MODELS S, V, CD, SL
ES-11 THERMOSTAT
VAV COOLING ONLY
A1 1N000*0 1N000*0 A1
A1 1R000*0 1R000*0 A1
A2 1N000A0 1N000A0 A2
A2 1R000A0 1R000A0 A2
A3 1X000*0 1X000*0 A3
A3 1Y000*0 1Y000*0 A3
A4 1X000A0 1X000A0 A4
A4 1Y000A0 1Y000A0 A4
A5 11J00*0 11J00*0 A5
A5 11K00*0 11K00*0 A5
A6 11J00A0 11J00A0 A6
A6 11K00A0 11K00A0 A6
ELMSDCT1
-A.M1-
2 YORK INTERNATIONAL
FORM AD2T-SECT-A
Te m p m as t e r
R
ES-11 THERMOSTAT
VAV COOLING ONLY
A7 12B00*0 12B00*0 A7
A7 12C00*0 12C00*0 A7
A8 12B00A0 12B00A0 A8
A8 12C00A0 12C00A0 A8
A9 12E00*0 12E00*0 A9
A9 12F00*0 12F00*0 A9
ELMSDCT2
-A.M2-
YORK INTERNATIONAL 3
SINGLE DUCT
VAV COOLING
SEQUENCE OF OPERATION:
CW
2
COM
OR
CCW
YE
3
R B Y
ES-11
ELECTRIC T-STAT
PRIMARY
AIR
FLOW
DAMPER
CLOSED
COLD T-STAT SETPOINT HOT
ROOM ROOM
B = 120V/1PH/60HZ
V = 208V/1PH/60HZ
Q = 240V/1PH/60HZ
C = 277V/1PH/60HZ
SEQUENCE OF OPERATION
2
COM
OR
S2
NO
CCW
YE
3
BAL. TAPS
LO
FLOW LO
S2
R B Y PROBE HI
HI ADJ. PRESS. DIF.
ES-11 SWITCH
ELECTRIC T-STAT
FLOW
AIR
NOTE: ELECTRIC ACTUATOR SHOWN WIRED FOR CW DAMPER OPEN. HI-LIMIT CONTROL PIPING
FOR CCW DAMPER OPEN, CONNECT YELLOW LINE FROM S2 (NO)
TERMINAL TO (CW) ACTUATOR TERMINAL AND CONNECT BLUE LINE
HI-LIMIT
FROM S2 (NC) TERMINAL TO (CCW) ACTUATOR TERMINAL.
SETTING
PRIMARY
AIR
FLOW
DAMPER
CLOSED
COLD T-STAT SETPOINT HOT
ROOM ROOM
B = 120V/1PH/60HZ
V = 208V/1PH/60HZ
Q = 240V/1PH/60HZ
C = 277V/1PH/60HZ
ELSDC001
-A1-
4 YORK INTERNATIONAL
FORM AD2T-SECT-A
SINGLE DUCT
VAV COOLING, XFMR BY OTHERS
SEQUENCE OF OPERATION:
CW
2
COM
OR
CCW
YE
3
R B Y
ES-11
ELECTRIC T-STAT
SEQUENCE OF OPERATION
OR
S2
NO
CCW
YE
3
BAL. TAPS
LO
FLOW LO
S2
PROBE HI
HI ADJ. PRESS. DIF.
R B Y SWITCH
ES-11
FLOW
AIR
ELECTRIC T-STAT
ELSDC002
-A2-
YORK INTERNATIONAL 5
SINGLE DUCT
VAV COOLING, C.O. STAT
SEQUENCE OF OPERATION:
CW
COM
OR WARM UP MODE:
WITH WARM AIR BEING SENSED IN THE MAIN
CCW
YE
DUCT AND THE STAT CALLING FOR HEAT,
THE PRIMARY AIR DAMPER WILL OPEN. AS
R1 R2 SPACE TEMPERATURE INCREASES, THE DAMPER
CHANGEOVER WILL MODULATE TOWARDS THE CLOSED POSITION.
