INTERLOCK 4.8 11.0

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 5.7 13.2
BLOCK

30 AMP BLOCK
FUSE

2.8 6.6

60 AMP BLOCK 5.7 13.2

1. MAX. K.W. BASED ON 48A, P.E., OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.016 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5G060

REV.1 8/5/00 PNEUMATIC


PSFH127
- J127 -

136 YORK INTERNATIONAL


FORM AD1T-SECT J

SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT


P.I., N.C. DAMPER, P.E. FAN START, POS. DAMPER CLOSE OFF, D.A. STAT, 1 PHASE, LOAD BEARING P.E. SWITCH W/ CONT. INTRLK.

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V
DISCONNECT SIGNAL TO PE1 ENERGIZES THE FAN & EP SWITCH.
SWITCH SPACE TEMP WARM (STAT OUTPUT HI). AT A STAT
OUTPUT OF 13 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
FUSING WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
OPTIONAL DISCONNECT SWITCH
ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
AND OR FUSING
PANEL WIRING DIAGRAM ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.

L1 (N) = 120V & 277V AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
TERMINAL 1 2
BLOCK UNOCCUPIED MODE:
BK WH
WHEN SIGNAL TO PE1 FALLS BELOW ITS SETPOINT
IT DE-ENERGIZES THE FAN & EP SWITCH, CAUSING THE
DAMPER TO CLOSE.
BK BK WH

C1-1 STANDARD 1 ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY


G JOB SPECIFICATIONS.
STAGE HEAT
RD C NO RD

PE-3 OPTIONAL 2
NC STAGE HEAT
BN C NO BN

PE-4 OPTIONAL 3
NC STAGE HEAT
(WHEN REQ.)
BK
TC BK C NO BK
C1
PE-2
NC
C NO BK BL/WH BK
BK
5 SC FM
PE-1
NC
BK
EP

PE1
P.E. SWITCH SUPPLIED BY FACTORY
(SIGNAL BY OTHERS)

N.C.
PNEUMATIC DIAGRAM
ACT. RECOMMENDED FIELD P.E. SWITCH SETTINGS:
(3)C
(1)NC (2)NO
PE-2 = 8 PSI
EP PE-3 = 6 PSI
BAL. TAPS VEL. CNTRLR PE-4 = 4 PSI
B (RESET BAND=3-8 PSI)
FLOW LO X CONSTANT
M 20 PSI MAIN
PROBE HI Y VOLUME
T TOTAL AIR
REV. D.A.. STAT HEAT COLD AIR
FLOW

RELAY 1 PIPE AIR


AIR

FLOW PLENUM AIR


M RESTRICTOR
1
3 OR OR 20 PSI MAIN

D.A.. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
2 PIPE COLD T-STAT BRANCH PRESSURE (PSIG) HOT
PE4 PE3 PE2 ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE J = LOAD BEARING P.E. W/ 30A
1 3.6 8.3 E = 120V/1PH/60HZ - 2 STAGE MAG. CONTACTOR INTERLOCK
30 AMP CONT.
LOAD BRG. PE

2 1.8 4.1 5 = 120V/1PH/60HZ - 3 STAGE K = LOAD BEARING P.E. W/ 50A


W/ INTRLK

PER STAGE 3 1.2 2.7


K = 277V/1PH/60HZ - 1 STAGE MAG. CONTACTOR INTERLOCK
1 5.7 13.2
50 AMP CONT. L = 277V/1PH/60HZ - 2 STAGE L = LOAD BEARING P.E. W/ 30A
2 2.8 6.6 MERC. CONTACTOR INTERLOCK
PER STAGE Y = 277V/1PH/60HZ - 3 STAGE
3 1.9 4.4
M = LOAD BEARING P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR INTERLOCK


SIZE & TYPE

DOOR INTERLOCK 4.8 11.0

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 5.7 13.2
BLOCK

30 AMP BLOCK
FUSE

2.8 6.6

60 AMP BLOCK 5.7 13.2

1. MAX. K.W. BASED ON 48A, P.E., OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.016 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5H060

REV.1 8/5/00 PNEUMATIC


PSFH128
- J128 -

YORK INTERNATIONAL 137


SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT
P.I., N.O. DAMPER, P.E. FAN START, POS. DAMPER CLOSE OFF, D.A. STAT, 1 PHASE, PILOT DUTY P.E. SWITCH

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V
DISCONNECT SIGNAL TO PE1 ENERGIZES THE FAN & EP SWITCH.
SWITCH SPACE TEMP WARM (STAT OUTPUT HI). AT A STAT
OUTPUT OF 13 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
FUSING WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
OPTIONAL DISCONNECT SWITCH
ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
AND OR FUSING
PANEL WIRING DIAGRAM ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.

L1 (N) = 120V & 277V AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
TERMINAL 1 2
BLOCK UNOCCUPIED MODE:
BK WH
WHEN SIGNAL TO PE1 FALLS BELOW ITS SETPOINT
IT DE-ENERGIZES THE FAN & EP SWITCH, CAUSING THE
DAMPER TO CLOSE.
BK BK WH

C1-1 STANDARD 1 ST. HEAT ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
G JOB SPECIFICATIONS.
RD RD

C2-1 OPTIONAL 2 ST. HEAT


BN BN

C NO (WHEN REQ.) C3-1 OPTIONAL 3 ST. HEAT


BK
TC C NO BK ST.1
BK BK
PE-1 5 C1
NC
PE-2
NC
ST.2
RD C NO RD
C2
PE-3
NC
ST.3
BN C NO BN
C3
PE-4
NC
BK BL/WH BK
SC FM

BK
EP

PE1
P.E. SWITCH SUPPLIED BY FACTORY
N.O. PNEUMATIC DIAGRAM (SIGNAL BY OTHERS)

ACT. (3)C RECOMMENDED FIELD P.E. SWITCH SETTINGS:


(1)NC (2)NO
EP PE-2 = 8 PSI
PE-3 = 6 PSI
BAL. TAPS VEL. CNTRLR PE-4 = 4 PSI
B (RESET BAND=8-13 PSI)
FLOW LO Y CONSTANT
M 20 PSI MAIN
PROBE HI X VOLUME
T TOTAL AIR
D.A.. STAT HEAT COLD AIR
FLOW

1 PIPE AIR
AIR

FLOW PLENUM AIR


RESTRICTOR
OR OR 20 PSI MAIN

D.A.. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
2 PIPE COLD T-STAT BRANCH PRESSURE (PSIG) HOT
PE4 PE3 PE2 ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE 2 = PILOT DUTY P.E. W/ 30A
1 3.6 8.3 E = 120V/1PH/60HZ - 2 STAGE MAG. CONTACTOR
DE-ENERGIZING
CONTACTOR

30 AMP 2 2.8 6.6 5 = 120V/1PH/60HZ - 3 STAGE 3 = PILOT DUTY P.E. W/ 50A


CONTACTOR 3 1.9 4.4
K = 277V/1PH/60HZ - 1 STAGE MAG. CONTACTOR
1 5.7 13.2
50 AMP L = 277V/1PH/60HZ - 2 STAGE 4 = PILOT DUTY P.E. W/ 30A
2 2.8 6.6 MERC. CONTACTOR
CONTACTOR Y = 277V/1PH/60HZ - 3 STAGE
3 1.9 4.4
5 = PILOT DUTY P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR


SIZE & TYPE

DOOR INTERLOCK 4.8 11.0

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 5.7 13.2
BLOCK

30 AMP BLOCK
FUSE

2.8 6.6

60 AMP BLOCK 5.7 13.2

1. MAX. K.W. BASED ON 48A, OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.008 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5E060

REV.1 8/5/00 PNEUMATIC


PSFH129
- J129 -

138 YORK INTERNATIONAL


FORM AD1T-SECT J

SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT


P.I., N.C. DAMPER, P.E. FAN START, POS. DAMPER CLOSE OFF, R.A. STAT, 1 PHASE, PILOT DUTY P.E. SWITCH

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V
DISCONNECT SIGNAL TO PE1 ENERGIZES THE FAN & EP SWITCH.
SWITCH SPACE TEMP WARM (STAT OUTPUT LOW). AT A STAT
OUTPUT OF 3 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
FUSING WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
OPTIONAL DISCONNECT SWITCH
ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
AND OR FUSING
PANEL WIRING DIAGRAM ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.

L1 (N) = 120V & 277V AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
TERMINAL 1 2
BLOCK UNOCCUPIED MODE:
BK WH
WHEN SIGNAL TO PE1 FALLS BELOW ITS SETPOINT
IT DE-ENERGIZES THE FAN & EP SWITCH, CAUSING THE
DAMPER TO CLOSE.
BK BK WH

C1-1 STANDARD 1 ST. HEAT ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
G JOB SPECIFICATIONS.
RD RD

C2-1 OPTIONAL 2 ST. HEAT


BN BN

C NO (WHEN REQ.) C3-1 OPTIONAL 3 ST. HEAT


BK
TC C NO BK ST.1
BK BK
PE-1 5 C1
NC
PE-2
NC
ST.2
RD C NO RD
C2
PE-3
NC
ST.3
BN C NO BN
C3
PE-4
NC
BK BL/WH BK
SC FM

BK
EP

PE1
P.E. SWITCH SUPPLIED BY FACTORY
N.C. PNEUMATIC DIAGRAM (SIGNAL BY OTHERS)

ACT. RECOMMENDED FIELD P.E. SWITCH SETTINGS:


(3)C
(1)NC (2)NO
PE-2 = 8 PSI
EP PE-3 = 10 PSI
BAL. TAPS PE-4 = 12 PSI
VEL. CNTRLR
B (RESET BAND=3-8 PSI)
FLOW LO X CONSTANT
M 20 PSI MAIN VOLUME
PROBE HI Y TOTAL AIR
T
COLD AIR HEAT
R.A. STAT
FLOW

AIR
1 PIPE PLENUM AIR
AIR

FLOW
RESTRICTOR
OR OR 20 PSI MAIN

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
R.A. STAT
2 PIPE HOT T-STAT BRANCH PRESSURE (PSIG) COLD
PE4 PE3 PE2 ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE 2 = PILOT DUTY P.E. W/ 30A
1 3.6 8.3 E = 120V/1PH/60HZ - 2 STAGE MAG. CONTACTOR
DE-ENERGIZING
CONTACTOR

30 AMP 2 2.8 6.6 5 = 120V/1PH/60HZ - 3 STAGE 3 = PILOT DUTY P.E. W/ 50A


CONTACTOR 3 1.9 4.4
K = 277V/1PH/60HZ - 1 STAGE MAG. CONTACTOR
1 5.7 13.2
50 AMP L = 277V/1PH/60HZ - 2 STAGE 4 = PILOT DUTY P.E. W/ 30A
2 2.8 6.6 MERC. CONTACTOR
CONTACTOR Y = 277V/1PH/60HZ - 3 STAGE
3 1.9 4.4
5 = PILOT DUTY P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR


SIZE & TYPE

DOOR INTERLOCK 4.8 11.0

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 5.7 13.2
BLOCK

30 AMP BLOCK
FUSE

2.8 6.6

60 AMP BLOCK 5.7 13.2

1. MAX. K.W. BASED ON 48A, OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.008 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5F060

REV.1 8/5/00 PNEUMATIC


PSFH130
- J130 -

YORK INTERNATIONAL 139


SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT
P.I., N.O. DAMPER, P.E. FAN START, POS. DAMPER CLOSE OFF, R.A. STAT, 1 PHASE, PILOT DUTY P.E. SWITCH

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V
DISCONNECT SIGNAL TO PE1 ENERGIZES THE FAN & EP SWITCH.
SWITCH SPACE TEMP WARM (STAT OUTPUT LOW). AT A STAT
OUTPUT OF 3 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
FUSING WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
OPTIONAL DISCONNECT SWITCH
ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
AND OR FUSING
PANEL WIRING DIAGRAM ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.

L1 (N) = 120V & 277V AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
TERMINAL 1 2
BLOCK UNOCCUPIED MODE:
BK WH
WHEN SIGNAL TO PE1 FALLS BELOW ITS SETPOINT
IT DE-ENERGIZES THE FAN & EP SWITCH, CAUSING THE
DAMPER TO CLOSE.
BK BK WH

C1-1 STANDARD 1 ST. HEAT ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
G JOB SPECIFICATIONS.
RD RD

C2-1 OPTIONAL 2 ST. HEAT


BN BN

C NO (WHEN REQ.) C3-1 OPTIONAL 3 ST. HEAT


BK
TC C NO BK ST.1
BK BK
PE-1 5 C1
NC
PE-2
NC
ST.2
RD C NO RD
C2
PE-3
NC
ST.3
BN C NO BN
C3
PE-4
NC
BK BL/WH BK
SC FM

BK
EP

PNEUMATIC DIAGRAM PE1


P.E. SWITCH SUPPLIED BY FACTORY
N.O. (SIGNAL BY OTHERS)
ACT. (3)C RECOMMENDED FIELD P.E. SWITCH SETTINGS:
(1)NC (2)NO
PE-2 = 8 PSI
EP
PE-3 = 10 PSI
BAL. TAPS VEL. CNTRLR PE-4 = 12 PSI
B (RESET BAND=8-13 PSI)
FLOW LO Y
M 20 PSI MAIN
PROBE HI X CONSTANT
T
VOLUME
REV. R.A.. STAT TOTAL AIR
FLOW

RELAY 1 PIPE HEAT


AIR

COLD AIR
AIR
M RESTRICTOR PLENUM AIR
1 FLOW
3 OR OR 20 PSI MAIN

R.A.. STAT
2 PIPE 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE4 PE3 PE2 HOT T-STAT BRANCH PRESSURE (PSIG) COLD
ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE 2 = PILOT DUTY P.E. W/ 30A
1 3.6 8.3 E = 120V/1PH/60HZ - 2 STAGE MAG. CONTACTOR
DE-ENERGIZING
CONTACTOR

30 AMP 2 2.8 6.6 5 = 120V/1PH/60HZ - 3 STAGE 3 = PILOT DUTY P.E. W/ 50A


CONTACTOR 3 1.9 4.4
K = 277V/1PH/60HZ - 1 STAGE MAG. CONTACTOR
1 5.7 13.2
50 AMP L = 277V/1PH/60HZ - 2 STAGE 4 = PILOT DUTY P.E. W/ 30A
2 2.8 6.6 MERC. CONTACTOR
CONTACTOR Y = 277V/1PH/60HZ - 3 STAGE
3 1.9 4.4
5 = PILOT DUTY P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR


SIZE & TYPE

DOOR INTERLOCK 4.8 11.0

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 5.7 13.2
BLOCK

30 AMP BLOCK
FUSE

2.8 6.6

60 AMP BLOCK 5.7 13.2

1. MAX. K.W. BASED ON 48A, OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.016 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5G060

REV.1 8/5/00 PNEUMATIC


PSFH131
- J131 -

140 YORK INTERNATIONAL


FORM AD1T-SECT J

SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT


P.I., N.C. DAMPER, P.E. FAN START, POS. DAMPER CLOSE OFF, D.A. STAT, 1 PHASE, PILOT DUTY P.E. SWITCH

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V
DISCONNECT SIGNAL TO PE1 ENERGIZES THE FAN & EP SWITCH.
SWITCH SPACE TEMP WARM (STAT OUTPUT HI). AT A STAT
OUTPUT OF 13 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
FUSING WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
OPTIONAL DISCONNECT SWITCH
ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
AND OR FUSING
PANEL WIRING DIAGRAM ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.

