Flexible control every step of the way


A simple wireless lighting control solution
for new and existing commercial buildings.
Scalable solutions — start small and grow Energy-saving control strategies

Vive wireless solutions offer a multi-strategy approach that accommodates your Combine lighting control strategies to maximize efficiency
budget and performance needs now, and for the future of your building.
 hat is the savings opportunity?
W
Lutron solutions can save 60%3 or more lighting energy.

Potential savings

1 2 3 4 Occupied: On Vacant: Off


Occupancy/vacancy sensing turns lights on
when occupants are in a space and off when they
vacate the space.
20 – 60%
Lighting4

Daylight harvesting dims electric lights when 25 – 60%


daylight is available to light the space. Lighting5
Full On Dim

Scheduling provides pre-programmed 10 – 20%


changes in light levels based on time of day. Lighting6
7am: Dim 7pm: Off

Demand response automatically reduces 30 – 50%


lighting loads during peak electricity usage times.
Full On Dim
Peak Period7

Single office Single Multiple Entire Plug load control automatically turns off loads 15 – 50%
after occupants leave a space. Controlled Load8
space floor floors building Appliance On Appliance Off

Start by adding Expand to new areas Duplicate the Vive offers seamless
control in a single or an entire floor at success of one floor integration to other
80%
High-end trim sets the maximum light level 10 – 30%
space and expand any time without across other floors building management based on customer requirements in each space. Lighting9
as budgets reprogramming or as your business systems to control every Max: 100% Max: 80%

and occupant replacing existing expands or tenants light in your building.


schedules allow. equipment. change. Control can
be independent on Personal dimming control gives occupants 10 – 20%
each floor, or linked the ability to adjust the light level. Lighting10
Full On Dim
via Vive wireless hubs.

HVAC integration controls heating,


ventilation, and air conditioning systems 5 – 15%
through contact closure, or BACnet protocol. HVAC11
Heating Cooling

System Optimization Service from Lutron identifies


Saving Saving
important lighting control adjustments to save additional
60 %
70 %
energy and create a more productive work environment Variable
Before After on an ongoing basis.

2 | Lutron Lutron | 3
For a list of sources please visit lutron.com/references.
Transform existing buildings with wireless lighting controls

Flexible, wireless controls and sensors


for simple, code-compliant design
Simple-to-use software

Add wireless hubs for centralized


Remotes
control and integration (optional)

Occupancy and
daylight sensors

Vive wireless hub

Lighting controllers Emergency lighting


controllers
Wired/
Ethernet

Plug load controllers


Demand BACnet Vive Vue software
response integration

Communication protocols

Communicate via RF Communicate via WiFi Communicate via wired


to control components to smart devices Ethernet to Vive hub

Integrated fixture
control and sensing

4 | Lutron Lutron | 5
Solutions for every space and budget DESIGN

The right control in the right space


The Vive product family lets you personalize control to each space in your
building without locking you into more or less control than you need

Simple switching

Restroom
Occupancy sensors control all lights together
by switching lights on and off in response to
room occupancy.

Switch | Occupancy sensor

Area dimming and sensing

Private office
Dim a group of lights together while also
providing manual control. Save additional
energy with daylight harvesting.

Dimming module | Occupancy sensor | Daylight sensor | Pico remote

Individual fixture dimming and sensing

Open office
Reduce labor cost while maximizing energy Vive wireless solutions — Choose any load and control type
savings to give each occupant personal
dimming control — increase comfort and
Any control type Any load type
enhance productivity.
• High-performance
dimming with Lutron
Hi-lume EcoSystem

Fixture control | Pico remote Other control types


– 0-10 V LED Incandescent/ Fluorescent Magnetic Electronic CFL


– Phase control halogen low voltage low voltage
– Switching
– CCO

6 | Lutron Lutron | 7
Flexible installation INSTALL

Simple retrofit — installs 70%1 faster than wired systems Wallbox mount


Vive wireless solutions reduce installation time and cost regardless of where they are installed or which or solution you choose.

Wallbox mount
• Replace an existing switch in a standard wallbox to
control a group of lights
• No new wiring required – works with the existing wiring
• Switching and dimming options available
• Communicates wirelessly to sensors and remotes

Wireless switch/dimmer
Ceiling mount

Ceiling mount
• PowPak modules mount on a standard junction box
in the ceiling to control a group of lights
• Saves installation time by eliminating wiring down
through walls
• Switching and dimming options available
• Communicates wirelessly to sensors and remotes

PowPak with J-box

Vive-enabled fixtures
Vive-enabled fixtures
• Wireless control and sensing built into the fixture
at the factory
• Simple to design and estimate—just count the fixtures
• No additional wiring
– Works with existing high-voltage wiring,
regardless of room layout
– No new wiring between fixtures
• Provides personal control for each occupant to
maximize comfort and energy savings
• Communicates wirelessly to sensors and remotes
Integral fixture control

8 | Lutron Lutron | 9
For a list of sources please visit lutron.com/references.
Easy setup INSTALL

Simple setup and programming options with the Vive wireless hub For systems without a Vive wireless hub

Mobile phone setup


Using Vive Vue software on any smart device you can wirelessly Automatic fixture identification
connect system controls and program system settings—no ladder 1 Press and hold on 2 Push button set up
required. Lutron’s patent pending RF signal strength detection
wireless device Lutron patent pending technology Use simple button-press programming to select and
automatically finds nearby devices making job setup faster. automatically finds and sorts the wireless associate wireless devices—it’s as easy as setting a
devices closest to the control station on your car radio.

Wireless dimmer

Press and hold for 6 seconds

Occupancy sensor

Press and hold for 6 seconds


It works! Sensor now talks to the wireless dimmer

10 | Lutron Lutron | 11
Save energy and improve building performance MAINTAIN

Energy reporting Load shed Schedules Light Control


Quickly view and display energy-usage information Easily set lighting reduction levels that automatically Use a 365 day calendar to automatically adjust lights based Directly adjust the light levels.
to drive decision making and demonstrate savings. respond during peak electricity usage times. on time of day, including single day and holiday events

Seamlessly integrate with your building system


Building/Energy Management Energy Dashboards and
The BACnet/IP protocol is the primary means of integration. BACnet is embedded or
Systems (BMS/EMS) Analytics Packages
native in the Vive wireless hub, which means no external interfaces or gateways are
required in order to communicate with other systems.

HVAC Audio & Video IT

12 | Lutron Lutron | 13
A smart building is now simple

Vive Vue software


Vive Vue software now provides the ability to tie multiple Vive hubs together in one software interface. Built with the simple, Intuitive control
scalable, wireless building blocks of the Vive Wireless system, Vive Vue software now delivers the advanced intelligence
necessary for today’s smart buildings and the IoT. A smart building is now easier than ever to achieve. View status, control lights, and optimize your building quickly
and efficiently with a graphical floorplan.

Optimize your space


Improve building layout based on actual occupancy and usage
information. With space utilization reports, you can quickly
identify over-used and under-used spaces to improve building
efficiency without expanding the building footprint.

Save energy purposefully


Energy reports allow you to view and monitor your energy
savings. With trending energy information over time, and easily
customizable reports, Vive Vue software helps you demonstrate
the energy-saving advantages of wireless lighting control.

14 | Lutron Lutron | 15
Enterprise Vue – Connected campus

Manage data and operations for multiple


Lutron lighting and shade control solutions
• A single data and management platform for your connected buildings
• The system interface delivers a simple, consistent user experience from any PC or tablet
• Open, easy integration with BACnet and web APIs leverages the IoT to enhance smart-building performance

Limelight Limelight

Enterprise Vue home screen

16 | Lutron Lutron | 17
Lutron security Lutron reliability

Clear Connect wireless technology


We build security into the product and the process from conception All Lutron wireless products utilize Lutron patented Clear Connect wireless technology which operates in an
to installation, and through the lifetime of the system. uncongested radio frequency band. The result is ultra-reliable communication and smooth dimming performance
with no flicker or delay. Other devices will not interfere with the Lutron lighting control system.

Everything we do is backed by Lutron’s first, and guiding, principle — Take Care of the
Customer with Superior Goods and Services. Every product, every system, and every
solution is designed, manufactured and tested to work as expected.

Clear Connect

Security by Design 3rd Party Validation



When building any new system, Lutron utilizes Security is complicated. Lutron has a dedicated team of
a dedicated security team to ensure best internal experts, but we also leverage external experts to
practices are implemented. Security is built-in. double- and triple-check our work.
It is not an afterthought or add on. 434 MHz: Lutron Clear Connect wireless technology
1. Multiple external experts engaged during
Examples of security features designed Lutron devices operate in an uncongested frequency band,
design process
into Vive include: providing ultra-reliable operation.
2. 3rd-Party penetration testing to identify and fix potential
1. Isolated wired and wireless architecture which vulnerabilities before they reach the field
strictly limits the possibility of the Vive Wi-Fi or
ClearConnect being used to access the corporate
network to gain confidential information Continuous Monitoring
2. A distributed security architecture — each hub and Improvements
has its own unique keys Security is a constantly moving target. Lutron uses “Other” frequency bands
a dedicated security team to continuously monitor the
3. NIST-recommended best practices for securing
market for potential threats and, when needed, send out
passwords, including salting and use of SCrypt
security patches to update installed systems.
4. AES 128-bit encryption for network communications

5. HTTPS (TLS 1.2) protocol for securing connections


to the hub over the wired network
Ongoing Support
Lutron has the resources you need to answer questions
6. WPA2 technology for securing connections to the about security when they arise.
hub over the Wi-Fi network
1. IT deployment guides

2. Guidance from our world class 24/7 technical


2.4 GHz: Cordless phones | Bluetooth devices | Wireless security cameras
support organization with IT expertise throughout
the product lifecycle Other devices operate in congested frequency bands, creating a high potential for wireless interference.