T-STAT WHEN COLD AIR IS SENSED IN THE DUCT, THE
CONTROL REVERTS BACK TO THE NORMAL
SENSING BULB
COOLING MODE OF OPERATION.
LOCATED IN
Y1 B1 B2 Y2 DUCTWORK
NOTE: CHANGE-OVER STAT SHOWN IN
STANDARD COOLING MODE.
BL YE
1 2 3
DAMPER
OPEN
R B Y
PRIMARY
ES-11 AIR
FLOW
ELECTRIC T-STAT
DAMPER
CLOSED
COLD T-STAT SETPOINT HOT
NOTE: ELECTRIC ACTUATOR SHOWN WIRED FOR CW DAMPER OPEN.
ROOM ROOM
FOR CCW DAMPER OPEN, CONNECT LINE FROM TERMINAL #2 B = 120V/1PH/60HZ
TO CCW TERMINAL, AND LINE FROM TERMINAL #3 TO CW TERMINAL
V = 208V/1PH/60HZ
ON ACTUATOR.
Q = 240V/1PH/60HZ
C = 277V/1PH/60HZ
SEQUENCE OF OPERATION
COM
OR
S2 WARM UP MODE:
NO
CCW
BL YE
BAL. TAPS
1 2 3 LO
FLOW LO HI-LIMIT
S2 SETTING
PROBE HI
HI ADJ. PRESS. DIF.
R B Y SWITCH
PRIMARY
ES-11
FLOW
AIR
AIR
ELSDC003
-A3-
6 YORK INTERNATIONAL
FORM AD2T-SECT-A
SINGLE DUCT
VAV COOLING, C.O. STAT, XFMR BY OTHERS
SEQUENCE OF OPERATION:
CW
COM
OR WARM UP MODE:
WITH WARM AIR BEING SENSED IN THE MAIN
CCW
YE
DUCT AND THE STAT CALLING FOR HEAT,
THE PRIMARY AIR DAMPER WILL OPEN. AS
R1 R2 SPACE TEMPERATURE INCREASES, THE DAMPER
CHANGEOVER WILL MODULATE TOWARDS THE CLOSED POSITION.
T-STAT WHEN COLD AIR IS SENSED IN THE DUCT, THE
CONTROL REVERTS BACK TO THE NORMAL
SENSING BULB
COOLING MODE OF OPERATION.
LOCATED IN
Y1 B1 B2 Y2 DUCTWORK
NOTE: CHANGE-OVER STAT SHOWN IN
STANDARD COOLING MODE.
BL YE
1 2 3
DAMPER
OPEN
R B Y
PRIMARY
ES-11 AIR
FLOW
ELECTRIC T-STAT
DAMPER
CLOSED
COLD T-STAT SETPOINT HOT
NOTE: ELECTRIC ACTUATOR SHOWN WIRED FOR CW DAMPER OPEN.
ROOM ROOM
FOR CCW DAMPER OPEN, CONNECT LINE FROM TERMINAL #2
TO CCW TERMINAL, AND LINE FROM TERMINAL #3 TO CW TERMINAL
ON ACTUATOR.
SEQUENCE OF OPERATION
COM
OR
S2 WARM UP MODE:
NO
CCW
BL YE
BAL. TAPS
1 2 3 LO
FLOW LO HI-LIMIT
S2 SETTING
PROBE HI
HI ADJ. PRESS. DIF.
R B Y SWITCH
PRIMARY
ES-11
FLOW
AIR
AIR
ELSDC004
-A4-
YORK INTERNATIONAL 7
SINGLE DUCT
VAV COOLING, C.O. RELAY
SEQUENCE OF OPERATION
COM
OR THE PRIMARY AIR DAMPER WILL OPEN. AS
SPACE TEMPERATURE INCREASES, THE DAMPER
CCW
YE
WILL MODULATE TOWARDS THE CLOSED POSITION.
WHEN CHANGE-OVER RELAY IS DE-ENERGIZED
(BY OTHERS) THE CONTROL REVERTS BACK TO
BK A B OR THE NORMAL COOLING MODE OF OPERATION.
8 7 CHANGEOVER 9 K1 8
RELAY NOTE: CHANGE-OVER RELAY SHOWN IN
STANDARD COOLING MODE.