L1 (N) = 120V & 277V AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
TERMINAL 1 2
BLOCK UNOCCUPIED MODE:
BK WH
WHEN SIGNAL TO PE1 FALLS BELOW ITS SETPOINT
IT DE-ENERGIZES THE FAN & EP SWITCH, CAUSING THE
DAMPER TO CLOSE.
BK BK WH

C1-1 STANDARD 1 ST. HEAT ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
G JOB SPECIFICATIONS.
RD RD

C2-1 OPTIONAL 2 ST. HEAT


BN BN

C NO (WHEN REQ.) C3-1 OPTIONAL 3 ST. HEAT


BK
TC C NO BK ST.1
BK BK
PE-1 5 C1
NC
PE-2
NC
ST.2
RD C NO RD
C2
PE-3
NC
ST.3
BN C NO BN
C3
PE-4
NC
BK BL/WH BK
SC FM

BK
EP

P.E. SWITCH SUPPLIED BY FACTORY


N.C.
PNEUMATIC DIAGRAM PE1
(SIGNAL BY OTHERS)
ACT. RECOMMENDED FIELD P.E. SWITCH SETTINGS:
(3)C
(1)NC (2)NO
PE-2 = 8 PSI
EP PE-3 = 6 PSI
BAL. TAPS VEL. CNTRLR PE-4 = 4 PSI
B (RESET BAND=3-8 PSI)
FLOW LO X CONSTANT
M 20 PSI MAIN
PROBE HI Y VOLUME
T TOTAL AIR
REV. D.A.. STAT HEAT COLD AIR
FLOW

RELAY 1 PIPE AIR


AIR

FLOW PLENUM AIR


M RESTRICTOR
1
3 OR OR 20 PSI MAIN

D.A.. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
2 PIPE COLD T-STAT BRANCH PRESSURE (PSIG) HOT
PE4 PE3 PE2 ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE 2 = PILOT DUTY P.E. W/ 30A
1 3.6 8.3 E = 120V/1PH/60HZ - 2 STAGE MAG. CONTACTOR
DE-ENERGIZING
CONTACTOR

30 AMP 2 2.8 6.6 5 = 120V/1PH/60HZ - 3 STAGE 3 = PILOT DUTY P.E. W/ 50A


CONTACTOR 3 1.9 4.4
K = 277V/1PH/60HZ - 1 STAGE MAG. CONTACTOR
1 5.7 13.2
50 AMP L = 277V/1PH/60HZ - 2 STAGE 4 = PILOT DUTY P.E. W/ 30A
2 2.8 6.6 MERC. CONTACTOR
CONTACTOR Y = 277V/1PH/60HZ - 3 STAGE
3 1.9 4.4
5 = PILOT DUTY P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR


SIZE & TYPE

DOOR INTERLOCK 4.8 11.0

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 5.7 13.2
BLOCK

30 AMP BLOCK
FUSE

2.8 6.6

60 AMP BLOCK 5.7 13.2

1. MAX. K.W. BASED ON 48A, OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.016 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5H060

REV.1 8/5/00 PNEUMATIC


PSFH132
- J132 -

YORK INTERNATIONAL 141


142 YORK INTERNATIONAL
FORM AD1T-SECT J

SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT


P.I., N.C. DAMPER, P.E. FAN START, POS. DAMPER CLOSE OFF, R.A. STAT, 3 PHASE, LOAD BEARING P.E. SWITCH W/ CONT. INTRLK.

SEQUENCE OF OPERATION:
L1 L2 L3
SIGNAL TO PE1 ENERGIZES THE FAN & EP SWITCH.
DISCONNECT
SPACE TEMP WARM (STAT OUTPUT LOW). AT A STAT
SWITCH
OUTPUT OF 3 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
FUSING WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
OPTIONAL DISCONNECT SWITCH ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
PANEL WIRING DIAGRAM AND OR FUSING ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
L1 L2 L3 N AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
TERMINAL 1 2 3 4
BLOCK UNOCCUPIED MODE:
BK WH WHEN SIGNAL TO PE1 FALLS BELOW ITS SETPOINT
BK BL IT DE-ENERGIZES THE FAN & EP SWITCH, CAUSING THE
DAMPER TO CLOSE.
BK STANDARD 1 STAGE HEAT
ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
C1-1 G JOB SPECIFICATIONS.
BK BK

C1-2
BK BK
C NO BK L1 1
TC ST.1 C C1-1
BK BK C NO BK NO BL
PE-1 5 C1 L2 2
RD 3 L3
NC RD
RD
PE-2 PE-3
NC NC C1-2
BK BL/WH BK
SC FM OPTIONAL 2 STAGE HEAT

BK
BK BK
EP L1 1
C1-1
RD
C NO
L2 2
PE1
P.E. SWITCH SUPPLIED BY FACTORY RD

(SIGNAL BY OTHERS) PE-3


NC
BN C NO BN

PE-4
NC
BL BL
L3 3
C1-2

N.C. PNEUMATIC DIAGRAM OPTIONAL 3 STAGE HEAT

ACT. (3)C RECOMMENDED FIELD P.E. SWITCH SETTINGS:


(1)NC (2)NO
EP PE-2 = 8 PSI
PE-3 = 10 PSI
BAL. TAPS VEL. CNTRLR PE-4 = 12 PSI
B (RESET BAND=3-8 PSI)
FLOW LO X
M 20 PSI MAIN CONSTANT
PROBE HI Y
T VOLUME
TOTAL AIR
R.A. STAT
FLOW

COLD AIR HEAT


1 PIPE AIR
AIR

FLOW PLENUM AIR


RESTRICTOR
OR OR 20 PSI MAIN

R.A. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE4 PE3 PE2 2 PIPE HOT COLD
T-STAT BRANCH PRESSURE (PSIG)
ROOM ROOM

HEATER COMPONENTS MAX. KW


3 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-3 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 208 V 480 V P = 208V/3PH/60HZ - 1 STAGE J = LOAD BEARING P.E. W/ 30A
1 10.7 24.9 R = 208V/3PH/60HZ - 2 STAGE MAG. CONTACTOR INTERLOCK
30 AMP CONT.
LOAD BRG. PE

2 4.4 9.1 1 = 208V/3PH/60HZ - 3 STAGE K = LOAD BEARING P.E. W/ 50A


W/ INTRLK

PER STAGE 3 2.9 6.0


U = 480V/3PH/60HZ - 1 STAGE MAG. CONTACTOR INTERLOCK
1 17.2 39.8
50 AMP CONT. W = 480V/3PH/60HZ - 2 STAGE L = LOAD BEARING P.E. W/ 30A
2 4.4 9.1 MERC. CONTACTOR INTERLOCK
PER STAGE 3 = 480V/3PH/60HZ - 3 STAGE
3 2.9 6.0
M = LOAD BEARING P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR INTERLOCK


SIZE & TYPE

DOOR INTERLOCK 14.3 33.2

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 17.2 39.8
BLOCK

30 AMP BLOCK
FUSE

8.6 19.9

60 AMP BLOCK 17.2 39.8

1. MAX. K.W. BASED ON 48A, P.E., OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.008 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5F060

REV.1 8/5/00 PNEUMATIC


PSFH134
- J134 -

YORK INTERNATIONAL 143


SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT
P.I., N.O. DAMPER, P.E. FAN START, POS. DAMPER CLOSE OFF, R.A. STAT, 3 PHASE, LOAD BEARING P.E. SWITCH W/ CONT. INTRLK.

SEQUENCE OF OPERATION:
L1 L2 L3
SIGNAL TO PE1 ENERGIZES THE FAN & EP SWITCH.
DISCONNECT
SPACE TEMP WARM (STAT OUTPUT LOW). AT A STAT
SWITCH
OUTPUT OF 3 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
FUSING WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
OPTIONAL DISCONNECT SWITCH ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
PANEL WIRING DIAGRAM AND OR FUSING ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
L1 L2 L3 N AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
TERMINAL 1 2 3 4
BLOCK UNOCCUPIED MODE:
BK WH WHEN SIGNAL TO PE1 FALLS BELOW ITS SETPOINT
BK BL IT DE-ENERGIZES THE FAN & EP SWITCH, CAUSING THE
DAMPER TO CLOSE.
BK STANDARD 1 STAGE HEAT
ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
C1-1 G JOB SPECIFICATIONS.
BK BK

C1-2
C NO BK BK BK
L1 1
TC ST.1
BK BK C NO BK C NO C1-1 BL
PE-1 5 C1 L2 2
RD 3 L3
NC RD
PE-2 RD
PE-3
NC NC C1-2
BK BL/WH BK
SC FM OPTIONAL 2 STAGE HEAT

BK
EP BK BK
L1 1
C1-1
RD
C NO
L2 2
PE1
P.E. SWITCH SUPPLIED BY FACTORY RD

(SIGNAL BY OTHERS) PE-3


NC
BN C NO BN

PE-4
NC
BL BL
L3 3
N.O.
PNEUMATIC DIAGRAM C1-2
OPTIONAL 3 STAGE HEAT
ACT. (3)C
(1)NC (2)NO RECOMMENDED FIELD P.E. SWITCH SETTINGS:
EP
PE-2 = 8 PSI
BAL. TAPS VEL. CNTRLR PE-3 = 10 PSI
B (RESET BAND=8-13 PSI) PE-4 = 12 PSI
FLOW LO Y
M 20 PSI MAIN
PROBE HI X CONSTANT
T
VOLUME
REV. R.A.. STAT TOTAL AIR
FLOW

RELAY 1 PIPE HEAT


AIR

COLD AIR
AIR
M RESTRICTOR PLENUM AIR
1 FLOW
3 OR OR 20 PSI MAIN

R.A.. STAT
2 PIPE 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE4 PE3 PE2 HOT T-STAT BRANCH PRESSURE (PSIG) COLD
ROOM ROOM

HEATER COMPONENTS MAX. KW


3 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-3 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 208 V 480 V P = 208V/3PH/60HZ - 1 STAGE J = LOAD BEARING P.E. W/ 30A
1 10.7 24.9 R = 208V/3PH/60HZ - 2 STAGE MAG. CONTACTOR INTERLOCK
30 AMP CONT.
LOAD BRG. PE

2 4.4 9.1 1 = 208V/3PH/60HZ - 3 STAGE K = LOAD BEARING P.E. W/ 50A


W/ INTRLK

PER STAGE 3 2.9 6.0


U = 480V/3PH/60HZ - 1 STAGE MAG. CONTACTOR INTERLOCK
1 17.2 39.8
50 AMP CONT. W = 480V/3PH/60HZ - 2 STAGE L = LOAD BEARING P.E. W/ 30A
2 4.4 9.1 MERC. CONTACTOR INTERLOCK
PER STAGE 3 = 480V/3PH/60HZ - 3 STAGE
3 2.9 6.0
M = LOAD BEARING P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR INTERLOCK


SIZE & TYPE

DOOR INTERLOCK 14.3 33.2

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 17.2 39.8
BLOCK

30 AMP BLOCK
FUSE

8.6 19.9

60 AMP BLOCK 17.2 39.8

1. MAX. K.W. BASED ON 48A, P.E., OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.016 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5G060

REV.1 8/5/00 PNEUMATIC


PSFH135
- J135 -

144 YORK INTERNATIONAL


FORM AD1T-SECT J

SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT


P.I., N.C. DAMPER, P.E. FAN START, POS. DAMPER CLOSE OFF, D.A. STAT, 3 PHASE, LOAD BEARING P.E. SWITCH W/ CONT. INTRLK.

SEQUENCE OF OPERATION:
L1 L2 L3
SIGNAL TO PE1 ENERGIZES THE FAN & EP SWITCH.
DISCONNECT
SPACE TEMP WARM (STAT OUTPUT HI). AT A STAT
SWITCH
OUTPUT OF 13 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
FUSING WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
OPTIONAL DISCONNECT SWITCH ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
PANEL WIRING DIAGRAM AND OR FUSING ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
L1 L2 L3 N AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
TERMINAL 1 2 3 4
BLOCK UNOCCUPIED MODE:
BK WH WHEN SIGNAL TO PE1 FALLS BELOW ITS SETPOINT
BK BL IT DE-ENERGIZES THE FAN & EP SWITCH, CAUSING THE
DAMPER TO CLOSE.
BK STANDARD 1 STAGE HEAT
ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
C1-1 G JOB SPECIFICATIONS.
BK BK

C1-2
C NO BK BK BK
L1 1
TC ST.1
BK BK C NO BK C NO C1-1 BL
PE-1 5 C1 L2 2
RD 3 L3
NC
RD RD
PE-2 PE-3
NC NC C1-2
BK BL/WH BK
SC FM OPTIONAL 2 STAGE HEAT

BK
EP BK BK
L1 1
C1-1
RD
C NO
L2 2
PE1
P.E. SWITCH SUPPLIED BY FACTORY RD
(SIGNAL BY OTHERS) PE-3
NC
BN C NO BN

PE-4
NC
BL BL
L3 3
C1-2
N.C.
PNEUMATIC DIAGRAM OPTIONAL 3 STAGE HEAT
ACT. (3)C RECOMMENDED FIELD P.E. SWITCH SETTINGS:
(1)NC (2)NO
EP PE-2 = 8 PSI
BAL. TAPS PE-3 = 6 PSI
VEL. CNTRLR
PE-4 = 4 PSI
B (RESET BAND=3-8 PSI)
FLOW LO X CONSTANT
M 20 PSI MAIN
PROBE HI Y VOLUME
T TOTAL AIR
REV. D.A.. STAT HEAT COLD AIR
FLOW

RELAY 1 PIPE AIR


AIR

FLOW PLENUM AIR


M RESTRICTOR
1
3 OR OR 20 PSI MAIN

D.A.. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
2 PIPE COLD T-STAT BRANCH PRESSURE (PSIG) HOT
PE4 PE3 PE2 ROOM ROOM

HEATER COMPONENTS MAX. KW


3 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-3 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 208 V 480 V P = 208V/3PH/60HZ - 1 STAGE J = LOAD BEARING P.E. W/ 30A
1 10.7 24.9 R = 208V/3PH/60HZ - 2 STAGE MAG. CONTACTOR INTERLOCK
30 AMP CONT.
LOAD BRG. PE

2 4.4 9.1 1 = 208V/3PH/60HZ - 3 STAGE K = LOAD BEARING P.E. W/ 50A


W/ INTRLK

PER STAGE 3 2.9 6.0


U = 480V/3PH/60HZ - 1 STAGE MAG. CONTACTOR INTERLOCK
1 17.2 39.8
50 AMP CONT. W = 480V/3PH/60HZ - 2 STAGE L = LOAD BEARING P.E. W/ 30A
2 4.4 9.1 MERC. CONTACTOR INTERLOCK
PER STAGE 3 = 480V/3PH/60HZ - 3 STAGE
3 2.9 6.0
M = LOAD BEARING P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR INTERLOCK


SIZE & TYPE

DOOR INTERLOCK 14.3 33.2

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 17.2 39.8
BLOCK

30 AMP BLOCK
FUSE

8.6 19.9

60 AMP BLOCK 17.2 39.8

1. MAX. K.W. BASED ON 48A, P.E., OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.016 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5H060

REV.1 8/5/00 PNEUMATIC


PSFH136
- J136 -

YORK INTERNATIONAL 145


SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT
P.I., N.O. DAMPER, P.E. FAN START, POS. DAMPER CLOSE OFF, D.A. STAT, 3 PHASE, PILOT DUTY P.E. SWITCH

SEQUENCE OF OPERATION:
L1 L2 L3
SIGNAL TO PE1 ENERGIZES THE FAN & EP SWITCH.
DISCONNECT
SPACE TEMP WARM (STAT OUTPUT HI). AT A STAT
SWITCH
OUTPUT OF 13 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
FUSING WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
OPTIONAL DISCONNECT SWITCH ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
PANEL WIRING DIAGRAM AND OR FUSING ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
L1 L2 L3 N AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
TERMINAL 1 2 3 4
BLOCK UNOCCUPIED MODE:
BK WH WHEN SIGNAL TO PE1 FALLS BELOW ITS SETPOINT
BK BL IT DE-ENERGIZES THE FAN & EP SWITCH, CAUSING THE
DAMPER TO CLOSE.
BK STANDARD 1 STAGE HEAT
ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
C1-1 G JOB SPECIFICATIONS.
BK BK

C1-2
C NO BK

TC ST.1
BK BK C NO BK
PE-1 5 C1
NC BK BK
PE-2 L1 1
NC C1-1 BL
3 L3
ST.2
RD C NO RD RD RD
C2 L2 2
C2-1
PE-3
NC OPTIONAL 2 STAGE HEAT
ST.3
BN C NO BN
C3
PE-4 BK BK
NC L1 1
BK BL/WH BK C1-1
SC FM RD RD
L2 2
C2-1
BN BN
BK
EP C3-1
BL BL
L3 3
C1-2
P.E. SWITCH SUPPLIED BY FACTORY
PNEUMATIC DIAGRAM PE1
(SIGNAL BY OTHERS) OPTIONAL 3 STAGE HEAT
N.O.
ACT. (3)C RECOMMENDED FIELD P.E. SWITCH SETTINGS:
(1)NC (2)NO
EP PE-2 = 8 PSI
PE-3 = 6 PSI
BAL. TAPS VEL. CNTRLR PE-4 = 4 PSI
B (RESET BAND=8-13 PSI)
FLOW LO Y CONSTANT
M 20 PSI MAIN
PROBE HI X VOLUME
T TOTAL AIR
D.A.. STAT HEAT COLD AIR
FLOW

1 PIPE AIR
AIR

FLOW PLENUM AIR


RESTRICTOR
OR OR 20 PSI MAIN

D.A.. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
2 PIPE COLD T-STAT BRANCH PRESSURE (PSIG) HOT
PE4 PE3 PE2 ROOM ROOM

