Professional Documents
Culture Documents
Unit Cold Start: 1. Start Service Water Pump 2. Start Auxiliary Cooling Water System
Unit Cold Start: 1. Start Service Water Pump 2. Start Auxiliary Cooling Water System
22. Put in the fire detection cooling fan and the boiler flame monitoring television, put in the furnace
smoke temperature probe, and check that the boiler four pipe leakage system is put into normal
operation.
23. Close the oil angle valve of each oil gun, open the main inlet and return oil manual valve of the fuel system
in front of the boiler, the front and rear manual valves of the inlet and return oil regulating valve, the front and
rear manual valves of the inlet and return oil filter screen and the front and rear manual valves of the inlet and
return oil flow meter, close the bypass valves of the inlet and return oil flow meter and the inlet and return oil
filter screen, and open the main compressed air valve of the fuel system.
25. Start the unit boiler slagging system operation, open the bottom slag valve.
26. Warm up auxiliary steam to air preheater for soot blowing and tiny oil ignition heater.
28. Start the operation of induced draft fan and forced draft fan, adjust the total air volume to 30% ~
40% BMCR, maintain the differential pressure between the secondary air box and the furnace not less
than 0.4kpa, set the furnace negative pressure at - 50 ~ - 100Pa, and put the induced draft fan into
automatic operation after the furnace negative pressure is stable.
29. Open all oil gun oil supply manual valves and compressed air supply manual valves.
31. The fuel leakage test is successful, and the furnace purging is started.
32. After the furnace purging is completed, the MFT is reset, the fuel inlet and oil return quick-close
valves are opened, the oil circulation in front of the furnace is established, the oil pressure is adjusted
from 2.8 to 3.2 MPa, and it is put into automatic operation.
39. Pre heating of high pressure control valve steam chamber before impulse starting of steam turbine
When the temperature of the inner or outer wall of the high-pressure regulating valve is lower than
150 ℃, the regulating valve steam chamber must be preheated before the start-up of the steam
turbine to avoid the excessive thermal shock to the regulating valve steam chamber during the start-
up of the steam turbine. The high-pressure main steam valve will not be opened from the
preheating of the control valve steam chamber until the preheating is completed. The main steam
for preheating enters the steam chamber of the control valve through the pre opening valve of No. 2
high pressure main steam valve.
Preparation for preheating of steam chamber of HP control valve
1) Check and confirm that the turbine is in turning state.
2) Check and confirm that EH oil pressure is normal.
3) Confirm that the main steam temperature is higher than 271 ℃, and the superheat degree is not
lower than 28 ℃.
High pressure regulating valve steam chamber preheating operation
1) Open the upper valve seat and lower valve seat of the high-pressure main steam valve for drainage,
and open the high-pressure steam guide pipe for drainage.
2) On the DEH screen of the steam turbine, click the "turbine hang up" button and select "hang up".
When the "turbine hang up" status is displayed as "hang up", it indicates that the turbine hang up is
successful.
3) Click "Valve warm" button on the DEH automatic control screen, select "Yes" and press "Go".
4) Confirm that the "on" indicator light of No. 2 high-pressure main steam valve is on, and the No. 2
main steam valve is slowly and slightly opened to 21%, and pre warm the high-pressure regulating
valve chamber.
5) When the metal temperature of the inner and outer wall of the valve chamber rises above 180 ℃,
and the temperature difference between the inner wall and the outer wall is less than 50 ℃, or the
preheating procedure has been carried out for more than 1 hour, the preheating of the high-
pressure valve chamber is completed.
6) After the pre heating of high-pressure regulating valve chamber, click the "valve pre heating" button,
select "no" on the operation screen, and press "execute". Confirm that No. 2 main steam valve is
fully closed.
7) During the pre heating period of the high-pressure regulating valve chamber, pay attention to the
monitoring that the metal temperature difference between the outer wall and the inner wall of the
regulating valve chamber shall not be greater than 90 ℃.
8) When the metal temperature difference between the inner and outer walls of the regulating valve
chamber exceeds 90 ℃, close the No. 2 main steam valve. When the metal temperature difference
between the inner and outer walls of the regulating valve chamber is less than 80 ℃, reopen No. 2
main steam valve for the preheating.
The following tests shall be carried out as required after the constant speed of 3000 rpm of steam turbine
a) High pressure (HPT) shut-off solenoid valve on-line test.
b) Spray Oil test.
c) Mechanical overspeed test (the unit shall be connected to the grid and run for at least 3 hours under 25%
MCR load before overspeed test).
d) Synchronization test (The generator is connected to the grid in the same time).
e) Generator no-load, short-circuit test.
f) Excitation system test