24V AC
K1-2
K1-1
SIGNAL BY OTHERS
5 1
2 4
BL YE
DAMPER
1 2 3 OPEN
PRIMARY
R B Y AIR
FLOW
ES-11
DAMPER
ELECTRIC T-STAT
CLOSED
COLD T-STAT SETPOINT HOT
ROOM ROOM
B = 120V/1PH/60HZ
NOTE: ELECTRIC ACTUATOR SHOWN WIRED FOR CW DAMPER OPEN.
FOR CCW DAMPER OPEN, CONNECT LINE FROM TERMINAL #2 V = 208V/1PH/60HZ
TO CCW TERMINAL, AND LINE FROM TERMINAL #3 TO CW TERMINAL Q = 240V/1PH/60HZ
ON ACTUATOR. C = 277V/1PH/60HZ
SEQUENCE OF OPERATION
C NC WARM UP MODE:
BL BL
CW
YE
SPACE TEMPERATURE INCREASES, THE DAMPER
WILL MODULATE TOWARDS THE CLOSED POSITION.
WHEN CHANGE-OVER RELAY IS DE-ENERGIZED
BK A B OR (BY OTHERS) THE CONTROL REVERTS BACK TO
8 7 CHANGEOVER 9 K1 8 THE NORMAL COOLING MODE OF OPERATION.
RELAY
NOTE: CHANGE-OVER RELAY SHOWN IN
24V AC
K1-2
K1-1
ES-11 FLOW
AIR
DAMPER
ELECTRIC T-STAT
CLOSED
HI-LIMIT CONTROL PIPING COLD T-STAT SETPOINT HOT
ROOM ROOM
NOTE: ELECTRIC ACTUATOR SHOWN WIRED FOR CW DAMPER OPEN. B = 120V/1PH/60HZ
FOR CCW DAMPER OPEN, CONNECT YELLOW LINE FROM S2 (NO) V = 208V/1PH/60HZ
TERMINAL TO (CW) ACTUATOR TERMINAL AND CONNECT BLUE LINE
FROM S2 (NC) TERMINAL TO (CCW) ACTUATOR TERMINAL. Q = 240V/1PH/60HZ
C = 277V/1PH/60HZ
ELSDC005
-A5-
8 YORK INTERNATIONAL
FORM AD2T-SECT-A
SINGLE DUCT
VAV COOLING, C.O. RELAY, XFMR BY OTHERS
SEQUENCE OF OPERATION
CW
(BY OTHERS) AND THE STAT CALLING FOR HEAT,
COM
OR THE PRIMARY AIR DAMPER WILL OPEN. AS
SPACE TEMPERATURE INCREASES, THE DAMPER
CCW
YE
WILL MODULATE TOWARDS THE CLOSED POSITION.
WHEN CHANGE-OVER RELAY IS DE-ENERGIZED
(BY OTHERS) THE CONTROL REVERTS BACK TO
THE NORMAL COOLING MODE OF OPERATION.
BK A B OR
8 7 CHANGEOVER 9 K1 8
RELAY NOTE: CHANGE-OVER RELAY SHOWN IN
STANDARD COOLING MODE.
K1-2
K1-1
24V AC
SIGNAL BY OTHERS
5 1
2 4
BL YE
DAMPER
1 2 3 OPEN
PRIMARY
R B Y AIR
FLOW
ES-11
DAMPER
ELECTRIC T-STAT
CLOSED
COLD T-STAT SETPOINT HOT
ROOM ROOM
NOTE: ELECTRIC ACTUATOR SHOWN WIRED FOR CW DAMPER OPEN.
FOR CCW DAMPER OPEN, CONNECT LINE FROM TERMINAL #2
TO CCW TERMINAL, AND LINE FROM TERMINAL #3 TO CW TERMINAL
ON ACTUATOR.
SEQUENCE OF OPERATION
C NC WARM UP MODE:
BL BL
CW
YE
SPACE TEMPERATURE INCREASES, THE DAMPER
WILL MODULATE TOWARDS THE CLOSED POSITION.