18 | Lutron Lutron | 19
Lutron technology and tools Lutron service and support

XCT sensing technology Setup the system yourself, or choose the right mix of support services.
Lutron’s occupancy sensing won’t leave occupants in the dark and eliminates callbacks Lutron offers a variety of flexible, scalable support options to meet the needs of your project and your budget.
• Lutron sensors provide exceptional prevention of false-ons and false-offs
• Superior sensitivity—recognizes the difference between fine human motion and background noise

Do it yourself Get a little help Leave the setup to us

Vive is designed to make If you’re looking for some extra If you prefer, the Lutron Services
installation and setup easy. peace of mind, Lutron Services Team can execute the full
Instructions are included with the can be purchased in flexible blocks system setup.
Major Motion Minor Motion product, and comprehensive, of time to provide just the right
Both remote and onsite setup
online help is available 24/7 on amount of support.
services are available. Remote
Person walking 3 feet Movements like extending our arms Lutron.com/ViveResources.
The Services Team can provide startup is generally a lower cost
Simple-to-follow videos and training, walk you through setup option and requires less lead time.
product guides are just a for a specific project area, answer
Remote setup — a designated
click away. any other questions you have, or
member of your team works with
help finish setup by closing
an off-site, Lutron-certified remote
punch-list items.
technician.
Choose from remote (online or Onsite setup — a Lutron-certified
phone-based) setup support, or service technician will perform
have a Lutron Service Technician the complete system setup at
come to your site. your project site.

Fine Motion No False-on

Small movements like Lights stay off when room is unoccupied


flipping pages of a book

If you are not sure what kind of support you need, Lutron can help.
Contact your local Lutron sales representative to discuss your project.

20 | Lutron Lutron | 21
The benefits: Simple to design Easily meet code

Access to tools and resources is at your fingertips. Summary of code requirements for lighting control
Exclusive access and quick answers keep your project moving. Vive wireless solutions ensure you can meet new construction and retrofit (lighting alterations12)
code requirements for ASHRAE 2010, ASHRAE 2013, IECC 2012, IECC 2015, and Title 24-201613.

For specific commercial building code lighting requirements in your state, please visit
Designer+ for Vive www.lutron.com/energycodes.
Lutron Designer+ for Vive is an intuitive, easy-to-use software tool
that allows you to design a Lutron Vive lighting control system with
visual “drag and drop” layout and connections. It also allows you to
generate comprehensive system design documentation, including
bills of materials, one-line diagrams, and sequence of operations. Vive Solutions

App guides to help you meet codes


Vive Solut
ions
ions
Vive Solut Commercial Application Guide

For access please contact myLutronsupport@lutron.com.


Code Compliance | Lighting Controls
Commerc
ial Applicatio
n Guide ANSI/ASHRAE/IES 90.1 2013 Code Com n Guide
ial Applicatio Controls pliance
Commerc | Lighting | Lighting
pliance 1 2010 Title 24-201 Cont rols
Code Com 90.
RAE/IES 6
ANSI/ASH

ions
Vive Solut
ions
Codes can often be complicated and difficult to navigate. We have commercial
Vive Solut

Commerc
Code Com
ial Applicatio
pliance
n Guide
| Lighting
Controls
Commerc
Code Com
IECC 201
ial Applicatio
pliance
n Guide
| Lighting
Cont rols
application guides that include examples of different spaces and corresponding
5

Lutron products for those spaces. Guides show you how you can use Lutron
2
IECC 201

Vive videos solutions to meet or exceed major energy code requirements.


Get access to Lutron Vive videos 24/7. Step-by-step setup,
installation, and programming help whenever you need it. Available online at www.lutron.com/appguides
Lutron.com/ViveResources.

Vive wireless specification typicals


Classroom | New Construction
ASHRAE 90.1-2010 by

Line-voltage
Conference
wiring
ASHRAE
Room | New Constr
90.1-2010
uction
by Low-voltage
wiring
uction
| New Constr
DZ 1 DZ 1 DZ 1

Break Room
2 2 2
Clear Connect
RF Communication

90.1-2010 Line-voltage 1 by
ASHRAE wiring DZ 1 =
Daylight Zone

Low-voltage Line-voltage
wiring 1 2 2 2 DZ 1
wiring
DZ 1

Clear Connect DZ 1
RF Communication Low-voltage
1 wiring

Clear Connect
2 2 2 RF Communication

1 2 DZ 1 & DZ
Daylight 2 =
Zones
DZ 2
DZ 2
DZ 2

Specifying wireless lighting control reduces design time and allows flexibility for changes
Symbol Model Number Description Qty
RMJS-8T-DV-B PowPak dimming module with 0-10 V 3

LRF2-DCRB-WH Radio Powr Savr wireless daylight sensor 1


Qty Symbol
Radio Powr Savr wireless corner-mount
LRF2-VKLB-P-WH 1 Model Number
1 vacancy sensor
Description
RMJS-8T-D
0-10 V PJ2-3BRL-GWH-L01 Pico wireless 3-button with raise/lower control 2 V-B
module with 1 Descriptio
Model Number PowPak
dimming nt LRF2-DCRB PowPak
dimming n
Symbol corner-mou PICO-WBX-ADAPT Pico wallbox adapter 2 -WH module with
V-B Savr wireless 1 Radio Powr 0-10 V Qty
RMJS-8T-D Radio Powr LRF2-VKLB Savr wireless
sensor control -P-WH daylight 2
vacancy Radio Powr sensor
LRF2-VKLB
-P-WH
3-button
with raise/lower 1
Control Functionality vacancy Savr wireless
Pico wireless PJ2-3BRL-
GWH-L01 sensor corner-mou
nt
1
GWH-L01

during the project without the need to redesign. Vive Wireless Specification Typicals allow
PJ2-3BRL- Pico wallbox
adapter Occupant Enters: Open Offi PICO-WBX Pico wireless
Lights do not automatically turn on when an occupant enters the space; ce must
lights | New
be turned -ADAPT 3-button
with raise/lower 1
-ADAPT by light level is set to 80%. ASHRAE Construction Pico wallbox control
PICO-WBX
Construction
on manually. Maximum 90.1-2010 Control Functio adapter
| New nality
2
Corridor
When Occupied:
nality turned on Occupant

© 03/2017 Lutron Electronics Co., Inc. P/N 368-4601 REV A


Egress must be
Control Functio
Automatic: Overhead lights dim/brighten based on daylight availability. There is one perimeter daylight zone. Enters: 2
space; lights Lights do
enters the
90.1-2010 Manual: Occupant uses wall dimmers to set desired light levels for both general and white-board lights. not
ASHRAE
an occupant on manually. automatically turn by
Enters: on when Occupant Exits: Maximum on when
Occupant automatically turn 80%. When Occupied light level an occupant
not is set to All lights automatically turn off 15 minutes after all occupants exit. is set to enters the
Lights do

A
light level for all lights.
Line-voltage
: 80%. space; lights

I P/N 368-4602 REV


Maximum Automatic wiring
light levels
DZ 1
must be

I
manually. : Overhead turned
to set desired Manual:
DZ 1
: Occupant lights dim/bright
When Occupied uses wall dimmer
DZ 1 Low-voltage

exit.
Add a Vive wireless hub to enable simple setup and re-zoning, system monitoring, timeclock DZ 1
Occupant
wiringuses
wall dimmer en based on daylight
Occupant functionality, and advanced integration. Exits: to set desired availability.
Manual: after all occupants All lights light levels There
15 minutes automatica for all lights. are two perimeter
Clear Connect
Exits: , timeclock
lly turn off
RF Communication
Occupant lly turn off
system monitoring

Co., Inc.
daylight zones.

REV A
15 minutes

for quick and easy design of many applications. Simply copy and paste the typicals into
automatica
All lights and re-zoning, DZ 1 = after all occupants
simple setup Add a Vive Daylight Zone

I P/N 368-4600
Code Notes: For non-daylight classrooms, all general lighting can be connected to a single 0-10 V dimming module. exit.
hub to enable

Lutron Electronics
. To emergency
power
wireless
wireless Receptacle Control is required for Shop and Laboratory classrooms. functionali hub to enable
Add a Vive and advanced integration ty, and advanced
Connect
Clear
Want to add a Vive
RF Communication
wireless hub for more features? Go to lutron.com/vive for complete compatibility and design details. simple setup
y, This solution requires 0-10 V enabled ballasts and drivers by others. integration and re-zoning,
functionalit Low-voltage . system monitoring

Co., Inc.
wiring
Line-voltage
wiring , timeclock

© 03/2017
For non-daylight

Lutron Electronics
Want to conference
sensor. add rooms the
zone and
a daylight details. This solution a Vive wireless hub lighting can
module per and design requires for be connected
compatibility 0-10 V enabledmore features? to a
0-10 V dimming e for complete Qty ballasts and Go to lutron.com/vivsingle 0-10 V dimming
include a
rooms with
daylight, Go to lutron.com/viv Symbol drivers by
others.
e for complete module.
compatibility
For break features? others. 1
for more drivers by Description Model Number and design
Code Notes:a Vive wireless hub

© 03/2017
add ballasts and details.
Want to 0-10 V enabled 0-10 V RMJS-8T-D
module with
requires
solution 1 V-B
Model Number
This
dimming PowPak Description
PowPak RMJS-20R- dimming
Symbol hallway

drawing packages for complete design, layout, and BOM information.