HEATER COMPONENTS MAX. KW


3 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-3 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 208 V 480 V P = 208V/3PH/60HZ - 1 STAGE 2 = PILOT DUTY P.E. W/ 30A
1 10.7 24.9 R = 208V/3PH/60HZ - 2 STAGE MAG. CONTACTOR
DE-ENERGIZING
CONTACTOR

30 AMP 2 5.3 12.4 1 = 208V/3PH/60HZ - 3 STAGE 3 = PILOT DUTY P.E. W/ 50A


PER STAGE 3 3.5 8.3
U = 480V/3PH/60HZ - 1 STAGE MAG. CONTACTOR
1 17.2 39.8
50 AMP W = 480V/3PH/60HZ - 2 STAGE 4 = PILOT DUTY P.E. W/ 30A
2 8.6 19.9 MERC. CONTACTOR
PER STAGE 3 = 480V/3PH/60HZ - 3 STAGE
3 5.7 13.2
5 = PILOT DUTY P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR


SIZE & TYPE

DOOR INTERLOCK 14.3 33.2

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 17.2 39.8
BLOCK

30 AMP BLOCK 8.6 19.9


FUSE

60 AMP BLOCK 17.2 39.8

1. MAX. K.W. BASED ON 48A, OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.008 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5E060

REV.1 8/5/00 PNEUMATIC


PSFH137
- J137 -

146 YORK INTERNATIONAL


FORM AD1T-SECT J

SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT


P.I., N.C. DAMPER, P.E. FAN START, POS. DAMPER CLOSE OFF, R.A. STAT, 3 PHASE, PILOT DUTY P.E. SWITCH

SEQUENCE OF OPERATION:
L1 L2 L3
SIGNAL TO PE1 ENERGIZES THE FAN & EP SWITCH.
DISCONNECT
SPACE TEMP WARM (STAT OUTPUT LOW). AT A STAT
SWITCH
OUTPUT OF 3 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
FUSING WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
OPTIONAL DISCONNECT SWITCH ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
PANEL WIRING DIAGRAM AND OR FUSING ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
L1 L2 L3 N AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
TERMINAL 1 2 3 4
BLOCK UNOCCUPIED MODE:
BK WH WHEN SIGNAL TO PE1 FALLS BELOW ITS SETPOINT
BK BL IT DE-ENERGIZES THE FAN & EP SWITCH, CAUSING THE
DAMPER TO CLOSE.
BK STANDARD 1 STAGE HEAT
ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
C1-1 G JOB SPECIFICATIONS.
BK BK

C1-2
C NO BK

TC ST.1
BK BK C NO BK
PE-1 5 C1
NC BK BK
PE-2 L1 1
NC C1-1 BL
3 L3
ST.2
RD C NO RD RD RD
C2 L2 2
C2-1
PE-3
NC OPTIONAL 2 STAGE HEAT
ST.3
BN C NO BN
C3
PE-4 BK BK
NC L1 1
BK BL/WH BK C1-1
SC FM RD RD
L2 2
C2-1
BN BN
BK
EP C3-1
BL BL
L3 3
C1-2
PNEUMATIC DIAGRAM PE1
P.E. SWITCH SUPPLIED BY FACTORY
(SIGNAL BY OTHERS) OPTIONAL 3 STAGE HEAT
N.C.
ACT. RECOMMENDED FIELD P.E. SWITCH SETTINGS:
(3)C
(1)NC (2)NO
PE-2 = 8 PSI
EP PE-3 = 10 PSI
BAL. TAPS PE-4 = 12 PSI
VEL. CNTRLR
B (RESET BAND=3-8 PSI)
FLOW LO X CONSTANT
M 20 PSI MAIN VOLUME
PROBE HI Y TOTAL AIR
T
COLD AIR HEAT
R.A. STAT
FLOW

AIR
1 PIPE PLENUM AIR
AIR

FLOW
RESTRICTOR
OR OR 20 PSI MAIN

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
R.A. STAT
2 PIPE HOT T-STAT BRANCH PRESSURE (PSIG) COLD
PE4 PE3 PE2 ROOM ROOM

HEATER COMPONENTS MAX. KW


3 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-3 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 208 V 480 V P = 208V/3PH/60HZ - 1 STAGE 2 = PILOT DUTY P.E. W/ 30A
1 10.7 24.9 R = 208V/3PH/60HZ - 2 STAGE MAG. CONTACTOR
DE-ENERGIZING
CONTACTOR

30 AMP 2 5.3 12.4 1 = 208V/3PH/60HZ - 3 STAGE 3 = PILOT DUTY P.E. W/ 50A


PER STAGE 3 3.5 8.3
U = 480V/3PH/60HZ - 1 STAGE MAG. CONTACTOR
1 17.2 39.8
50 AMP W = 480V/3PH/60HZ - 2 STAGE 4 = PILOT DUTY P.E. W/ 30A
2 8.6 19.9 MERC. CONTACTOR
PER STAGE 3 = 480V/3PH/60HZ - 3 STAGE
3 5.7 13.2
5 = PILOT DUTY P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR


SIZE & TYPE

DOOR INTERLOCK 14.3 33.2

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 17.2 39.8
BLOCK

30 AMP BLOCK 8.6 19.9


FUSE

60 AMP BLOCK 17.2 39.8

1. MAX. K.W. BASED ON 48A, OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.008 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5F060

REV.1 8/5/00 PNEUMATIC


PSFH138
- J138 -

YORK INTERNATIONAL 147


SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT
P.I., N.O. DAMPER, P.E. FAN START, POS. DAMPER CLOSE OFF, R.A. STAT, 3 PHASE, PILOT DUTY P.E. SWITCH

SEQUENCE OF OPERATION:
L1 L2 L3
SIGNAL TO PE1 ENERGIZES THE FAN & EP SWITCH.
DISCONNECT
SPACE TEMP WARM (STAT OUTPUT LOW). AT A STAT
SWITCH
OUTPUT OF 3 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
FUSING WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
OPTIONAL DISCONNECT SWITCH ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
PANEL WIRING DIAGRAM AND OR FUSING ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
L1 L2 L3 N AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
TERMINAL 1 2 3 4
BLOCK UNOCCUPIED MODE:
BK WH WHEN SIGNAL TO PE1 FALLS BELOW ITS SETPOINT
BK BL IT DE-ENERGIZES THE FAN & EP SWITCH, CAUSING THE
DAMPER TO CLOSE.
BK STANDARD 1 STAGE HEAT
ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
C1-1 G JOB SPECIFICATIONS.
BK BK

C1-2
C NO BK

TC ST.1
BK BK C NO BK
PE-1 5 C1
NC BK BK
PE-2 L1 1
NC C1-1 BL
3 L3
ST.2
RD C NO RD RD RD
C2 L2 2
C2-1
PE-3
NC OPTIONAL 2 STAGE HEAT
ST.3
BN C NO BN
C3
PE-4 BK BK
NC L1 1
BK BL/WH BK C1-1
SC FM RD RD
L2 2
C2-1
BN BN
BK
EP C3-1
BL BL
L3 3
C1-2
PNEUMATIC DIAGRAM PE1 P.E. SWITCH SUPPLIED BY FACTORY
OPTIONAL 3 STAGE HEAT
(SIGNAL BY OTHERS)
N.O.
RECOMMENDED FIELD P.E. SWITCH SETTINGS:
ACT. (3)C
(1)NC (2)NO PE-2 = 8 PSI
EP PE-3 = 10 PSI
PE-4 = 12 PSI
BAL. TAPS VEL. CNTRLR
B (RESET BAND=8-13 PSI)
FLOW LO Y
M 20 PSI MAIN CONSTANT
PROBE HI X
T VOLUME
TOTAL AIR
REV. R.A.. STAT
FLOW

RELAY 1 PIPE COLD AIR HEAT


AIR

AIR
M RESTRICTOR FLOW PLENUM AIR
1
3 OR OR 20 PSI MAIN

R.A.. STAT
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
2 PIPE
HOT T-STAT BRANCH PRESSURE (PSIG) COLD
PE4 PE3 PE2 ROOM ROOM

HEATER COMPONENTS MAX. KW


3 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-3 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 208 V 480 V P = 208V/3PH/60HZ - 1 STAGE 2 = PILOT DUTY P.E. W/ 30A
1 10.7 24.9 R = 208V/3PH/60HZ - 2 STAGE MAG. CONTACTOR
DE-ENERGIZING
CONTACTOR

30 AMP 2 5.3 12.4 1 = 208V/3PH/60HZ - 3 STAGE 3 = PILOT DUTY P.E. W/ 50A


PER STAGE 3 3.5 8.3
U = 480V/3PH/60HZ - 1 STAGE MAG. CONTACTOR
1 17.2 39.8
50 AMP W = 480V/3PH/60HZ - 2 STAGE 4 = PILOT DUTY P.E. W/ 30A
2 8.6 19.9 MERC. CONTACTOR
PER STAGE 3 = 480V/3PH/60HZ - 3 STAGE
3 5.7 13.2
5 = PILOT DUTY P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR


SIZE & TYPE

DOOR INTERLOCK 14.3 33.2

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 17.2 39.8
BLOCK

30 AMP BLOCK 8.6 19.9


FUSE

60 AMP BLOCK 17.2 39.8

1. MAX. K.W. BASED ON 48A, OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.016 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5G060

REV.1 8/5/00 PNEUMATIC


PSFH139
- J139 -

148 YORK INTERNATIONAL


FORM AD1T-SECT J

SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT


P.I., N.C. DAMPER, P.E. FAN START, POS. DAMPER CLOSE OFF, D.A. STAT, 3 PHASE, PILOT DUTY P.E. SWITCH

SEQUENCE OF OPERATION:
L1 L2 L3
SIGNAL TO PE1 ENERGIZES THE FAN & EP SWITCH.
DISCONNECT
SPACE TEMP WARM (STAT OUTPUT HI). AT A STAT
SWITCH
OUTPUT OF 13 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
FUSING WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
OPTIONAL DISCONNECT SWITCH ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
PANEL WIRING DIAGRAM AND OR FUSING ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
L1 L2 L3 N AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
TERMINAL 1 2 3 4
BLOCK UNOCCUPIED MODE:
BK WH WHEN SIGNAL TO PE1 FALLS BELOW ITS SETPOINT
BK BL IT DE-ENERGIZES THE FAN & EP SWITCH, CAUSING THE
DAMPER TO CLOSE.
BK STANDARD 1 STAGE HEAT
ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
C1-1 G JOB SPECIFICATIONS.
BK BK

C1-2
C NO BK

TC ST.1
BK BK C NO BK
PE-1 5 C1
NC BK BK
PE-2 L1 1
NC C1-1 BL
3 L3
ST.2
RD C NO RD RD RD
C2 L2 2
C2-1
PE-3
NC OPTIONAL 2 STAGE HEAT
ST.3
BN C NO BN
C3
PE-4 BK BK
NC L1 1
BK BL/WH BK C1-1
SC FM RD RD
L2 2
C2-1
BN BN
BK
EP C3-1
BL BL
L3 3
C1-2
P.E. SWITCH SUPPLIED BY FACTORY
PNEUMATIC DIAGRAM PE1
(SIGNAL BY OTHERS) OPTIONAL 3 STAGE HEAT
N.C.
ACT. RECOMMENDED FIELD P.E. SWITCH SETTINGS:
(3)C
(1)NC (2)NO
PE-2 = 8 PSI
EP PE-3 = 6 PSI
BAL. TAPS VEL. CNTRLR PE-4 = 4 PSI
B (RESET BAND=3-8 PSI)
FLOW LO X CONSTANT
M 20 PSI MAIN
PROBE HI Y VOLUME
T TOTAL AIR
REV. D.A.. STAT HEAT COLD AIR
FLOW

RELAY 1 PIPE AIR


AIR

FLOW PLENUM AIR


M RESTRICTOR
1
3 OR OR 20 PSI MAIN

D.A.. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
2 PIPE COLD T-STAT BRANCH PRESSURE (PSIG) HOT
PE4 PE3 PE2 ROOM ROOM

HEATER COMPONENTS MAX. KW


3 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-3 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 208 V 480 V P = 208V/3PH/60HZ - 1 STAGE 2 = PILOT DUTY P.E. W/ 30A
1 10.7 24.9 R = 208V/3PH/60HZ - 2 STAGE MAG. CONTACTOR
DE-ENERGIZING
CONTACTOR

30 AMP 2 5.3 12.4 1 = 208V/3PH/60HZ - 3 STAGE 3 = PILOT DUTY P.E. W/ 50A


PER STAGE 3 3.5 8.3
U = 480V/3PH/60HZ - 1 STAGE MAG. CONTACTOR
1 17.2 39.8
50 AMP W = 480V/3PH/60HZ - 2 STAGE 4 = PILOT DUTY P.E. W/ 30A
2 8.6 19.9 MERC. CONTACTOR
PER STAGE 3 = 480V/3PH/60HZ - 3 STAGE
3 5.7 13.2
5 = PILOT DUTY P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR


SIZE & TYPE

DOOR INTERLOCK 14.3 33.2

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 17.2 39.8
BLOCK

30 AMP BLOCK 8.6 19.9


FUSE

60 AMP BLOCK 17.2 39.8

1. MAX. K.W. BASED ON 48A, OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.016 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5H060

REV.1 8/5/00 PNEUMATIC


PSFH140
- J140 -

YORK INTERNATIONAL 149


SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT
P.I., N.O. DAMPER, P.E. FAN START, UNOCCUPIED MODE, POS. DAMPER CLOSE OFF, D.A. STAT, 1 PHASE, LOAD BEARING P.E. SWITCH

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V OCCUPIED MODE:
DISCONNECT SIGNAL TO PE1 ENERGIZES THE FAN.
SWITCH SPACE TEMP WARM (STAT OUTPUT HI). AT A STAT
OUTPUT OF 13 PSI THE VEL. CNTRLR WILL BE CONTROLLING
FUSING AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
OPTIONAL DISCONNECT SWITCH CONTROLLING AT ITS MINIMUM.
AND OR FUSING ON A FURTHER DROP IN SPACE TEMP., PE3 WILL CLOSE
PANEL WIRING DIAGRAM ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.

L1 (N) = 120V & 277V AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
TERMINAL 1 2 UNOCCUPIED MODE:
BLOCK
BK WH WHEN THE PRESSURE APPLIED TO PE1 (SET AND CONTROLLED
BY OTHERS) IS DROPPED BELOW ITS SETPOINT IT MAKES
C NO BK TO NC CONTACT ENABLING PE2, TURNING OFF FAN AND
C DEENERGIZING EP CAUSING THE DAMPER TO CLOSE.
BK NO BK WH G
PE-1 5 AS TEMP DROPS, STAT OUTPUT DROPS, STARTING
NC
STANDARD 1 FAN WHEN PRESSURE DROPS BELOW PE2 SETPOINT.
PE-3
C NO NC STAGE HEAT
RD RD C NO RD ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
PE-2
NC JOB SPECIFICATIONS.
PE-4 OPTIONAL 2
NC STAGE HEAT ALL P.E. SWITCHS MUST BE SET IN THE FIELD PER JOB
BN C NO BN REQUIREMENTS.

PE-5 OPTIONAL 3
NC STAGE HEAT

BK BL/WH BK
SC FM

EP

PE1
P.E. SWITCH SUPPLIED BY FACTORY
(SIGNAL BY OTHERS)

N.O. PNEUMATIC DIAGRAM


RECOMMENDED FIELD P.E. SWITCH SETTINGS:
ACT. 3(C)
(NC)1 2(NO) PE-2 = 8 PSI
EP PE-3 = 8 PSI
PE-4 = 6 PSI
BAL. TAPS VEL. CNTRLR PE-5 = 4 PSI
B (RESET BAND=8-13 PSI)
FLOW LO Y CONSTANT
M 20 PSI MAIN
PROBE HI X VOLUME
T TOTAL AIR
D.A.. STAT HEAT COLD AIR
FLOW

1 PIPE AIR (UNOCCUPIED)


AIR

FLOW PLENUM AIR


FAN STARTS
RESTRICTOR
OR OR (FIELD CALIB.)
20 PSI MAIN

D.A.. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE5 PE4 PE3 PE2 2 PIPE COLD T-STAT BRANCH PRESSURE (PSIG) HOT
ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE 1 = LOAD BEARING P.E.
SWITCH

1 2.8 6.7 E = 120V/1PH/60HZ - 2 STAGE


LOAD BEARING
P.E.