WHEN CHANGE-OVER RELAY IS DE-ENERGIZED
(BY OTHERS) THE CONTROL REVERTS BACK TO
BK A B OR
CHANGEOVER 9 K1 8 THE NORMAL COOLING MODE OF OPERATION.
8 7
RELAY
NOTE: CHANGE-OVER RELAY SHOWN IN
K1-2
K1-1
ES-11 FLOW
AIR
DAMPER
ELECTRIC T-STAT
CLOSED
HI-LIMIT CONTROL PIPING COLD T-STAT SETPOINT HOT
ROOM ROOM
NOTE: ELECTRIC ACTUATOR SHOWN WIRED FOR CW DAMPER OPEN.
FOR CCW DAMPER OPEN, CONNECT YELLOW LINE FROM S2 (NO)
TERMINAL TO (CW) ACTUATOR TERMINAL AND CONNECT BLUE LINE
FROM S2 (NC) TERMINAL TO (CCW) ACTUATOR TERMINAL.
ELSDC006
-A6-
YORK INTERNATIONAL 9
SINGLE DUCT
VAV COOLING
SEQUENCE OF OPERATION:
ES-11
ELECTRIC T-STAT
DAMPER
OPEN
PRIMARY
AIR
FLOW
DAMPER
CLOSED
COLD T-STAT SETPOINT HOT
ROOM ROOM
B = 120V/1PH/60HZ
V = 208V/1PH/60HZ
Q = 240V/1PH/60HZ
C = 277V/1PH/60HZ
SEQUENCE OF OPERATION
HI-LIMIT
SETTING
PRIMARY
AIR
FLOW
DAMPER
CLOSED
COLD T-STAT SETPOINT HOT
ROOM ROOM
B = 120V/1PH/60HZ
V = 208V/1PH/60HZ
Q = 240V/1PH/60HZ
C = 277V/1PH/60HZ
ELSDC007
-A7-
10 YORK INTERNATIONAL
FORM AD2T-SECT-A
SINGLE DUCT
VAV COOLING, XFMR BY OTHERS
SEQUENCE OF OPERATION:
R B Y
ES-11
ELECTRIC T-STAT
DAMPER
OPEN
PRIMARY
AIR
FLOW
DAMPER
CLOSED
COLD T-STAT SETPOINT HOT
ROOM ROOM
SEQUENCE OF OPERATION
ELECTRIC T-STAT
HI-LIMIT
SETTING
PRIMARY
AIR
FLOW
DAMPER
CLOSED
COLD T-STAT SETPOINT HOT
ROOM ROOM
ELSDC008
-A8-
YORK INTERNATIONAL 11
SINGLE DUCT
VAV COOLING, C.O. STAT
SEQUENCE OF OPERATION:
BL YE
1 2 3
DAMPER
OPEN
R B Y
PRIMARY
ES-11 AIR
FLOW
ELECTRIC T-STAT
DAMPER
CLOSED
COLD T-STAT SETPOINT HOT
ROOM ROOM
B = 120V/1PH/60HZ
V = 208V/1PH/60HZ
Q = 240V/1PH/60HZ
C = 277V/1PH/60HZ
SEQUENCE OF OPERATION
BL YE
BAL. TAPS
1 2 3 LO
FLOW LO HI-LIMIT
S2 SETTING
PROBE HI
HI ADJ. PRESS. DIF.
R B Y SWITCH
PRIMARY
ES-11
FLOW
AIR
AIR
ELSDC009
-A9-
12 YORK INTERNATIONAL
FORM AD2T-SECT-A
SINGLE DUCT
VAV COOLING, C.O. STAT, XFMR BY OTHERS
SEQUENCE OF OPERATION:
BL YE
1 2 3
DAMPER
OPEN
R B Y
PRIMARY
ES-11 AIR
FLOW
ELECTRIC T-STAT
DAMPER
CLOSED
COLD T-STAT SETPOINT HOT
ROOM ROOM
SEQUENCE OF OPERATION
BL YE
BAL. TAPS
1 2 3 LO
FLOW LO HI-LIMIT
S2 SETTING
PROBE HI
HI ADJ. PRESS. DIF.