V-B Savr wireless DV-B module with
2 0-10 V Qty
RMJS-8T-D Radio Powr sensor LRF2-DCRB 20 A PowPak
occupancy control -WH relay module
-P-WH with raise/lower 2 2
LRF2-OHLB 3-button Radio Powr
Pico wireless LRF2-OCR2 Savr wireless
B-P-WH daylight sensor 1
GWH-L01 adapter Radio Powr
PJ2-3BRL- Pico wallbox occupancy Savr wireless ceiling-mou
PJ2-3BRL- sensor 1
-ADAPT GWH-L01 nt
PICO-WBX Pico wireless
PICO-WBX 3-button
-ADAPT with raise/lower 4

Vive forum and FAQs


Pico wallbox control
nality 80%.
Control Functio 1
adapter
is set to
Control Functio light level.
Maximum
light level
cannot
Occupant
Enters: 1
nality
Enters: to maximum Manual control All lights
automatica
Occupant lly turn on to low end. Maximum lly turn on
automatica dim all lights to 50% light

A
All lights adjust, or light level

I P/N 368-4604 REV


: to turn on, 10%. When Occupied is set to 80%. Controlled level. Occupant
When Occupied uses wall switch level is set to Automatic : receptacle turns on
lights to
Occupant light exit. : Overhead s automatica maximum
Manual: Minimum level
off the lights. after all occupants Manual:
Occupant lights dim/bright lly regain
power when manually.
fully shut 15 minutes uses wall en based occupant
light level Occupant dimmers on
Exits: to set desireddaylight availability. enters.

REV A
minimum Exits:
Occupant lly go to

Co., Inc.
All lights light levels There
All lights
automatica
on to full
output. automatica for all lights. is one perimeter

I P/N 368-4603
off 15 minutes lly turn off daylight
y Mode: power turns after all occupants 15 minutes zone.

Lutron Electronics
Emergenc to emergency after all occupants
connected exit. exit. 50%
Lighting of all receptacle
Add a Vive
wireless s automatica

Available online at www.lutron.com/viveresources

Co., Inc.
functionalit
provide an hub to enable lly turn
UL 924 compliance, zones. y, and advanced simple setup

© 03/2017
that require corridors with daylight integration and re-zoning,

Have a question? Go to Forums.lutron.com to search

Lutron Electronics
projects Code Notes:
signal. For a daylight sensor
for
Want to For non-daylight . system monitoring
loss of control Add design details. add open offi
output upon to emergency fixtures.compatibility and This solution a Vive wireless hub ces, all general , timeclock
go to full for requires lighting can
the egress
fixtures connected e for complete 0-10 V enabledmore features? be
Verify that per load
controller
Go to lutron.com/viv ballasts and Go to lutron.com/vivconnected to a single
Code Notes: control relay (ALCR) more features? others. drivers by e for complete 0-10 V
load for drivers by others. compatibility dimming module.
automatic a Vive wireless hub

© 03/2017
add ballasts and and design
Want to 0-10 V enabled details.
requires
This solution

Frequently asked Questions, pose a question, or talk to


other Vive users in a live forum.

Energy code quick reference guides


Get the lighting and receptacle control requirements along with suggested functionality to
meet the latest versions of ASHRAE 90.1, IECC, and Title 24 all on one page.

Available online at www.lutron.com/viveresources

Vive training
Visit Lutron.com/LCIOnline —Sign up for free, online training
modules with practice exercises that walk you through the
Vive system.

22 | Lutron Lutron | 23
For a list of sources please visit lutron.com/references.
Vive Wireless hub

Features and benefits How it works


• Communicates with controls on a floor using Lutron wireless All wireless devices to be associated to the Vive wireless hub must be within 71 ft (22 m)

wireless hub
Clear Connect technology (range radius of 71 ft [22 m]) of the Vive wireless hub and must be on the same floor as the Vive wireless hub.
• Distributed system architecture
- Pico remote controls and sensors communicate directly with the load
devices they control and must be located within 30 ft (9 m)
of the device with which they are associated Conference Room
PowPak Dimming Module
• Supports timeclock events based on both sunrise and sunset
or fixed time-of-day
Vive Hub
RF coverage
• Integrated multi-color LED provides feedback on what mode
the hub is in Private Office
Maestro Wireless
Vive wireless hub • Two contact closure Inputs for integration with devices by others Dimmer 30 ft (9 m) 30 ft (9 m)
including devices for Title 24 Automatic Demand Response Maximum Maximum
Dimensions
• Each hub provides an individual dashboard for its coverage area and
W: 6.5" (165 mm)
allows you to link to other hub dashboards from the mobile application
H: 1.5" (38 mm)
71 ft (22 m)
D: 2.8" (71 mm) Maximum

Product options
30 ft (9 m) 30 ft (9 m)
Vive wireless hub models Maximum Maximum

Starter (up to 75 devices)


Setup, Monitor
HJS-0-FM Flush mount and Control 100 ft (30 m)
Vive Hub

Standard

HJS-1-FM Flush mount


Vive hub power supply
Range with multiple Vive hubs
HJS-1-SM Surface mount
Dimensions Personal Control
W: 4.0" (102 mm) Pico
Remote Control
H: 1.7" (43 mm) Premium (with BACnet)
D: 2.8" (71 mm)
HJS-2-FM Flush mount Sensors
71 ft (22 m) 100 ft 71 ft (22 m)
Radio Powr Savr
Maximum (30 m) Maximum
HJS-2-SM Surface mount Occupancy Sensor

Open Office
Note: A minimum distance of 10 ft (3 m) between Vive wireless hubs on the PowPak Radio Powr Savr
Fixture
same floor is required. Control Daylight Sensor

Note: A corporate Wi-Fi network can interfere with the Wi-Fi on the Vive 100 ft (30 m)
Note: Pico remote controls and sensors must be within
wireless hub. Where a corporate Wi-Fi network exists, it is recommended 30 ft (9 m) of the load device they are controlling
to do one of the following: 1) Connect to the Vive wireless hub and change
the Wi-Fi channel to one that isn’t used by the corporate network or
2) Connect the Vive wireless hub to the corporate network using the
Ethernet connection on the hub, and disable the hub’s Wi-Fi.
Note: Vive wireless hub must be mounted a minimum of 10 ft (3 m) from a
Wi-Fi router or access point.

24 | Lutron Lutron | 25
Load Controllers: J-box mounted switches and dimmers

How to design and specify How to design and specify


• One relay module
 • One dimming module with 0-10 V control

For each controlled lighting zone in the space For each controlled 0-10 V lighting zone in the space
• Control
 • Control

Select appropriate model based on the size of the 8 A: 0-10 V controlled fixtures and switches compatible
connected load with third-party 0-10 V fluorescent ballasts,
1
 6 A: 1920 W or 1/2 HP @ 120 V or LED drivers, and fixtures
PowPak relay module 4432 W or 1 1/2 HP @ 277 V PowPak dimming module • Input 120/277 V

5 A: 600 W or 1/6 HP @ 120 V or with 0-10 V control • 0-10 V Link: Communicates with up to 60 mA of fixtures
Dimensions 1385 W or 1/3 HP @ 277 V

PowPaks
W: 2.89" (48 mm) • Contact closure output
 Dimensions
H: 3.44" (87 mm) For sending occupancy information to third-party equipment such W: 2.89" (48 mm) Product options
D: 1.25" (32 mm) as HVAC systems H: 3.44" (87 mm)
D: 1.25" (32 mm) 8 A models with 0-10 V control
• Input 120/277 V


RMJS-8T-DV-B

Product options
16 A models

RMJS-16R-DV-B

RMJS-16RCCO1-DV-B One contact closure output

5 A models

RMJS-5R-DV-B

RMJS-5RCCO1-DV-B One contact closure output

26 | Lutron Lutron | 27
Load Controllers: J-box mounted switches and dimmers

How to design and specify How it works


• One contact closure output module In response to information received from a Radio Powr Savr occupancy/vacancy sensor, the PowPak
For each additional contact closure output you require contact closure output module communicates room occupancy to the VAV terminal unit. By not heating or
cooling an unoccupied room, the electricity consumed by the HVAC system can be reduced.

Product options
Cooling Supply
Standard Filter coil fan
PowPak contact
RMJS-CCO1-24-B Contact closure output C
closure output module

Dimensions

PowPaks
W: 2.89" (48 mm) C
H: 3.44" (87 mm) Note: If using a relay module with the contact closure output, you do
D: 1.25" (32 mm) not need to add a contact closure output module unless a second
contact closure output is needed VAV Damper open VAV Damper closed

Occupied Unoccupied

Radio Powr Savr PowPak contact closure


occupancy/vacancy output module
sensor (ceiling mount)

28 | Lutron Lutron | 29
Load Controllers: Plug load control

How to design and specify How it works


• One relay module
 Plug loads, such as task lighting, computer monitors, and printers, account for greater than 5% of
For each 20 A receptacle circuit you want to control commercial electricity usage3. Many energy codes now require control of receptacles for compliance.
• Input 120/277 V
 The occupancy/vacancy sensor wirelessly communicates room occupancy to the relay module.
Based on the occupancy status received, the relay module switches the power to the receptacles on or off,
reducing the amount of energy consumed.
Product options
20 A models
PowPak relay module
General purpose switch
RMJS-20R-DV-B 
Dimensions 120-277 V receptacles

PowPaks
W: 2.89" (48 mm)
H: 3.44" (87 mm) General purpose switch
RMJS-20RCCO1-DV-B 
D: 1.25" (32 mm) 20 A, 120-277 V receptacles
with one contact closure output

20 A 20 A

Occupied Unoccupied

Radio Powr Savr Pico control PowPak 20 A relay


occupancy/vacancy sensor with wallplate receptacle module
(ceiling mount)

30 | Lutron Lutron | 31
For a list of sources please visit lutron.com/references.
Load Controllers: Plug load control

How to design and specify How it works


• One wireless receptacle Plug loads, such as task lighting, computer monitors, and printers, account for greater than 5% of
For each receptacle circuit you want to control commercial electricity usage3. Many energy codes now require control of receptacles for compliance.