PER STAGE 2 1.4 3.3 5 = 120V/1PH/60HZ - 3 STAGE


3 0.9 2.2
K = 277V/1PH/60HZ - 1 STAGE
DISCONNECT

L = 277V/1PH/60HZ - 2 STAGE
SIZE & TYPE

DNF-40 2.8 6.7 Y = 277V/1PH/60HZ - 3 STAGE


DOOR INTERLOCK
BLOCK
FUSE

30 AMP BLOCK 2.8 6.7

1. MAX. K.W. BASED ON P.E. MAX LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.008 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5E080

REV.1 8/5/00 PNEUMATIC


PSFH141
- J141 -

150 YORK INTERNATIONAL


FORM AD1T-SECT J

SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT


P.I., N.C. DAMPER, P.E. FAN START, UNOCCUPIED MODE, POS. DAMPER CLOSE OFF, R.A. STAT, 1 PHASE, LOAD BEARING P.E. SWITCH

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V OCCUPIED MODE:
DISCONNECT SIGNAL TO PE1 ENERGIZES THE FAN.
SWITCH SPACE TEMP WARM (STAT OUTPUT LOW). AT A STAT
OUTPUT OF 3 PSI THE VEL. CNTRLR WILL BE CONTROLLING
FUSING AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
OPTIONAL DISCONNECT SWITCH CONTROLLING AT ITS MINIMUM.
AND OR FUSING ON A FURTHER DROP IN SPACE TEMP., PE3 WILL CLOSE
PANEL WIRING DIAGRAM ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.

L1 (N) = 120V & 277V AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
TERMINAL 1 2 UNOCCUPIED MODE:
BLOCK
BK WH WHEN THE PRESSURE APPLIED TO PE1 (SET AND CONTROLLED
BY OTHERS) IS DROPPED BELOW ITS SETPOINT IT MAKES
C NO BK TO NC CONTACT ENABLING PE2, TURNING OFF FAN AND
C DEENERGIZING EP CAUSING THE DAMPER TO CLOSE.
BK NO BK WH G
PE-1 5 AS TEMP DROPS, STAT OUTPUT DROPS, STARTING
NC
STANDARD 1 FAN WHEN PRESSURE DROPS BELOW PE2 SETPOINT.
PE-3
C NO NC STAGE HEAT
RD
RD C NO RD ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
PE-2
NC JOB SPECIFICATIONS.
PE-4 OPTIONAL 2
NC STAGE HEAT ALL P.E. SWITCHS MUST BE SET IN THE FIELD PER JOB
BN C NO BN REQUIREMENTS.

PE-5 OPTIONAL 3
NC STAGE HEAT

BK BL/WH BK
SC FM

EP

PE1
P.E. SWITCH SUPPLIED BY FACTORY
(SIGNAL BY OTHERS)

N.C. PNEUMATIC DIAGRAM RECOMMENDED FIELD P.E. SWITCH SETTINGS:


ACT. 3(C) PE-2 = 8 PSI
(NC)1 2(NO) PE-3 = 8 PSI
EP PE-4 = 10 PSI
PE-5 = 12 PSI
BAL. TAPS VEL. CNTRLR
B (RESET BAND=3-8 PSI) CONSTANT
FLOW LO X
M 20 PSI MAIN VOLUME
PROBE HI Y TOTAL AIR
T
COLD AIR HEAT
R.A. STAT AIR
FLOW

(UNOCCUPIED)
1 PIPE FLOW PLENUM AIR
AIR

FAN STARTS
RESTRICTOR (FIELD CALIB.)
OR OR 20 PSI MAIN

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
R.A. STAT HOT T-STAT BRANCH PRESSURE (PSIG) COLD
PE5 PE4 PE3 PE2 2 PIPE ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE 1 = LOAD BEARING P.E.
SWITCH

1 2.8 6.7 E = 120V/1PH/60HZ - 2 STAGE


LOAD BEARING
P.E.

PER STAGE 2 1.4 3.3 5 = 120V/1PH/60HZ - 3 STAGE


3 0.9 2.2
K = 277V/1PH/60HZ - 1 STAGE
DISCONNECT

L = 277V/1PH/60HZ - 2 STAGE
SIZE & TYPE

DNF-40 2.8 6.7 Y = 277V/1PH/60HZ - 3 STAGE


DOOR INTERLOCK
BLOCK
FUSE

30 AMP BLOCK 2.8 6.7

1. MAX. K.W. BASED ON P.E. MAX LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.008 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5F080

REV.1 8/5/00 PNEUMATIC


PSFH142
- J142 -

YORK INTERNATIONAL 151


SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT
P.I., N.O. DAMPER, P.E. FAN START, UNOCCUPIED MODE, POS. DAMPER CLOSE OFF, R.A. STAT, 1 PHASE, LOAD BEARING P.E. SWITCH

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V OCCUPIED MODE:
DISCONNECT SIGNAL TO PE1 ENERGIZES THE FAN.
SWITCH SPACE TEMP WARM (STAT OUTPUT LOW). AT A STAT
OUTPUT OF 3 PSI THE VEL. CNTRLR WILL BE CONTROLLING
FUSING AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
OPTIONAL DISCONNECT SWITCH CONTROLLING AT ITS MINIMUM.
AND OR FUSING ON A FURTHER DROP IN SPACE TEMP., PE3 WILL CLOSE
PANEL WIRING DIAGRAM ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.

L1 (N) = 120V & 277V AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
TERMINAL 1 2 UNOCCUPIED MODE:
BLOCK
BK WH WHEN THE PRESSURE APPLIED TO PE1 (SET AND CONTROLLED
BY OTHERS) IS DROPPED BELOW ITS SETPOINT IT MAKES
C NO BK TO NC CONTACT ENABLING PE2, TURNING OFF FAN AND
C DEENERGIZING EP CAUSING THE DAMPER TO CLOSE.
BK NO BK WH G
PE-1 5 AS TEMP DROPS, STAT OUTPUT DROPS, STARTING
NC
STANDARD 1 FAN WHEN PRESSURE DROPS BELOW PE2 SETPOINT.
PE-3
C NO NC STAGE HEAT
RD
RD C NO RD ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
PE-2
NC JOB SPECIFICATIONS.
PE-4 OPTIONAL 2
NC STAGE HEAT ALL P.E. SWITCHS MUST BE SET IN THE FIELD PER JOB
BN C NO BN REQUIREMENTS.

PE-5 OPTIONAL 3
NC STAGE HEAT

BK BL/WH BK
SC FM

EP

PE1
P.E. SWITCH SUPPLIED BY FACTORY
(SIGNAL BY OTHERS)

N.O.
PNEUMATIC DIAGRAM
RECOMMENDED FIELD P.E. SWITCH SETTINGS:
ACT. 3(C)
(NC)1 2(NO) PE-2 = 8 PSI
EP PE-3 = 8 PSI
PE-4 = 10 PSI
BAL. TAPS VEL. CNTRLR PE-5 = 12 PSI
B (RESET BAND=8-13 PSI)
FLOW LO Y
M 20 PSI MAIN CONSTANT
PROBE HI X
T VOLUME
TOTAL AIR
REV. R.A.. STAT HEAT
FLOW

COLD AIR
RELAY 1 PIPE AIR
AIR

(UNOCCUPIED)
FLOW PLENUM AIR
M RESTRICTOR FAN STARTS
1 (FIELD CALIB.)
3 OR OR 20 PSI MAIN

R.A.. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
2 PIPE HOT T-STAT BRANCH PRESSURE (PSIG) COLD
PE5 PE4 PE3 PE2
ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE 1 = LOAD BEARING P.E.
SWITCH

1 2.8 6.7 E = 120V/1PH/60HZ - 2 STAGE


LOAD BEARING
P.E.

PER STAGE 2 1.4 3.3 5 = 120V/1PH/60HZ - 3 STAGE


3 0.9 2.2
K = 277V/1PH/60HZ - 1 STAGE
DISCONNECT

L = 277V/1PH/60HZ - 2 STAGE
SIZE & TYPE

DNF-40 2.8 6.7 Y = 277V/1PH/60HZ - 3 STAGE


DOOR INTERLOCK
BLOCK
FUSE

30 AMP BLOCK 2.8 6.7

1. MAX. K.W. BASED ON P.E. MAX LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.016 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5G080

REV.1 8/5/00 PNEUMATIC


PSFH143
- J143 -

152 YORK INTERNATIONAL


FORM AD1T-SECT J

SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT


P.I., N.C. DAMPER, P.E. FAN START, UNOCCUPIED MODE, POS. DAMPER CLOSE OFF, D.A. STAT, 1 PHASE, LOAD BEARING P.E. SWITCH

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V OCCUPIED MODE:
DISCONNECT SIGNAL TO PE1 ENERGIZES THE FAN.
SWITCH SPACE TEMP WARM (STAT OUTPUT HI). AT A STAT
OUTPUT OF 13 PSI THE VEL. CNTRLR WILL BE CONTROLLING
FUSING AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
OPTIONAL DISCONNECT SWITCH CONTROLLING AT ITS MINIMUM.
AND OR FUSING ON A FURTHER DROP IN SPACE TEMP., PE3 WILL CLOSE
PANEL WIRING DIAGRAM ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.

L1 (N) = 120V & 277V AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
TERMINAL 1 2 UNOCCUPIED MODE:
BLOCK
BK WH WHEN THE PRESSURE APPLIED TO PE1 (SET AND CONTROLLED
BY OTHERS) IS DROPPED BELOW ITS SETPOINT IT MAKES
C NO BK TO NC CONTACT ENABLING PE2, TURNING OFF FAN AND
C DEENERGIZING EP CAUSING THE DAMPER TO CLOSE.
BK NO BK WH G
PE-1 5 AS TEMP DROPS, STAT OUTPUT DROPS, STARTING
NC
STANDARD 1 FAN WHEN PRESSURE DROPS BELOW PE2 SETPOINT.
PE-3
C NO NC STAGE HEAT
RD RD C NO RD ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
PE-2
NC JOB SPECIFICATIONS.
PE-4 OPTIONAL 2
NC STAGE HEAT ALL P.E. SWITCHS MUST BE SET IN THE FIELD PER JOB
BN C NO BN REQUIREMENTS.

PE-5 OPTIONAL 3
NC STAGE HEAT

BK BL/WH BK
SC FM

EP

PE1
P.E. SWITCH SUPPLIED BY FACTORY
(SIGNAL BY OTHERS)

N.C.
PNEUMATIC DIAGRAM
RECOMMENDED FIELD P.E. SWITCH SETTINGS:
ACT. 3(C)
(NC)1 2(NO) PE-2 = 8 PSI
EP PE-3 = 8 PSI
PE-4 = 6 PSI
BAL. TAPS VEL. CNTRLR PE-5 = 4 PSI
B (RESET BAND=3-8 PSI)
FLOW LO X CONSTANT
M 20 PSI MAIN
PROBE HI Y VOLUME
T TOTAL AIR
REV. D.A.. STAT HEAT COLD AIR
FLOW

RELAY 1 PIPE AIR (UNOCCUPIED)


AIR

FLOW PLENUM AIR


M FAN STARTS
1 RESTRICTOR
3 OR OR (FIELD CALIB.)
20 PSI MAIN

D.A.. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
2 PIPE COLD T-STAT BRANCH PRESSURE (PSIG) HOT
PE5 PE4 PE3 PE2 ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE 1 = LOAD BEARING P.E.
SWITCH

1 2.8 6.7 E = 120V/1PH/60HZ - 2 STAGE


LOAD BEARING
P.E.

PER STAGE 2 1.4 3.3 5 = 120V/1PH/60HZ - 3 STAGE


3 0.9 2.2
K = 277V/1PH/60HZ - 1 STAGE
DISCONNECT

L = 277V/1PH/60HZ - 2 STAGE
SIZE & TYPE

DNF-40 2.8 6.7 Y = 277V/1PH/60HZ - 3 STAGE


DOOR INTERLOCK
BLOCK
FUSE

30 AMP BLOCK 2.8 6.7

1. MAX. K.W. BASED ON P.E. MAX LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.016 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5H080

REV.1 8/5/00 PNEUMATIC


PSFH144
- J144 -

YORK INTERNATIONAL 153


SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT
P.I., N.O. DAMPER, P.E. FAN START, UNOCCUPIED MODE, POS. DAMPER CLOSE OFF, D.A. STAT, 1 PHASE, LOAD BEARING P.E. SWITCH W/ CONT. INTRLK.

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V OCCUPIED MODE:
DISCONNECT SIGNAL TO PE1 ENERGIZES THE FAN.
SWITCH SPACE TEMP WARM (STAT OUTPUT HI). AT A STAT
OUTPUT OF 13 PSI THE VEL. CNTRLR WILL BE CONTROLLING
FUSING AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
OPTIONAL DISCONNECT SWITCH CONTROLLING AT ITS MINIMUM.
AND OR FUSING ON A FURTHER DROP IN SPACE TEMP., PE3 WILL CLOSE
PANEL WIRING DIAGRAM ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
L1 (N) = 120V & 277V
TERMINAL AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
1 2
BLOCK UNOCCUPIED MODE:
BK WH
WHEN THE PRESSURE APPLIED TO PE1 (SET AND CONTROLLED
BY OTHERS) IS DROPPED BELOW ITS SETPOINT IT MAKES
BK BK WH
TO NC CONTACT ENABLING PE2, TURNING OFF FAN AND
C1-1 STANDARD 1 DEENERGIZING EP CAUSING THE DAMPER TO CLOSE.
G AS TEMP DROPS, STAT OUTPUT DROPS, STARTING
STAGE HEAT
FAN WHEN PRESSURE DROPS BELOW PE2 SETPOINT.
RD C NO RD

PE-4 OPTIONAL 2 ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY


NC STAGE HEAT
JOB SPECIFICATIONS.
BN C NO BN
ALL P.E. SWITCHS MUST BE SET IN THE FIELD PER JOB
PE-5 OPTIONAL 3 REQUIREMENTS.
C NO BK NC STAGE HEAT
(WHEN REQ.)
BK
TC BK C NO BK
PE-1 5 C1
NC
C PE-3
NO NC
RD BK BL/WH BK
PE-2 SC FM
NC

BK
EP

PE1
P.E. SWITCH SUPPLIED BY FACTORY
(SIGNAL BY OTHERS)

N.O. PNEUMATIC DIAGRAM


RECOMMENDED FIELD P.E. SWITCH SETTINGS:
ACT. 3(C)
(NC)1 2(NO) PE-2 = 8 PSI
EP PE-3 = 8 PSI
PE-4 = 6 PSI
BAL. TAPS VEL. CNTRLR PE-5 = 4 PSI
B (RESET BAND=8-13 PSI)
FLOW LO Y CONSTANT
M 20 PSI MAIN
PROBE HI X VOLUME
T TOTAL AIR
D.A.. STAT HEAT COLD AIR
FLOW

1 PIPE AIR (UNOCCUPIED)


AIR

FLOW PLENUM AIR


FAN STARTS
RESTRICTOR
OR OR (FIELD CALIB.)
20 PSI MAIN

D.A.. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE5 PE4 PE3 PE2 2 PIPE COLD T-STAT BRANCH PRESSURE (PSIG) HOT
ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE J = LOAD BEARING P.E. W/ 30A
1 3.6 8.3 E = 120V/1PH/60HZ - 2 STAGE MAG. CONTACTOR INTERLOCK
30 AMP CONT.
LOAD BRG. PE

2 1.8 4.1 5 = 120V/1PH/60HZ - 3 STAGE K = LOAD BEARING P.E. W/ 50A


W/ INTRLK

PER STAGE 3 1.2 2.7


K = 277V/1PH/60HZ - 1 STAGE MAG. CONTACTOR INTERLOCK
1 5.7 13.2
50 AMP CONT. L = 277V/1PH/60HZ - 2 STAGE L = LOAD BEARING P.E. W/ 30A
2 2.8 6.6 MERC. CONTACTOR INTERLOCK
PER STAGE Y = 277V/1PH/60HZ - 3 STAGE
3 1.9 4.4
M = LOAD BEARING P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR INTERLOCK


SIZE & TYPE

DOOR INTERLOCK 4.8 11.0

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 5.7 13.2
BLOCK

30 AMP BLOCK
FUSE

2.8 6.6

60 AMP BLOCK 5.7 13.2

1. MAX. K.W. BASED ON 48A, P.E., OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.008 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5E080

REV.1 8/5/00 PNEUMATIC


PSFH145
- J145 -

154 YORK INTERNATIONAL


FORM AD1T-SECT J

SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT


P.I., N.C. DAMPER, P.E. FAN START, UNOCCUPIED MODE, POS. DAMPER CLOSE OFF, R.A. STAT, 1 PHASE, LOAD BEARING P.E. SWITCH W/ CONT. INTRLK.