R B Y SWITCH
PRIMARY
ES-11
FLOW
AIR
AIR
ELSDC010
-A10-
YORK INTERNATIONAL 13
SINGLE DUCT
VAV COOLING, C.O. RELAY
SEQUENCE OF OPERATION
K1-1
24V AC
5 1 SIGNAL BY OTHERS
2 4
BL YE
DAMPER
1 2 3 OPEN
PRIMARY
R B Y AIR
FLOW
ES-11
DAMPER
ELECTRIC T-STAT
CLOSED
COLD T-STAT SETPOINT HOT
ROOM ROOM
B = 120V/1PH/60HZ
V = 208V/1PH/60HZ
Q = 240V/1PH/60HZ
C = 277V/1PH/60HZ
SEQUENCE OF OPERATION
C NC C NC WARM UP MODE:
BL BL OR
OPEN WITH THE CHANGE-OVER RELAY (K1) ENERGIZED,
LSE NO (BY OTHERS) AND THE STAT CALLING FOR HEAT,
S2
NO YE C NC OR THE PRIMARY AIR DAMPER WILL OPEN. AS
CLOSE SPACE TEMPERATURE INCREASES, THE DAMPER
LSR NO WILL MODULATE TOWARDS THE CLOSED POSITION.
BN WHEN CHANGE-OVER RELAY IS DE-ENERGIZED
10 (BY OTHERS) THE CONTROL REVERTS BACK TO
CHANGEOVER THE NORMAL COOLING MODE OF OPERATION.
8 7 BK A B OR
RELAY 9 K1 8
NOTE: CHANGE-OVER RELAY SHOWN IN
K1-2
K1-1
ES-11 FLOW
AIR
DAMPER
ELECTRIC T-STAT
CLOSED
HI-LIMIT CONTROL PIPING COLD T-STAT SETPOINT HOT
ROOM ROOM
B = 120V/1PH/60HZ
V = 208V/1PH/60HZ
Q = 240V/1PH/60HZ
C = 277V/1PH/60HZ
ELSDC011
-A11-
14 YORK INTERNATIONAL
FORM AD2T-SECT-A
SINGLE DUCT
VAV COOLING, C.O. RELAY, XFMR BY OTHERS
SEQUENCE OF OPERATION
K1-1
24V AC
5 1 SIGNAL BY OTHERS
2 4
BL YE
DAMPER
1 2 3 OPEN
PRIMARY
R B Y AIR
FLOW
ES-11
DAMPER
ELECTRIC T-STAT
CLOSED
COLD T-STAT SETPOINT HOT
ROOM ROOM
SEQUENCE OF OPERATION
C NC C NC WARM UP MODE:
BL BL OR
OPEN WITH THE CHANGE-OVER RELAY (K1) ENERGIZED,
LSE NO (BY OTHERS) AND THE STAT CALLING FOR HEAT,
S2
NO YE C NC OR THE PRIMARY AIR DAMPER WILL OPEN. AS
CLOSE SPACE TEMPERATURE INCREASES, THE DAMPER
LSR NO WILL MODULATE TOWARDS THE CLOSED POSITION.
BN WHEN CHANGE-OVER RELAY IS DE-ENERGIZED
10 (BY OTHERS) THE CONTROL REVERTS BACK TO
CHANGEOVER THE NORMAL COOLING MODE OF OPERATION.
8 7 BK A B OR
RELAY 9 K1 8
NOTE: CHANGE-OVER RELAY SHOWN IN
K1-2
K1-1
ES-11 FLOW
AIR
DAMPER
ELECTRIC T-STAT
CLOSED
HI-LIMIT CONTROL PIPING COLD T-STAT SETPOINT HOT
ROOM ROOM
ELSDC012
-A12-
YORK INTERNATIONAL 15
P.O. Box 1592, York, Pennsylvania USA 17405-1592 Tele. 800-861-1001 Subject to change without notice. Printed in USA
Copyright © by York International Corporation 2000 www.york.com ALL RIGHTS RESERVED