One wireless receptacle can also control standard The occupancy/vacancy sensor wirelessly communicates room occupancy to the wireless receptacle.
receptacles wired downstream Based on the occupancy status received, the wireless receptacle switches the power on or off, reducing the
amount of energy consumed. The wireless receptacle will control normal receptacles downstream.
• Input 120V


RF receptacle with
top controlled
Product options
15 A models
Dimensions
W: 2.94" (75 mm) CAR2S-15-STR - 15 A 
Split (half switching;
H: 4.69" (119 mm) single pole/downstream)
D: 1.4" (36 mm)
CAR2S-15-DTR - 15 A Duplex (dual switching;
single pole/downstream)

20 A models

CAR2S-20-STR - 20 A 
Split (half switching;
single pole/downstream)

CAR2S-20-DTR - 20 A 
Duplex (dual switching;
single pole/downstream)

20 A 20 A

Occupied Unoccupied

Radio Powr Savr Pico control RF receptacle


occupancy/vacancy sensor with wallplate with top control
(ceiling mount)

32 | Lutron Lutron | 33
For a list of sources please visit lutron.com/references.
Load Controllers: Wireless individual fixture control

How to design and specify How to design and specify


• Vive integral fixture control • One PowPak Wireless Fixture Contol
For each fixture in the space For each fixture in the space
• Digitally controls up to three drivers/ballasts per fixture
 • Controls 1A of lead or up to three drivers/ballasts/per fixture

• Select either Clear Connect (RF) only or Clear Connect (RF) & • Select either Area sensing or individual fixture sensing
XCT Sensing • PowPak fixture sensor Combined occupancy/daylight sensor

Vive Integral Fixture Control


Product options Vive Wireless fixture controller
Product options
Wireless individual in-fixture control

PowPaks
Dimensions Sensor Dimensions 0-10 V control models
W: .827" (21 mm) DFCSJ-OEM-RF  Clear Connect (RF) only W: 2.89" (48 mm)
FCJS-010 
H: 2.477" (62.9 mm) H: 3.44" (87 mm)
Clear Connect (RF) and Occupancy/
DFCSJ-OEM-OCC  D: 1.25" (32 mm)
FCJS-010-BULK8 8-pack
Daylight Sensing
Dimensions
with Occupancy/Daylight Sensor  ontact your local fixture representative and ask for a Vive-enabled
C
EcoSystem control models
W: .927" (23.5 mm) fixture or visit lutron.com/findafixture
H: 2.577" (65.4 mm) Note: Wireless sensors and controls must be located within 60 ft (18 m)
How it works FCJS-ECO 
line of sight, or 30 ft (9 m) through walls of each other.
Install the fixture control directly to a FCJS-ECO-BULK8 8-pack
fixture or on a junction box nearest
to the fixture. Install the sensor on the
Clear Connect (RF) + Sensing ceiling near the fixture to optimize
Sensor models
coverage in the desired area.

FC-SENSOR Occupancy/Daylight sensor


Note: Avoid mounting the fixture sensor
Clear Connect (RF) Only in direct sunlight or in the light which is FC-VSENSOR Vacancy/Daylight sensor
cast from the fixture.

Fixture sensor coverage diagrams XCT Occupancy/Vacancy sensing


15 ft
(4.6 m)
Applies to both products
Clear Connect Ceiling
Clear Connect (RF)
Wireless Fixture
Controller 9 ft
(2.7 m) 9.8 ft
(3 m)
9 ft
Fixture Controller (2.7 m) 3 ft
(0.9 m)

30 ft (9 m) 0
Maximum
Floor 3 ft
Link
(0.9 m)
15 ft 9 ft 3 ft 3 ft 9 ft 15 ft
Test

6.9 ft
Pico
0 (2.1 m)
Pico Remote Control Radio Powr Savr Radio Powr Savr Remote
Control (4.6 m) (2.7 m) (0.9 m) (0.9 m) (2.7 m) (4.6 m)
(up to 10) occupancy sensor daylight sensor
9 ft
(2.7 m)
(up to 10) (1 maximum) 300 ft (28 m ) major motion
2 2

150 ft2 (14 m2) minor motion


when mounted 15 ft
(4.6 m)
on a 9 ft (2.7 m) ceiling 15 ft 9 ft 3 ft 0 3 ft 9 ft 15 ft
(4.6 m) (2.7 m) (0.9 m) (0.9 m) (2.7 m) (4.6 m)

34 | Lutron Lutron | 35
Load Controllers: UL 924 rated emergency wireless controls

How to design and specify How it works


• 
One UL 924 PowPak module per ighting zone or fixture, depending During normal power conditions, the UL 924 rated PowPak modules can dim loads and respond to local button
on model presses, Pico wireless controls, and occupancy/daylight sensors.

Relay module control: If utility power fails and the emergency PowPak loses power for greater than 250 msec, the emergency generator back-
• 16 A: 1920 W or 1/2 HP @ 120 V up source activates and the automatic transfer switch senses loss of normal power and switches to emergency power.

4432 W or 1/2 HP @ 277 The emergency PowPak regains power and automatically goes into emergency mode (full output, relay closed and
0 –10 V- signal goes to 10.0 V-) for 90 minutes. All local buttons, Pico wireless controls and occupancy/daylight
0-10 V module control: sensors will not respond.
PowPak UL 924 emergency
lighting modules
• 8 A: 0-10 V controlled fixtures and switches compatible with
When normal power is restored to the Vive hub and emergency PowPak, the emergency PowPak will return to the
third-party 0-10 V fluorescent ballasts, LED drivers, and fixtures

PowPaks
previous light level within 2 minutes of normal power being restored. It will again accept local button control, input from
Dimensions • 
0-10 V link: Communicates with up to 60 mA of fixtures Pico wireless controls, and occupancy/daylight sensors
W: 2.89" (48 mm)
H: 3.44" (87 mm) Fixture control:
D: 1.25" (32 mm) • 1 A of load or up to 3 drivers and ballasts System Wiring Diagram (Vive Hub with Emergency PowPak)
120 / 277 V~ Normal Feed 24 V-
• Input (all models)
 120/277 V Neutral (N) Common

UL 924 listed
Product options Line/Hot (L) Junction Box Junction Box To additional
RMJS-8T-DV-B
Neutral (N) PowPaks
Relay RMJS-16R-DV-B-EM Switched Line/Hot
Normal
Switched Line/Hot
Normal
(+) (+)
0– 10 V- 0–10 V-
(–) Driver / Ballast (–) Driver / Ballast
0-10 V RMJS-8T-DV-B-EM
FCJS-ECO FCJS-ECO
120 – 277 V~ 50 / 60 Hz 1 A 120 – 277 V~ 50 / 60 Hz 1 A

Fixtures FCJS-010-EM PowPak®


UL 2043
Plenum Rated
PowPak®
UL 2043
Plenum Rated

FJJS-ECO-EM lutron.com
®
- 25 mA
12 V-
IEC SELV / NEC® Class 2 lutron.com
®
- 25 mA
12 V-
IEC SELV / NEC® Class 2
1.844.LUTRON1 Sensor | Détecteur 1.844.LUTRON1 Sensor | Détecteur
México: México:
1.888.235.2910
lutron.com 1.888.235.2910
lutron.com

RMJS-8T-DV-B RMJS-8T-DV-B
(Normal) (Normal)
120 / 277 V~ Normal Feed

Neutral (N)
 OTE: Solution is not applicable for
* N
Uninterruptible Power Supply (UPS)
120 / 277 V~ Generator/  backup system. RMJS-8T-DV-B-EM
Emergency Feed must see a complete change-over of
power from normal to emergency for
the unit to go into emergency mode.
Neutral (N)

Automatic
Transfer
Switch
Emergency
Backup Generator *

120 / 277 V~
Emergency Feed Junction Box
To additional
RMJS-8T-DV-B-EM
Neutral (N) PowPaks
Switched Line/Hot
(+) Normal / Emergency
Not Provided by Lutron 0-10 V-
(–) Driver / Ballast

FCJS-ECO
120 – 277 V~ 50 / 60 Hz 1 A

PowPak®
UL 2043
Plenum Rated

- 25 mA
12 V-
®
lutron.com IEC SELV / NEC® Class 2
1.844.LUTRON1 Sensor | Détecteur
México:
1.888.235.2910
lutron.com

36 | Lutron RMJS-8T-DV-B-EM
(Emergency) Lutron | 37
Load Controllers: In-wall switches and dimmers