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V OCCUPIED MODE:
DISCONNECT SIGNAL TO PE1 ENERGIZES THE FAN.
SWITCH SPACE TEMP WARM (STAT OUTPUT LOW). AT A STAT
OUTPUT OF 3 PSI THE VEL. CNTRLR WILL BE CONTROLLING
FUSING AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
OPTIONAL DISCONNECT SWITCH CONTROLLING AT ITS MINIMUM.
AND OR FUSING ON A FURTHER DROP IN SPACE TEMP., PE3 WILL CLOSE
PANEL WIRING DIAGRAM ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
L1 (N) = 120V & 277V
TERMINAL AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
1 2
BLOCK UNOCCUPIED MODE:
BK WH
WHEN THE PRESSURE APPLIED TO PE1 (SET AND CONTROLLED
BY OTHERS) IS DROPPED BELOW ITS SETPOINT IT MAKES
BK BK WH
TO NC CONTACT ENABLING PE2, TURNING OFF FAN AND
C1-1 STANDARD 1 DEENERGIZING EP CAUSING THE DAMPER TO CLOSE.
G AS TEMP DROPS, STAT OUTPUT DROPS, STARTING
STAGE HEAT
FAN WHEN PRESSURE DROPS BELOW PE2 SETPOINT.
RD C NO RD

PE-4 OPTIONAL 2 ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY


NC STAGE HEAT
JOB SPECIFICATIONS.
BN C NO BN
ALL P.E. SWITCHS MUST BE SET IN THE FIELD PER JOB
PE-5 OPTIONAL 3 REQUIREMENTS.
C NO BK NC STAGE HEAT
(WHEN REQ.)
BK
TC BK C NO BK
PE-1 5 C1
NC
C PE-3
NO NC
RD BK BL/WH BK
PE-2 SC FM
NC

BK
EP

PE1
P.E. SWITCH SUPPLIED BY FACTORY
(SIGNAL BY OTHERS)

N.C. PNEUMATIC DIAGRAM RECOMMENDED FIELD P.E. SWITCH SETTINGS:


ACT. 3(C) PE-2 = 8 PSI
(NC)1 2(NO) PE-3 = 8 PSI
EP PE-4 = 10 PSI
PE-5 = 12 PSI
BAL. TAPS VEL. CNTRLR
B (RESET BAND=3-8 PSI) CONSTANT
FLOW LO X
M 20 PSI MAIN VOLUME
PROBE HI Y TOTAL AIR
T
COLD AIR HEAT
R.A. STAT AIR
FLOW

(UNOCCUPIED)
1 PIPE FLOW PLENUM AIR
AIR

FAN STARTS
RESTRICTOR (FIELD CALIB.)
OR OR 20 PSI MAIN

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
R.A. STAT HOT T-STAT BRANCH PRESSURE (PSIG) COLD
PE5 PE4 PE3 PE2 2 PIPE ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE J = LOAD BEARING P.E. W/ 30A
1 3.6 8.3 E = 120V/1PH/60HZ - 2 STAGE MAG. CONTACTOR INTERLOCK
30 AMP CONT.
LOAD BRG. PE

2 1.8 4.1 5 = 120V/1PH/60HZ - 3 STAGE K = LOAD BEARING P.E. W/ 50A


W/ INTRLK

PER STAGE 3 1.2 2.7


K = 277V/1PH/60HZ - 1 STAGE MAG. CONTACTOR INTERLOCK
1 5.7 13.2
50 AMP CONT. L = 277V/1PH/60HZ - 2 STAGE L = LOAD BEARING P.E. W/ 30A
2 2.8 6.6 MERC. CONTACTOR INTERLOCK
PER STAGE Y = 277V/1PH/60HZ - 3 STAGE
3 1.9 4.4
M = LOAD BEARING P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR INTERLOCK


SIZE & TYPE

DOOR INTERLOCK 4.8 11.0

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 5.7 13.2
BLOCK

30 AMP BLOCK
FUSE

2.8 6.6

60 AMP BLOCK 5.7 13.2

1. MAX. K.W. BASED ON 48A, P.E., OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.008 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5F080

REV.1 8/5/00 PNEUMATIC


PSFH146
- J146 -

YORK INTERNATIONAL 155


SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT
P.I., N.O. DAMPER, P.E. FAN START, UNOCCUPIED MODE, POS. DAMPER CLOSE OFF, R.A. STAT, 1 PHASE, LOAD BEARING P.E. SWITCH W/ CONT. INTRLK.

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V OCCUPIED MODE:
DISCONNECT SIGNAL TO PE1 ENERGIZES THE FAN.
SWITCH SPACE TEMP WARM (STAT OUTPUT LOW). AT A STAT
OUTPUT OF 3 PSI THE VEL. CNTRLR WILL BE CONTROLLING
FUSING AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
OPTIONAL DISCONNECT SWITCH CONTROLLING AT ITS MINIMUM.
AND OR FUSING ON A FURTHER DROP IN SPACE TEMP., PE3 WILL CLOSE
PANEL WIRING DIAGRAM ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
L1 (N) = 120V & 277V
TERMINAL AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
1 2
BLOCK UNOCCUPIED MODE:
BK WH
WHEN THE PRESSURE APPLIED TO PE1 (SET AND CONTROLLED
BY OTHERS) IS DROPPED BELOW ITS SETPOINT IT MAKES
BK BK WH
TO NC CONTACT ENABLING PE2, TURNING OFF FAN AND
C1-1 STANDARD 1 DEENERGIZING EP CAUSING THE DAMPER TO CLOSE.
G AS TEMP DROPS, STAT OUTPUT DROPS, STARTING
STAGE HEAT
FAN WHEN PRESSURE DROPS BELOW PE2 SETPOINT.
RD C NO RD

PE-4 OPTIONAL 2 ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY


NC STAGE HEAT
JOB SPECIFICATIONS.
BN C NO BN
ALL P.E. SWITCHS MUST BE SET IN THE FIELD PER JOB
PE-5 OPTIONAL 3 REQUIREMENTS.
C NO BK NC STAGE HEAT
(WHEN REQ.)
BK
TC BK C NO BK
PE-1 5 C1
NC
C PE-3
NO NC
RD BK BL/WH BK
PE-2 SC FM
NC

BK
EP

PE1
P.E. SWITCH SUPPLIED BY FACTORY
(SIGNAL BY OTHERS)

N.0. PNEUMATIC DIAGRAM RECOMMENDED FIELD P.E. SWITCH SETTINGS:


ACT. 3(C) PE-2 = 8 PSI
(NC)1 2(NO) PE-3 = 8 PSI
EP PE-4 = 10 PSI
PE-5 = 12 PSI
BAL. TAPS VEL. CNTRLR
B (RESET BAND=8-13 PSI) CONSTANT
FLOW LO Y
M 20 PSI MAIN VOLUME
PROBE HI X TOTAL AIR
T
COLD AIR HEAT
REV. R.A. STAT AIR
FLOW

(UNOCCUPIED)
RELAY 1 PIPE FLOW PLENUM AIR
AIR

FAN STARTS
M RESTRICTOR (FIELD CALIB.)
1
3 OR OR 20 PSI MAIN

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
R.A. STAT HOT T-STAT BRANCH PRESSURE (PSIG) COLD
PE5 PE4 PE3 PE2 2 PIPE ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE J = LOAD BEARING P.E. W/ 30A
1 3.6 8.3 E = 120V/1PH/60HZ - 2 STAGE MAG. CONTACTOR INTERLOCK
30 AMP CONT.
LOAD BRG. PE

2 1.8 4.1 5 = 120V/1PH/60HZ - 3 STAGE K = LOAD BEARING P.E. W/ 50A


W/ INTRLK

PER STAGE 3 1.2 2.7


K = 277V/1PH/60HZ - 1 STAGE MAG. CONTACTOR INTERLOCK
1 5.7 13.2
50 AMP CONT. L = 277V/1PH/60HZ - 2 STAGE L = LOAD BEARING P.E. W/ 30A
2 2.8 6.6 MERC. CONTACTOR INTERLOCK
PER STAGE Y = 277V/1PH/60HZ - 3 STAGE
3 1.9 4.4
M = LOAD BEARING P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR INTERLOCK


SIZE & TYPE

DOOR INTERLOCK 4.8 11.0

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 5.7 13.2
BLOCK

30 AMP BLOCK
FUSE

2.8 6.6

60 AMP BLOCK 5.7 13.2

1. MAX. K.W. BASED ON 48A, P.E., OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.008 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5G080

REV.1 8/5/00 PNEUMATIC


PSFH147
- J147 -

156 YORK INTERNATIONAL


FORM AD1T-SECT J

SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT


P.I., N.C. DAMPER, P.E. FAN START, UNOCCUPIED MODE, POS. DAMPER CLOSE OFF, D.A. STAT, 1 PHASE, LOAD BEARING P.E. SWITCH W/ CONT. INTRLK.

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V OCCUPIED MODE:
DISCONNECT SIGNAL TO PE1 ENERGIZES THE FAN.
SWITCH SPACE TEMP WARM (STAT OUTPUT HI). AT A STAT
OUTPUT OF 13 PSI THE VEL. CNTRLR WILL BE CONTROLLING
FUSING AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
OPTIONAL DISCONNECT SWITCH CONTROLLING AT ITS MINIMUM.
AND OR FUSING ON A FURTHER DROP IN SPACE TEMP., PE3 WILL CLOSE
PANEL WIRING DIAGRAM ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
L1 (N) = 120V & 277V
TERMINAL AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
1 2
BLOCK UNOCCUPIED MODE:
BK WH
WHEN THE PRESSURE APPLIED TO PE1 (SET AND CONTROLLED
BY OTHERS) IS DROPPED BELOW ITS SETPOINT IT MAKES
BK BK WH
TO NC CONTACT ENABLING PE2, TURNING OFF FAN AND
C1-1 STANDARD 1 DEENERGIZING EP CAUSING THE DAMPER TO CLOSE.
G AS TEMP DROPS, STAT OUTPUT DROPS, STARTING
STAGE HEAT
FAN WHEN PRESSURE DROPS BELOW PE2 SETPOINT.
RD C NO RD

PE-4 OPTIONAL 2 ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY


NC STAGE HEAT
JOB SPECIFICATIONS.
BN C NO BN
ALL P.E. SWITCHS MUST BE SET IN THE FIELD PER JOB
PE-5 OPTIONAL 3 REQUIREMENTS.
C NO BK NC STAGE HEAT
(WHEN REQ.)
BK
TC BK C NO BK
PE-1 5 C1
NC
C PE-3
NO NC
RD BK BL/WH BK
PE-2 SC FM
NC

BK
EP

PE1
P.E. SWITCH SUPPLIED BY FACTORY
(SIGNAL BY OTHERS)

N.C. PNEUMATIC DIAGRAM


RECOMMENDED FIELD P.E. SWITCH SETTINGS:
ACT. 3(C)
(NC)1 2(NO) PE-2 = 8 PSI
EP PE-3 = 8 PSI
PE-4 = 6 PSI
BAL. TAPS VEL. CNTRLR PE-5 = 4 PSI
B (RESET BAND=3-8 PSI)
FLOW LO X CONSTANT
M 20 PSI MAIN
PROBE HI Y VOLUME
T TOTAL AIR
REV. D.A.. STAT HEAT COLD AIR
FLOW

RELAY 1 PIPE AIR (UNOCCUPIED)


AIR

FLOW PLENUM AIR


M FAN STARTS
1 RESTRICTOR
3 OR OR (FIELD CALIB.)
20 PSI MAIN

D.A.. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
2 PIPE COLD T-STAT BRANCH PRESSURE (PSIG) HOT
PE5 PE4 PE3 PE2 ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE J = LOAD BEARING P.E. W/ 30A
1 3.6 8.3 E = 120V/1PH/60HZ - 2 STAGE MAG. CONTACTOR INTERLOCK
30 AMP CONT.
LOAD BRG. PE

2 1.8 4.1 5 = 120V/1PH/60HZ - 3 STAGE K = LOAD BEARING P.E. W/ 50A


W/ INTRLK

PER STAGE 3 1.2 2.7


K = 277V/1PH/60HZ - 1 STAGE MAG. CONTACTOR INTERLOCK
1 5.7 13.2
50 AMP CONT. L = 277V/1PH/60HZ - 2 STAGE L = LOAD BEARING P.E. W/ 30A
2 2.8 6.6 MERC. CONTACTOR INTERLOCK
PER STAGE Y = 277V/1PH/60HZ - 3 STAGE
3 1.9 4.4
M = LOAD BEARING P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR INTERLOCK


SIZE & TYPE

DOOR INTERLOCK 4.8 11.0

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 5.7 13.2
BLOCK

30 AMP BLOCK
FUSE

2.8 6.6

60 AMP BLOCK 5.7 13.2

1. MAX. K.W. BASED ON 48A, P.E., OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.008 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5H080

REV.1 8/5/00 PNEUMATIC


PSFH148
- J148 -

YORK INTERNATIONAL 157


SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT
P.I., N.O. DAMPER, P.E. FAN START, UNOCCUPIED MODE,POS. DAMPER CLOSE OFF, D.A. STAT, 1 PHASE, PILOT DUTY P.E. SWITCH

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V
DISCONNECT SIGNAL TO PE1 ENERGIZES THE FAN & EP SWITCH.
SWITCH SPACE TEMP WARM (STAT OUTPUT HI). AT A STAT
OUTPUT OF 13 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
FUSING WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
OPTIONAL DISCONNECT SWITCH
ON A FURTHER DROP IN SPACE TEMP., PE3 WILL CLOSE
AND OR FUSING
PANEL WIRING DIAGRAM ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.

L1 (N) = 120V & 277V AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
TERMINAL 1 2
BLOCK UNOCCUPIED MODE:
BK WH WHEN THE PRESSURE APPLIED TO PE1 (SET AND CONTROLLED
BY OTHERS) IS DROPPED BELOW ITS SETPOINT IT MAKES
BK BK WH TO NC CONTACT ENABLING PE2, TURNING OFF FAN AND
DEENERGIZING EP CAUSING THE DAMPER TO CLOSE.
C1-1 STANDARD 1 ST. HEAT G AS TEMP DROPS, STAT OUTPUT DROPS, STARTING
RD RD
FAN WHEN PRESSURE DROPS BELOW PE2 SETPOINT.
C2-1 OPTIONAL 2 ST. HEAT
BN BN
ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
C NO (WHEN REQ.) C3-1 OPTIONAL 3 ST. HEAT JOB SPECIFICATIONS.
BK TC C NO BK ST.1
BK BK
PE-1 5 C1
NC
PE-3
C NO NC
BK ST.2
RD C NO RD
PE-2 C2
NC
PE-4
NC
ST.3
BN C NO BN
C3
PE-5
NC
BK BL/WH BK
SC FM

BK
EP

PE1
P.E. SWITCH SUPPLIED BY FACTORY
N.O. PNEUMATIC DIAGRAM (SIGNAL BY OTHERS)

ACT. (3)C RECOMMENDED FIELD P.E. SWITCH SETTINGS:


(1)NC (2)NO
EP PE-2 = 8 PSI
PE-3 = 8 PSI
BAL. TAPS VEL. CNTRLR PE-4 = 6 PSI
B (RESET BAND=8-13 PSI)
FLOW LO Y CONSTANT
M 20 PSI MAIN
PROBE HI X VOLUME
T TOTAL AIR
D.A.. STAT HEAT COLD AIR
FLOW

1 PIPE AIR
AIR

FLOW PLENUM AIR


RESTRICTOR
OR OR 20 PSI MAIN

D.A.. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
2 PIPE COLD T-STAT BRANCH PRESSURE (PSIG) HOT
PE4 PE4 PE3 PE2 ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE 2 = PILOT DUTY P.E. W/ 30A
1 3.6 8.3 E = 120V/1PH/60HZ - 2 STAGE MAG. CONTACTOR
DE-ENERGIZING
CONTACTOR

30 AMP 2 2.8 6.6 5 = 120V/1PH/60HZ - 3 STAGE 3 = PILOT DUTY P.E. W/ 50A


CONTACTOR 3 1.9 4.4
K = 277V/1PH/60HZ - 1 STAGE MAG. CONTACTOR
1 5.7 13.2
50 AMP L = 277V/1PH/60HZ - 2 STAGE 4 = PILOT DUTY P.E. W/ 30A
2 2.8 6.6 MERC. CONTACTOR
CONTACTOR Y = 277V/1PH/60HZ - 3 STAGE
3 1.9 4.4
5 = PILOT DUTY P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR


SIZE & TYPE

DOOR INTERLOCK 4.8 11.0

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 5.7 13.2
BLOCK

30 AMP BLOCK
FUSE

2.8 6.6

60 AMP BLOCK 5.7 13.2

1. MAX. K.W. BASED ON 48A, OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.008 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5E080

REV.1 8/5/00 PNEUMATIC


PSFH149
- J149 -

158 YORK INTERNATIONAL


FORM AD1T-SECT J

SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT


P.I., N.C. DAMPER, P.E. FAN START, UNOCCUPIED MODE, POS. DAMPER CLOSE OFF, R.A. STAT, 1 PHASE, PILOT DUTY P.E. SWITCH

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V
DISCONNECT SIGNAL TO PE1 ENERGIZES THE FAN & EP SWITCH.
SWITCH SPACE TEMP WARM (STAT OUTPUT LOW). AT A STAT
OUTPUT OF 3 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
FUSING WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
OPTIONAL DISCONNECT SWITCH
ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
AND OR FUSING
PANEL WIRING DIAGRAM ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.

