IM30T DataSheet - en 71

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

M

LINE

IM30-T NC. N7-R1

THREE-PHASE THERMAL + OVERCURRENT +


EARTH FAULT RELAY

46, 49, 50/51, 50N/51N, 51BF, 68, I2t


T> I>->> I2t Io>->>

· Three Phase-Fault levels PROG/ BLOCK BR. Is>->>


I.R.F. INPUT FAIL.

· Three Earth-Fault levels


MICROELETTRICA SCIENTIFICA I/In 100%
· Two Thermal image elements with prealarm MILANO ITALIA

· Two Negative Sequence current levels MODE SELECT


+

· One I2t level MULTIFUNCTION


THERMAL +
_
· Blocking Output and Blocking Input for pilot wire OVERCURRENT +
EARTH FAULT
PROG.
RELAY TYPE
selectivity coordination IM30-T

· Breaker Failure protection ENTET/RESET

· Modbus Communication Protocol


· UL / CSA listed

Three-phase thermal plus overcurrent plus earth fault relay, suitable for protection of transformers and
HV & MV, power transmission and distribution systems.

The relay computes the direct and the negative sequence components of the current system for effective
negative sequence current protection.

Selectable 1 or 5 A rating for phase as well as neutral inputs.

The neutral current input circuits include a 3rd harmonic active filter.

Real Time Measurements = IA - IB - IC - Io - Tw - Tf - I1 - I2


Maximum Demand and Inrush Recording = IA - IB - IC - Io - Tw - Tf - I2

Programmable Input Quantities


Fn = System frequency : (50 - 60)Hz

In = Rated primary current of phase CTs : (0 - 9999)A, step 1A

On = Rated primary current of earth fault detection CTs : (0 - 9999)A, step 1A

1F - 50/51 (I>): First Overcurrent Element


- Current setting range : I> = (0.25 - 4)In, step 0.01In
- Instantaneous output : £ 0.03s
- Definite trip time delay in the independent time operation mode tI> = (0.05 - 30)s, step 0.01s
- Trip time delay at 10x[I>] in inverse time operation modes }
Operation mode F(I>): F(I>) = D : Independent definite time F(I>) = MI : IEEE moderate inverse time curve
F(I>) = A : IEC curve type A F(I>) = VI : IEEE very inverse time curve
F(I>) = B : IEC curve type B F(I>) = I : IEEE inverse time curve
F(I>) = C : IEC curve type C F(I>) = EI : IEEE extremely inverse time curve
F(I>) = SI : IEEE standard inverse time curve
NC.N7- RI IM30-T

2F - 50/51 (I>>): Second Overcurrent Element


- Current setting range : I>> = (0.5 - 40)In, step 0.1In
- Instantaneous output : £ 0.03s
- Independent time delay : tI>> = (0.05 - 3)s, step 0.01s
- Automatic doubling of level I>> on inrush : I>>x2 = ON/OFF

3F - 50/51 (I>>>): Third Overcurrent Element


- Current setting range : I>>> = (0.5 - 40)In, step 0.1In
- Instantaneous output : £ 0.03s

1F - 50N/51N (O>): First Earth Fault Element


- Current setting range : O> = (0.02 - 0.4)On, step 0.01On
- Instantaneous output : £ 0.04s
}
- Definite trip time delay in the independent time operation mode tO> = (0.05 - 30)s, step 0.01s
- Trip time delay at 10x[O>] in inverse time operation modes
Operation mode F(O>): F(O>) = D : Independent definite time F(O>) = MI : IEEE moderate inverse time curve
F(O>) = A : IEC curve type A F(O>) = VI : IEEE very inverse time curve
F(O>) = B : IEC curve type B F(O>) = I : IEEE inverse time curve
F(O>) = C : IEC curve type C F(O>) = EI : IEEE extremely inverse time curve
F(O>) = SI : IEEE standard inverse time curve

2F - 50N/51N (O>>): Second Earth Fault Element


- Current setting range : O>> = (0.02 - 4)On, step 0.01On
- Instantaneous element : £ 0.04s
- Independent time delay : tO>> = (0.05 - 3)s, step 0.01s

3F - 50N/51N (O>>>): Third Earth Fault Element


- Current setting range : O>>> = (0.02 - 4)On, step 0.01On
- Instantaneous output : £ 0.04s

F49 : Thermal Image


- Rated thermal current : It = (0.5 - 2)In, step 0.01In
- Windings' warming up time constant : tw = (1 - 60)min, step 1min.
- Windings continuous admissible overload : Ibw = (1.05 - 1.5)It, step 0.01It
- Oil/Iron warming up time constant : tf = (10 - 400)min, step 1min.
- Temperature prealarm : Ta/n = (50 - 120)%Tn, step 1%Tn

1F - 46 : First Current Unbalance (Negative Sequence)


- Current setting range : 1Is = (0.1 - 0.8)It, step 0.1It
- Independent time delay : t1Is = (1 - 8)s, step 1s (t1Is = trip time @ Is = It)

2F - 46 : Second Current Unbalance (Negative Sequence)


- Current setting range : 2Is = (0.2 - 2)It, step 0.1It
- Independent time delay : t2Is = (0.05 - 3)s, step 0.01s

F I²t>: Inrush Energy


This element performs a max I²t protection; tripping takes place when I²t > (2It)²t2
- Starting level : I > 2It (It = Rated thermal current, same as for F49)
- Trip time delay @ I=2It : t2 = (0.1 - 10 - Dis)s, step 0.1s

Breaker Failure Element


- Trip time delay : tBF = (0.05 - 0.25)s, step 0.01s
IM30-T NC.N7-RI

Connexion Diagram

IM30-T

RS485 RS485

MS-SCE1358-R3 MS-SCE1434-R1
Standard Output Double Output

Ordering data

Power supply
0 Type 1 : 24 à 100 Vac et 24 à 125 Vdc ± 20 %.
0 Type 2 : 80 à 220 Vac et 90 à 250 Vdc ± 20 %.

Execution
0 Flush mounting
0 Surface mounting
0 Standard rack 19”3U

Rated input
0 In = 1 A
0 In = 5 A

Special request