How to design and specify How to design and specify


• Select one switch per lighting zone • Select one wireless dimmer per lighting zone
• Select appropriate model based on the size of the • Select appropriate model based on the size and type
connected load of existing load
- 6 A: 600 W lighting @ 120 V • Most models do not require a neutral
- 8 A: 960 W lighting @ 120 V or 2216 W @ 277 V • Select from up to 27 colors to complement the décor*
• If existing switch does not have a neutral, choose the model • Add an accessory dimmer or a Pico wireless remote
Maestro wireless available for 120/277 V with no neutral required Maestro wireless
for rooms with multiple switches for a single zone
switches dimmers
• Select from up to 27 colors to complement the décor*
Dimensions Dimensions
W: 2.94" (75 mm)
• Add an additional Pico remote for rooms with multiple switches for a
single zone W: 2.94" (75 mm)
Product options
H: 4.69" (119 mm) H: 4.69" (119 mm) Maestro Wireless dimmers
D: 1.44" (38 mm) D: 1.44" (38 mm)
Product options MRF2S-6CL-XX 150 W dimmable CFL/LED,

Switch/Dimmers
600 W incandescent/halogen,
Dual Voltage No Neutral switches 600 VA MLV, 120 V, no neutral

MRF2S-8S-DV-XX 
8 A lighting, 1/10 HP fan @ 120 V only, MRF2S-6ELV-XX 600 W ELV, 120 V
120-277 V, no neutral
MRF2S-6ND-120-XX 600 W/VA incandescent/halogen/
MLV, 120 V
120 V Neutral required switches MA-R-XX Accessory dimmer for multi-location
lighting controls, 120 V
MRF2S-6ANS-XX 6 A lighting, 1/10 HP fan, 120 V only

MRF2-8ANS-120-XX 8 A lighting, 1/4 HP fan, 120 V only

* (XX in the model number represents color/finish code; use WH for


White; please visit www.lutron.com for other color choices.)

38 | Lutron Lutron | 39
Remotes: Pico wireless remotes

How to design and specify How it works


• 
Select one 2-button Pico wireless remote to add a location with No wires—put it where it’s most accessible

ON/OFF control
• Pedestal mount for tabletop use
• 
Select one 3-button Pico wireless remote to add a location with
Pico wireless remotes ON/OFF control and one preset • Surface mount anywhere with Claro wallplate
3-button 3-button 3-button • 
Select one 2-button with raise/lower Pico wireless remote to add a 10-year battery life

with raise/ nightlight location with ON/OFF and BRIGHTEN/DIM control
lower with raise/ • 
Select one 3-button with raise/lower Pico wireless remote to add a
lower
location with ON/OFF, BRIGHTEN/DIM control and one preset
• 
Select whether a nightlight is needed (2-button and 3-button with
raise/lower only)

Note: Spaces with a PowPak relay or dimming module will not have
a local control in the room unless a Pico is added

2-button 2-button 2-button Product options


with raise/ nightlight
lower
2-button remotes
PJ2-2BRL-GXX-L01 2-button with raise/lower
wireless remote
Dimensions
W: 1.28" (33 mm) PJ2-2B-GXX-L01 2-button wireless remote

Pico remote
H: 2.60" (66 mm)
D: 0.33" (8 mm) PJN-2B-GXX-L01 Nightlight 2-button wireless remote

3-button remotes Dim lights to reduce glare on screen

PJ2-3BRL-GXX-L01 
3-button with raise/lower
wireless remote

PJ2-3B-GXX-L01 3-button wireless remote

PJN-3BRL-GXX-L01 Nightlight 3-button with raise/lower


Pico wall mounted Raise lights for Individual
wireless remote
(in a wallplate) —  reading visibility fixture control
Add a new point of
control anywhere with
absolutely no wires

(XX in the model number represents color/finish code)


40 | Lutron Lutron | 41
Remotes: Pico accessories

How to design and specify How to design and specify


• The Pico wireless remote is a flexible and easy-to-use device that • Select one Pico pedestal for each tabletop location based on the
allows the user to control Lutron wireless load-control devices from number of Pico remotes at each location
anywhere in the space. This battery-operated control requires no
Pico wireless remotes external power or communication wiring. Tabletop accessories
4-button 4-button 4-button
Product options
2-group zone scene
control control control Product options Tabletop accessories

 L-PED1-WH pedestal for one Pico remote


4-button remotes
L-PED2-WH pedestal for two Pico remotes
Dimensions PJ2-4B-GWH-L21P 2-group control

W: 1.28" (33 mm) L-PED3-WH pedestal for three Pico remotes


PJ2-4B-GWH-L01 Zone control
H: 2.60" (66 mm)
L-PED4-WH pedestal for four Pico remotes
D: 0.33" (8 mm) PJ2-4B-GWH-L31 Scene control

• Custom-engraved models for Zone control keypads (-L01, -S01)


and Scene control keypads (-L31, -S31) are available but require a
different set of button marking codes when ordering How to design and specify
Note: 2-Group (-L21, -S21, -LS21) and 4-Group Toggle (-L41)
• 
Select one Pico wallbox adapter for each Pico that you
controls are not offered with the custom engraving option).
would like wall mounted with a Claro-style wallplate
• Select one Claro wallplate (up to 4-gang) for all Pico and
Maestro Wireless wall-mounted control locations where
Standard Custom Claro style is desired

Pico remote
Button Marking Codes Engraving Engraving
Zone Control
Lights -L01 -EL1 Product options
Shades -S01 -ES1 Wall-mount accessories
Scene Control
PICO-WBX-ADAPT Pico wallbox adapter
Lights -L31 -EL2
Shades -S31 -ES2 CW-1-WH Claro 1-gang wallplate

CW-2-WH Claro 2-gang wallplate

CW-3-WH Claro 3-gang wallplate

CW-4-WH Claro 4-gang wallplate

Wall-mount accessories
Pico wallplate adapter and Claro wallplate

Dimensions
W: 2.94" (75 mm)
H: 4.69" (119 mm)
D: 1.44" (38 mm)
42 | Lutron Lutron | 43
Sensors: Ceiling occupancy/vacancy sensors

How to design and specify Sensor coverage diagrams


• A single occupancy sensor can communicate to all control
devices in the room Ceiling mount, 360° Coverage varies
• Use in small rooms or areas with medium to high partitions by ceiling height
Floor view
• For 8 ft ceilings: 484 ft2
• For 12 ft ceilings: 676 ft2 Ceiling
Key:
Wireless occupancy/
8 ft
Ceiling
vacancy sensors (2.4 m) Minor motion
Product options Ceiling
8 ft
height
Dimensions (2.4 m)
Major motion
Ceiling
W: 3.57" (91 mm)
Ceiling-mount sensors height
Floor
H: 3.57" (91 mm) 15 ft 12 ft 9 ft 6 ft 3 ft 0 ft 3 ft 6 ft 9 ft 12 ft 15 ft
LRF2-OCR2B-P-WH Occupancy/vacancy Floor (4.6 m) (3.7 m) (2.7 m) (1.8 m) (0.9 m) (0 m) (0.9 m) (1.8 m) (2.7 m) (3.7 m) (4.6 m)
D: 1.13" (29 mm) 15 ft 12 ft 9 ft 6 ft 3 ft 0 ft 3 ft 6 ft 9 ft 12 ft 15 ft
LRF2-VCR2B-P-WH Vacancy only (4.6 m) (3.7 m) (2.7 m) (1.8 m) (0.9 m) (0 m) (0.9 m) (1.8 m) (2.7 m) (3.7 m) (4.6 m)

Top view
Accessories
L-CMDPIRKIT Ceiling-mount sensor lens masking kit

L-CRMK-WH Ceiling-mount sensor recess-


Sensor
mounting bracket
Wire cage guard Sensor
L-WIRECAGE-C Wire guard for ceiling-mount sensor
Dimensions
W: 7.0" (178 mm) Occupant

D: 3.25" (83 mm) Occupant

9 ft 6 ft 3 ft 0 ft 3 ft 6 ft 9 ft
(2.7 m) (1.8 m) (0.9 m) (0 m) (0.9 m) (1.8 m) (2.7 m)
9 ft 6 ft 3 ft 0 ft 3 ft 6 ft 9 ft
(2.7 m) (1.8 m) (0.9 m) (0 m) (0.9 m) (1.8 m) (2.7 m)

Sensors
Ceiling-mount sensor coverage chart (for sensor mounted in center of room)
Maximum room dimensions Radius of coverage
Ceiling height for complete floor coverage at floor
8 ft (2.4 m) 18 x 18 ft (5.5 x 5.5 m) 324 ft2 (30.2 m2) 13 ft (4.0 m)
9 ft (2.7 m) 20 x 20 ft (6.1 x 6.1 m) 400 ft2 (37.2 m2) 14.5 ft (4.4 m)
10 ft (3.0 m) 22 x 22 ft (6.7 x 6.7 m) 484 ft2 (44.9 m2) 16 ft (4.9 m)
12 ft (3.7 m)** 26 x 26 ft (7.9 x 7.9 m) 676 ft2 (62.4 m2) 19 ft (5.8 m)

* Sensor mounting shown at 7 ft (2.1 m). Mounting height should be between 6 and 8 ft (1.6 and 2.4 m).
** 12 ft (3.7 m) is the maximum mounting height allowed.