L1 (N) = 120V & 277V AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
TERMINAL 1 2
BLOCK UNOCCUPIED MODE:
BK WH
WHEN THE PRESSURE APPLIED TO PE1 (SET AND CONTROLLED
BY OTHERS) IS DROPPED BELOW ITS SETPOINT IT MAKES
BK BK WH
TO NC CONTACT ENABLING PE2, TURNING OFF FAN AND
C1-1 STANDARD 1 ST. HEAT G
DEENERGIZING EP CAUSING THE DAMPER TO CLOSE.
RD RD AS TEMP DROPS, STAT OUTPUT DROPS, STARTING
OPTIONAL 2 ST. HEAT FAN WHEN PRESSURE DROPS BELOW PE2 SETPOINT.
C2-1
BN BN

C NO (WHEN REQ.) C3-1 OPTIONAL 3 ST. HEAT


BK
TC C NO BK ST.1
BK BK
PE-1 5 C1
NC ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
C NO PE-3 JOB SPECIFICATIONS.
NC
BK ST.2
RD C NO RD
PE-2 C2
NC
PE-4
NC
ST.3
BN C NO BN
C3
PE-5
NC
BK BL/WH BK
SC FM

BK
EP

PE1
P.E. SWITCH SUPPLIED BY FACTORY
N.C. PNEUMATIC DIAGRAM (SIGNAL BY OTHERS)
RECOMMENDED FIELD P.E. SWITCH SETTINGS:
ACT. (3)C PE-2 = 8 PSI
(1)NC (2)NO PE-3 = 8 PSI
EP PE-4 = 10 PSI
BAL. TAPS VEL. CNTRLR PE-5 = 12 PSI
B (RESET BAND=3-8 PSI)
FLOW LO X CONSTANT
M 20 PSI MAIN VOLUME
PROBE HI Y TOTAL AIR
T
COLD AIR HEAT
R.A. STAT
FLOW

AIR
1 PIPE PLENUM AIR
AIR

FLOW
RESTRICTOR
OR OR 20 PSI MAIN

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
R.A. STAT
2 PIPE HOT T-STAT BRANCH PRESSURE (PSIG) COLD
PE4 PE3 PE2 ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE 2 = PILOT DUTY P.E. W/ 30A
1 3.6 8.3 E = 120V/1PH/60HZ - 2 STAGE MAG. CONTACTOR
DE-ENERGIZING
CONTACTOR

30 AMP 2 2.8 6.6 5 = 120V/1PH/60HZ - 3 STAGE 3 = PILOT DUTY P.E. W/ 50A


CONTACTOR 3 1.9 4.4
K = 277V/1PH/60HZ - 1 STAGE MAG. CONTACTOR
1 5.7 13.2
50 AMP L = 277V/1PH/60HZ - 2 STAGE 4 = PILOT DUTY P.E. W/ 30A
2 2.8 6.6 MERC. CONTACTOR
CONTACTOR Y = 277V/1PH/60HZ - 3 STAGE
3 1.9 4.4
5 = PILOT DUTY P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR


SIZE & TYPE

DOOR INTERLOCK 4.8 11.0

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 5.7 13.2
BLOCK

30 AMP BLOCK
FUSE

2.8 6.6

60 AMP BLOCK 5.7 13.2

1. MAX. K.W. BASED ON 48A, OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.008 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5F080

REV.1 8/5/00 PNEUMATIC


PSFH150
- J150 -

YORK INTERNATIONAL 159


SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT
P.I., N.O. DAMPER, P.E. FAN START, UNOCCUPIED MODE, POS. DAMPER CLOSE OFF, R.A. STAT, 1 PHASE, PILOT DUTY P.E. SWITCH

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V
DISCONNECT SIGNAL TO PE1 ENERGIZES THE FAN & EP SWITCH.
SWITCH SPACE TEMP WARM (STAT OUTPUT LOW). AT A STAT
OUTPUT OF 3 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
FUSING WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
OPTIONAL DISCONNECT SWITCH
ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
AND OR FUSING
PANEL WIRING DIAGRAM ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.

L1 (N) = 120V & 277V AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
TERMINAL 1 2
BLOCK UNOCCUPIED MODE:
BK WH
WHEN THE PRESSURE APPLIED TO PE1 (SET AND CONTROLLED
BY OTHERS) IS DROPPED BELOW ITS SETPOINT IT MAKES
BK BK WH TO NC CONTACT ENABLING PE2, TURNING OFF FAN AND
DEENERGIZING EP CAUSING THE DAMPER TO CLOSE.
C1-1 STANDARD 1 ST. HEAT G AS TEMP DROPS, STAT OUTPUT DROPS, STARTING
RD RD
FAN WHEN PRESSURE DROPS BELOW PE2 SETPOINT.
OPTIONAL 2 ST. HEAT
C2-1
BN BN

C NO C3-1 OPTIONAL 3 ST. HEAT ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
(WHEN REQ.) JOB SPECIFICATIONS.
BK
TC C NO BK ST.1
BK BK
PE-1 5 C1
NC
PE-3
C NO NC
ST.2
RD
RD C NO RD
PE-2 C2
NC
PE-4
NC
ST.3
BN C NO BN
C3
PE-5
NC
BK BL/WH BK
SC FM

BK
EP

PNEUMATIC DIAGRAM PE1


P.E. SWITCH SUPPLIED BY FACTORY
N.O. (SIGNAL BY OTHERS)
RECOMMENDED FIELD P.E. SWITCH SETTINGS:
ACT. (3)C
(1)NC (2)NO PE-2 = 8 PSI
EP PE-3 = 8 PSI
PE-4 = 10 PSI
BAL. TAPS VEL. CNTRLR PE-5 = 12 PSI
B (RESET BAND=8-13 PSI)
FLOW LO Y
M 20 PSI MAIN
PROBE HI X CONSTANT
T
VOLUME
REV. R.A.. STAT TOTAL AIR
FLOW

RELAY 1 PIPE HEAT


AIR

COLD AIR
AIR
M RESTRICTOR PLENUM AIR
1 FLOW
3 OR OR 20 PSI MAIN

R.A.. STAT
2 PIPE 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE5 PE4 PE3 PE2 HOT T-STAT BRANCH PRESSURE (PSIG) COLD
ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE 2 = PILOT DUTY P.E. W/ 30A
1 3.6 8.3 E = 120V/1PH/60HZ - 2 STAGE MAG. CONTACTOR
DE-ENERGIZING
CONTACTOR

30 AMP 2 2.8 6.6 5 = 120V/1PH/60HZ - 3 STAGE 3 = PILOT DUTY P.E. W/ 50A


CONTACTOR 3 1.9 4.4
K = 277V/1PH/60HZ - 1 STAGE MAG. CONTACTOR
1 5.7 13.2
50 AMP L = 277V/1PH/60HZ - 2 STAGE 4 = PILOT DUTY P.E. W/ 30A
2 2.8 6.6 MERC. CONTACTOR
CONTACTOR Y = 277V/1PH/60HZ - 3 STAGE
3 1.9 4.4
5 = PILOT DUTY P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR


SIZE & TYPE

DOOR INTERLOCK 4.8 11.0

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 5.7 13.2
BLOCK

30 AMP BLOCK
FUSE

2.8 6.6

60 AMP BLOCK 5.7 13.2

1. MAX. K.W. BASED ON 48A, OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.016 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5G080

REV.1 8/5/00 PNEUMATIC


PSFH151
- J151 -

160 YORK INTERNATIONAL


FORM AD1T-SECT J

SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT


P.I., N.C. DAMPER, P.E. FAN START, UNOCCUPIED MODE, POS. DAMPER CLOSE OFF, D.A. STAT, 1 PHASE, PILOT DUTY P.E. SWITCH

SEQUENCE OF OPERATION:
L1 (N) = 120V & 277V
DISCONNECT SIGNAL TO PE1 ENERGIZES THE FAN & EP SWITCH.
SWITCH SPACE TEMP WARM (STAT OUTPUT HI). AT A STAT
OUTPUT OF 13 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
FUSING WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
OPTIONAL DISCONNECT SWITCH
ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
AND OR FUSING
PANEL WIRING DIAGRAM ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.

L1 (N) = 120V & 277V AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
TERMINAL 1 2
BLOCK UNOCCUPIED MODE:
BK WH
WHEN THE PRESSURE APPLIED TO PE1 (SET AND CONTROLLED
BY OTHERS) IS DROPPED BELOW ITS SETPOINT IT MAKES
BK BK WH TO NC CONTACT ENABLING PE2, TURNING OFF FAN AND
DEENERGIZING EP CAUSING THE DAMPER TO CLOSE.
C1-1 STANDARD 1 ST. HEAT G AS TEMP DROPS, STAT OUTPUT DROPS, STARTING
RD RD
FAN WHEN PRESSURE DROPS BELOW PE2 SETPOINT.
OPTIONAL 2 ST. HEAT
C2-1
BN BN ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
JOB SPECIFICATIONS.
C NO (WHEN REQ.) C3-1 OPTIONAL 3 ST. HEAT
BK
TC C NO BK ST.1
BK BK
PE-1 5 C1
NC
PE-3
C NO NC
ST.2
RD
RD C NO RD
PE-2 C2
NC
PE-4
NC
ST.3
BN C NO BN
C3
PE-5
NC
BK BL/WH BK
SC FM

BK
EP

P.E. SWITCH SUPPLIED BY FACTORY


N.C.
PNEUMATIC DIAGRAM PE1
(SIGNAL BY OTHERS) RECOMMENDED FIELD P.E. SWITCH SETTINGS:
ACT. (3)C PE-2 = 8 PSI
(1)NC (2)NO PE-3 = 8 PSI
EP PE-4 = 10 PSI
BAL. TAPS PE-4 = 12 PSI
VEL. CNTRLR
B (RESET BAND=3-8 PSI)
FLOW LO X CONSTANT
M 20 PSI MAIN
PROBE HI Y VOLUME
T TOTAL AIR
REV. D.A.. STAT HEAT COLD AIR
FLOW

RELAY 1 PIPE AIR


AIR

FLOW PLENUM AIR


M RESTRICTOR
1
3 OR OR 20 PSI MAIN

D.A.. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
2 PIPE COLD T-STAT BRANCH PRESSURE (PSIG) HOT
PE5 PE4 PE3 PE2 ROOM ROOM

HEATER COMPONENTS MAX. KW


1 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-1 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 120 V 277 V D = 120V/1PH/60HZ - 1 STAGE 2 = PILOT DUTY P.E. W/ 30A
1 3.6 8.3 E = 120V/1PH/60HZ - 2 STAGE MAG. CONTACTOR
DE-ENERGIZING
CONTACTOR

30 AMP 2 2.8 6.6 5 = 120V/1PH/60HZ - 3 STAGE 3 = PILOT DUTY P.E. W/ 50A


CONTACTOR 3 1.9 4.4
K = 277V/1PH/60HZ - 1 STAGE MAG. CONTACTOR
1 5.7 13.2
50 AMP L = 277V/1PH/60HZ - 2 STAGE 4 = PILOT DUTY P.E. W/ 30A
2 2.8 6.6 MERC. CONTACTOR
CONTACTOR Y = 277V/1PH/60HZ - 3 STAGE
3 1.9 4.4
5 = PILOT DUTY P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR


SIZE & TYPE

DOOR INTERLOCK 4.8 11.0

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 5.7 13.2
BLOCK

30 AMP BLOCK
FUSE

2.8 6.6

60 AMP BLOCK 5.7 13.2

1. MAX. K.W. BASED ON 48A, OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.016 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5H080

REV.1 8/5/00 PNEUMATIC


PSFH152
- J152 -

YORK INTERNATIONAL 161


SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT
P.I., N.O. DAMPER, P.E. FAN START, UNOCCUPIED MODE, POS. DAMPER CLOSE OFF, D.A. STAT, 3 PHASE, LOAD BEARING P.E. SWITCH W/ CONT. INTRLK.

SEQUENCE OF OPERATION:
SIGNAL TO PE1 ENERGIZES THE FAN & EP SWITCH.
L1 L2 L3
SPACE TEMP WARM (STAT OUTPUT HI). AT A STAT
DISCONNECT
OUTPUT OF 13 PSI THE VEL. CNTRLR WILL BE CONTROLLING
SWITCH AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
FUSING
CONTROLLING AT ITS MINIMUM.
ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
OPTIONAL DISCONNECT SWITCH ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
PANEL WIRING DIAGRAM AND OR FUSING AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
L1 L2 L3 N UNOCCUPIED MODE:
TERMINAL WHEN THE PRESSURE APPLIED TO PE1 (SET AND CONTROLLED
1 2 3 4 BY OTHERS) IS DROPPED BELOW ITS SETPOINT IT MAKES
BLOCK
BK WH TO NC CONTACT ENABLING PE2, TURNING OFF FAN AND
BK BL DEENERGIZING EP CAUSING THE DAMPER TO CLOSE.
AS TEMP DROPS, STAT OUTPUT DROPS, STARTING
BK FAN WHEN PRESSURE DROPS BELOW PE2 SETPOINT.
STANDARD 1 STAGE HEAT
C1-1 G
BK BK
ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
JOB SPECIFICATIONS.
C1-2
C NO BK BK BK
L1 1
TC ST.1
BK BK C NO BK C NO C1-1 BL
PE-1 5 C1 L2 2
RD 3 L3
NC
RD RD
C NO PE-3 PE-4
NC NC
RD
C1-2
PE-2 BK BL/WH BK
NC SC FM OPTIONAL 2 STAGE HEAT

BK
EP BK BK
L1 1
C1-1
RD
C NO
P.E. SWITCH SUPPLIED BY FACTORY L2 2
PE1 RD
(SIGNAL BY OTHERS) PE-4
NC
BN C NO BN

PE-5
NC
BL BL
L3 3
N.O. PNEUMATIC DIAGRAM C1-2

ACT. OPTIONAL 3 STAGE HEAT


(3)C
(1)NC (2)NO RECOMMENDED FIELD P.E. SWITCH SETTINGS:
EP PE-2 = 8 PSI
PE-3 = 8 PSI
BAL. TAPS VEL. CNTRLR PE-4 = 6 PSI
B (RESET BAND=8-13 PSI) PE-5 = 4 PSI
FLOW LO Y
M 20 PSI MAIN
PROBE HI X
T CONSTANT
D.A.. STAT VOLUME
TOTAL AIR
FLOW

1 PIPE HEAT
AIR

COLD AIR
AIR
RESTRICTOR
OR OR 20 PSI MAIN FLOW PLENUM AIR

D.A.. STAT
2 PIPE
PE3 PE2
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE5 PE4
COLD T-STAT BRANCH PRESSURE (PSIG) HOT
ROOM ROOM

HEATER COMPONENTS MAX. KW


3 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-3 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 208 V 480 V P = 208V/3PH/60HZ - 1 STAGE J = LOAD BEARING P.E. W/ 30A
1 10.7 24.9 R = 208V/3PH/60HZ - 2 STAGE MAG. CONTACTOR INTERLOCK
30 AMP CONT.
LOAD BRG. PE

2 4.4 9.1 1 = 208V/3PH/60HZ - 3 STAGE K = LOAD BEARING P.E. W/ 50A


W/ INTRLK

PER STAGE 3 2.9 6.0


U = 480V/3PH/60HZ - 1 STAGE MAG. CONTACTOR INTERLOCK
1 17.2 39.8
50 AMP CONT. W = 480V/3PH/60HZ - 2 STAGE L = LOAD BEARING P.E. W/ 30A
2 4.4 9.1 MERC. CONTACTOR INTERLOCK
PER STAGE 3 = 480V/3PH/60HZ - 3 STAGE
3 2.9 6.0
M = LOAD BEARING P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR INTERLOCK


SIZE & TYPE

DOOR INTERLOCK 14.3 33.2

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 17.2 39.8
BLOCK

30 AMP BLOCK
FUSE

8.6 19.9

60 AMP BLOCK 17.2 39.8

1. MAX. K.W. BASED ON 48A, P.E., OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.008 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5E080

REV.1 8/5/00 PNEUMATIC


PSFH153
- J153 -

162 YORK INTERNATIONAL


FORM AD1T-SECT J

SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT


P.I., N.C. DAMPER, P.E. FAN START, UNOCCUPIED MODE, POS. DAMPER CLOSE OFF, R.A. STAT, 3 PHASE, LOAD BEARING P.E. SWITCH W/ CONT. INTRLK.