44 | Lutron Lutron | 45
Sensors: Wall-/Hall-/Corner-mount occupancy/vacancy sensors

How to design and specify Sensor coverage diagrams


• 
A single occupancy sensor can communicate to all
control devices in the room Wall mount*, 180° Corner mount*, 90° Key:
1,500 ft2—minor motion 1,225 ft2—minor motion Minor motion
3,000 ft2—major motion 2,500 ft2—major motion
Product options Major motion
Top view Top view
Wall-mount sensors
Radio Powr Savr 25 ft
(7.6 m)
50 ft
(15.2 m)
Wireless sensors • Use in large open rooms with few tall obstructions
• Coverage: 3,000 ft2 15 ft
Dimensions (4.6 m)

W: 1.8" (46 mm) LRF2-OWLB-P-WH Occupancy/vacancy 35 ft


(10.7 m)
H: 4.35" (110 mm)
LRF2-VWLB-P-WH
0 ft
D: 1.35" (34 mm) Vacancy only (0 m)

Corner-mount sensors 15 ft
(4.6 m)

• Use in medium to large open rooms with few tall obstructions


25 ft
• Coverage: 2,500 ft2 (7.6 m)
0 ft 50 ft 60 ft
(0 m) (15.2 m) (18.3 m)

LRF2-OKLB-P-WH Occupancy/vacancy
0 ft
(0 m)
0 ft 35 ft 50 ft
(0 m) (10.7 m) (15.2 m)
LRF2-VKLB-P-WH Vacancy only Hallway*, long narrow field of view
Coverage varies by hallway width and length
Flexible armature mounting kit Hallway sensors Top view

Dimensions • For a 6 ft wide hallway: 50 ft coverage 10 ft


(3.0 m)
• For a 10 ft wide hallway: 150 ft coverage 5 ft
W: 3.62" (92 mm) (1.5 m)
H: 2.18" (55 mm) 0 ft
LRF2-OHLB-P-WH Occupancy/vacancy (0 m)
5 ft
(1.5 m)
LRF2-VHLB-P-WH Vacancy only
10 ft
(3.0 m)
0 ft 150 ft
(0 m) (45.7 m)
Accessories

Sensors
LRF-ARM-WH 
Flexible armature mounting kit for Radio
Powr Savr wall, hall, corner sensors Hallway sensor maximum recommended length chart
(sensor centered within hallway)
Wire cage guard L-WIRECAGE-C Wire guard for ceiling-mount sensor
Dimensions Width of hallway Length of hallway
L-WIRECAGE-W Wire guard for in-wall sensor
W: 7.0" (178 mm) 6 ft (1.6 m) or less 50 ft (15.2 m)
H: 5.75" (146 mm)
8 ft (2.4 m) 100 ft (30.5 m)
D: 4.5" (114 mm)
10 ft (3.0 m) or more 150 ft (45.7 m)

* Sensor mounting shown at 7 ft (2.1 m). Mounting height should be between 6 and 8 ft (1.6 and 2.4 m).
** 12 ft (3.7 m) is the maximum mounting height allowed.

46 | Lutron Lutron | 47
Sensors: Daylight sensors

How to design and specify Sensor coverage diagrams


• 
A single daylight sensor is capable of controlling: Bottom of sensor
- All Maestro switching and dimming zones
Wireless daylight sensors
- All PowPak switching zones Locat
Dimensions - All PowPak dimming modules with 0-10 V control
Bottom of sensor Arrow
W: 1.6" (41 mm) 1-2 H
H: 1.6" (41 mm) by the
Locat
D: 0.7" (17 mm)
H (towar
Product options 1-2 H Arrow
Daylight sensor Location for average size areas by the
3 ft (1 m)
Arrow points towards the area viewed H (towar
LRF2-DCRB-WH Daylight sensor
by the sensor (towards windows).
H = Effective Window Height
3 ft (1 m)
* Sensor mounting shown at 7 ft (2.1 m). Mounting height should be
between 6 and 8 ft (1.6 and 2.4 m).
** 12 ft (3.7 m) is the maximum mounting height allowed.
H = Effective Window Height

Bottom of sensor

Locati
Bottom of sensor (corrid
Location for narrow areas Locati
Arrow
(corridors, private offices) by the
(corrid
Arrow points towards the area viewed by the
sensor (away from window).
(away
Arrow f

Sensors
by the
(away f

48 | Lutron Lutron | 49
Lutron service solutions

Available setup support services Available startup services


Blocks of setup support time Onsite full-scope startup
• Lutron Services Representative — either onsite or remotely —  • Lutron Service Representative onsite to ensure proper system
supports the installation team in setting up the system startup and configuration
• Utilize the technician’s time in the way that best suits your needs: • Train facilities staff to best utilize and maintain the lighting

training, punch list items, or complete programming independently control assets


• Mix and match remote and onsite blocks of time and use them • Reduce risk and keep your Installation team small by having

when you need them during the construction timeline us do the setup for you.
• Choose the amount of time you need • Includes a Commercial System Limited Warranty

• Onsite startup enhancements available


Setup support services Full-scope startup
4- & 8-Hour onsite blocks Product options Onsite
4-Hour remote blocks Blocks of setup support time Remote Remote full-scope startup
Additional setup support services • Dedicated Lutron Remote Technician works with your installation
LSC-OS-PROG8-SP 8 hours of onsite setup support
team to ensure proper system startup and configuration
LSC-OS-PROG4-SP 4 hours of onsite setup support • Introduce end user facilities staff to system components

and resources available


LSC-RMT-PROG4-SP 4 hours of remote setup support • Less lead time to schedule than onsite startup

• Lower cost than onsite startup

• Commercial system limited warranty available


Additional setup support services
available with blocks and startup

LSC-PREWIRE Prewire visit


Product options
LSC-TRAINING Customer-site solution training
Setup service models
LSC-AF-VISIT Onsite scene and level tuning
Full scope startup
LSC-WALK Onsite performance—
LSC-OS-SU-VIVE Onsite full-scope startup
verification walk-through
LSC-RMT-SU-VIVE Remote full-scope startup

Startup enhancements (Available with onsite full-scope startup)


LSC-AH-SU Startup performed at night or weekends
(weekend work available in certain locations)

LSC-SENS-LT Sensor layout & tuning

Service Solutions
LSC-SPV-DOC System performance—
verification documentation

LSC-SPV-DOC-T24 Title 24 acceptance test visit

50 | Lutron Lutron | 51
Lutron service solutions Vive Warranty & Technology Support

Available Operational Services Commercial System Technology Support Plans (TSPs)


• Support the facilities team to maximize system potential
Limited Warranty All Lutron Technology Support Plans provide 100% parts
• Reprogram the system as space needs change over time and diagnostic labor coverage for up to 10 years. Optional
The commercial system limited warranty offers
• Support retro-commissioning requirements response-time guarantees and preventive maintenance
5 years of parts coverage, 2 years of first-available
• Pre-purchase with the system to capture costs in capital budget visits enable the coverage to be customized to meet the
onsite/remote response time for system issues,
facility’s needs. TSPs are available for any Vive system;
and 24/7 technical support. Warranty included
Product options with onsite full-scope startup & available with
a warranty audit visit will be included with the purchase
of a TSP when full-scope startup is not purchased.
remote full-scope startup
Operational service models
Operational services Product options Product options
Operational services Vive Technology Support Plans
LSC-TRAINING Customer-site solution training Vive Limited Warranty
Solution training
LSC-SYSOPT System optimization service Silver Level Technology
LSC-SILV-IW 
System optimization LSC-B2 Commercial System
Support Plan
Onsite reconfiguration 2-Year Limited
LSC-OS-PROG8-EN 8 hours of onsite reconfiguration support
Remote reconfiguration LSC-GOLD-IW Gold Level Technology
LSC-OS-PROG4-EN 4 hours of onsite reconfiguration support Support Plan

LSC-RMT-PROG4-EN 4 hours of remote reconfiguration support LSC-PLAT-IW Platinum Level Technology


Support Plan
Remote and onsite services are also available for purchase after the
system is in operation at hourly, half-day and full-day rates; contact LSC-WARR-AUD Warranty Audit Visit
Lutron at lscwarranty@lutron.com for more information.

Note: For detailed warranty and technology support


plan descriptions see lutron.com/services

Vive Warranty information


Vive wireless solutions are all covered by a 5-year parts warranty with registration of the product. Additional technology
support options are available to meet your project needs. See the options below.

Commercial System
Support Options Limited Warranty Silver (TSP) Gold (TSP) Platinum (TSP)
Duration up to 10 years of coverage • • •
100% Replacement Parts • (5 yrs) • • •

Service Solutions
Diagnostic Labor— First Available Response • (2 yrs) •
Diagnostic Labor— 72-Hour Response •
Diagnostic Labor — 24-Hour Response •
Annual Preventive Maintenance Visit • •

52 | Lutron Lutron | 53
Ordering Information

Model Number Description List Price (US) Model Number Description List Price (US)

Vive wireless hub Wireless Receptacle


HJS-0-FM Starter Vive wireless hub, flush mount 1,700.00 CAR2S-15-STR 15 A Split (half switching; single pole/downstream, 120 V 170.00
HJS-1-FM Standard Vive wireless hub, flush mount Contact Lutron CAR2S-15-DTR 15 A Duplex (dual switching; single pole/downstream, 120 V 170.00
HJS-1-SM Standard Vive wireless hub, surface mount sales for a quote CAR2S-20-STR 20 A Split (half switching; single pole/downstream, 120 V 190.00
HJS-2-FM Premium Vive wireless hub, flush mount CAR2S-20-DTR 20 A Duplex (dual switching; single pole/downstream, 120 V 190.00
HJS-2-SM Premium Vive wireless hub, surface mount

PowPak relay module


Vive Vue Dashboard Software
RMJS-20R-DV-B 20 A general purpose switch 139.00
VIVE-VUE Vive Vue Software Dashboard License Contact Lutron sales for a quote RMJS-20OCC1DV-B 20 A general purpose switch with one contact closure output 154.00