SEQUENCE OF OPERATION:
L1 L2 L3
SIGNAL TO PE1 ENERGIZES THE FAN & EP SWITCH.
DISCONNECT
SPACE TEMP WARM (STAT OUTPUT LOW). AT A STAT
SWITCH
OUTPUT OF 3 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
FUSING WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
OPTIONAL DISCONNECT SWITCH ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
PANEL WIRING DIAGRAM AND OR FUSING ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
L1 L2 L3 N AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
TERMINAL 1 2 3 4
BLOCK UNOCCUPIED MODE:
BK WH
WHEN THE PRESSURE APPLIED TO PE1 (SET AND CONTROLLED
BK BL
BY OTHERS) IS DROPPED BELOW ITS SETPOINT IT MAKES
TO NC CONTACT ENABLING PE2, TURNING OFF FAN AND
BK STANDARD 1 STAGE HEAT DEENERGIZING EP CAUSING THE DAMPER TO CLOSE.
C1-1 G AS TEMP DROPS, STAT OUTPUT DROPS, STARTING
BK BK FAN WHEN PRESSURE DROPS BELOW PE2 SETPOINT.
C1-2
C NO BK
ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
ST.1 JOB SPECIFICATIONS.
BK TC BK C NO BK
PE-1 5 C1
NC
C NO PE-3
NC
BK BL/WH BK
PE-2 SC FM
NC

BK
BK BK
EP L1 1
C1-1
RD
C NO
P.E. SWITCH SUPPLIED BY FACTORY L2 2 RD
PE1
(SIGNAL BY OTHERS) PE-4
NC
L1 1
BK BK
BN C NO BN

C NO C1-1 BL
L2 2
RD 3 L3 PE-5
RD NC
RD BL BL
PE-4 L3 3
NC C1-2 C1-2

N.C. PNEUMATIC DIAGRAM OPTIONAL 2 STAGE HEAT OPTIONAL 3 STAGE HEAT

ACT. (3)C RECOMMENDED FIELD P.E. SWITCH SETTINGS:


(1)NC (2)NO PE-2 = 8 PSI
EP PE-3 = 8 PSI
PE-4 = 10 PSI
BAL. TAPS VEL. CNTRLR
PE-5 = 12 PSI
B (RESET BAND=3-8 PSI)
FLOW LO X
M 20 PSI MAIN CONSTANT
PROBE HI Y
T VOLUME
TOTAL AIR
R.A. STAT
FLOW

COLD AIR HEAT


1 PIPE AIR
AIR

FLOW PLENUM AIR


RESTRICTOR
OR OR 20 PSI MAIN

R.A. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE5 PE4 PE3 PE2 2 PIPE HOT COLD
T-STAT BRANCH PRESSURE (PSIG)
ROOM ROOM

HEATER COMPONENTS MAX. KW


3 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-3 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 208 V 480 V P = 208V/3PH/60HZ - 1 STAGE J = LOAD BEARING P.E. W/ 30A
1 10.7 24.9 R = 208V/3PH/60HZ - 2 STAGE MAG. CONTACTOR INTERLOCK
30 AMP CONT.
LOAD BRG. PE

2 4.4 9.1 1 = 208V/3PH/60HZ - 3 STAGE K = LOAD BEARING P.E. W/ 50A


W/ INTRLK

PER STAGE 3 2.9 6.0


U = 480V/3PH/60HZ - 1 STAGE MAG. CONTACTOR INTERLOCK
1 17.2 39.8
50 AMP CONT. W = 480V/3PH/60HZ - 2 STAGE L = LOAD BEARING P.E. W/ 30A
2 4.4 9.1 MERC. CONTACTOR INTERLOCK
PER STAGE 3 = 480V/3PH/60HZ - 3 STAGE
3 2.9 6.0
M = LOAD BEARING P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR INTERLOCK


SIZE & TYPE

DOOR INTERLOCK 14.3 33.2

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 17.2 39.8
BLOCK

30 AMP BLOCK
FUSE

8.6 19.9

60 AMP BLOCK 17.2 39.8

1. MAX. K.W. BASED ON 48A, P.E., OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.008 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5F080

REV.1 8/5/00 PNEUMATIC


PSFH154
- J154 -

YORK INTERNATIONAL 163


SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT
P.I., N.O. DAMPER, P.E. FAN START, UNOCCUPIED MODE, POS. DAMPER CLOSE OFF, R.A. STAT, 3 PHASE, LOAD BEARING P.E. SWITCH W/ CONT. INTRLK.

SEQUENCE OF OPERATION:
L1 L2 L3
SIGNAL TO PE1 ENERGIZES THE FAN & EP SWITCH.
DISCONNECT
SPACE TEMP WARM (STAT OUTPUT LOW). AT A STAT
SWITCH
OUTPUT OF 3 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
FUSING WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
OPTIONAL DISCONNECT SWITCH ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
PANEL WIRING DIAGRAM AND OR FUSING ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
L1 L2 L3 N AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
TERMINAL 1 2 3 4
BLOCK UNOCCUPIED MODE:
BK WH
WHEN THE PRESSURE APPLIED TO PE1 (SET AND CONTROLLED
BK BL
BY OTHERS) IS DROPPED BELOW ITS SETPOINT IT MAKES
TO NC CONTACT ENABLING PE2, TURNING OFF FAN AND
BK STANDARD 1 STAGE HEAT DEENERGIZING EP CAUSING THE DAMPER TO CLOSE.
C1-1 G AS TEMP DROPS, STAT OUTPUT DROPS, STARTING
BK BK FAN WHEN PRESSURE DROPS BELOW PE2 SETPOINT.
C1-2
C NO BK ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
TC ST.1 JOB SPECIFICATIONS.
BK BK C NO BK
PE-1 5 C1
NC
C PE-3
NO NC
BK BL/WH BK
PE-2 SC FM
NC

BK
EP BK BK
L1 1
C1-1
RD
C NO
L2 2
PE1
P.E. SWITCH SUPPLIED BY FACTORY RD

(SIGNAL BY OTHERS) PE-4


NC
BK BK C
L1 1 BN NO BN

C NO C1-1 BL
L2 2
RD 3 L3 PE-5
RD NC
RD BL
PE-4 BL
NC L3 3
PNEUMATIC DIAGRAM C1-2 C1-2
N.O.
OPTIONAL 2 STAGE HEAT OPTIONAL 3 STAGE HEAT
ACT. (3)C
(1)NC (2)NO RECOMMENDED FIELD P.E. SWITCH SETTINGS:
EP PE-2 = 8 PSI
PE-3 = 8 PSI
BAL. TAPS VEL. CNTRLR PE-4 = 10 PSI
B (RESET BAND=8-13 PSI)
FLOW LO Y PE-5 = 12 PSI
M 20 PSI MAIN
PROBE HI X CONSTANT
T
VOLUME
REV. R.A.. STAT TOTAL AIR
FLOW

RELAY 1 PIPE HEAT


AIR

COLD AIR
AIR
M RESTRICTOR PLENUM AIR
1 FLOW
3 OR OR 20 PSI MAIN

R.A.. STAT
2 PIPE 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
PE5 PE4 PE3 PE2 HOT T-STAT BRANCH PRESSURE (PSIG) COLD
ROOM ROOM

HEATER COMPONENTS MAX. KW


3 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-3 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 208 V 480 V P = 208V/3PH/60HZ - 1 STAGE J = LOAD BEARING P.E. W/ 30A
1 10.7 24.9 R = 208V/3PH/60HZ - 2 STAGE MAG. CONTACTOR INTERLOCK
30 AMP CONT.
LOAD BRG. PE

2 4.4 9.1 1 = 208V/3PH/60HZ - 3 STAGE K = LOAD BEARING P.E. W/ 50A


W/ INTRLK

PER STAGE 3 2.9 6.0


U = 480V/3PH/60HZ - 1 STAGE MAG. CONTACTOR INTERLOCK
1 17.2 39.8
50 AMP CONT. W = 480V/3PH/60HZ - 2 STAGE L = LOAD BEARING P.E. W/ 30A
2 4.4 9.1 MERC. CONTACTOR INTERLOCK
PER STAGE 3 = 480V/3PH/60HZ - 3 STAGE
3 2.9 6.0
M = LOAD BEARING P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR INTERLOCK


SIZE & TYPE

DOOR INTERLOCK 14.3 33.2

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 17.2 39.8
BLOCK

30 AMP BLOCK
FUSE

8.6 19.9

60 AMP BLOCK 17.2 39.8

1. MAX. K.W. BASED ON 48A, P.E., OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.016 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5G080

REV.1 8/5/00 PNEUMATIC


PSFH155
- J155 -

164 YORK INTERNATIONAL


FORM AD1T-SECT J

SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT


P.I., N.C. DAMPER, P.E. FAN START, UNOCCUPIED MODE, POS. DAMPER CLOSE OFF, D.A. STAT, 3 PHASE, LOAD BEARING P.E. SWITCH W/ CONT. INTRLK.

SEQUENCE OF OPERATION:
L1 L2 L3
SIGNAL TO PE1 ENERGIZES THE FAN & EP SWITCH.
DISCONNECT
SPACE TEMP WARM (STAT OUTPUT HI). AT A STAT
SWITCH
OUTPUT OF 13 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
FUSING WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
OPTIONAL DISCONNECT SWITCH ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
PANEL WIRING DIAGRAM AND OR FUSING ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
L1 L2 L3 N AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
TERMINAL 1 2 3 4
BLOCK UNOCCUPIED MODE:
BK WH
WHEN THE PRESSURE APPLIED TO PE1 (SET AND CONTROLLED
BK BL
BY OTHERS) IS DROPPED BELOW ITS SETPOINT IT MAKES
TO NC CONTACT ENABLING PE2, TURNING OFF FAN AND
BK STANDARD 1 STAGE HEAT DEENERGIZING EP CAUSING THE DAMPER TO CLOSE.
C1-1 G AS TEMP DROPS, STAT OUTPUT DROPS, STARTING
BK BK FAN WHEN PRESSURE DROPS BELOW PE2 SETPOINT.
C1-2
ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
C NO BK
JOB SPECIFICATIONS.
TC ST.1
BK BK C NO BK
PE-1 5 C1
NC
C NO PE-3
NC
BK BL/WH BK
PE-2 SC FM
NC

BK
EP BK BK
L1 1
C1-1
RD
C NO
L2 2
PE1
P.E. SWITCH SUPPLIED BY FACTORY RD
(SIGNAL BY OTHERS) PE-4
NC
BK BK C NO
L1 1 BN BN

C NO C1-1 BL
L2 2
RD 3 L3 PE-5
RD
NC
RD BL BL
PE-4 L3 3
NC C1-2 C1-2
N.C.
PNEUMATIC DIAGRAM OPTIONAL 3 STAGE HEAT
OPTIONAL 2 STAGE HEAT
ACT. (3)C RECOMMENDED FIELD P.E. SWITCH SETTINGS:
(1)NC (2)NO PE-2 = 8 PSI
EP PE-3 = 8 PSI
BAL. TAPS PE-4 = 6 PSI
VEL. CNTRLR
PE-5 = 4 PSI
B (RESET BAND=3-8 PSI)
FLOW LO X CONSTANT
M 20 PSI MAIN
PROBE HI Y VOLUME
T TOTAL AIR
REV. D.A.. STAT HEAT COLD AIR
FLOW

RELAY 1 PIPE AIR


AIR

FLOW PLENUM AIR


M RESTRICTOR
1
3 OR OR 20 PSI MAIN

D.A.. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
2 PIPE COLD T-STAT BRANCH PRESSURE (PSIG) HOT
PE5 PE4 PE3 PE2 ROOM ROOM

HEATER COMPONENTS MAX. KW


3 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-3 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 208 V 480 V P = 208V/3PH/60HZ - 1 STAGE J = LOAD BEARING P.E. W/ 30A
1 10.7 24.9 R = 208V/3PH/60HZ - 2 STAGE MAG. CONTACTOR INTERLOCK
30 AMP CONT.
LOAD BRG. PE

2 4.4 9.1 1 = 208V/3PH/60HZ - 3 STAGE K = LOAD BEARING P.E. W/ 50A


W/ INTRLK

PER STAGE 3 2.9 6.0


U = 480V/3PH/60HZ - 1 STAGE MAG. CONTACTOR INTERLOCK
1 17.2 39.8
50 AMP CONT. W = 480V/3PH/60HZ - 2 STAGE L = LOAD BEARING P.E. W/ 30A
2 4.4 9.1 MERC. CONTACTOR INTERLOCK
PER STAGE 3 = 480V/3PH/60HZ - 3 STAGE
3 2.9 6.0
M = LOAD BEARING P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR INTERLOCK


SIZE & TYPE

DOOR INTERLOCK 14.3 33.2

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 17.2 39.8
BLOCK

30 AMP BLOCK
FUSE

8.6 19.9

60 AMP BLOCK 17.2 39.8

1. MAX. K.W. BASED ON 48A, P.E., OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.016 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5H080

REV.1 8/5/00 PNEUMATIC


PSFH156
- J156 -

YORK INTERNATIONAL 165


SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT
P.I., N.O. DAMPER, P.E. FAN START, UNOCCUPIED MODE, POS. DAMPER CLOSE OFF, D.A. STAT, 3 PHASE, PILOT DUTY P.E. SWITCH

SEQUENCE OF OPERATION:
L1 L2 L3
SIGNAL TO PE1 ENERGIZES THE FAN & EP SWITCH.
DISCONNECT
SPACE TEMP WARM (STAT OUTPUT HI). AT A STAT
SWITCH
OUTPUT OF 13 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
FUSING WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
OPTIONAL DISCONNECT SWITCH ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
PANEL WIRING DIAGRAM AND OR FUSING ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
L1 L2 L3 N AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
TERMINAL 1 2 3 4
BLOCK UNOCCUPIED MODE:
BK WH
WHEN THE PRESSURE APPLIED TO PE1 (SET AND CONTROLLED
BK BL BY OTHERS) IS DROPPED BELOW ITS SETPOINT IT MAKES
TO NC CONTACT ENABLING PE2, TURNING OFF FAN AND
BK STANDARD 1 STAGE HEAT DEENERGIZING EP CAUSING THE DAMPER TO CLOSE.
G AS TEMP DROPS, STAT OUTPUT DROPS, STARTING
C1-1
BK BK FAN WHEN PRESSURE DROPS BELOW PE2 SETPOINT.