PowPak relay module Individual fixture control


RMJS-5R-DV-B 5 A relay 109.00 FCJS-010 0-10 V Control Module 78.00
RMJS-5RCCO1-DV-B 5 A relay with one contact closure output 124.00 FCJS-ECO EcoSystem Control Module 78.00
RMJS-16R-DV-B 16 A relay 129.00 FCJS-010-BULK8 0-10 V Control Module 8-pack 600.00
RMJS-16RCCO1-DV-B 16 A relay with one contact closure output 144.00 FCJS-ECO-BULK8 EcoSystem Control Module 8-pack 600.00
FC-SENSOR Occupancy/Daylight Sensor 35.00
UL 924 rated emergency wireless controls FC-VSENSOR Vacancy/Daylight Sensor 35.00

RMJS-16R-DV-B-EM Emergency rated 16 A relay 179.00 DFCSJ-OEM-RF* Vive Integral Fixture Control (RF Only) 60.00

RMJS-8T-DV-B-EM Emergency rated 8 A, 0-10 V dimmer 200.00 DFCSJ-OEM-OCC* Vive Integral Fixture Control (with Sensing) 70.00

FCJS-ECO-EM Emergency rated EcoSystem control module 128.00


FCJS-010-EM Emergency rated 0-10 V control module 128.00

PowPak dimming module with 0-10 V control


RMJS-8T-DV-B Controls up to 8 A of 0-10 V controlled fixtures 150.00

PowPak contact closure output module

RMJS-CCO1-24-B one contact closure output 109.00

* Contact your local fixture representative and ask for a Vive-enabled fixture
or visit lutron.com/findafixture Fixture adders may vary.

54 | Lutron Lutron | 55
Ordering Information

Model Number Description List Price (US) Model Number Description List Price (US)

Maestro Wireless switches*


Pico wireless remotes*
MRF2S-6ANS-XX 6 A lighting, 3 A fan (1/10 HP motor), 120 V 108.00
PJ2-2BRL-GXX-L01 2-button with raise/lower 25.00
MRF2S-8S-DV-XX 8 A lighting, 3 A fan (1/10 HP motor, 120 V only), spec grade 170.00
PJ2-2B-GXX-L01 2-button 25.00
MRF2S-8ANS-120-XX 8 A lighting, 5.8 A fan (1/4 HP motor), spec grade, 120 V 140.00
PJN-2B-GXX-L01 Nightlight 2-button 58.00
PJ2-3BRL-GXX-L01 3-button with raise/lower 21.00
Maestro Wireless dimmers* PJ2-3B-GXX-L01 3-button 25.00
MRF2S-6CL-XX 150 W dimmable CFL/LED, 600 W incandescent 108.00 PJN-3BRL-GXX-L01 Nightlight 3-button with raise/lower 58.00
halogen, 600 VA MLV, 120 V, no neutral
PJ2-4B-GXX-L21P 4-button with 2 group control 39.00
MRF2S-6ELV-XX 600 W ELV, 120 V 209.00
PJ2-4B-GXX-L01 4-button with zone control 25.00
MRF2S-6ND-120-XX 600 W/VA incandescent/halogen/MLV, 120 V 150.00 PJ2-4B-GXX-L31 4-button with scene control 39.00
* (XX in the model number represents color/finish code; price shown is for white (WH) models only.)
Maestro Wireless/Maestro occupancy sensing control companion devices* Price for other colors varies.

MA-AS-XX Multi-location companion switch, 120 V 35.50


MA-AS-277-XX Multi-location companion switch, 277 V 44.00 Pico accessories*
MA-R-XX Multi-location companion dimmer, 120 V 28.40 PICO-WBX-ADAPT Pico wireless remote wallbox adapter 8.00
MA-R-277-XX Multi-location companion dimmer, 277 V 45.40 CW-1-XX Claro 1-gang wallplate 5.00
CW-2-XX Claro 2-gang wallplate 10.00
* (XX in the model number represents color/finish code; use WH for White; please visit www.lutron.com CW-3-XX Claro 3-gang wallplate 15.20
for other color choices.) Price indicated for gloss finish products.
CW-4-XX Claro 4-gang wallplate 21.00
L-PED1-XX** Pico wireless remote single pedestal 15.00
L-PED2-XX** Pico wireless remote double pedestal 30.00
L-PED3-XX** Pico wireless remote triple pedestal 100.00

Maestro Colors * (XX in the model number represents color/finish code; use WH for White; please visit www.lutron.com
for other color choices.) Price indicated for gloss finish products.
** (XX in the model number represents color/finish code; use WH for White; please visit www.lutron.com
Gloss Colors Satin Colors (Prices vary from Gloss Colors)
for other color choices.) Price indicated for White finish products.
S White (WH) Hot (HT) Terracotta (TC) Palladium (PD)
S Ivory (IV) Merlot (MR) Greenbriar (GB) Mocha Stone (MS)
S Almond (AL) Plum (PL) Bluestone (BG) Goldstone (GS)
S Light Almond (LA) Turquoise (TQ) Taupe (TP) Desert Stone (DS)
S Gray (GR) Sea Glass (SG) Eggshell (ES) Stone (ST) Pico Colors
S Brown (BR) Midnight (MN) Biscuit (BI) Limestone (LS)
Gloss Colors
S Black (BL) Sienna (SI) Snow (SW)
White (WH) White/Gray (WG)
Ivory (IV) Black (BL)
Light Almond (LA)

56 | Lutron Lutron | 57
Ordering Information

Model Number Description List Price (US) Model number Description List Price (US)

Radio Powr Savr occupancy/vacancy sensors* Vive Startup Services


LRF2-OCR2B-P-WH Ceiling-mount, 360° field-of-view, occupancy/vacancy sensor 85.00 LSC-OS-SU-VIVE Onsite full-scope startup
LRF2-OWLB-P-WH Wall-mount, 180° field-of-view, occupancy/vacancy sensor 85.00
LSC-RMT-SU-VIVE Remote full-scope startup
LRF2-OKLB-P-WH Corner-mount, 90° field-of-view, occupancy/vacancy sensor 85.00
LSC-AH-SU After hours startup Contact Lutron
LRF2-OHLB-P-WH Hallway, occupancy/vacancy sensor 85.00
sales for a quote
Sensor layout & tuning
LSC-SENS-LT 

Occupancy/vacancy sensor accessories LSC-SPV-DOC System performance-verification documentation

L-CMDPIRKIT Sensor lens masking kit for Radio Powr Savr ceiling sensor 11.80 LSC-SPV-DOC-T24 Title 24 acceptance test visit
L-CRMK-WH Recess-mounting bracket for Radio Powr Savr ceiling sensor 17.00
LRF-ARM-WH Flexible armature mounting kit for Radio Powr Savr 59.00 Vive Setup Support Services
wall, hall, corner sensors
LSC-OS-PROG8-SP Onsite programming — 8-hour block
L-WIRECAGE-WBX Wire guard for in-wall sensor, White 65.00
L-WIRECAGE-C Wire guard for ceiling-mount sensor, White 65.00 LSC-OS-PROG4-SP Onsite programming —4-hour block
L-WIRECAGE-W Wire guard for wall-mount and hallway sensors, White 65.00 Remote programming —8-hour block
LSC-RMT-PROG8-SP 
Contact Lutron
LSC-PREWIRE Prewire visit
sales for a quote
Radio Powr Savr daylight sensor
LSC-TRAINING Customer-site solution training
LRF2-DCRB-WH Ceiling-mount daylight sensor 120.00
LSC-AF-VISIT Onsite scene and level tuning

Wallplates* LSC-WALK Onsite performance-verification walkthrough

CW-1-XX Claro 1-gang wallplate 5.00


Vive Operational Services
CW-2-XX Claro 2-gang wallplate 10.00
CW-3-XX Claro 3-gang wallplate 15.20 LSC-TRAINING Customer-site solution training
CW-4-XX Claro 4-gang wallplate 21.00 LSC-SYSOPT System optimization service
Contact Lutron
LSC-OS-PROG8-EN 8 hours of onsite reconfiguration support
* (XX in the model number represents color/finish code; use WH for White; please visit www.lutron.com sales for a quote
for other color choices.) Price indicated for gloss finish products. LSC-OS-PROG4-EN 4 hours of onsite reconfiguration support

LSC-RMT-PROG4-EN 4 hours of remote reconfiguration support

Vive Limited Warranty and Technology Support Plans


LSC-B2 Commercial system limited warranty

LSC-SILV-IW Silver level technology support plan


Contact Lutron
LSC-GOLD-IW Gold level technology support plan sales for a quote
LSC-PLAT-IW Platinum level technology support plan

LSC-WARR-AUD Warranty audit visit

58 | Lutron Lutron | 59
In-wall: Occupancy/vacancy switches Standalone Solutions

Features and benefits


• Standalone solutions are not compatible with the Vive hub

Standalone
• 
Lutron XCT technology for superior sensitivity prevents false
ons and false offs
• Automatically turns lights off when space is unoccupied
• Easy to install; directly replaces an existing control
• 
Lutron's Smart Ambient Light Detection learns your
Maestro sensor
preferences over time and adapts accordingly
Dimensions • 
Lutron’s Adaptive Zero-Cross Switching extends relay lifetime
W: 2.94" (75 mm) • 180° sensor field-of-view; must have unobstructed view
H: 4.69" (119 mm)
D: 1.44" (38 mm)
• 
Up to 900 ft2 major motion coverage and 400 ft2 minor
motion coverage
• Adjustable timeout—1, 5, 15, 30 minutes

Other energy saving


• 
Vacancy/partial-on models available to meet
CA Title 24 requirements
• 
Dual-circuit sensors provide bi-level control of two circuits, as
required by specific energy codes

devices by Lutron
• Select from up to 27 colors to complement the décor*

Product options
These devices do not integrate with the Vive System Maestro Sensor switch†
Maestro dual-circuit
sensor switch MS-OPS2-XX 2 A lighting, 120 V PIR occupancy/
Dimensions vacancy; single pole, no neutral

W: 2.94" (75 mm) MS-OPS5M-XX 5 A lighting, 120 V PIR occupancy/


H: 4.69" (119 mm) vacancy; 3 A fan, multi-location/3-way/
D: 1.44" (38 mm) single pole, no neutral

MS-OPS6M2-DV-XX 6 A lighting, 120-277 V PIR occupancy/


vacancy, 3 A fan (120 V only); no neutral

MS-OPS6M2N-DV-XX 6 A lighting, 120-277 V PIR occupancy/


vacancy, 3 A fan (120 V only); neutral
required

* (XX in the model number represents color/


Maestro Dual-circuit sensor switch
finish code; use WH for White; please
visit www.lutron.com for other color MS-OPS6-DDV-XX 6 A lighting per circuit, 120-277 V PIR
choices.) See Maestro colors on page 51. dual-circuit occupancy/vacancy; 4.4 A

Vacancy-only models available. Replace the fan (120 V only) per circuit; single pole
"O" in the model number with a "V".