C1-2 ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY


C NO BK JOB SPECIFICATIONS.
TC ST.1
BK BK C NO BK
PE-1 5 C1
NC BK BK
PE-3 L1 1
C NO NC BL
ST.2 C1-1 3 L3
RD C NO RD RD RD
C2 L2 2
PE-2
NC C2-1
PE-4
NC OPTIONAL 2 STAGE HEAT
ST.3
BN C NO BN
C3
PE-5 BK BK
NC L1 1
BK BL/WH BK C1-1
SC FM RD RD
L2 2
C2-1
BN BN
BK
EP C3-1
BL BL
L3 3
C1-2
P.E. SWITCH SUPPLIED BY FACTORY
PNEUMATIC DIAGRAM PE1
(SIGNAL BY OTHERS) OPTIONAL 3 STAGE HEAT
N.O.
ACT. (3)C RECOMMENDED FIELD P.E. SWITCH SETTINGS:
(1)NC (2)NO PE-2 = 8 PSI
EP PE-3 = 8 PSI
PE-4 = 6 PSI
BAL. TAPS VEL. CNTRLR PE-5 = 4 PSI
B (RESET BAND=8-13 PSI)
FLOW LO Y CONSTANT
M 20 PSI MAIN
PROBE HI X VOLUME
T TOTAL AIR
D.A.. STAT HEAT COLD AIR
FLOW

1 PIPE AIR
AIR

FLOW PLENUM AIR


RESTRICTOR
OR OR 20 PSI MAIN

D.A.. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
2 PIPE COLD T-STAT BRANCH PRESSURE (PSIG) HOT
PE5 PE4 PE3 PE2 ROOM ROOM

HEATER COMPONENTS MAX. KW


3 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-3 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 208 V 480 V P = 208V/3PH/60HZ - 1 STAGE 2 = PILOT DUTY P.E. W/ 30A
1 10.7 24.9 R = 208V/3PH/60HZ - 2 STAGE MAG. CONTACTOR
DE-ENERGIZING
CONTACTOR

30 AMP 2 5.3 12.4 1 = 208V/3PH/60HZ - 3 STAGE 3 = PILOT DUTY P.E. W/ 50A


PER STAGE 3 3.5 8.3
U = 480V/3PH/60HZ - 1 STAGE MAG. CONTACTOR
1 17.2 39.8
50 AMP W = 480V/3PH/60HZ - 2 STAGE 4 = PILOT DUTY P.E. W/ 30A
2 8.6 19.9 MERC. CONTACTOR
PER STAGE 3 = 480V/3PH/60HZ - 3 STAGE
3 5.7 13.2
5 = PILOT DUTY P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR


SIZE & TYPE

DOOR INTERLOCK 14.3 33.2

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 17.2 39.8
BLOCK

30 AMP BLOCK 8.6 19.9


FUSE

60 AMP BLOCK 17.2 39.8

1. MAX. K.W. BASED ON 48A, OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.008 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5E080

REV.1 8/5/00 PNEUMATIC


PSFH157
- J157 -

166 YORK INTERNATIONAL


FORM AD1T-SECT J

SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT


P.I., N.C. DAMPER, P.E. FAN START, UNOCCUPIED MODE, POS. DAMPER CLOSE OFF, R.A. STAT, 3 PHASE, PILOT DUTY P.E. SWITCH

SEQUENCE OF OPERATION:
L1 L2 L3
SIGNAL TO PE1 ENERGIZES THE FAN & EP SWITCH.
DISCONNECT
SPACE TEMP WARM (STAT OUTPUT LOW). AT A STAT
SWITCH
OUTPUT OF 3 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
FUSING WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
OPTIONAL DISCONNECT SWITCH ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
PANEL WIRING DIAGRAM AND OR FUSING ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
L1 L2 L3 N AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
TERMINAL 1 2 3 4
BLOCK UNOCCUPIED MODE:
BK WH
WHEN THE PRESSURE APPLIED TO PE1 (SET AND CONTROLLED
BK BL BY OTHERS) IS DROPPED BELOW ITS SETPOINT IT MAKES
TO NC CONTACT ENABLING PE2, TURNING OFF FAN AND
BK STANDARD 1 STAGE HEAT DEENERGIZING EP CAUSING THE DAMPER TO CLOSE.
G AS TEMP DROPS, STAT OUTPUT DROPS, STARTING
C1-1
BK BK FAN WHEN PRESSURE DROPS BELOW PE2 SETPOINT.

C1-2 ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY


C NO BK JOB SPECIFICATIONS.
TC ST.1
BK BK C NO BK
PE-1 5 C1
NC BK BK
PE-3 L1 1
C NO NC BL
ST.2 C1-1 3 L3
RD C NO RD RD RD
C2 L2 2
PE-2
NC C2-1
PE-4
NC OPTIONAL 2 STAGE HEAT
ST.3
BN C NO BN
C3
PE-5 BK BK
NC L1 1
BK BL/WH BK C1-1
SC FM RD RD
L2 2
C2-1
BN BN
BK
EP C3-1
BL BL
L3 3
C1-2
PNEUMATIC DIAGRAM PE1
P.E. SWITCH SUPPLIED BY FACTORY
(SIGNAL BY OTHERS) OPTIONAL 3 STAGE HEAT
N.C.
ACT. RECOMMENDED FIELD P.E. SWITCH SETTINGS:
(3)C
PE-2 = 8 PSI
(1)NC (2)NO
PE-3 = 8 PSI
EP PE-4 = 10 PSI
BAL. TAPS VEL. CNTRLR PE-5 = 12 PSI
B (RESET BAND=3-8 PSI)
FLOW LO X CONSTANT
M 20 PSI MAIN VOLUME
PROBE HI Y TOTAL AIR
T
COLD AIR HEAT
R.A. STAT
FLOW

AIR
1 PIPE PLENUM AIR
AIR

FLOW
RESTRICTOR
OR OR 20 PSI MAIN

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
R.A. STAT
2 PIPE HOT T-STAT BRANCH PRESSURE (PSIG) COLD
PE5 PE4 PE3 PE2 ROOM ROOM

HEATER COMPONENTS MAX. KW


3 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-3 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 208 V 480 V P = 208V/3PH/60HZ - 1 STAGE 2 = PILOT DUTY P.E. W/ 30A
1 10.7 24.9 R = 208V/3PH/60HZ - 2 STAGE MAG. CONTACTOR
DE-ENERGIZING
CONTACTOR

30 AMP 2 5.3 12.4 1 = 208V/3PH/60HZ - 3 STAGE 3 = PILOT DUTY P.E. W/ 50A


PER STAGE 3 3.5 8.3
U = 480V/3PH/60HZ - 1 STAGE MAG. CONTACTOR
1 17.2 39.8
50 AMP W = 480V/3PH/60HZ - 2 STAGE 4 = PILOT DUTY P.E. W/ 30A
2 8.6 19.9 MERC. CONTACTOR
PER STAGE 3 = 480V/3PH/60HZ - 3 STAGE
3 5.7 13.2
5 = PILOT DUTY P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR


SIZE & TYPE

DOOR INTERLOCK 14.3 33.2

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 17.2 39.8
BLOCK

30 AMP BLOCK 8.6 19.9


FUSE

60 AMP BLOCK 17.2 39.8

1. MAX. K.W. BASED ON 48A, OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.008 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5F080

REV.1 8/5/00 PNEUMATIC


PSFH158
- J158 -

YORK INTERNATIONAL 167


SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT
P.I., N.O. DAMPER, P.E. FAN START, UNOCCUPIED MODE, POS. DAMPER CLOSE OFF, R.A. STAT, 3 PHASE, PILOT DUTY P.E. SWITCH

SEQUENCE OF OPERATION:
L1 L2 L3
SIGNAL TO PE1 ENERGIZES THE FAN & EP SWITCH.
DISCONNECT
SPACE TEMP WARM (STAT OUTPUT LOW). AT A STAT
SWITCH
OUTPUT OF 3 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
FUSING WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
OPTIONAL DISCONNECT SWITCH ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
PANEL WIRING DIAGRAM AND OR FUSING ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
L1 L2 L3 N AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
TERMINAL 1 2 3 4
BLOCK UNOCCUPIED MODE:
BK WH WHEN THE PRESSURE APPLIED TO PE1 (SET AND CONTROLLED
BK BL BY OTHERS) IS DROPPED BELOW ITS SETPOINT IT MAKES
TO NC CONTACT ENABLING PE2, TURNING OFF FAN AND
BK STANDARD 1 STAGE HEAT DEENERGIZING EP CAUSING THE DAMPER TO CLOSE.
G AS TEMP DROPS, STAT OUTPUT DROPS, STARTING
C1-1 FAN WHEN PRESSURE DROPS BELOW PE2 SETPOINT.
BK BK

C1-2 ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY


C NO BK JOB SPECIFICATIONS.
TC ST.1
BK BK C NO BK
PE-1 5 C1
NC BK BK
C
PE-3 L1 1
NO NC BL
ST.2 C1-1 3 L3
RD C NO RD RD RD
PE-2 C2 L2 2
NC C2-1
PE-4
NC OPTIONAL 2 STAGE HEAT
ST.3
BN C NO BN
C3
PE-5 BK BK
NC L1 1
BK BL/WH BK C1-1
SC FM RD RD
L2 2
C2-1
BN BN
BK
EP C3-1
BL BL
L3 3
C1-2
PNEUMATIC DIAGRAM PE1 P.E. SWITCH SUPPLIED BY FACTORY
OPTIONAL 3 STAGE HEAT
(SIGNAL BY OTHERS)
N.O.
RECOMMENDED FIELD P.E. SWITCH SETTINGS:
ACT. (3)C PE-2 = 8 PSI
(1)NC (2)NO PE-3 = 8 PSI
EP PE-4 = 10 PSI
PE-5 = 12 PSI
BAL. TAPS VEL. CNTRLR
B (RESET BAND=8-13 PSI)
FLOW LO Y
M 20 PSI MAIN CONSTANT
PROBE HI X
T VOLUME
TOTAL AIR
REV. R.A.. STAT
FLOW

RELAY 1 PIPE COLD AIR HEAT


AIR

AIR
M RESTRICTOR FLOW PLENUM AIR
1
3 OR OR 20 PSI MAIN

R.A.. STAT
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
2 PIPE
HOT T-STAT BRANCH PRESSURE (PSIG) COLD
PE5 PE4 PE3 PE2 ROOM ROOM

HEATER COMPONENTS MAX. KW


3 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-3 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 208 V 480 V P = 208V/3PH/60HZ - 1 STAGE 2 = PILOT DUTY P.E. W/ 30A
1 10.7 24.9 R = 208V/3PH/60HZ - 2 STAGE MAG. CONTACTOR
DE-ENERGIZING
CONTACTOR

30 AMP 2 5.3 12.4 1 = 208V/3PH/60HZ - 3 STAGE 3 = PILOT DUTY P.E. W/ 50A


PER STAGE 3 3.5 8.3
U = 480V/3PH/60HZ - 1 STAGE MAG. CONTACTOR
1 17.2 39.8
50 AMP W = 480V/3PH/60HZ - 2 STAGE 4 = PILOT DUTY P.E. W/ 30A
2 8.6 19.9 MERC. CONTACTOR
PER STAGE 3 = 480V/3PH/60HZ - 3 STAGE
3 5.7 13.2
5 = PILOT DUTY P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR


SIZE & TYPE

DOOR INTERLOCK 14.3 33.2

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 17.2 39.8
BLOCK

30 AMP BLOCK 8.6 19.9


FUSE

60 AMP BLOCK 17.2 39.8

1. MAX. K.W. BASED ON 48A, OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.016 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5G080

REV.1 8/5/00 PNEUMATIC


PSFH159
- J159 -

168 YORK INTERNATIONAL


FORM AD1T-SECT J

SERIES FLOW FAN TERMINAL W/ ELECTRIC HEAT


P.I., N.C. DAMPER, P.E. FAN START, UNOCCUPIED MODE, POS. DAMPER CLOSE OFF, D.A. STAT, 3 PHASE, PILOT DUTY P.E. SWITCH

SEQUENCE OF OPERATION:
L1 L2 L3
SIGNAL TO PE1 ENERGIZES THE FAN & EP SWITCH.
DISCONNECT
SPACE TEMP WARM (STAT OUTPUT HI). AT A STAT
SWITCH
OUTPUT OF 13 PSI THE VEL. CNTRLR WILL BE CONTROLLING
AT ITS MAXIMUM. AS THE SPACE TEMP FALLS, THE DAMPER
FUSING WILL MODULATE TOWARDS THE CLOSED POSITION. AT A
STAT OUTPUT OF 8 PSI, THE VEL. CNTRLR WILL BE
CONTROLLING AT ITS MINIMUM.
OPTIONAL DISCONNECT SWITCH ON A FURTHER DROP IN SPACE TEMP., PE2 WILL CLOSE
PANEL WIRING DIAGRAM AND OR FUSING ENERGIZING THE FIRST STAGE OF ELECTRIC HEAT.
L1 L2 L3 N AS THE SPACE TEMP INCREASES, THE SEQUENCE REVERSES.
TERMINAL 1 2 3 4
BLOCK UNOCCUPIED MODE:
BK WH
WHEN THE PRESSURE APPLIED TO PE1 (SET AND CONTROLLED
BK BL BY OTHERS) IS DROPPED BELOW ITS SETPOINT IT MAKES
TO NC CONTACT ENABLING PE2, TURNING OFF FAN AND
BK STANDARD 1 STAGE HEAT DEENERGIZING EP CAUSING THE DAMPER TO CLOSE.
G AS TEMP DROPS, STAT OUTPUT DROPS, STARTING
C1-1
BK BK FAN WHEN PRESSURE DROPS BELOW PE2 SETPOINT.

C1-2
ADJUST SPEED CONTROL TO OBTAIN CFM REQUIRED BY
C NO BK
JOB SPECIFICATIONS.
TC ST.1
BK BK C NO BK
PE-1 5 C1
NC BK BK
PE-3 L1 1
C NO NC BL
ST.2 C1-1 3 L3
RD C NO RD RD RD
C2 L2 2
PE-2
NC C2-1
PE-4
NC OPTIONAL 2 STAGE HEAT
ST.3
BN C NO BN
C3
PE-5 BK BK
NC L1 1
BK BL/WH BK C1-1
SC FM RD RD
L2 2
C2-1
BN BN
BK
EP C3-1
BL BL
L3 3
C1-2
P.E. SWITCH SUPPLIED BY FACTORY
PNEUMATIC DIAGRAM PE1
(SIGNAL BY OTHERS) OPTIONAL 3 STAGE HEAT
N.C.
ACT. RECOMMENDED FIELD P.E. SWITCH SETTINGS:
(3)C
PE-2 = 8 PSI
(1)NC (2)NO
PE-3 = 8 PSI
EP PE-4 = 6 PSI
BAL. TAPS VEL. CNTRLR PE-5 = 4 PSI
B (RESET BAND=3-8 PSI)
FLOW LO X CONSTANT
M 20 PSI MAIN
PROBE HI Y VOLUME
T TOTAL AIR
REV. D.A.. STAT HEAT COLD AIR
FLOW

RELAY 1 PIPE AIR


AIR

FLOW PLENUM AIR


M RESTRICTOR
1
3 OR OR 20 PSI MAIN

D.A.. STAT 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
2 PIPE COLD T-STAT BRANCH PRESSURE (PSIG) HOT
PE5 PE4 PE3 PE2 ROOM ROOM

HEATER COMPONENTS MAX. KW


3 PHASE-60 HZ VOLTAGES
VOLTAGE CODE-3 PHASE HEATER CONTROL CODE
HEATER VOLTAGE 208 V 480 V P = 208V/3PH/60HZ - 1 STAGE 2 = PILOT DUTY P.E. W/ 30A
1 10.7 24.9 R = 208V/3PH/60HZ - 2 STAGE MAG. CONTACTOR
DE-ENERGIZING
CONTACTOR

30 AMP 2 5.3 12.4 1 = 208V/3PH/60HZ - 3 STAGE 3 = PILOT DUTY P.E. W/ 50A


PER STAGE 3 3.5 8.3
U = 480V/3PH/60HZ - 1 STAGE MAG. CONTACTOR
1 17.2 39.8
50 AMP W = 480V/3PH/60HZ - 2 STAGE 4 = PILOT DUTY P.E. W/ 30A
2 8.6 19.9 MERC. CONTACTOR
PER STAGE 3 = 480V/3PH/60HZ - 3 STAGE
3 5.7 13.2
5 = PILOT DUTY P.E. W/ 50A
DISCONNECT

DNF-40 MERC. CONTACTOR


SIZE & TYPE

DOOR INTERLOCK 14.3 33.2

ALL CONTACTORS
DNF-80 ARE DE-ENERGIZING
DOOR INTERLOCK 17.2 39.8
BLOCK

30 AMP BLOCK 8.6 19.9


FUSE

60 AMP BLOCK 17.2 39.8

1. MAX. K.W. BASED ON 48A, OR CONTACTOR MAX. LOAD


2. SEE UNIT MODEL MAX. K.W. CHARTS FOR OTHER K.W. LIMITS
3. FUSING SIZED PER N.E.C. AT 125% OF SELECTED LOAD

ALL HEATERS ARE U.L. OR E.T.L. LISTED OPTIONAL WIRING OR PIPING


.016 SCFM = AIR CONSUMPTION (LESS STAT) FIELD WIRING OR PIPING CONTROL CODE: 5H080

REV.1 8/5/00 PNEUMATIC


PSFH160
- J160 -

YORK INTERNATIONAL 169


NOTES

170 YORK INTERNATIONAL


FORM AD1T-SECT J

NOTES

YORK INTERNATIONAL 171


P.O. Box 1592, York, Pennsylvania USA 17405-1592 Tele. 800-861-1001 Subject to change without notice. Printed in USA
Copyright © by York International Corporation 2000 www.york.com ALL RIGHTS RESERVED
Form AD1T-SECT J (1000)
New Release

You might also like