60 | Lutron Lutron | 61
In-wall: Occupancy/vacancy switches Standalone Solutions

Features and benefits Features and benefits


• Standalone solutions are not compatible with the Vive hub • Standalone solutions are not compatible with the Vive hub

Standalone
• L
 utron XCT technology greatly enhances the performance • 
Lutron XCT technology for superior sensitivity
of dual-technology sensors, enabling them to detect very prevents false ons and false offs
fine motion like typing • Automatically turns lights off when space is unoccupied
• Automatically turns lights off when space is unoccupied • Easy to install; directly replaces an existing control
• Easy to install; directly replaces an existing control • 
Lutron's Smart Ambient Light Detection learns your
Maestro dual-technology Lutron's Smart Ambient Light Detection learns your preferences In-wall PIR occupancy/

preferences over time and adapts accordingly
sensor switch over time and adapts accordingly vacancy sensor switches
• 180° sensor field-of-view; must have unobstructed view
Dimensions • Lutron’s Adaptive Zero-Cross Switching extends relay lifetime Dimensions
• 
Up to 900 ft2 major motion coverage and 400 ft2 minor
W: 2.94" (75 mm) • 180° sensor field-of-view; must have unobstructed view W: 2.94" (75 mm) motion coverage
H: 4.69" (119 mm) H: 4.69" (119 mm)
• Up to 900 ft2 major motion coverage and 400 ft2 minor Adjustable timeout—1, 5, 15, 30 minutes
D: 1.44" (38 mm) D: 1.44" (38 mm) •

motion coverage
• 
Vacancy models available to meet CA Title 24
• Adjustable timeout—1, 5, 15, 30 minutes requirements
• Vacancy models available to meet CA Title 24 requirements • Select from up to 27 colors to complement the décor*
• Dual-circuit sensors provide bi-level control of two circuits, as
required by specific energy codes
• Select from up to 27 colors to complement the décor*
Product options
Product options 0-10 V dimmer sensor‡

Maestro Sensor switch† MS-Z101-XX 


8 A lighting 120-277 V; occupancy/
vacancy; multi-location/3-way/single pole
MS-A102-XX  A lighting, 120-277 V dual-tech
6
occupancy/vacancy sensor, 4.4 A fan
Controls electronic LED drivers and fluorescent ballasts
(120 V only); single pole, no neutral
• Miswire and load incompatibility alert —lens will
Maestro dual-technology, 
MS-B102-XX  A lighting, 120-277 V dual-tech
6 flash red if control is miswired or connected to an
dual-circuit sensor switch occupancy/vacancy sensor, 4.4 A
incompatible fixture
fan (120 V only); multi-location/3-way,
Dimensions Selectable dimming curve optimizes performance of
neutral required •

W: 2.94" (75 mm) 0-10 V LED drivers


H: 4.69" (119 mm) • 
Lutron’s Adaptive Zero-Cross Switching extends relay lifetime
D: 1.44" (38 mm) Maestro Dual-circuit sensor switch


MS-A202-XX  A lighting per circuit, 120-277 V
6
dual-tech occupancy/vacancy, 4.4 A
fan (120 V only) per circuit; single pole,
no neutral
* (XX in the model number represents color/ * (XX in the model number represents color/
finish code; use WH for White; please visit 
MS-B202-XX 6 A lighting per circuit, 120-277 V finish code; use WH for White; please
www.lutron.com for other color choices.) visit www.lutron.com for other color
See Maestro colors on page 51.
dual-tech occupancy/vacancy choices.) See Maestro colors on page 51.
sensor, 4.4 A fan (120 V only) per
Vacancy only models available. Add "-V-"
†  †
Vacancy-only models available. Replace the
before the color code (XX). circuit; 3-way, neutral required "O" in the model number with a "V".

62 | Lutron Lutron | 63
Features and benefits Model number Description List Price (US)
• Standalone solutions are not compatible with the Vive hub
Sensor switches *
• C•L dimmer for control of screw-based CFLs and LEDs
MS-OPS2-XX 2 A lighting, 120 V PIR occupancy/vacancy; single pole,
no neutral 29.00
Product options MS-OPS5M-XX 5 A lighting, 120 V PIR occupancy/vacancy; 3 A fan,
multi-location/3-way/single pole, no neutral 41.50
C•L dimmer sensor†
MS-OPS6M2-DV-XX 6 A lighting, 120-277 V PIR occupancy/vacancy, 3 A fan
C•L dimmer sensor† MSCL-OP153M-XX  L dimmer with PIR sensor;
C • (120 V only); no neutral 53.00
Dimensions occupancy/vacancy; MS-OPS6M2N-DV-XX 6 A lighting, 120-277 V PIR occupancy/vacancy, 3 A fan
multi-location/3-way/single pole; (120 V only); neutral required 53.00
W: 2.94" (75 mm)
150 W CFL/LED, MS-OPS6M2U-DV-XX 6 A lighting, 120-277 V PIR occupancy/vacancy, 3 A fan
H: 4.69" (119 mm)
600 W incandescent/halogen (120 V only); configurable ground or neutral wire 54.00
D: 1.44" (38 mm)

* (XX in the model number represents color/finish code; use WH for White; Dual-circuit sensor switches  *
please visit www.lutron.com for other color choices.) See Maestro
colors on page 49. MS-OPS6-DDV-XX 6 A lighting per circuit, 120-277 V PIR dual-circuit occupancy/
† 
Vacancy-only models available. vacancy; 4.4 A fan (120 V only) per circuit; single pole 89.00
Replace the “O” in the model number with a “V”.
MS-PPS6-DDV-XX 6 A lighting per circuit, 120-277 V PIR dual-circuit partial-on
‡ 
For dual-tech or 0-10 V vacancy models,
Add “-V-” before the color code (XX).
occupancy/vacancy, 4.4 A fan (120 V only) per circuit; single pole 89.00

Dual-technology sensor switches * *

Sensor coverage diagrams MS-A102-XX 6 A lighting, 120-277 V dual-tech occupancy/vacancy sensor,


4.4 A fan (120 V only); single pole, no neutral 100.00
MS-B102-XX 6 A lighting, 120-277 V dual-tech occupancy/vacancy sensor,
In-wall 4.4 A fan (120 V only); multi-location/3-way, neutral required 100.00

PIR beam diagram


(for reference only) Dual-technology dual-circuit sensor switches * *
MS-A202-XX 6 A lighting per circuit, 120-277 V dual-tech occupancy/vacancy,
4.4 A fan (120 V only) per circuit; single pole, no neutral 125.00
MS-B202-XX 6 A lighting per circuit, 120-277 V dual-tech occupancy/
vacancy sensor, 4.4 A fan (120 V only) per circuit;
3-way, neutral required 125.00

Sensor dimmers * *
MS-Z101-XX 8 A lighting 120-277 V; occupancy/vacancy; multi-location/
3-way/single pole 110.00
(1.5 m)
(1.5 m)
(9 m)

(6 m)

(6 m)
(3 m)

(3 m)

(9 m)
30 ft

30 ft
20 ft

20 ft
10 ft

10 ft

(6 m)

(6 m)
(3 m)

(3 m)
10 ft

10 ft
5 ft
20 ft

5 ft

20 ft
0

MSCL-OP153M-XX C L dimmer with PIR sensor; occupancy/vacancy;



0

single pole/3-way/multi-location; 150 W CFL/LED,


600 W incandescent/halogen 54.00
* Sensor mounting shown at 7 ft (2.1 m). Mounting height should be between 6 and 8 ft (1.6 and 2.4 m).

* Vacancy models available to meet California Title 24 section 119(j) requirements.


** For dual-tech or 0-10 V vacancy models, add "-V-" before the color code (XX).

64 | Lutron Lutron | 65
For a list of all Vive wireless solutions Questions?
product model numbers and pricing call us
see lutron.com/vive 1.844.588.7661

lutron.com
Lutron Electronics Co., Inc., 7200 Suter Road, Coopersburg, PA 18036-1299

Customer Assistance
Online: lutron.com/help
Email: support@lutron.com
Phone: 1.844.LUTRON1 (588.7661) — includes 24/7 technical support
I
© 5/2018 Lutron Electronics Co., Inc. P/N 367-2597 REV H

You might also like